PRO Rack/Tower Series UPS. User's Manual
|
|
|
- Flora Chapman
- 9 years ago
- Views:
Transcription
1 PRO Rack/Tower Series UPS User's Manual Para Systems, Inc Lemay Dr. Carrollton, TX Phone: Fax: Internet: minutemanups.com UPS Sizing: sizemyups.com PN R3
2 1. Introduction 2 2. Controls and Indicators 6 3. Installation 7 4. Operation Troubleshooting Replacing the Battery Obtaining Service Specifications Limited Product Warranty 24 A1. Declaration of Conformity 25 Copyright 2009 All rights reserved. All MINUTEMAN trademarks are property of Para Systems, Inc. Other trademarks are property of their respective owners. 1
3 This symbol indicates "Direct Current Supply" This symbol indicates "Equipment Grounding Conductor" Thank you for purchasing this power protection product. It has been designed and manufactured to provide many years of trouble free service. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS! Please read this manual before installing your PRO Rack/Tower Series UPS, models PRO1000RT, PRO1500RT as it provides important information that should be followed during installation and maintenance of the UPS and batteries allowing you to correctly set up your system for the maximum safety and performance. Included is information on customer support and factory service if it is required. If you experience a problem with the UPS please refer to the Troubleshooting guide in this manual to correct the problem or collect enough information so that the Technical Support Department can rapidly assist you. This symbol indicates "ATTENTION" This symbol indicates "Risk of Electrical Shock" This symbol indicates "Alternating Current Supply Phase" CAUTION! Connect the UPS to a two pole, three wire grounding AC wall outlet. The receptacle must be connected to the appropriate branch protection (circuit breaker or fuse). Connection to any other type of receptacle may result in a shock hazard and violate local electrical codes. Do not use extension cords, adapter plugs, or surge strips. CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over-current protection in accordance with the National Electric Code, ANSI/NFPA 70. CAUTION! To reduce the risk of electrical shock with the installation of this UPS equipment and the connected equipment, the user must ensure that the combined sum of the AC leakage current does not exceed 3.5mA. CAUTION! To reduce the risk of electrical shock in conditions where the load equipment grounding cannot be verified, disconnect the UPS from the AC wall outlet before installing a computer interface cable. Reconnect the power cord only after all signaling connections are made. WARNING: This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONLY. WARNING: Risk of Electrical Shock. Hazardous live parts inside these power supplies are energized from the battery even when the AC input is disconnected. 2 This symbol indicates "Alternating Current Supply" CAUTION! To de-energize the outputs of the UPS: 1. If the UPS is on press and release the On/Off/Test Button. 2. Disconnect the UPS from the AC wall outlet. 3. To de-energize the UPS completely, disconnect the battery. 3
4 CAUTION! This UPS series is only intended to be install in an indoor temperature controlled environment that is free of conductive contaminants. CAUTION! The Maximum ambient operating temperature for this UPS series is 40 C ( 0 ~ 40 C for Ambient Operation). ON / OFF / TEST BUTTON: To turn the UPS on: press and hold the On/Off/Test Button until the alarm sounds one beep and then release. The UPS will perform a five second self-test. Once the UPS has passed its self-test the UPS will provide an output and the load will be powered. To turn the UPS off: press and hold the On/Off/Test Button until the alarm sounds one beep and then release. To perform a tensecond battery test: With the UPS in the AC mode, press and hold the On/Off/Test Button until the alarm sounds four beeps, and then release. During the test, the UPS will switch to the Battery mode, the On-Battery icon will illuminate and the alarm will sound. Receiving Inspection After removing your UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored. The packing materials that your UPS was shipped in are carefully designed to minimize any shipping damage. In the unlikely case that the UPS needs to be returned to the manufacturer, please use the original packing material. Since the manufacturer is not responsible for shipping damage incurred when the system is returned, the original packing material is inexpensive insurance. PLEASE SAVE THE PACKING MATERIALS! 4 NOTICE! The output of this device is not sinusoidal. It has a total harmonic distortion and maximum single harmonic as below: PRO1000RT Total harmonic 57.2% Single harmonic 46.1% PRO1500RT Total harmonic 42.8% Single harmonic 26.6% NOTICE: This equipment has been tested and found to comply with the limits for a Class B computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules and the Class B limits for radio noise emissions from digital apparatus set out in the Radio Interference of the Canadian Department of Communications. These limits are designed to provide reasonable protection against such interference in a residential installation. This equipment generates and uses radio frequency and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, this equipment may cause interference to radio and television reception. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Re-orient the receiving antenna. Relocate the computer with respect to the receiver. Move the computer away from the receiver. Plug the computer into a different outlet so that the computer and receiver are on different branch circuits. Shielded communications interface cables must be used with this product. WARNING: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. NOTE: These UPSs are shipped with the batteries disconnected. The batteries must be connected before putting these UPSs into service. Refer to Section 3 "Installation" for connecting the batteries. Life Support Policy As a general policy, we do not recommend the use of any of our products in life support applications where failure or malfunction of the product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. We do not recommend the use of any of our products in direct patient care. We will not knowingly sell our products for use in such applications unless it receives in writing assurances satisfactory to us that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) our liability is adequately protected under the circumstances. Examples of devices considered to be life support devices are neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants, anesthesia ventilators, and infusion pumps as well as any other devices designated as critical by the United States FDA. Hospital grade wiring devices and leakage current may be ordered as options on many of our UPS systems. We do not claim that units with this modification are certified or listed as Hospital Grade by us or any other organization. Therefore, these units do not meet the requirements for use in direct patient care. 5
