Typical Finished Basement Details
|
|
|
- Sybil Harrell
- 10 years ago
- Views:
Transcription
1 Fauquier County, Virginia Typical Finished Basement Details Based on the 2012 International Residential Code Finished basements must be constructed in conformance with this document. For requirements, details and information not contained herein, you must consult the Virginia Residential Code. Code books may be viewed online or purchased from the International Code Council at iccsafe.org. A copy of this document is required to be on the job site and available to the inspector during each required inspection.
2 Fauquier County, Virginia Typical Finished Basement Details CONTENTS Section Page 1 General Notes Emergency Escape and Rescue Wall Construction Drilling and Notching Floor/ceiling Construction Mechanical Plumbing Electrical... 9 Version: , 6/6/2015 Fauquier County, Virginia - Typical Finished Basement Details Page 2 of 10
3 1. Habitable rooms (excluding closets, hallways, laundry rooms, storage spaces and bathrooms) shall have an area of not less than 70 square feet and shall not be less than 7 feet in any direction. 2. Hallways shall not be less than 36 inches in width. 3. Basement ceiling height shall not be less than 7 feet above the finished floor. Structural members spaced 4 feet or more apart may project up to 6 inches below the required ceiling height. 4. Bathrooms shall be equipped with a fan vented directly to the outside. A fan is not required if the bathroom contains a window with an opening of 1.5 square feet or more. 5. Space under stairs shall be protected with ½-inch drywall on the underside or with a non-accessible enclosure clad in ½-inch drywall. SECTION 1: GENERAL NOTES 6. A smoke alarm shall be installed in the basement and in each basement bedroom. New smoke alarms shall be interconnected so that when one is activated all will sound. Smoke alarms must be hardwired with a battery backup. 7. If adding a bedroom and the house is equipped with a gas-fired appliance, a carbon monoxide alarm shall be installed in the basement. 8. All basement stairs shall have a light source to illuminate all treads and landings. Lights shall be operated by a switch located at the top and bottom of the stairs. 9. A minimum of R-13 battened insulation or R-11 continuous insulation shall be installed for the full height and length of the basement wall. SECTION 2: EMERGENCY ESCAPE AND RESCUE Where required. An emergency escape and rescue opening in the form of a window or door to the outside is required for all finished basements and in all bedrooms regardless of the house s age. However, openings in the bedroom may serve the entire basement. If your basement does not currently have one of the emergency escape and rescue options below, then you must provide one. Cutting openings in existing basement walls is outside the scope of these details. Therefore, a plan submission is required for the new openings only. All other conditions of the finished basement may be taken from these details. Emergency escape and rescue options. The following openings can be used for emergency escape and rescue. Window opening in a walk-out basement condition. Window opening into a window well or areaway. Door in a walk-out basement condition. Door opening to an areaway. Door to bulkhead enclosure (Bilco door or similar). Opening requirements. The emergency escape and rescue opening shall meet the requirements below. See FIGURE 1 for typical window opening requirements. All doors and windows must be operable from the inside without the need of a key or tool. The opening must be a minimum of 5.7 square feet. Version: , 6/6/2015 Fauquier County, Virginia - Typical Finished Basement Details Page 3 of 10 opening area = 5.7sf 1 Windows must have a sill 44 inches or less above the finished floor. 44" to sill 20" min. top of floor window in open position 24" min. 1 Windows opening directly to outside in a walk-out condition are permitted to have an opening area equal to 5.0 square feet. FIGURE 1: EMERGENCY ESCAPE AND RESCUE OPENING REQUIREMENTS
