1 CHAPTER 8 ELECTRICAL SERVICE Lead Author: Steve Helfman, MD; Assistant Professor of Anesthesiology; Emory University Atlanta, GA Checklist 1. Should the operating room (OR) be considered a wet location? 2. Will shock protection be provided, and, if so, will it use isolated power or ground fault circuit interrupters (GFCIs)? 3. What should be the type, location, and number of electrical outlets? 4. Is there a need for uninterruptible power supplies (UPS) and/or standby generators? Key Considerations Electrical power to the OR can be: 1) standard, grounded power, as in the home; 2) isolated power, which was required up until 1984; or 3) GFCIs. If the OR is considered a wet location, then either isolated power or GFCIs are required. Most people who work in the OR would agree that the OR is a wet location because saline solutions and blood are frequently spilled on the floor, but you may need to convince hospital administrators and architects. GFCIs might cost hundreds of dollars per OR. They provide safety from faulty equipment, cutting power to it and anything else connected to same outlet. This may cause power to be cut to monitors or other devices because of a faulty radio or headlight. Isolated power might cost in the tens of thousands of dollars per OR. It provides safety by alerting to faulty equipment while keeping it, and everything else connected to the same outlet, powered. Determine the number of electrical outlets. A future National Fire Protection Association (NFPA) standard may call for a minimum of 36 outlets in each OR and is highly suggested. Determine whether the electrical outlets will be standard three-prong or twist-lock type connectors. Determine the need for equipment (e.g., lasers and some x-ray equipment) that may require 240-volt power with special electrical outlets. Consider additional electrical outlets in anesthesia workrooms if you will need to charge transport monitors, portable ultrasound machines, intravenous (IV) pumps, or other equipment. 69
2 Electrical Power There are three ways to provide electrical power to the OR: 1) standard, grounded power, as in the home; 2) isolated power, which was required up until 1984; and 3) GFCIs. With the common type of grounded power that is supplied to the home, it is relatively easy for an individual to become part of an electrical circuit and receive a potentially harmful electric shock. GFCIs are commonly installed in wet locations (e.g., bathrooms and kitchens) in the home in order to provide protection against electric shock. The GFCI will interrupt the power in the event that a hazardous current is flowing. All electrical devices on that branch circuit will have the power supply interrupted. The standards, codes, and Joint Commission requirements revolve around two issues. If the OR is considered a wet location, then either isolated power or GFCIs are required. Most people who work in the OR would agree that the OR is a wet location because saline solutions and blood are frequently spilled on the floor. Discussions are underway within the NFPA to declare that all ORs are wet locations or to declare that they are wet locations by default, with local risk management able to determine that they are not wet locations. Members of the American Society of Anesthesiologists Committee on Equipment and Facilities have been unanimous in their opinion that all ORs are wet locations. The design team must decide whether to provide isolated power supply or GFCIs. Administrators may look upon this issue as a way to save money. There is a large cost differential between GFCI and isolated power. GFCIs might cost hundreds of dollars per OR, while isolated power might cost between $5000 and $9000 per isolation panel, with one or more panels used per OR. If isolated power is selected, malfunctioning equipment will generate an alarm but will not automatically shut off. Many anesthesiologists prefer this approach. The drawback of isolated power, however, is that in many cases, it is difficult to identify which piece of equipment has malfunctioned and is causing the alarm. Furthermore, isolated power systems generate the alarm based upon the total leakage current, and, with many different pieces of electrical equipment connected, each individual piece of equipment may be within its leakage specifications yet the total current is above the leakage limit. Thus, there is no malfunction and, yet, the alarm is sounding. 70
3 If GFCIs are selected, then malfunctioning equipment will be automatically shut off. It is generally simple to identify the equipment that has automatically shut off and plug it into a different circuit. The automatic shutoff could pose safety issues, however, if monitors or lifesupport equipment suddenly lose power. Life-support devices (e.g., ventilators, cardiopulmonary bypass machines, etc.) commonly contain internal battery backup. If other necessary equipment (e.g., fixed patient monitors) lack internal battery backup, freestanding UPS can be used between the GFCI outlet and the piece of equipment. Adding freestanding UPS to a GFCI system remains less expensive than an isolated system. Figure 1 71
