1 5$7,*6 %. Stamford Range Please be advised that the ratings contained in this publication are for machines manufactured in Stamford, UK only, and were accurate at the time of going to print. Product ratings can and do vary as improvements and changes are constantly made to our products. Users are advised to verify all ratings, that are critical, with our Marketing Department.

2 RATINGS BOOK GLOSSARY Winding configurations and winding numbers 6 Wire Reconnectable Windings such as,, 07 and 6 have 6 exit leads brought into the terminal box, and hence may only be configured for series star and series delta connections. Star Ph 4W Output Terminals (U.V.W.N.) Delta Ph 4W Output Terminals (U.V.W.) Delta Ph 4W Output Terminals (U.V.W.) BC, UC, & HC4 W ire Reconnectable W indings such as, 4, 7 and 5 have exit leads brought into the terminal box and hence may be configured for series star, series delta or parallel star. Series Star Ph 4W Output Terminals (U.V.W.N.) Parallel Star PH 4W Output Terminals (U.V.W.N.) Series Delta Ph 4W Output Terminals (U.V.W.N.) It is also possible to connect wire windings for single phase operation in the double delta configuration. Doub le Delta Ph W Output Terminals (U.W.N.) (BC/UC only) 4 Wire Dedicated Windings such as 05 and 06 are specifically designed for single phase operation, and cannot be re-connected for three phase supply.

3 Rating definitions All ratings are based on altitude up to 000 m etres above sea level. BASE CONTINUOUS RATING Also known as BASIC CON TINUOUS - BR (ISO 858-) or C ontinuous R unning Duty - Duty type S (EN 6004-, IEC4- AND BS4999 part 0) or Continuous Duty (NEMA MG-). As the title suggests the generator is capable of supporting the specified kva rating at the specified ambient and power factor for continuous use without over stressing the insulation system. PEAK STANDBY RATING (40 C ambient temperature) This rating is defined in ISO 858- as PEAK C ONTIN UOUS PR it equates to S0 (rating with discrete constant loads) in EN6004- and STANDBY RATING in N EMA MG-. H ere the class H temperature rise is allow ed to increase above the BASE continuous rating. The result is an increased rating at the expense of reducing the lifetime of the generator by between to 6 tim es. Peak standby continuous rating offers an economical sizing for em ergency back up power supplie s. PEAK STANDBY RATING (7 C ambient temperature) EN states that with the customer s prior agreem ent an increase in rating m ay be made to account for a decrease in ambient temperature. The ratings quoted at 7 C ambient allow for an increased temperature rise to bring the operating tem perature of the generator to the sam e level as seen at 40 C am bient as above. Winding Numbers Used on Stamford AC Generators W indings for Stamford ac generators may be selected to give voltages for different connections as this table:- 50Hz W INDING EXIT SERIE S PA RALLE L SERIE S DO UBLE OT HER SERIE S PA RALLE L SERIE S DO UBLE OT HER NUMBER LEADS STAR STAR DELTA DELTA STAR STAR DELTA DELTA ( P HAS E) ( P HAS E) ( P HAS E) ( P HAS E) ( P HAS E) ( P HAS E) ( P HAS E) ( P HAS E) ( P HAS E) ( P HAS E) 05 * * ** *** Hz * Windings 05 & 06 provide a higher rating for single phase supply than can be achieved from re-connectable windings. ** Windin g 65 is used on LVSI 84 generators only. *** Winding 7 can only be supplied on BC 84 generators, an au xiliary windin g ca n be incorporated for use with SA 665 AVR.

4 INDEX - LOW VOLTAGE (UP TO 690V) CONTROL FREQUENCY AMBIENT TEMP SYSTEM APPLICATION POLES (Hz) TEMP RISE PAGE AVR (F) BASE 4 AVR (H) BASE 5 AVR (F) BASE 6 AVR (H) BASE 7 AVR (F) BASE 8 AVR (H) BASE AVR (H) PEAK 4 AVR (H) PEAK 6 AVR (F) BASE 8 AVR (H) BASE AVR (H) PEAK 6 AVR (H) PEAK 8 AVR (F) BASE 0 AVR (H) BASE 0 AVR (H) PEAK AVR (H) PEAK AVR (F) BASE AVR (H) BASE AVR (H) PEAK AVR (H) PEAK AVR MARINE (B) BASE 4 AVR MARINE (F) BASE 5 AVR MARINE (H) BASE 6 AVR MARINE (B) BASE 7 AVR MARINE (F) BASE 8 AVR MARINE (H) BASE 9 AVR MARINE (B) BASE 40 AVR MARINE (F) BASE 40 AVR MARINE (H) BASE 4 AVR MARINE (B) BASE 4 AVR MARINE (F) BASE 4 AVR MARINE (H) BASE 4 TRANSFORMER BASE 44 TRANSFORMER BASE 45

5 EASY PAGE RECOGNITION In addition to the indexes above, the pages in this book are marked in the bottom corner of each page with the following codes for ease of recognition. The top corner of each page is marked with the frequency, speed and number of poles. B F H SB 40 SB 7 T Base rating with class "B" temperature rise. Base rating with class "F" temperature rise. Base rating with class "H" temperature rise. Peak rating based on 40 C ambient temperature. Peak rating based on 7 C ambient temperature. Transformer controlled generators - not thermally rated.

