1 Linton House Highgate Rd London NW5 1RS Fiire Riisk Assessment Common parts of Ironworks 58 Dace Road London E3 2NX 16 th July 2009 Common Parts Ironworks, 58 Dace Road, London E3 2NX 1
2 Contents Section Topic Page 1 Terms of Reference 3 2 Duties of the Responsible Person 4 3 Background Information 4 4 Description of Premises 5 5 Sources of Ignition 6 6 Sources of Fuel 7 7 Building Design and Layout 7 8 Those at Risk (Life Risk) 8 9 Procedures, Training and Recording 9 10 Fire Detection and Warning 9 11 Means of Fighting Fire 9 12 Means of Escape Points of Contact Fire Risk Assessment & Management Action Plan 12 Appx. A Suggested Electrical Inspection / Testing Criteria 19 Appx B Staff Inspection Diagram (Portable Electrical Appliances) 20 Common Parts Ironworks, 58 Dace Road, London E3 2NX 2
3 1 Terms of Reference 1.1 This report and assessment has been completed by Ace Consultancy at the request of Ringley Ltd., to inspect, review and assess existing arrangements for managing fire safety in compliance with The Regulatory Reform (Fire Safety) Order 2005 for the communal areas of the 58 Dace Road, Bow premises. 1.2 The report provides a general review of existing fire precautionary arrangements, with recommendations to ensure compliance with fire safety legislation and for general fire precautions to be effectively managed. 1.3 Recommendations, contained in the Risk Assessment have been given Priority Ratings to assist the Responsible Person with planning. 1. Indicates a serious contravention requiring immediate action; 2. Indicates a deficiency requiring action within a month 3. Indicates a less serious deficiency requiring action within two months 4. Indicates where improvements could be made to further enhance good practice. 1.4 Responsibility for the implementation of recommendations contained in the Fire Risk Assessment Action Plan rests with the Responsible Person (see 2 below). Failure to take proper management responsibility can result in the prosecution of an employer, building owner, or occupier. 1.5 When compiling this report references were made to the requirements and principles of the: o The Regulatory Reform (Fire Safety) Order 2005 o The Management of Health and Safety at Work Regulations 1999 o The Health and Safety (Safety, Signs and Signals) Regulations 1996 o The Workplace (Health, Safety and Welfare) Regulations The assessment does NOT include private living accomodation 2 Duties of the Responsible Person 2.1 The Responsible Person is the employer if the workplace is to any extent under his control. Where this is not the case the Responsible Person is the person who has control of the premises (as occupier or otherwise) in connection with the carrying on of a trade, business or other undertaking. If the person in control does not have control in connection with the carrying on of a trade, business or other undertaking then the owner is the Responsible Person. Common Parts Ironworks, 58 Dace Road, London E3 2NX 3
4 2.2 The Responsible Person has a duty to: o take general fire precautions o carry out, record and implement the conclusions of a risk assessment o equip the premises with appropriate fire fighting equipment, detectors, alarms, suitable emergency routes and exits o take special precautions where dangerous substances are present to eliminate or reduce the fire risk o take particular matters into account when employing young people and identifying in the risk assessment those people especially at risk o ensure that employees, and others at the premises have relevant fire safety information o ensure employees have adequate safety training and understand the evacuation procedures o nominate a sufficient number of competent persons to assist in implementing preventative and protective measures, including safety drills o maintain all fire fighting equipment, and o review the risk assessment when necessary 3 Background Information 3.1 The Regulatory Reform (Fire Safety) Order replaces the Fire Precautions (Workplace) Regulations 1997 and the Fire Precautions Act 1971, in relation to fire safety in non-domestic premises and imposes a general duty to take such fire precautions as may be reasonably required, to ensure premises are safe for the occupants and those in the immediate vicinity. 3.2 The aim of the Regulatory Reform (Fire Safety) Order 2005 is to ensure that persons in control of premises i.e. owners, managers, occupiers, or employers take a risk assessment approach to fire safety. 3.3 The Regulatory Reform (Fire Safety) Order 2005 requires a Fire Risk Assessment is completed to ensure: o a fire can be detected in a reasonable time and people warned o people can vacate the building safely o those occupying the building know what to do if there is a fire o fire safety equipment is tested and maintained o a decision is taken with regard to the course of action required to address any defects or deficiencies. 3.4 The Assessment is a proactive way of addressing the following areas by: o identifying hazards and assessing the risks: o formulating and implementing control measures to minimise risks: o informing, instructing and training personnel: o monitoring conditions to ensure that the fire safety measures are being correctly implemented and maintained: Common Parts Ironworks, 58 Dace Road, London E3 2NX 4