5 REAR PANEL CONTROL PANEL 1. RS232 Comminucations Port is for UPS monitoring and control. 2. USB Communications Port is for UPS monitoring and control. 3. The RJ11/45 are used for phone/fax/modem and network protection. 4. Accessory Slot is for option cards. 5. Battery Backup & Surge output receptacles for mission critical equipment. 6. Surge ONLY output receptacles for non-critical equipment. 7. Input power cord is for connecting to the Utility Power. 8. Input circuit breaker is for protection against an excessive overload. Model # PRO1000RT PRO1500RT Input Power Plug NEMA 5-15P W/10 ft cord Output Power Receptacles 6-NEMA 5-15R Battery Backup & Surge 2-NEMA 5-15R Surge Only 1. Scroll Button: To scroll through the UPS parameters. 2. Battery Capacity Bar Graph: Displays the amount of Battery Capacity available in the AC and Battery mode. 3. Load Capacity Bar Graph: Displays the amount of load connected to the UPS in the AC and Battery mode. 4. AC normal and Boost/Buck mode Icon: Illuminates when the UPS is in the AC normal mode and flashs when the UPS is in the Boost or the Buck mode. 5. On-Battery Icon: Illuminates when the UPS is operating in the Battery mode. 6. Overload Icon: Illuminates when the amount of load attached to the UPS exceeds its power rating, 7. UPS Parameters and Error codes: Input - Voltage and Frequency. Output - Voltage and Frequency. Estimated Runtime (minutes) - AC normal and Battery mode. S.L.F - A site wiring fault has been detected. FAL - An internal fault has been detected. 8. On/Off/Test Button: To turn the UPS On/Off and to perform a ten-second battery test. 6 INSTALLATION PLACEMENT This UPS series is only intended to be install in an indoor temperature controlled environment that is free of conductive contaminants. DO NOT operate the UPS in: extremely dusty and/or unclean areas, locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight. Select a location, which will provide good air circulation for the UPS at all times. Route power cords so they cannot be walked on or damaged. Typical battery life is 3 to 5 years. Environmental factors do affect battery life. High temperatures, poor utility power, and frequent, short duration discharges have a negative impact on battery life. 7
6 INSTALLATION Be sure to read the installation placement and all the cautions before installing the UPS. Place the UPS in the final desired location and complete the rest of the installation procedure. These UPSs are shipped with the internal batteries disconnected. The batteries must be connected before putting these UPSs into service. See the Connecting The Batteries procedure to connect the batteries. CONNECTING THE BATTERIES (QUALIFIED SERVICE PERSONNEL ONLY) Please read all of the WARNINGS and CAUTIONS before attempting to connect the batteries. 1. Remove the UPS from the shipping box and set on the floor or a bench top. 2. Remove the front panel retaining screws. 3. Lay the front panel on top of the UPS. 4. Verify proper polarity. Connect the battery connectors (red and black) together. NOTE: Some sparking might occur, this is normal. 5. Re-install the front panel onto the UPS. 6. Re-install the front panel retaining screws. 7. Continue with the rest of the Installation. RACKMOUNT CONFIGURATION This UPS comes with mounting brackets for the standard 19" (46.5cm) rack. The mounting brackets to fit a 23" (59.2cm) standard rack are also available. The screws for mounting the UPS to the rack are not included (screw size varies with rack size). 1. Locate the mounting bracket screw holes on the side panels of the UPS, at the front of the UPS. NOTE: The mounting brackets can also be mounted in the middle of the UPS. 2. Align the mounting bracket with the mounting bracket screw holes. 3. Attach the mounting bracket with the retaining screws. 4. Mount the UPS into the rack and secure with the retaining screws. WARNING: Use two or more people when installing the UPS. Use CAUTION, the UPS is extremely heavy. Do not move the rack after the units have been installed. The rack may be unstable due to the weight distribution. 5. The Rackmount Configuration is complete. See Connecting your Equipment 8 TOWER CONFIGURATION The tower configuration allows the user to install the UPS in the up-right position next to the tower computer. The tower brackets are provided with the UPS. WARNING: Use two or more people when installing the UPS. Use CAUTION, the UPS is extremely heavy. 1. Once the location of the UPS has been determined, place the tower brackets in the desired location. WARNING: The UPS must be installed in the proper up-right position. If the UPS is not installed in the proper up-right position the Batteries will be damaged. Once the UPS is placed in the tower position, looking at the front panel the YELLOW Battery disconnected label on the top cover of the UPS MUST be on your left hand side. 9
7 2. The LCD face plate can be rotated to read in the up-right position. Remove the front panel from the UPS. On the backside of the front panel, push the LCD face plate outwards the face plate will pop out. Position the LCD face plate so that it reads in the up-right position. Re-install the front panel on the UPS. 3. The two rackmount brackets are used for the two tower brackets. Remove the retaining screws and attached the tower brackets as shown. The tower brackets go on both sides of the UPS. Make sure that the UPS is stable. 4. The Tower Configuration is complete. See Connecting your Equipment. 4. Use the template to mark the screw hole position on the wall. CAUTION, you should always were protective gear for your hands and eyes when operating power tools. 5. Attach the four retaining screws to the wall and make sure that all of the retaining screws are screwed into structural material. Then clean the area of any loose material. Do not tighten the retaining screws all the way, leave approximately 3/8" of the retaining screws sticking out. 6. Position the UPS, so that the mounting bracket keyed holes line up with the four retaining screws. Slide the UPS down until its resting securely on the four retaining screws. 7. Tighten the four retaining screws to secure the UPS to the wall. 8. The Wallmount Configuration is complete. See Connecting your Equipment. WALLMOUNT CONFIGURATION The wallmount configuration allows the user to mount the UPS on the wall. There is a wallmount bracket kit available for the UPS. The kit includes two wall mounting brackets, ten retaining screws, and the wallmount template. WARN- ING: Use two or more people when installing the UPS. Use CAUTION, the UPS is extremely heavy. The UPS's side panels have mounting bracket screw holes for attaching the wall mounting brackets. 1. Once the location and position of the UPS has been determined, lay the UPS down flat. WARNING: The UPS must be installed in the proper up-right position. If the UPS is not installed in the proper up-right position the Batteries will be damaged. Once the UPS is placed on the wall, looking at the front panel the YELLOW Battery disconnected label on the top cover of the UPS MUST be on your left hand side. 2. Align the mounting brackets with the mounting bracket screw holes and attach with the six retaining screws. 3. The LCD face plate can be rotated to read in the up-right position. Remove the front panel from the UPS. On the backside of the front panel, push the LCD face plate outwards the face plate will pop out. Position the LCD face plate so that it reads in the up-right position. Re-install the front panel on the UPS. 10 CONNECTING YOUR EQUIPMENT Plug the mission critical equipment into the Battery Backup & Surge output receptacles on the rear panel of the UPS. Plug the non-critical equipment into the Surge Only output receptacles on the rear panel of the UPS. Ensure that the connected equipment does not exceed the maximum output rating of the UPS (refer to the information label on the UPS or the electrical specifications in this manual). DO NOT PLUG EXTENSION CORDS, ADAPTER PLUGS, SURGE STRIPS OR POWER STRIPS INTO THE OUTPUT RECEPTACLES OF THE UPS. NOTE: Risk of damaging the UPS and/or connected equipment. CAUTION! DO NOT connect a laser printer to the output of the UPS. 11
