DOMESTIC SMOKE ALARMS

Size: px
Start display at page:

Download "DOMESTIC SMOKE ALARMS"

Transcription

1 DIgest DG 525 DOMESTIC SMOKE ALARMS Emma Warren Smoke alarms in homes can save lives, are easy to use and are inexpensive. If correctly specified, installed and maintained, they will give an early warning of fire that can allow occupants to safely escape, while nuisance alarms are minimised. This Information Paper provides guidance on the different types of smoke alarm available, and on correctly specifying, locating, installing and maintaining fire detection and alarm systems. It reviews a number of the recommendations given in relevant regulatory guidance, as well as the use of third-party-approved fire detection and alarm products and installers. The information provided will be of particular interest to UK house builders, building control officers, specifiers, manufacturers, building owners and the fire and rescue services, and may also be of use to similar professionals in other countries subject to local code or national legislative requirements. INTRODUCTION The number of UK homes fitted with smoke alarms has risen from just 8% in 1988 to 91% in 2008 [1], as a result of the changes to the Building Regulations Approved Document B Fire Safety [2] in This has led to a dramatic reduction in deaths and injuries from household fires, but there are still more than 200 deaths and some 7500 injuries from the 36,000 dwelling fires attended by fire and rescue services every year [3]. Many of these casualties could be avoided if people had early warning of fire and were able to escape in time. Smoke alarms that are appropriately selected, located, fitted and maintained can dramatically improve fire safety in homes A suitably specified, located and maintained smoke alarm can provide this warning by detecting smoke in the early stages of the fire and sounding an alarm. UK fire statistics show that you are almost twice as likely to die in a domestic fire where there is no working smoke alarm as you are where one is present [3]. TYPES OF SMOKE ALARM Domestic smoke alarms are simple, self-contained but often interconnected units, incorporating a smoke detector, power source and alarm sounder. Smoke detectors There are two types of smoke alarm in common use: one is fitted with an ionisation smoke detector, the other with an optical or photoelectric detector.

2 2 DOMESTIC SMOKE ALARMS DG 525 Figure 1: Inside a smoke alarm that uses an ionisation detector Figure 3: Inside a smoke alarm that uses an optical detector Figure 2: Ionisation smoke chamber Apollo Fire Detectors Ltd 1997/RHD/JDR Figure 4: Optical smoke chamber Apollo Fire Detectors Ltd 1997/RHD Ionisation detectors Ionisation detectors (Figure 1) make use of the radioactive element Americium 241. Americium emits alpha radiation that can only travel a few centimetres in air and can be stopped by a sheet of paper, and so is safe for use in the home. The radiation passes through an air-filled space in the detector (the ionisation chamber), enabling a small current to flow between two electrodes. If smoke enters the chamber it absorbs the alpha particles. This reduces the ionisation and interrupts the current, setting off the alarm when a preset threshold level is reached (Figure 2). Optical or photoelectric detectors An optical detector (Figure 3) contains a light source, typically an LED, collimated into a beam using a lens. A photosensor is fitted at an angle to this light beam. When smoke particles enter the device they scatter the light, directing some of it towards the sensor and setting off the alarm (Figure 4). Combination and other alarms Smoke alarms that contain both ionisation and optical detectors are available. They offer increased alarm sensitivity across a range of fire types (smouldering and flaming) as a result of the detectors differing capabilities (see Ionisation or optical detector alarms? below). Heat and carbon monoxide (CO) detectors are also available for use in domestic properties, but are considerably less sensitive than smoke alarms and should therefore be used in conjunction with, not instead of, smoke alarms. Heat and CO detectors are increasingly fitted where ionisation and optical devices are not suitable for example, heat detectors are recommended for installation in kitchens. An important recent development has been the introduction of multisensor smoke alarms to the domestic market. They contain more than one type of sensor, eg a combined optical/heat detector or optical/co detector. Interconnection Smoke alarms throughout the dwelling can be wired together, enabling them all to sound when one device alarms. This gives more efficient warning and greater escape time to occupants, and can reduce the risk to both life and property. Radio signals can also be used to connect smoke alarms, allowing the benefits of interconnection without the disruption and expense that wired connection can entail. This makes smoke alarm installation simpler, enabling dwelling occupiers to install interconnected smoke alarm systems themselves under the manufacturer s instructions. Wireless smoke alarms may be preferred for aesthetic reasons, particularly in listed or historic dwellings, and can also be used during construction or refurbishment to protect a property in which wiring has not yet been installed.

3 DOMESTIC SMOKE ALARMS DG Power sources Smoke alarms can be powered by batteries either standard 9V or rechargeable lithium batteries or by mains power. Mains-powered smoke alarms, which need to be installed by qualified electricians, are generally more reliable and are available with a battery backup in case of power cuts. In 2008, battery-powered smoke alarms failed to operate in 36% of UK fires where a smoke alarm was present, mainly because of missing or flat batteries. Over the same period, only 15% of mains-powered smoke alarms failed to operate, mainly because the smoke did not reach the detectors [3]. The introduction of 10-year rechargeable lithium batteries for smoke alarms has allowed greater reliability by reducing maintenance requirements. In many smoke alarms, the battery lifetime is now as long as the alarm lifetime. An additional option is a smoke alarm that plugs into light sockets and uses rechargeable batteries that charge when the light is on. SELECTING SMOKE ALARMS BS :2004 (Fire detection and fire alarm systems for buildings Code of practice for the design, installation and maintenance of fire detection and fire alarm systems in dwellings) [4] provides detailed guidance on the use of smoke alarms in new and existing dwellings, both for single-family properties and for houses in multiple occupation (HMOs). When introduced in 1995, BS became a key set of recommendations for building professionals, detection- and alarm-system designers, installers, landlords and others with an interest in fire safety in the home. In the 2004 update, recommendations were made more stringent, eg by increasing the minimum level of protection required in new buildings, recommending standby power supplies for mains-powered smoke alarms and increasing the emphasis on reducing the number of false alarms. The current standard for smoke alarm devices is BS EN 14604:2005 (Smoke alarm devices) [5]. This specifies the requirements, testing methods, performance criteria and manufacturers instructions for both optical and ionisation devices for use in residential buildings. It is used throughout the European Economic Area. Other available guidance on smoke alarm selection includes the listings of third-party-assessed and approved manufacturers and products such as those produced by the Loss Prevention Certification Board (LPCB), which are outlined below. Current UK fire safety regulations are summarised in Box 1. Ionisation or optical detector alarms? While the two main types of detector are both generally suitable for use in homes, each has advantages depending on the particular circumstances. BS recommends that the choice of smoke alarm for a space should consider both the likely type of fire (flaming or smouldering) and the need to avoid false or nuisance alarms. Box 1: UK fire safety regulations The fire safety requirements in the British Isles vary across the different regions/nations, as follows: England and Wales: guidance on complying with the requirements in the building regulations is provided in Approved Document B (2006) [2]. Scotland: the document used is Section 2 of the Domestic Technical Handbook [6]. Northern Ireland: Technical Booklet E (2005) [7] is used. Republic of Ireland: Technical Guidance Document Part B (2006) [8] is used. These documents outline the requirements for new buildings, extensions, alterations and changes of purpose. In the UK, existing dwellings are covered by the Housing Health and Safety Rating System (HHSRS) [9] under the Housing Act 2004 [10], and in the case of HMOs and some other multiple-occupancy properties, fire safety duties are also imposed by the Regulatory Reform (Fire Safety) Order 2005 [11]. Ionisation detectors more rapidly detect the small smoke particles produced by fast-flaming fires, and are therefore recommended where these present the greater risk to occupants such as in living rooms. Optical detectors respond more quickly to smouldering fires, which produce larger smoke particles. They are recommended for areas such as bedrooms where, for example, a cigarette dropped onto furniture or bedding will result in a smouldering fire. Optical detectors are more effective at detecting particles at a distance from the fire, where the particles are likely to have coalesced to reach a greater size [12]. They are therefore recommended for circulation spaces in homes eg halls and landings which are more distant from likely fire ignition sources. Optical detectors are also recommended in areas of high air flow, where ionisation detectors can experience problems because the ions may be blown out of their ionisation chambers. Ionisation detectors being quick to react to small particles are more likely to respond to fumes such as those produced by cooking, and are therefore more prone to nuisance alarms when installed in circulation areas [13]. Neither type of smoke alarm is suitable for installation in cooking areas, as nuisance alarms would be too frequent. Heat alarms are therefore recommended for the kitchen, the room in a dwelling where most fires start [3]. In the past, ionisation detectors have been used more widely because they are cheaper to produce than optical detectors. However, in recent years increased security concerns have made the storage, transport and disposal of the radioactive material used in ionisation detectors a more complex and expensive issue. Third-party certification Third-party certification is an assessment and approval process carried out by an independent body that is not associated with either the manufacturer or the customer, in order to confirm that a product meets and will continue to meet a specified standard.