5 o reviewing and revising the assessment if there are significant changes that could affect existing fire safety precautions. 3.5 The common areas of the building have been assessed for: o Sources of ignition o Sources of Fuel o Building Design and Layout o Those at Risk (Life Risk) o Procedures, Training and Recording o Fire Detection and Warning o Means of Fighting Fire o Means of Escape all of which can contribute to the probability of a fire occurring, the anticipated fire severity, the ability to resist the spread of fire and smoke and the danger to people in and around the building. 3.6 Sections 5 to 12 of the report identify basic fire precaution requirements and should be read in conjunction with recommendations listed in Section 14 - The Fire Risk Assessment / Action Plan. 3.7 Recommendations are based on the observations as they appeared at the time of inspection on Thursday 16 th July Brief Description of the Premises 4.1 The 58 Dace Road Complex consists of a main 8 storey building (ground car parking area and 8 upper floors) and three 5 storey interconnecting wings accommodating a total of some 79 self contained flats. Access to the redeveloped factory site is via electronically controlled gates from Dace Road between two original warehouse buildings. Entrance to the flats is via a main electronically controlled entrance into the main block lift lobby and stairway. Fire escape stairways terminate with gated egress points in the car park. The main entrance doors, fire escape gates and site entrance gates fail safe when the alarm is activated. A stand alone building containing the security office and electrical substation is located in the vicinity of the car parking area. View from across the canal Gated Entrance between original buildings Common Parts Ironworks, 58 Dace Road, London E3 2NX 5
6 5 Sources of Ignition 5.1 The hazards posed by ignition sources include: o Heating Boilers and Appliances o Cooking Equipment o Electrical Hazards o Contractors o Smoking Materials o Arson 5.2 All places of work are now designated No Smoking areas. 5.3 Electrical hazards account for a large number of fires. However, it is Assessor s opinion that this relatively newly built complex is being effectively managed. There is no reason to soppose that the electrical system is anything but fully compliant. 5.4 To ensure compliance with the requirements of the IEE Wiring Regulations the system should be tested by a NICEIC electrician every 5 years and the results recorded. No evidence was requested at the time of inspection to confirm whether or not this requirement is being met. 5.5 Portable Electrical Appliances (including Extension Leads) should be tested in accordance with HSE recommendations, (See Appendix A), labelled, the results recorded and Test Certificates kept readily available for inspection. At the time of inspection the only appliances appeared to be in the areas used by the Security Officer, namely the Security Office and the Electrical Intake/Services Utility Room. 5.6 No gas boilers or appliances were seen during the inspection of the communal areas. Privately owned gas boilers are not covered by the Reform Order. However, any gas boilers or appliances which are the property of the building owner/landlord must be serviced in accordance with requirements. 5.7 Systems should be in place to monitor contractors if/when employed to carry any maintenance or remedial work likely to involve processes requiring heat or flames. These may include incineration, welding, soldering, flame cutting or frictional heat, etc. 5.8 Arson is always a potential problem with 40% of all non-domestic fires being started deliberately. Residents should be asked to demonstrate vigilance by monitoring internal and external areas and reporting any concerns. At the time of inspection there were no areas of concern with regards to arson either internally or externally due to the part-time attendance of the Security Officer, the electronically controlled security gates and entrance and the CCTV coverage. Common Parts Ironworks, 58 Dace Road, London E3 2NX 6
7 6 Sources of Fuel 6.1 Combustible and flammable materials may serve as a source of fuel within buildings. Materials either stored or in use, i.e. fabrics, furnishings, furniture and waste can all contribute to fuel a fire and should therefore be isolated from sources of ignition. 6.2 At the time of inspection all communal areas of the complex, with the possible exception of the Electrical Intake Room were completely devoid of any combustible materials. 6.3 At the time of inspection the ground level car parking facility beneath the building was clean, tidy and well organised. 6.4 Post is delivered in bulk to the security office where it is sorted by flat numbers and placed it in the occupants individual metal post boxes located under the building in the parking area. Large items are retained in the security office. 7 Building Design and Layout 7.1 The design and layout of a building is required to ensure: o satisfactory provision of means of giving an alarm of fire and a satisfactory means of escape; o fire spread over the internal linings of walls is inhibited; o the stability of the building in the event of fire by having a sufficient degree of separation within buildings and between adjoining premises and inhibit the unseen spread if fire and smoke in concealed spaces in buildings 7.2 Here the main common stairway is a spiral design within a fire resisting enclosure/lift lobby and discharge directly to a final exit. Alternative escape staircases are located on external communal balconies and discharge into the ground level car parking area. 7.3 Doors leading onto the staircase enclosure are fully compliant fire doors and at the time of inspection were all fully functioning and locating correctly. Main Staircase/Lift Lobby Smoke Ventilation Dry Risers Common Parts Ironworks, 58 Dace Road, London E3 2NX 7