8 CONNECTING THE UPS TO AN AC SOURCE CAUTION - To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over-current protection in accordance with the National Electric Code, ANSI/NFPA 70. Plug the UPS into a two pole, three wire, grounded receptacle only. DO NOT PLUG THE UPS INTO EXTENSION CORDS, ADAPTER PLUGS, SURGE STRIPS OR POWER STRIPS. DO NOT CUT THE INPUT PLUG OFF AND ATTEMPT TO HARDWIRE THIS UPS, DO- ING SO WILL VOID THE WARRANTY. CHECKING THE SITE WIRING FAULT After plugging the UPS into the wall outlet, check the LCD screen on the front panel of the UPS for a Site Wiring Fault (S.L.F). If the S.L.F is illuminated, the UPS is plugged into an improperly wired wall outlet. If the UPS indicates a Site Wiring Fault (S.L.F), have a Qualified Electrician correct the problem. CHARGING THE BATTERY The UPS will charge the internal batteries whenever the UPS is connected to an AC source and there is an acceptable AC voltage present (90-150VAC). It is recommended that the UPS's batteries be charged for a minimum of 4 hours before use. The UPS may be used immediately, however, the On Battery runtime may be less than normally expected. Typical battery life is 3 to 5 years. Environmental factors do affect battery life. High temperatures, poor utility power, and frequent, short duration discharges have a negative impact on battery life. NOTE: If the UPS is going to be out of service or stored for a prolonged period of time, the batteries must be recharged for at least twentyfour hours every ninety days. COMMUNICATIONS PORT CONNECTION (OPTIONAL) The power monitoring software and interface cables can be used with the UPS. Use only the interface cables that come with these UPSs. Connect the interface cable (Serial or USB) to the appropriate communications port on the rear panel of the UPS. Connect the other end of the cable to the device that will be monitoring/controlling the UPS. NOTE: Connecting to the Communications Port is optional. The UPS works properly without this connection. ACCESSORY SLOT (OPTIONAL) The Accessory slot on the rear panel of the UPS is for an SNMP Card or a Dry Contact Relay card. Contact your local dealer for the available option cards. NOTE: Connecting to the Communications Port is optional. The UPS works properly without this connection. NETWORK/PHONE/FAX/MODEM PROTECTION CONNECTION (OPTIONAL) Connect a 10/100 Base-T network, single line phone, Fax or Modem line to the RJ11/45 modular connectors on the rear panel of the UPS. This connection will require another length of telephone or network cable. The cable coming from the telephone service or networked system is connected to the port marked IN. The equipment to be protected is connected to the port marked "OUT". NOTE: Connecting to the Network/Phone/Fax/Modem modular connectors is optional. The UPS works properly without this connection. 12 CAUTION! The TNV connector shall use the same type of RJ45. SYSTEM OVERVIEW This Line-Interactive UPS protects computers, servers, telecom systems, VoIP systems, security systems, and a variety of electronic equipment from blackouts, brownouts, overvoltages, and surges. The AVR function continuously corrects the voltages, in-between the brownout and overvoltage transfer points (90-150VAC), to a safe usable level. When the UPS is operating in the AVR mode the audible alarm will remain silent and the AC normal mode indicator will blink. During normal AC operation, the UPS will quietly and confidently protect your system from power anomalies. The UPS will charge the batteries with the UPS in the on or off position when the UPS is plugged into the wall outlet and there is an acceptable AC voltage present (90-150VAC). When a blackout, brownout, or an overvoltage condition occurs; the UPS will transfer to the battery mode, the On Battery indicator will illuminate and the audible alarm will sound once every five seconds indicating that the commercial power is lost or unacceptable. When the commercial power returns or is at an acceptable level, the UPS will automatically transfer back to the AC normal mode and start recharging the batteries. During an extended outage when there is approximately two minutes of backup time remaining the audible alarm will sound twice every five seconds. This Low Battery Warning is informing the user that they should save all open files and turn off their computer. When the batteries reach the predetermined level the UPS will automatically shutdown protecting the batteries from over discharging. Once the commercial power returns the UPS will automatically restart, providing safe usable power to the connected equipment and start recharging the batteries. TURNING THE UPS ON / OFF To turn the UPS on: press and hold the On/Off/Test Button until the alarm sounds one beep and then release. The UPS will perform a five second internal self-test. Once the UPS has passed its internal self-test the UPS will provide an output and the load will be powered. To turn the UPS off: press and hold the On/Off/Test Button until the alarm sounds one beep and then release. TEST BUTTON To perform a ten-second user invoked battery test: With the UPS in the AC normal mode, press and hold the On/Off/Test Button until the alarm sounds four beeps, and then release. During the test, the UPS will switch to the Battery mode, the On-Battery icon will illuminate and the alarm will sound. SCROLL BUTTON Press the Scroll Button to scroll through the UPS parameters. The UPS parameters are displayed on the LCD screen. 13
9 LCD SCREEN The LCD provides the user with a variety of useful information. The LCD has a realtime meter to display, in numeric fashion, the following data: Input Voltage and Frequency Output Voltage and Frequency Connected Load Capacity Battery Capacity Estimated runtime in the AC and DC mode The LCD will include dedicated icons for the following information: AC Normal On Battery AVR Mode (Boost and Buck) The AC Normal icon will flash Overload Weak/Bad Battery (Battery Capacity Bar Graph will flash) Site Wiring Fault (S.L.F. will be displayed) UPS Fault (FAL will be displayed) The LCD does have a backlight that will turn on when the UPS is turned on. After approximately 20-seconds the backlight will turn off to conserve energy. When an event (alarm) occurs, such as going to the battery mode, the backlight will turn on for approximately 20-seconds to alert the user that an event has occurred and then the backlight will turn off. While the Scroll button is in use the backlight will remain on. Approximately 20-seconds after the Scroll button has stopped being used the backlight will turn off to conserve energy. SELF-TEST The self-test feature is useful to verify the correct operation of the UPS and the condition of the batteries. The length of the test that is automatically performed every two weeks is longer than the start-up or user invoked test. This every two week test will run for approximately fifteen-seconds to measure the battery s capability to support the output load. The start-up and user invoked test will run for approximately ten-seconds. If the UPS fails one of these tests, one of the icons or the information displayed on the LCD will remain illuminated indicating the type of problem. NOTE: The UPS will automatically perform a self-test on start-up and every two weeks. RS232 COMMUNICATIONS PORT The power monitoring software and interface cables can be used with the UPS. Use only the interface cables that come with these UPSs. The RS232 communication port is a standard DB9 female with both RS232 and simulated contact closure capability. The pinout for the port is depicted per the chart below: Pin 1: Simulated contact closure Low Battery Warning, NO Pin 2: /TXD Pin 3: /RXD and receive UPS shutdown command (connect a minimum of +5VDC to a maximum of +12VDC for 4-seconds to completely shutdown the UPS. The shutdown command is ONLY active in the battery mode) Pin 5: Ground Pin 8: Simulated contact closure AC fail, NO Pins 4, 6, 7, 9: Not Used ACCESSORY SLOT The Accessory slot on the rear panel of the UPS is for an SNMP Card or a Dry Contact Relay card. Contact your local dealer for the available option cards. 