FIRE PUMP ESSENTIALS. Chamco Industries

Size: px
Start display at page:

Download "FIRE PUMP ESSENTIALS. Chamco Industries"

Transcription

1 FIRE PUMP ESSENTIALS Chamco Industries

2 THE FIRE PUMPS FOUR TYPES/STYLES OF FIRE PUMPS Horizontal, split case. (250 usgpm usgpm) Vertical Turbine. ( 250 usgpm usgpm ) End Suction. ( commercial ) Vertical Inline. ( commercial )

3 FIRE PUMP TYPES DIESEL DRIVEN HORIZONTAL ELECTRIC DRIVEN HORIZONTAL

4 FIRE PUMP TYPES JOCKEY PUMP VERTICAL TURBINE FIRE PUMP & ENGINE

5 ENGINES Engines are UL or FM approved for Fire Service, and built by: Caterpillar ( full range, mostly above 200hp ) Cummins ( limited range, hp ) Clarke Engine ( best range, hp )

6 RIGHT ANGLE GEAR DRIVES Right Angle Gear Drives are FM approved for Fire Service, and built by: Randolph Manufacturing Amarillo Gear Johnson Gear

7 FIRE PUMP CONTROLLERS Pump Control panels, for Electric and Diesel drives are UL or FM or ULC approved for Fire Service, and built by: Cutler Hammer Firetrol Metron

8 FIRE PUMP CONTROLLERS Control panels for Diesel drives and Jockey Pumps:

9

10 NFPA 20 Does not specify when or if a fire pump must be installed Specifies: How, Components, Equipment, Power Source are acceptable to use Provides the minimum requirements needed for satisfactory operation of listed fire pumps NFPA 20 covers every type of listed fire pump Most common is centrifugal

11 Equivalency NFPA 20 is not intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength, fire resistance, effectiveness, durability, and safety over those prescribed in this standard. AHJ has the final call

12 NFPA 20 Terms Shall Mandatory requirement Should Indicates a recommendation that is advised but not required

13 What Makes a Pump a Fire Pump 4.2 Stationary pumps shall be selected based on the conditions under which they are to be installed and used Capacities are based on calculated system demand, and pressures are based on available pressure from the water supply

14 What Makes a Pump a Fire Pump Unit Responsibility One supplier for pump, driver, controls Typically falls on the pump manufacturer SHOULD was used not Shall Recommendation, having unit responsibility helps ensure that all components are compatible 4.5 Certified Shop Test Needs to be furnished from the pump manufacturer to the purchaser, and must include head capacity and BHP Why? To verify that the fire pump was tested by the manufacturer prior to shipment and met the conditions.

15 What Makes a Pump a Fire Pump Head The Head available from a water supply shall be figured on the basis of a flow for 150% rated capacity. (EG: 1000GPM pump shall be able to reach a capacity of 1500GPM)

16 What Makes a Pump a Fire Pump 4.7 Pumps, Drivers, and Controllers A Pump shall not be equipped with more than one driver Each pump shall have it s own dedicated driver Each driver shall have it s own dedicated controller

17 What Makes a Pump a Fire Pump Maximum Pressure for Centrifugal Pumps The net pump shutoff pressure plus the maximum static suction pressure adjusted for elevation shall not exceed the pressure for which the system components are rated Ex: 145psi, shut off pressure is 168psi, and suction pressure is 30psi. You need to have 250# fittings on the discharge side of the system. Don t over design the pump and use a throttle device to regulate pressure!!

18 NFPA Centrifugal Pump Capacities Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

19 Automatic (circulation) Relief Valve The valve shall provide flow of sufficient water to prevent the pump form overheating when operating at shutoff. Up to 2500GPM the nominal size shall be ¾ 3000GPM and higher shall be 1 Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

20 Devices in Suction Piping Devices in Suction Piping No device or assembly, unless identified in that will stop, restrict the starting, or restrict the discharge of a fire pump or pump driver shall be installed in the suction piping. The purpose is to prohibit anything in the suction that would cause excess turbulence, friciton loss, or cut off the flow to the pump while running at 150% capacity. Cutting off the supply would cause catastrophic failure to the pump. Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