6 ' - ' Pole CLASS "F" TEMP RISE 05 C PHASE ( WIRE ) ( WIRE ) POWER FACTOR SERIES STAR PARALLEL STAR SERIES DELTA DOUBLE DELTA WDG NO. kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw BCI 6D BCI 6E BCI 6F BCI 6G BCI 8H BCI 8J BCI 8K BCAI 6D BCAI 6E BCAI 6F BCAI 6G BCAI 6J BCAl 6L Pole CLASS "F" TEMP RISE 05 C POWER FACTOR VOLTS WDG NO. BCI 6D BCI 6E BCI 6F BCI 6G BCI 8H BCI 8J BCI 8K BCAI 6D BCAI 6E BCAI 6F BCAI 6G BCAI 6J BCAl 6L PHASE ( DEDICATED ) kva kw kva kw kva kw kva kw kva kw kva kw /40 4

7 CLASS "H" TEMP RISE 5 C Pole PHASE ( WIRE ) ( WIRE ) POWER FACTOR SERIES STAR PARALLEL STAR SERIES DELTA DOUBLE DELTA WDG NO. kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw BCI 6D BCI 6E BCI 6F BCI 6G BCI 8H BCI 8J BCI 8K BCAI 6D BCAI 6E BCAI 6F BCAI 6G BCAI 6J BCAl 6L CLASS "H" TEMP RISE 5 C Pole PHASE ( DEDICATED ) POWER FACTOR VOLTS WDG NO kva kw kva kw kva kw kva kw kva kw kva kw BCI 6D BCI 6E BCI 6F BCI 6G BCI 8H BCI 8J BCI 8K BCAI 6D BCAI 6E BCAI 6F BCAI 6G BCAI 6J BCAl 6L /40 5

8 Pole CLASS "F" TEMP RISE 05 C PHASE PHASE ( WIRE ) ( WIRE ) ( WIRE ) POWER FACTOR SERIES STAR PARALLEL STAR SERIES DELTA DOUBLE DELTA WDG NO. kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw BCI 6D BCI 6E BCI 6F BCI 6G BCI 8H BCI 8J BCI 8K BCAI 6D BCAI 6E BCAI 6F BCAI 6G BCAI 6J BCAl 6L Pole CLASS "F" TEMP RISE 05 C POWER FACTOR VOLTS WDG NO. BCI 6D BCI 6E BCI 6F BCI 6G BCI 8H BCI 8J BCI 8K BCAI 6D BCAI 6E BCAI 6F BCAI 6G BCAI 6J BCAl 6L PHASE ( DEDICATED ) kva kw kva kw kva kw kva kw kva kw kva kw /40 6

9 - CLASS "H" TEMP RISE 5 C Pole PHASE ( WIRE ) ( WIRE ) POWER FACTOR SERIES STAR PARALLEL STAR SERIES DELTA DOUBLE DELTA WDG NO. kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw BCI 6D BCI 6E BCI 6F BCI 6G BCI 8H BCI 8J BCI 8K BCAI 6D BCAI 6E BCAI 6F BCAI 6G BCAI 6J BCAl 6L CLASS "H" TEMP RISE 5 C Pole PHASE ( DEDICATED ) POWER FACTOR VOLTS WDG NO kva kw kva kw kva kw kva kw kva kw kva kw BCI 6D BCI 6E BCI 6F BCI 6G BCI 8H BCI 8J BCI 8K BCAI 6D BCAI 6E BCAI 6F BCAI 6G BCAI 6J BCAl 6L /40 7

10 CLASS "F" TEMP RISE 05 C PHASE ( WIRE ) ( WIRE ) POWER FACTOR SERIES STAR PARALLEL STAR SERIES DELTA DOUBLE DELTA WINDING NO. 5 kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw BCI 64A N/A N/A BCI 64B N/A N/A BCI 64C N/A N/A BCI 64D N/A N/A BCI 84E BCI 84F BCI 84G BCI 84H N/A N/A BCI 84J N/A N/A BCAI 64A N/A N/A BCAI 64B N/A N/A BCAI 64C N/A N/A BCAI 64D N/A N/A BCAI 64E BCAI 64F BCAI 64G BCLI 64A N/A N/A BCLI 64B N/A N/A BCLI 64C N/A N/A BCLI 64D N/A N/A BCLI 84E BCLI 84F UCI 4C UCI 4D UCI 4E N/A N/A UCI 4F UCI 4G UCDI 4C UCDI 4D UCDI 4E N/A N/A UCDI 4F UCDI 4G UCI 74C N/A N/A UCI 74D N/A N/A UCI 74E N/A N/A UCI 74F N/A N/A UCI 74G N/A N/A UCI 74H N/A N/A UCDI 74J N/A N/A N/A N/A #### 6.0 #### UCDI 74K N/A N/A N/A N/A #### 7.0 #### 05/40 8

11 CLASS "F" TEMP RISE 05 C PHASE ( DEDICATED) POWER FACTOR VOLTAGE WINDING NO kva kw kva kw kva kw kva kw kva kw kva kw BCI 64A BCI 64B BCI 64C BCI 64D BCI 84E BCI 84F BCI 84G BCI 84H BCI 84J BCAI 64A BCAI 64B BCAI 64C BCAI 64D BCAI 64E BCAI 64F BCAI 64G BCLI 64A BCLI 64B BCLI 64C BCLI 64D BCLI 84E BCLI 84F UCI 4C UCI 4D UCI 4E UCI 4F UCI 4G UCDI 4C UCDI 4D UCDI 4E UCDI 4F UCDI 4G UCI 74C UCI 74D UCI 74E UCI 74F UCI 74G UCI 74H UCDI 74J N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A UCDI 74K N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 05/40 9

12 CLASS "F" TEMP RISE 05 C PHASE ( / 6 WIRE ** ) ( WIRE ) POWER FACTOR SERIES STAR * PARALLEL STAR SERIES DELTA DOUBLE DELTA WINDING NO. / / / / 5 / 6 kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw HCI 444C HCI 444D HCI 444E HCI 444F HCKI 444C HCKI 444D HCKI 444E HCKI 444F HCI 544C HCI 544D HCI 544E HCI 544F HCKI 544C HCKI 544D HCKI 544E HCKI 544F HCI 64G HCI 64H HCI 64J HCI 64K HCI 74E HCI 74F HCI 74G HCI 74H HCI 74J N/A N/A HCKI 74E HCKI 74F HCKI 74G HCKI 74H THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING * Parallel star is applicable to windings and 5 only. ** HCI 74, HCKI 74, generator windings are 6 wire only, so parallel star connection is not possible. Winding 5 is not available on these generators, so parallel star connection giving 0V-45V is not possible. Refer to factory for Delta ratings. 05/40 0