4 Every health care facility must have a source of emergency power. This is usually a generator that is capable of supplying a significant amount of the facility s electrical power requirements in the event that the local electrical utility company experiences a power failure. Emergency outlets in the OR (and elsewhere in the hospital) are commonly colored red, and if the main electrical service is lost, only these red outlets will continue to supply electricity. If stored fuel is used to power on-site generators, there must be enough storage capacity for at least 24 hours of continuous operation. Although various codes may dictate that a minimum number of electrical outlets in the OR and postanesthesia care unit be connected to the emergency generator, it is desirable to have all of them connected. Electrical Outlets Standards call for operating and delivery rooms to have at least six receptacles convenient to the head of the procedure table and for each OR to have at least eight duplex receptacles. In today s environment, most would consider that woefully inadequate. A future NFPA standard may call for a minimum of 36 outlets in each OR. It is far better to have too many than too few electrical outlets. Although it is possible to identify and quantify the electrical requirements for modern day OR equipment, it is impossible to predict how much electrical equipment will be used in the ORs of the future. Therefore, electrical outlets should be placed on every wall. Also, in order to help reduce the hazard of multiple electrical cords on the floor, outlets also should be placed in the ceiling and gas/electric columns. These can be located at the head of the bed on both sides of the OR table or both sides of the anesthesia workstation and are useful for plugging in monitors, infusion pumps and fluid warmers. Figure 2 72
5 Figure 3 Ceiling outlets at the foot of the table can be used for many pieces of surgical equipment. Cords can be plugged into the ceiling outlet, extending to 6.5 to 7 feet from the floor. Figure 4 The electrical outlets can have either the standard three-prong or twist-lock type connectors. Virtually all hospital electrical equipment comes with three-prong plugs. Twist-lock plugs were an older replacement for explosion-proof connectors that were required in the days of flammable anesthetics. Twist-lock plugs provide some protection against accidental disconnection. 73
6 Twist-lock plugs on OR equipment were once very popular in order to prevent the equipment from wandering to other parts of the hospital because other areas of the hospital lacked the correct electrical outlets to plug in the equipment. Over time, adapter cables (from standard to twist-lock and from twist-lock to standard) appeared throughout the hospital. These adapter cables posed additional expense and hazard, and most hospitals have abandoned the twist-lock connectors. GFCI circuits are not readily available with twist-lock outlets. Figure 5 Certain equipment (e.g., lasers and some x-ray equipment) may require 208- or 240-volt power, with special electrical outlets. The need for these outlets and their location within each OR need to be anticipated in the design phase. If anesthesia workrooms will be used to charge transport monitors, portable ultrasound machines, IV pumps, or other equipment, appropriate electrical service should be provided for this purpose. 74
7 Bibliography American Institute of Architects Academy of Architecture for Health. Guidelines for Construction and Equipment of Hospital and Health Care Facilities. Washington, DC: AIA Press; Association of Operating Room Nurses. Recommended practices. Traffic patterns in the surgical suite. AORN J. 1993;57(3): Azar I, Eisenkraft JB. Waste, anesthetic gas spillage and scavenging systems. In: Ehrenwerth J, Eisenkraft JB, eds. Anesthesia Equipment: Principles and Applications. St. Louis, MO: Mosby; 1993: Dorsch JA, Dorsch SE. Understanding Anesthesia Equipment, Construction, Care, and Complications. 3rd ed. Baltimore, MD: Williams & Wilkins; ECRI. Medical gas and vacuum systems. Health Devices. 1994;23(1-2):4-53. Ehrenwerth J. Operating room design. ASA Newsletter. 1994(Nov);58: Ehrenwerth J, Seifert HA. Electrical and fire safety. In: Barash PG, Cullen BF, Stoelting RK, eds. Clinical Anesthesia. 6th ed. Philadelphia, PA: Lippincott, Williams & Wilkins; Eichhorn JH, Ehrenwerth J. Medical gases: storage and supply. In: Ehrenwerth J, Eisenkraft JB, eds. Anesthesia Equipment: Principles and Applications. St. Louis, MO: Mosby; 1993:3-26. Gowin J. The nurse s view of operating room design and function. Anesthesiology. 1969;31(2): MacDonald AG. A short history of fires and explosions caused by anesthetic agents. Br J Anaesth. 1994;72(6): National Fire Protection Association. NFPA 70: National Electrical Code. Quincy, MA: National Fire Protection Association; National Fire Protection Association. NFPA 99: Standards for Health Care Facilities. Quincy, MA: National Fire Protection Association; Seifert HA. Fire safety in the operating room. Progr Anesthesiol. 1994; 8: TWIST-LOCK and HUBBELLOCK Devices. Hubbel Incorporated Online Catalog [Web site]. Section b:75. Available at: 75
SECTION.3400 - MECHANICAL: ELECTRICAL: PLUMBING
SECTION.3400 - MECHANICAL: ELECTRICAL: PLUMBING 10A NCAC 13D.3401 HEATING AND AIR CONDITIONING Heating and cooling systems shall meet the American Society of Heating, Refrigerating, and Air Conditioning
Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords?