4 Window well requirements. When grade conditions require the sill of the window to be below the outside grade elevation, then a window well must be constructed. The required horizontal area of a window well is a minimum of 9 square feet minimum as measured when the window is in the open position (this is important when the window is a crank-out type). See FIGURE 2. Window well construction. A plan submission to the county is required for the construction of a new window well. If you choose to use a prefabricated window well, you must submit the manufacturer s specification during the permit application process. window well provide 12" wide ladder when window well is more than 44" deep 3" min. 6" max. 36", min. each direction 18" max. emergency escape and rescue opening FIGURE 2: WINDOW WELL REQUIREMENTS Ladder requirements. When a window well is deeper than 44 inches, a permanent, attached ladder or steps must be provided per FIGURE 2. If the ladder projects more than 6 inches into the required horizontal area, the size of the window well must be increased to compensate. SECTION 3: WALL CONSTRUCTION Studs. Studs may be utility grade or better. Walls shall have a single pressure treated bottom plate and can have a single or double top plate. Studs shall be placed at 16 inches on center, but may be increased to a 24 inches on center when applied finish material is drywall. Attachment requirements. Wall construction shall be fastened in accordance with TABLE 1. TABLE 1: FASTENING SCHEDULE CONNECTION NAILING METHOD FASTENER Top plate to stud End nail 2-16d (3½" x 0.135") 2-16d (3½" x 0.135") Toe nail or or Stud to bottom plate 3-8d (2½" x 0.113") 1 Stud to bottom plate End nail 2-16d (3½" x 0.135") 1 Bottom plate to floor Face nail 16d concrete nail (3½" x 16"o.c. Header to jack stud 4-8d (2½" x 0.113") Toe nail (see FIGURE 3) each side of header at each end 1 Fasteners are required to be hot-dipped galvanized. Headers. A single flat 2x4 may be used as a header in interior nonbearing walls for openings up to 8 feet in width if the portion of the wall above the opening is not more than 24 inches in height. If the opening does not meet these conditions, the header shall be framed per FIGURE 3 and sized per TABLE 2. Two-ply headers shall be fastened together using 16d (3½" x 0.135") face nails at 16 inches on center staggered along the top and bottom edges. TABLE 2: HEADER SIZE 1 HEADER SIZE SPAN LENGTH (2)2x4 4' (2)2x6 6' (2)2x8 10' (2)2x10 12' (2)2x12 16' 1 Non-load bearing walls only. Version: , 6/6/2015 Fauquier County, Virginia - Typical Finished Basement Details Page 4 of 10
5 Fireblocking. Fireblocking shall be provided to seal off concealed spaces and to form an effective fire barrier between stories. Fireblocking shall be provided in the following locations. In concealed spaces of stud walls and partitions, including furred spaces at the ceiling and floor level where the top plate is attached to the underside of the floor joists. See FIGURE 4. At all interconnections between concealed vertical and horizontal spaces such as occur at soffits, bulkheads, drop ceilings, etc. See FIGURE 5. In concealed spaces of stud walls offset from the basement wall. See FIGURE 6 In concealed spaces between stair stringers at the top and bottom of the stair run. At gaps and openings around vents, pipes and ducts at the ceiling and floor level. Fireblocking material. Fireblocking shall consist of one of the materials listed below. jack stud, each side of opening header FIGURE 3: FRAMING AT HEADERS king stud, each side of opening ½-inch gypsum board. 2x lumber (2x4, 2x6, etc.). Two thicknesses of 1x lumber (1x4, 1x6, etc.) with staggered joints. ¾-inch plywood, OSB or particleboard with joints backed by 6 inches of the same material. ¼-inch cement, cement/fiber board (e.g., Durock). At gaps 1 inch or less, batts or blankets of mineral wool or fiberglass pack tightly or approved fireblocking caulk. existing floor system new 2x 24" o.c. to support top plate 1 existing floor system new 2x 24" o.c. to support top plate basement wall new ceiling/wall finish top plate serves as fireblocking new stud wall 2 1 Attach top plate to underside of joists where floor framing is perpendicular to stud wall. 2 R-13 insulation should be provided between studs. FIGURE 4: FIREBLOCKING WITH STUD WALL AGAINST BASEMENT WALL basement wall 2x or other fireblocking material at ceiling/soffit elevation dropped ceiling or soffit new stud wall 2 1 Attach top plate to underside of joists where floor framing is perpendicular to stud wall. 2 R-13 insulation should be provided between studs. FIGURE 5: FIREBLOCKING AT DROP CEILING Version: , 6/6/2015 Fauquier County, Virginia - Typical Finished Basement Details Page 5 of 10