14 USB COMMUNICATIONS PORT This UPS series supports USB communications. Use the interface cable that comes with the UPS. The USB communications protocol is HID. The HID USB driver comes standard in the Windows OS. Simply plug the USB cable into the UPS and the computer then follow the prompts on the screen. POWER MONITORING SOFTWARE The UPS comes with power monitoring software. See the software CD for the installation of the power monitoring software. ALARMS ON BATTERY When the UPS is operating on the batteries, the AC normal icon will extinguish, the On-Battery icon will illuminate and the alarm will sound one beep every five seconds. Once the UPS returns to the normal AC mode, the alarm will stop, the On- Battery icon will extinguish and the AC normal icon will illuminate. LOW BATTERY WARNING When the batteries reach the predetermined level, the alarm will sound two beeps every five seconds and the Battery Bar Graph will display the remaining battery capacity. This condition will continue until either AC returns or the UPS s self protection circuit shuts the UPS down to protect the battery from over discharging. WEAK/BAD BATTERY The UPS automatically tests the battery s condition. If the battery is weak, bad or disconnected, the Battery Capacity Bar Graph will flash and the alarm will sound three beeps every five minutes until the battery is either reconnected or replaced. This alarm will be repeated until the batteries pass a self-test. It is recommended that the UPS be allowed to charge overnight before performing a battery test to confirm a Weak/Bad Battery condition. OVERLOAD When the amount of load attached to the UPS exceeds its power rating, the Overload icon will illuminate and the alarm will sound continuously (AC and Battery modes). This alarm will remain on until the excess load is removed or the UPS s self protection circuit shuts the UPS down. To clear the overload alarm when the UPS has shutdown requires that the UPS perform a battery test. First remove part of the load, then turn the UPS on, the Overload icon and the alarm will be on. Second either use the Test Button or unplug the input power cord to perfom the battery test. UPS FAULT When the UPS detects an internal fault, "FAL" will be displayed on the LCD screen, the alarm will sound continuously and the output will be turned off. The fault condition, in some instances, may be reset by turning the UPS off and then on. If the fault condition does not clear the UPS must be sent in for service. BATTERY OVER CHARGE PROTECTION If the charger is providing too much voltage to the battery the UPS will turn off the charger to protect the battery. When the charger voltage exceeds 14.52V/battery the charger will turn off. The alarm will sound three beeps every five seconds and the Battery Capacity Bar Graph will flash. In some instances, the charger may be reset by turning the UPS off and then on. When the charger voltage exceeds 15.0V/battery the charger will turn off. The alarm will sound three beeps every five seconds and the Battery Capacity Bar Graph will flash. The UPS will automatically transfer to the battery mode and operate until the UPS shuts down due to battery exhaustion. The UPS must be sent in for service. 15
10 Symptom Possible Cause UPS will not turn on On/Off/Test button not pressed UPS operates in Input AC circuit breaker is battery mode only, tripped even though there is normal AC present "FAL" is displayed on the LCD The AC mode icon is illuminated, but there is no output UPS does not provide expected runtime The Battery Capacity Bar Graph is flashing Overload icon is illuminated The AC mode icon is flashing and the alarm is silent "S.L.F" is displayed on the LCD UPS has detected an internal fault The UPS is being controlled via its communications port The batteries may be weak or at the end of their useful service life Loose connections at the batteries, Weak batteries, Bad batteries The output load has exceeded the UPS's capacity The UPS is operating in the Boost or the Buck mode The UPS has detected an improperly wired wall outlet. What To Do Press, hold and then release the On/Off button to start UPS Reset circuit breaker by pressing the plunger back in. If the AC circuit breaker trips after UPS starts up, reduce the load on the UPS Call for service Disconnect the computer cable from the UPS and press the On button. If UPS works normally, the software has control of the UPS Charge the batteries for 8- hours and retest. If the runtime is still less than expected, the batteries may need to be replaced, even though the Weak/Bad Battery LED is not illuminated Check battery connections, charge the batteries for 8- hours, replace the batteries Check the specifications (see section 8). Remove part of the load The UPS is performing its intended function Contact a Qualified Electrician to correct the problem. REPLACING THE BATTERY (QUALIFIED SERVICE PERSONNEL ONLY) Please read all of the WARNINGS and CAUTIONS before attempting to service the batteries. Typical battery life is 3 to 5 years. Environmental factors do affect battery life. High temperatures, poor utility power, and frequent, short duration discharges have a negative impact on battery life. WARNING! This UPS contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONLY. CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be toxic. CAUTION: Do not dispose of batteries in a fire. The batteries may explode. The batteries in this UPS are recyclable. Dispose of the batteries properly. The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly. Refer to local codes for proper disposal requirements or return the battery to the supplier. CAUTION: The battery system can present a risk of electrical shock. These batteries produce sufficient current to burn wire or tools very rapidly, producing molten metal. Observe these precautions when replacing the batteries: 1. Remove watches, rings, or other metal objects. 2. Use hand tools with insulated handles. 3. Wear protective eye gear (goggles), rubber gloves and boots. 4. Do not lay tools or other metal parts on top of batteries. 5. Disconnect the charging source prior to connecting or disconnecting the battery terminals. 6. Determine if the battery is inadvertently grounded. If the battery is, remove the source of the grounding. Contact with any part of a grounded battery can result in an electrical shock. The likelihood of such shock will be reduced, if such grounds are removed during installation and maintenance
11 CAUTION: Replace batteries with the same number and type as originally installed in the UPS. These batteries have pressure operated vents. These UPSs contain sealed non-spillable maintenance-free lead acid batteries. Model # PRO1000RT PRO1500RT 6. Remove the front panel retaining screws. (FIG. 2) 7. Lay the front panel on top of the UPS. FIG. 2 Battery Module Part # BM0043 BM0044 BATTERY REPLACEMENT PROCEDURE PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING TO REPLACE THE BATTERIES Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. To hot-swap the battery module start with step number Turn off the equipment that is plugged into the output of the UPS. 2. Press the On/Off/Test Button on the front panel to turn the UPS off. 3. Unplug the UPS's AC power cord from the AC wall outlet. 4. Unplug the equipment from the output receptacles of the UPS. 5. Unplug the computer interface cable from the rear panel of the UPS. FIG Remove the two retaining screws for the battery retaining bracket. (FIG. 3) 9. Remove the battery retaining bracket. FIG