13 CLASS "H" TEMP RISE 5 C PHASE ( WIRE ) ( WIRE ) POWER FACTOR SERIES STAR PARALLEL STAR SERIES DELTA DOUBLE DELTA WINDING NO. 5 kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw BCI 64A N/A N/A BCI 64B N/A N/A BCI 64C N/A N/A BCI 64D N/A N/A BCI 84E BCI 84F BCI 84G BCI 84H N/A N/A BCI 84J N/A N/A BCAI 64A N/A N/A BCAI 64B N/A N/A BCAI 64C N/A N/A BCAI 64D N/A N/A BCAI 64E BCAI 64F BCAI 64G BCLI 64A N/A N/A BCLI 64B N/A N/A BCLI 64C N/A N/A BCLI 64D N/A N/A BCLI 84E BCLI 84F UCI 4C UCI 4D UCI 4E N/A N/A UCI 4F UCI 4G UCDI 4C UCDI 4D UCDI 4E N/A N/A UCDI 4F UCDI 4G UCI 74C N/A N/A UCI 74D N/A N/A UCI 74E N/A N/A UCI 74F N/A N/A UCI 74G N/A N/A UCI 74H N/A N/A UCDI 74J N/A N/A N/A N/A UCDI 74K N/A N/A N/A N/A /40

14 CLASS "H" TEMP RISE 5 C PHASE ( DEDICATED ) POWER FACTOR VOLTS WINDING NO kva kw kva kw kva kw kva kw kva kw kva kw BCI 64A BCI 64B BCI 64C BCI 64D BCI 84E BCI 84F BCI 84G BCI 84H BCI 84J BCAI 64A BCAI 64B BCAI 64C BCAI 64D BCAI 64E BCAI 64F BCAI 64G BCLI 64A BCLI 64B BCLI 64C BCLI 64D BCLI 84E BCLI 84F UCI 4C UCI 4D UCI 4E UCI 4F UCI 4G UCDI 4C UCDI 4D UCDI 4E UCDI 4F UCDI 4G UCI 74C UCI 74D UCI 74E UCI 74F UCI 74G UCI 74H UCDI 74J N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A UCDI 74K N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 5/40

15 CLASS "H" TEMP RISE 5 C PHASE ( / 6 WIRE ** ) ( WIRE ) POWER FACTOR VOLTS: SERIES STAR * PARALLEL STAR SERIES DELTA DOUBLE DELTA WINDING NO. / / / / 5 / 6 kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw HCI 444C HCI 444D HCI 444E HCI 444F HCKI 444C HCKI 444D HCKI 444E HCKI 444F HCI 544C HCI 544D HCI 544E HCI 544F HCKI 544C HCKI 544D HCKI 544E HCKI 544F HCI 64G HCI 64H HCI 64J HCI 64K HCI 74E HCI 74F HCI 74G HCI 74H HC I74J N/A N/A HCKI 74E HCKI 74F HCKI 74G HCKI 74H THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING * Parallel star is applicable to windings and 5 only. ** HCI 74, HCKI 74, generator windings are 6 wire only, so parallel star connection is not possible. Winding 5 is not available on these generators, so parallel star connection giving 0-45V is not possible. Refer to factory for Delta ratings. 5/40

16 CLASS "H" TEMP RISE 50 C (PEAK STANDBY RATING) PHASE PHASE ( WIRE ) ( WIRE ) ( DEDICATED ) POWER FACTOR SERIES STAR PARALLEL STAR SERIES DELTA DOUBLE DELTA 0-40 OTHER WINDING NO kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw BCI 64A BCI 64B BCI 64C BCI 64D THESE GENERATORS ARE NOT OFFERED AT THIS RATING BCI 84E N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A BCI 84F BCI 84G BCI 84H N/A N/A BCI 48J N/A N/A NOT OFFERED AT THIS RATING BCAI 64A BCAI 64B BCAI 64C BCAI 64D BCAI 64E BCAI 64F BCAI 64G BCLI 64A BCLI 64B BCLI 64C BCLI 64D BCLI 84E BCLI 84F THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING UCI 4C UCI 4D UCI 4E N/A N/A UCI 4F UCI 4G UCDI 4C UCDI 4D UCDI 4E N/A N/A UCDI 4F UCDI 4G UCI 74C N/A N/A UCI 74D N/A N/A UCI 74E N/A N/A UCI 74F N/A N/A UCI 74G N/A N/A UCI 74H N/A N/A UCDI 74J N/A N/A N/A N/A UCDI 74 K N/A N/A N/A N/A THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING NOT OFFERED AT THIS RATING 50/40 4

17 CLASS "H" TEMP RISE 50 C (PEAK STANDBY RATING) PHASE PHASE ( / 6 WIRE ** ) ( WIRE ) ( DEDICATED ) POWER FACTOR SERIES STAR * PARALLEL STAR SERIES DELTA DOUBLE DELTA 0-40 OTHER WINDING NO. / / / / 5 / kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw HCI 444C HCI 444D HCI 444E HCI 444F HCKI 444C HCKI 444D HCKI 444E HCKI 444F HCI 544C HCI 544D HCI 544E HCI 544F HCKI 544C HCKI 544D HCKI 544E HCKI 544F HCI 64G HCI 64H HCI 64J HCI 64K HCI 74E HCI 74F HCI 74G HCI 74H HCI 74J N/A N/A HCKI 74E HCKI 74F HCKI 74G HCKI 74H THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING * Parallel star is applicable to windings and 5 only. ** HCI 74, HCKI 74, generator windings are 6 wire only, so parallel star connection is not possible. Winding 5 is not available on these generators, so parallel star connection giving 0-45V is not possible. Refer to factory for Delta ratings. 5 50/40

