1 VdS Guidelines for Fire Extinguishing Systems VdS 3518en Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01)
2 Publisher and Publishing house: VdS Schadenverhütung GmbH Amsterdamer Str D Köln Phone: , Fax: Copyright by VdS Schadenverhütung GmbH. All rights reserved.
3 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems Guidelines for Fire Extinguishing Systems Safety and Health Protection in Connection with Gas Extinguishing Systems CONTENTS Preliminary note Scope of application Definitions General requirements Hazard Classes Installation and equipment Alarm systems Delay devices Pre-warning time Stopptaster Blocking devices Overview of alarm and delay devices Piping Enclosures Escape routes Doors Marking Operating instructions Operation Proper Operation Operating procedure and training Rectification of faults Blocking of extinguishing systems Behaviour in a fire situation Fighting of initial fires Re-entry of flooded areas Use of emergency stop device Odorisation Inspections Obligatory inspections Approval inspections Periodical inspections Inspection records Annex 1 Sample for Approval Protocol
4 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01) Annex 2 Material Data Annex 3 Requirements for emergency stop device Annex 4 (informative) Calculation of the extinguishing gas... and of the residual oxygen concentration Extinguishing gas concentration Halogenated hydrocarbons Residual oxygen concentration Annex 5 Rules and Regulations
5 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems These Guidelines represent a summary of BGR 134 (status July 1998, up-dated reprint January 2004), up-dated by BGI 888 (status January 2004) and explanations. These Guidelines have been developed in co-operation with the Arbeitskreis Feuerschutz (Fire Protection Team) of the industrial Employer s Liability Insurance Association and bvfa. They are applicable as from publication, unless terms of these Guidelines have to be observed already due to applicable legal standards or as generally recognised codes of practice. Preliminary note These Guidelines are addressed primarily to the owner and are intended to assist him in the implementation of his duties resulting from national work safety regulations or accident prevention regulations and to show him ways how to avoid work accidents, occupational diseases and health risks. When observing the recommendations included in these Guidelines, especially the exemplary solution possibilities, the owner can expect to have taken appropriate measures for the prevention of work accidents, occupational diseases and work-related health risks. In case the committees established for the concretisation of national occupational safety regulations have determined technical rules, these shall take precedence. Oxygen-displacing gases, such as carbon dioxide, nitrogen, noble gases (e.g. argon) and mixtures thereof (e.g. Argonite, Inergen) are used as extinguishant in fixed fire extinguishing systems. They extinguish fires, essentially by displacing atmospheric oxygen from the fireground. Equally, halogenated hydrocarbons (e.g. FM 200 and Novec1230) are used as extinguishant in fixed fire extinguishing systems. Their extinguishing effect is based on a chemical/physical principle. The extinguishing gas concentration developed for an adequate extinguishing effect or the lowered oxygen concentration respectively does not allow a permanent presence of persons in this atmosphere. Depending on the inhaled concentration, these gases have an exciting, paralysing or suffocating effect. When using extinguishing gases or gas mixtures in fixed fire extinguishing systems, the respective critical concentrations from which on there is a hazard to life has to be evaluated, determined and documented by the installer (see also Annex 2 Material Data). E.g. carbon dioxide can be expected to be harmful from a concentration of 5% by volume CO 2 on and from a concentration of more than 8% by volume CO 2 on there is a risk of death. 5
6 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01) 1 Scope of application 1.1 These Guidelines are applicable to fixed fire extinguishing systems with gaseous extinguishants, hereinafter referred to as extinguishing systems. 1.2 These Guidelines are not applicable to extinguishing systems on seagoing vessels, watercrafts and floating equipment of inland waterway navigation with operating permit as well as in underground mining. 1.3 Deviating from 1.1, paragraphs to 5.10, 6.3 to 6.9, to as well as are not applicable to extinguishing systems of Hazard Class I (see 4) because there is no hazard to persons when these extinguishants are discharged. Generally, there is no hazard to persons due to these extinguishants in case of objects that are open or not accessible or located in inaccessible rooms. This also applies to rooms in which, because of their size or construction, the extinguishing gas concentration remains under and the oxygen concentration remains above the limit which is critical for a hazard to people, even when the entire extinguishing gas design quantity is discharged. This is also applicable when several such systems are provided in one room whose activation systems can jointly react to the same event or trigger a flooding. 2 Definitions In the sense of these Guidelines, the following terms are defined: Work and traffic area: The work and traffic area in the vicinity of rooms or facilities that are protected with gas extinguishing systems is that area which can be reached by people. When the areas protected with gas extinguishing systems are accessible areas themselves, then these areas are included in the work and traffic area. Activation is the release of the extinguishing system for flooding, either automatic or manual. Delayed activation is the release of the extinguishing alarm and of the delay device and the delayed release of the extinguishant for flooding. Flooding is the discharge of the extinguishant into the flooding zone. Extinguishing alarm includes visual and audible signals that are emitted directly before, during and after flooding in the hazard area. Hazard Area: In case of total flooding systems, this generally corresponds to the extinguishing area. (See also 5.8 and 5.9) In case of local application systems, this is the area where the harmful concentration may be exceeded by a release of the extinguishing system. 6
7 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems The hazard area shall be defined for each system, since an alarm shall be sounded in the hazard area. The hazard area can, particularly in case of open local application systems, temporarily change due to the discharge of the extinguishing gas into the environment. Flooding zone is the entirety of all areas which are included in the scope of protection of the extinguishing system and which are flooded simultaneously. Local application/object protection is the flooding of an object, e.g. a machine, painting facility, with the extinguishing gas quantity designed for the extinguishing effect. Room protection/total flooding is the flooding of a self-contained and enclosed room with an extinguishing gas quantity designed for the extinguishing effect. Design quantity is the extinguishing gas quantity that is required for the build-up of an effective extinguishing gas concentration within the flooding zone. Extinguishing gas quantity is the total gas quantity discharged into the flooding zone. (Decisive for the max. extinguishing gas and the min. oxygen concentration.) Odorisation is the adding of odorants which