1 13D Systems What, Why and How Oregon Fire Sprinkler Coalition
2 The Fire Problem Statistics National Each day 7 people die home fires Each year on average over 2,500 people die and more than 13,000 people are injured in home fires Fires kill more people each year than all natural disasters combined Children and the elderly are most at risk Oregon From 2004 to 2013 there were: nearly 350 fire deaths more than 2,500 injuries Source: NFPA
3 Residential Sprinklers A Proven Solution Occupant safety: Sprinklers reduce civilian fire deaths by 83% Sprinklers reduce civilian fire injury medical costs by 53% Sprinklers reduce civilian fire injury total costs by 41% Source: NFPA
4 Residential Sprinklers A Proven Solution Firefighter safety: Sprinklers are responsible for an estimated 65% reduction in firefighter fire ground injuries Property Loss: Sprinkler reduce direct property damage per fire by 69% Source: NFPA
5 13D Born of Necessity America Burning 1973: Nation Commission on Fire Prevention and Control More fire deaths in homes than any other industrialized nation Identified a need to: Reduce fire deaths in America Make sprinklers more affordable Make residential sprinklers more aesthetically appealing
6 13D Born of Necessity America Burning 1973 Brought about: NFIRS - National Fire Incident Reporting System USFA US Fire Administration NFA National Fire Academy And.
7 The Standard of Care NFPA 13D A Different Philosophy than NFPA 13: Focus on life-safety (survivability) Operate in tandem with smoke alarms for occupant notification Address affordability A Balance: Life Safety and Money
8 NFPA 13D A Standard Referenced by Codes Codes point toward standards A Standard becomes code when it is referenced by an enabling document, such as a state building code Oregon Fire Code Based on IFC Oregon Structural Specialty Code Based on IBC
9 NFPA 13D A Standard Referenced by Codes Codes address when sprinklers apply: Access issues Grades Lot characteristics Tradeoffs Ordinances / Statutes Standards address how the sprinklers apply: Design criteria Sprinkler locations / spacing Materials allowed Connection to water supplies
10 NFPA 13D Scope and purpose Scope of Document: This standard shall cover the design, installation, and maintenance of automatic sprinkler systems for protection against the fire hazards in one- and two-family dwellings and manufactured homes This standard shall be based on the concept that the sprinkler system is designed to protect against a fire originating from a single ignition location.
11 NFPA 13D Scope and purpose Purpose of Document: The purpose of this standard shall be to provide a sprinkler system that aids in the detection and control of residential fires and thus provides improved protection against injury and life loss A sprinkler system shall be designed and installed in accordance with this standard to prevent flashover (total involvement) in the room of fire origin, where sprinklered, and to improve the chance for occupants to escape or be evacuated.
12 NFPA 13D Scope and purpose Standard Applies to: Single Family residence Townhouses If built to the IRC (ORSC) Duplex Homes Manufactured homes
13 Design Principles Sprinklers in an easier design scenario Design approach based on historical data Water supply is only required to accommodate two sprinklers at any given time Even with that approach, 84% of the time, a single head controls the fire in this type of system If the largest room can be protected with a single sprinkler, the design can be based on one head flowing Source: NFPA
14 Design Principles Sprinklers in an easier design scenario Sprinklers are located where loss of life historically occurs: Kitchens Bedrooms Living rooms / Corridors Source: NFPA
15 Design Principles Sprinklers in an easier design scenario Sprinklers are not required in: Closets (under 24 Sq Ft) Bathrooms (under 55 Sq Ft) Exterior eaves / porches balconies / closets Rooms in attics or under structure that aren t connected to dwelling area And do not contain fuel-fired equipment Source: NFPA
16 13D System Types Stand-Alone Type: A sprinkler system where the aboveground piping serves only fire sprinklers
17 13D System Types Multi-Purpose System: A piping system intended to serve both domestic needs in excess of a single fixture and fire protection needs from one common piping system throughout the dwelling unit(s).