12 10. Disconnect the Battery connectors (red and black). (FIG. 4) 11. Grasp the battery pull tab and gently pull the battery module out of the UPS and set aside. NOTE: Use Caution, the battery module is heavy. FIG. 4 IF THE UPS REQUIRES SERVICE 12. Slide the new battery module into the UPS. 13. Re-install the battery retaining bracket. 14. Re-install the two retaining screws for the battery retaining bracket. 15. Verify proper polarity. Reconnect the battery connectors (red and black). NOTE: Some sparking might occur, this is normal. 16. Re-install the front panel on the UPS. 17. Re-install the front panel retaining screws. 18. Properly dispose of the old batteries at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries. 19. The UPS is now ready for the normal operation. NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the battery module, the user must initiate a self-test to clear the Weak/Bad Battery Alarm. To initiate a self-test see section 4 "TEST BUTTON". 1. Use the TROUBLESHOOTING section to eliminate obvious causes. 2. Verify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem. 3. Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem call or fax the Technical Support department at the following numbers; Voice phone (972) , FAX line (972) or contact Minuteman UPS at [email protected]. Please have the following information available BEFORE calling the Technical Support Department. A. Your name and address. B. Where and when the unit was purchased. C. All of the model information about your UPS. D. Any information on the failure, including LEDs that may be illuminated. E. A description of the protected equipment, including model numbers if possible. F. A technician will ask you for the above information and, if possible, help solve your problem over the phone. In the event that the unit requires factory service, the technician will issue you a Return Material Authorization Number (RMA #). G. If the UPS is under warranty, the repairs will be done at no charge. If not, there will be a charge for repair. 4. Pack the UPS in its original packaging. If the original packaging is no longer available, ask the Technical Support Technician about obtaining a new set. It is important to pack the UPS properly in order to avoid damage in transit. Never use Styrofoam beads for a packing material. A. Include a letter with your name, address, day time phone number, RMA number, a copy of your original sales receipt, and a brief description of the problem. 5. Mark the RMA # on the outside of all packages. The factory cannot accept any package without the RMA # marked on the outside. 6. Return the UPS by insured, prepaid carrier to: 20 Para Systems Inc. MINUTEMAN UPS 1455 LeMay Drive Carrollton, TX ATTN: RMA # 21
13 Model Number Topology Maximum Power Capacity Number of Phase Nominal Voltage Acceptable Input voltage Voltage Range Frequency Limits Low Voltage Transfer Point High Voltage Transfer Point Input Protection Voltage Range Efficiency (Line Mode) Waveform Type Nominal Voltage Voltage Regulation Frequency Transfer Time Protection SYSTEM SPECIFICATIONS PRO1000RT Line-Interactive, Simulated Sine Wave 1000VA 700W INPUT Single (1 2W +G) 120VAC 0-160VAC VAC 50 or 60 Hz, +/-5Hz, autosensing 90V resets to Utility Power at 94V or higher 150V resets to Utility Power at 146V or lower Resettable Circuit Breaker OUTPUT NON-BATTERY OPERATION VAC Voltage Regulation 120VAC: -13.3% % Frequency Range 60Hz: 55-65Hz or 50Hz: 45-55Hz Overload Capacity >90% (Full Load) OUTPUT BATTERY OPERATION Simulated Sine Wave (Step Wave) 120VAC Nominal +/-5% (until Low Battery Warning) 50/60Hz, +/-0.5Hz (unless synchronized to utility) 6 ms Typical PRO1500RT 1500VA 1050W AC Mode: 110% for 5-seconds then fault, 120% Shutdown Immediately DC Mode: 110% for 10-seconds then shutdown, 120% Shutdown Immediately Over-Current, Short-Circuit Protected and Latching Shutdown REGULATORY COMPLIANCE Battery Type Typical Recharge Time Typical Battery Life Battery Module Part # Runtime: Half Load (minutes) Runtime: Full Load (minutes) Surge Energy Rating Surge Current Capability Surge Response Time Surge voltage let-through (as a percentage of an applied ANSI C62.41 Cat. A +/-6 kv) 10/100 Base-T surge protection let-through (as a percentage of an applied +/-6 kv 1.2/50 us, 500 a 8/20 us test) Telephone line surge protection let-through (as a percentage of an applied +/-6 kv 1.2/50 us, 500a 8/20 us test) Noise Filter Audible Noise at 1 m (3 ft.) Size - Net L X W X H Weight - Net Size - Shipping L X W X H Weight - Shipping BATTERY SYSTEM Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid From Full load dishcarge: 4-hours to 80%, 8-hours to 90% 3 to 5 years. Environmental factors do affect battery life. High temperatures, poor utility power, and frequent, short duration discharges have a negative impact on battery life. BM0043 SURGE PROTECTION AND FILTERING 1140 J 6500 Amps total BM ns (instantaneous) normal mode; <5 ns common mode < 5% < 5% < 1% >45db normal and common mode EMI/RFI suppression <45 dba ENVIRONMENTAL Operating Temperature 0 to 40 degrees C (+32 to +104 degrees F) at Operating Elevation 0 to 1,500m (0 to +5,000 ft) Operating Temperature 0 to 35 degrees C (+32 to +95 degrees F) at Operating Elevation 1501 to 3,000m (0 to +10,000 ft) Storage Temperature -15 to +45 C (+5 to +113 F) Operating/Storage Humidity 95% Non-Condensing Storage Elevation 0 to 15,000m (0 to +50,000 ft) 17 5 PHYSICAL 15.7 x 17.3 x 3.5" 398 x 440 x 89 mm 35.1 lbs 15.9 Kgs 40.8 lbs 18.5 Kgs 20.7 x 21.9 x 8.5" 526 x 555 x 215 mm 43.0 lbs 19.5 Kgs 48.5 lbs 22.0 Kgs Safety and Approvals EMC Verification ctuvus (conforms to UL1778, CSA 22.2 standards) FCC Class B, CE certified 22 23
14 A1. DECLARATION OF CONFORMITY Para Systems, Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equipment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. The customer pays for shipping the unit to Para Systems. Para Systems pays ground freight to ship the unit back to the customer. Replacement parts and warranty labor will be borne by Para Systems. For equipment located outside of the United States and Canada, Para Systems only covers faulty parts. Para Systems products repaired or replaced pursuant to this warranty shall be warranted for the unexpired portion of the warranty applying to the original product. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. Application of Council Directive(s): 89/336/EEC, 73/23/EEC Standard(s) to which Conformity is declared: Manufacturer s Name: Para Systems, Inc. (MINUTEMAN UPS) Manufacturer s Address: 1455 LeMay Drive Carrollton, Texas USA Type of Equipment: Uninterruptible Power Supplies (UPS) Model No: PRO1000RT, PRO1500RT EN55022, EN55024 EN , EN EN The warranty shall be void if (a) the equipment is damaged by the customer, is improperly used, is subjected to an adverse operating environment, or is operated outside the limits of its electrical specifications; (b) the equipment is repaired or modified by anyone other than Para Systems or Para Systems approved personnel; or (c) has been used in a manner contrary to the product s User's Manual or other written instructions. Any technical advice furnished before or after delivery in regard to use or application of Para Systems s equipment is furnished without charge and on the basis that it represents Para Systems s best judgment under the circumstances, but it is used at the recipient s sole risk. EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation of implied warranties; therefore, the aforesaid limitation(s) may not apply to the purchaser. EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, Para Systems is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, cost of substitutes, claims by third parties, or otherwise. The sole and exclusive remedy for breach of any warranty, expressed or implied, concerning Para Systems s products and the only obligation of Para Systems hereunder, shall be the repair or replacement of defective equipment, components, or parts; or, at Para Systems s option, refund of the purchase price or substitution with an equivalent replacement product. This warranty gives you specific legal rights and you may also have other rights which vary from state to state. Year of Manufacture: Beginning November 1, 2009 I hereby declare that the equipment specified above conforms to the above Directive(s). Robert Calhoun (Name) Manager Engineering (Position) Place: Carrollton, Texas, USA Date: November 1, 2009 No employee, salesman, or agent of Para Systems is authorized to add to or vary the terms of this warranty