Electrical Safety Electricity can be a friend, but it can also hurt if you do not treat it with respect. Everyday someone loses his or her home or business due to an electrical fire. These tragedies are
2012 Operating Room Design Manual
CHAPTER 16 REMOTE AND HAZARDOUS LOCATIONS Lead Author: John Rogoski, DO, Assistant Professor of Clinical Anesthesiology, Ohio State University College of Medicine Checklist: Is the room size large enough
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
2012 Operating Room Design Manual
CHAPTER 9 ROOM VENTILATION SYSTEMS Lead Author: Kamal Maheshwari, MD, Staff Anesthesiologist, Cleveland Clinic Foundation Checklist 1. Does the ventilation system in your operating room (OR) meet the standards
2 electrical. electrical. 2010 PulteGroup, Inc. All Rights Reserved.
2 12 2010 PulteGroup, Inc. All Rights Reserved. circuit breakers Circuit breakers protect your home s system from power failure. The wiring in your home is protected by circuit breakers. Circuit breakers,
HOUSING QUALITY STANDARDS (HQS)
HOUSING QUALITY STANDARDS (HQS) Series 5 Electrical Safety And INSPECTIONS 5.01 ELS Revised 8-17-06 Electricity is Dangerous All electrical repairs should be made by licensed professionals. Touching any
Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS
Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS The Language Used In This Document Does Not Create An Employment Contract Between The Employee And The Agency. This Document Does
Electrical Hazards. Power Tools. Extension Cords
Electrical Hazards Electrical hazards can be found in nearly every roofing work site. Whether the hazard is posed by worn or damaged power tools or cords, improperly grounded tools or equipment, or the
in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put it into perspective: Electrocutions can be Prevented
Home fires are a major problem in the United States Each year, home electrical problems alone account for an estimated 53,600 fires. These fires cause more than 500 deaths, injure 1,400 people, and account
2010 2011 Operating Room Manual
CHAPTER 3 ERGONOMICS AND WORKFLOW Lead Author: Robert Loeb, MD; Associate Professor of Anesthesiology; University of Arizona Tucson, AZ Contributors: Ramon Berguer, MD; Clinical Professor of Surgery; University
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS
Technical Update TAA.TU.11093 Rev. 1
http://www.gambro.com/en/usa_tech/ 800-525-2623 303-222-6500 Technical Update TAA.TU.11093 Rev. 1 Effective: 05 APR 2013 CO# 13084 Product: Subject: From: Phoenix Dialysis System Required Electrical Safety
OPERATING ROOM SAFETY. Off-Site Locations
OPERATING ROOM SAFETY Off-Site Locations 1 The objective of this training program is to identify hazards present in operating rooms and to list actions that can be taken to minimize these hazards. 3 4
Union County Public Schools. Facilities Department. Electrical. Safe Work Practices
1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County
Home Electrical Safety Challenge
Home Electrical Safety Challenge Home Electrical Safety Challenge Why is there a different kind of outlet in my bathroom? What does that TEST button do? Why does the circuit breaker trip every time my
Utility Distribution Systems
Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date
Smart House And Home Automation Technologies
Smart House And Home Automation Technologies Mark D. Gross in Encyclopedia of Housing W. van Vliet -- (ed), Sage, 1998 design machine group University of Washington Seattle WA USA 98195-5720 http://depts.washington.edu/dmachine
ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist
Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited
Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section
October Safety Subject
October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that
Guidelines for the Management of the Obstetrical Patient for the Certified Registered Nurse Anesthetist
American Association of Nurse Anesthetists 222 South Prospect Avenue Park Ridge, IL 60068 www.aana.com Guidelines for the Management of the Obstetrical Patient for the Certified Registered Nurse Anesthetist
Laboratory Safety Guideline Electrical Safety
Introduction The typical laboratory contains a wide variety of electrically-powered equipment including stirrers, shakers, pumps, hot plates, heaters, power supplies, ovens, and electrophoresis equipment.