make the smell-free extinguishing gas perceptible. Extinguishing gas concentration (EGC) is the concentration of extinguishing gas in % by volume which is reached after flooding in the atmosphere of the flooding zone and, in case of open local application systems, also in its vicinity. NOAEL (no observed adverse effect level) is the highest extinguishing gas concentration in % by volume at which no harmful effects have been noted yet. LOAEL (lowest observed adverse effect level) is the lowest extinguishing gas concentration in % by volume at which harmful effects have been noted. Life-threatening concentration (LTC) is the lowest extinguishing gas concentration from which on there is acute risk of death already in case of a short-term stay. Pre-warning time is the time from the beginning of the extinguishing alarm until the beginning of flooding. Blocking device is a contrivance by means of which the extinguishant discharge can be blocked mechanically. Delay device is the contrivance which delays the beginning of the flooding. Emergency stop device is a control device with automatic reset function that prevents flooding during the pre-warning time for the duration of its actuation. 7
8 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01) 3 General requirements 3.1 For their safe operation, extinguishing systems shall conform to the generally recognised codes of practice and be operated properly. Deviations are admissible, provided that the same level of safety is ensured otherwise. Generally recognised codes of practice are, for example, the standards specified in the annex as well as the guidelines of VdS Schadenverhütung. 3.2 The technical solutions contained in these Guidelines do not exclude other at least equally safe solutions that might have materialised in technical rules of other member states of the European Union or other contracting states of the Agreement on the European Economic Area. This applies, for example, to technical solutions that are permitted in VdS approvals for the corresponding hazard class. 3.3 Test reports of testing laboratories which are certified in other member states of the European Union or in other contracting states of the Agreement on the European Economic Area are taken into consideration in the same way as German test reports, provided that the tests, test procedures and constructional requirements on which these test reports are based are equal to those of the German agencies. This is particularly the case when such agencies comply with the requirements as stipulated in the standard series EN or EN ISO/IEC respectively. 4 Hazard Classes Depending on the substances to be extinguished (fire load) and the extinguishing gases used, differently high extinguishing gas and oxygen concentrations may be applied. These different concentrations also result in a different threat to the persons within the hazard area. Corresponding to this threat, the extinguishing systems with gaseous extinguishants can be subdivided into four classes: Class I Extinguishing gas concentration up to NOAEL (EGC < NOAEL) and oxygen concentration above 12% (O 2 > 12% by volume) Class II Extinguishing gas concentration between NOAEL and LOAEL (NOAL < EGC < LOAEL) and oxygen concentration above 10% (O 2 > 10% by volume) Class III Extinguishing gas concentration above LOAEL and below life-threatening concentration (LOAEL < EGC < LTC) and oxygen concentration above 8% (O 2 > 8% by volume). Class IV Extinguishing gas concentration at and above life-threatening concentration (EGC > LTC) and/or oxygen concentration below 8% (O 2 < 8% by volume). The concentrations of the individual extinguishing gases may be gathered from Annex 2 Material Data. 8
9 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems 5 Installation and equipment 5.1 Alarm systems For the warning of persons, flooding zones resp. hazard areas shall be provided with audible and, if required, visual alarm systems in order to ensure the alert of people present in the flooding zone resp. hazard area The signal of the audible alarm devices shall be distinctly different from the operational noises and be at least by 5 db(a) above the environment sound level. If necessary, visual alarm devices shall be available in addition to the audible ones. Visual alarm devices shall provide a conspicuous signal by way of flashing As far as extinguishing systems with gaseous extinguishants are concerned, the extinguishing alarm shall be switched off only after it has been ensured that no unauthorised people can enter the hazard areas any more. This can, for example, be achieved by warning lamps or luminous signs at the entrances to the hazard areas or by locking the entrances. These measures shall be maintained until the hazard areas have been vented and can be entered safely again. Note from the editors: 5.4 to 5.10 of BGI 888 have been replaced by the following tables and paragraphs for better clarity. The content has remained unchanged Electrical or pneumatic alarm systems may be used. One distinguishes between the following types of alarm systems: Type Unsecured alarm device Secured alarms device Simple alarm device Secured alarm device Requirements for energy supply Low voltage supply (230V mains). The supply shall not be able to be interrupted apart from the main distribution panel with its own marked fuse circuit. Secured supply according to DIN VDE Supervision of gas volume Supervision of gas volume Requirements for the cabling from energy supply to alarm devices Secured supply line according to DIN VDE Standard line of supply Double line of supply (separately routed) Table 1: Types of alarm devices The energy supply for the alarm must in any case be sufficient for a duration of 30 minutes In Hazard Classes I and II, at least one of the alarm devices mentioned in shall be used. However, the use of unsecured alarm devices in Hazard Class II is not admissible. 9
10 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01) In Hazard Classes III and IV, at least two of the alarm devices mentioned in shall be used. The alarm systems shall be independent from each other, i.e. separate energy sources, separately routed cables and separate alarm devices. In Hazard Class IV, shall be observed in addition. The admissible combinations for Hazard Classes III and IV are specified in Table For extinguishing systems of Hazard Class IV, the delay and alarm devices shall ensure the alarm and evacuation of people present in the extinguishing area even under adverse conditions. Adverse conditions in the sense of these Guidelines are overvoltages or other electromagnetic influences that may result in the destruction or malfunctioning of /electronic components in alarm or activation devices and thus in an abnormal release of extinguishant. Alarm type 1 Alarm type 2 Unsecured Secured Simple Secured Unsecured not allowed Class III allowed Class IV allowed 3) Class III allowed Class IV not allowed Secured Class III allowed 2) Class IV allowed 2)3) Simple allowed allowed 1) Class III allowed 1) allowed allowed Class IV allowed 3) Secured allowed 1) 1) The requirement for independent energy supplies will not apply if two audible alarms devices are used for low pressure CO 2 systems where both alarm devices are supplied by the extinguishant container. 2) 3) The requirement for independent separated energy supplies will not apply if two secured supplies are used. Only permitted if fire detection and control are exclusively mechanical or. Table 2: Allowed combinations of the two alarm devices required for Hazard Classes III and IV 5.2 Delay devices Extinguishing systems that can cause harm to persons due to flooding shall be provided with delay devices Delay devices shall ensure that flooding will be performed only after the alarm devices have been activated and the set pre-warning time has elapsed For this purpose depending on the Hazard Class of the extinguishing system or non- (mechanical, ) delay devices may be used. The use of delay devices in Hazard Classes III and IV is not admissible. 10
