1 GS 1 Protecting Data Centers Against Intentional Electromagnetic Interference and High Altitude Electromagnetic Pulse Data Center Facility Infrastructure Threat and Mitigation Considerations 1
2 GS 1 Protecting Data Centers Against Intentional Electromagnetic Interference and High Altitude Electromagnetic Pulse Michael A. Caruso Director, Government & Specialty Business Development 2
3 The Concern Functions of Government, Private and Public Data Centers are becoming an increasingly significant component of the Critical Infrastructure The concern over the effects of HEMP and IEMI has grown exponentially in non-government applications. The need to address HEMP and IEMI protection in Data Centers that support Critical Infrastructure is urgent. Current Data Center Designs and IT Equipment Designs do not address HEMP and IEMI 3
4 Terminology Electromagnetic Pulse (EMP) An umbrella term identifying two forms of damaging high power electromagnetic signals High-altitude Electromagnetic Pulse (HEMP) Damaging electromagnetic signals (>50,000 volts/meter) emitted from a nuclear detonation in outer space at any altitude above 18 miles (30 km) Note: No damaging near field or radiation effects Intentional Electromagnetic Interference (IEMI) Damaging and/or Disruptive data altering electromagnetic signals caused by the malicious use of electromagnetic weapons (nondetonation, within targeted footprints) 4
5 Known IEMI THREATS Boeing CHAMP Truck Mounted Suitcase 5
6 Risk Potential How much EMP is needed to destroy your data equipment? Volts per meter (V/m) are the standard units of electric field strength used to determine electromagnetic immunity in products and equipment. Most electronic equipment can survive a pulse of 10 Volts per meter. An EMP would create a pulse of >10,000 V/m. 6
7 Risk Potential Immunity Standards IT Equipment - 10 Volts/meter Medical Equipment 10 Volts/meter Network Telephone Equipment 10 Volts/meter Aircraft- (HIRF) 7,200 Volts/meter Automobiles 100 Volts/meter Military Equipment 200 Volts/meter 7
8 MITIGATION and PROTECTION PROTECTION LEVEL 1 (Survival of Data and Equipment) EMP Protected Environment With EMP protected enclosures and treated points of entry, your data and processing equipment will survive. Although the power, cooling, and utilities in an unprotected host facility may not be immediately available, your equipment will remain safe. And, when power, cooling and utilities and are restored, your data equipment will be fully operable. 8
9 MITIGATION and PROTECTION PROTECTION LEVEL 2 (Survival & Continuous Operations of Data & Equipment) Independent Power and Utilities If an EMP event occurs, your data and processing equipment will continuously operate with a fully independent and protected power and utility source. This unit may be located inside your suite or outside the existing data center facility. Your data processing and communication will not be interrupted. 9
10 MITIGATION and PROTECTION HVAC, Generator & Telecommunications Must be addressed for Protection Level 2 10
11 CONCLUSIONS Computer/Business/Distribution/Communication/Manufacturing systems have become a significant part of our modern critical infrastructure system and must now consider EMP Protection Both narrowband and wideband EMP waveforms can be produced by nonlethal weapons using modern technology Modern electronics are extremely vulnerable EMP waveforms Protection measures are available, but many businesses are not aware of the threat and/or not willing to invest the time or money There is a prevailing It Can t Happen attitude..but it will and has! 11
12 Thank you Michael A. Caruso Director, Government & Specialty Business Development 1360 North Wood Dale Road Suite G Wood Dale, IL Office Cell Fax [email protected] 12
EMP... Electromagnetic Pulse. one of the greatest threats facing technology-driven clients today
EMP... Electromagnetic Pulse one of the greatest threats facing technology-driven clients today Do you remember in the movie Oceans Eleven when Las Vegas was rendered powerless by an EMP event? That could
Electromagnetic Pulse: Effects on the U.S. Power Grid
Executive Summary The nation s power grid is vulnerable to the effects of an electromagnetic pulse (EMP), a sudden burst of electromagnetic radiation resulting from a natural or man-made event. EMP events
Network Vulnerability to Electromagnetic Pulse Attacks
Network Vulnerability to Electromagnetic Pulse Attacks Steve Goeringer Jason Rupe Abstract An approach to assessing transport network robustness to single event EMP attacks. 2015 Polar Star Consulting,