8 7.4 The building has smoke ventilation which is activated manually or automatically on the alarm. Dry riser points are located on each floor within the lift lobby/staircase enclosure 7.5 It can only be assumed that, based on the standard of construction throughout, compartment walls, floors and fire stopping barriers are fully compliant with building regulations. The age and quality of the building suggest that the lift meets requirements to qualify as a fire fighting lift for use under the direct control of the fire and rescue service in fighting a fire All exit doors and gates are designed to fail safe. 8 Those at Risk (Life Risk) 8.1 Arrangements must be made to ensure that in an emergency everyone can evacuate to a place of safety. Particular attention should be paid to: Disabled people Children Young persons Employees Contractors. 8.2 The spiral staircases could prove difficult for elderly and disabled people to negotiate, particularly in an emergency. However, if, as suspected, the lift can be used by the fire and rescue service to aid evacuation, any risk to these people will be greatly reduced. 8.3 The design and layout of the building complex provides good access and egress for the able bodied. 9 Procedures, Training and Recording 9.1 The Regulatory Reform (Fire Safety) Order 2005 requires that procedures are in place to ensure: o emergency escape routes remain free from obstructions o monitoring and servicing arrangements are in place for fire extinguishers, fire detection equipment, emergency lights and fire doors o doors requiring to be kept shut or locked shut, remain so o electrical systems and portable appliances are checked Recommendations regarding these requirements are listed under their appropriate headings in the Fire Risk Assessment and Action Plan Spreadsheet - Section 14. Common Parts Ironworks, 58 Dace Road, London E3 2NX 8
9 10 Fire Detection, Warning and Emergency Lighting 10.1 Current building regulations require all new flats to be provided with detectors linked for a general alarm. The regulations also require that all escape routes to have adequate artificial lighting and escape lighting Smoke detectors are installed in all communal areas visited at the time of inspection. External detector indicator lights are fitted to enclosed areas such as the electrical cupboards and the electrical intake/services room. In addition manual call points are located on each landing The fire panel is located in the main entrance hall Emergency and escape lighting is standard throughout the complex 11 Means of Fighting Fire 11.1 No fire fighting equipment is currently available. Whilst it is generally recognised that fire fighting equipment can reduce the risk of a small fire developing into a large one, much depends on the person using the equipment being familiar with the operating instructions. The design and construction of the building to adequately resist the spread of fire and smoke suggests that the provision of fire fighting equipment for use by inexperienced people could prove detrimental rather than beneficial Dry risers are located in the staircase enclosure on each floor of the main building 12 Means of Escape 12.1 The provision for means of escape for flats are based on the assumption that: o the fire is generally in a flat o there is no reliance on external rescue o there is a high degree of compartmentation o the materials used in the common parts of the building should prevent the spread of fire beyond the immediate vicinity Common Parts Ironworks, 58 Dace Road, London E3 2NX 9
10 12.2 At the time of inspection the main building escape routes were free of obstructions. However, on the external wings of the complex communal balconies from the rear exits of the flats were obstructed by the occupants garden ornaments, tables and chairs and one or two privacy screens. These balconies offer an alternative escape should a fire occur in the front of a flat, which suggests that they should remain clear of any major or permanent obstructions Some external decking is beginning to warp creating a potential tripping hazard. Warped Decking Rear Balcony - Obstructions 13 Points of Contact Should you require additional information or clarification contact: Ace Fire Consultancy, Linton House, 39/51 Highgate Road, Kentish Town, London NW5 1RS Dave Ritchie Tel: Mobile: dave@aceasbestos.com Vic Warren Tel: Mobile: vic.warren@blueyonder.co.uk The Fire Protection Association London Road Moreton in Marsh Gloucestershire GL56 0RH Tel: Web: For information about health and safety: HSE Infoline Tel: hse.infoline@natbrit.com Common Parts Ironworks, 58 Dace Road, London E3 2NX 10
11 14 FIRE RISK ASSESSMENT & ACTION PLAN SPREADSHEET Communal Areas, Ironworks, 58 Dace Road, Bow, London E3 2NX (Note: Item numbers correspond to with Section in the Covering Report) Recommendations based on conditions as they appeared at the time of inspection on Thursday 16 th July 2009 Item Shortfall/Concern Present Risk Recommendation Target Date or Priority Revised Risk Action by Completion Date and Signature SOURCES OF IGNITION No evidence requested at the time of inspection to confirm the fixed electrical installation is being tested in accordance with requirements by a NICEIC approved electrician and the results recorded Low o Ensure electrical inspections and testing is being (or due to be) carried out in accordance with requirements. o Ensure evidence of fixed electrical testing is readily available for inspection by H&S and Fire Enforcement Officers Priority 2 Low Responsible Person Electrical portable appliances should be tested in accordance with HSE recommendations. (Portable electrical appliances used by the Security Officer i.e. Microwave, Heater etc. Low o Create an inventory of portable electrical appliances, including extension leads, o Ensure all electrical appliances and extension leads are correctly fused o Test appliances in accordance with HSE recommended intervals. (See Report Appendix A) o Ensure evidence of portable appliance test certificates are kept readily available for inspection by H&S and Fire Enforcement Officers Priority 3 Low Responsible Person Common Parts Ironworks, 58 Dace Road, London E3 2NX 11
