SPECIFICATIONS OF STATCOM TRANSFORMER (FOR 2.5 MVAR STATCOM)
|
|
|
- Angelina Laura Bryan
- 9 years ago
- Views:
Transcription
1 SPECIFICATIONS OF STATCOM TRANSFORMER (FOR 2.5 MVAR STATCOM) PROJECT EQUIPMENT Quantity : 2.5 MVAR STATCOM. The transformer will be used for connecting a 2.5 MVA Inverter with grid at 6.6 kv. : Transformer : 1 No. 1. Primary Rating (at all taps) : 3 MVA Continuous (Fundamental) 2. Frequency : 50 Hz (Fundamental) 3. Vector group : YNd11d11 HV Winding Star Connection LV Windings Delta Connection 4. HV Winding Voltage (L-L) : 6.6 kv ± 10%, 3-phase 5. LV Winding Voltage (L-L) : 2365 V (Fundamental) LV Winding Current : Rating of each secondary winding is 1.5MVA. However, when only any one of the secondary winding is loaded, then that winding will be loaded to the maximum of 1.64MVA (i.e. a secondary current of 400A). 6. Tapping on HT Windings : ± 2.5 %, ± 5 % (Rated kva on all Taps) 7. H.V. Neutral : This will be the fourth terminal in HV cable box, and insulated to full line voltage including clearances and creepages. Current carrying capacity and size shall be same as line terminals. 8. Impedance, Tolerance : 5% on principal tap ( Minimum) Tolerance + 10 % - 0 % Impedance of the both the secondary windings should be identical 9. Duty : Inverter duty. The transformer secondary will be connected to a three-phase inverter with inductor of 0.15 PU inductance. The THD on inverter output voltage in operating range varies between 15 % to 25 %. 11. DC Component (mv) : 160mV ( This is always present in the input supply of transformer. Transformer should be suitably designed. 12. Over-fluxing : Transformer shall be suitable for 125% over fluxing at the time of STATCOM start-up (duration of 10 secs.)
2 13. Insulation : All windings to be uniformly insulated. The windings to be designed to BIL Level 2 of IS Protection : The transformer should be provided with Buchholz relay. Other relevant protections as per BIS should be provided. 15. Current Transformers on HT side : Insulation Class of CT 6.6 kv 1) 2 nos. of 300 / 5 Amps, 10 VA, 5P10 Class on Line 2) 1 no. of 150 /5 Amps, 10 VA, 5P10 Class on Neutral Current Transformers on LT side : Insulation Class of CT 3.3 k V 6 nos. of 600 / 5 Amps, 10 VA, 5P10 Class on Line. (3 nos. of CT per each secondary windidng) 16. Type of cooling : ONAN. Mineral oil filled 17. Installation : Outdoor duty (Under direct sunlight) 18. Ambient temp. : 55 Degree C 19. Temperature rise (a) Design ambient temp. : 55 Degree C. (b) Temp. rise of top of : 50 Degree C. oil by thermometer (c) Temp. rise of wdg. : 55 Degree C by resistance method 20. Relative Humidity : 100 % 21. Short Ckt. level at 6.6 kv : 300 MVA 22. Suitability to withstand : The transformer should be designed to withstand vacuum breaker switching on HT side 23. Transformer Material a) Material of winding : Copper Electrolytic Grade b) Core : Not to exceed 1.3 Wb/m 2 at any tap position with ± 10% voltage variation from voltage corresponding to the tap. The laminated core shall be of high grade cold rolled grain oriented silicon steel. c) Tank : Tank shall be of welded construction and fabricated from tested low carbon steel. It shall be designed for a continuous internal pressure of 0.35 Kg/sq. cm over normal hydrostatic pressure of oil. The tank cover shall be sloped to prevent retention of rain water. All bolted connections shall be fitted with weather proof hot oil resistant neoprene gasket, in between for complete oil tightness. Calculation for pressure test shall be submitted. Bi directional skids, rollers, jacking pads( four nos), lifting lugs shall be provided. d) Hardware : All nuts and bolts exposed to weather shall be hot dip galvanised or cadmium plated or zinc passivated steel.