Digital C4I Interoperability: The EM Protection Issue
Digital C4I Interoperability: The EM Protection Issue Robert Pfeffer U.S. Army Nuclear and Chemical Agency ATTN: ATNA-NU (R. Pfeffer) 7150 Heller Loop Suite 101 Springfield, VA 22150-3198 Abstract In this
Harmful Interference into Satellite Telecommunications by Cyber Attack
Kobe and QM Symposium on International Law "Diversity of Transnational Criminal Justice" Harmful Interference into Satellite Telecommunications by Cyber Attack 10 April 2015 Yuri Takaya Research Fellow/Lecturer,
The Early-Time (E1) High-Altitude Electromagnetic Pulse (HEMP) and Its Impact on the U.S. Power Grid
Meta-R-320 The Early-Time (E1) High-Altitude Electromagnetic Pulse (HEMP) and Its Impact on the U.S. Power Grid Edward Savage James Gilbert William Radasky Metatech Corporation 358 S. Fairview Ave., Suite
Evaluating Cell Phone and Personal Communications Equipment and their EMC Effects on Automotive Audio and In-Cabin Modules
Evaluating Cell Phone and Personal Communications Equipment and their EMC Effects on Automotive Audio and In-Cabin Modules Craig W. Fanning Elite Electronic Engineering, Inc. 1516 Centre Circle Downers
Does it state the management commitment and set out the organizational approach to managing information security?
Risk Assessment Check List Information Security Policy 1. Information security policy document Does an Information security policy exist, which is approved by the management, published and communicated
Metrics and Methods for Security Risk Management
Metrics and Methods for Security Risk Management Carl S. Young ELSEVIER AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD PARIS SAN DIEGO SAN FRANCISCO SINGAPORE SYDNEY TOKYO Syngress is an imprint of
IEC and CISPR Standards
IEC and CISPR Standards With thanks to Gideon Wiid, PhD student, and Paul van der Merwe EE Eng, 2 May, 2007 EMC Definition: Electromagnetic compatibility itself is defined as [1]: "the ability of an equipment
Disruptive Effects of Electromagnetic Interference on Communication and Electronic Systems
Disruptive Effects of Electromagnetic Interference on Communication and Electronic Systems James Burrell Research project submission for the partial fulfillment of the requirements for the degree of Master
EEI Business Continuity. Threat Scenario Project (TSP) April 4, 2012. EEI Threat Scenario Project
EEI Business Continuity Conference Threat Scenario (TSP) April 4, 2012 EEI Threat Scenario 1 Background EEI, working with a group of CIOs and Subject Matter Experts, conducted a survey with member companies
I. PURPOSE II. SITUATION AND ASSUMPTIONS
I. PURPOSE This annex describes the processes for providing reliable and effective communications among organizations participating in an emergency operation. This Annex is designed to support the City
INFRAGARD.ORG. Portland FBI. Unclassified 1
INFRAGARD.ORG Portland FBI 1 INFRAGARD Thousands of Members One Mission Securing Infrastructure The subject matter experts include: 2 INFRAGARD Provides a trusted environment for the exchange of Intelligence
Physical Security of Remote Pilot Stations and Aircrafts (when On Ground)
Physical Security of Remote Pilot Stations and Aircrafts (when On Ground) Airbus Defence and Space / Military Aircraft / INFOSEC Juan Domingo Airbus Defence and Space INFOSEC Expert IF-G-MES84-15002 Table
Supply Chain Risk Management. Operating ahead of the threat, not behind the vulnerabilities
Supply Chain Risk Management Operating ahead of the threat, not behind the vulnerabilities Navigation in the Meeting Room Notes box for audio information and other announcements To enlarge the slide, click
New England Defense Contracting Trends
New England Defense Contracting Trends 2006 2010 Prepared for the Defense Technology Initiative University of Massachusetts Donahue Institute Economic and Public Policy Research Unit October, 2011 About
Investigation of the Risk of Electromagnetic Security on Computer Systems
Investigation of the Risk of Electromagnetic Security on Computer Systems Changlin Zhou, Member, IACSIT, IEEE, Qun Yu, and Litao Wang Abstract Electromagnetic environmental effects (E3) and compromising
Users Manual FA106 / FA306 version 1.0. Field Analyzer. FA106 and FA306. Users Manual
Field Analyzer FA106 and FA306 Users Manual 1 Contents Contents...2 Preface...3 Chapter 1 Basic Functions...4 1.1 Turning on/off...4 1.2 Choosing the required measuring mode...4 1.3 Picture of front panel...5
Introduction. So, What Is a Btu?