12 5.6.1 Maintenance of Gas Boilers and appliances. Low o Ensure that any gas boilers owned by the building owner or landlord are serviced annually by a registered fitter o Servicing /maintenance records should be kept readily available for inspection by Fire and H&S Enforcement Officers. Priority 3 Low Responsible Person Systems should be in place to monitor contractors if/when employed to carry any maintenance or remedial work likely to involve processes requiring heat or flames. High o No work involving heat or flames should be allowed without a Permit to Work. o Contractors should provide method statements to ensure risk of fire is reduced to the lowest possible level for any maintenance or remedial work requiring heat or flames. o Contractors should be monitored to ensure compliance, whenever possible Priority 1 (When required) Med Responsible Person Arson Low o Keep the Bin Store locked especially when there is no Security Officer on site. o Monitor Parking Areas to ensure the existing good standard of housekeeping are maintained. On going Low Responsible Person SOURCES OF FUEL - COMBUSTIBLE AND FLAMMABLE MATERIALS Combustible Materials in the Electrical Intake/ Services Room/CCTV Monitoring Room Med o Monitor the area to ensure paperwork and other combustible materials remain at a minimum. o Monitor all communal areas to ensure the existing high standard of housekeeping is maintained On going Low Responsible Person Common Parts Ironworks, 58 Dace Road, London E3 2NX 12
13 BUILDING DESIGN AND LAYOUT Fire doors Low o Maintenance schedules should be established to ensure doors are regularly monitored and remain in full working order Smoke ventilation Low o The smoke ventilation system should be monitored and serviced to ensure it remains operational o Testing and servicing records should be kept readily available for inspection by Fire and H&S Enforcement Officers Fire Fighting Lift Low o Confirm whether the lift is certified as a Fire Fighting Lift. o If the lift is not a Fire Fighting Lift fix Do not use in the event of fire notices adjacent to lift call buttons Priority 2 Low Responsible Person Priority 3 Low Responsible Person Priority 2 Low Responsible Person THOSE AT RISK People with special needs, the elderly and children should always be considered a greater risk than the rest of the population Med o Implement recommendations listed under other headings. Low Common Parts Ironworks, 58 Dace Road, London E3 2NX 13
14 PROCEDURES, TRAINING AND RECORDING Fire precautions information for occupants and contractors visiting the premises for servicing and/or maintenance purposes Low o Employees and Contractors should be provided with appropriate information to ensure they are fully conversant with fire procedures for their areas of work o Consider (if not already provided) including basic fire safety information in Sale/ Lease/Tenant Agreements. Priority 3 Priority 4 Low Responsible Person FIRE DETECTION, WARNING & EMERGENCY LIGHTING Fire Detection and Alarm System Low o Ensure the fire alarm system is serviced and maintained by a competent person every six months o The manual system should be tested weekly using a different call point on each occasion. o Records of all servicing and testing will need to be kept readily available for inspection by Fire and H&S Enforcement Officers. Priority 3 Low Responsible Person Emergency/escape lighting Low Low o Emergency Lights should be, Visually Inspected Weekly: to confirm Indicator Lights are illuminated. Tested Monthly: to confirm they illuminate. Tested every Six Months: to ensure they operate for one third of their rated duration and Tested Annually: to ensure they operate for their full rated duration. Priority 3 Low Responsible Person Common Parts Ironworks, 58 Dace Road, London E3 2NX 14
15 MEANS OF FIGHTING FIRE Dry Risers Low o Ensure all Dry Riser Points are labelled Priority 2 Low Responsible Person MEANS OF ESCAPE Obstructions on rear exit communal balconies. Med o Confirm whether or not the Communal Rear Balconies are designated Escape Routes. o If, as suspected, rear balconies are designated escape routes inform occupants accordingly regarding obstructions o Existing and future occupants should be informed of their responsibilities regarding fire precautions. Priority 3 Low Responsible Person Warped decking on communal walkways Med o Monitor decking for tripping hazards Priority 2 Low Responsible Person THE RESPONSIBLE PERSON (see 2.1 for definition) IS ULTIMATLY RESPONSIBLE FOR THE IMPLEMENTATION OF THE ACTION PLAN The assessment should be amended as recommendations are completed. Implementation of the recommendations should ensure compliance with the Regulatory Reform (Fire Safety) Order 2005 Implementation of these control measures will rate this building LOW RISK. ORIGINAL REPORT/ASSESSMENT COMPLETED BY: Vic Warren CMIOSH 16 th July 2009 Common Parts Ironworks, 58 Dace Road, London E3 2NX 15
16 Appendix A HSE s Electrical Inspection/Testing Criteria All portable electrical equipment should be inspected and tested as follows: Equipment/environment User checks Formal visual inspection Combined inspection and testing* Information technology: e.g. desktop computers, VDU screens No Annually No if double insulated - otherwise up to 5 years Photocopiers, fax machines: (rarely moved) No Annually No if double insulated - otherwise up to 5 years Double insulated equipment: NOT hand-held. Moved occasionally, e.g. fans, table lamps, slide projectors No Annually No Double insulated equipment: HAND-HELD e.g. some floor cleaners, electric mowers, electric drills Annually (more often if subject to heavy use) Annually Earthed equipment (Class I): e.g. all portable equipment with 3 core cables such as: electric kettles, some floor cleaners, irons, steamers, kitchen equipment etc Annually Annually Refrigerators, freezers No Annually 1-5 years, depending on environment Detachable Cables (leads) and plugs connected to the above. Annually 1-5 years depending on the type of equipment it is connected to Extension leads (mains voltage) The above list is not definitive. If in doubt contact local H&S Enforcing Officer. THE REQUIREMENTS LISTED ABOVE APPLY EQUALLY TO CONTRACTORS AND OTHERS WORKING ON YOUR PREMISES Common Parts Ironworks, 58 Dace Road, London E3 2NX 16
17 Appendix B INSPECTION DIAGRAM To be used before using any PORTABLE ELECTRICAL APPLIANCES The Cable Is it in good condition, with no sign of damage? No The Casing Is it in good order, (not cracked or damaged)? The Plug Withdraw from use and report to line manager Is it in good order with no sign of damage and the cable secure? The Label Is the test date valid? Go ahead and use Common Parts Ironworks, 58 Dace Road, London E3 2NX 17