ELECTRICAL SAFETY. The standard unit for measuring electrical current.
ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
INSPECTION AND TESTING OF EMERGENCY GENERATORS
INSPECTION AND TESTING OF EMERGENCY GENERATORS Certification requirements NFPA 101(00), Sec. 7.9.2.3 requires that emergency generators be installed, tested and maintained in accordance with NFPA 110,
Lead Author: Tangwan Azefor, MD, Clinical Associate, Department of Anesthesiology & Critical Care Medicine, Johns Hopkins Bayview Medical Center
CHAPTER 6 SUPPLY CHAIN Lead Author: Tangwan Azefor, MD, Clinical Associate, Department of Anesthesiology & Critical Care Medicine, Johns Hopkins Bayview Medical Center Checklist: * How many anesthesia
Are you aware. Outline
Electrical Safety of Medical Equipment Hasan Al-Nashash School of Engineering American University of Sharjah (AUS) 1 Are you aware Electrocutions are the 5th leading cause of accidental death in the U.S.
in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put Into Perspective Electrocutions Can Be Prevented
Home fires are a major problem in the United States Each year, home electrical problems alone account for an estimated 53,600 fires. These fires cause more than 500 deaths, 1,400 injuries, and $1.4 billion
USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018
USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and
Understanding Ambulatory Surgical Centers and Office Surgical Suites
Understanding Ambulatory Surgical Centers and Office Surgical Suites The Issues of Code, Licensing, and Reimbursement Daniel Roark, Assoc. AIA Skip Gregory, NCARB Who is Studio+? People Passion Process
Dear Neuton Owner, This is a helpful hint to guide you in getting the most out of your NEUTON Battery and Charger.
Battery-Powered Mower NEUTON 24-Volt Charger Instructions Booklet Dear Neuton Owner, In order for you to get the most out of your Neuton Mower, we recently reviewed and revised our battery-charging instructions.
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL
Element D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
B. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems.
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and device plates and decorative box covers. B. Related
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
3053 Electrical Safety Training Program Course Outline
3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting
NOTE: Additional user information for your printer may be available in the "Manuals" section at support.dell.com.
CAUTION: General Safety Instructions Use the following safety guidelines to help ensure your own personal safety and to help protect your equipment and working environment from potential damage. NOTE:
Element D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
EKOS Cart. Instructions for Use
EKOS Cart Instructions for Use EKOS Corporation 11911 North Creek Parkway South Bothell, WA 98011 USA (425) 415-3100 (tel) (425) 415-3102 (fax) [email protected] (e-mail) - 1-4913-002 REV E Intended Use
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
ELECTRICAL REQUIREMENTS FOR HEALTH CARE FACILITIES
ELECTRICAL REQUIREMENTS FOR HEALTH CARE FACILITIES Review Guide for: Hospitals Nursing Facilities Clinics Office of Statewide Health Planning and Development Facilities Development Division www.oshpd.ca.gov
North Carolina State University Emergency Facilities Closure Checklist- Part I
North Carolina State University Emergency Facilities Closure Checklist- Part I Unplanned or spontaneous events often disrupt daily operations on campus. In the event that an incident may interrupt your
AST Guideline Statement on Humidity in the Operating Room
AST Guideline Statement on Humidity in the Operating Room Approved April 10, 2015 Introduction The maintenance of the required level of relative humidity (RH) in the operating room (OR) has been essential
How SafePlug Smart Receptacles Can Save Money in Commercial Buildings
How SafePlug Smart Receptacles Can Save Money in Commercial Buildings by Steve Montgomery, P.E. 2D2C, Inc. SafePlug smart receptacle system add the ability to accurately identify exactly what appliance
St Peter s College ELECTRICAL SAFETY. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
St Peter s College ELECTRICAL SAFETY References: A. Peninsula Business Services Guidance Note 4-1, Electrical Safety. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
Severe Weather Safety Resources to help weather the storm
Severe Weather Safety Resources to help weather the storm Hurricanes: By the Basics What: A Hurricane is a severe weather system that brings high winds, torrential rain, storm surges, and flooding. Hurricanes
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
Online UPS. PowerWalker VFI 1000R/1U
Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.