21 Water Flow Test Devices Every fire pump needs a method for performing the acceptance test. 1) Test Header Flows readings are usually taken with a Pitot tube 3) Flowmeter A special pipe is run for the discharge back to the water supply with a flowmeter, control valve, and check valve in the line A fire pump installation shall be arranged to allow the test of the pump at its rated conditions as well as the suction supply at the maximum flow available from the fire pump. Two objectives: 1) To make sure the pump itself will function correctly 2) Make sure the water supply can deliver the correct amount Under no circumstance may a fire pump be placed into service without an acceptance test!!! Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

22 Automatic Air Release Automatic Air Release Unless the requirements of are met, pumps that are automatically controlled shall be provided with a listed float-operated air release valve having a normal 0.50 in. (12.7 mm) minimum diameter discharge to atmosphere. Air in the impeller can cause cavitation, dmage the impeller, and negatively impact pump perfomance! Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

23 Listed Fire Pump Controllers All controllers and transfer switches shall be specifically listed for electric motor driven Fire Pump Service All controllers shall be specifically listed for diesel engine-driven fire pump

24 Field Acceptance Testing A copy of the manufacturers certified pump test characteristics curve shall be available for comparison of the results of the field acceptance test The fire pump shall perform at minimum, rated, and peak loads without objectionable overheating of any component

25 NFPA Whenever a critical path component in a piece of centrifugal pump equipment is replaced, changed, or modified, a field/on-site retest shall be performed Table

26 TESTING METHODS

27 Courtesy of Proctor & Gamble, Cincinnati, OH

28 Two hydrants are normally required to conduct a flow test of the water supply. This is the flow hydrant, the second hydrant will only have a pressure gauge and will be used to obtain a static (no flow) and residual pressure reading (while water is flowing).

29 FLOW IN GPM H E A D.... A PUMP CHURN Pressure ACTUAL CITY WATER FROM FLOW TEST B RATED 100 % FLOW. C 150 % RATED 100% FLOW

30 PUMP FLOW DETERMINATION WITH ( UL / FM ) FLOW METER

31 PUMP FLOW DETERMINATION WITH NOZZLE ( UL / FM ) PLAY PIPE and PITOT TUBE

32 <FM> Short Play Pipe 1 1/8 Nozzle 1 ¾ Nozzle Pitot Tube Underwriters Play Pipe 1 ¾ Nozzle

33 Maintenance

34 Owner / Operators trained in required maintenance, weekly operation, required testing, and record keeping? Did the pump distrbutor provide the required instruction manuals and a weekly check list for the required weekly testing, maintenance, and inspections of the pump, driver, and controller? NFPA NFPA If not, he is not doing his job!!! Weekly Check list should include those items required by NFPA 25 Chapter 8.

35

36 Review ALL Required Weekly/Annual Maintenance NOTE: Clean Grease Forced out of the Drain hole with PLUG REMOVED!! Check For Excess Grease

37 Annual Alignment Check AFTER alignment has been re-checked (ANNUALLY) the coupling should be lubricated and reassembled. Be sure to check the set screws for tightness

38 EMERGENCY MANUAL STARTING PROCEDURE (11.6.6) CUMMINS SET at 120 % of Rated RPM ** #1 COOLING WATER #2 FUEL # 3 NOTE! BE SURE THAT YOU KNOW WHERE THE OVERSPEED RESET IS ON EVERY TYPE OF ENGINE THAT YOU SELL!! CRANK

39 Develop a check list of your own for both electric and diesel Fire Pumps. -OR- Make a copy of NFPA 25, Chapter 8 for use as a guide for weekly checks.

40

41 HAVE THESE FOLKS BEEN PROPERLY TRAINED?

42 ? This is the ONLY WM case relief valve on record, that always had a tight shut off with NO nuisance leakage - until the fire pump overheated and was destroyed!!