6 existing floor system new 2x 24" o.c. to support top plate and fireblocking basement wall basement wall new ceiling/wall finish new continuous horizontal fireblocking secured to new blocking above 1 new offset stud wall 2 new stud wall 2 vertical fireblocking at 10' o.c. maximum HORIZONTAL FIREBLOCKING VERTICAL FIREBLOCKING (looking down) 1 Attach top plate and fireblocking to underside of joists where floor framing is perpendicular to stud wall. 2 If cavity between basement wall and new stud wall does not contain existing insulation, then R-13 insulation should be installed. FIGURE 6: FIREBLOCKING WITH OFFSET STUD WALL Interior finishes. Wall and ceiling finish materials must meet the requirements listed below. Materials must have a flame spread classification no greater than 200 and a smoke density classification no greater than 450. This does not apply to trim, molding, handrails and doors. Cement or fiber-cement board (e.g., Durock) must be installed on walls of bathtub and shower spaces and finished with a non-absorbent surface. Wood veneer or hardboard paneling less than ¼-inch shall not be permitted. Gypsum board must be ½-inch minimum. SECTION 4: DRILLING AND NOTCHING Studs. Studs in non-load bearing walls may be notched or drilled in accordance with FIGURE 7. Joists and/or beams. Drilling and notching of existing wood joists or beams shall meet the requirements below. Drilling and notching 2x lumber shall be in conformance with FIGURE 8. Cantilevered (overhanging) joists cannot be notched. Drilling and notching of manufactured wood I-joists, LVL or other engineered wood product shall be per the manufacturers instructions. Drilling and notching of open web floor trusses is prohibited without submitted calculations performed by a registered design professional licensed in Virginia. drilled hole diameter shall not exceed 40% of the stud depth (1.4" for 2x4) 5 8 " min. to edge notch must not exceed 40% of the stud depth (1.4" for 2x4) stud top plate drilled holes shall not be located in the same cross- section of a cut or notch pressure treated bottom plate FIGURE 7: DRILLING AND NOTCHING STUDS Version: , 6/6/2015 Fauquier County, Virginia - Typical Finished Basement Details Page 6 of 10
7 1/3 span length 1/3 span length 1/3 span length drilling permitted drilling permitted drilling permitted notching permitted notching prohibited notching permitted 2" 1/3 depth 2" 1/6 depth FIGURE 8: DRILLING AND NOTCHING JOISTS SECTION 5: FLOOR/CEILING CONSTRUCTION Draftstopping. When a ceiling is not directly attached to the underside of the floor joists above or when the floor joists are comprised of open web trusses, draftstopping must be provided. Install draftstopping to create equal-sized concealed areas not exceeding 1,000 square feet. Draftstopping shall be installed parallel to the floor framing members. See FIGURE 9 and FIGURE 10. draftstopping draftstopping FIGURE 9: DRAFTSTOPPING AT DROP CEILING FIGURE 10: DRAFTINGSTOPPING AT OPEN WEB TRUSSES Draftstopping material. Draftstopping shall consist of ½-inch minimum gypsum board, ⅜-inch minimum wood plywood/osb or ⅜-inch minimum particleboard, Type 2-M-W. SECTION 6: MECHANICAL Appliance access. Furnaces, water heaters and other appliances must be accessible without removing permanent construction and shall meet the following minimum criteria. 30 inches x 30 inches clear floor space at front/control side. Doors to furnace rooms shall be 24 inches minimum and be of sufficient size to remove the largest appliance. Combustion air. Furnace rooms with fuel-fired appliances must be provided with two permanent openings to adjacent spaces: one within 12 inches of the top and one within 12 inches from the bottom of the adjoining wall. Each opening must have a minimum free area equal to 1 square inch per 1,000 Btu per hour input rating of all appliances in the furnace room, but not less than 100 square inches. The openings are not required if a louvered door is provided or the furnace room area is greater than 50 cubic feet per 1,000 Btu per hour input rating of all appliances installed in the room. Version: , 6/6/2015 Fauquier County, Virginia - Typical Finished Basement Details Page 7 of 10