18 Your Safety is Our Concern! Reg Office: 309a Kentish Town Road, London NW5 2TJ Common Parts Ironworks, 58 Dace Road, London E3 2NX 18
FIRE RISK ASSESSMENT SW13 0HA
FIRE RISK ASSESSMENT at Carmichael Court Grove Road London SW13 0HA ON BEHALF OF Farrar Property Management Date of assessment: 14/01/2013 Recommended review date: January 2015 CONTENTS 1.0 INTRODUCTION
More informationFire Safety Log Book
Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton
More informationThe terms hazard and risk are often used, which we define as the following:
Fire Safety Last updated in October 2010 This information sheet aims to give safety reps a basic understanding of fire safety and fire risk assessments under the current law. More detailed information
More informationFor use by landlords of small premises Premises Address
fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):
More informationFIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT This template has been provided to assist the Responsible Person with the preparation of a Fire Risk Assessment and is not intended for commercial
More informationFire precautions in dwellings. Private sector housing Providing homes building communities
Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared
More informationFIRE SAFETY RISK ASSESSMENT
FIRE SAFETY RISK ASSESSMENT For small single occupancy premises Premises Hertco Ltd ACME House, Old London Road, Hertford SG17 7LD Fire Safety Risk Assessment for Small Premises Introduction Regulatory
More informationFor use by landlords of small premises Premises Address
fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):
More informationHow To Write A Fire Risk Assessment
Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes
More informationGrasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment
Grasshoppers Rugby Football Sports and Social Club The Fire Risk Assessment Revision 1 Dated: 15th February 2013 CONTENTS 1. PREMISES DETAILS 2. PREMISES PLAN 3. HAZARDS 4. HISTORY 5. MITIGATING THE EFFECTS
More informationUCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS
Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern
More information1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety.
Management Checklist 1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety. 2. Fire Hazard and Risk Assessment. Use
More informationFire Safety Risk Assessment Checklist for Residential Care Premises
Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or
More informationAction required (Please tick) If you answered YES, record Action Points at STEP 4
RECORD OF FIRE SAFETY RISK ASSESSMENT Building Name & Use: Address: Postcode: Name of person(s) with fire safety duties: Name and contact details of assessor: Date of Assessment: 6 th February 2011 Laurel
More informationUPP Residential Services Fire Risk Assessment
UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This
More informationLondon Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords
London Borough of Barnet Fire Safety in Houses in Multiple Occupation A Guide to Landlords March 2016 Contents Introduction p.3 Summary of main requirements p.3 Fire Safety Precautions p.4 Protecting the
More information1.1. EMERGENCY PROCEDURE On discovering a fire or being informed of an emergency;
Fire Action Plan FIRE ACTION PLAN SEStran aims to provide and maintain safe & healthy working conditions, equipment and systems of work for all our employees, and to provide such information, training
More informationCITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY
CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY This policy was written in July 2014 and will be agreed by the Board of Governors in October 2014. To be reviewed by June
More informationFire Risk Assessment For Simple Premises
Fire Risk Assessment For Simple Premises Responsible Person (Employer or other person having control of the relevant premises) Company / Premises Name Address of Premises Postcode Primary Use of Premises
More informationNEW FIRE SAFETY LEGISLATION
NEW FIRE SAFETY LEGISLATION The Fire and Rescue Services (Northern Ireland) Order 2006 The Fire Safety Regulations (Northern Ireland) 2010 Fire Safety legislation changed A SHORT GUIDE TO MAKING YOUR PREMISES
More informationLee Baron FIRE RISK ASSESSMENT
FIRE RISK ASSESSMENT, 13/21 Cantelupe Road, East Grinstead Prepared for: Lee Baron 7 Swallow Place Oxford Circus London W1B 2AG Prepared by: Violet McIntyre CMIOSH William Martin Compliance Solutions Limited
More informationFIRE DETECTION AND ALARM SYSTEMS
HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some
More informationFire Safety Requirements for Child Care Centre
Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,
More informationFIRE RISK ASSESSMENT
The Regulatory Reform (Fire Safety) Order 2005 FIRE RISK ASSESSMENT Employer or other responsible person Name of Premises Address Post Code Telephone N o Name of Assessor(s) Date of Assessment Date of
More informationFIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie
FIRE SAFETY REGISTER Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie 1 CONTENTS Section Title Page 1.0 Introduction 3 2.0 Guidance for the completion
More informationRegulatory Reform (Fire Safety) Order 2005. A short guide to making your premises safe from fire
Regulatory Reform (Fire Safety) Order 2005 making your premises safe from fire A s h m a o k r i t n gu g id y e o r to u premises safe from fire Introduction This booklet provides simple and practical
More informationFire Policy and Procedures. Cañada Blanch Spanish School
Fire Policy and Procedures Cañada Blanch Spanish School SUMMARY 1. Introduction (p. 3) 2. Roles and responsibilities (p. 3) -- Headteacher -- Fire Team -- All staff -- Contractors 3. Fire procedures (p.