4 4 DOMESTIC SMOKE ALARMS DG 525 Manufacturers of third-party-approved smoke alarms will have had their products rigorously tested and approved by certification bodies such as the LPCB, and are subject to a combination of regular company audits and schedules of ongoing tests. This gives users the confidence that the alarms will perform as expected, provided they have been correctly installed and maintained. LPCBapproved smoke alarm manufacturers and products and detection- and alarm-system installers are listed in the LPCB Red Book (see While not required by law in the UK, third-party certification offers a number of benefits to specifiers. Expensive mistakes, for example, can be avoided by using products that have been independently shown to be effective. Specifying third-party-approved products also reduces risks, mitigating accusations of negligence by proving due diligence. There are also benefits for manufacturers, including the potential to improve global sales the use of thirdparty-approved products is often specified, and in some territories is mandatory. It can also add value to products, and reduce liability by proving due diligence. SPECIFYING FIRE DETECTION AND ALARM SYSTEMS BS assists with the specification of fire detection and alarm systems by defining grades of alarm system and categories of protection required. Which grade of alarm system? BS grades fire detection and alarm systems from Grade A to Grade F, taking such issues as power source reliability and the level of control and monitoring possible into account. In general, the greater the fire risk and the more demanding the application, the more comprehensive the system needs to be. The grades used are outlined below: Grade A: fire detection and alarm system with control and indicating equipment compliant with BS EN 54-2:1998 [14] and power supply compliant with BS EN 54-4:1998 [15], designed and installed in accordance with BS :2002 [16]. Grade B: fire detection and alarm system comprising fire detectors (other than smoke/heat alarms) and sounders, with control and indicating equipment compliant with BS EN 54-2 and power supply compliant with BS EN Grade C: detectors and sounders (can be combined in smoke/heat alarms) connected to a common power supply, with a standby supply and central control equipment. Grade D: system of interlinked (wired or radio) mainspowered smoke alarms (plus heat alarms if required), each with backup power. Grade E: system of interlinked (wired or radio) mainspowered smoke alarms (plus heat alarms if required), with no backup power. Grade F: a fire detection and alarm system comprising one or more battery-powered smoke alarms (plus heat alarms if required). Higher-grade systems (A C) Large buildings, buildings containing a considerable number of dwelling units and those where the fire risk is particularly high may justify Grade A or B systems. Where a system is designed for property protection, insurers may require a Grade A system, although in smaller properties Grade B or C systems may be sufficient. Grade D systems Grade D is the minimum type of system for new dwellings that complies with the guidance in Approved Document B. The use of mains-powered alarms that each incorporate a standby supply should address the problems outlined below, but if ready access to control is considered necessary a Grade C or higher system will be needed. Grade E systems Grade E systems are not suitable in new dwellings. Mainspowered smoke alarms are potentially more reliable than battery-powered, but are not suitable where the power supply may be intermittent due either to the inability of residents to pay for it or the unreliability of mains supply. Grade F systems Grade F systems should not be installed in new dwellings, but may be considered for existing dwellings if there is a reasonable certainty that batteries will be replaced this is a key issue with battery-operated smoke alarms. Occupants on a tight budget, for example, may find it difficult to afford replacement batteries. In addition, some occupiers might remove the batteries to prevent false alarms or to use in other battery-powered items, and then forget to replace them. What category of protection? BS defines three categories of fire detection and alarm system that are concerned with protecting life (L) in dwellings (D). These are based on the areas in which the detectors and alarms are required, and therefore the level of protection the system offers (Figure 5). They are: Category LD1: detectors throughout the dwelling in all circulation spaces comprising the escape routes, and in all rooms or areas in which a fire might start (other than bathrooms, toilets and shower rooms). Category LD2: detectors installed in all circulation spaces comprising the escape routes, and in all rooms that present a high fire risk to occupants. Category LD3: a system of detectors in all of the circulation spaces comprising the escape routes from the dwelling. BS also defines two categories of fire alarm system installed to protect property in dwellings: PD1 and PD2. Category LD1 and LD2 systems While a Category LD1 system offers the most protection in terms of early fire detection, a good level of protection can be obtained using an LD2 system, which may contain detectors in the kitchen and living room, for example, in addition to the circulation areas.