11 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems 5.3 Pre-warning time The pre-warning time shall be long enough to allow leaving the hazard areas from any point without undue haste. It shall be at least 10 seconds long. In addition to the automatic delay device, an emergency stop device may be useful for CO 2 systems, see For total flooding systems, a pre-warning time shall become effective for each automatic or manual release of the extinguishing system For object protection systems, local application systems, or small extinguishing units as per DIN Small extinguishing units, requirements, testing a pre-warning time is required when the entire applicable extinguishing gas quantity exceeds the NOAEL or 5% by volume CO 2 or when the oxygen concentration falls below 12% by volume in the work and traffic area which houses the object to be protected. This is also applicable when several such systems are provided in one room whose activation systems can jointly react to the same event or trigger due to a flooding. This is, for example, prevented when a further activation of adjacent systems is automatically interlocked with the initial activation or when alarm and delay devices are activated in case of a secondary or subsequent activation during which the NOAEL value for the extinguishing gas or 5% by volume CO 2 is exceeded or when the O 2 concentration is less than 12% by volume. 5.4 Emergency stop device In particular cases, an emergency stop device for CO 2 system as an additional facility may be useful provided that it enables the rescue of people prior to commencement of flooding and meets the requirements specified in Annex 3. The use of an emergency stop device is purposeful, for example, when principally at least two persons are present who can help in the event of a release. 5.5 Blocking devices It shall be possible to disable a release of the extinguishing system. The blocking shall be performed mechanically and such that an extinguishant discharge is safely prevented. See also An actuation of the blocking devices shall be clearly visible. This can be achieved, for example, by a visual indication. Note: Additional requirements for the blocking devices are included in the VdS Guidelines 2093, 2380 and
12 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01) 5.6 Overview of alarm and delay devices Corresponding to their Hazard Class evaluation, at least the alarm and delay devices specified in the table below are required for the safe operation of extinguishing systems with gaseous extinguishants. Hazard Class Alarm devices Delay device I II III IV 1) 2) 3) 4) 5) unsecured secured simple secured unsecured secured simple secured unsecured secured simple secured allowed allowed allowed allowed unsecured secured simple secured not allowed allowed allowed allowed unsecured not allowed secured allowed allowed 2) simple allowed allowed allowed 1) secured allowed allowed allowed 1) allowed 1) unsecured not allowed secured allowed 3) allowed 2) 3) simple not allowed allowed allowed 1) secured allowed 3) allowed allowed 1) allowed 1) not required 4) delay non- delay 5) non- delay The requirement for separate energy sources does not apply when two alarm devices are used in CO 2 low pressure extinguishing systems and when both alarm devices are supplied from the extinguishant container. The requirement for separate energy sources does not apply when two secured alarm devices are used. Only admissible when fire detection and control are exclusively mechanical or. Considering psychological aspects, a delayed flooding with pre-warning time should also take place in this case, unless there is a good reason not to do so. For reasons of property protection, this is also advisable since the extinguishing effect can be adversely influenced by the opening of doors during flooding. The non- arrangement is preferred as it is, according to experience, more robust and less prone to failure (EMC). Table 3: Overview of alarm and delay devices 12
13 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems 5.7 Piping Piping must be ly grounded. Grounding serves the purpose of avoiding electrostatic charges. 5.8 Enclosures Rooms that are protected with extinguishing systems shall be arranged such that extinguishants cannot unintentionally escape in such quantities that people in adjacent rooms or areas will be affected. On principle, the tightness of such rooms should be inspected. This applies in particular, when changes result due to conversion, new installations or modifications of the installation If it cannot be prevented that discharging extinguishant also escapes into adjacent rooms or areas, these shall be included in the alarm system. 5.9 Escape routes Escape routes shall be available for all extinguishing and hazard areas. For escape route requirements see Workplace Regulations. In case of an increased hazard to persons due to particular constructional conditions or due to the facility to be protected, shorter escape routes than determined in "Workplace Regulation ASR 10/1 Doors, Gates" may be necessary. Rooms whose single escape and rescue route runs through the extinguishing area have to be treated, as far as alarm and delay are concerned, like the extinguishing area Doors Doors shall be of self-closing construction, swing open in the escape direction and be easily openable from inside at any time and without any other tools. See also Workplace Regulation ASR 10/1 Doors, Gates. In case two or more doors are available, it is sufficient when all doors located in the course of escape and rescue routes conform to the requirements of these regulations. When several doors are available and only one escape and rescue route is provided, then a second door shall conform to these requirements If, for operational reasons, self-closing doors have to be kept open, these shall be fitted with hold-open systems that are designed such that automatic closing on release of the extinguishing system is ensured. 13
14 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01) 5.11 Marking All entrances to hazard areas of Class IV extinguishing systems shall be provided with warning sign W 00 Warnung vor einer Gefahrstelle [Hazard Area Warning] and an additional sign bearing the inscription Gas 1 Extinguishing System In case of fire alarm or discharge of extinguishing gas 1 leave room immediately! Danger to Life! 1 Name of the extinguishing gas used The signs shall conform to the regulation for the prevention of accidents "Sicherheits- und Gesundheitsschutzkennzeichnung am Arbeitsplatz" (BGV A8). At all entrances to hazard areas of extinguishing systems of Classes I, II and III, the term "Danger to Life" may be replaced by "Danger to Health" Operating instructions For extinguishing systems, operating instructions of the installer shall be available in the German language and contain all information required for safe operation. This must include, in particular, information about commissioning; behaviour upon release; maintenance and testing; behaviour in case of fault; behaviour in case of shutdown. 6 Operation 6.1 Proper Operation The owner shall be responsible for the proper operation of extinguishing systems. 6.2 Operating procedure and training The owner shall develop an operating procedure based on the operating instructions provided by the installer, which covers, in particular, all necessary safety information. Suitable operating procedures are, for example, information sheets of the system manufacturers, provided they contain all information important for safety and are easily understandable The owner shall instruct any persons who have access to the hazard areas before they take up their activities as well as regularly, and at least annually regarding any possible hazards of the extinguishant and any necessary protection measures on the basis of the operating procedures. The instruction shall be documented. The instruction may be part of the general instruction at the workplace. 14