Ventilation Standard For Health Care Facilities
The following article was published in ASHRAE Journal, October 2008. Copyright 2008 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White
IMPORTANT INSTRUCTIONS & OPERATING MANUAL Houston 50 Inch Electric Wall Mounted Fireplace Black / White Model Number:MFE5050BK Model Number:MFE5050WH Read these instructions carefully before attempting
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
Fire Protection Notice No. 9 ELECTRICAL SAFETY
Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily
Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000
Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,
2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes
2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 1) Tamper resistant receptacles. 2009 CEC Required in dwelling units 2012 CEC Expanded to child care facilities First introduced in the 2009
Instruction / Installation Sheet DataComm Electronics 50-6623-WH-KIT Flat Panel TV Cable Organizer Kit with Duplex Power Solution
Instruction / Installation Sheet DataComm Electronics 50-6623-WH-KIT Flat Panel TV Cable Organizer Kit with Duplex Power Solution DataComm Electronics, Inc. 6349 Peachtree Street Norcross, GA 30071-1725
REHABILITATION OF MOBILE HOMES R4 34 606
REHABILITATION OF MOBILE HOMES R4 34 606 PURPOSE The purpose of this program is to provide minimum safety standards for homes manufactured before the implementation of the HUD Manufactured Home Construction
Help protect your home, possessions and family.
Help protect your home, possessions and family. A guide to your Square D electrical distribution system SM Make the most of your energy Understanding your home s electrical distribution system As one of
Safety in Offices and other General Areas
Safety in Offices and other General Areas 1. INTRODUCTION This document covers health and safety in offices and other 'general areas' including corridors, stairs, entrances, small kitchens and rest areas.
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity
Home Solar Kit 1800. Owner s Manual. Model: HS 1800-60
Home Solar Kit 1800 Owner s Manual Model: HS 1800-60 1. INTRODUCTION Thank you for purchasing the KISAE Home Solar Kit. With our state of the art, easy to use design, this product will offer you reliable
Electrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual
Operation and Maintenance Manual Introduction Read all instructions thoroughly. Installation of the OilTector must comply with all Federal, State and Local Codes, Regulations and Practices. The OilTector
Charging what can be more simple? SAE J1772
Charging what can be more simple? SAE J1772 Charging What Can Be More Simple? We charge our electronic devices everyday Laptops Cell phones PDAs Bluetooth devices Power tools MP3 players Toys Other Why
Electrical Design TABLE OF CONTENTS FOREWORD... 1. BASIC ELEMENTS OF ELECTRICITY... 2 Electricity works much like water Ohm s Law
TABLE OF CONTENTS Electrical Design TABLE OF CONTENTS FOREWORD.......................................................................... 1 BASIC ELEMENTS OF ELECTRICITY..................................................
ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED
Preparation: Safety Mgr Authority: Dennis Johnston Issuing Dept: Safety Page: Page 1 of 9 Purpose The purpose of the Electrical Safety program is to set forth procedures for the safe use of electrical
Owner s Manual. Not suitable for mobile applications. Important Safety Instructions 2. Quick Installation 3. Basic Operation 4. Storage & Service 7
Register online today for a chance to win a FREE Tripp Lite product! www.tripplite.com/warranty Owner s Manual Internet Office & BC Personal UPS Systems Not suitable for mobile applications. Important
2012 Operating Room Design Manual
CHAPTER 15 FREE-STANDING AND OUTPATIENT SURGERY FACILITIES Lead Authors: Michael Wajda, MD, Medical Director of Ambulatory Anesthesia, New York University Langone Medical Center, NY; Charlotte Bell, MD,
Hospital Isolated Power Systems
4800CT9801R4/08 08 Class 4800 CONTENTS Description..............................................Page General Information........................................... 3 Surgical Facility Panels.......................................