18 13D System Types Passive Purge (Flow Through): A type of sprinkler system that serves a single toilet in addition to the fire sprinklers.
19 13D System Types Network System: A type of multipurpose system utilizing a common piping system supplying domes- tic fixtures and fire sprinklers where each sprinkler is supplied by a minimum of three separate paths
20 System Components and Features System Alarms Two Alarm scenarios: Notification provided by NFPA 72 compliant Smoke Alarms, or Waterflow device and local bell (optional) OR +
21 System Components and Features Residential Sprinkler Heads Performance Higher wall wetting Fuel loads are near walls in residential occupancies Controls the environment Greater coverage areas Faster response Easily applicable design criteria Design criteria maximizes a smaller water supply : NFPA
22 System Components and Features Residential Sprinkler Heads: Aesthetically Appealing There are many cutting-edge, flush type heads that blend into the ceiling Some manufacturers offer as many as 300 custom paint colors. :
23 System Components and Features Piping and Materials A variety of common material types All listed for potable water supplies CPVC PEX / Other Copper
24 Municipal Water Supplies Works with the plumbing supply, not in addition to it: Only 7 PSI required for fire sprinklers Most domestic systems require 8 PSI (UPC, IPC) 16 GPM could supply a one head sprinkler design. Most average homes require a minimum of 18 GPM for domestic use (IRC) Most residential sprinkler systems will flow more, but a ¾ meter (35 GPM) will usually be plenty of water (2 sprinklers x 16 GPM = 32 GPM) Source: OPSC
25 Municipal Water Supplies Upgrading to a 1 meter isn t the only option! 3/4 meters are a popular option for many Water Purveyors (35 GPM) A system can sometimes be designed using an existing 5/8 meter (20 GPM) Most average homes require a minimum of 18 GPM for domestic use Source: OPSC / IRC
26 Municipal Water Supplies An increasing number of Water Purveyors are starting to recognize that sprinklers use less water than the water used from unmetered fire hydrants that would otherwise be needed to suppress a fire in a home Sprinklers use 90% less water than the fire service would use if sprinklers weren t installed. They reduce fire damage by 97% They reduce greenhouse gas emissions by 98%. Sprinklers also reduce wastewater pollution. Source: FM Global
27 Private / Stored Water Supplies An easy solution for private water supplies (tanks and wells) 10 minute Duration: A typical scenario: 280 Gallon Tank (28 GPM x 10 Min) 7 minute Duration (Single story under 2000 Sq Ft): This can be as low as 196 Gallon Tank (28 GPM x 7 Min) Source: NFPA 13D
28 Private / Stored Water Supplies Tanks and pumps not required to be listed In some scenarios, a tank and pump supply might be more cost effective than a meter upsizing fee and SDC charge Source: NFPA 13D
29 System Maintenance A Maintenance Friendly System - Requirements 13D Inspection, Testing and Maintenance (ITM) The maintenance requirements are simple: Walk the sprinklers periodically (no specific time requirement) to look for: Obstructions to discharge (storage, etc) Painted or damaged heads Annual backflow test, if device is installed (not typically required) Source: NFPA 13D
30 System Maintenance A Maintenance Friendly System - Recommendations 13D Inspection, Testing and Maintenance (ITM) The maintenance recommendations are also simple: Annual flow test if a waterflow detector and bell are installed (optional devices) Annual backflow test, if device is installed (backflow device not typically required) Annual inspection by a qualified contractor Source: NFPA 13D
31 13D Saves Lives and Money! Taking advantage of the 13D Design to Save Money Bang for your buck Pricing the system: Get several bids Oregon state online list of contractors Builders Exchanges Google it! Phone book Contact local Fire and Building Departments Call some builders Explore the different system types