43

44

45 Vertical Turbine Fire Pump NFPA 20 (7. 1)

46 NOTE: Automatic air release NFPA 20 ( ) SHALL BE Located between the fire pump and the discharge check valve. * Motor HP and current limits, multiplied by the service factor, must not be exceeded under any condition of pump load. CHECK! NFPA 20 (9.5.2)*

47 NOTE: Automatic air release SHALL BE Located in the highest point in the discharge line, between the fire pump and the discharge check valve. NFPA 20 ( ) *

48 NFPA 20 ( ) ACCESS FOR REMOVAL?**

49 NFPA 20 ( ) I beams must be parallel to the engine!*

50 NFPA 20 ( )

51 One degree of off-set is the preferred angle, per drive shaft manufacturers!! NFPA 20 ( )*

52

53 NFPA 20 ( )* Top Shaft Nut is used to raise shaft and impellers approximately 1/8 inch. (see instruction book)

54 NFPA Screen openings equal to 1 sq. in. for every GPM (pump capacity at 150%) (at LOWEST Water LEVEL) NFPA 20 (5.14.8)* Water Vel, 2 /sec Max Water Vel. 1 /sec Max * #12 Confirm proper submergence (Pump Length) * ( ) NFPA 20 (A ) (5.14.8)

55

56 Removable screens NFPA 20 ( ) Intake size NFPA 20 ( )*

57 With a vertical turbine fire pump a plugged screen will affect the water level in the sump and a plugged basket strainer on the bottom of the pump will reduce the total pump performance as the flow increases. NFPA Zebra Mussel Infestation ( )

58 VTFP INTAKE PROBLEMS.. Removable screens NFPA 20 ( ) Intake size??? NFPA 20 ( ) 2 ft/sec and 1 Sq. Inch per GPM at 150% Flow?

59 Pond Maintenance -OR- Lack of!!!

60

61

62

SPP Pumps Inc. Atlanta

SPP Pumps Inc. Atlanta SPP Pumps Inc. Atlanta UL Listed, FM Approved Fire Pump Sets Horizontal Split Case Pumps Flows from 200-5000 US GPM Vertical Turbine Flows to 5000 US GPM In-Line Pumps Flows to 750 US GPM End Suction Flows

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

CHAPTER. Fire Pumps FIRE PUMP OVERVIEW. Fire Pump Unit Defined. Fire Pump Unit Responsibility

CHAPTER. Fire Pumps FIRE PUMP OVERVIEW. Fire Pump Unit Defined. Fire Pump Unit Responsibility Fire Pumps CHAPTER 4 Commissioning of fire pumps is much more involved than commissioning of most other systems and must be completed correctly to verify operation of this critical equipment. This chapter

More information

TECHNICAL ADVISORY BULLETIN

TECHNICAL ADVISORY BULLETIN RISK CONTROL AND CLAIM ADVOCACY PRACTICE TECHNICAL ADVISORY BULLETIN November 2014 www.willis.com FIRE PUMP TESTING Fire pumps are a critical part of a fire protection system, especially when they are

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com

FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com FAIRBANKS NIJHUIS FIRE PUMPS www.fairbanksnijhuis.com FAIRBANKS NIJHUIS Long established as a leading fire pump manufacturer, Fairbanks Nijhuis offers a broad range of horizontal and vertical split case,

More information

Design & Construction Standards, Revised January 2013 5.21.30-1

Design & Construction Standards, Revised January 2013 5.21.30-1 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.

More information

Pressure Limiting Driver (PLD)

Pressure Limiting Driver (PLD) Pressure Limiting Driver (PLD) Discharge Pressure Control Suction Pressure Control June 9 2009 Mark Evans Clarke Fire Protection Products Justin Strousse Clarke Fire Protection Products Overview Discharge

More information

FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS. www.fairbanksnijhuis.com

FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS. www.fairbanksnijhuis.com FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS FAIRBANKS NIJHUIS Packaged Fire Pump Systems At the heart of our systems you ll find the Fairbanks Nijhuis pumps you ve relied on for over 90 years. Fairbanks

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As

More information

TOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump?

TOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump? KNOWLEDGE: K1.01 [3.3/3.5] P21 Which one of the following contains indications of cavitation in an operating centrifugal pump? A. Low flow rate with low discharge pressure. B. Low flow rate with high discharge

More information

FIRE FIGHTING PACKAGES

FIRE FIGHTING PACKAGES FIRE FIGHTING PACKAGES UNE 166.002 ISO 14001 0128 A Leader s Response Bombas Ideal S.A. has been manufacturing pumps since 1902. Throughout this period, the most advance technology available has been used

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around

More information

VERTICAL TURBINE AND PROPELLER PUMPS

VERTICAL TURBINE AND PROPELLER PUMPS VERTICAL TURBINE AND PROPELLER PUMPS INTRODUCTION Vertical Turbine and Propeller Pumps Model 7000 Series Turbine Pump Model 800 Series Axial Flow Propeller Pump Model 800 Series Mixed Flow Propeller Pump

