1 TITLE Long Term Maintenance and Care for S36A E. C. Wright 02/09/04 This document is to be used in conjunction with Installation, Operation and Maintenance Schedule IOMS 635. Its aim is to provide guidance for owners of equipment which has been in service more than 25 years. Contents Introduction Page 2 Key Questions Page 2 Condition Assessment Page 3 Non-Intrusive PDM Page 3 Dynamic Characteristics Page 5 Asbestos Page 6 Recommended Care Program Page 6 Spares for Maintenance Page 6 Factory Based Overhaul Page 6 Factory Based Rebuild-Refurbishment Page 7 Recommendation for Life Extension Page 7 Beta Arc Protection Page 7 Appendix 1 Recommended Maintenance Regime Page 9 Appendix 2 Maintenance Spares Page 10 Appendix 3 Up-rating & Retrofit Page 22 1
2 Introduction During normal every day operation, switchgear works well within its design envelope and therefore, even after many years of service, appears superficially to be OK. Fault clearance however may require the equipment to work at near maximum performance and substandard equipment will be susceptible to significant damage. To maintain rating capability key components/functions must be in good operational condition: The above does not indicate that the product has a limited lifespan, if fact the S36A range has proven to be very reliable when well looked after. We can actually take advantage of the sub-station history of older equipment to design bespoke maintenance, which will not only extend the working life but will reduce the chance of catastrophic damage and can even reduce maintenance costs. The owner of older equipment (25 years and beyond) should have the information which will allow him to design a maintenance plan to suit his needs. This document will help with that process. Key Questions 1. How often is the equipment switched? 2. Is this switching duty at full rated current or well below rated current? 3. How often does the system see a fault? 4. What environmental conditions exist within the sub-station? Is the switchgear dirty or damp or both? (we are concerned here mainly with the primary insulation) 5. Do we know the condition of the primary functional systems of the switchgear a. Primary Insulation. b. Contacts, and Arc Chutes. c. The dynamic operating characteristics of mechanism and contacts. Points 1 to 4 should be available from historical records and we will look later how we will use this information. Point 5 is actually our recommended starting point. We feel it is logical to make a condition assessment of the equipment, and instigate any repairs prior to introducing a new maintenance regime. Using the condition assessment approach at suitable intervals will also help ensure full rating capability is maintained. 2
3 Condition Assessment Recommended site testing For condition assessment of Reyrolle S36A Speed Curving - In house electronic system Using original test parameters. Non-intrusive Discharge Non-intrusive Discharge Monitoring. Discharge monitoring is recommended to identify any possible deterioration of filled joints such as the shrouds in the Busbar and Transformer Chambers, surface discharges on primary insulation and similar possible sources. The system used is non-intrusive. Magnetic probes are attached to the outer skin of the switchgear and are designed to pickup magnetic wave pulses, a phenomenon of electrical discharge. Each probe will pick up a source of discharge but the monitor can determine by time of flight which probe is closest to the source. (see diagrams below) The monitor sweeps the probes approximately every 5 minutes over a period (usually one week) and therefore can determine if the problem is constant, the level and therefore the severity. Recommendations will be given. Owners of the switchgear can be shown how to transfer monitoring equipment from one board the next and information to ourselves for analysis. 3
4 Our report gives graphical information, explanation and recommendation for repair. Part of the graphical information from a recent report is shown below. 4
5 Dynamic Contact and Mechanism Characteristics When a circuit breaker design passes its short circuit and mechanical operations type tests, certain dynamic characteristics are recorded and used as a profile in all subsequent routine production tests. In other words every production circuit breaker should have the same rating capability. A typical speed curve is shown below. The above test combined with visual inspection of Contacts and Arc Chutes will give a very good indication of rating compatibility. 5