15 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems 6.3 Rectification of faults The owner shall have rectified any faults of the extinguishing system which impair personnel protection without delay. If this is not possible, he shall shut down the system. During this time fire protection shall be ensured in another way. 6.4 Blocking of extinguishing systems In case work has to be done in hazardous areas that does not allow leaving of the rooms within the pre-warning time, then the extinguishing system shall be blocked. Work that requires such a blocking can be for example: Work on scaffolds or in narrow rooms When people that have not been instructed (see 6.2.2) are present in the hazard area, the extinguishing system shall be blocked A blocking of the extinguishing system may be purposeful when performing work that may cause unintentional release of the extinguishing system. Work for which such a blocking may be useful can be for example: Work in the extinguishing area that may deceive the fire detection system, testing and maintenance work on the extinguishing system The blocking of extinguishing systems may only be performed or arranged for by a person authorised by the owner and who at the same time is responsible for ensuring fire protection in another way. 6.5 Behaviour in a fire situation Upon release of the extinguishing alarm by audible or visual alarm devices, any people present in the hazard areas have to leave these. Re-entry of the rooms is permissible only after a person authorised by the owner has issued a release for entry of the areas exposed to the extinguishing gas. It is appropriate to fix assembly points where the Insureds have to go to after evacuation of the workplaces. This way, the missing of people who had previously been working in the hazard area can be ascertained. There is a hazard to life not only due to the extinguishing gas or too low an oxygen concentration but also due to the fumes caused by combustion. 6.6 Fighting of initial fires When initial fires are fought manually, the extinguishing work shall not be continued after release of the extinguishing alarm. 6.7 Re-entry of flooded areas Flooded rooms may only be re-entered when a release to do so has been issued by the person authorised by the owner or by the fire brigade after thorough investigation. If required, concentration measurements of the extinguishing gases and of the oxygen concentration need to be performed Flooded rooms shall be ventilated prior to re-entry. In doing so, it shall be ensured that people in adjacent rooms and in the vicinity will not be jeopardised. 15
16 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01) The venting of the flooded rooms shall only be performed by people who have been instructed accordingly. In case the rooms have to be entered for venting, this is permissible only when using a breathing apparatus that is independent from the surrounding atmosphere. 6.8 Use of emergency stop device After operation of the emergency stop device the extinguishing area may be entered during the pre-warning time only for rescuing people. 6.9 Odorisation If there is a risk that people in lower rooms may be jeopardised by the discharge of CO 2, then the extinguishant shall be odorised for olfactory perception by non-toxic additives having an odour that is typical of the hazard. Odorisation of other extinguishing gases may be purposeful in individual cases. A hazard to life by the discharge and accumulation of extinguishants in hazardous concentrations shall be expected in lower unventilated rooms, e.g. in press pits and cellars of hydraulic units. 7 Inspections See also Obligatory inspections The owner shall have extinguishing systems inspected by an expert or a competent person. See also BG-Grundsätze 920 Grundsätze für die Prüfung von Feuerlöschanlagen mit sauerstoffverdrängenden Gasen (Employer's Liability Insurance Association principles 920 "Principles for the inspection of fire extinguishing systems with oxygen-displacing gases"). An expert is who, on account of his technical education and experience, disposes of particular knowledge in the field of extinguishing systems and who is familiar with the relevant national work safety regulations, accident prevention regulations and the generally recognised codes of practice (e.g. rules, DIN standards, VDE regulations, technical rules of other member states of the European Union or other contracting states of the Agreement on the European Economic Area). He shall be capable of inspecting and assessing extinguishing systems. A competent person is who, on account of his technical education and experience, disposes of sufficient knowledge in the field of extinguishing systems and who is familiar with the relevant national work safety regulations, accident prevention regulations and the generally recognised codes of practice (e.g. rules, DIN standards, VDE regulations, technical rules of other member states of the European Union or other contracting states of the Agreement on the European Economic Area) to such an extent that he can evaluate the safe condition of extinguishing systems. The necessary knowledge may, for example, be acquired from the installer of the corresponding system The competent person shall dispose of the technical equipment required for testing, servicing and maintenance. 16
17 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems In case the expert or the competent person finds any deficiencies, he shall report these deficiencies to the owner. The owner shall arrange for the rectification of the deficiencies reported to him In case a hazard to life has to be expected due to the deficiencies found, the extinguishing system shall be shut down. Prior to re-commissioning of the extinguishing system, the owner shall arrange for the rectification of these deficiencies and, within 3 months after re-commissioning at the latest, he shall initiate a new inspection carried out by an expert. See also Approval inspections For extinguishing systems whose use does not involve any hazard to life, the owner shall arrange for an approval inspection carried out by a competent person after installation or after major modifications of the system. The competent person shall document in an approval protocol that the system does not involve any hazard to life. In case of doubt, the Employer's Liability Insurance Association in charge may require the inspection to be carried out by an expert. See also Annex For extinguishing systems during whose operation a hazard to life cannot be excluded, the owner shall arrange for an approval inspection by an expert after installation or after major modifications of the system. This inspection shall have been completed 6 months after commissioning at the latest. For the evaluation of the extinguishing systems, the necessary documents, such as installation certificate, pipework calculation and drawings shall be made available to the expert. Expert: see explanations referring to The owner shall have the expert provide a test report on the compliance with the requirements of these Guidelines The owner shall have these extinguishing systems be subjected to a preliminary inspection by a competent person prior to commissioning, unless the test as per has already been completed. 