15 26 Notes: Notes: 27
Entrust Series UPS. User's Manual
Entrust Series UPS User's Manual 1. Introduction 2 2. Controls and Indicators 6 3. Installation 7 4. Operation 10 5. Troubleshooting 12 6. Replacing the Battery 13 7. Obtaining Service 16 8. Specifications
User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply
User Manual English APC Smart-UPS SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack-Mount Uninterruptible Power Supply 990-1851C, 10/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed
PRO-E SERIES. User's Manual
PRO-E SERIES User's Manual Para Systems, Inc. 1455 Lemay Dr. Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.com PN - 34000226 Rev. 1 PRO-E
User Manual. English. APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC. Tower Uninterruptible Power Supply
User Manual English APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC Tower Uninterruptible Power Supply 990-1587A 12/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent
Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS
+ Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
Endeavor Series On-Line UPS User's Manual
Endeavor Series On-Line UPS User's Manual Para Systems, Inc. 1455 Lemay Dr. Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.com PN - 34000274
User s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
Owner s Manual. Not suitable for mobile applications. Important Safety Instructions 2. Quick Installation 3. Basic Operation 4. Storage & Service 7
Register online today for a chance to win a FREE Tripp Lite product! www.tripplite.com/warranty Owner s Manual Internet Office & BC Personal UPS Systems Not suitable for mobile applications. Important
Installation and Operation Back-UPS 1250, 1300, 1500
Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with
APC Step-Down Transformer. User s Manual
APC Step-Down Transformer Models: AP9621, SURT005, SURT006, SUTF3, SYTF2, SYTF2J, SYTF3 and SYTF3J User s Manual English 990-7820D, July 2003 TABLE OF CONTENTS APC Contact Numbers and Support Visit the
Powerware 5110 UPS User s manual
Powerware 5110 UPS 2005 Eaton Corporation All Rights Reserved The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care
Back-UPS 650 VA 120 V with AVR (BX650CI-LM)
Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit
BroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
Back-UPS Pro 1300/1500 Installation and Operation
Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a
User Manual. English. APC Smart-UPS 1000/1500 VA 100/120/230 VAC 750/1000XL VA 120/230 VAC. Tower Uninterruptible Power Supply
User Manual English APC Smart-UPS 1000/1500 VA 100/120/230 VAC 750/1000XL VA 120/230 VAC Tower Uninterruptible Power Supply 990-1074C 06/2012 Introduction American Power Conversion Corporation (APC) is
Triple Expansion Chassis
Triple Expansion Chassis AP9604 Installation Manual Contents Introduction............................. 1 Installation.............................. 2 Power Considerations...................... 5 Operations..............................
User Manual. English. APC Smart-UPS. 2200 VA 120/230 Vac. 3000 VA 100/120/208/230 Vac. 2U Rack Mount Uninterruptible Power Supply
User Manual English APC Smart-UPS 2200 VA 120/230 Vac 3000 VA 100/120/208/230 Vac 2U Rack Mount Uninterruptible Power Supply 990-1352A 11/2003 Introduction The APC Uninterruptible Power Supply (UPS) is
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
750VA/1000VA/1500VA 100/120/230VAC 2U
User s Manual English Smart-UPS 750VA/1000VA/1500VA 100/120/230VAC 2U Rack Mount Uninterruptible Power Supply 990-1194 5/02 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
Operation Manual. Smart-UPS C. Uninterruptible Power Supply. Tower 1000/1500 VA. 120/230 Vac. su0813a
Operation Manual Smart-UPS C Uninterruptible Power Supply Tower 1000/1500 VA 120/230 Vac su0813a Product Description The APC by Schneider Electric Smart-UPS is a high performance uninterruptible power
Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.
Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial MODEL NUMBER: SMART2200RM2U Highlights 2.2kVA / 2200VA / 1920W line interactive 2U
USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018
USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and
User Manual. Smart-UPS TM C. Uninterruptible Power Supply SRC250 SRC450. 110/120/230 Vac. Tower/Rack-Mount 1U
User Manual Smart-UPS TM C Uninterruptible Power Supply SRC250 SRC450 110/120/230 Vac Tower/Rack-Mount 1U Smart-UPS TM C Uninterruptible Power Supply 250/450 VA 110/120/230 Vac Tower/Rack-Mount 1U English
How To Install A Power Supply (Uplast) With A Battery Pack
APC Smart-UPS RT SURTA48XLBP/SURTA48XLBPJ External Battery Pack User Manual Introduction/Before Installation About this Manual The APC Smart-UPS RT external battery pack (SURTA48XLBP or SURTA48XLBPJ) connects
Online UPS. PowerWalker VFI 1000R/1U
Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
CAUTION. CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage and minor or moderate injury.
Product Description The APC by Schneider Electric Smart-UPS is a high performance uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts,
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
Line Interactive UPS
EN Line Interactive UPS PowerMust 636 LCD (650VA), Line Int., Schuko PowerMust 848 LCD (850VA), Line Int., Schuko PowerMust 636 LCD (650VA), Line Int., IEC PowerMust 848 LCD (850VA), Line Int., IEC PowerMust
Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6. User s manual
Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6 User s manual Index Safety Warnings... 2 1 Introduction... 3 2 General Characteristics... 4 3 Receipt and site selection... 4 4 EXTERNAL
Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U
Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U SURT192RMXLBP2 SURT192RMXLBP2J English 990-2485B 02/2009 Introduction About this UPS The American Power Conversion (APC ) SURT192RMXLBP2 external
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
Power Max Level 2 Charging Station en Installation and Operating Instructions This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the
User s Manual. Professional Rack Mount LCD Series PR1000ELCDRT2U/PR1500ELCDRT2U/ PR2200ELCDRT2U K01-0000070-01
EN User s Manual Professional Rack Mount LCD Series PR1000ELCDRT2U/PR1500ELCDRT2U/ PR2200ELCDRT2U K01-0000070-01 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS This manual contains important
How To Use A Power Supply Unit (Upland)
Pure Sine Wave Line Interactive UPS PowerWalker VI 1000RT/LE PowerWalker VI 1500RT/LE Manual Uninterruptible Power Supply System SAFETY INSTRUCTION CAUTION 1 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL [email protected] / www.tuncmatik.com Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3.
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
Out-of-Band Management Card
Out-of-Band Management Card AP9608 Installation Manual Related Documents For information on using the Out-of-Band Management Card after installation and startup, see the online User s Guide specific to
Model 70A00-1. GSM Cellular Communications Center
Home Automation, Inc. Model 70A00-1 GSM Cellular Communications Center Operation Manual Document Number 70I00-1 Rev A August, 2009 Contents Description... 1 Use with security systems...1 Everyday use...2
Line Interactive UPS. PowerWalker VI 500T/HID PowerWalker VI 750T/HID PowerWalker VI 1000T/HID PowerWalker VI 1500T/HID.