More information

Axial and Mixed Flow Pumps for Large Volume Pumping

Axial and Mixed Flow Pumps for Large Volume Pumping Vertical Industrial and Process Axial and Mixed Flow for Large Volume Pumping Encased (Can ) Water and Process Liquid Vertical Turbine for Water Supply from Drilled Wells Vertical close coupled single

More information

Trash Pumps Models: 56200, 562000, 56201, 562001, 56300, 563000, 56301, 563001

Trash Pumps Models: 56200, 562000, 56201, 562001, 56300, 563000, 56301, 563001 Trash Pumps Models: 56200, 562000, 56201, 562001, 56300, 563000, 56301, 563001 Specifically designed pumps for heavy duty applications Handles solids with eas and simple to open and clean Standard roll

More information

SJT / SJM / SJP Large Vertical Pumps

SJT / SJM / SJP Large Vertical Pumps SJT / SJM / SJP Large Vertical Pumps The Heart of Your Process SJT, SJM, SJP Large Vertical Pumps Product Overview SJT Turbine Ns 1800 < 5000 nq 35 < 110 SJM Mixed Flow Ns 5800 < 8300 nq 113 < 161 SJP

More information

TECHNICAL INFORMATION Bulletin

TECHNICAL INFORMATION Bulletin Peerless Pump Company 2005 Dr. M.L. King Jr. Street, P.O. Box 7026, Indianapolis, IN 46207-7026, USA Telephone: (317) 925-9661 Fax: (317) 924-7338 www.peerlesspump.com www.epumpdoctor.com TECHNICAL INFORMATION

More information

TECHNICAL INFORMATION Bulletin

TECHNICAL INFORMATION Bulletin Peerless Pump Company 2005 Dr. M.L. King Jr. Street, P.O. Box 7026, Indianapolis, IN 46207-7026, USA Telephone: (317) 925-9661 Fax: (317) 924-7338 www.peerlesspump.com www.epumpdoctor.com TECHNICAL INFORMATION

More information

Para la protecció n de la vida y las propiedades, las Bombas de Incendio AC ofrece paquetizados que satisfacen cada necesidad.

Para la protecció n de la vida y las propiedades, las Bombas de Incendio AC ofrece paquetizados que satisfacen cada necesidad. BOMBAS DE INCENDIO EQUIPOS ESTACIONARIOS ITT Industries ISO 9001 A-C Fire Pumps System Para la protecció n de la vida y las propiedades, las Bombas de Incendio AC ofrece paquetizados que satisfacen cada

More information

300 Series PA Pump and Cooler Assemblies

300 Series PA Pump and Cooler Assemblies Type 300 Series PA Sizes 300 thru 370 (Page 1 of 9) 300 Series PA Pump and Cooler Assemblies Pump and Cooler Assemblies with Air/Oil Heat Exchanger When compact gear drives require assistance to dissipate

More information

OPERATION & MAINTENANCE MANUAL. for VERTICAL INLINE PUMPS

OPERATION & MAINTENANCE MANUAL. for VERTICAL INLINE PUMPS OPERATION & MAINTENANCE MANUAL for VERTICAL INLINE PUMPS PATTERSON PUMP COMPANY A SUBSIDIARY OF THE GORMAN-RUPP COMPANY PO Box 790 9201 Ayersville Road Toccoa, Georgia 30577 Telephone: 706-886-2101 SAFETY

More information

Goulds Water Technology

Goulds Water Technology APPLICATIONS Specifically designed for: Homes Farms Cottages Booster service SPECIFICATIONS Pump: Pipe connections: 1¼" NPT suction, 1" NPT discharge, 1" NPT drive (pressure) Pressure switch: AS4 preset

More information

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety

More information

Pump Maintenance - Repair

Pump Maintenance - Repair Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.

More information

Horizontal Split Case Fire Pumpset Diesel Engine Driven

Horizontal Split Case Fire Pumpset Diesel Engine Driven SERIES Horizontal Split Case Fire Pumpset Diesel Engine Driven Selected Models INTRODUCTION Lubi offers LHCD series state-of-the-art fire pumpset with diesel engine driven, horizontal split case pump.