8 SECTION 7: PLUMBING Showers. Showers and shower compartments must meet the following requirements. Shower compartments must have a minimum total area of 900 square inches and a minimum dimension of 30 inches in any direction. Shower compartments may have a minimum dimension of 25 inches provided it maintains a cross sectional area of 1,300 square inches. Hinged shower doors must open outward. All glass which encloses as shower must be safety glazed. Shower control valves must be scald resistant (in accordance with ASSE/ANSI 1016) with a hot water limit of 120 degree F. Fixture clearances. Toilets, sinks and showers shall have the minimum clearances listed below. 21 inches in front of sinks and toilets. 24 inches in front of shower stall opening. 4 inches between two adjacent sinks. 4 inches between a sink and a toilet. 4 inches between a sink and a wall. 2 inches between a sink and a bathtub. 15 inches clearance from a toilet's centerline to an adjacent fixture or wall on each side. Drain size. Fixture drain size must meet the dimensions below and must be equipped with a strainer and stopper. TABLE 3: MINIMUM DRAIN SIZE FIXTURE DIAMETER Bathroom sink 1¼" Bathtubs 1½" Sinks (other than bathroom) 1½" Laundry tubs 1½" Shower 1½" Clothes washer discharge. The discharge of a clothes washer must be through and air break as shown in FIGURE 11. clothes washer discharge AT SINK AT STANDPIPE FIGURE 11: AIRBREAK AT CLOTHES WASHER DISCHARGE Version: , 6/6/2015 Fauquier County, Virginia - Typical Finished Basement Details Page 8 of 10
9 SECTION 8: ELECTRICAL Panelboard (circuit breaker box). Panel boards must meet the requirements listed below. A workspace 30 inches wide and 36 inches deep from floor to the ceiling with a minimum height of 6.5 feet shall be provided in front of the panel boards. Panel board workspace must not be used for storage at any time. Panel boards must not be located in clothes closets or bathrooms. A light shall be provided for the panel board workspace. Pipes or ducts cannot be located above the panelboard. Branch circuits. Branch circuits must meet the requirements listed below. See TABLE 4 for more information. Use a 15- to 20-ampere rated branch circuit for general use purposes such as lighting and outlets. One plugged-in electrical device shall not exceed 80 percent of the circuit rating. Hardwired appliances or equipment may be included in a general use circuit provided its rating does not exceed 50 percent of the circuit rating. A dedicated 20-ampere minimum branch circuit must be provided to serve laundry room outlets only. A dedicated 20-ampere branch circuit must be provided to serve the bathroom receptacles. Branch circuits which serve bedroom outlets must have circuit breakers equipped as combination arcfault/over current circuit interrupters. TABLE 4: BRANCH CIRCUIT REQUIREMENTS Ci rcuit Ratin g Circuit Element 15 amp 20 amp 30 amp Minimum conductor size Maximum breaker size Outlets rating or Maximum load Lighting requirements. Lights must meet the requirements listed below. At least one switched light shall be provided in each room and hallway. A switched outlet may be substituted except in bathrooms and hallways. A switched outlet cannot count towards a required outlet, see Outlets on page 10. At least one switched or pull chain light must be provided in each storage area and at or near heating and air conditioning appliances and equipment. Lighting fixtures must not be installed within 3 feet horizontally and 8 feet vertically of a bathtub rim or shower stall threshold. A light fixture may be installed above a shower area if it is constructed so that water cannot enter or accumulate in wiring areas and the lighting fixture is marked suitable for wet locations. Version: , 6/6/2015 Fauquier County, Virginia - Typical Finished Basement Details Page 9 of 10