6 Asbestos It should be noted that S36A Arc Chutes contain White Asbestos components. Current UK legislation requires 1. Owners should have a register of where asbestos is located. 2. If the Arc Chutes are in good condition they can be left in service. 3. If the Arc Chutes are removed from site they must have the asbestos removed. VA TECH Product Services can provide an Asbestos removal and Arc Chute refurbishment service. Recommended Care Program Appendix 1 As suggested earlier an alternative program of care to that shown in IOMS 635 should be introduced when the equipment has been in service longer than 25 years. Spares for normal maintenance needs Appendix 2 These spares are recommended for the normal wear and aging of the equipment. Up-rating & Retrofit Appendix 3 Factory based Overhaul When site based maintenance procedures cannot achieve consistent and correct circuit breaker operation. Our factory based overhaul service is designed to bring a circuit breaker back to full rating capability with the minimum work. This is achieved by a process of an initial test and inspection to establish work to be done and an agreement with the customer to proceed. Traveler circuit breakers can be made available to reduce outage times. Factory based Rebuild-Refurbishment This process is recommended for circuit breakers older than 25 years. The process is a complete rebuild with replacement of key components and wiring which achieves an almost As New result. The end result not only re-establishes rating but dramatically extends the working life of the equipment. 6
7 Recommendation to achieve Life Extension and Low Cost of Ownership. The process recommended in Appendix 1, a combination of Refurbishment, Condition Assessment and Bespoke Maintenance will extend the working life of the equipment. The logic of this is shown diagrammatically below. The process of targeted or bespoke maintenance also has the potential to reduce maintenance cost. BETA ARC FAULT PROTECTION In the early 1990 s the requirement for Internal Arc Protection on all new Primary Switchgear designs became part of IEC and UK EATS specifications. The driver for introducing this was of course safety for the operator. Adding design features to cope with the specification is relatively straight forward when starting a new product design. However retrofitting the capability on existing designs is generally not viable. 7
8 The advent of the BETA protection device gives us a viable method of achieving the IEC Arc Fault criteria as a retrofit solution on old air insulated chambers. As a bonus, BETA not only gives enhanced operator safety, but it dramatically reduces the possibility of collateral damage Faults will be contained in chamber of origin. BETA protection can be used to protect the following S36A chambers Circuit Breaker Busbar Current Transformer Air insulated cable boxes. (cable boxes may be compound filled) The principle of BETA operation is shown below. 8
9 APPENDIX 1 Recommended Maintenance Regime for S36A in service over 25 years. Interval Circuit Breaker Enclosure 25 years Rebuild Refurbishment Discharge Monitoring 8 year Discharge Monitoring Speed Curve Interrupter Inspection Clean and Lubricate Discharge Monitoring Clean and Lubricate Touch-up paint if necessary 4 year Only required for poor environments (8 year report may Clean and Lubricate (Discharge Monitoring) Clean and Lubricate Touch-up paint if necessary (Discharge Monitoring) suggest additional tests) Every 2000 operations at low system current. Clean, lubricate and inspect mechanism. Every 2000 operations at high system current. Clean, lubricate and inspect mechanism. Interrupter Inspection After Fault Interrupter Inspection Yearly if CB not operated Electrical Close & Trip several times. APPENDIX 2 Maintenance Spares Extracted from IOMS 635 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 Appendix 3 Up-rating It is not practical to up-rate the 500 MVA unit to 750 MVA. It is possible to up-rate the 750 MVA unit to give an enhanced make capability of 900 MVA Retrofit A vacuum retrofit circuit breaker is available, they can be fitted to all circuit breakers rated up to 11kV 1200A 750MVA. On-board surge suppressors can be fitted for motor circuit applications. Before After Refurbishment After Retrofit 21
DISTRIBUTION OPERATIONS AND MAINTENANCE
EB-00-00 Filed: 00 Aug Page of DISTRIBUTION OPERATIONS AND MAINTENANCE PREVENTIVE MAINTENANCE Preventive Maintenance is intended to maintain or improve customer service reliability, extend equipment life
CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services
CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services SpecialistS IN ELECTRICAL SUPPORT SERVICES TO MINING, UTILITIES & industry Ampcontrol is committed to supporting our customers to maintain efficient
Houston Service Center Medium Voltage Service and Aftermarket Solutions
Houston Service Center Medium Voltage Service and Aftermarket Solutions Table of contents Introduction...3 Breaker refurbishment...4 Protective relay & control service and support...5 Power Service and
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
ICM Project Station Infrastructure and Equipment
EB 0 00 Schedule B. ( pages) ICM Project Station Infrastructure and Equipment (THESL) EB 0 00 Schedule B. I EXECUTIVE SUMMARY 0. Project Description Many Municipal Substations (MS) located outside of downtown
Advantages of Fixed Circuit Breaker Switchgear
Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker
Extend the Life of Existing Switchgear
Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...