5 DOMESTIC SMOKE ALARMS DG Figure 5: Smoke alarm coverage provided by the three BS categories of fire detection system If the risk to occupants from fire in any part of the building is high, eg if an occupant suffers from a disability, a Category LD1 or LD2 system should be considered, based on a full risk assessment that takes account of all of the fire protection measures and fire safety systems in place. Category LD3 systems A Category LD3 system is the minimum that is required in new dwellings in order to comply with the guidance in Approved Document B. This system protects the escape routes for occupiers not directly involved in the fire, but may not provide protection to those in the fire s immediate vicinity. Meeting the needs of the various building types BS provides recommendations on the minimum grade and category needed to protect different types of housing. These apply to buildings where details of the occupants are unknown, such as in newbuilds or buildings with high occupant turnover. For a specific property where occupant needs are known, the recommendations can be modified to a higher standard based on a risk assessment. Recommendations for existing properties depend on whether they meet the for fire in BS :1990 (Fire precautions in the design, construction and use of buildings Code of practice for residential buildings) [17], or in national building regulations. These include recommendations on fire-rated partitions, ceilings and doors. If there is some doubt as to whether a dwelling complies with these regulations, the more stringent recommendation for dwellings that do not comply should be followed. The recommendations for the minimum grade and category of system in single-family dwellings and shared dwellings (no more than six people sharing in a similar manner to a family, eg student houses) are outlined below (Tables 1 and 2). There may be requirements in addition to the recommendations for minimum protection in Tables 1 and 2. These are detailed in BS , and include issues such as the type and placement of alarm and battery lifetime. Where occupants or property are considered to be at high risk, these recommendations may not be sufficient and a risk assessment should be carried out. Houses in multiple occupation For the purposes of fire safety, HMOs can be defined as dwellings in which three or more unrelated persons live, who do not form a single household. The minimum levels of protection for HMOs are outlined below (Table 3). Reducing nuisance alarms in larger HMOs In larger HMOs, a mixed alarm system one with a mixture of system grades for different needs, such as Grade D systems in individual dwelling units with a Grade A system in communal areas is recommended. This is because many nuisance alarms can result from several households undertaking activities such as cooking, which can disrupt all occupants of a HMO if a simpler single-grade system is used. The result can be that occupants disable or ignore alarms, and therefore jeopardise their own safety. An example of a mixed system that could meet the needs of a large HMO is a Category L3 system recommended by BS (Fire detection and fire alarm systems for buildings Code of practice for system design, installation, commissioning and maintenance) [16]. This includes interlinked smoke detectors in the communal escape routes, and smoke, heat or CO detectors in the adjoining rooms. In addition, the individual dwelling units will be protected with stand-alone smoke alarm

6 6 DOMESTIC SMOKE ALARMS DG 525 Table 1: Minimum fire protection by grade and category of fire alarm system for dwellings with no floor greater than 200 m 2 in area Class of building Owner-occupied bungalow, flat or other one-storey dwelling Rented bungalow, flat or other one-storey dwelling Owner-occupied maisonette or two-storey dwelling Rented maisonette or two-storey dwelling New dwelling Existing dwelling meeting Existing dwelling not meeting Grade Category Grade Category Grade Category D LD2 F LD3 D LD2 D LD2 F LD3 D LD2 D LD2 F LD3 D LD2 D LD2 D LD3 D LD2 Three-storey dwelling D LD2 D LD3 D LD2 Four- or more storey dwelling B LD2 D LD2 B LD2 Table 2: Minimum fire protection by grade and category of fire alarm system for dwellings with one or more floors greater than 200 m 2 in area Class of building Bungalow, flat or other one-storey dwelling New dwelling Existing dwelling meeting Existing dwelling not meeting Grade Category Grade Category Grade Category D LD2 D LD3 D LD2 Maisonette or two-storey dwelling B LD2 B LD2 B LD2 Three- or more storey dwelling Grade A, Category LD2 system with detectors sited as per BS for a Category L2 system Table 3: Minimum fire protection by grade and category of fire alarm system for HMOs Class of building One- or two-storey HMO with no floor greater than 200 m 2 in area New dwelling Existing dwelling meeting Existing dwelling not meeting Grade Category Grade Category Grade Category D LD2 D LD3 D LD2 All other HMOs Individual dwelling units D LD2 D LD3 D LD2 Communal areas Grade A, Category LD2 system with detectors sited as per BS for a Category L2 system systems in each self-contained unit. Such a system would provide a warning to residents of the HMO before the escape routes become smoke filled, but would reduce the number of nuisance alarms. There are other solutions for reducing nuisance alarms, such as systems with a short delay (typically no more than two minutes) in triggering the smoke alarms in dwelling units other than that in which the alarm was initiated. This enables the occupier to investigate and reset the smoke alarm if there is no cause for concern. In most HMOs, it is appropriate to include manual call points in the fire detection and alarm system. Responsibility Responsibility for fire safety in a HMO is considered under the Management of Houses in Multiple Occupation Regulations 2006 [18]. Under these regulations, the manager of the HMO is responsible for ensuring that fire alarms and equipment are maintained in good order. However, in a mixed system the occupiers of each unit may be responsible for maintaining the smoke alarms within their own dwelling unit and should be made aware of this responsibility even though a separate system is installed to protect escape routes. Detailed guidance on meeting fire safety requirements for different types of HMO and shared housing can be found in LACORS Housing: fire safety [19]. INSTALLATION AND SITING The correct installation of a fire detection and alarm system is extremely important for its effective performance in practice. The system must be installed in accordance with manufacturers instructions, and be properly sited. To ensure this, it is recommended that systems are designed and installed by third-party-certificated contractors, such as those approved to LPS 1014 (Requirements for certificated fire detection and alarm system firms) [20]. Manufacturers instructions for securing alarms to ceilings or walls, which typically requires mechanical fixings, should be followed. Deviation from these can