18 7 C AMBIENT TEMPERATURE CLASS "H" TEMP RISE 6 C (PEAK STANDBY RATING) PHASE PHASE ( WIRE ) ( WIRE) ( DEDICATED ) POWER FACTOR SERIES STAR PARALLEL STAR SERIES DELTA DOUBLE DELTA 0-40 OTHER WINDING NO kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw BCI 64A BCI 64B BCI 64C BCI 64D THESE GENERATORS ARE NOT OFFERED AT THIS RATING BCI 84E N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A BCI 84F BCI 84G BCI 84H N/A N/A BCI 84J N/A N/A THESE GENERATORS ARE NOT OFFERED AT THIS RATING BCAI 64A BCAI 64B BCAI 64C BCAI 64D BCAI 64E BCAI 64F BCAI 64G BCLI 64A BCLI 64B BCLI 64C BCLI 64D BCLI 84E BCLI 84F THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING UCI 4C UCI 4D UCI 4E N/A N/A UCI 4F UCI 4G UCDI 4C UCDI 4D UCDI 4E N/A N/A UCDI 4F UCDI 4G UCI 74C N/A N/A UCI 74D N/A N/A UCI 74E N/A N/A UCI 74F N/A N/A UCI 74G N/A N/A UCI 74H N/A N/A UCDI 74J N/A N/A N/A N/A UCDI 74K N/A N/A N/A N/A THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING NOT OFFERED AT THIS RATING 6/7 6

19 7 C AMBIENT TEMPERATURE CLASS "H" TEMP RISE 6 C (PEAK STANDBY RATING) PHASE PHASE ( / 6 WIRE ** ) ( WIRE ) ( DEDICATED ) POWER FACTOR SERIES STAR * PARALLEL STAR SERIES DELTA DOUBLE DELTA 0-40 OTHER WINDING NO. / / / / 5 / kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw HCI 444C HCI 444D HCI 444E HCI 444F HCKI 444C HCKI 444D HCKI 444E HCKI 444F HCI 544C HCI 544D HCI 544E HCI 544F HCKI 544C HCKI 544D HCKI 544E HCKI 544F HCI 64G HCI 64H HCI 64J HCI 64K HCI 74E HCI 74F HCI 74G HCI 74H HCI 74J N/A N/A HCKI 74E HCKI 74F HCKI 74G HCKI 74H THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING * Parallel star is applicable to windings and 5 only. ** HCI 74, HCKI 74, generator windings are 6 wire only, so parallel star connection is not possible. Winding 5 is not available on these generators, so parallel star connection giving 0-45V is not possible. Refer to factory for Delta ratings. 6/7 7

20 Pole CLASS "F" TEMP RISE 05 C ( WIRE ) POWER FACTOR SERIES STAR PARALLEL STAR SERIES DELTA WINDING NO. 4 7 kva kw kva kw kva kw kva kw kva kw kva kw BCI 64A BCI 64B BCI 64C BCI 64D BCI 84E BCI 84F BCI 84G BCI 84H BCI 84J BCAI 64A BCAI 64B BCAI 64C BCAI 64D BCAI 64E BCAI 64F BCAI 64G BCLI 64A BCLI 64B BCLI 64C BCLI 64D BCLI 84E BCLI 84F UCI 4C UCI 4D UCI 4E UCI 4F UCI 4G UCDI 4C UCDI 4D UCDI 4E UCDI 4F UCDI 4G UCI 74C UCI 74D UCI 74E UCI 74F UCI 74G UCI 74H UCDI 74J N/A N/A UCDI 74K N/A N/A N/A N/A 05/40 8

21 CLASS "F" TEMP RISE 05 C ( / 6 WIRE * ) POWER FACTOR SERIES STAR * PARALLEL STAR SERIES DELTA WINDING NO. 4 / / / / / 7 / 07 kva kw kva kw kva kw kva kw kva kw kva kw HCI 444C HCI 444D HCI 444E N/A N/A HCI 444F HCKI 444C HCKI 444D HCKI 444E N/A N/A HCKI 444F HCI 544C HCI 544D HCI 544E HCI 544F HCKI 544C HCKI 544D HCKI 544E HCKI 544F HCI 64G HCI 64H HCI 64J, HCI 64K, HCI 74E HCI 74F HCI 74G 4 N/A N/A HCI 74H HCI 74J N/A N/A HCKI 74E HCKI 74F HCKI 74G 4 N/A N/A HCKI 74H * Parallel star is applicable to windings, 4 and 7 only. ** HCI 74, HCKI 74, generator windings are 6 wire only, so parallel star connection is not possible. 4 5 Figures given for winding /4 apply to 80V only. Winding 4 is not available on these generators, so parallel star connection giving 90-08V is not possible. Winding 7 is not available on these generators, so parallel star connection giving 00V is not possible. Refer to factory for Delta ratings. Figures given for windings /4 apply to V only. 9 05/40

22 CLASS "F" TEMP RISE 05 C PHASE PHASE ( WIRE ) ( DEDICATED ) POWER FACTOR DOUBLE DELTA OTHER WINDING NO kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw BCI 64A BCI 64B BCI 64C BCI 64D BCI 84E BCI 84F BCI 84G BCI 84H BCI 84J BCAI 64A BCAI 64B BCAI 64C BCAI 64D BCAI 64E BCAI 64F BCAI 64G BCLI 64A BCLI 64B BCLI 64C BCLI 64D BCLI 84E BCLI 84F UCI 4C UCI 4D UCI 4E UCI 4F UCI 4G UCDI 4C UCDI 4D UCDI 4E UCDI 4F UCDI 4G UCI 74C UCI 74D UCI 74E UCI 74F UCI 74G UCI 74H UCDI 74J N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A UCDI 74K N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 05/40 0

23 CLASS "F" TEMP RISE 05 C PHASE PHASE ( WIRE ) ( DEDICATED ) POWER FACTOR DOUBLE DELTA OTHER WINDING NO kva kw kva kw kva kw kva kw kva kw HCI 444C HCI 444D HCI 444E HCI 444F HCKI 444C HCKI 444D HCKI 444E HCKI 444F HCI 544C HCI 544D HCI 544E HCI 544F HCKI 544C HCKI 544D HCKI 544E HCKI 544F THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING HCI 64G HCI 64H HCI 64J HCI 64K HCI 74E HCI 74F HCI 74G HCI 74H HCI 74J HCKI 74E HCKI 74F HCKI 74G HCKI 74H THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING THESE GENERATORS ARE NOT OFFERED AT THIS RATING 05/40