Line Interactive UPS PowerWalker VI 500T/HID PowerWalker VI 750T/HID PowerWalker VI 1000T/HID PowerWalker VI 1500T/HID Quick Start Guide CONTT IMPORTANT SAFETY INSTRUCTIONS... 1 1. Introduction... 4 2.
UPS-2200R-HH/UPS-2200R-HHIP
USER MANUAL UPS-2200R-HH/UPS-2200R-HHIP RACKMOUNT UNINTERRUPTIBLE POWER SUPPLY C UL R US LISTED 082410-01 THANK YOU Thank you for purchasing the UPS-2200R-HH/UPS-2200R-HHIP Rackmount UPS. The UPS provides
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS, Sine
SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial
SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMX1000RT2U Highlights 1kVA / 1000VA / 900W line-interactive 2U rack/tower UPS, Sine
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS,
UPS 1000-2200 VA User s Manual
UPS 1000-2200 VA Powerware 5125 1000 2200 VA Table of contents 1. Introduction... 7 2. Installation... 8 Inspecting Equipment... 8 Installing UPS... 8 UPS Rear Panels... 9 3. Operation and Configuration...
user s manual Battery Case model #: SPB3200 Battery Case Charger for Samsung Galaxy S 4
user s manual model #: SPB3200 Charger for Samsung Galaxy S 4 What s Included Unpack the battery case and make sure all accessories are put aside so they will not be lost. hello. USB to Micro USB Cable
Residential Gateway (RG) Battery Backup REV B
Residential Gateway (RG) Battery Backup REV B Save this user manual This manual contains important instructions regarding the installation and operation of this device. Read this manual thoroughly before
User Manual. Smart-UPS. Uninterruptible Power Supply 750/1000/1500 VA. 100/120/230 Vac. Rack Mount 2U
User Manual Smart-UPS Uninterruptible Power Supply 750/1000/1500 VA 100/120/230 Vac Rack Mount 2U Smart-UPS TM Uninterruptible Power Supply 750/1000/1500 VA 100/120/230 Vac Rack-Mount 2U EN 990-1194E 08/2014
SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial
SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMART500RT1U Description Tripp Lite's SMART500RT1U intelligent, line-interactive rack/tower uninterruptible
SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial
SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SMART1000RM1U Description Tripp Lite SMART1000RM1U 1000VA / 1kVA / 800 watt line interactive,
Uninterruptible Power Supply
96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features
Wireless Indoor/ Outdoor Thermometer
Wireless Indoor/ Outdoor Thermometer Owner s Manual Please read before using this equipment. ˆ Contents FCC Information... 3 FCC Declaration of Conformity... 5 Preparation... 5 Installing Batteries...
USB to RS232 Adapter User s Manual
USB to RS232 Adapter User s Manual 34000212 Rev0 Table of Contents Warnings...3 Introduction...4 USB to RS232 Adapter Package Contents...4 Setup Procedure...5 Setup Procedure for Windows 98, ME, and 2000...5
User Manual. English. APC Smart-UPS RT. 3000/5000/6000 VA 200-240 VAC Tower/Rack Mount 3U Uninterruptible Power Supply
User Manual English APC Smart-UPS RT 3000/5000/6000 VA 200-240 VAC Tower/Rack Mount 3U Uninterruptible Power Supply 990-1289D 03/2006 Introduction The APC Smart-UPS RT is a high-performance, uninterruptible
User Manual 1K/2K/3K Online UPS
User Manual 1K/2K/3K Online UPS Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4. Operation...
USER MANUAL Online UPS 1K/2K/3K Rack
USER MANUAL EN Online UPS 1K/2K/3K Rack Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3. Installation 2 1-4. Operation 2
350, 500, 650 and 1000 MODELS
P D Technology Ltd PDT Power Series Instruction Manual Domestic, Commercial & Industrial PLEASE READ THE INSIDE FRONT COVER BEFORE INSTALLING THE PDT POWER SERIES 350, 500, 650 and 1000 MODELS P D Technology
APC Smart-UPS 2400/3000 VA 100/110-120 VAC 3U. Uninterruptible Power Supply
User Manual English APC Smart-UPS 2400/3000 VA 100/110-120 VAC 3U Tower/Rack Mount Uninterruptible Power Supply 990-2233A 02/2005 Introduction/Before Installation Introduction/Before Installation About
SmartPro 230V 750VA 500W Line-Interactive Sine Wave UPS, SNMP, Webcard, Tower, USB, DB9 Serial
SmartPro 230V 750VA 500W Line-Interactive Sine Wave UPS, SNMP, Webcard, Tower, USB, DB9 Serial MODEL NUMBER: SMX750SLT Highlights 750VA line interactive tower UPS; Sine wave output 220/230/240V nominal
User Manual. English. APC Smart-UPS RT. 8000/10000 VA 200-240 Vac Tower/Rack-Mount 6U Uninterruptible Power Supply
User Manual English APC Smart-UPS RT 8000/10000 VA 200-240 Vac Tower/Rack-Mount 6U Uninterruptible Power Supply 990-2689D 01/2007 Introduction The APC Smart-UPS RT is a high-performance, uninterruptible
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
7 High-Resolution Digital Photo Frame
TM 16-1003 User s Guide 7 High-Resolution Digital Photo Frame One demo photo included, as illustrated Please read this user s guide before using your new photo frame. Package contents Photo Frame AC Adapter
AC Power For Business-Critical Continuity. Liebert PSI. User Manual 750/1000/1500/2200/3000, 230VAC
AC Power For Business-Critical Continuity Liebert PSI User Manual 750/1000/1500/2200/3000, 230VAC TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS................................................1 GLOSSARY
EKOS Cart. Instructions for Use
EKOS Cart Instructions for Use EKOS Corporation 11911 North Creek Parkway South Bothell, WA 98011 USA (425) 415-3100 (tel) (425) 415-3102 (fax) [email protected] (e-mail) - 1-4913-002 REV E Intended Use
Model #: SMART2200CRMXL
Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: [email protected] Model #: SMART2200CRMXL SmartPro Compact Rackmount UPS System - Precision Protection for
SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial
SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial MODEL NUMBER: SMART1500SLT Highlights 1.5kVA / 1500VA line interactive tower UPS; Sine wave output
Weather Radio Alarm Clock
1200093 User s Guide Weather Radio Alarm Clock Thank you for purchasing your Weather Radio Alarm Clock from RadioShack. Please read this user s guide before installing, setting up, and using your new weather
Mini Power Bank and Charger
Mini Power Bank and Charger Owner s Manual Please read before using this equipment. Your charger is ETL listed to UL standards and meets all applicable FCC standards. WARNING: To reduce the risk of fire
OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port
OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port MODEL NUMBER: OMNIVS1500 Highlights 1500VA / 1.5kVA tower 120V line-interactive UPS Corrects brownouts and overvoltages from 75 to 147V