32 Conclusion 13D is designed to be an achievable balance between protection and cost
33 Questions?
Roland Garcia Pearland Fire Department
Roland Garcia Pearland Fire Department NFPA13D Texas Legislation Conflicting Views - Fire Service and Home Builders Incentives offered in the ICC Detect and control residential fires Prevent injury and
More informationH O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S
H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S HomeFireSprinkler.org F I R E T H E L A R G E ST S I N G L E C AU S E O F
More informationHow To Install A Fire Sprinkler
Fire Sprinklers: Coming to a Home Near You With a smoking record for saving lives and protecting houses, it s no surprise sprinklers were adopted into the International Residential Code BY CHRIS ERMIDES
More informationC I T Y O F S E L M A F I R E D E P A R T M E N T
C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:
More informationOntario Association of Fire Chiefs Position Paper Residential Fire Sprinklers
Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers The Ontario Association of Fire Chiefs (OAFC) supports changes to the Ontario Building Code to require that all new residential
More informationWe look forward to working with you. Worldwide Headquarters 1400 Pennbrook Parkway Lansdale, PA 19446. www.tyco-rapidresponse.com
TYCO IS HERE TO HELP Tyco will work closely with you to make the installation of Rapid Response Residential Fire Sprinkler Systems a quick and easy addition to your new home construction. We can develop
More informationFIRE SPRINKLER TALKING POINTS
An Overview of the Issues FIRE SPRINKLER TALKING POINTS Because of changes in residential construction technology, improved building code requirements especially for electrical and smoke alarm systems
More informationFire Sprinkler Fact Sheet
Fire Sprinkler Fact Sheet Because of changes in residential construction technology, improved building code requirements - especially for electrical and smoke alarm systems, as well as consumer behavior
More informationWHAT YOU NEED TO KNOW ABOUT INSURING A HOME WITH FIRE SPRINKLERS
WHAT YOU NEED TO KNOW ABOUT INSURING A HOME WITH FIRE SPRINKLERS A GUIDE FOR PROPERTY & CASUALTY INSURANCE PROFESSIONALS HomeFireSprinkler.org FIRE THE LARGEST SINGLE CAUSE OF PROPERTY LOSS Fire is the
More informationConcord Department of Fire and Life Safety FIRE MARSHAL S OFFICE
Concord Department of Fire and Life Safety FIRE MARSHAL S OFFICE September 1, 2005 Fire Suppression Operations in Residential Occupancies equipped with Residential Fire Sprinkler Systems. Since human beings
More informationDesign Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
More informationBUILD FOR QUALITY BUILD FOR VALUE BUILD FOR LIFE
BUILD FOR QUALITY BUILD FOR VALUE BUILD FOR LIFE AUTOMATIC FIRE SPRINKLER PROTECTION Residential fire sprinkler system installations are increasing every day thanks to growing buyer demand, lower costs,
More informationFraternity and Sorority House Fire Safety
Fraternity and Sorority House Fire Safety Buddy Dewar Director of Regional Operations National Fire Sprinkler Association 850-222-2070 How To Manage Greek Housing Fire Sprinkler Retrofit Brief Overview.
More informationINTERNATIONAL RESIDENTIAL CODE PLUMBING
INTERNATIONAL RESIDENTIAL CODE PLUMBING RP1-07/08 P2503.5.1 Proposed Change as Submitted: Proponent: Michael Cudahy, representing Plastic Pipe and Fittings Association Revise as follows: P2503.5.1 Rough
More informationYour Instructor. Two Biggest Obstacles to Residential Sprinklers. Two Biggest Obstacles to Residential Sprinklers
Residential Sprinklers ----- Issues and Answers Your Instructor Jeffrey M. Shapiro, PE Executive Director IRC Fire Sprinkler Coalition 1 2 The IRC Fire Sprinkler Coalition Not-for-profit association representing
More informationUse Of Residential Fire Sprinklers In New Housing Projects
STAFF REPORT ACTION REQUIRED Use Of Residential Fire Sprinklers In New Housing Projects Date: May 22, 2007 To: From: Wards: Reference Number: Community Development and Recreation Toronto Fire Services
More informationPROTECT WHAT YOU VALUE MOST
PROTECT WHAT YOU VALUE MOST HOME FIRE SPRINKLERS SAVE LIVES Fire kills more people in the United States annually than all natural disasters combined. In fact, more than 4,000 people perish in fires each
More informationSARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
More informationEconomic Cost Benefit Analysis of Residential Fire Sprinkler Systems Cape Coral, FL July 2012
Economic Cost Benefit Analysis of Residential Fire Sprinkler Systems Cape Coral, FL July 2012 Prepared by: Newport Partners, LLC Davidsonville, MD Economic Cost Benefit Analysis of Residential Fire Sprinkler
More informationCOMMON MYTHS ABOUT FIRE SPRINKLER PROTECTION
"Water damage from a sprinkler system will be more extensive than fire damage." Water damage from a sprinkler system will be much less severe than the damage caused by water from firefighting hose-lines
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
More informationPreparation for 2015 Residential Code Changes Discussion with Local Builders and Designers
City of Duluth Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers Thank you for taking the time to join us today. We know you are busy and your time is valuable.