7 DOMESTIC SMOKE ALARMS DG result in failure in situ of the devices, or in them falling from a height causing a safety risk to building occupants and possible damage to the device. Such damage may lead to problems that include overheating batteries, false alarms, exposed electrical connections and fire detection failures. Siting of alarms Nuisance alarms can result from poor smoke alarm siting, which may induce occupants to remove batteries or damage the devices. In the UK in 2008, 39% of the battery-powered smoke alarms that failed to trigger during a fire did so because of a missing battery or some other act to disable the smoke alarm [3]. BS recommends that smoke and heat alarms be ceiling mounted where possible, at least 300 mm from walls or light fittings. In circulation spaces, no point should be more than 7.5 m from a smoke alarm, and there should be at least one smoke alarm in every hallway and corridor. No bedroom door should be more than 3 m from a smoke alarm, and there should be a smoke alarm between each bedroom and every other room (other than bathrooms, toilets and shower rooms). For Category LD1 or LD2 systems, no point in a room that is being protected should be more than 7.5 m from an alarm. More detailed guidance is included in BS Audibility requirements BS recommends that a smoke alarm sounder should provide at least 85 db at the door of each bedroom unless there is an alarm or sounder within the bedroom if there is a fire anywhere in the dwelling. For some HMOs in which high levels of background noise or other factors mean that greater audibility is required, a sound level of 75 db at the bedhead is advised. BS notes that, in practice, this is unlikely to be accomplished without a sounder or alarm within the bedroom. MAINTENANCE Poor smoke alarm maintenance can result in the increased frequency of nuisance alarms or in smoke alarm failure during a fire. Routine testing should be undertaken weekly to ensure that no major failure has occurred, as recommended by fire and rescue services throughout the UK. Grade A systems should be tested as recommended by BS All other systems should be tested by operating every alarm in the building. With smoke or heat alarms, this can be done by operating the test button on each device. If the building has been unoccupied for a period in which power could have failed, the system should be tested on reoccupation of the dwelling. Recently developed handheld remote programming and testing tools can be used to test smoke alarms, allowing testing to be undertaken on alarms that are difficult to reach or by people who are less mobile. Grade A, B and C systems should be serviced at least every six months, as recommended in BS , and in accordance with the installer s or manufacturer s instructions as appropriate. It is recommended, particularly for Grade A systems, that this is undertaken by a third-party-approved contractor with specialist knowledge of fire detection and alarm systems, such as those approved to LPS Smoke alarms in Grade D, E and F systems should be cleaned in accordance with the manufacturer s instructions at regular intervals, often six-monthly. The build-up of dust and other background particles in the optical or ionisation chamber can make the detector more sensitive, and therefore more prone to false alarms [21]. Alternatively, dust build-up can block up the entry paths for smoke into the detector, making it less sensitive and less likely to react to a fire. If experience shows that the build-up of dust is likely to affect the performance of the device, cleaning should be undertaken more frequently. A recent innovation drift compensation uses microprocessors to monitor slow changes in background particulates, and adjust the sensitivity of the smoke alarm accordingly. Smoke alarms using standard 9V batteries should have replacement batteries on at least a yearly basis, and smoke alarms should be replaced after 10 years of use. SUMMARY The widespread use of domestic smoke alarms has done much to improve fire safety in UK homes. But while new technologies are delivering more reliable smoke alarms systems, the correct specification, installation and maintenance of alarms remains vital to ensuring that they perform properly. The two commonly used types of smoke alarm employ either ionisation or optical smoke detectors to give early, and sometimes life-saving, warning of fire. BS , a key source of guidance on the use of domestic smoke detectors, recommends that the choice of smoke alarm should consider both the likely type of fire (flaming or smouldering) and the need to avoid false or nuisance alarms. The use of smoke alarm products and installers with third-party certification is recommended. Product manufacturers and installers that comply with thirdparty-certification schemes, such as those operated by the LPCB, are subject to independent and ongoing assessment in order to ensure the consistency of product and performance. Grades of alarm system and categories of protection required are defined by BS , and can be used to simply and clearly specify effective alarms systems (eg Grade D, Category LD2). BS also provides recommendations on the minimum grade and category needed to protect different types of housing, including houses in multiple occupation. To ensure that they work well and that nuisance alarms are minimised, smoke alarms must be located and installed correctly; they must be regularly tested and cleaned, and the reliability of their power sources ensured.

8 8 DOMESTIC SMOKE ALARMS DG 525 REFERENCES * 1 Department for Communities and Local Government (DCLG). Fire statistics monitor. Issue 02/11. London, DCLG, 24 June Department for Communities and Local Government (DCLG). The Building Regulations Approved Document B: Fire safety. Volume 1: Dwellinghouses; Volume 2: Buildings other than dwellinghouses (2006 edn). London, DCLG, Department for Communities and Local Government (DCLG). Fire statistics, United Kingdom London, DCLG, BSI. Fire detection and fire alarm systems for buildings Code of practice for the design, installation and maintenance of fire detection and fire alarm systems in dwellings. BS :2004. London, BSI, BSI. Smoke alarm devices. BS EN 14604:2005. London, BSI, Scottish Government Building Standards Division. The Building (Scotland) Amendment Regulations Domestic Technical Handbook. Section 2: Fire (2011 edn). Edinburgh, Scottish Government, Department of Finance and Personnel Northern Ireland. The Building Regulations (Northern Ireland) Technical Booklet E: Fire safety (2005 edn). Belfast, TSO, Department of the Environment, Heritage and Local Government. Building Regulations (Republic of Ireland) Technical Guidance Document Part B: Fire safety (2006 edn). Dublin, TSO, The Housing Health and Safety Rating System (England) Regulations SI London, TSO, The Housing Act Chapter 34. London, TSO, Regulatory Reform (Fire Safety) Order SI London, TSO, Fleming J M. Photoelectric vs. ionization detectors: a review of the literature. Proceedings of the Fire Suppression and Detection Research Application Symposium, National Fire Protection Research Foundation, Orlando, FL, February Available at: 13 National Institute of Standards and Technology (NIST). Performance of home smoke alarms. NIST Technical Note Washington, DC, NIST, December 2007 revision. 14 BSI. Fire detection and fire alarm systems Control and indicating equipment. BS EN 54-2: A1:2006. London, BSI, BSI. Fire detection and fire alarm systems Power supply equipment. BS EN 54-4:1998. London, BSI, BSI. Fire detection and fire alarm systems for buildings Code of practice for system design, installation, commissioning and maintenance. BS :2002. London, BSI, BSI. Fire precautions in the design, construction and use of buildings Code of practice for residential buildings. BS :1990. London, BSI, The Management of Houses in Multiple Occupation (England) Regulations SI 372. London, TSO, Local Authorities Coordinators of Regulatory Services (LACORS). Housing: fire safety. Guidance on fire safety provisions for certain types of existing housing. London, LACORS, Loss Prevention Certification Board (LPCB). Requirements for certificated fire detection and alarm system firms. LPS Watford, BRE Global, Available at: 21 Dziekan M. Where there s smoke there s (not always) fire: an inside look at smoke detectors. The Citizen Scientist, 23 July Available at: weeklyissues/ /feature1/index.html. Acknowledgements The preparation and publication of this Digest was funded by BRE Trust. The author also wishes to thank FireAngel (Figures 1 and 3) and Apollo Fire Detectors (Figures 2 and 4) for supplying the images used in this Digest. * All URLs accessed May The publisher accepts no responsibility for the persistence or accuracy of URLs referred to in this publication, and does not guarantee that any content on such websites is, or will remain, accurate or appropriate. BRE is the UK s leading centre of expertise on the built environment, construction, energy use in buildings, fire prevention and control, and risk management. BRE is a part of the BRE Group, a world leading research, consultancy, training, testing and certification organisation, delivering sustainability and innovation across the built environment and beyond. The BRE Group is wholly owned by the BRE Trust, a registered charity aiming to advance knowledge, innovation and communication in all matters concerning the built environment for the benefit of all. All BRE Group profits are passed to the BRE Trust to promote its charitable objectives. BRE is committed to providing impartial and authoritative information on all aspects of the built environment. We make every effort to ensure the accuracy and quality of information and guidance when it is published. However, we can take no responsibility for the subsequent use of this information, nor for any errors or omissions it may contain. BRE, Garston, Watford WD25 9XX Tel: , enquiries@bre.co.uk, BRE Digests are authoritative summaries of the state-of-the-art on specific topics in construction design and technology. They draw on BRE s expertise in these areas and provide essential support for all involved in design, specification, construction and maintenance. Digests, Information Papers, Good Building Guides and Good Repair Guides are available on subscription in hard copy and online through BRE Connect. For more details call BRE publications are available from or IHS BRE Press, Willoughby Road, Bracknell RG12 8FB Tel: , Fax: , brepress@ihs.com Requests to copy any part of this publication should be made to: IHS BRE Press, Garston, Watford WD25 9XX Tel: brepress@ihs.com DG 525 BRE 2012 June 2012 ISBN

Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings

Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings Building Control Householder Guidance Leaflet No. 29 Fire detection in dwellings This leaflet is one of a series produced by the Hertfordshire Building Control Technical Forum GUIDANCE NOTE FOR HOME OWNERS

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010

BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Page 1 of 7 PURPOSE: This Guidance

More information

FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS

FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS 1 FIRE ALARMS IN DWELLINGS By John Ware IN THE UK around 80% of all fire deaths and injuries occur in dwellings, a total of 450 to 500 deaths and 14,000 injuries per annum, according to BS 5839-6: 2004.