More informationContents. 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4
Contents 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4 2. Scope and Application 2.1 Scope of the Guide 5 2.2 Premises to which the
More informationFire Risk Assessment Safety Checklist
Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory
More informationFire Safety Risk Assessment
1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept
More informationFire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1
Network Building Fire Safety Management Plan & Fire Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting
More informationRisk Management Guidelines
Fire Prevention on Construction Sites The Joint Code of Practice on the Protection from Fire of Construction Sites and Buildings Undergoing Renovation Introduction In response to increasing numbers and
More informationTo promote and protect the private residential landlord. Fire Safety Logbook. Information. Advice. Support. Services START DATE:
To promote and protect the private residential landlord Fire Safety Logbook Information Advice Support Services START DATE: PROPERTY DETAILS Property Address: Post Code: Licence Holder/Manager: CONTACT
More informationFire risk assessment a guide for businesses
Fire risk assessment a guide for businesses Disclaimer Cornwall Fire and Rescue Service provide this guide to assist businesses to improve fire safety in their premises, but stress the person completing
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005. Fire Risk Assessment. 145 Drury Lane Covent Garden London WC2B 5TA
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 Fire Risk Assessment 145 Drury Lane Covent Garden London WC2B 5TA Annex A (informative) Model pro-forma for documentation of the fire risk assessment for premises
More informationFACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
More informationGreater Manchester Fire and Rescue Service
Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY
More informationFURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS
Fire Safety Technical Guide FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS 1.0. Introduction 1.1. Furniture and furnishings may significantly increase fire spread in rooms and those circulation spaces,
More informationLANCASTER UNIVERSITY. MANUAL OF SAFETY Section 29 POLICY ON FIRE RISK ASSESSMENTS
LANCASTER UNIVERSITY MANUAL OF SAFETY Section 29 POLICY ON FIRE RISK ASSESSMENTS 1 Introduction 1.1 The Fire Precautions (Workplace) Regulations, require the University to carry out fire risk assessments
More informationFire Risk Assessment for Simple Premises Guidance Notes
Fire Risk Assessment for Simple Premises Guidance Notes The UK s national fire safety organisation Protecting people, property, business and the environment Introduction This guide and the accompanying
More informationBastille Court 2 Paris Garden London SE1 8ND Telephone: 020 7902 5314 Fax: 020 7902 5301 E-mail: training@thefpa.co.uk Web: http://www.thefpa.co.
Bastille Court 2 Paris Garden London SE1 8ND Telephone: 020 7902 5314 Fax: 020 7902 5301 E-mail: training@thefpa.co.uk Web: http://www.thefpa.co.uk Fire Risk Assessment Course Health & Safety at Work Inspectorate,
More informationFIRE SAFETY GUIDANCE NOTE Regulatory Reform (Fire Safety) Order 2005
FIRE SAFETY GUIDANCE NOTE Regulatory Reform (Fire Safety) Order 2005 Number: GN66 This Guidance Note provides advice on the requirements of the Regulatory Reform (Fire Safety) Order 2005 and how to complete
More informationFire Safety logbook
Raising Awareness Reducing Risk CHANGE THIS TITLE TO COMPANY NAME Property / Business Name Address Line 1 This Log book should be kept up to date and be made available for inspection by the Fire Authority
More information1. Introduction 3. 2. Scope and Application 5
Contents 1. Introduction 3 1.1 Reason for this Guide 1.2 Interpretation 1.3 Principles of fire safety 1.4 Legal provisions 2. Scope and Application 5 2.1 Scope of the Guide 2.2 Premises to which the Guide
More informationHousing Act 2004 Regulatory Reform (Fire Safety) Order 2005 Fire Safety in Purpose-Built Flats Have you taken sufficient action?
Housing, Culture & Enterprise Private Sector Housing Hove Town Hall (Room 217) Norton Road Hove BN3 3BQ Telephone: (01273) 293156 Fax No: (01273) 292452 Email: psh@brighton-hove.gov.uk D G Prichard QFSM,
More informationCONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
More informationFIRE RISK ASSESSMENT WORKED EXAMPLE
FIRE RISK ASSESSMENT WORKED EXAMPLE 1 PREMISES PARTICULARS BE-INT05 Premises Name S M Enterprises Address Small Place Medium Road Anywhere Tel no: 01234 567890 Date of Risk Assessment 1 st July 2011 Use
More informationSPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS
Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses
More information1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS
Fire Risk assessment 1.0 APPOINTMENTS 1.1 Responsible Person. In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO) the School s Head, Mrs J M Miles is appointed as the Responsible Person
More informationSt Peter s College ELECTRICAL SAFETY. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
St Peter s College ELECTRICAL SAFETY References: A. Peninsula Business Services Guidance Note 4-1, Electrical Safety. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
More informationBRO Roles & Responsibilities Form Page 1 of 9
BRO Roles & Responsibilities Form Page 1 of 9 This document must identify the (s) and/or the person delegated to undertake the duties listed below. These duties are required by legislation and/or Council
More informationENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III. HOUSES IN MULTIPLE OCCUPATION Space Standards
ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III HOUSES IN MULTIPLE OCCUPATION Space Standards ADOPTED HOUSING STANDARDS:CATEGORY F HOUSES Houses within this category would be of a low priority
More informationNORTH BIRMINGHAM ACADEMY
NORTH BIRMINGHAM ACADEMY FIRE AND EVACUATION PROCEDURES FIRE DRILLS: These are carried out once a term. Observations and details of each drill are recorded in the logbook, which is kept by the Assistant
More informationRESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK MARIE CURIE SCEAUX GARDENS ESTATE LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
More informationRHP SERVICES: INFORMATION FOR LANDLORDS AND PROPERTY OWNERS
RHP SERVICES: INFORMATION FOR LANDLORDS AND PROPERTY OWNERS Types of Property We are looking for licensed houses in multiple occupation (HMOs), studio, one, two, three four and five bedroom homes. RHP
More informationIFE Level 4 Certificate in Fire Science and Fire Safety (HL)
IFE Level 4 Certificate in Fire Science and Fire Safety (HL) Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the prevention and detection of fire in premises and
More informationMaintaining portable electric equipment in low-risk environments
Maintaining portable electric equipment in low-risk environments Introduction This leaflet explains the simple and sensible precautions that need to be taken to prevent danger from portable or movable
More informationFire Safety Challenges and Solutions. Claire Guise Health and Safety Manager
Fire Safety Challenges and Solutions Claire Guise Health and Safety Manager Marie Curie Cancer Care (UK Wide) 9 Palliative Care Hospices (owned) Facilities Manager in place (NEBOSH General Certificate
More informationPRACTICAL FIRE SAFETY GUIDANCE FOR EDUCATIONAL AND DAY CARE FOR CHILDREN PREMISES
PRACTICAL FIRE SAFETY GUIDANCE FOR EDUCATIONAL AND DAY CARE FOR CHILDREN PREMISES Revised February 2008 The guidance in this document has been jointly produced by the Scottish Government s Police and Community
More informationCourse of Construction Questionnaire
Course of Construction Questionnaire CLIENT DETAILS Broker: Contact: Insured s name: Policy number: Address undergoing works: Insured s contact phone number: 1) Name and address of Contractor: 2) Contractor
More informationQ The Quoin Consultancy
Q The Quoin Consultancy Catholic Church of the Sacred Heart & St. John the Evangelist London Road, Bushey Hertfordshire WD23 1BA FIRE RISK ASSESSMENT CONTENTS REVIEW LOG SECTION 1.0 - INTRODUCTION 1.1
More informationFire Risk Assessment Report
Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Site Contact Date of Assessment Date of Report St Augustines Priory Main School Building Hillcrest Rd, London
More informationFIRE RISK ASSESSMENT. The Workplace Fire Precautions Legislation
FIRE RISK ASSESSMENT The Workplace Fire Precautions Legislation The Fire Precautions (Workplace) Regulations 1997 The Fire Precautions (Workplace)(Amendment) Regulations 1999 The Management of Health and
More informationFIRE RISK ASSESSMENT PRINCIPLES A GUIDE FOR LICENSED PREMISES
NFG27 FIRE RISK ASSESSMENT PRINCIPLES A GUIDE FOR LICENSED PREMISES The Workplace Fire Precautions Legislation brings together existing Health & Safety and Fire Legislation to form a set of dedicated Fire
More informationGENERAL FIRE SAFETY TERMS & DEFINITIONS
UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:
More informationProposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company
RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing
More informationSafety in Offices and other General Areas
Safety in Offices and other General Areas 1. INTRODUCTION This document covers health and safety in offices and other 'general areas' including corridors, stairs, entrances, small kitchens and rest areas.
More informationFLA S FIRE SAFETY INITIATIVE
Improving Workers Lives Worldwide FLA S FIRE SAFETY INITIATIVE Preventing fires and saving lives by empowering workers and factory managers SCENARIO 1 OCCURS AT FACTORY ABC, WHICH HAS NOT IMPLEMENTED NECESSARY
More informationFIRE SAFETY RECORD OF TESTS LOGBOOK
FIRE SAFETY RECORD OF TESTS LOGBOOK PREMISES ADDRESS: Responsible person AN INTRODUCTION TO YOUR LOG BOOK The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person for a premises to
More informationRESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK CASTLEMEAD CAMBERWELL ROAD LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
More informationFire safety advice for landlords
YOU CAN PREVENT IT Fire safety advice for landlords Introduction Each year there are over 50,000 fires in dwellings in the UK. These result in around 300 hundred fatalities and several thousand serious
More informationGatehouse School. Fire Risk Assessment
Gatehouse School Fire Risk Assessment DATE: 6th October 2014 REVIEW DATE: October 2015 INDEX 1. Premises Particulars 2. General Statement of Policy 3. Management Systems 4. General Description of Premises
More informationFIRE SAFETY PRECAUTIONS
FIRE SAFETY PRECAUTIONS LOG BOOK PLEASE KEEP AVAILABLE 1 Business Name Premises Information Building / Unit Number Property Name Road: (Address Line 1) (Address Line 2) Locality: Town: Post Code: Name
More informationISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone
More informationNorthern Ireland Housing Executive: HMO Fire Safety Guide
Northern Ireland Housing Executive: HMO Fire Safety Guide Contents Equality Statement 5 Houses in Multiple Occupation (HMOs) means of escape in case of fire and other fire precautions 6 1.0 Introduction
More informationLandlord/Agent Code of Conduct
Landlord/Agent Code of Conduct Commitment to this is a requirement of the Home Stamp accreditation scheme The Home Stamp Code of Conduct aims to provide guidance and advice regarding the management of
More informationSummary of Preliminary Assessment on Structural, Fire and Electrical Safety
Name of the Factory Address of the Factory Present Status of the Factory Structural Assessment Conducted by : Galaxy Stitch Ltd. : BSCIC Industrial Estate, Plot no. A102, Tongi Gazipur Bangladesh : Under
More informationFire Safety Log Book
Fire Safety Log Book Record of tests, training, maintenance and inspections Premises name: Address: Town: Postcode: Log book start date: We recommend an up to date copy of all fire safety related records
More information1.1.4 The findings from Fire Risk Assessment must be incorporated into the FRAMS Action Plan to manage fire safety at each premise.