More informationCITY OF MEDFORD INTEROFFICE MEMO
CITY OF MEDFORD INTEROFFICE MEMO FIRE DEPARTMENT TO: Mike Dyal, City Manager FROM: Dave Bierwiler, Fire Chief DATE: July 11, 2007 RE: Residential Fire Sprinklers and Access Issues Executive Summary: On
More informationFIRE SPRINKLERS IN TOWNHOMES/CONDOMINIUMS
CITY OF BLAINE SAFETY SERVICES Fire Inspections 10801 Town Square Drive Blaine MN 55449 Business Phone 763-785-6187 Fax 763-717-2634 City of Blaine Fire Prevention Inspection Policy FIRE SPRINKLERS IN
More informationCHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
More informationAutomatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
More informationAgenda Item # Page f BILL 141 -THE HOME FIRE SPRINKLER ACT, 2004 RECOMMENDATION
il Agenda Item # Page f mm 3 3 1 I I CHAIR AND MEMBERS II To COMMUNITY AND PROTECTIVE SERVICES COMMITTEE SEPTEMBER 12,25 FROM JOHNKOBARDA FIRE CHIEF AND DIRECTOR OF PARAMEDIC SERVICES /ISUBJECT I BILL
More informationInstructions for Obtaining a Certificate of Smoke Detector, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance
Princeton Department of Emergency & Safety Services Instructions for Obtaining a Certificate of, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance 1. Obtain an application Download from /forms
More informationRhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report?
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL 1951 Smith Street, North Providence, RI 02911 Telephone: (401) 383-7717 Fax: (401) 383-8879 John E. Chartier, EFO, CFI State Fire Marshal Rhode Island State
More informationTEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs
TITLE 22 PART 17 CHAPTER 363 RULE 363.11 EXAMINING BOARDS TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs (a) General requirements for Course Providers
More informationMARKETING HOMES PROTECTED BY FIRE SPRINKLER SYSTEMS
MARKETING HOMES PROTECTED BY FIRE SPRINKLER SYSTEMS A GUIDE FOR REAL ESTATE PROFESSIONALS HomeFireSprinkler.org HOME FIRE SPRINKLER SYSTEMS A GROWING TREND THAT S HERE TO STAY If you re marketing a home
More informationHome Fire Sprinkler Facts vs. Myths
Home Fire Sprinkler Facts vs. Myths MYTH: Home fire sprinklers can malfunction and cause severe water damage to my home. They re more of a liability than a help! FACT: It is extremely rare for home fire
More informationSection 9 Major Urban Fire
Section 9 Major Urban Fire Table of Contents WHY MAJOR URBAN FIRES ARE A THREAT...9-2 HAZARD PROFILE...9-3 HISTORY OF MAJOR URBAN FIRES...9-4 POTENTIAL DAMAGES AND LOSSES...9-5 MAJOR URBAN FIRE MITIGATION
More informationResources. Presentation By: Wayne Waggoner, NFSA
Resources Presentation By: Wayne Waggoner, NFSA Resources Residential Fire Sprinklers - Step By Step a Communities Approach Sprinklers for Dwellings Training Manual Built for Life HFSC Builders Kit Look
More informationMAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015
MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 **Disclaimer: This document is to serve as informational purposes only. This is not a code book or a final interpretation of the
More informationMINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES
MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES September 13, 2012 MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES WELCOME Exits Restrooms
More informationUtility Service Application
Utility Service Application for Multi-family/Non-residential Developments Thank you for contacting the City of Tampa for your water and wastewater utility service needs. We have assembled this package
More informationHome Fire Sprinkler Cost Assessment
Home Fire Sprinkler Cost Assessment Final Report Prepared by: Newport Partners September 2008 Fire Protection Research Foundation FOREWORD Residential fire sprinkler ordinances have been adopted by several
More informationDevelopment Services City of Lawrence, KS
Development Services City of Lawrence, KS Building Planning Table R301.2 (1) Climatic & Geographic Design Criteria Building Planning The design criteria for wind speed increased from 90 MPH to 115 MPH.