More information

Fire Standards & Regulations Are you confused?

Fire Standards & Regulations Are you confused? Fire Standards & Regulations Are you confused? Regulatory Reform (Fire Safety) Order Local Licensing Requirements BS 5839-6: 2013 Building Regulations Document B LACORS Fire Safety Guidance Fire Alarm

More information

Fire precautions in dwellings. Private sector housing Providing homes building communities

Fire precautions in dwellings. Private sector housing Providing homes building communities Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared

More information

ELECTRONIC FIRE & SECURITY SYSTEMS. Smoke Alarms, Fire Detection and Alarm Systems in Dwellings

ELECTRONIC FIRE & SECURITY SYSTEMS. Smoke Alarms, Fire Detection and Alarm Systems in Dwellings ELECTRONIC FIRE & The FS Short Guide Series Smoke larms, Fire Detection and larm Systems in Dwellings n Introduction to BS 5839-6:2004 and the associated legislative framework SECURITY SYSTEMS Supporting

More information

Application Guide HMOs

Application Guide HMOs Application Guide HMOs 2 Aims of this guide 3 What is AlarmSense? 3 What is an HMO 3 Fire Protection for an HMO 3 Approved Document B 4 Mandatory Licensing 4 BS 5839 4 Categories of System 6 Application

More information

What you need to know about. Smoke alarms for residential buildings

What you need to know about. Smoke alarms for residential buildings What you need to know about Smoke alarms for residential buildings Are s compulsory? Smoke alarms are compulsory and must be installed in residential buildings on or near the ceiling of every storey. What

More information

Practice Note 2006-27

Practice Note 2006-27 Practice Note Self-Contained smoke alarms to existing buildings This updates the previous Practice Note 2005-27 issued May 2005. Reference to the BCA in this Practice Note means Volume One and Volume Two

More information

720r Addendum: Siting the 720r

720r Addendum: Siting the 720r 720r Addendum: Siting the 720r UK 1 Cooper Security Limited 2013 Every effort has been made to ensure that the contents of this leaflet are correct. However, neither the authors nor Cooper Security Limited

More information

Frequently Asked Questions Mains Powered Smoke, Heat and RF Alarms

Frequently Asked Questions Mains Powered Smoke, Heat and RF Alarms Mains Powered Smoke, Heat and RF Alarms Aico Ltd, Mile End Business Park, Maesbury Road, Oswestry, Shropshire SY10 8NN Tel: 0870 758 4000 Fax: 0870 758 4010 e-mail: enquiries@aico.co.uk www.aico.co.uk

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection

More information

SMOKE ALARMS CLASS 1A BUILDINGS

SMOKE ALARMS CLASS 1A BUILDINGS SMOKE ALARMS CLASS 1A BUILDINGS A smoke alarm is a device that combines both smoke detection and alarm facilities into a single unit. Smoke alarms are required to be installed in all new residential Class

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed

More information

London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords

London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords London Borough of Barnet Fire Safety in Houses in Multiple Occupation A Guide to Landlords March 2016 Contents Introduction p.3 Summary of main requirements p.3 Fire Safety Precautions p.4 Protecting the

More information

Fire Alarm system Installation Guide

Fire Alarm system Installation Guide Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this

More information

INSTALLER INSTRUCTIONS

INSTALLER INSTRUCTIONS 230V~ SMOKE & HEAT ALARMS ALKALINE BATTERY BACK-UP Ei141RC - Ionisation Ei144RC - Heat Ei146RC - Optical RECHARGEABLE LITHIUM CELL BACK-UP Ei161RC - Ionisation Ei164RC - Heat Ei166RC - Optical INSTALLER

More information

Northern Ireland Housing Executive: HMO Fire Safety Guide

Northern Ireland Housing Executive: HMO Fire Safety Guide Northern Ireland Housing Executive: HMO Fire Safety Guide Contents Equality Statement 5 Houses in Multiple Occupation (HMOs) means of escape in case of fire and other fire precautions 6 1.0 Introduction

More information

OHIO BOARD OF BUILDING STANDARDS. Smoke Alarms and Fire Safety

OHIO BOARD OF BUILDING STANDARDS. Smoke Alarms and Fire Safety OHIO BOARD OF BUILDING STANDARDS Smoke Alarms and Fire Safety Updated January 2016 2 UNDERSTANDING THE TERMINOLOGY Detector. An initiation device suitable for connection to a circuit that has a sensor

More information

Public Health Association of Australia: Policy-at-a-glance Smoke Alarms in Residential Housing Policy

Public Health Association of Australia: Policy-at-a-glance Smoke Alarms in Residential Housing Policy Public Health Association of Australia: Policy-at-a-glance Smoke Alarms in Residential Housing Policy Key message: 1. Smoke Alarms Save lives 2. Each year in Australia an average of 58 people are killed

More information

Risk Management Guidelines

Risk Management Guidelines Automatic Fire Alarm (AFA) Automatic Fire Detection (AFD) Introduction AFD can be described as being the means or equipment used to raise an alarm, whilst AFA is actually the action of the alarm itself.

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

DOMESTIC SMOKE ALARMS

DOMESTIC SMOKE ALARMS SOUTH AUSTRALIAN METROPOLITAN FIRE SERVICE HOME FIRE SAFETY INFORMATION For further advice contact the Community Safety Department South Australian Metropolitan Fire Service on 8204 3611 DOMESTIC SMOKE

More information

THE LANDLORDS AND HOUSEBUILDERS GUIDE TO FIRE AND CO SAFETY

THE LANDLORDS AND HOUSEBUILDERS GUIDE TO FIRE AND CO SAFETY August 2006 THE LANDLORDS AND HOUSEBUILDERS GUIDE TO FIRE AND CO SAFETY A comprehensive guide to smoke, heat and carbon monoxide alarms, making sense of: National Building Regulations Codes of Practice

More information

Call reduction guidance for false alarm/ unwanted fire signals

Call reduction guidance for false alarm/ unwanted fire signals Call reduction guidance for false alarm/ unwanted fire signals Acting to Protect & Save Introduction Devon & Somerset Fire & Rescue Service attend in excess of 20,000 incidents each year, approximately

More information

Reducing false alarms

Reducing false alarms Toolkit for Reducing false alarms from Automatic Fire Detection Systems Working together to make Cornwall safer Please read the information and guidance in this leaflet, and answer the questions in sections

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839 AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What

More information

False Alarm/Unwanted Fire Signals Reduction Guidance

False Alarm/Unwanted Fire Signals Reduction Guidance False Alarm/Unwanted Fire Signals Reduction Guidance Compiled By: South Wales Fire and Rescue Service Contents Introduction Why reduce false alarms Typical Causes Actions that can be taken Introduction