7.3 Periodical inspections The owner shall, in addition to 7.2.2, have the proper functioning of extinguishing systems, during whose use a hazard to life cannot be excluded, tested by a competent person or expert as required, however, at least once a year. However, periodical inspections of the extinguishing systems shall be carried out by an expert at least every two years. These inspections may, for example, be carried out on an alternating yearly basis by an expert and a competent person, however, an inspection of the extinguishing system by the expert is required every two years. Particular operational conditions may require to have the alarm system inspected at shorter intervals After each release of the extinguishing system, the owner shall have the entire system additionally checked by a competent person. 17
18 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01) 7.4 Inspection records The results of the inspections as per 7.1 to 7.3 shall be recorded in a log book or inspection report. This also applies to deficiencies found or objections against the operation of the system The records about the approval inspections as per 7.2 shall be kept on file over the entire useful life of the extinguishing system The records about the periodical inspections as per 7.3 shall be kept on file for at least 4 years. A storage on EDP data carriers is admissible The records shall be submitted on demand to the authority. 18
19 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems Annex 1 Sample for Approval Protocol Sample for an approval protocol for gas extinguishing systems whose use does not involve any hazard to life Approval protocol for a...gas extinguishing system: Manufacturer/installer:... Type:... Extinguishing gas:... Extinguishing gas quantity:... Chemical composition:... Installation site:... Company:... Flooding zone:... Total flooding/enclosed volume: The room volume (breathing air volume in flooding zone) is approx... m 3. The... gas concentration in the flooding zone does not exceed... % by volume 1) The oxygen concentration in the flooding zone does not fall below... % by volume 1) A harmful... - gas concentration (...% by volume) is not exceeded. A harmful oxygen concentration (12% by volume) is not fallen below. The flooding zone is not accessible. Adjacent rooms/environment shall be separated from the flooding zone in a sufficiently gas-tight way. 1) Evidence of: flooding test with concentration measurement (Report No....) calculation (see annex) Object protection/local application (not or partly enclosed volume): The... gas concentration in the work and traffic area does not exceed...% by volume 1) The oxygen concentration in the work and traffic area does not fall below.% by volume 1) A harmful... gas concentration (...% by volume) is not exceeded. A harmful oxygen concentration (12 % by volume) is not fallen below. The flooding zone is not accessible. The work and traffic area is separated from the flooding zone in a sufficiently gastight way. 1) Evidence of: flooding test with concentration measurement (Report No....) calculation (see annex) Competent person:... Company:... Address: Place, Date Signature 19
20 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01) Annex 2 Material Data The following table specifies examples of presently used extinguishing gases whose data are required for hazard classification. The safety data sheets and its instructions regarding the safe handling of extinguishing gases shall be followed at any rate. This also applies to any extinguishing gases not specified here, for which the relevant safety data sheets shall be adhered to. In the case of gas mixtures the hazardous potential of all components shall be considered. Extinguishing gas NOAEL in % by volume ext. gas LOAEL in % by volume ext. gas LBK in % by volume ext. gas Density at 20 C and 1013mbar in kg/m 3 CO 2 8 IG 01 Argon IG 100 Nitrogen IG 541 (52% nitrogen, 40% argon, 8% CO 2 ) (Trade name: Inergen) IG 55 (50% argon, 50% nitrogen) (Trade name: Argonite) HFC227ea (Trade name: FM-200) FK (Trade name Novec 1230) 5,0 5,0 5,0 1,84 43,0 4 52,0 5 62,0 6 1,662 43,0 4 52,0 5 62,0 6 1,165 43,0 4 52,0 5 62,0 6,7 1,418 43,0 4 52,0 5 62,0 6 1,412 9,0 10,5 12 7,283 10,0 not available not available 13,908 4 corresponds to 12% by volume oxygen 5 corresponds to 10% by volume oxygen 6 corresponds to 8% by volume oxygen 7 corresponds to 5% by volume CO 2 8 from 5% by volume CO 2 a hazard to life is involved Table 4: Toxicity classification for extinguishing gases 20
21 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems Annex 3 Requirements for emergency stop device A 3.1 The CO 2 emergency stop device shall be effective during pre-warning time only. A 3.2 The CO 2 emergency stop device shall be effective for the duration of its uninterrupted operation only. A 3.3 After release of the CO 2 emergency stop device flooding shall start immediately, however, it shall be ensured that the pre-warning time established for the system will be observed. The extinguishing alarm shall continue sounding while the CO 2 emergency stop device is being operated. A 3.4 An operation of the CO 2 emergency stop deivce shall be indicated visually and audibly at a permanently manned location on the premises from which quick help can be initiated. In case a separate parallel indication is required in addition to the indication device, the transmission cable shall be a primary line. Any faults on this primary line shall be indicated on the parallel indication. If this is not possible, the use of a CO 2 emergency stop device is not purposeful. The indication shall remain until it is reset manually. A 3.5 If in electronic data processing systems, this applies for example to EDP areas with false floors >20m² (room and false floor) EDP systems (room, false floor and equipment protection) structurally separated extinguishing areas can be flooded separately as well as all together, then the CO 2 emergency stop device(s) shall act simultaneously on all delay devices. In case of a malfunction in the incoming cables to the CO 2 emergency stop device or in the incoming cables to the controls of the fire extinguishing system required for the stop function (e.g. stop valve) it shall be impossible to initiate an extinguishing function. This also applies to malfunctions that occur during the pre-warning time with or without operation of the emergency stop device. Any malfunction shall be indicated at a permanently manned location. 21