10 Outlets. Outlets must meet the requirements listed below. Outlets shall be tamper resistant. Outlets shall be placed in accordance with FIGURE 12. The minimum wall length which requires an outlet is 2 feet. Kneewalls, built-in bars and other fixed room dividers must be included for outlet spacing. Hallways more than 10 feet long must have a minimum of one outlet. Outlets installed for specific appliances must be within 6 feet of the appliance location. Bathrooms must have at least one outlet located on a wall adjacent to each basin and within 36 inches of the bathroom sink. All bathroom outlets must have ground fault circuit interrupter (GFCI) protection. At least one outlet must be provided to serve laundry appliances and sinks. Each unfinished portion of the basement is required to have at least one outlet that is GFCI protected. An outlet must be provided within 25 feet of heating and air conditioning appliances and equipment. 6' 12' 6' 6' 2' typical outlet 6' 12' 12' FIGURE 12: TYPICAL OUTLET DISTRIBUTION Light fixtures in closets. Fixtures installed in clothes closets shall be limited to surface mounted or recessed incandescent fixtures with completely enclosed lamps and surface mounted or recessed fluorescent fixtures. See TABLE 5 for clearance requirements. Fixture Type TABLE 5: CLOSET LIGHT FIXTURE CLEARNANCES 1 Fluorescent Bulb 2 LED Bulb 2 Surface mounted 6" 12" Recessed 6" 6" 1 Incandescent bulbs are prohibited. 2 Fluorescent and LED bulbs are permitted in storage areas when identified for this use. Version: , 6/6/2015 Fauquier County, Virginia - Typical Finished Basement Details Page 10 of 10
Typical Finished Basement Details
Fairfax County, Virginia Typical Finished Basement Details Based on the 2012 International Residential Code Finished basements must be constructed in conformance with this document. For requirements, details
FINISHED BASEMENT REQUIREMENT GUIDE
Basement Guide www.douglas.co.us FINISHED BASEMENT REQUIREMENT GUIDE Current Codes: 2012 International Residential Code 2009 International Energy Conservation Code 2014 National Electrical Code 2012 I-Code
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
How To Build A Basement House
Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
Single Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
FINISHED BASEMENT SUBMITTAL GUIDE
FINISHED BASEMENT SUBMITTAL GUIDE The text and illustrations included in this submittal guide represent the opinions of the Manheim Township Code Compliance Department. This guide is for education and
BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009)
BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009) PERMIT SUBMITAL CHECKLIST: Signed and completed Building Permit application form. 2 Copies of plans showing proposed layout and
Building Department John Fiedler Construction Official Ext. 211. SAMPLE GUIDE FOR 1&2 FAMILY DWELLING BASEMENTS Rev 4-3-2014
TOWNSHIP OF HILLSBOROUGH COUNTY OF SOMERSET Hillsborough Township Municipal Complex The Peter J. Biondi Building 379 South Branch Road Hillsborough, NJ 08844 P: (908) 369-4313 F: (908) 369-3954 Building
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov Finishing a basement to make additional living space in a house is a popular construction project for many homeowners.
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
Basement Development Construction requirements for the development of basements in residential dwellings.
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Basement Development Construction requirements for the development of basements in residential dwellings. June 2009 contents GENERAL INFORMATION 3 BUILDING
Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER:
Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: SECTIONS 1, 2, 3, AND 4 MUST BE COMPLETED BY APPLICANT BEFORE INSPECTION
GENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
GENERAL WIRING RULES FOR HOUSES
GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
Bath Planning Guidelines With Access Standards
Bath Planning Guidelines With s 1: Door/Entry The clear opening of a doorway should be at least 32. This would require a minimum 2-10 door. If the existing structure precludes changing the opening then
How To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
Applications for building permits will not be reviewed until all of the required information has been submitted.