Introduction The way of life that we Americans take for granted every day depends upon a stable and abundant supply of affordable energy. Energy shortages can quickly affect our everyday lives and harm
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
Fiber Optics: Engineering from Global to Nanometer Dimensions
Fiber Optics: Engineering from Global to Nanometer Dimensions Prof. Craig Armiento Fall 2003 1 Optical Fiber Communications What is it? Transmission of information using light over an optical fiber Why
Telephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
Radio Frequency Interference (RFI) Shielding Principles
Radio Frequency Interference (RFI) Shielding Principles 1.0 Introduction The purpose of this document is to provide Krieger Specialty Products clients and personnel information pertaining to shielding
BUILDING DESIGN FOR HOMELAND SECURITY. Unit IV Vulnerability Assessment
Unit IV Vulnerability Assessment Vulnerability Any weakness that can be exploited by an aggressor or, in a non-terrorist threat environment, make an asset susceptible to hazard damage Unit IV-2 Unit Objectives
Security & Surveillance Cabling Systems
Security & Surveillance Cabling Systems Security and Surveillance Cabling Systems The video security industry is growing and ever-changing, offering a wealth of opportunity for today s security professionals.
Services we provide. Tel: +1 561-623-8810 email: [email protected] http://www.eetengineering.com
EET Engineering specializes in providing timely, cost-efficient, quality engineering solutions to support the successful implementation of our customer s requirements. For over 24 years, our leadership
Subj: SURVIVABILITY POLICY AND STANDARDS FOR SURFACE SHIPS AND CRAFT OF THE U.S. NAVY
DEPARTMENT OF THE NAVY OFFICE OF THE CHIEF OF NAVAL OPERATIONS 2000 NAVY PENTAGON WASHINGTON, DC 20350-2000 OPNAVINST 9070.1A N9 OPNAV INSTRUCTION 9070.1A From: Chief of Naval Operations Subj: SURVIVABILITY
Security+ Guide to Network Security Fundamentals, Fourth Edition. Chapter 13 Business Continuity
Security+ Guide to Network Security Fundamentals, Fourth Edition Chapter 13 Business Continuity Objectives Define environmental controls Describe the components of redundancy planning List disaster recovery
Chicago Center Fire Contingency Planning and Security Review
Chicago Center Fire Contingency Planning and Security Review Background In the early morning hours of September 26, 2014, the Federal Aviation Administration s (FAA) Chicago Air Route Traffic Control Center
CONSIDERATIONS FOR A POWER TRANSFORMER EMERGENCY SPARE STRATEGY FOR THE ELECTRIC UTILITY INDUSTRY
CONSIDERATIONS FOR A POWER TRANSFORMER EMERGENCY SPARE STRATEGY FOR THE ELECTRIC UTILITY INDUSTRY Prepared by The Electric Power Research Institute for the U.S. Department of Homeland Security Science
Radio waves and health. Mobile communications
Radio waves and health Mobile communications Mobile communications and health Mobile telephony Radio communications have been used for more than a hundred years in various sorts of applications. Already
Measurement of Protection from Cell Phone Radiation by 8ight Protect Disc
Measurement of Protection from Radiation by Protect Disc Research conducted by Lisa Tully, PhD, [email protected] Energy Medicine Research Institute, Boulder, CO May, Abstract A study was conducted
Rack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
THE NARTE EMC ENGINEER CERTIFICATION PROCESS - A PERSONAL EXPERIENCE
THE NARTE EMC ENGINEER CERTIFICATION PROCESS - A PERSONAL EXPERIENCE Sandy Mazzola, NCE, EMC-002506 002506-NE BAE Systems Inc. NARTE NARTE is a worldwide, non-profit, professional telecommunications association
NIST Disaster Resilience Framework
NIST Disaster Resilience Framework Communication and Information Systems Presenter: David Mizzen Applied Research Associates Chapter Goals Provide guidance to: 1. Understand potential vulnerabilities/damage
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
Clinic Business Continuity Plan Guidelines