3 24. Overall Dimensions : The overall transformer dimensions should be within the dimensions of 3700 (L) X 2700 (B) X 3100 (H). The floor area should not exceed (3700 (L) X 2700 (B) ). HT and LT terminals should be mounted on 2700mm side of the transformer. All dimensions are in mm. 25. Noise : Not to exceed values specified in NEMA TR Insulating oil : Fresh oil (before pouring into transformer) should be as per IS 335, without inhibitor. 10% extra oil shall be supplied for top ping in non returnable containers in sealed drums. 27. Construction : Earth screen to be provided between primary and secondary side. Since the transformer is used for converter duty. Since the transformer is used for converter duty, it should be 3 legged core, 5 legged core is not allowed. 28. Terminal arrangement : Suitable for termination of XLPE cable with Raychem type heat shrinkable terminating kits on HT side and LT side. 4mm thick Aluminum blank (undrilled) gland plates to be supplied with H.T., L.T. and Marshalling boxes. Bushings of Porcelain confirming to IS 2099 & IS The minimum length between cable gland plate and cable lug to be 550 mm for both H.V. and L.T. side cable boxes. Terminal marking shall be as per IS Epoxy bushings are not acceptable. Terminals to be threaded or Plug type 29. Tap changer : OFF circuit tap changer with padlocking facility as per IS 2026 with warning plate " SWITCH TO BE OPERATED WITH TRANSFORMER DE-ENERGISED" 30. Painting (Transformer : Polyurethane and accessories) 31. Shade : 631 as per IS Fittings and accessories : As per Annexure-A 33. Standards : IS Testing (Routine Tests) : As per Annexure B 35. Quality plan : Supplier should submit his Quality Plan for approval (Post Ordering stage) 36. Testing (Type Tests) : As per Annexure - B. Procedure as per IS No load loss & Load : Guaranteed maximum values without any positive loss tolerance shall be given with the offer. An amount of Rs /- per KW of differential copper loss and Rs.60,000/- per KW of differential iron
4 loss will be levied on the manufacturer, if these losses exceed the guaranteed losses quoted. For the bid comparison purpose, price loading will be done at above rates for losses. 38. Data Sheet : DATA SHEET is enclosed with this specification. The same is to be filled up and submitted along with the technical offer. 39. Information Reqd. with the offer : (a) Filled up data sheet (Annexure C) (b) Deviations to this specification. If there are no deviations, supplier must mention the same explicitly in their technical offer. (c) Unpriced prebid must be enclosed with technical offer. Price bid must contain list of type tests with individual charges and also price for individual items in list of spares (d) Supplier to give charges for individual type tests. (e) Supplier to furnish item wise price for list of spares. (f) Short description on the construction of core, and disposition of windings in the transformer. 40. Information required : Outline GA Drg. showing weights, dimensions, after order placement foundation plan and List of Accessories. Drawing along with design summary should be submitted for approval 41. Document to be submitted : (a) Operation and Maintenance manual. (b) Test Certificates for Routine & Type tests, and guarantee Certificates. (c ) Guarantee Certificate NOTE: 1. The test charges for each type test must be mentioned test wise in the price bid. However, a confirmation to that effect must be contained in the technical offer. Unpriced copy of price bid must be enclosed in Technical offer. 2. Once the order is placed, the supplier should submit design calculations for approval for the purpose of the conformity of the designed transformer for inverter duty. 3. The transformer has to be tested in presence of BHEL engineers for dispatch clearance. For any Technical Clarifications, please contact : Shri S Eswara Rao, Manager(PES) / Dr BP Muni, AGM(PES) ID : [email protected] / [email protected]