Session Four: Internal Arc Safety in New and Existing Switchgear
Session Four: Internal Arc Safety in New and Existing Switchgear Richard Blakeley RPS SWITCHGEAR LIMITED 1. INTRODUCTION Commercial pressures are increasing on organisations to maximise their plant utilisation,
Residual life aspects on GIS with the focus on SF 6
Residual life aspects on GIS with the focus on SF 6 Speaker: Karsten Pohlink 25. March 2015 The presentation refers to CIGRÉ WORKING GROUP B3.17 RESIDUAL LIFE CONCEPTS APPLIED TO HV GIS CIGRE Technical
Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.
Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850
Relion Power system protection and automation reference Extending substation life cycle with IEC 61850 Extending substation life cycle with IEC 61850 A step-by-step power system retrofit approach for optimizing
Enhance Power Equipment Reliability with Predictive Maintenance Technologies
Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of
Comparison between Gas- and Air Insulated Network Concepts with the Life Cycle Cost Method
Comparison between Gas- and Air Insulated Network Concepts with the Life Cycle Cost Method Ingo Jeromin, Gerd Balzer, Technische Universität Darmstadt, Jürgen Backes, Richard Huber, EnBW Regional AG Stuttgart
Service Power Technologies. Retrofitting A future-oriented concept in lifecycle management
Retrofitting A future-oriented concept in lifecycle management Retrofit solutions for gas-insulated switchgear > 50 kv to 170 kv ABB-supplied high-voltage substations generally have a service life of approx.
Predictive Maintenance
PART ONE of a predictive maintenance series Predictive Maintenance Overview Predictive maintenance programs come in all shapes and sizes, depending on a facility s size, equipment, regulations, and productivity
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
SF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV
MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
Effective Condition Assessment of Medium Voltage Switchgear
Effective Condition Assessment of Medium Voltage Switchgear Abstract There is a general trend within electricity distribution companies and operators of large private electricity networks to extend maintenance
Decision model for End of Life management of switchgears
Decision model for End of Life management of switchgears Hans Picard Jan Verstraten Mirjam Hakkens Rudy Vervaet Eaton Electrical Dow Chemical Eaton Electrical Dow Chemical (retired) Europalaan 202 P.O.
Electrical switchgear and safety: A concise guide for users
Electrical switchgear and safety: A concise guide for users Introduction This leaflet is aimed at owners and operators of electrical switchgear in industrial and commercial organisations who have little
Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy
Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay
Electrical Predictive and Preventative Maintenance
Electrical Predictive and Preventative Maintenance Electrical and mechanical equipment is subject to failure at the worst possible time for no apparent reason. - Mose Ramieh III There are two types
Safe and secure distribution of medium voltage with AX1
Safe and secure distribution of medium voltage with AX1 The intelligent switchgear AX1 is a modern, air-insulated switchgear that lies at the very front line of safety and security safety for operating
Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS)
TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012
TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012 Session 2 Technological challenges to cope with in TWENTIES field tests
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
Evaluating Fire- and Heat-Damaged Electrical Equipment
Evaluating Fire- and Heat-Damaged Electrical Equipment www.nema.org 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to heat
21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
High Voltage Electrical Equipment Failure Diagnosis. Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd
High Voltage Electrical Equipment Failure Diagnosis Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd High Voltage Electrical Equipment Failure Diagnosis Definition of High Voltage