More informationREQUIREMENTS FOR SINGLE FAMILY DWELLINGS
REQUIREMENTS FOR SINGLE FAMILY DWELLINGS New Single Family Dwelling Additions or Renovations to Single Family Dwelling An application for a building permit, when adding plumbing fixtures to a new single
More informationATTENTION BUILDERS, CONTRACTORS AND DEVELOPERS
ATTENTION BUILDERS, CONTRACTORS AND DEVELOPERS Wellington Fire Protection District Development and Construction Plan Review Fee Policy. For any questions, contact the Fire Marshal at (970) 568-3232, ext
More informationSMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection
More informationFIRE SUPPRESSION INSTALLATION CITY OF HARRISONBURG, VIRGINIA
FIRE SUPPRESSION INSTALLATION CITY OF HARRISONBURG, VIRGINIA I. PURPOSE The purpose of this document is to provide planners and designers with information necessary in the design and construction of sprinkler
More informationEducational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
More informationBuilding Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
More informationA Call for Fire Sprinklers in Chicago s Existing Residential High-Rises
FIREDYNE ENGINEERING, P.C. Fire Protection Engineering Code Consulting 18222 CORK ROAD, TINLEY PARK, IL 60477 PHONE: (708) 633-8140 From testimony presented to the Chicago Building Committee A Call for
More informationLOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
More informationNFPA 101 2012 SELECT SIGNIFICANT CHANGES
NFPA 101 2012 SELECT SIGNIFICANT CHANGES William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire INTRODUCTION NFPA 101 is
More informationArapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
More informationREGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE SUPPRESSION SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S. EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire
More informationCITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY
Draft CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY Draft Los Angeles Plumbing Code (LAPC) 2008 California Plumbing Code (CPC) 2007 Uniform Plumbing Code (UPC) 2006 Major Code Changes Preliminary
More informationTruth in Sale of Housing Disclosure Report NOTICE - Read Entire Report Carefully. This is not a Buyer's Inspection!
NOTICE - Read Entire Report Carefully. This is not a Buyer's Inspection! Current Owner Name: Mpls City Property Atn Cped (p Contact: Mpls City Property Atn Cped (p Business/Relationship: Owner Address:
More informationRequired Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
More informationCity of Elk River BASEMENT Office Use Only
City of Elk River BASEMENT Office Use Only Fire and Building Safety Division (FABS) Building Permit Application Notes Scan Permit Total Date Permit # PID # $ Site Address Suite/Unit Structure Type Single
More informationDESIGN GUIDE FOR INSTALLING PARTIAL SPRINKLER PROTECTION IN UNFINISHED BASEMENT AREAS
UP DESIGN GUIDE FOR INSTALLING PARTIAL SPRINKLER PROTECTION IN UNFINISHED BASEMENT AREAS March 2014 This document is not intended to advocate nor discourage the installation of residential sprinkler systems
More informationOregon Plumbing Rule and Law RV 3.3.16
PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.
More informationSPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST
SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following
More informationHome Fire Sprinkler Cost Assessment - 2013
Home Fire Sprinkler Cost Assessment - 2013 Final Report Prepared by: Newport Partners The Fire Protection Research Foundation One Batterymarch Park Quincy, MA, USA 02169-7471 Email: foundation@nfpa.org
More informationFires in residences have taken a high toll of life and property. In 2002 there were:
Home Fire Safety RESIDENTIAL SPRINKLERS SPRINKLER SYSTEMS IN INDUSTRY Schools, office buildings, factories, and other commercial buildings have benefited from fire protection sprinkler systems for over
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and
More informationT r a i n i n g T a b l e t
V o l u m e 3, I s s u e 3 M a r c h, 2 0 1 3 QRS calls: When do I make a QRS report? Recently we were asked to clarify how to decide if a QRS report should be entered into the Firehouse Software. In a
More informationTruth in Sale of Housing Disclosure Report NOTICE - Read Entire Report Carefully. This is not a Buyer's Inspection!
NOTICE - Read Entire Report Carefully. This is not a Buyer's Inspection! Current Owner Name: Mpls City Property Atn Cped (p Contact: Mpls City Property Atn Cped (p Business/Relationship: Owner Address:
More informationIs the Apartment in my House Legal?
Is the Apartment in my House Legal? THE CITY OF ORILLIA S GUIDE TO APARTMENTS IN HOUSES Legal Means: Complies with the Planning Act and/or City s Zoning By-law Building Permit for the apartment has been
More informationRHODE ISLAND DIVISION OF STATE FIRE MARSHAL
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL Smoke Alarm and Carbon Monoxide Brochure JOHN E. CHARTIER STATE FIRE MARSHAL 118 PARADE STREET PROVIDENCE, RI 02909 DAYS 401-462-4200 24 Hr. 401-222-2331 FAX#
More informationHOME FIREFA 43 PROTECTION
HOME FIREFA 43 Revised April 1997 (Supersedes FA 43 dated July, 1986 PROTECTION Residential Fire Sprinkler Systems Federal Emergency Management Agency U.S. Fire Administration This document was scanned
More informationNC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02
NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 PART A: Project Data and Classification 1. Project name & location Renovation of the Cheerwine Building, 322 East Council St.,
More informationCompliance Date Approaches for Installation of Fire Sprinkler Systems
Compliance Date Approaches for Installation of Fire Sprinkler Systems By Frank Monikowski It has been nearly three years since the Centers for Medicare and Medicaid Services (CMS) announced amended federal
More informationMERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS
MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth
More informationSAMPLE INSPECTION REPORT PREPARED FOR: John Q Public
925 W. Baseline Road Suite 105-Y1 Tempe AZ 85283 Tel: 480-456-8809 Fax: 480-456-6139 Mobile: 602-790-0976 www.accuproinspect.com AccuPro@AccuProINSPECT.com SAMPLE INSPECTION REPORT PREPARED FOR: John Q
More informationEFSN Training i Module 1. 90 Minutes
Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler
More informationMinimum Housing and Health Standards
APPENDIX M.O. 57/2012 Minimum Housing and Health Standards Original version July 20, 1999. Revisions to Part lll, Housing Premises, sections 3 and 4, June 30, 2012 (all revisions are bolded and underlined).