Clinic Business Continuity Plan Guidelines Emergency notification contacts: Primary Role Name Address Home phone Mobile/Cell phone Business Continuity Plan Coordinator QSP Business Continuity Plan Coordinator
Secure and Reliable Wireless Communications for Geological Repositories and Nuclear Facilities
Session S14: Safeguards Needs at Geological Repositories and Encapsulation Facilities Secure and Reliable Wireless Communications for Geological Repositories and Nuclear Facilities Richard E. Twogood Dirac
TELECOMMUNICATION SYSTEM HAZARD MITIGATION STRATEGIC PLANNING
TELECOMMUNICATION SYSTEM HAZARD MITIGATION STRATEGIC PLANNING A.K. Tang 1 1 President, L&T Engineering and Project Management Consultant, Mississauga. Canada Email: [email protected] ABSTRACT: Telecommunication
30 In Compliance October 2014 www.incompliancemag.com
30 In Compliance October 2014 www.incompliancemag.com Medical Devices in a Wireless World BY IVAYLO TANKOV While wireless technology is now an integral component of a wide variety of manufactured products,
Software Radio Applications
Software Radio Applications S-72.333 Postgraduate Seminar on Radio Communications Aarne Hummelholm [email protected] Communications Laboratory 15.2.2005 AGENDA - WHAT IS A SOFTWARE RADIO - WHO POSSIBLE
Public Private Partnerships and National Input to International Cyber Security
Public Private Partnerships and National Input to International Cyber Security 10 September 2009 Tallinn, Estonia Maeve Dion Center for Infrastructure Protection George Mason University School of Law Arlington,
Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012
Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012 CHANGE CONTROL RECORD: Version Date Action* Reason for Revision
Microwave Photonic Systems Inc. Joshua L. Korson & Richard J. Stewart
Fiber Optic Communications Equipment Provides Backhaul Infrastructure for Critical Satellite Based Continuity of Communications Solutions: IRIDUIM, INMARSAT, GEO SATCOM Microwave Photonic Systems Inc.
AN96-07. Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x
TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x On January 1, 1996, exports into Europe began facing some tough transient immunity standards. The International Electrotechnical Commission (IEC), a worldwide
Application Note: Spread Spectrum Oscillators Reduce EMI for High Speed Digital Systems
Application Note: Spread Spectrum Oscillators Reduce EMI for High Speed Digital Systems Introduction to Electro-magnetic Interference Design engineers seek to minimize harmful interference between components,
NUCLEAR HIGH ALTITUDE ELECTROMAGNETIC PULSE IMPLICATIONS FOR HOMELAND SECURITY AND HOMELAND DEFENSE
USAWC STRATEGY RESEARCH PROJECT NUCLEAR HIGH ALTITUDE ELECTROMAGNETIC PULSE IMPLICATIONS FOR HOMELAND SECURITY AND HOMELAND DEFENSE by Lieutenant Colonel Thomas C. Riddle United States Army Colonel William
What do SAE standards offer the Automotive Electronics industry?
What do SAE standards offer the Automotive Electronics industry? Just about everything. Volume 2, 2009 SAE standards stand ready to serve industry s growing need for globally harmonized standards solutions.
Policy wording. General conditions. AMI Businesspack Business Insurance. Your duty to comply. About this Businesspack policy. Interpreting this Policy
AMI Businesspack Business Insurance Policy wording Welcome, thanks for choosing to protect your business with IAG New Zealand Limited. AMI Insurance Limited is part of the IAG group of companies in New
Analysis of Immunity by RF Wireless Communication Signals
64 PIERS Proceedings, Guangzhou, China, August 25 28, 2014 Analysis of Immunity by RF Wireless Communication Signals Hongsik Keum 1, Jungyu Yang 2, and Heung-Gyoon Ryu 3 1 EletroMagneticwave Technology
OpenBTS Development Kit
OpenBTS Development Kit Specifications, Installation & Operation Doc. Rev. 1 Copyright c 2013 Range Networks, Inc. All rights reserved Contents 1 Introduction 6 1.1 Scope and Audience.........................................
This presentation will introduce you to the concepts and terminology related to disaster recovery planning for businesses.