More information

Model 1210C Battery Powered Pump Shown. Description

Model 1210C Battery Powered Pump Shown. Description 12 Volt DC Rotary Vane Pump Series 1200C Model 1210C Battery Powered Pump Shown Description of Included Models Model Number FR1205C FR1210C FR1211C FR2410C FR2411C Description Basic 12 volt DC pump with

More information

The cylinder head bolts tightening stages have been updated as listed in Table 1.

The cylinder head bolts tightening stages have been updated as listed in Table 1. NUMBER: 07 EPA04 MBE 4000-6 S.M. REF.: 1.2.2 ENGINE: MBE 4000 DATE: November 2007 SUBJECT: CYLINDER HEAD BOLTS TIGHTENING STAGES PUBLICATION: 6SE412 The cylinder head bolts tightening stages have been

More information

TRAINING BULLETIN Fire Apparatus Pump Test

TRAINING BULLETIN Fire Apparatus Pump Test TOPIC: TRAINING BULLETIN Fire Apparatus Pump Test EFFECTIVE DATE: 05/06 DOC NO: TB081 CROSS REF: INTRODUCTION District Fire Apparatus Pump Testing is completed on an annual basis. Currently, pump testing

More information

C. starting positive displacement pumps with the discharge valve closed.

C. starting positive displacement pumps with the discharge valve closed. KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the

More information

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS Products Include: 60 gpm eductors Style 3060, 3061, 3062 & 3070 95 gpm eductors Style

More information

Horizontal Split Case Fire Pumpset Electric Motor Driven 50 Hz

Horizontal Split Case Fire Pumpset Electric Motor Driven 50 Hz SERIES Horizontal Split Case Fire Pumpset Electric Motor Driven 50 Hz Selected Models INTRODUCTION Lubi offers LHCE series state-of-the-art fire pumpset with electric motor driven, horizontal split case

More information

NFPA 20 Update 2013 Edition. Revision Cycle. NFPA 20 Update 2013 5/1/2013. Goals and Objectives

NFPA 20 Update 2013 Edition. Revision Cycle. NFPA 20 Update 2013 5/1/2013. Goals and Objectives NFPA 20 Update 2013 Edition Kenneth E. Isman, PE P.E. FSFPE F.S.F.P.E. Vice President of Engineering NFPA 20 Update 2013 Edition Goals and Objectives By the end of this presentation, the participant will

More information

The Jockey Pump, an Important Part of a Fire Pump System.

The Jockey Pump, an Important Part of a Fire Pump System. The Jockey Pump, an Important Part of a Fire Pump System. May 18, 2008 A Jockey Pump is an important component of a fire pump system. The Jockey Pump is not as mundane, as many engineers, contractors and

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850

KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850 INSTALLATION AND OPERATING INSTRUCTIONS KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850 Product advantages Automatic float switch as water

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

Approval Standard for Centrifugal Fire Pumps (Horizontal, End Suction Type)

Approval Standard for Centrifugal Fire Pumps (Horizontal, End Suction Type) Approval Standard for Centrifugal Fire Pumps (Horizontal, End Suction Type) Class Number 1319 January 2015 Copyright 2015 by FM Approvals LLC. All rights reserved. Foreword FM Approvals are intended to

More information

N/NH Truck-mounted fire pump series

N/NH Truck-mounted fire pump series N/NH Truck-mounted fire pump series Normal pressure pump type N Combined normal- and high-pressure fire pump type NH Certified according to EN 1028 and UL classified Rosenbauer - N/NH Truck-mounted fire

More information

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP1100J FTA1100J Diesel Engine Fire Pump Controllers Product Description Description Firetrol combined automatic and manual Mark

More information

Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic energy).

Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic energy). HYDRAULIC MACHINES Used to convert between hydraulic and mechanical energies. Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic

More information

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS GAP.14.1.2.2 A Publication of Global Asset Protection Services LLC WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS INTRODUCTION A hydrant or other large-volume flow test is necessary for proper water

More information

Fire Protection Pumps

Fire Protection Pumps Experience In Motion Fire Protection Pumps Pump Supplier to the World Flowserve is the driving force in the global industrial pump marketplace. No other pump company in the world has the depth or breadth

More information

PUMPS TYPE OF PUMP PRESSURE/FLOW RATING CHARACTERISTICS. Centrifugal Low Pressure/High Flow Flow changes when

PUMPS TYPE OF PUMP PRESSURE/FLOW RATING CHARACTERISTICS. Centrifugal Low Pressure/High Flow Flow changes when PUMPS Pumps provide the means for moving water through the system at usable working pressures. The operation and maintenance of these pumps are some of the most important duties for many water utility

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions

More information

TROUBLESHOOTING GUIDE

TROUBLESHOOTING GUIDE RJS SELF-PRIMING SHALLOW WELL JET PUMPS a. Motor will not start: 1. No power to pressure switch due to blown fuses, open switches or loose connections. 2. Pump pressure switch not closed. b. Pump fails

More information

BOWIE PUMPS OPERATION - MAINTENANCE

BOWIE PUMPS OPERATION - MAINTENANCE BOWIE PUMPS OPERATION - MAINTENANCE PUMPING PRINCIPLE: The meshing owieeof the gears cause a slight depression, with the resulting enmeshing of the gears causing a vacuum drawing the fluid being pumped

More information

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

Volkswagen Jetta, Golf, GTI 1999, 2000 2.8 Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

Volkswagen Jetta, Golf, GTI 1999, 2000 2.8 Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17) 17 Engine-Lubrication (Page GR-17) Lubrication system components, removing and installing Oil filter housing, disassembling and assembling Oil pan, removing and installing Oil pressure and oil pressure

More information

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will

More information

Owner s Manual. Models: 2S5P & 3S5P OPERATION AND MAINTENANCE OF SELF-PRIMING CENTRIFUGAL TRASH PUMPS PEDESTAL DRIVE

Owner s Manual. Models: 2S5P & 3S5P OPERATION AND MAINTENANCE OF SELF-PRIMING CENTRIFUGAL TRASH PUMPS PEDESTAL DRIVE Owner s Manual Models: 2S5P & 3S5P OPERATION AND MAINTENANCE OF SELF-PRIMING CENTRIFUGAL TRASH PUMPS PEDESTAL DRIVE WARNING!! Installation & Operating Instructions Self-Priming Centrifugal Pump DO NOT

More information

Fire Pump Applications

Fire Pump Applications Fire Pump Applications Installation & Maintenance Manual Universal Joint Driveshafts www.cumminsfirepower.com Table of Contents Section 1 General 1.1 Introduction 1.2 Safety Precautions 1.3 Warranty Statement

More information

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6 - B 1 Product Detail Engineering Data... B2 Structural Support... B6 Engineering Specifications... B9 - B 2 Engineering Data REMARK: Do not use for construction. Refer to factory certified dimensions &

More information

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

3, 4, 6 & 8 Model H Series Alarm Check Valve Installation and Maintenance Guide ", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,

More information

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions. B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary

More information

Power Cube Open Source Ecology Page 1. Power Cube. Version 4

Power Cube Open Source Ecology Page 1. Power Cube. Version 4 Power Cube Open Source Ecology Page 1 Power Cube Version 4 Power Cube Open Source Ecology Page 2 Contents Table of Contents Power Cube... 1 Contents...2 Introduction... 3 Bill Of Materials...4 Discrete

More information

BLADDER SURGE CONTROL SYSTEM

BLADDER SURGE CONTROL SYSTEM PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures

More information

Module 9: Basics of Pumps and Hydraulics Instructor Guide

Module 9: Basics of Pumps and Hydraulics Instructor Guide Module 9: Basics of Pumps and Hydraulics Instructor Guide Activities for Unit 1 Basic Hydraulics Activity 1.1: Convert 45 psi to feet of head. 45 psis x 1 ft. = 103.8 ft 0.433 psi Activity 1.2: Determine

More information

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed

More information

Vertical selfpriming Side-Channel Pumps Type WPV

Vertical selfpriming Side-Channel Pumps Type WPV Vertical selfpriming Side-Channel Pumps Type WPV FIELD OF APPLICATION The side-channel pumps are selfpriming and operate more economically (better efficiency) than normal centrifugal pumps when handling

More information

IMPORTANT SAFETY NOTICE

IMPORTANT SAFETY NOTICE IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will minimize your risk of injury. ITT Goulds