5 ANNEXURE - A All accessories shall be provided confirming to IS The following fittings and accessories shall be provided: SL.NO DESCRIPTION QTY 01. Oil filling hole with cover Conservator with sump & drain valve 1 with plug/cover plate. The Breather shall be mounted at a height less than 1600 mm from the ground. 03. a) Magnetic Oil level gauge(dial type) 1 with minimum and maximum filling level markings. It should have two independent electrically insulated low level alarm contacts suitable for 220 V DC. The oil level at 30 deg C shall be marked on the gauge. Contact suitable for 220 V DC. b) Prismatic oil level gauge Thermometer pockets Air release plug on tank cover Lifting lugs 1 SET 07. Top filter valve Dehydrating breather with Silica gel 1 and oil seal 09. Off circuit tap changing switch on 1 tank cover with tap position indicator, locks and handle. 10. Rating and terminal marking stainless 1 steel/anodised aluminum plate, with details etched in MKS & SI units. 11. Earthing terminals without lugs suitable 2 for connecting 50x6 mm galvanized mild steel flat. 12. Diagram plate 1
6 13. Drain cum bottom filter valve Base channel with towing holes/lugs Four Jacking Pads to enable transformer 1 SET with oil to be raised or lowered using hydraulic or screw jacks. 16. Manufacture's name plate (stainless steel) Bi-directional rollers + Bi-directional skids 1 SET 18. Detachable radiator with bottom drain 1 SET plug, top air release plug and top & bottom shut off valve. 19. Buchholtz relay should be of double float 1 SET type with testing & sampling cocks, alarm and trip contacts and one isolating valve on conservator side mm dial type oil temp. Indicator and 1 SET winding temp. Indicators with max. pointer with alarm and trip contacts. Contacts suitable for 220V DC. Indicator accuracy ± 2%. Alarm and trip points to be adjustable. Full scale temp. 240 deg C. Least count 2 deg C. Oil / Winding temp. Indicators should be provided with resetting device. 21. Cable glands & lugs 1 SET Cable sizes shall be informed at the time of drawing finalisation. Cable lugs shall be of tinned copper for crimping to stranded aluminum conductor cable. Cable glands will be of double compression type. 22. Marshalling box (protection class IP55 and 1 No IS 2147) epoxy painted. Should be vermin, weather, dust proof. Terminal connector of control cable should be DOWELL make or equivalent. 20% extra spare terminals reqd. All TBs to be complete with insulating barriers, clip on type terminals suitable to 2.5 sq mm stranded copper wire. The marshaling box and temperature indicators shall not be mounted at a height greater than 1600 mm from the ground level. The box shall be tank mounted with sloping roof. All incoming cables shall enter from bottom. Sheet steel to be 1.6 mm thick. Thermostatically Controlled space heaters shall be provided. 23. Inspection openings on tank with handles 2 Nos. 24. Remote WTI For Remote Control Panel 1 No. It shall not be a repeater dial of Local WTI
7 NOTE :1) Contacts of all temp indicators, Bucholoz relays and auxiliary devices shall be suitable for 220 V dc supply. All alarm and trip contacts shall also be suitable for 220 V dc circuits. External power supply will not be provided. 2) Nuts and bolts exposed to weather to be hot dipped galvanized or cadmium plated or zinc passivated steel. 3) Control wiring to be done with 1100 V grade PVC LV Winding Delta Connection wire, 2.5 mm stranded copper wire. 4) Cable glands and lugs shall be supplied loose along with transformer. See Pt 22. Cable glands will be double compression nickel plated brass. Cable lugs will be installed with fixing hardware in the cable box.
8 ANNEXURE - B B) Final testing of Finished Transformer The following tests shall be conducted on the finished transformer. - Routine tests in accordance with the latest issue/ amendments of IS Magnetic Balance Test The following type tests shall be conducted on the transformer. - Temperature rise test as per IS2026 with latest amendments. - Full wave Impulse test on HV wdg, LV windings. Voltage peak shall be as per list 2 of IS 2026, Note : (i) Supplier shall submit price for each type test test-wise in the offer.