1. An Introduction This presentation will introduce you to the concepts and terminology related to disaster recovery planning for businesses. This presentation was prepared by the South Central Economic
PBSi Business Continuity Planning
Business Continuity Planning Definition Business Continuity planning is a planning process designed to reduce the risk that disruptive failures or events could seriously harm your business. It is designed
Report of the Commission to Assess the Threat to the United States from Electromagnetic Pulse (EMP) Attack
Report of the Commission to Assess the Threat to the United States from Electromagnetic Pulse (EMP) Attack Volume 1: Executive Report 2004 Dr. John S. Foster, Jr. Mr. Earl Gjelde Dr. William R. Graham
A DESCRIPTION OF THE SOFTWARE ELEMENT OF THE NASA EME FLIGHT TESTS
NASA Contractor Report 201635 A DESCRIPTION OF THE SOFTWARE ELEMENT OF THE NASA EME FLIGHT TESTS Sandra V. Koppen Lockheed Martin Engineering & Sciences Company, Hampton, Virginia 23666 Contract: NAS1-19000
Clinic Business Continuity Plan Guidelines
Clinic Business Continuity Plan Guidelines Published: January 2015 Table of Contents Emergency Notification Contacts Primary... 2 Emergency Notification Contacts Backups (in case primary is unavailable)...
Professional Development Kit Series
Professional Development Kit Series Specifications, Installation & Operation Doc. Rev. 2 Copyright c 2013 Range Networks, Inc. All rights reserved Contents 1 Introduction 6 1.1 Scope and Audience.........................................
40 Years of experience in EMC testing
40 Years of experience in EMC testing Your reference laboratory for tests of generation, propagation and reception of electromagnetic energy in civil, military and industrial applications. CESI has been
White Paper Assured PNT Inside Military Ground Vehicles Using D3
White Paper Assured PNT Inside Military Ground Vehicles Using D3 Brian Paul December 2013 Introduction Global Positioning System (GPS) technology has become an integral part of Mission Command systems
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen
Common Power Problems & Power Protection Solutions
W H I T E P A P E R Common Power Problems & Power Protection Solutions Executive Summary All systems, from home theaters and office desktops to enterprise IT equipment in data centers, are prone to downtime,
BUILDING DESIGN FOR HOMELAND SECURITY. Unit I Building Design for Homeland Security
BUILDING DESIGN FOR HOMELAND SECURITY Unit I Building Design for Homeland Security Participant Introductions Name Affiliation Area of Concentration BUILDING DESIGN FOR HOMELAND SECURITY Unit I-2 Course
SSM3K335R SSM3K335R. 1. Applications. 2. Features. 3. Packaging and Pin Configuration. 2012-07-19 Rev.3.0. Silicon N-Channel MOS (U-MOS -H)
MOSFETs Silicon N-Channel MOS (U-MOS-H) SSM3K335R SSM3K335R 1. Applications Power Management Switches DC-DC Converters 2. Features (1) 4.5-V gate drive voltage. (2) Low drain-source on-resistance : R DS(ON)
with Component Rating A Simple Perspective
Cat-6A UTP and Shielded with Component Rating A Simple Perspective Asef Baddar RCDD, DCD Sr. Technical Manager Leviton Middle East Category Specifications Agenda Terminology International & North America
Waves - Transverse and Longitudinal Waves
Waves - Transverse and Longitudinal Waves wave may be defined as a periodic disturbance in a medium that carries energy from one point to another. ll waves require a source and a medium of propagation.
Electromagnetic Compatibility Considerations for Switching Power Supplies
Electromagnetic Compatibility Considerations Characterization of the EMI problem requires understanding the interference source Switching power supplies generate Electromagnetic Interference (EMI) by virtue
Understanding SMD Power Inductors. Application Note. July 2011
Understanding SMD Power Inductors July 2011 Application Note Power inductors play an important role in voltage conversion applications by yielding lower core losses. They are also used to store energy,
Critical Infrastructure
Critical Infrastructure Long-term Trends and Drivers and Their Implications for Emergency Management June 2011 Overview The state and nature of infrastructure is likely to change over the next several
BUSINESS CONTINUITY PLAN
Business Logo or Name here BUSINESS CONTINUITY PLAN FOR PERSONAL CARE PROVIDERS TEMPLATE PREPARED BY DEVON COUNTY COUNCIL EMERGENCY PLANNING SERVICE BUSINESS CONTINUITY PLAN LIST OF CONTENTS 1. DISCLAIMER...
Analog signal converters CC-E I/I Current / current isolators
ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between
Safety and security are simply good business.