More information

Smoke Alarm Legislation Frequently Asked Questions

Smoke Alarm Legislation Frequently Asked Questions THE REQUIREMENT FOR SMOKE ALARMS Is it law for residential properties to have mains powered smoke alarms installed? Residential properties that are subject to sale, transfer of ownership, rent or hire

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

Guidance Sheet : Legislative Requirements for Rented Properties

Guidance Sheet : Legislative Requirements for Rented Properties Guidance Sheet : Legislative Requirements for Rented Properties Introduction: Letting your property and becoming a landlord may seem like the simple solution to filling an empty property and it can be

More information

Guidance on loft conversions in two-storey houses

Guidance on loft conversions in two-storey houses Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for

More information

The Smoke and Carbon Monoxide Alarm (England) Regulations 2015

The Smoke and Carbon Monoxide Alarm (England) Regulations 2015 The Smoke and Carbon Monoxide Alarm (England) Regulations 2015 Q&A Booklet for the Private Rented Sector landlords and tenants September 2015 Department for Communities and Local Government Crown copyright,

More information

Know Your Smoke Alarm

Know Your Smoke Alarm Know Your Smoke Alarm Updated January 29th 2008 Port Angeles Fire Department, Washington Ver. 1.0 Purpose of Smoke Alarms A smoke detector or smoke alarm is a device that detects smoke and issues an alarm

More information

Fire Facts Smoke Alarms

Fire Facts Smoke Alarms Fire Facts Smoke Alarms Your chances of dying in a home fire may be reduced by 50 per cent if a working smoke alarm is present in your home. Smoke alarms, when properly installed, tested and maintained,

More information

FIRE SAFETY PRINCIPLES FOR RESIDENTIAL ACCOMMODATION

FIRE SAFETY PRINCIPLES FOR RESIDENTIAL ACCOMMODATION FIRE SAFETY PRINCIPLES FOR RESIDENTIAL ACCOMMODATION HOUSING REGULATION TEAM HOUSING SERVICES 25 th July 2011 Foreword This document has been produced by Leeds City Council, in consultation with the West

More information

For use by landlords of small premises Premises Address

For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Home Owners Guide to Smoke Alarm Safety

Home Owners Guide to Smoke Alarm Safety Home Owners Guide to Smoke Alarm Safety Smoke alarms save lives. Most importantly - only working smoke alarms save lives. You and your family are at risk if: You do not have batteries in your smoke alarms

More information

Smoke Alarms. New smoke alarm requirements for existing buildings from 1 May 2006. Introduction. Advisory note March 2006

Smoke Alarms. New smoke alarm requirements for existing buildings from 1 May 2006. Introduction. Advisory note March 2006 New smoke alarm requirements for existing buildings from 1 May 2006 Advisory note March 2006 Introduction To enhance safety and minimise loss-of-life in building fires, the NSW Parliament, in July last

More information

LOUTH COUNTY COUNCIL STATEMENT OF POLICY ON DOMESTIC FIRE DETECTION AND ALARM SYSTEMS

LOUTH COUNTY COUNCIL STATEMENT OF POLICY ON DOMESTIC FIRE DETECTION AND ALARM SYSTEMS LOUTH COUNTY COUNCIL STATEMENT OF POLICY ON DOMESTIC FIRE DETECTION AND ALARM SYSTEMS Louth County Council as both a Housing and Fire Authority has a responsibility to encourage compliance and best practise

More information

Smoke & Carbon Monoxide

Smoke & Carbon Monoxide A Guide to the Massachusetts Smoke & Carbon Monoxide Requirements when Selling a Oneor Two-Family Residence FIRE SERVICES Department of Fire Services PO Box 1025 Stow, MA 01775 978-567-3300 www.mass.gov/dfs

More information

Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition

Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building

More information

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone

More information

Fire safety for landlords

Fire safety for landlords Fire safety for landlords Acting Acting to to Protect & Save Are you a landlord and confused about your responsibilities towards fire safety? The law and regulations can often seem complicated and grey.

More information

To promote and protect the private residential landlord. Fire Safety Logbook. Information. Advice. Support. Services START DATE:

To promote and protect the private residential landlord. Fire Safety Logbook. Information. Advice. Support. Services START DATE: To promote and protect the private residential landlord Fire Safety Logbook Information Advice Support Services START DATE: PROPERTY DETAILS Property Address: Post Code: Licence Holder/Manager: CONTACT

More information

Smoke Alarm Legislation

Smoke Alarm Legislation Is it law for residential properties to have mains powered smoke alarms installed? Residential properties that are subject to sale, rent or hire are required under the Building Regulations 2012 to install

More information

FIRE & CO SAFETY IN HOUSING

FIRE & CO SAFETY IN HOUSING Cl/SfB (68.52) Uniclass L7625 January 2015 FIRE & CO SAFETY IN HOUSING Essential guidance for: RSLs and other landlords Housebuilders and developers Architects and Surveyors Building Control Officers Electrical

More information

AlarmSense 2-wire detection and alarm system. Product Guide

AlarmSense 2-wire detection and alarm system. Product Guide AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority

More information

Your Questions Answered

Your Questions Answered Your Questions Answered What do smoke alarm laws in Queensland require? Since July 1997, all new and significantly renovated homes and units have been required to have mains-powered smoke alarms installed

More information

Smoke & Carbon Monoxide

Smoke & Carbon Monoxide A Guide to the Massachusetts Smoke & Carbon Monoxide Requirements when Selling a Oneor Two-Family Residence FIRE SERVICES Department of Fire Services www.mass.gov/dfs M.G.L. C 148 S. 26F - THE LAW Massachusetts

More information

Smoke Alarms prhp prhp

Smoke Alarms prhp prhp Smoke Alarms All registered landlords should have received a copy of the Advice pack for Private Landlords prepared by the Scottish Executive, as the Scottish Government was formerly known. This Advice

More information

Fire safety advice for landlords

Fire safety advice for landlords YOU CAN PREVENT IT Fire safety advice for landlords Introduction Each year there are over 50,000 fires in dwellings in the UK. These result in around 300 hundred fatalities and several thousand serious

More information

Guidance Document on SELECTION AND SPECIFICATION OF FIRE ALARM CATEGORY IN ACCORDANCE WITH BS 5839-1

Guidance Document on SELECTION AND SPECIFICATION OF FIRE ALARM CATEGORY IN ACCORDANCE WITH BS 5839-1 Guidance Document on SELECTION AND SPECIFICATION OF FIRE ALARM CATEGORY IN ACCORDANCE WITH BS 5839-1 FIA Guidance for the Fire Protection Industry This Guidance Note is intended as a general guidance and

More information

FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS

FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS INFORMATION PAPER IP 21/10 FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS Tom Lennon and Danny Hopkin The use of Structural Insulated Panel (SIP) systems in construction in the UK has increased

More information

The Alberta Fire Code requires all homes in the province to have working smoke alarms.