9 ANNEXURE - C DATA SHEET 1) Manufacturer s Name and address : 2) Service Class / KVA rating : 3) Rated Voltage a) HV Winding KV : b) LV Winding KV : 4) Rated frequency : 5) Number of phases : 6) Connections a) HV Winding : b) LV Winding KV : 7) Connection symbol : 8) Type of cooling : 9) Tap changing equipment a) Manufacturer : b) Type : c) No of steps : d) Tap range % to % : 10) Guaranteed positive sequence impedance at 75 deg C with 100% rating a) Principal tap : b) Maximum tap (Approx) : c) Minimum tap (Approx) : 11) Temp. rise over an ambient of 50 deg C a) Top oil deg C : b) Winding(by resistance measurement method deg C ) : 12) Guaranteed losses at rated voltage on principal
10 tap and at rated current rated frequency: a) No load loss KW * } SEE NOTE BELOW b) Copper loss at full * } load and 75 deg C KW 13) Withstand time for three phase : short circuit at terminals (sec.) 14) No load current at rated voltage and rated : frequency (Amps) (Approx) 15) Insulation level a) Separate source power frequency voltage withstand i) HV Winding (KV rms) : ii) LV Winding (KV rms) : iii) HV Bushing : iv) LV Bushing : v) Neutral Bushing : b) Induced over voltage withstand i) HV Winding (KV rms) : ii) LV Winding (KV rms) : c) Full wave lightning impulse withstand i) HV Winding (KV) : ii) LV Winding (KV) : iii) HV Bushing : iv) LV Bushing : v) Neutral Bushing : * NOTE : LOSS FIGURES TO BE GIVEN WITHOUT ANY POSITIVE TOLERANCE. THESE FIGURES WILL BE USED FOR BID COMPARISON PURPOSE. d) Switch impulse withstand voltage i) HV Winding (KV) : ii) LV Winding (KV) : iii) HV Bushing :
11 16) Regulation at full load at 75 deg C a) At unity power factor (percent) : b) At 0.8 power factor (percent) : 17) Terminal arrangement a) High Voltage : b) Low Voltage : c) LV Neutral : d) HV Neutral : 18) Over excitation withstand time (sec) a) 120% : b) 150% : 19) Bushing a) High Voltage i) Manufacturer : ii) Type : iii) Minimum creepage distance(mm) : b) Low Voltage i) Manufacturer : ii) Type : iii) Minimum creepage distance(mm) : c) Neutral i) Manufacturer : ii) Type : iii) Minimum creepage distance(mm) : 20) Proposed method of transformer shipment : 21) Total quantity of oil (litres) required for first : filling 22) Is vacuum filling required, if so, : state absolute pressure
12 23) Efficiency at 75 deg C at unity power factor a) At full load ( percent ) : b) At 3/4 full load (percent) : c) At 1/2 full load (percent) : 24) Approximate dimensions a) Tank enclosure (mm) : L x B x H b) Overall L x B x H (mm) c) Limiting dimensions confirmed as in pt 37 of spec: YES / NO 25) Untanking height (mm) : 26) Approximate weight a) Core and winding (Kg) : b) Tank cover (Kg) : c) Tank fitting (Kg) : d) Oil (Kg) : e) Total weight (Kg) : 27) Despatch details (Kg) a) Approximate mass of heaviest : package (Kg) b) Approximate dimensions of largest package i) Length (mm) : ii) Breadth (mm) : iii) Height (mm) : 28) Reference standards : 29) Type of Construction (Core/Shell) : 30) Thermal time constant (Hours) : 31) Magnetizing inrush current (Amps)
13 32) No load current at rated frequency and at(approx) i) 90% voltage (Amps) : ii) 100% voltage (Amps) : iii) 110% voltage (Amps) : 33) Power factor of no load current : 34) Zero sequence impedance at : principle tap 35) Capacitance between winding and to : earth (micro farads) 36) Percentage reactance at rated current and frequency and at i) Principal tap : ii) Maximum tap : iii) Minimum tap : 37) Off circuit tap changer details a) Ratings i) Rated voltage : ii) Rated current : iii) Step voltage : iv) Numbers of steps : 38) Radiator i) Overall dimensions lxbxh (mm) : ii) Total weight with oil (Kg) : iii) Total weight without oil (Kg) : iv) Type of mounting : v) Thickness of Radiator tube(approx) : radiator sheet steel (approx)
14 39) Weight of Transformer a) Core (Kg) (approx) : b) Windings i) HV (Kg)(approx) : ii) LV (Kg) : c) Insulation (Kg)(approx) : d) Tank/enclosure and fittings (Kg) : e) Oil (kg) : f) Untanking weight (Heaviest weight) (Kg) : g) Total weight (Kg) : 40) Dimensions a) Tank enclosure (mm) : L x B x H(approx) b) Overall L x B x H (mm) : 41) Shipping details a) Weight of heaviest package (Kg) : b) Total shipping weight (Kg)(approx) : c) No. of packages : d) Dimensions of largest package : (mm) l x b x h e) Parts detached for transport: conservator tank, : radiator,eq.pipe,explosion vent etc. 42) Size of filter hose (mm) : 43) Core a) Form of core : b) Net core area (mm 2 ) : c) Type of joint between core and yoke : d) Thickness of stamping (mm) : e) Percentage silicon content (percent) :