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

Pumping Fuel & Fuel Oil

Pumping Fuel & Fuel Oil Pumping Fuel & Fuel Oil Fuels & Rotary Pumps Though the handling of fuel oil is not necessarily "challenging," the reliable handling of fuel oils is critical for heating and transportation systems. Rotary

More information

APPENDIX F VIBRATION TESTING PROCEDURE

APPENDIX F VIBRATION TESTING PROCEDURE APPENDIX F VIBRATION TESTING PROCEDURE Appendix F SPS-F-1 of 14 VIBRATION PERFORMANCE TESTING I. General Perform a vibration analysis on all motor driven equipment listed below after it is installed and

More information

The conditions below apply to the curves shown on the following pages.

The conditions below apply to the curves shown on the following pages. GENERAL INFORMATION STAINLESS STEEL, SILVERLINE, EVERGREEN & GOLDLINE SERIES PERFORMANCE CURVE CONDITIONS The conditions below apply to the curves shown on the following pages. a. The Performance curves

More information

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line

More information

world class fire pumps

world class fire pumps PRE-PAC world class fire pumps Protect Life and Property With Prepackaged Fire Control FIRE PUMP DIVISION I S O 9 0 0 1 C E R T I F I E D Patterson Pumps... A World Leader in Fire Control Patterson Pump

More information

2" & 3" Poly Wet Seal Pump Instruction Manual

2 & 3 Poly Wet Seal Pump Instruction Manual Always place the pump as close to the liquid to be pumped as possible. Keep the suction line short and with few bends. Keep the pump and engine on a level foundation. A poor foundation and a heavy suction

More information

World-Class Fire Suppression Pumping Solutions

World-Class Fire Suppression Pumping Solutions World-Class Fire Suppression Pumping Solutions Standing Guard for the Safety of Millions From Europe to Australia, South America to the Far East, commercial, residential and industrial facilities around

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID

More information

Air Eliminators and Combination Air Eliminators Strainers

Air Eliminators and Combination Air Eliminators Strainers Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.

More information

Minor losses include head losses through/past hydrants, couplers, valves,

Minor losses include head losses through/past hydrants, couplers, valves, Lecture 10 Minor Losses & Pressure Requirements I. Minor Losses Minor (or fitting, or local ) hydraulic losses along pipes can often be estimated as a function of the velocity head of the water within

More information

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES 4.0 PUMP CLASSES Pumps may be classified in two general types, dynamic and positive displacement. Positive displacement pumps

More information

Clark County Fire Prevention

Clark County Fire Prevention Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF

More information

Bell & Gossett Parts List DHP-650-PL. Replacement Parts for Hoffman Series VBF & Hoffman Series HBF. Boiler Feed Units

Bell & Gossett Parts List DHP-650-PL. Replacement Parts for Hoffman Series VBF & Hoffman Series HBF. Boiler Feed Units Bell & Gossett Parts List DHP-650-PL Replacement Parts for Hoffman Series VBF & Hoffman Series HBF Boiler Feed Units SERIES VBF & HBF Index How to use this Parts List...Page 3 30 VBF (Part number 161024

More information

Chapter 3.5: Fans and Blowers

Chapter 3.5: Fans and Blowers Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist

More information

TD01211 PIN: NX010 201007.2 nd Edition. Water Motor Alarm MODEL: NX010 TECHNICAL DATA

TD01211 PIN: NX010 201007.2 nd Edition. Water Motor Alarm MODEL: NX010 TECHNICAL DATA Water Motor Alarm MODEL: NX010 GENERAL DESCRIPTION TECHNICAL SPECIFICATIONS Model NX010 Working Water Pressure Range 5 to 175 psig 0.035 to 1.2 MPa (0.35 to 12 bar) Shipping Weight 11 lbs 5 kg Alarm Line

More information

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17)

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17) 17 Engine-Lubrication system (Page GR-17) Lubrication system components, removing and installing Oil pan, removing and installing Oil pressure and oil pressure switch, checking Dynamic oil pressure warning

More information

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority

More information

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE. SUBMERSIBLE PUMP selection A submersible pump consists of the following basic elements: < Bowl Assembly < Motor < Cable < Drop Pipe < Surface Plate (with)(without) discharge elbow DATA REQUIRED FOR SELECTION