Fire Safety Policy 1.1 Policy Statement of Intent 1.1.1 Under the current UK Legislation (In England and Wales, the Regulatory Reform (Fire Safety) Order 2005, Fire (Scotland) Act 2005, Fire and Rescue
More informationIntroduction. CE marked construction products
Introduction This Technical Booklet has been prepared by the Department of Finance and Personnel and provides for certain methods and standards of building which, if followed, will satisfy the requirements
More informationAVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839
AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What
More informationCall reduction guidance for false alarm/ unwanted fire signals
Call reduction guidance for false alarm/ unwanted fire signals Acting to Protect & Save Introduction Devon & Somerset Fire & Rescue Service attend in excess of 20,000 incidents each year, approximately
More informationFire Alarm system Installation Guide
Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this
More informationCompliance Schedules and Building Warrant of Fitness
Compliance Schedules and Building Warrant of Fitness Purpose of this guidance information The purpose of this guidance information is to help building owners and managers of commercial, industrial or communal
More informationEmployee Health and Safety Induction Training Record
COMPANY NAME Employee Health and Safety Induction Training Record Employee name Job Title Department Start Date - PBS 2010/2 Employee Health & Safety Induction Training Record Page 1 of 6 INDUCTION TRAINING
More informationPRACTICAL FIRE SAFETY GUIDANCE FOR FACTORIES AND STORAGE PREMISES
PRACTICAL FIRE SAFETY GUIDANCE FOR FACTORIES AND STORAGE PREMISES Revised February 2008 The guidance in this document has been jointly produced by the Scottish Government s Police and Community Safety
More informationGuidance When Sub-Letting a Flat
Guidance When Sub-Letting a Flat If you are sub-letting your flat or if you are thinking of doing so, please read this Guidance Note carefully. It is important that you fully understand your legal obligations
More informationFire Safety Policy. Fire Safety Policy: May 2011 Page 1 of 6. Version 1. Scope:
Version 1 Fire Safety Policy Scope: Effective Date: Review Date: Signed Off by: Author: Policy Owned by: This policy applies to Hackney Homes Ltd working on behalf of the London Borough of Hackney July
More informationNOTTINGHAMSHIRE FIRE & RESCUE SERVICE. Fire Risk Assessment Information / Guidance
NOTTINGHAMSHIRE FIRE & RESCUE SERVICE Fire Risk Assessment Information / Guidance Version 2 - dated March 2014 Nottinghamshire Fire & Rescue Service www.notts-fire.gov.uk CONTENTS Introduction Fire Risk
More informationRESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK PERRONET HOUSE PRINCESS STREET LONDON SE1 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
More informationFire Risk Assessment
Fire Risk Assessment London House School of English 63-65 Westgate Bay Avenue Westgate-on-Sea Kent CT8 8SW UK Tel: +44 (0) 1843 831 216 Fax: +44 (0) 1843 831 100 Email: enquiries@london-house.co.uk Website:
More informationGuidance for Electrical Contractors on Emergency Lighting Legislation
Guidance for Electrical Contractors on Emergency Lighting Legislation Issued in the interests of safety by in conjunction with the Industry Committee for Emergency Lighting ECA / ICEL Guidance For Electrical
More informationFIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
More informationRC44. for fire risk assessment of catering extract ventilation
Catering extract 17/10/06 15:45 Page 1 RC44 for fire risk assessment of catering extract ventilation IMPORTANT NOTICE This document has been developed through the Insurers Fire Research Strategy scheme
More informationCATERING CONTRACTORS General Code of Safety Practice
Residential & Business Services Director s Office CATERING CONTRACTORS General Code of Safety Practice CONTENTS 1 Introduction 2 2 Commencement of Work 3 3 Vehicles 3 4 Temperature control 3 5 Food hygiene
More informationFIRE SAFETY POLICY GUIDANCE
FIRE SAFETY POLICY GUIDANCE Author: RAE TURRELL Currently under review: March 2011 Health & Safety Business Partner FIRE SAFETY POLICY GUIDANCE CONTENTS PART 1: INTRODUCTION Page Quick at a glance Key
More informationLONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION
LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION 1. Minimum Standards: This document sets out the minimum standards required in HMOs located within the London Borough
More informationWorkplace Fire Safety
Teaching Guide Workplace Fire Safety for staff Seattle Fire Department Fire Prevention Division Workplace Fire Safety Instructor Outline Introduction Goals: To ensure that employees are knowledgeable in
More informationBS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
More informationFIRE SAFETY ONLINE TRAINING
INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency
More information