NOTICE: Applications for building permits will not be reviewed until all of the required information has been submitted. Once all items are submitted a minimum of ten (10) working days are required to
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
City of St. Charles Basement Finish or Remodel
City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct
Johnson County Kansas Unincorporated
BASEMENT FINISHING AND REMODELING CODE GUIDELINES Johnson County Kansas Unincorporated One of the objectives of the Johnson County Building Officials Association is to enhance construction uniformity and
PDmB, Inc. Definitions
Page 1 of 11 Definitions S Satisfactory Meets industry standards for proper material and installation NP Not Present Condition or item was not present at time of inspection NI Not Inspected Condition or
The replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
Development Services City of Lawrence, KS
Development Services City of Lawrence, KS Building Planning Table R301.2 (1) Climatic & Geographic Design Criteria Building Planning The design criteria for wind speed increased from 90 MPH to 115 MPH.
H:\forms\handouts\bldg049 1 of 11 Revised Mar 2/15/dh
Accessory Apartment Construction Guide For Single Detached Dwelling and Semi-Detached Dwellings that have been in existence for at least five (5) years Notes: Buildings that are less than five (5) years
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
DEPARTMENT OF ECONOMIC AND COMMUNITY DEVELOPMENT, BUILDING DIVISION 333 90 TH Street Daly City CA 94015 (650) 991-8061
NOTE: A completed form will be attached to your approved plans and must be signed by the contractor or person doing the work prior to issuance of permit. Those code sections applicable to your approved
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical
Residential Decks. Planning and Development Services Department
Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: [email protected] Planning and Development Services Department Residential Decks
Does Wall Township require an inspection by the building department on resale of a home?
Selling your home Does Wall Township require an inspection by the building department on resale of a home? No. We do not require a Certificate of Continued Occupancy on the resale of home. A Smoke Detector,
Residential Electrical Inspection. Checklist
443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us Residential Electrical Inspection (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 Checklist Generally, Minnesota
Electrical Code Regulation
Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county
SECTION 19 RESIDENTIAL CONSTRUCTION IN FLOODZONES
SECTION 19 RESIDENTIAL CONSTRUCTION IN FLOODZONES The purpose of the following information and documents are to clarify procedures used by the Sonoma County Permit & Resource Management Department to enforce
Arapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
Residential Code Requirements
Residential Code Requirements 2013 Adopted Codes effective January 1 st, 2014 The code requirements in this document are excerpts only, not a comprehensive list of all requirements that may apply to your
Georgia Association of Home Inspectors
Georgia Association of Home Inspectors Standards of Practice for Framing Inspections OVERVIEW The purpose of the GAHI (Georgia Association of Home Inspectors) Standards of Practice for Framing Inspections
Chapter 6 ROOF-CEILING SYSTEMS
Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;
Residential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
8/18/14. Introduction to. Framing. Terminology and Concepts
8/18/14 Introduction to Framing Terminology and Concepts Terminology: Framing Level Two points on exactly the same horizontal plane. Square Intersecting lines or faces that form an exact 90 angle. Plumb
Residential Electrical Inspection Checklist
Residential Electrical Inspection Checklist Based on the 2008 National Electrical Code Generally, Minnesota law requires all electrical work to be performed by licensed, bonded and insured electrical contractors
Home Inspection Report
Arizona Home Inspections, LLC By Jack Randall 6810 N Andrea Doria Tucson, AZ 85704 Office-Fax 520-887-2594 Home Inspection Report 835 N Rose Water Place Tucson, AZ Prepared For: Michele Balitski Copyright
POST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
Building Condition Assessment Report
Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.
City of Elk River BASEMENT Office Use Only
City of Elk River BASEMENT Office Use Only Fire and Building Safety Division (FABS) Building Permit Application Notes Scan Permit Total Date Permit # PID # $ Site Address Suite/Unit Structure Type Single
Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers
City of Duluth Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers Thank you for taking the time to join us today. We know you are busy and your time is valuable.