The Alberta Fire Code requires all homes in the province to have working smoke alarms. Your chances of dying in a home fire may be significantly reduced if a working smoke alarm is present in your home. Smoke alarms, when properly installed, tested and maintained, provide an early warning

More information

LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION

LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION 1. Minimum Standards: This document sets out the minimum standards required in HMOs located within the London Borough

More information

Are photoelectric smoke alarms better than ionization smoke alarms for adjacent to kitchen installations, to minimize nuisance alarms?

Are photoelectric smoke alarms better than ionization smoke alarms for adjacent to kitchen installations, to minimize nuisance alarms? Are photoelectric smoke alarms better than ionization smoke alarms for adjacent to kitchen installations, to minimize nuisance alarms? Information Report Applied Research Office of the Fire Marshal March

More information

For use by landlords of small premises Premises Address

For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

CERTIFICATE OF COMPLIANCE

CERTIFICATE OF COMPLIANCE CERTIFICATE OF COMPLIANCE (Smoke Detector Inspection) Smoke detectors and carbon monoxide detectors must be in the proper locations and operational. Your house must also be properly numbered in order to

More information

Landlords Guide to Electrical Safety. Supported by:

Landlords Guide to Electrical Safety. Supported by: Landlords Guide to Electrical Safety Supported by: Abbreviations BS CLG EIC ESC British Standard Communities and Local Government Electrical Installation Certificate Electrical Safety Council EWR Electricity

More information

RHODE ISLAND DIVISION OF STATE FIRE MARSHAL

RHODE ISLAND DIVISION OF STATE FIRE MARSHAL RHODE ISLAND DIVISION OF STATE FIRE MARSHAL Smoke Alarm and Carbon Monoxide Brochure JOHN E. CHARTIER STATE FIRE MARSHAL 118 PARADE STREET PROVIDENCE, RI 02909 DAYS 401-462-4200 24 Hr. 401-222-2331 FAX#

More information

Guide to Massachusetts Smoke & Carbon Monoxide Requirements

Guide to Massachusetts Smoke & Carbon Monoxide Requirements Guide to Massachusetts Smoke & Carbon Monoxide Requirements When Selling a One- or Two-Family Residence DEPARTMENT OF FIRE SERVICES Stephen D. Coan State Fire Marshal M.G.L. c 148 s. 26F - The Law Massachusetts

More information

Standard the the Raising

Standard the the Raising Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction

More information

Fire Safety Log Book

Fire Safety Log Book Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton

More information

Smoke alarms. for the home PROTECT YOUR HOME FROM FIRE

Smoke alarms. for the home PROTECT YOUR HOME FROM FIRE Smoke alarms for the home PROTECT YOUR HOME FROM FIRE Smoke alarms the essentials Smoke alarms are cheap, easy to get hold of and, used properly, they really are lifesavers! There s no excuse for not having

More information

Fire, Smoke, Heat & CO Alarms

Fire, Smoke, Heat & CO Alarms (68.52) X Product Guide Fire, Smoke, Heat & CO Alarms When Lives are at Risk, it Pays to Fit the Best! Contents Aico Introduction 3 Standards and Regulations 4-5 Alarm Sensor Types 6 Positioning, Wiring

More information

Houses in Multiple Occupation

Houses in Multiple Occupation Houses in Multiple Occupation Houses in Multiple Occupation Foreword This document has been created to both encourage and advise landlords, property owners and agencies to understand the Houses in Multiple

More information

MINERVA MX MX Virtual Multi-Sensor Detectors

MINERVA MX MX Virtual Multi-Sensor Detectors DATASHEET MINERVA MX MX Virtual Multi-Sensor Detectors Over 20 fire detection modes Tyco MX FASTLOGIC Expert algorithms MX HPO detection Algorithms Up to 250 detectors per loop Optional bi-directional

More information

Ionization alarms are best suited for rooms, which contain highly combustible material. These types of material include:

Ionization alarms are best suited for rooms, which contain highly combustible material. These types of material include: Smoke Detector University Most people are aware of the danger of fire but are unaware of the fatality of smoke. More people die from breathing smoke than by burns. In fact, deaths from smoke inhalation

More information

Analogue addressable devices

Analogue addressable devices Discovery Analogue addressable devices from Channel Safety Systems Discovery Analogue addressable devices Discovery is a range of high-specification, intelligent fire detectors that are developed to meet

More information

RHP SERVICES: INFORMATION FOR LANDLORDS AND PROPERTY OWNERS

RHP SERVICES: INFORMATION FOR LANDLORDS AND PROPERTY OWNERS RHP SERVICES: INFORMATION FOR LANDLORDS AND PROPERTY OWNERS Types of Property We are looking for licensed houses in multiple occupation (HMOs), studio, one, two, three four and five bedroom homes. RHP

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you

More information

Diocese of St Albans Diocesan Advisory Committee Advisory Leaflet 40. Fire Alarm Systems. A short guide to fitting them in Churches and Church Halls

Diocese of St Albans Diocesan Advisory Committee Advisory Leaflet 40. Fire Alarm Systems. A short guide to fitting them in Churches and Church Halls Diocese of St Albans Diocesan Advisory Committee Advisory Leaflet 40 Fire Alarm Systems A short guide to fitting them in Churches and Church Halls Introduction The majority of churches will not need to

More information

10 YEAR LIFE SMOKE ALARM

10 YEAR LIFE SMOKE ALARM User Manual 10 YEAR LIFE SMOKE ALARM ST-620 Please read me as I could save your life. Please retain this user manual for future reference CONTENTS INTRODUCTION 2 ALARM SMART SILENCE 11 AUTOMATIC POWER

More information

Smoke Alarm Performance in Residential Structure Fires

Smoke Alarm Performance in Residential Structure Fires U.S. Fire Administration TOPICAL FIRE RESEARCH SERIES Volume 1, Issue 15 March 2001 (Rev. December 2001) Smoke Alarm Performance in Residential Structure Fires FINDINGS S Smoke alarms save lives and money.

More information

How To Comply With The Loss Prevention Certification Board

How To Comply With The Loss Prevention Certification Board Loss Prevention Standard LPS 1014: Issue 5.3 This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information purposes only. Its use for testing, assessment,

More information

Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm Systems

Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm Systems Thames House, 29 Thames Street Kingston upon Thames, Surrey, KT1 1PH Phone: +44 (0) 8549 5855 Website: www.fia.uk.com Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm

More information

Property Accreditation Standards 2014/2015

Property Accreditation Standards 2014/2015 Property Accreditation Standards 2014/2015 Promoting responsible renting of student housing in the city of Southampton Letting period 1st July 2014 to 30th June 2015 Version 1, 10/12/2013 All properties

More information

Fire detection equipment

Fire detection equipment PRODUCT CATALOG Fire detection equipment www.apollo-fire.com Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980,

More information

Product Guide for Smoke & Heat Alarms. Product Guide for Smoke & Heat Alarms. Ahead on Quality Ahead on Performance Ahead on Features