22 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01) Annex 4 (informative) Calculation of the extinguishing gas and of the residual oxygen concentration 1 Extinguishing gas concentration The extinguishing gas concentration prevailing in a room after discharge of the entire extinguishing gas quantity, can be estimated by means of the following equations: 1.1 Inert gases 1 M C = X with x = e ρ V with: C = extinguishing gas concentration in Vol% M = mass of extinguishing gas discharged into the room, in kg ρ = density of extinguishing gas at normal ambient conditions (e.g. 20 C, 1,013 bar), in kg/m³ V = volume of room into which the extinguishing gas is discharged, in m³ 1.2 Halogenated hydrocarbons M C = 100 M + ρ V with: C = extinguishing gas concentration in Vol-% M = mass of extinguishing gas discharged into the room, in kg ρ = density of extinguishing gas at normal ambient conditions (e.g. 20 C, 1,013 bar), in kg/m³ V = volume of room into which the extinguishing gas is discharged, in m³ 2 Residual oxygen concentration The residual oxygen concentration prevailing in a room after discharge of the entire extinguishing gas quantity can be estimated by means of the following equation: O C = 20,9 100 with: O2 = oxygen concentration after flooding in room, in % by volume C = extinguishing gas concentration in % by volume (e.g. calculated acc. Clause 1) Note: The equation is based on an oxygen concentration of 20,9% by volume before flooding (value for dry air). 22
23 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems Annex 5 Rules and Regulations The following relevant rules and regulations need to be observed in particular: Laws, ordinances Labour protection laws Equipment safety law Operational safety ordinance Source of supply: Buchhandel oder Carl Heymanns Verlag KG, Luxemburger Straße 449, Köln Employers Liability Insurance Association (BG) principles and regulations for operational safety and health Regulation for accident prevention Principles of prevention (BGV A1) Regulation for accident prevention Safety and health protection signs at workplaces (BGV A8) BG Regulation "Provision of fire extinguishers at workplaces (BGR 133) BG Regulation "Regulations for the use of breathin apparatus" (BGR 190) BG Principles "Principles for the inspection of fire extinguishing systems with oxygendisplacing gases Source of supply: competent Employers Liability Insurance Association or Carl Heymanns Verlag KG, Luxemburger Straße 449, Köln Standards DIN 2403 Identification of pipelines according to the fluid conveyed DIN Classification of breathing apparatus; Overview DIN 4066 Information signs for fire brigade DIN Portable fire extinguishers; Maintenance DIN EN 3 Portable fire extinguishers DIN Small extinguishing units; Requirements, testing DIN Fire detection and fire alarm systems; Design and operation DIN Danger signals for workplaces DIN EN 54 Components of automatic fire detection and fire alarm systems DIN VDE Alarm systems for fire, intrusion and hold-up; Part 1: General requirements ISO General requirements for the competence of testing and calibration laboratories Source of supply: Beuth Verlag GmbH, Burggrafenstraße 6, Berlin resp. VDE- Verlag GmbH, Bismarckstraße 33, Berlin 23
24 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01) VdS Guidelines VdS Guidelines for CO 2 fire extinguishing systems Planning and installation, VdS 2093 VdS Guidelines for fire extinguishing systems using non-liquefied inert gases VdS 2380 VdS Guidelines for fire extinguishing systems for halocarbon gases VdS 2381 VdS Guidelines for the triggering of fire extinguishing systems VdS 2496 Source of supply: VdS Schadenverhütung GmbH, Amsterdamer Str , Köln 24
25 VdS 3518en : (01) Safety and Health Protection in Connection with Gas Extinguishing Systems 25
26 26 Safety and Health Protection in Connection with Gas Extinguishing Systems VdS 3518en : (01)
5162 E. Working in oxygen-reduced atmospheres BGI/GUV-I 5162 E. Information
5162 E BGI/GUV-I 5162 E Information Working in oxygen-reduced atmospheres November 2013 Imprint About us Publisher: German Social Accident Insurance (DGUV) Mittelstraße 51 10117 Berlin Tel.: 030 288763800
Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230
Technologies Gas extinguishing systems MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 ire protection Efficient and compact MX 1230 fire extinguishing systems fight fires using Novec
COMITÉ EUROPÉEN DES ASSURANCES
COMITÉ EUROPÉEN DES ASSURANCES SECRETARIAT GENERAL 3bis, rue de la Chaussée d'antin F 75009 Paris Tél. : +33 1 44 83 11 73 Fax : +33 1 44 83 11 85 Web : cea.assur.org DELEGATION A BRUXELLES Square de Meeûs,
INERGEN - EXTINGUISHING SYSTEMS
INERGEN - EXTINGUISHING SYSTEMS INERGEN : THE CLEAN SOLUTION. INERGEN extinguishes without leaving any residues, with 100% environmental neutrality to avoid harming nature. As digitalization increases,
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
CO 2. fire extinguishing systems
fire extinguishing systems Extinguishing technique is a colourless, odourless and electrical non-conductive gas. In systems the is mixed with a special identifiable odour. The extinguishing effect of is
IMO. 8 June 1998 *** I:\CIRC\MSC\848.WPD INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR E Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G IMO Ref. T4/4.03 MSC/Circ.848 8 June 1998 REVISED GUIDELINES FOR
ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
GAS EXTINGUISHING SYSTEMS INERT GAS EXTINGUISHING SYSTEMS. Argotec Liquid Argon Gas Extinguishing Technology (LAR)
GAS EXTINGUISHING SYSTEMS INERT GAS EXTINGUISHING SYSTEMS Argotec Liquid Argon Gas Extinguishing Technology (LAR) INNOVATION modern technologie snuffed out cold Argotec liquid argon gas ex tinguishing
BRANCH SOLUTION. Automatic fire extinguishing systems for paint spraying plants. Safe for certain.
BRANCH SOLUTION Automatic fire extinguishing systems for paint spraying plants Safe for certain. ISK IDENTIFYING With the extreme high degree of automation in painting technology, the risk of fire has
ECHM Recommendations for Safety in multiplace medical hyperbaric chambers
ECHM Recommendations for Safety in multiplace medical hyperbaric chambers Coordination and Correspondence : D. MATHIEU, Service d'urgence Respiratoire, de Réanimation Médicale et de Médecine hyperbare
Fire Safety Risk Assessment Checklist for Residential Care Premises
Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or
Control and Indicating Equipment
VdS Guidelines for Fire Detection and Fire Alarm Systems VdS 2540en Control and Indicating Equipment Requirements and Test Methods VdS 2540en : 2010-12 (02) Publishing house: VdS Schadenverhütung GmbH
Alarm and Detection/Suppression
Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent
EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT
EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES
Fire Risk Assessment Safety Checklist
Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory
Safety and Environmental Information for External Companies Koehler Oberkirch
and al and at Work 1. Delivery, Notice, Signature After receiving the following information sheets, the team leader from every external company is required to read through them, explain them to their employees,
Material Safety Data Sheet
1 IDENTIFICATION OF THE SUBSTANCE AND COMPANY a) SUBSTANCE: Natural Gas b) COMPANY: Bord Gáis Éireann PO Box 51 Gasworks Road Cork Telephone: (021) 453 4000 Emergency Telephone: 1850 20 50 50 2 COMPOSITION/INFORMATION
FIRE SAFETY PRECAUTIONS
FIRE SAFETY PRECAUTIONS LOG BOOK PLEASE KEEP AVAILABLE 1 Business Name Premises Information Building / Unit Number Property Name Road: (Address Line 1) (Address Line 2) Locality: Town: Post Code: Name
WORKING IN CONFINED SPACES GUIDELINES
WORKING IN CONFINED SPACES GUIDELINES Contents 1 Introduction... 2 2 Scope... 2 3 Definitions... 2 4 Responsibilities... 3 4.1 Permit Authoriser... 3 4.2 Permit Receiver... 3 4.3 Responsible UOW Officer...