THE BUSINESS ASE FOR YBER SEURITY What s this about in a nutshell? The importance of cyber security for manufacturing and computer control systems has only recently been recognized and therefore has not
USE OF MOBILE TELEPHONES AND OTHER WIRELESS COMMUNICATIONS DEVICES - INTERFERENCE WITH ELECTRONIC MEDICAL EQUIPMENT
USE OF MOBILE TELEPHONES AND OTHER WIRELESS COMMUNICATIONS DEVICES - INTERFERENCE WITH ELECTRONIC MEDICAL EQUIPMENT The radio spectrum is now more crowded than ever before with a variety of devices which
Comparison of Information Sharing, Monitoring and Countermeasures Provisions in the Cybersecurity Bills
April 4, 2012 Comparison of Information Sharing, Monitoring and Countermeasures Provisions in the Cybersecurity Bills The chart below compares on civil liberties grounds four bills that seek to promote
Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER. www.ep2000.com 800.500.
Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER Introduction Heat in the System The modern facility has been revolutionized by advancements
The use of Conductive Cement in data Centers as Building Material
Bulletin of Environment, Pharmacology and Life Sciences Bull. Env.Pharmacol. Life Sci., Vol 4 [Spl issue 1] 2015: 14-19 2014 Academy for Environment and Life Sciences, India Online ISSN 2277-1808 Journal
Mobile Phone Base-Station Audit
Mobile Phone Base-Station Audit Audit site: Aylesbury Road Wing Leighton Buzzard Beds LU7 0NY The Office of Communications (Ofcom) is responsible for management of the civil radio spectrum in the UK. Following
Results of Airborne Monitoring by the Ministry of Education, Culture, Sports, Science and Technology and the U.S. Department of Energy
May 6, 2011 Results of Airborne Monitoring by the Ministry of Education, Culture, Sports, Science and Technology and the U.S. Department of Energy The results of the Airborne Monitoring by the Ministry
Simulation électromagnétique 3D et câblage, exemples dans l'automobile et aéronautique :
Simulation électromagnétique 3D et câblage, exemples dans l'automobile et aéronautique : CST, Christophe Morin 1 www.cst.com Agenda - Présentation CST - Simulation câblage dans modèle 3D - Exemples automobile
How to Prevent Power Surges: The Leading Cause of Serial Device Server Failures
How to Prevent Power Surges: The Leading Cause of Serial Device Server Failures Jasmine Lin Product Manager, Moxa Inc Voltage spikes are brief events that rarely last more than a few microseconds, but
AN-6 COMMON MISTAKES IN LIGHTNING PROTECTION OF PHONE LINE INTERFACE CIRCUITS
AN-6 COMMON MISTAKES IN LIGHTNING PROTECTION OF PHONE LINE INTERFACE CIRCUITS By Joe Randolph Introduction Lightning protection of phone line interface circuits is a complicated topic. The specific protection
Clamp Filters that Suppress Emission Noise Provide Immunity Against Surge Noise
TDK EMC Technology Product Section Clamp Filters that Suppress Emission Noise Provide Immunity Against Surge Noise TDK Shonai Corporation Satoru Saito Reduce Emission Noise from Cables Even if an electronic
Verizon NEBS TM Compliance: HVAC Systems NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9808 Issue 1, April 2014
Verizon NEBS TM Compliance: HVAC Systems NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9808 Issue 1, April 2014 CHANGE CONTROL RECORD: Version Date Action* Reason for Revision 1 4/14/2014
Integrated Metering Systems, Inc.
Integrated Metering Systems, Inc. EM Pro Energy Allocation System Product Guide Technical Specifications PN: 114-000X Revision 0.7 List of Figures... 2 List of Tables... 2 1. Product Description... 3 1.1
Developer s Guide to Submetering Submetering Specifications for Multi-Housing Construction
AmericanWater&EnergySavers 4431NorthDixieHighway BocaRaton,FL33431 TolFree:(800)90-908 Office:(61)361-4014 Fax:(61)361-4201 Developer s Guide to Submetering Submetering Specifications for Multi-Housing
CHAPTER 4. Electromagnetic Spectrum
ELEC4504 Avionics Systems 9 CHAPTER 4. Electromagnetic Spectrum 4.1. Electromagnetic (EM) Waves In free space (or the atmosphere) the electric field is perpendicular to the magnetic field and both are
SARPS about Emergency frequency. 12 May 2015
SARPS about Emergency frequency 12 May 2015 Annex 6 3.1.5 If an emergency situation which endangers the safety of the aeroplane or persons becomes known first to the flight operations officer/flight dispatcher,