24 CLASS "H" TEMP RISE 5 C ( WIRE ) POWER FACTOR SERIES STAR PARALLEL STAR SERIES DELTA WINDING NO. 4 7 kva kw kva kw kva kw kva kw kva kw kva kw BCI 64A BCI 64B BCI 64C BCI 64D BCI 84E BCI 84F BCI 84G BCI 84H BCI 84J BCAI 64A BCAI 64B BCAI 64C BCAI 64D BCAI 64E BCAI 64F BCAI 64G BCLI 64A BCLI 64B BCLI 64C BCLI 64D BCLI 84E BCLI 84F UCI 4C UCI 4D UCI 4E UCI 4F UCI 4G UCDI 4C UCDI 4D UCDI 4E UCDI 4F UCDI 4G UCI 74C UCI 74D UCI 74E UCI 74F UCI 74G UCI 74H UCDI 74J N/A N/A UCDI 74K N/A N/A N/A N/A 5/40

25 - CLASS "H" TEMP RISE 5 C ( / 6 WIRE ** ) POWER FACTOR SERIES STAR * PARALLEL STAR SERIES DELTA WINDING NO. 4 / / / / / 7 / 07 kva kw kva kw kva kw kva kw kva kw kva kw HCI 444C HCI 444D HCI 444E N/A N/A HCI 444F HCKI 444C HCKI 444D HCKI 444E N/A N/A HCKI 444F HCI 544C HCI 544D HCI 544E HCI 544F HCKI 544C HCKI 544D HCKI 544E HCKI 544F HCI 64G HCI 64H , HCI 64J , HCI 64K HCI 74E HCI 74F HCI 74G 4 N/A N/A HCI 74H HCI 74J 4 N/A N/A N/A N/A HCKI 74E HCKI 74F HCKI 74G 4 N/A N/A HCKI 74H * Parallel star is applicable to windings, 4 and 7 only. ** HCI 74, HCKI 74, generator windings are 6 wire only, so parallel star connection is not possible. 4 5 Figures given for winding /4 apply to 80V only. Winding 4 is not available on these generators, so parallel star connection giving 90-08V is not possible. Winding 7 is not available on these generators, so parallel star connection giving 00V is not possible. Refer to factory for Delta ratings. Figures given for windings /4 apply to 46V only. 5/40

26 CLASS "H" TEMP RISE 5 C PHASE PHASE ( WIRE ) ( DEDICATED ) POWER FACTOR DOUBLE DELTA OTHER WINDING NO kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw kva kw BCI 64A BCI 64B BCI 64C BCI 64D BCI 84E BCI 84F BCI 84G BCI 84H BCI 84J BCAI 64A BCAI 64B BCAI 64C BCAI 64D BCAI 64E BCAI 64F BCAI 64G BCLI 64A BCLI 64B BCLI 64C BCLI 64D BCLI 84E BCLI 84F UCI 4C UCI 4D UCI 4E UCI 4F UCI 4G UCDI 4C UCDI 4D UCDI 4E UCDI 4F UCDI 4G UCI 74C UCI 74D UCI 74E UCI 74F UCI 74G UCI 74H UCDI 74J N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A UCDI 74K N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 5/40 4

STAMFORD Product Guide

STAMFORD Product Guide Product Guide MOVE 2005 7/11/06 15:46 Page 1 STAMFORD Product Guide R There for you TM Versatile, robust and reliable brushless ac generators up to 2750kVA Product Guide MOVE 2005 7/11/06 15:46 Page 2

More information

BCI184E - Technical Data Sheet

BCI184E - Technical Data Sheet BCI184E - Technical Data Sheet BCI184E SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS PI144K - Winding 311 Technical Data Sheet PI144K SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section

More information

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet PI044E - Winding 311 Technical Data Sheet PI044E SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

PM734F - Technical Data Sheet Winding 28

PM734F - Technical Data Sheet Winding 28 - Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including

More information

UCI274C - Technical Data Sheet

UCI274C - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

UCI274H - Technical Data Sheet

UCI274H - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet HCM434F - Winding 311 Technical Data Sheet HCM434F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards

More information

PI734D - Technical Data Sheet

PI734D - Technical Data Sheet PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

PI734B - Technical Data Sheet

PI734B - Technical Data Sheet PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

3790 en - 06.2007 / d. Alternators LSA 46.2-4 Pole. Electrical and mechanical data

3790 en - 06.2007 / d. Alternators LSA 46.2-4 Pole. Electrical and mechanical data 379 en - 6.7 / d Alternators LSA 46.2-4 Pole Electrical and mechanical data SPECIALLY ADAPTED FOR APPLICATIONS The LSA 46.2 alternator is designed to be suitable for typical generator applications, such

More information

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw ,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted

More information

Atlas Copco Generators

Atlas Copco Generators Atlas Copco Generators QIX 15 - QIX 540 16 kva LTP to 549 kva LTP at 50 & 60 Hz The QIX options include Earth leakage relay Qc generating set control panels for all standby and/or paralleling applications

More information

Transformers from 25va to 500kva. Standard despatch in days not weeks

Transformers from 25va to 500kva. Standard despatch in days not weeks Transformers from 25va to 500kva Standard despatch in days not weeks JMS Transformers Ltd 20 Ivatt Way Westwood Business Park Peterborough PE3 7PG UK Tel: +44 (0)1733 760000 Fax +44 (0)1733 760004 e-mail:

More information

Spark-ignited generator set

Spark-ignited generator set Specification sheet Spark-ignited generator set 30 60 kw standby EPA emissions Description Cummins Power Generation commercial generator sets are fully integrated power generation systems providing optimum

More information

CRK 2-130 A-W-A-BUBV 85805906

CRK 2-130 A-W-A-BUBV 85805906 GRUNDFOS DATA BOOKLET CRK 2-13 A-W-A-BUBV 858596 Grundfos Pump 497113 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crk2/497113/crk-2-13-13-a-w-a-auuv.html

More information

Data Sheet. AC Industrial Electric Motors

Data Sheet. AC Industrial Electric Motors Data Pack B Issued ovember 2005 1502325812 Data Sheet AC Industrial Electric Motors Standards organisations The RS-ABB range of ac induction motors is produced to common European standards, these being

More information

Marine Generating Sets 3.7 to 50 kva

Marine Generating Sets 3.7 to 50 kva Marine Generating Sets 3.7 to 50 kva The Marine Engineer s Preference BetaSet - Standard Marine Generators Beta Marine has considerable experience from over twenty years of manufacturing marine generating