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial MODEL NUMBER: SMARTINT3000VS Highlights 3kVA / 3000VA / 2250W line interactive tower UPS system 230V
Installation and Operation
Installation and Operation Smart-UPS ΤΜ SR1 Uninterruptible Power Supply SR18KXIET SR110KXIET 220/230/240 Vac Tower suo0759b Smart-UPS TM SR1 Uninterruptible Power Supply 8000/10000 VA 220/230/240 Vac
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial
TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SM1000RM1UTAA Description Tripp Lite SM1000RM1UTAA 1000VA / 1kVA / 800 watt line
AXIS T81B22 DC 30W Midspan
INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial
2013 VTech Printed in China 91-009656-000 US
Rechargeable Power Pack User s Manual 2013 VTech Printed in China 91-009656-000 US INTRODUCTION The Rechargeable Power Pack makes it easier than ever to keep the InnoTab 3 or InnoTab 3S charged and ready
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V APC Smart-UPS, 670 Watts / 1000 VA,Input 230V / Output 230V, Interface Port DB-9 RS-232, SmartSlot, USB Includes: CD with software, Smart UPS signalling
110244-003. PrintPAD CN3/4/3e/4e. User Guide
110244-003 PrintPAD CN3/4/3e/4e User Guide TABLE OF CONTENTS PrintPAD CN3/4 & PrintPAD CN3e/4e Printer Views...1 Open View...1 Closed View...1 Using Batteries: General Guidelines...1 Installing and/or
Installation Guide Smart-UPS X Tower/Rack-Mount 2U 2000/2200/3000 VA
Installation Guide Smart-UPS X Tower/Rack-Mount 2U 2000/2200/3000 VA Important Safety Messages Read the instructions carefully to become familiar with the equipment before trying to install, operate, service
USER MANUAL Online UPS 1K/2K/3K
USER MANUAL EN Online UPS 1K/2K/3K Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1.1. Transportation 2 1.2. Preparation 2 1.3. Installation 2 1.4. Operation 2 1.5.
ADSL Modem Installation Guide. Model # 36R515 Part # 030-300108 Rev. D Revision Date 12/2000. ADSL Modem Installation Guide
ADSL Modem Installation Guide Model # 36R515 Part # 030-300108 Rev. D Revision Date 12/2000 ADSL Modem Installation Guide Installation Instructions Westell ADSL Modem 1. Package Inspection and Contents...2
HP R12000 and R18000 DirectFlow UPS User Guide
HP R12000 and R18000 DirectFlow UPS User Guide Abstract This document includes installation, configuration, and operation information for the HP R12000 and R18000 DirectFlow UPS. This document is for the
Installation Guide Smart-UPS X External Battery Pack SMX120BP
Installation Guide Smart-UPS X External Battery Pack SMX120BP Inventory Inspect the contents upon receipt. Notify the carrier and dealer if there is damage. Two bezels Tie brackets used to secure multiple
iosafe Solo External Hard Drive
Users Manual & Limited Warranty iosafe Solo External Hard Drive USB 2.0 Fireproof Waterproof FloSafe Cooling Technology Data Recovery Service 910-10841-00 REV 7.1 2 COPYRIGHTS Copyright iosafe, Inc. 2009.
EATS16 EATS16N. Installation and user manual ENGLISH. Copyright 2015 EATON All rights reserved.
ENGLISH EATS6 EATS6N Installation and user manual Copyright 05 EATON All rights reserved. Service and suppt: Call your local service representative SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual
NFC Communication Tray Model: HHX-IT3-Z
INSTRUCTION MANUAL NFC Communication Tray Model: HHX-IT3-Z ENGLISH CONTENTS Introduction...3 Important safety information...4 Know your unit...6 Transferring data to the PC...7 Care and maintenance...8
10000HXL31/15000HXL31/20000HXL31
Table of Contents www.eaton.com/dxups USER MANUAL ON LINE UPS 10000HXL31/15000HXL31/20000HXL31 Uninterruptible Power Supply Table of Contents 1. Brief introduction 1.1 System and model description---------------------------------------------------------------------1
Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P
Technical Data Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P Topic Page 1609-P Specifications 2 1609-P Approximate Dimensions and Shipping Weights 3 Additional Resources
User Guide for the Wireless Headset (HS-11W) 9235346 Issue 1
User Guide for the Wireless Headset (HS-11W) 9235346 Issue 1 DECLARATION OF CONFORMITY We, NOKIA CORPORATION declare under our sole responsibility that the product HS-11W is in conformity with the provisions
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
QuickSpecs. Models HP T1500 UPS JPN/TWN. HP UPS T1000 G2, T1500 G2 Models Overview
Overview The Tower UPS "G2" models are the next generation HP tower UPSs with USB support. These new UPSs are designed to provide advanced power protection (or increased uptime and data corruption avoidance)
3 WATT LED SPOTLIGHT Model No. SLM - 3801
3 WATT LED SPOTLIGHT Model No. SLM - 3801 OWNER'S MANUAL Customer Service Tel: 1-800-268-3319 Superex Canada Ltd, Toronto,M2H 3B8 Made in China Table of Contents A). Important Safety Instructions B). Charging
3U, 2200 VA Audio/Video Pure Sine Wave UPS System
3U, 2200 VA Audio/Video Pure Sine Wave UPS System MODEL NUMBER: HTR22-3U Description Tripp Lite's HTR22-3U Pure Sine Wave 2200VA/1600W on-line, double-conversion UPS system prevents media data loss, equipment
Conference Phone UserÕs Manual. Part No. 54-2070-01R1 Printed in Korea. 2002 Bogen Communications, Inc.
Part No. 54-2070-01R1 Printed in Korea. 2002 Bogen Communications, Inc. UserÕs Manual Notice Every effort was made to ensure that the information in this guide was complete and accurate at the time of
AXIS 291 1U Video Server Rack Installation Guide
AXIS 291 1U Video Server Rack Installation Guide About This Document This document describes how to install Axis blade video servers in the AXIS 291 1U Video Server Rack. Updated versions of this document
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
Alarm Clock USER GUIDE
Alarm Clock USER GUIDE Jazwares, Inc. 2012 CONTENTS Please read the instructions along with the Alarm Clock carefully before you use it, so that you can operate it conveniently. WELCOME & Warnings Page
READ FIRST! Universal Car/Air Adapter User Manual
AutoAir Manual 1/9/03 2:03 PM Page 1 READ FIRST! Universal Car/Air Adapter User Manual Congratulations! Your new Kensington Universal Car/Air Adapter is a highly efficient Universal Car/Air Adapter for
Installation & Operation Manual
GET CONNECTED Installation & Operation Manual DEVICE INTEGRATION AND CHARGING KIT TranzIt USB IS32 Note to Readers, The information contained within the following documentation is subject to change without