Product Guide for Smoke & Heat Alarms. Product Guide for Smoke & Heat Alarms. Ahead on Quality Ahead on Performance Ahead on Features (68.52) X Product Guide for Smoke & Heat Alarms Product Guide for Smoke & Heat Alarms Ahead on Quality Ahead on Performance Ahead on Features Stockist When Lives are at Risk it Pays to Fit the Best Aico

More information

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons Your responsibilities if you have an automatic fire alarm A handy guide for owners and responsible persons Kent Fire and Rescue Service Contents Your responsibilities if you have an automatic fire alarm

More information

Guidance for Electrical Contractors on Emergency Lighting Legislation

Guidance for Electrical Contractors on Emergency Lighting Legislation Guidance for Electrical Contractors on Emergency Lighting Legislation Issued in the interests of safety by in conjunction with the Industry Committee for Emergency Lighting ECA / ICEL Guidance For Electrical

More information

M J Spearpoint & J N Smithies Fire Research Station, Building Research Establishment, Garston, Watford, WD6 7JR, UK

M J Spearpoint & J N Smithies Fire Research Station, Building Research Establishment, Garston, Watford, WD6 7JR, UK Reference: Spearpoint M J, Smithies J N. Practical comparison of domestic smoke alarm sensitivity standards. Proc. 11 th International Conference on Fire Detection, AUBE '99, pp. 576-587, Duisburg, Germany,

More information

Smoke alarms in the home

Smoke alarms in the home CFPA-E Guideline No 10:2008 Smoke alarms in the home FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation in the European

More information

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses

More information

MUNICIPALITY OF KAZABAZUA. SMOKE DETECTORS By-Law number 07-2012

MUNICIPALITY OF KAZABAZUA. SMOKE DETECTORS By-Law number 07-2012 MUNICIPALITY OF KAZABAZUA SMOKE DETECTORS By-Law number 07-2012 Notice of motion : August 7, 2012 Publication : September 9, 2012 Adoption : November 15, 2012 Effective November 15, 2012 Resolution: 2012-09-234

More information

PUBLIC Law, Chapter 162 LD 550, item 1, 124th Maine State Legislature An Act To Protect Maine Residents from Home Fires and Carbon Monoxide

PUBLIC Law, Chapter 162 LD 550, item 1, 124th Maine State Legislature An Act To Protect Maine Residents from Home Fires and Carbon Monoxide PLEASE NOTE: Legislative Information cannot perform research, provide legal advice, or interpret Maine law. For legal assistance, please contact a qualified attorney. An Act To Protect Maine Residents

More information

Fire and Security Products and Services

Fire and Security Products and Services www.redbooklive.com Fire and Security Products and Services Making LPCB Approval work for you Not all fire and security products and services on the market can be trusted in the event of a fire or attempted

More information

Kidde Safety Europe, Mathisen Way, Colnbrook, SL3 0HB, UK. www.kiddefyrnetics.co.uk. Kidde Fyrnetics 2000 SAVE THIS MANUAL FOR FUTURE REFERENCE

Kidde Safety Europe, Mathisen Way, Colnbrook, SL3 0HB, UK. www.kiddefyrnetics.co.uk. Kidde Fyrnetics 2000 SAVE THIS MANUAL FOR FUTURE REFERENCE Battery Smoke alarm Owner s Manual 9V Interconnectable Alarms For models: 19HI, 19HILL, 29I, 29ILL, 29HI, 29HILL, Thank you for choosing a Kidde Fyrnetics alarm. Please read through our guide in full.

More information

Reducing the Risk of Fire Through Telecare Commissioning Standards. London Fire Brigade

Reducing the Risk of Fire Through Telecare Commissioning Standards. London Fire Brigade Reducing the Risk of Fire Through Telecare Commissioning Standards London Fire Brigade Sheltered Accommodation Irene - Surrey Coroner s Court 9 th May 2014 HM Coroner Richard Travers highlighted the delay

More information

1. Basic Information about your Smoke Alarm. 2. Locating your Smoke Alarm

1. Basic Information about your Smoke Alarm. 2. Locating your Smoke Alarm B14464-R3-100TY-U&C-ENG.qxd 14/3/04 6:50 AM Page 1 1. Basic Information about your Smoke Alarm A Smoke Alarm is an early warning device. Used correctly it can give you and your family valuable extra time

More information

LONDON BOROUGH OF BARKING AND DAGENHAM PRIVATE SECTOR HOUSING HMO LICENSING APPLICATION FORM GUIDANCE NOTES

LONDON BOROUGH OF BARKING AND DAGENHAM PRIVATE SECTOR HOUSING HMO LICENSING APPLICATION FORM GUIDANCE NOTES LONDON BOROUGH OF BARKING AND DAGENHAM PRIVATE SECTOR HOUSING HMO LICENSING APPLICATION FORM GUIDANCE NOTES NOTES TO PART 1 If you are the person filling in this application form, then you are the applicant.

More information

The Types of Standard 2 Guidance on the Standards 2 Changes to Legislation 2

The Types of Standard 2 Guidance on the Standards 2 Changes to Legislation 2 CONTENTS INTRODUCTION 2 The Types of Standard 2 Guidance on the Standards 2 Changes to Legislation 2 SCOTTISH CORE STANDARDS FOR ACCREDITED LANDLORDS 3 1 Communication with the Tenant 3 2 Equality Issues,

More information

Overview. Components of an alarm system Technology behind the equipment Communication Platforms Industry Terminology False Alarm Tips DSC products

Overview. Components of an alarm system Technology behind the equipment Communication Platforms Industry Terminology False Alarm Tips DSC products Basic Security 101 Overview Components of an alarm system Technology behind the equipment Communication Platforms Industry Terminology False Alarm Tips DSC products Components of an Alarm System Main Control

More information

Basic Information about your Smoke Alarm. Locating your Smoke Alarm

Basic Information about your Smoke Alarm. Locating your Smoke Alarm B10274-R4-105B-U&C-ENG 30/9/09 8:23 AM Page 1 Basic Information about your Smoke Alarm A Smoke Alarm is an early warning device. Used correctly it can give you and your family valuable extra time to escape.

More information

Kidde Safety Europe, Mathisen Way, Colnbrook, SL3 0HB, UK. www.kiddefyrnetics.co.uk. Kidde Fyrnetics 2003 SAVE THIS MANUAL FOR FUTURE REFERENCE

Kidde Safety Europe, Mathisen Way, Colnbrook, SL3 0HB, UK. www.kiddefyrnetics.co.uk. Kidde Fyrnetics 2003 SAVE THIS MANUAL FOR FUTURE REFERENCE Smoke and Heat alarm Owner s Manual 230V Interconnectable Mains Operated Alarms For models: 123I, 123/9HI, 123/9HILL, 223I, 223/9I, 223/9ILL, 223/9HI, 223/9HILL, 323/9HI, 323/9HILL Your home is protected

More information

ELECSA and the Fire Industry

ELECSA and the Fire Industry ELECSA and the Fire Industry Guide to Fire Protection and Fire Risk Assessment schemes www.elecsa.co.uk 80% Black 100% Black Section 1: What are the opportunities in the Fire Industry? Regulation of the

More information