More information

Three phase circuits

Three phase circuits Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Buck - Boost Transformers

Buck - Boost Transformers Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single

More information

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The

More information

CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24" 1 X

CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24 1 X CURRENT TRANSFORMER MODEL 546 1.10" I.D. PAGE No 1-38 REV 15DEC00 TERMINAL OPTION LEAD WIRE OPTION 1.10 0 1.20 2.55 3.00 3.47 0.18 x 0.31 SLOT ( 2 PLACES) 8-32 BRASS STUD (2 PLACES) UL1015 #16 AWG LEAD

More information

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

Figure. 1 - Split Phase 240/120V circuit (180 phase shift) This technical note describes the option of connecting the 60Hz XW Inverter/Charger to a three-phase source by using a transformer to convert the AC source to split-phase 240/120V. INTRODUCTION: Split-phase

More information

ENERGY SOLUTIONS RESIDENTIAL STORAGE BATTERY SYSTEM

ENERGY SOLUTIONS RESIDENTIAL STORAGE BATTERY SYSTEM ENERGY SOLUTIONS RESIDENTIAL STORAGE BATTERY SYSTEM MAKING SMART TOWNS, BUILDING SMART COMMUNITIES WHY PANASONIC? RESIDENTIAL STORAGE BATTERY SYSTEM The next evolution in solar energy solutions. Panasonic

More information

Diesel Generating Set

Diesel Generating Set MODEL Standby Power(50Hz) Prime Power(50Hz) 44KW /55KVA 40KW /50KVA Standard Features General Features: Engine( DCEC Cummins 4BTA3.9 -G) Radiator 40 O C max,fans are driven by belt, with safety guard 24V

More information

Three-Phase Electric Power Distribution for Computer Data Centers

Three-Phase Electric Power Distribution for Computer Data Centers Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of

More information

Drive Technology \ Drive Automation \ System Integration \ Services. DR Motor Common Connection Diagrams

Drive Technology \ Drive Automation \ System Integration \ Services. DR Motor Common Connection Diagrams Drive Technology \ Drive Automation \ System Integration \ Services DR Motor Common Connection Diagrams Edition 06/2010 9PD0058 / US SEW-EURODRIVE Driving the world Table of Contents Overview... 5 Important

More information

NIKY and NIKY S. UPS SINGLE-PHASE from 600 to 3000 VA GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

NIKY and NIKY S. UPS SINGLE-PHASE from 600 to 3000 VA GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES NIKY and NIKY S UPS SINGLE-PHASE from 600 to 3000 VA GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES Niky S line interactive Sinusoidal output Microprocessor control MODEM/LAN telephone

More information

ENERGY-SAVINg DRIVE PACKAGE DE ES FR IT. Overview

ENERGY-SAVINg DRIVE PACKAGE DE ES FR IT. Overview ENERGY-SAVINg DRIVE PACKAGE SPriPM Motor & YASKAWA V1000 Inverter Drive EN DE ES FR IT Overview - Super Premium IPM Motor & YASKAWA V1000 Inverter Drive The Motor-Inverter Package was developed to support

More information

Definition AC Power Distribution

Definition AC Power Distribution COMMON AC POWER DISTRIBUTION CONFIGURATIONS The input voltage needed to power electronic equipment is provided by the manufacture in the product specifications. Matching this requirement to the facility

More information

Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P

Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P Technical Data Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P Topic Page 1609-P Specifications 2 1609-P Approximate Dimensions and Shipping Weights 3 Additional Resources

More information

for Energy Storage System, New & Renewable Energy

for Energy Storage System, New & Renewable Energy PCS Total Solution for Energy Storage System, New & Renewable Energy The product competitiveness of our customers will be more upgraded with PLASPO s power conversion technology The perfect power conversion

More information

Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com

Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com CURRENT TRANSFORMER MODEL J " x 7" PAGE No 2-2 REV 8DEC00 TERMINAL OPTION LEAD WIRE OPTION 8-2 BRASS SCREW TERMINALS (2 PLACES) SEE NOTE 9 6 9 8 6 Ø 2 9 (4 PLACES) UL 05 #6 AWG LEAD WIRE, STANDARD LENGTH

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

Re-defining the utility-scale inverter

Re-defining the utility-scale inverter Re-defining the utility-scale inverter We believe in green energy in the ability to meet and contribute to growing power demands while supporting a smart grid that serves a smart society. Solution at a

More information

TYPE APPROVAL CERTIFICATE

TYPE APPROVAL CERTIFICATE DET NORSKE VERITAS TYPE APPROVAL CERTIFICATE CERTIFICATE NO. E-12702 This is to certify that the Electric Motor with type designation(s) RN series 56 up to 315L Manufactured by Rotor B.V. EIBERGEN, Netherlands

More information

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors APPENDIX APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS RJ12 connectors Pin # 1 Signal Name Not Used 2 +TR Description + Data Line 3 +R Remote OFF Required or Remote OFF control 4 -TR 5 Not Used 6 RTN -

More information

Annex-A TECHNICAL SPECIFICATION

Annex-A TECHNICAL SPECIFICATION Annex-A TECHNICAL SPECIFICATION FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 0.4kV (2,000kVA) DIESEL GENERATOR 1 1.0 SCOPE This specification covers the requirements of design, manufacture, delivery

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

Baldor Electric Position on DOE Small Motor Rule

Baldor Electric Position on DOE Small Motor Rule Baldor Electric Position on DOE Small Motor Rule WP0035 WP0034 Page 1 of 6 US Integral DOE Small HP Motor Rule Rule Baldor Electric Position on DOE Small Motor Rule 10/28/14 On March 9, 2010 the US Department

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

R448 & R448 V50 A.V.R.

R448 & R448 V50 A.V.R. Armature + 6- This manual is to be given to the end user F1 ST5 Field Slow fuse 250V 10 A with LAM without LAM 10 Yellow 11 Red 12 Black 9 Green X2 Z1 X1 Z2 E+ E- 0V 110 22 ST3 requency ST10 50Hz 60Hz

More information

FAULT FINDING MANUAL. For Stamford AC Generators

FAULT FINDING MANUAL. For Stamford AC Generators FAULT FINDING MANUAL For Stamford AC Generators 1 SAFETY PRECAUTIONS Test procedures recommended in this manual assume that the reader is fully conversant with electrical safety principles, and is familiar

More information

OJ L 191, 23.7.2009, p. 26. OJ L 2, 7.1.2014, p. 1.