Electrical Shore Connections / Cold Ironing
STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version
uptimeplus.co.uk predictive maintenance strategy galileo Supported by
uptimeplus.co.uk predictive maintenance strategy galileo Supported by Why galileo? The search for an alternative maintenance methodology is a result of general lack of visibility on asset s reliability,
Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering
LOW VOLTAGE CIRCUIT BREAKER GUIDELINES FOR DATA CENTERS Reliability requires consulting engineers and end users to grasp design, maintenance basics By Reza Tajali, P.E. Square D Power Systems Engineering
Proactive Asset Management for GIS A six step process for reducing risk, cost, and improving reliability
White paper Proactive Asset Management for GIS A six step process for reducing risk, cost, and improving reliability Gas Insulated Substations (GIS) are often critical assets for most organizations. GIS
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been
How To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
New standardized approach to arc flash protection
New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200
Keeping electrical switchgear safe
Keeping electrical switchgear safe Keeping electrical switchgear safe Health and Safety Failure of electrical switchgear can cause death, serious injury and major damage. If you own or operate this type
UFES Active protection for switchgear
Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
Best Practice Catalog Generator Switchgear
Best Practice Catalog Generator Switchgear Revision 2.0, 8/23/2012 Prepared by MESA ASSOCIATES, INC. Chattanooga, TN 37402 and OAK RIDGE NATIONAL LABORATORY Oak Ridge, Tennessee 37831-6283 managed by UT-BATTELLE,
www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.
s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage
Document 7 Asset Category 11kV Switchgear SPN
Document 7 Asset Category 11kV Switchgear SPN Asset Stewardship Report 2014 Brian Matthews Approved by Richard Wakelen / Barry Hatton Document Date 03/03/2014 Document History Version Date Details Originator
employed to ensure the continuing reliability of critical systems.
4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective
Fusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Predictive Maintenance in a Mission Critical Environment
March 2009 Predictive Maintenance in a Mission Critical Environment This paper discusses the need to proactively protect mechanical and electrical support systems in data processing centers and data storage
ABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE
Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
Model 1756 Test Lead Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you
CAPACITOR BANK TESTING SWP
1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.
EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK
EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK F. Malone*, P.D. Doyle *ESB International, Ireland [email protected] ESB International, Ireland [email protected]
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
PD Monitor GIS. 24/7 Partial Discharge (PD) monitoring system for Gas Insulated Switchgear. Benefits NEW PRODUCT
NEW PRODUCT PD Monitor GIS 24/7 Partial Discharge (PD) monitoring system for Gas Insulated Switchgear For automatic, continuous monitoring of mission critical GIS assets Benefits The most cost effective
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
CERTIFICATE ISO 9001:2008 ISO 14001:2004 BS OHSAS 18001:2007. hereby certifies that the company
CERTIFICATE ISO 9001:2008 ISO 14001:2004 BS OHSAS 18001:2007 hereby certifies that the company ABB AG - Energietechnik Division Energietechnik Produkte/-Systeme business field: Development, Marketing,
Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
Emirates Aluminium starts up World s first fully integrated power distribution system from ABB
Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s
Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.
Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
ELECTRICAL SAFETY RISK ASSESSMENT
ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
Protect your home and family with Advanced Technology from Cutler-Hammer
Protect your home and family with Advanced Technology from Cutler-Hammer Residential Home Fire Statistics Annually - over 415,000 Residential Fires Annually - over 40,000 electrical fires over 350 deaths
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au
ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks
Technical Electrical Field Service Support. Knowledge + Experience = Power. Field Service
Technical Electrical Field Service Support Knowledge + Experience = Power Field Service WRE Field Service Wismer & Rawlings Electric Ltd. Substation Testing and Commissioning Mission Statement To be recognized
Erik Backström, High Voltage breakers, After Sales & Service High voltage SF 6 live tank circuit breakers After Sales & Service Training course
Erik Backström, High Voltage breakers, After Sales & Service High voltage SF 6 live tank circuit breakers After Sales & Service Training course description HPL 72,5-300 B1 with BLG1002A Level A & B Training
High-Voltage GIS yesterday - today - tomorrow
High-Voltage GIS yesterday - today - tomorrow Peter Glaubitz, Siemens AG, Principal Expert GIS-Technology siemens.at/future-of-energy Table of content GIS yesterday beginning and establishment of Gas-
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
Engineering Specification
Engineering Specification Electrical 33KV AC INDOOR SWITCHGEAR NON-WITHDRAWABLE Owner: Approved by: Chief Engineer, Electrical Neal Hook Chief Engineer Electrical Authorised by: Version 2.1 Issued May
Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring
Siemens Integrated Substation Condition Monitoring System Circuit Breaker Monitoring System Description Introduction The Circuit Breaker Monitor [CBM] is only one example of the way that the Substation
Relion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE
Relion Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Fast substation busbar protection with IEC 61850 and GOOSE Falu Elnät AB applies new power
690 V is a good alternative in the process industry
690 V is a good alternative in the process industry The process industry in the Nordic countries generally uses voltage of 690 V for process motors, whereas Central Europe, Great Britain and the USA usually
Communicate and view data from meters with one simple device
Communicate and view data from meters with one simple device PowerLogic EGX300 integrated gateway-server Web Monitoring Communications Plug and Play Plug into your energy usage with a simple mouse click
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
EVANS ENTErprises, Inc.
EVANS ENTErprises, Inc. Since 1954 THE LEADER IN ELECTRO-MECHANICAL SALES, SERVICE AND INTERGRATION Our Mission Our purpose at Evans Enterprises is to serve customers by providing increased value of product
Energy Transmission and Distribution Services
Energy Transmission and Distribution Services Business segment presentation Asset Services Energy is an essential part of our daily lives Industry Education Mobility Workplace Entertainment Homes Healthcare
Ultrasound Condition Monitoring
Ultrasound Condition Monitoring Whitepaper Alan Bandes UE Systems, Inc. Abstract: Instruments based on airborne/structure borne ultrasound technology offer many opportunities for reducing energy waste
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
Medium Voltage Distribution FLUVAC. Vacuum Circuit Breaker Up to 24 kv 630 A 21 ka. Operation Maintenance Instructions. www.schneider-electric.
Medium Voltage Distribution FLUVAC Vacuum Circuit Breaker Up to 24 kv 630 A 21 ka Operation Maintenance Instructions www.schneider-electric.com Contents Introduction... 3 Our Service Unit: our specialists,
ACS INDOOR SWITCHGEAR
ACS INDOOR SWITCHGEAR Fleet Strategy Document ACS INDOOR SWITCHGEAR 2015 2020 Fleet Strategy Transpower New Zealand Limited 2013. All rights reserved. Page 1 of 63 C O P Y R I G H T 2013 T R A N S P O
Disconnectors and Earthing Switches 36 kv up to 800 kv
Power Transmission and Distribution Disconnectors and Earthing Switches 36 kv up to 800 kv Ruhrtal & Siemens: A strong and successful team We manufacture high quality high-voltage disconnectors and earthing
Electrical Distribution Services for Mining and Metals Industries
Electrical Distribution Services for Mining and Metals Industries Solutions to help maximize plant reliability and ensure personnel safety Make the most of your energy SM Electrical Systems are Serious
Asset Monitoring Solutions Integrated monitoring packages for a smarter, more reliable power grid
Asset Monitoring Solutions Integrated monitoring packages for a smarter, more reliable power grid Single breaker power plants Newly installed fleets The primary goal of Asset Monitoring is to provide a
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
GUIDELINES FOR WATER-DAMAGED ELECTRICAL EQUIPMENT
GUIDELINES FOR HANDLING WATER-DAMAGED ELECTRICAL EQUIPMENT NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION 1300 NORTH 17 TH STREET, SUITE 1752 ROSSLYN, VIRGINIA 22209 703 841-3200 703 841-5900 FAX WWW.NEMA.ORG
Union County Public Schools. Facilities Department. Electrical. Safe Work Practices
1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County
Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical
Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Victor Lee Commercial Marketing Manager SEA Eaton Oil & Gas Solution Tech Day 2013 Eaton. All Rights Reserved. Eaton is a leading