More information

2100 AD 015 0009 Mirror Elevator Ball Nut Replacement Procedure

2100 AD 015 0009 Mirror Elevator Ball Nut Replacement Procedure 2100 AD 015 0009 Mirror Elevator Ball Nut Replacement Procedure Derek Guenther 1/28/2015 Rev. Purpose The purpose of this document is to describe the procedure necessary to replace one of the ball nuts

More information

4" SUBMERSIBLE PUMPS

4 SUBMERSIBLE PUMPS 4" SUBMERSIBLE PUMPS 4" SUBMERSIBLE PUMPS 50/60 HZ Multi-stage centrifugal submersible pumps for clean water in 4" wells. The 4" VSP pump series is carefully designed and manufactured for maximum resistant

More information

TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007

TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007 TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES 301.010 ANNUAL SERVICE TEST FOR FIRE HOSE EFFECTIVE: OCTOBER 2007 The Department will test all fire hose annually. The testing of fire hose determines its serviceability.

More information

Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description

Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description Worldwide Contacts www.tyco-fire.com Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description The TYCO Type D3 PROTECTO- SPRAY Nozzles are open (non-automatic) directional

More information

MODEL 300505 INSTALLATION INSTRUCTIONS

MODEL 300505 INSTALLATION INSTRUCTIONS WWW.BURCAM.COM 2190 Boul. Dagenais West TEL: 514.337.4415 LAVAL (QUEBEC) FAX: 514.337.4029 CANADA H7L 5X9 info@burcam.com Your pump has been carefully packaged at the factory to prevent damage during shipping.

More information

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION & MAINTENANCE MANUAL INSTALLATION, OPERATION & MAINTENANCE MANUAL Flanged Disk Check Valve with Strainer Ref. GENEBRE: 2450 2451 2452 1 INSTRUCTIONS FOR INSTALLATION, OPERATION & MAINTENANCE MANUAL 1. Spare parts... 3 1.1

More information

Pump Selection and Sizing (ENGINEERING DESIGN GUIDELINE)

Pump Selection and Sizing (ENGINEERING DESIGN GUIDELINE) Guidelines for Processing Plant Page : 1 of 51 Rev 01 Feb 2007 Rev 02 Feb 2009 Rev 03 KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru. (ENGINEERING DESIGN GUIDELINE)

More information

Vertical Pumps for the Oil & Gas Industry

Vertical Pumps for the Oil & Gas Industry Vertical Pumps for the Oil & Gas Industry ITT API Expert ITT Commitment ITT is committed to the Oil and Gas market, which is the largest segment of our business. We have been investing in technology to

More information

First Revision No. 147-NFPA 20-2013 [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 147-NFPA 20-2013 [ Global Input ] Submitter Information Verification. Committee Statement of 168 1/13/2014 1:38 PM First Revision No. 147-NFPA 20-2013 [ Global Input ] 11.4.1.3.3 Outlets shall terminate at least 12 ft above the finished ground level. Submitter Full Name: Chad Duffy Organization:

More information

AABC Specifications for Testing and Balancing HVAC Systems

AABC Specifications for Testing and Balancing HVAC Systems AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL

More information

Horizontal Jet Pumps 1/3-1-1/2 HP

Horizontal Jet Pumps 1/3-1-1/2 HP Horizontal Jet s 1/3-1-1/2 FW01 0909 Supersedes 0409 The CPJ, CPH and EK models feature the famous Flint and Walling Service Plus motor, available in either NEMA J or Uni-frame flange construction. The

More information

AIR LINE VALVES AND GAUGES

AIR LINE VALVES AND GAUGES AIR LINE VALVES AND GAUGES INGERSOLL-RAND AIR LINE VALVES AND GAUGES Maintaining consistent air pressure throughout the entire system is crucial for maximum performance and productivity. Ingersoll-Rand

More information

Pump Skid Fabrication for Magnetic Coupling. Rick Soltis Chief Mechanic City of Bedford

Pump Skid Fabrication for Magnetic Coupling. Rick Soltis Chief Mechanic City of Bedford Pump Skid Fabrication for Magnetic Coupling Rick Soltis Chief Mechanic City of Bedford Contents Magnetic Couplings What They Are, How They Work, Where They re Used Fabrication and Manufacturing of Pump

More information