March 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
BUILDING SAFETY UNIT
POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential
Typical Deck Details
Fairfax County, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code The design details in this document apply to residential, single-level decks only. Construction cannot deviate
Your Basement Remodeling Specialist LLC
Your Basement Remodeling Specialist LLC Contents Introduction 3 Remodel Details 4 Basement Bid Scope 5 Financial Arrangements 6 Homeowners Shopping Guide 7 The following is provided with your actual quote:
Residential Plan Routing Information
Residential Plan Routing Information BUILDING INSPECTIONS 800 4th AVENUE EAST WEST FARGO, ND 58078 PHONE: 701-433-5480 The building Inspection s Department receives and issues all applications for building
Electrical Wiring Technical Bulletin
Electrical Wiring Technical Bulletin Overview In general, SIP construction is easier and more cost effective when things are planned and thought out before the panels are manufactured. This process will
Uniform Construction Code (UCC) Building Permit Application Package
Uniform Construction Code (UCC) Residential Building Permit Application Package Per the Uniform Construction Code (UCC) all structures must be built per the standards of the most currently adopted International
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist
Total Home Inspection Checklist
Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are
REHABILITATION OF MOBILE HOMES R4 34 606
REHABILITATION OF MOBILE HOMES R4 34 606 PURPOSE The purpose of this program is to provide minimum safety standards for homes manufactured before the implementation of the HUD Manufactured Home Construction
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer
Summit Series Single Section and Double Section Homes
Single Section and Double Section Homes SM-01 All New 20 Wides Now Available! SM-08 Units shown with optional features SM-01-4814 42 Bedrooms 41 Bathrooms 648 Sq. Ft. SM-01-5214 42 Bedrooms 41 Bathrooms
Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector
Plumbing Helpful Hints Residential Construction Bert Polk Plumbing Inspector Lincoln County 2015 Waste and vent fittings Vent 90 medium 90 long 90 1/16 bend,1/8 bend,1/6 bend, medium 90 san tee combination
Inspection Item COMMENTS
APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:
SUMMARY REPORT THE BOTTOM LINE. Electrical. Report Number: 1860. Inspection Date: Saturday, February XX, XXXX
SUMMARY REPORT Report Number: 1860 Inspection Date: Saturday, February XX, XXXX Property Address: XX XXXXX XXX Toronto, ON XXX XZX Client Name: Xxxx Xxxxxxxxxxxxx Prepared by: Andrew Marioselva BSc,CHI
2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012
2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,
Building Information Packet
Code Enforcement Department 882-9225 Building Information Packet The following information has been compiled to help you as a homeowner or contractor with the various steps and requirements for a building
*It is unlawful to occupy or use any project for which a permit was issued without first receiving final inspection approval from this department.
Department of Permitting Services 255 Rockville Pike, 2nd Floor Rockville, MD 20850-4166 Phone: 311 in Montgomery County or (240) 777-0311 Fax (240)-777-6262 http://www.montgomerycountymd.gov/permittingservices
RRIO Checklist. Use of checklist: Definitions: Limitations
CITY OF SEATTLE RENTAL REGISTRATION AND INSPECTION ORDINANCE (RRIO) RRIO Checklist Use of checklist: Property owners will use the RRIO Checklist to confirm that their rental housing properties and units
Thermal Imaging for Home Inspectors
Thermal Imaging for Home Inspectors Structural member placement The gabled end of a cathedral ceiling. Note the studs and the ceiling joists with blocking. What is that glow in the upper right hand corner?
1/2" CDX PLY W/ 8d @ 6"/ 6"/ 12" 2x ROOF RAFTERS @ 16"OC W/ R-30 BATT. INSUL. (COMMON NAILS)
TYPE V CONSTRUCTION IS A CLASSIFICATION OF BUILDINGS BY CONSTRUCTION MATERIALS AND METHODS. IT IS THE LEAST RESTRICTIVE PERMITTED BY THE UNIFORM BUILDING CODE AND INCLUDES LIGHT, WOOD-FRAME CONSTRUCTION.
Building Permit Application
Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER
CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE NONSTRUCTURAL DESIGN REQUIREMENTS This section contains portions of the California Building Code which relate to basic minimum nonstructural design requirements for a residence.