More informationDevelopment Services Guidelines
Dear Customer/Developer: Balcones Heights 3300 Hillcrest San Antonio, Texas 78201 210-735-9148 ext 246 Fax: 210-735-9409 Development Services Guidelines Welcome to the City of Balcones Heights, we look
More informationHousing Quality Standards Inspection Checklist
Housing Quality Standards Inspection Checklist To prevent delays, the R.T.A. must be complete and upon submission the unit must be in move in condition or an inspection will not be conducted. A Fair Housing
More informationBUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
More informationCOMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9
COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9 GUIDELINES FOR THE PREPARATION OF FIRE PROTECTION SYSTEM NARRATIVE REPORTS 780 CMR 903.1.1 State
More information#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the
More informationMaintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
More informationCity of San Antonio (COSA) Boarding Homes Fire Sprinkler System Training
City of San Antonio (COSA) Boarding Homes Fire Sprinkler System Training Development Services Department (DSD) & San Antonio Fire Department (SAFD) 1901 S. Alamo Wednesday, January 23, 2013 9:00 am 11:00
More informationSIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes)
SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes) Maintenance Office Administrative Office Billing Office 530-426-7802 530-426-7800 916-332-4872
More informationNational Fallen Firefighter Foundation (NFFF) 16 Firefighter Life Safety Initiatives
NFFF Life Safety Initiative #1: Define and advocate the need for a cultural change within the fire service relating to safety; incorporating leadership, management, supervision, accountability, and personal
More informationELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
More informationPROPERTY INSPECTION REPORT
Whisper Computer Solutions, Inc. P.O. Box 690502 San Antonio, TX 78269-0502 Phone: (210)681-6325 Fax: (210)681-6325 Email: support@whispersolutions.com PROPERTY INSPECTION REPORT Prepared For: Concerning:,
More informationA Code Review for Emergency Generators and Indoor Use of Portable Generators
A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a
More informationPLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS. Second Edition. Prepared by
PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS Second Edition Prepared by NAHB Research Center, Inc. 400 Prince Georges Boulevard Upper Marlboro, MD 20774-8731 DISCLAIMER This
More informationICC CODE CORNER 2012 IFC Code & Commentary
SECTION 908 EMERGENCY ALARM SYSTEMS 908.1 Group H occupancies. Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as required in Chapter
More information527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
More informationWELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION
WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION 1 HOUSEKEEPING 2 CHANGES We will be covering the significant changes to the International Residential Code and the changes common to
More informationOne of the fundamental design elements that every
Preliminary Design Information Before starting the water system design, you must assemble a collection of information. This includes information from the owner, the local utility, and the architect. Things
More informationFire Alarm Systems Permit Packet. City of Greer Fire Department
Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting
More informationDaycare Center Fires
U.S. Fire Administration TOPICAL FIRE RESEARCH SERIES Volume 2, Issue 15 November 2001 (Rev. March 2002) Daycare Center Fires FINDINGS S An estimated 325 fires occur in daycare centers/facilities each
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationHOMEOWNER S PERMIT GUIDE
HOMEOWNER S PERMIT GUIDE WHEN IS A PERMIT REQUIRED? Department of Development and Permits 306 Cedar Road, City Hall 2 nd Floor P.O. Box 15225 Chesapeake, VA 23328 Phone: (757) 382-6018 Fax: (757) 382-8448
More informationSmoke Alarm Performance in Residential Structure Fires
U.S. Fire Administration TOPICAL FIRE RESEARCH SERIES Volume 1, Issue 15 March 2001 (Rev. December 2001) Smoke Alarm Performance in Residential Structure Fires FINDINGS S Smoke alarms save lives and money.
More informationCommercial Fire Inspections
Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated
More informationSCHEDULE A BY-LAW B-6 CLASSES OF PERMITS AND FEES
1. CALCULATION OF PERMIT FEES SCHEDULE A BY-LAW B-6 CLASSES OF PERMITS AND FEES Permit fees shall be calculated based on the formula given below, unless otherwise specified in this schedule: Permit Fee
More informationFire Safety Risk Assessment
1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept
More informationHOME FIRE PROTECTION SYSTEMS SPRINKLER SYSTEMS IN INDUSTRY
HOME FIRE PROTECTION RESIDENTIAL FIRE SPRINKLER SYSTEMS SPRINKLER SYSTEMS IN INDUSTRY Sh Schools, office buildings, factories, and other commercial buildings have benefited from fire protection sprinkler
More information