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers
CBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
DETERMINE THE HAZARD VOLUME. The first step is to calculate the total volume of the hazard being protected.
SUBFLOOR PROTECTION CO 2 DESIGN GUIDE The Subfloor Application Profile (AP 006) provides guidance on fire protection requirements for spaces beneath raised floors. In the event of a fire, the Fike Carbon
BRANCH SOLUTION. Fire protection for wind turbines. Safe for certain
BRANCH SOLUTION Fire protection for wind turbines Safe for certain RISKING A FIRE IS RISKING YOUR INVESTM Over the last few years, the generation of electricity from wind energy has become a major technology
FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT This template has been provided to assist the Responsible Person with the preparation of a Fire Risk Assessment and is not intended for commercial
FIRE SAFETY RECORD OF TESTS LOGBOOK
FIRE SAFETY RECORD OF TESTS LOGBOOK PREMISES ADDRESS: Responsible person AN INTRODUCTION TO YOUR LOG BOOK The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person for a premises to
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
SAFETY AND HEALTH PROGRAM
PROGRAM NUMBER NO. PAGES 05-005 10 REVISION ISSUE DATE Revision 2 11/1/2005 SAFETY AND HEALTH PROGRAM Confined Space Entry 1.0 INTRODUCTION Confined Space Entry is a serious workplace hazard, capable of
READ FIRST. Confined Space Entry Procedure. San José State University Environmental Health and Safety. Confined Space Entry Procedure
READ FIRST 1. The purpose of a is to save lives by controlling the inherent hazards of a confined space prior to entry. a. If possible, avoid entering a confined space. Every consideration should be given
Risk Engineering Guideline
www.hdi.global HDI Risk Consulting Risk Engineering Guideline Impairment of fire protection systems Basic protection systems should not be impaired without adequate replace compensation with provisions.
SCBA Frequently Asked Questions
SCBA Frequently Asked Questions Q. WHEN SHOULD I USE SCBA? A. An SCBA is the choice when dealing with any oxygen deficient atmosphere that is IDLH (Immediately Dangerous to Life or Health), or any environment
Safety and Environmental Information for External Companies
1. Delivery, Notice, Signature After receiving the following information sheets, the team leader from every external company is required to read through them, explain them to their employees, and after
Standard the the Raising
Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction
PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
Confined Spaces. The National Food and Drink Manufacturing Conference October 2012
Confined Spaces The National Food and Drink Manufacturing Conference October 2012 Confined spaces A silent killer! What is a confined space Typical hazards Examples of confined space in the food and drink
Fire Safety Log Book
Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton
Natural Gas Emergencies
Natural Gas Emergencies Purpose To protect the personnel within the department, and citizens from the hazards involved in a natural gas emergency. The Incident Commander is to use his/her best judgment
FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie
FIRE SAFETY REGISTER Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie 1 CONTENTS Section Title Page 1.0 Introduction 3 2.0 Guidance for the completion
SAFETY SIGNAGE PROCEDURE
Page 1 of 10 SAFETY SIGNAGE PROCEDURE 1.0 PURPOSE 1.1 To enable a reference to signage to meet legislative requirements and ensure in cases of emergency appropriate signage is visible. 2.0 SCOPE 2.1 This
The terms hazard and risk are often used, which we define as the following:
Fire Safety Last updated in October 2010 This information sheet aims to give safety reps a basic understanding of fire safety and fire risk assessments under the current law. More detailed information
TANKER - SHORE SAFETY CHECK-LIST
TANKE - SHOE SAFETY CHECK-LIST Part A - Bulk Liquid General - Physical Checks Bulk Liquid - General Tanker Terminal Code emarks 1 There is safe access between the tanker and shore. L1 The fendering arrangements
FIRE DETECTION AND ALARM SYSTEMS
HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some
Guidelines for. the employment EXTERNAL COMPANIES
Guidelines for the employment of EXTERNAL COMPANIES on the grounds of Institut für Mikroelektronik Stuttgart Allmandring 30a 70569 Stuttgart Contents 1. Purpose and objective... 3 1.1 General directions...
The Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
Operating instructions Supply system for flammable liquids. Labor
Operating instructions Supply system for flammable liquids Labor Table of contents Safety General safety instructions.................... 2 Warning instructions used in this operating instruction 3 Correct
Safety and Environmental Information for External Companies
Health and and al Health and at 1. Delivery, Notice, Signature After receiving the following information sheets, the assembly leader from every external company is required to read through them, explain
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
Grasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment
Grasshoppers Rugby Football Sports and Social Club The Fire Risk Assessment Revision 1 Dated: 15th February 2013 CONTENTS 1. PREMISES DETAILS 2. PREMISES PLAN 3. HAZARDS 4. HISTORY 5. MITIGATING THE EFFECTS
Guidance for Those Who Use and Store Gas Cylinders
King s Gate Tel 6320 www.safety.ncl.ac.uk Safety Office February 2012 Guidance for Those Who Use and Store Gas Cylinders Version 3 Newcastle University 2012 This guide is designed to help staff manage
INTERNATIONAL STANDARD
IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60
On-Site Risk Management Audit Checklist for Program Level 3 Process
On-Site Risk Management Audit Checklist for Program Level 3 Process Auditor name: Date: I. Facility Information: Facility name: Facility location: County: Contact name: RMP Facility I.D. Phone Number:
MATERIAL SAFETY DATA SHEET
DOT ID No: UN 2187 MATERIAL SAFETY DATA SHEET DOT Hazard Class: 2.2 Emergency No.: +971-6-5336481 Page No. : 1/5 DOT Shipping Label : Non Flammable Gas Date last updated: 22/09/2009 Revision no: 00 1.
HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008
HSE information sheet Fire and explosion hazards in offshore gas turbines Offshore Information Sheet No. 10/2008 Contents Introduction.. 2 Background of gas turbine incidents in the UK offshore sector...2
Fire Policy and Procedures. Cañada Blanch Spanish School
Fire Policy and Procedures Cañada Blanch Spanish School SUMMARY 1. Introduction (p. 3) 2. Roles and responsibilities (p. 3) -- Headteacher -- Fire Team -- All staff -- Contractors 3. Fire procedures (p.