2012 CODES SIGNIFICANT CHANGES 2012 IBC
2012 CODES SIGNIFICANT CHANGES 2012 IBC 1. Section 303.4 added language that includes commercial kitchens which are associated with restaurants, cafeterias, and similar dining facilities to be classified
The better way to build TM. Installation Manual. EXTERIOR WALL SIPs
The better way to build TM Installation Manual EXTERIOR WALL SIPs July 2015 EXTERIOR WALL SIPs Installation Manual Table of Contents Topics General Requirements................................... 3 Materials..............................................
COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS
COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS Permit applicants shall submit three (3) COMPLETE SETS of plans and specifications with each application for a permit. Plans and specifications
Residential Electrical Inspection. Checklist
Electrical Licensing and Inspection 443 Lafayette Road North St. Paul, Minnesota 55155-4342 www.doli.state.mn.us 651-284-5064 Fax: 651-284-5743 TTY: 651-297-4198 1-800-DIAL-DLI Residential Electrical Inspection
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
Whitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.
Building Type Building Code Whitley Classroom Buildings BOCA, UBC, SBCCI, NEC, ADA Structural Support Outrigger construction standard, Whitley model classrooms. Main support beams to be 12 11.8# per lineal
LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
New Ontario Building Code Highlights
New Ontario Building Code Highlights Part 9 This summary highlights items that are believed to be significant changes to the 2012 OBC and is not intended to include all changes made within this or other
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Duchesne County Department of Building Safety
Duchesne County Department of Building Safety 734 North Center St., P.O. Box 317 Duchesne, Utah 84021-0317 Phone (435) 738-1153 Karl D. Mott Building Official BUILDING PERMIT PROCESS DOCUMENTS TO BE SUBMITTED
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Residential Decks Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers
ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers This handout is intended to be a general overview of residential electrical requirements as noted in the 2014 National Electrical
2. What building projects are exempted? (permit not required)
BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and
Pre-Drywall Inspection Report
SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion
Quality Home Inspections, LLC 4433 Tennyson Street Denver, Colorado 80212 303-885-1288
Page 1 of 22 Quality Home Inspections, LLC 4433 Tennyson Street Denver, Colorado 80212 303-885-1288 Printed Friday, January 16, 2015 Inspected By: Dale Gibbs Referral Information Joe Agent Client Information:
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
Code Enforcement Inspection Manual. City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division
Code Enforcement Inspection Manual City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division LIVING ROOM 304.15 EXTERIOR DOOR(S) Check door(s) and trim for condition,
EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST
DATE TIME EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST INSPECTOR: LICENSE # ADDRESS: PROPERTY OWNER: SINGLE: DOUBLE: MULTI-UNIT # OF UNITS POINT OF INSPECTION Sanitation IPMC 302.1
Additions and Alterations
Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal
How to secure your property after a disaster
How to secure your property after a disaster The Red Guide to Recovery HOuse secured properly Board-Up of Windows, Doors and Roof Hole. Lot secured with Perimeter Fencing. Fires, floods, tornadoes, hurricanes,
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
4. ANCHOR BOLTS AND STRAPS a. ½" anchor bolts shall be embedded 7" into concrete a maximum of 6' on center and 12" from corners and ends of plates.
GENERAL CODE REQUIREMENTS (BASEMENTS) 1. FOOTINGS a. Footings shall be below frost line depth (42"). b. For an 8" foundation wall, footings shall be no less than 8" deep and 16" wide. c. Steel reinforcement
CONSTRUCTION DETAILS & LOAD DESIGN CHARTS
Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description
BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER
BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION # BLOCK LOT VACANT YES NO CURRENT OWNER NAME ADDRESS TELEPHONE # PROSPECTIVE
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
Custom 30 x 20-8 Garage Plan Plan #g233 By SDS-CAD Specialized Design Systems
P O Box 34 Mendon, Utah Custom 30 x 20-8 Garage Plan Plan #g233 By Page 1 Title Page Page 2 Main Floor Plan Page 3 Foundation Plan Page 4 Elevation Views Page 5 Framing and Details Page 6 Typical Section