15 f) Maximum flux density in core at rated frequency and at i) 90% voltage (Wb/m 2 ) : ii) 100% voltage (Wb/m 2 ) : iii) 110% voltage (Wb/m 2 ) : g) Type of core binding : 44) Winding a) Type of winding i) HV : ii) LV : b) Current density at rated load i) HV (A/mm 2 ) : ii) LV (A/mm 2 ) : c) Conductor area i) HV (A/mm 2 ) : ii) LV (A/mm 2 ) : d) Maximum current density under short circuit i) HV (A/mm 2 ) : ii) LV (A/mm 2 ) : 45) Clearance a) Minimum clearance between phase i) In oil (mm) : ii) In air (mm) : b) Minimum clearance of HV winding : to tank/enclosure (in oil, if applicable),(mm) c) Minimum clearance of HV winding : to earth (In oil, if applicable),(mm) d) Clearance between core and coil (mm) : e) Clearance between coils (mm) :
16 46) Tank/enclosure details i) Side (mm) : ii) Bottom (mm) : iii) Cover (mm) : 47) Insulation levels i) Power Frequency : ii) Lightning Impulse : HV LV 48) Bushings HV LV i) Type : Porcelain Porcelain ii) Rated Voltage : iii) Lightning Impulse : iv) Creepage distance : v) Power Frequency : 49) Magnetic Oil Level Gauge : (Dial type) Size 50) List of deviations ( if any )enclosed : YES / NO enclosed with offer. If no deviations please mention the same here.
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is
SECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:
REQUIREMENT : The equipment offered shall be highly reliable suitable to operate satisfactorily in hot humid and polluted climate. The equipments offered shall work satisfactorily within temperature range
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva
to 1250 kva Page 1/10 Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva This technical specification is valid for the business unit E.ON Sweden of the market unit E.ON Nordic.
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR)
TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR) (SPECIFICATION NO. DIST/MM-II/03/2005) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
3/2-way Solenoid Valve, direct-acting, NC or NO
3/2-way Solenoid Valve, direct-acting, NC or NO Electrical connection cable plug, Form A With or without manual override as standard Threaded port and sub-base s Impulse optional Type 6014 can be combined
SECTION 16322 SUBSTATION TRANSFORMERS
SUBSTATION TRANSFORMERS PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the primary and/or secondary substation transformers as specified herein and as shown on the contract
italtec PRINTED CIRCUITS EQUIPMENT PRINTED CIRCUITS EQUIPMENT Insulator machines Echting machines Special equipment and machines
PRINTED CIRCUITS EQUIPMENT PRINTED CIRCUITS EQUIPMENT Insulator machines Echting machines Special equipment and machines On customer request it is possible to supply: Benches for PCB Oven for PCB Chemicals
DS 600. A contact free flux gate based current measurement sensor 600A rms
DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
This section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
Vario-Series Accessories
Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates
Solar Hot Water Heaters
Solar Hot Water Heaters Three High Vacuum Water inlet Stainless Steel screw Gel seal and insulation Water outlet Dust proof seals Non Pressure Models Details ASWH-1b ( Color Painted 304 ) ASWH-1c ( stainless
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132
Operators manual Basic water heater
Operators manual Basic water heater Isotemp Basic water heater has been designed and produced to ensure that your water heater will give long and trouble free operation for many years. It is important,
ASME Packaged Indirect Fired Water Heater
Utilizes Or HTHW To Heat Domestic Water, Semi-Instantaneous or Storage Type Model BW Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone cement lining
HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer
168-08 TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE APPARATUS A three-phase outdoor oil-immersed distribution transformer DESIGNATION 1000 kva SERIAL No. 1-08-112-01-0001 Rated power Rated voltage
SF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power:
PHOTOVOLTAIC (PV) solar panels Electricity - CE & ISO 9000 certified Photovoltaic solar panels convert sunlight into useful electricity. ZEDfabric supplies high quality mono-crystalline silicon cell PV
Transformer Design & Design Parameters
Transformer Design & Design Parameters - Ronnie Minhaz, P.Eng. Power Transmission + Distribution GENERATION TRANSMISSION SUB-TRANSMISSION DISTRIBUTION DISTRIBUTED POWER 115/10 or 20 kv 500/230 230/13.8
RAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
DRY TYPE TRANSFORMER
PRODUCT LEAFLET DRY TYPE TRANSFORMER Single-phase, three-single, three-two and three-phase transformers 1.1 kv to 7.2 kv classes 1 60 40152-13/09/2011 Dry Type Transformers Transformers meant to be installed
James M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
Assisted lift operated 2/2-way solenoid valves Type EV250B
MAKING MODERN LIVING POSSIBLE Data sheet Assisted lift operated 2/2-way solenoid valves Type EV250B EV250B with assisted lift can operate from zero and up to 10 bar differential pressure. This 2/2-way
SELECTION GUIDE. Nominal Input
www.murata-ps.com NKE Series FEATURES RoHS Compliant Sub-Miniature SIP & DIP Styles 3kVDC Isolation UL Recognised Wide Temperature performance at full 1 Watt load, 40 C to 85 C Increased Power Density
REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)
SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY
CAPACITOR BANK TESTING SWP
1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Magnum Mobile Generator MMG55 Specifications
Empowering Real People Magnum Mobile Generator MMG55 Specifications ENGINE John Deere PE5030TF270 - turbocharged, diesel engine o Prime - 72 hp @ 1800 rpm o Standby - 80 hp @ 1800 rpm o 4 cylinder o 3.0
Light Duty Commercial Electric Water Heater
Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and
Meter Relays. 077 Series Analogue Meter Relays. Features. Applications
077 Series Analogue Features Monitors and controls any variable which can be converted to an A.C. or D.C. signal. Rugged, shock and vibration resistant design Indicator, relays and power unit in one housing
Presentation of the France Transfo factories
Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
J TB/TW Temperature limiter, temperature monitor
JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: [email protected] Internet: www.jumo.net
1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide
1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.
SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.
Tasarım ve Baskı: AJANSBRAND A 15.09.2014
www.kosgeb.gov.tr Tasarım ve Baskı: AJANSBRAND A 15.09.2014 THE ENERGY TRANSFERRED TO NATURE www.atstrafo.com ABOUT Having been founded in Adıyaman Organized Industrial District in 2003, ATS Trafo carries
TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)
TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless
Multi-tap Transformers
Multi-tap Transformers Three-Phase Multi-tap Transformer for Electrical Submersible Applications Functional Specification Guide Functional Specification for Multi-tap Transformers for Electrical Submersible
Table of Contents. TransformerIQ FAQs 1
[12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is
OLI. Oil level indicator
OLI Oil level indicator Oil level indicator Unexpected or accidental oil leakages may occur randomly along transformer s lifetime. Clear indication of oil level inside transformer tank and on load tap
APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors
APPENDIX APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS RJ12 connectors Pin # 1 Signal Name Not Used 2 +TR Description + Data Line 3 +R Remote OFF Required or Remote OFF control 4 -TR 5 Not Used 6 RTN -
For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary
UNITED ARAB EMIRATES FEDERAL ELECTRICITY AND WATER AUTHORITY
UNITED ARAB EMIRATES FEDERAL ELECTRICITY AND WATER AUTHORITY DETAILED TECHNICAL SPECIFICATION FOR 33/11KV 20/28MVA POWER TRANSFORMER, NER & RTCC PANELS SPECIFICATION NO. Tx- 1.03 (Revised in March 2010)
Power transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.
EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium
2 X 2000 KVA, 415V DG SYSTEM FOR PROPOSED DATA CENTRE NCMRWF, NOIDA, UP.
Client:- Project:-Proposed Data Centre at Noida. 2 X 2000 KVA, 415V DG SYSTEM TECHNICAL SPECIFICATIONS FOR PROPOSED DATA CENTRE AT NCMRWF, NOIDA, UP. Page 1 of 12 Client:- Project:-Proposed Data Centre
understanding medium frequency induction melting furnace and its components
understanding medium frequency induction melting furnace and its components 9 Spruce Street, Jersey City, NJ 07306 USA [email protected] INDUCTION MELTING FURNACE AND ITS COMPONENTS The purpose
MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
Low Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
Data sheet ECC 12 and 22
Application ECC is an electronic room temperature controller for water-based systems. ECC can control - fan-coil units - inductions units - air conditioning systems - small ventilating systems - 2-pipe
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
Series 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
Commercial Electric Water Heater
MODEL SE Commercial Electric Water Heater 6-120 Gallon Capacity, up to 58 KW in all Three Phase Voltages, Over 6 KW in all Single Phase Voltages Features Heavy Duty Construction Hydrastone cement lining
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
UGVCL/SP/591/11KV HT AB CABLE
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
Explosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
Cold Room & Refrigeration System (Casserole Assembly) No of units: 1
Technical Specifications Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 For chiller storage of all sorts of items Chiller storage temperature: 2-5 C Provides excellent thermal efficiency
Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA
Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation
LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS
Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON
TECHNICAL SPECIFICATION FOR 11 & 22 KV DISTRIBUTION TRANSFORMERS OF RATINGS 63 KVA & 100 KVA CAPACITY (SPECIFICATION NO.WORKS T&D : 01-N/2001)
TECHNICAL SPECIFICATION FOR 11 & 22 KV DISTRIBUTION TRANSFORMERS OF RATINGS 63 KVA & 100 KVA CAPACITY (SPECIFICATION NO.WORKS T&D : 01-N/2001) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE
Quick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
Step Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA
SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/ 1 X C-UA- LTXLPE/2006) MAHARASHTRA STATE ELECTRICITY
TECHNICAL SPECIFICATIONS
1. Standards BOS Item / System I ii iii TECHNICAL SPECIFICATIONS Applicable BIS /Equivalent IEC Standards / Applicable MNRE Specifications Standard Description Standard Number Crystalline Silicon Terrestrial
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations
12S, 14S, 15S Series Time Delay Relays and Sequencers Time Delay Relays and Sequencers The Therm-O-Disc type 12S, 14S and 15S series time delay relays and sequencers are field-proven devices for controlling
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
STB Series Enclosures
STB Series Enclosures Features/Applications: The STB series of sheet steel enclosures are designed to meet the requirement for distribution and lighting junction boxes. Available in 14 sizes with standard
Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
Technical data UNIBLOCK UBSF 180 625
Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow
ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations
Material Name: - 8 MVA, 33/11KV POWER TRANSFORMER CONTENTS
Material Name: - 8 MVA, 33/11KV POWER TRANSFORMER CONTENTS SECTION No DESCRIPTION PAGE NO. SECTION-IV(B) TECHNICAL SPECIFICATION 8 MVA POWER TRANSFORMER 01-37 ANNEXURE-IV(B) Technical Data Schedule For
Annex-A TECHNICAL SPECIFICATION
Annex-A TECHNICAL SPECIFICATION FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 0.4kV (2,000kVA) DIESEL GENERATOR 1 1.0 SCOPE This specification covers the requirements of design, manufacture, delivery
Linear Luminaire with LED Series EXLUX 6402/2
> Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE
OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203)
1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide
1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before