Safe Work in Confined Spaces
Safe Work in Confined Spaces This publication is prepared by the Occupational Safety and Health Branch Labour Department Edition November 2010 This publication is issued free of charge and can be obtained
Committee on Hazardous Substances (AGS)
TRGS 555 Page - 1 - Edition: February 2008 amended and supplemented: GMBl No. 28 p. 608 (date 2.7.2009) Technical Rules for Hazardous Substances Working instruction and information for workers TRGS 555
Performance Specification for Pedestrian Facilities at Temporary Standalone Traffic Signals
traffic systems and signing TR 2503 Issue B February 2006 Performance Specification for Pedestrian Facilities at Temporary Standalone Traffic Signals Crown Copyright 2005 First published 2005 Printed and
Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company
RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing
BS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
Planning Information. Passenger and Freight Elevators.
A company of ThyssenKrupp Elevator Thyssen Aufzüge tk This planning information will give you an overview of the most important planning criteria of passenger and freight elevators. However you should
Compliance Schedules and Building Warrant of Fitness
Compliance Schedules and Building Warrant of Fitness Purpose of this guidance information The purpose of this guidance information is to help building owners and managers of commercial, industrial or communal
Conventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
Confined spaces can be deadly. What is a confined space?
Confined spaces A brief guide to working safely This leaflet explains what you, as an employer, may need to do to protect your employees when working in confined spaces. It will also be useful to the self-employed
* * * EMERGENCY OVERVIEW * * * High pressure gas. Can cause rapid suffocation. Can increase respiration and heart rate.
SUPPLIER ADDRESS: PRODUCT NAME: Saxon Wharf, Lower York St Southampton SO14 5QF, UK 1. CHEMICAL PRODUCT EMERGENCY PHONE NUMBER: COMPRESSED GAS, N.O.S. SYNONYMS: None (Contains: CARBON DIOXIDE & NITROGEN)
melbourne//australia data center specifications internet + intellectual property + intelligence tel: +61 2 9948 8888 fax: +61 2 9948 1111
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Melbourne,. We can colocate standard rack-mountable servers or other
Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book:
Fire Safety Log Book Premises Name: Premises Address: Date From: Date To: Location of Log Book: CONTENTS PART 1 FIRE SAFETY ADVICE 1 PART 2 FIRE PRECAUTIONS 2 Section 1 Guidance on Fire Risks and Preventative
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.
Page 1 of 5 COMPRESSED GASES A compressed gas is defined as any mixture of gases in a container with a pressure exceeding 40 psi. at 70 o F, or 104 psi. at 130 o F; or any flammable liquid with an absolute
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
singapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other
Fire Safety Requirements for Child Care Centre
Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,
RESTRICTED ACCESS AND CONFINED SPACES
Health & Safety Services Unit name goes here Safety Code of Practice 39 1 st Edition, July 2011 RESTRICTED ACCESS AND CONFINED SPACES University of Reading 2015 Page 1 Contents 1 Summary... 3 2 Introduction...
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Confined Space Air Monitoring
November 2008 Vol. 26. No. 3 Confined Space Air Monitoring Scott Shinn, C.I.H. Scott Shinn is a Certified Industrial Hygienist with 3M OH&ESD Technical Service and Regulatory Affairs. Summary Over the
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
ICC CODE CORNER 2012 IFC Code & Commentary
SECTION 908 EMERGENCY ALARM SYSTEMS 908.1 Group H occupancies. Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as required in Chapter
High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance
Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety
Machinery Safety. Presented by Paul Laidler. TÜV SÜD Product Service
Machinery Safety Presented by Paul Laidler Machinery Division Safety Solutions Assistance in meeting the requirements of machinery safety legislation Machinery, Low Voltage and Electro Magnetic Compatibility
8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en
8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................
FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589.
FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589 Bulletin 16-12 Fire Drills This guideline was developed to assist persons
WORK IN CONFINED SPACES
WORK IN CONFINED SPACES STFC Safety Code No 11 Rev. 1.4, Issued April, 2015 Note - This document may have been superseded by a more recent version. Revisions 1 Initial Launch November 2007 1.1 Minor changes
SAFETY AND ENVIRONMENTAL INFORMATION FOR EXTERNAL COMPANIES. Koehler Kehl
1. Delivery, Notice, Signature After receiving the following information sheets, the team leader from every external company is required to read through them, explain them to their employees, and after
MARULENG LOCAL MUNICIPALITY
MARULENG LOCAL MUNICIPALITY Data Centre Physical Access and Environmental Control Policy Draft: Data Centre Access Control and Environmental Policy Page 1 Version Control Version Date Author(s) Details
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
OREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
Rules for Classification and Construction Additional Rules and Guidelines 3 Machinery Installations
VI Rules for Classification and Construction Additional Rules and Guidelines 3 Machinery Installations 5 Guidelines for Design, Equipment and Testing of Gas Welding Installations on Seagoing Ships Edition
26.3.3 The Ship/Shore Safety Check-List
International Safety Guide for Oil Tankers and Terminal Fifth Edition 2006-12-05 26.3.3 The Ship/Shore Safety Check-List Ship's Name Berth Date of Arrival Port Time of Arrival Part `A' - Bulk Liquid General
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
EUROPEAN INDUSTRIAL GASES ASSOCIATION
WORK PERMIT SYSTEMS IGC Doc 40/02/E EUROPEAN INDUSTRIAL GASES ASSOCIATION AVENUE DES ARTS 3-5 B 1210 BRUSSELS Tel : +32 2 217 70 98 Fax : +32 2 219 85 14 E-mail : [email protected] Internet : http://www.eiga.org
Inspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
WASTE Application Form - Dublin Waste to Energy SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE
SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE Describe the existing or proposed measures, including emergency procedures, to minimise the impact on the environment of an accidental emission or spillage.
Confined Spaces Safe Working Practices
Confined Spaces Safe Working Practices INTRODUCTION Any person planning, authorising, directing or supervising work in CONFINED SPACES must comply with the Confined Spaces Regulations 1997. These notes
fulfils all requirements for medium protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages.
The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company EWE TEL GmbH Cloppenburger Straße 310 26133 Oldenburg to confirm that its security area Data Center