OJ L 191, 23.7.2009, p. 26. OJ L 2, 7.1.2014, p. 1. Table of Contents 1. Purpose of the guidelines and disclaimer... 2 1.1. The Regulations... 2 2. Scope... 2 3. Historic developments... 4 4. Scope and Requirements... 5 4.1. Scope... 5 4.2. Requirements...

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

Sub sea Cable Technology

Sub sea Cable Technology EERA DeepWind 2014 Sub sea Cable Technology Hallvard Faremo SINTEF Energy Research Brief presentation of: Wind Farm Cable R&D project Technology for a better society 1 High Voltage Subsea Cables Networking

More information

Floodlight Range Installation Guide

Floodlight Range Installation Guide SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

Server Technology Intl.

Server Technology Intl. Server Technology, Inc. 3-Phase Power in the Data Center White Paper STI-100-005 North America/ASIA EMEA Server Technology, Inc. Server Technology Intl. 1040 Sandhill Drive Sienna Court Reno, NV 89521

More information

Avoiding AC Capacitor Failures in Large UPS Systems

Avoiding AC Capacitor Failures in Large UPS Systems Avoiding AC Capacitor Failures in Large UPS Systems White Paper #60 Revision 0 Executive Summary Most AC power capacitor failures experienced in large UPS systems are avoidable. Capacitor failures can

More information

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A Active harmonic conditioner from 20 to 480 A Contents 1 - Installations concerned... 2 1.1 - New installations... 2 1.2 - Existing installations... 2 2 - General... 2 2.1 - Scope... 2 2.2 - Applicable

More information

Life Expectancy : Class A Class B Class C Class D 30,000hrs 10,000hrs 3,000hrs 1000hrs

Life Expectancy : Class A Class B Class C Class D 30,000hrs 10,000hrs 3,000hrs 1000hrs 3.2 Motor Run Capacitors : continuous operation ypical Applications : Motor Run Capacitor ideal for various motor applications in washing machine, air conditioner, electric water pump, power factor collection

More information

Distribution Dry Type Transformers

Distribution Dry Type Transformers 8 TRASFORMERS Distribution Dry Type Transformers Table (Contact Sales office for List Price) (commonly used) 1a. 115 C Rise F 1b. 80 C Rise B 4. Wall Brackets1 W 6. Low noise XdB below std. LX Type bg

More information

STANDBY 150 ekw 188 kva PRIME 135 ekw 169 kva

STANDBY 150 ekw 188 kva PRIME 135 ekw 169 kva DIESEL GENERATOR SET FEATURES Image shown may not reflect actual package. STANDBY 150 ekw 188 kva PRIME 135 ekw 169 kva Caterpillar is leading the power generation marketplace with Power Solutions engineered

More information

1 Temperature Derating Guide

1 Temperature Derating Guide VLT HVAC Drive FC 02 Application Note Temperature Derating Guide Temperature Derating Guide.. Abstract This paper provides detailed data regarding the operation of the VLT HVAC Drive FC02 at varying ambient

More information

Automatic Voltage Regulator User s Manual

Automatic Voltage Regulator User s Manual Resp. dept. R&D We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. Copyright

More information

Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting, excitation system

Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting, excitation system SYNCHRONOUS MACHINES Tze-Fun Chan Hong Kong Polytechnic University, Hong Kong, China Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting,

More information

Generators Selection and Pricing Catalog

Generators Selection and Pricing Catalog Marathon Generators Sales Team Goodall Industrial Equipment Power Source Midwest, Inc. FJ Toolan Inc. EPAC Sales & Service P.O. Box 354 Natick, MA 01760 Phone: 508/651-2668 Fax: 508/655-3332 E-mail: sales@goodallsales.com

More information

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H. POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

How the efficiency of induction motor is measured?

How the efficiency of induction motor is measured? How the efficiency of induction motor is measured? S. Corino E. Romero L.F. Mantilla Department of Electrical Engineering and Energy E.T.S.I.I. y T. Universidad de Cantabria Avda de Los Castros, 395 Santander

More information

0.84" x 2.00" Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com SPLIT CORE CURRENT TRANSFORMER MODEL 1SP.

0.84 x 2.00 Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com SPLIT CORE CURRENT TRANSFORMER MODEL 1SP. SPLIT CORE CURRENT MODEL 1SP 0.84" x 2.00" PAGE No 3-2 REV 18DEC00 UL 1015 LEAD WIRE, STANDARD LENGTH IS 36 E DIMENSIONS A = 0.84 MIN B = 2.00 MIN C = 3.31 MAX D = 3.09 MAX E = 0.61 MAX F = 0 MAX F C B

More information

Medium voltage product. Instrument transformers for indoor applications Product overview

Medium voltage product. Instrument transformers for indoor applications Product overview Medium voltage product Instrument transformers for indoor applications Product overview 02 Contents Introduction Current transformers Supporting type 6 TPU, TPE 7 KOFA, IHBF 10 Dummy Bus type 8 KOKS 12,

More information

VLT Series 3500 Adjustable Frequency Drive Instruction Manual

VLT Series 3500 Adjustable Frequency Drive Instruction Manual Adjustable Frequency Drive Instruction Manual VLT Series 3500 Instruction Manual 175R5237 - Document Version 5.00 This manual applies to all VLT Series 3502-3800 Adjustable Frequency Drives with software

More information

ELECTROPUTERE ROTATING ELECTRICAL MACHINES DIVISION

ELECTROPUTERE ROTATING ELECTRICAL MACHINES DIVISION ELECTROPUTERE ROTATING ELECTRICAL MACHINES DIVISION SC ELECTROPUTERE SA SC ELECTROPUTERE SA 1. Vision, Mission, Values SC ELECTROPUTERE SA 2. LOCATION Craiova: Located in the South West of the country,

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

Three-phase AC circuits

Three-phase AC circuits Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

GTEC transfer switch open transition

GTEC transfer switch open transition GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS

More information

We will discuss common industrial applications with guides for the proper use of electric motors on these.

We will discuss common industrial applications with guides for the proper use of electric motors on these. INTRODUCTION: Baldor Electric Company has prepared this Specifiers Guide to help you cover all the bases when you are specifying electric motors. It will cover in a generic way most of the subjects which

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

Screened cable and data cable segregation

Screened cable and data cable segregation December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;

More information

Presentation of the France Transfo factories

Presentation of the France Transfo factories Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15

More information

APS100 Rental Generator Set Specification

APS100 Rental Generator Set Specification BARTONVIE * CEDAR RAPIDS * DAVENPORT * EAST PEORIA * HANNIBA * MOBERY * ROCK FAS * SPRINGFIED * URBANA APS100 Rental Generator Set Specification STANDBY 100 kw 60 Hz/PRIME 90 kw 60 Hz FEATURES EPA TIER

More information

Power Take-Off Generators

Power Take-Off Generators Power Take-Off Generators PTO Generators, 15 kw 100 kw Single & Three Phase PTO Carts & PTO Shafts Two Five Year Limited Warranty Represented By: Viking Power Products Co. PO Box 127 Lewisville, PA 19351

More information

80 Series - Modular timers 16 A. Features 80.01 80.11

80 Series - Modular timers 16 A. Features 80.01 80.11 80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h

More information

Comparative study for cables and busbars

Comparative study for cables and busbars Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary

More information

HIGH SPEED PERMANENT MAGNET SYNCHRONOUS MOTOR / GENERATOR DESIGN FOR FLYWHEEL APPLICATIONS

HIGH SPEED PERMANENT MAGNET SYNCHRONOUS MOTOR / GENERATOR DESIGN FOR FLYWHEEL APPLICATIONS HIGH SPEED PERMANENT MAGNET SYNCHRONOUS MOTOR / GENERATOR DESIGN FOR FLYWHEEL APPLICATIONS Aleksandr Nagorny, Ph.D. National Research Council Outline Introduction Selection of the Rated Point The major

More information

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay

More information

Basic Nameplate Information

Basic Nameplate Information Basic Nameplate Information General Information: Most equipment nameplates will have some common items of information. Many of these are self explanatory, and include: Manufacturer Manufacturerʼs address

More information

SECTION 13. Multipliers. Outline of Multiplier Design Process:

SECTION 13. Multipliers. Outline of Multiplier Design Process: SECTION 13 Multipliers VMI manufactures many high voltage multipliers, most of which are custom designed for specific requirements. The following information provides general information and basic guidance

More information

CA723, CA723C. Voltage Regulators Adjustable from 2V to 37V at Output Currents Up to 150mA without External Pass Transistors. Features.

CA723, CA723C. Voltage Regulators Adjustable from 2V to 37V at Output Currents Up to 150mA without External Pass Transistors. Features. CA73, CA73C Data Sheet April 1999 File Number 788. Voltage Regulators Adjustable from V to 37V at Output Currents Up to 1mA without External Pass Transistors The CA73 and CA73C are silicon monolithic integrated

More information

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of

More information

Galaxy VM. Three-phase power protection. schneider-electric.com

Galaxy VM. Three-phase power protection. schneider-electric.com Galaxy VM Three-phase power protection schneider-electric.com 2 schneider-electric.com schneider-electric.com 3 Galaxy VM trusted partner for your business continuity Features and benefits Highly efficient,

More information

PIN CONFIGURATION FEATURES ORDERING INFORMATION ABSOLUTE MAXIMUM RATINGS. D, F, N Packages

PIN CONFIGURATION FEATURES ORDERING INFORMATION ABSOLUTE MAXIMUM RATINGS. D, F, N Packages DESCRIPTION The µa71 is a high performance operational amplifier with high open-loop gain, internal compensation, high common mode range and exceptional temperature stability. The µa71 is short-circuit-protected

More information

30-120 3 Phase Modular Finally the benefits of Modular ups are for all

30-120 3 Phase Modular Finally the benefits of Modular ups are for all MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion

More information

47000 SERIES - ELECTRONIC TRANSFORMERS

47000 SERIES - ELECTRONIC TRANSFORMERS 7000 SERIES - ELECTRONIC TRANSFORMERS MYRRA encapsulated electronic transformers are Switched Mode Power Supplies based on Flyback topology. They constitute an interesting alternative to the traditional

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for

More information

COMPUTER AIDED ELECTRICAL DRAWING (CAED) 10EE65

COMPUTER AIDED ELECTRICAL DRAWING (CAED) 10EE65 COMPUTER AIDED ELECTRICAL DRAWING (CAED) EE Winding Diagrams: (i) DC Winding diagrams (ii) AC Winding Diagrams Terminologies used in winding diagrams: Conductor: An individual piece of wire placed in the

More information

BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES

BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES The Edison British Style semiconductor protection fuses include a 660VAC line utilizing new filler technology. These new fuses have greatly reduced peak let-through current and energy under fault conditions

More information

ELECTRIC CENTRAL HEATING FLOW BOILER

ELECTRIC CENTRAL HEATING FLOW BOILER ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Product Brochure. Certified Mining Motors

Product Brochure. Certified Mining Motors Product Brochure Certified Mining Motors Profile Baldor Electric Company (a member of the ABB group) is a world leader in motors for the mining industry. In the continuous (24/7) operation of underground

More information

12V Dimmable Driver EL-TMDRVR

12V Dimmable Driver EL-TMDRVR Elemental LED, LLC website: elementalled.com 11 9 5 P a r k A v e., S u i t e 2 11 Emeryville, CA 94608 toll free 877.564.5051 fax 510.740.4457 12V Dimmable Driver EL-TMDRVR ETL Listed #4001928 CSA Listed

More information

AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass

AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass APC AIS 3000, 12 kw / 15 kva,input 208V 3PH / Output 120V, 208V, 208V 3PH, Interface Port DB-9 RS-232,

More information

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current. Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.

More information

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

3) What is the difference between Insulating, Isolating, and Shielded Winding transformers? Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer

More information