Electrical Safety Tips. Help us keep you safe
Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural
Section B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850
Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
Master Workplace Inspection Checklist for General Shop Safety. MASTER WORKPLACE INSPECTION CHECKLIST General Shop Safety
Integrated Risk Management Master Workplace Inspection Checklist for General Shop Safety Document Type: Form Control Number: UIRM- FM_012_50 File Code: UIRM-001 Last Reviewed: March 2014 Department/Unit:
Electrocution Hazards
Electrocution Hazards 1 Electricity Accidents People who work directly or indirectly with electricity can be the victims of serious electrocution injury or death on construction sites. These accidents
466-1936 Rev E October 2004 ZZZ*(6HFXULW\FRP. Part No: 60-883-95R. CareGard. User Guide
) *(6HFXULW\ 466-1936 Rev E October 2004 ZZZ*(6HFXULW\FRP Part No: 60-883-95R CareGard User Guide FCC Notices FCC Part 15 Information to the User Changes or modifications not expressly approved by GE Security
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
GENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical
www.ealarm.com.my P/N 5-051-371-00 Rev D
System 236 System 236i P/N 5-051-371-00 Rev D Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced alarm systems on the market today, designed to provide
Why Construction Workers are Getting Electrocuted
Why Construction Workers are Getting Electrocuted Michael McCann, PhD, CIH Director of Safety and Ergonomics The Center to Protect Workers Rights [email protected] Causes of Death in Construction, 1992-98
AORN Recommended Practices. AORN Practices. RPs Related to Environmental Services. Joan Blanchard, RN, MSS, CNOR, CIC September 10, 2008
AORN Recommended Practices Joan Blanchard, RN, MSS, CNOR, CIC September 10, 2008 AORN Practices AORN Recommended Practices are AORN s official position on aseptic technique and technical practices. This
Carbon Monoxide Detection in Commercial Buildings (
1 Technical Guideline for School Districts and BOCES to comply with regulations for Carbon Monoxide Detection in Commercial Buildings (Section 1228.4 of Part 1228 of Title 19 NYCRR). General: This document
Dining Services OSHA Safety Training Program TRAINING RECORD
Dining Services OSHA Safety Training Program TRAINING RECORD Employee Title: This record documents the safety training received by Dining Services employees, including student employees, as required by
Datacenter Site Selection Checklist
Checklist Use this checklist to aid in the process of selecting a new site for the data center. When visiting potential building sites, print the checklist off and take it along to record impressions and
Instructions & Safety Information Models A220-20D and A220-20L Version 2
Quick 220 Voltage Converting Power Supply Instructions & Safety Information Models A220-20D and A220-20L Version 2 Quick 220 Systems LLC PO Box 47489 Phoenix, Arizona 85068-7489 800-347-0394 602-938-6057
SUMP PUMP. Sump Pump Backup Systems. City of Ann Arbor B A C K U P O P T I O N S. Does everyone need a backup system?
Sump Pump Backup Systems A backup sump pump is a system used to protect your basement from flooding when the main sump pump isn't operating. There are several types of backup systems including battery
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE
TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
Arc Fault Circuit Interrupters Frequently Asked Questions
Contents My AFCI is tripping! What do I do? What is the difference between branch feeder and combination type Arc Fault Circuit Interrupters? What is new with the 2008 NEC versus the 2005 NEC with respect
Engineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Communication
ReadyNet Easy Jack 2 Voice/Data and Data Only Owner s Manual PX-211d and PX-211v
ReadyNet Easy Jack 2 Voice/Data and Data Only Owner s Manual PX-211d and PX-211v Phonex Broadband Corporation dba ReadyNet 6952 High Tech Drive Midvale, Utah 84047 801.566.0100 Phone 801.566.0880 Fax www.readynetsolutions.com
Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au
ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks