Residual life aspects on GIS with the focus on SF 6

Size: px
Start display at page:

Download "Residual life aspects on GIS with the focus on SF 6"

Transcription

1 Residual life aspects on GIS with the focus on SF 6 Speaker: Karsten Pohlink 25. March 2015

2 The presentation refers to CIGRÉ WORKING GROUP B3.17 RESIDUAL LIFE CONCEPTS APPLIED TO HV GIS CIGRE Technical Brochure 499 (06/2012) Members: K Pohlink / Convenor (CH), C Jones (UK), P Coventry (UK), W Degen (DE), E Duggan (IE), P Glaubitz (DE), P Fletcher (UK), M Hyvärinen (FI) Z Lefter (HU), A Mjelve (NO), M Reuter (DE), B Skyberg (NO), K Uehara (JP), T Yokota (JP), Corresponding Member: D Kopejtkova (CZ) 2

3 Overview The TB 499 & Tutorial includes the following chapters Introduction & Scope Experience & Reliability of GIS Equipment Information & Assessment Maintenance Strategies Life Limiting Factors of GIS & Condition Assessment Impact of System Changes Support of Old GIS Options for Life Extension Evaluation Process and Health Indices Disposal & End of Life Procedures Conclusions & Discussions Case Studies All chapters include subjects related to SF 6 3

4 Introduction HV GIS (High Voltage Gas Insulated Switchgear) has been in service for approximately 45 years Experience has shown that GIS is generally a very reliable technology - particularly when used indoor Number of installations is continuously increasing Task: What is the service life expectation of the long time installed GIS? by: Identification and discussion of the factors which determine the expected residual life of HV GIS Guidance on evaluating the expected residual life Options for extending the residual lifetime End-of-life procedure for HV GIS including SF 6 gas Examples of residual life assessments and decisions 4

5 GIS Age Profile Age profile of the Worldwide GIS installed base (2010) 5

6 Experience of GIS Lifetime of early GIS is more than the anticipated years - today s expectation: >50 years No generic life limiting process have been reported so far Substation build in 1973, some circuit breakers replaced around year

7 Experience of GIS However some issues of ageing and deterioration have occurred in the following areas: Gas leakages (mainly for outdoor installations, flange corrosion) Specific material/design issues (graphite type bursting disks, seals) Corrosion Mechanical wear Electrical wear Issues can be solved in most cases by enhanced maintenance and refurbishment Use of a supplementary seal around the flange 7

8 Experience of GIS GIS

9 Experience of GIS GIS

10 Experience of GIS GIS

11 Experience of GIS GIS

12 Experience of GIS GIS

13 Experience of GIS GIS

14 Experience of GIS Layout of GIS bays Single/Double busbar single phase encapsulated from

15 Experience of GIS Layout of Three phase enclosed GIS bays from

16 GIS Reliability Survey Data from 3rd survey TB513 (2012) 16

17 GIS Reliability Survey The general trend is towards improving reliability of newer GIS. This could be explained by an age related deterioration of older GIS; however it is our view that it is a consequence of the inherent lower reliability of early GIS designs. This view is supported by the higher failure rates reported in the first and second surveys [first survey 1991; second survey in 1996] Following aspects should be taken into consideration: Information to evaluate GIS Maintenance Strategies Life Limiting Factors & Condition Assessment 17

18 Evaluation process for residual life options 18

19 Information to evaluate GIS Name plate information [equipment] Descriptions and reports of any data available regarding operational history: number of operations, abnormal operational conditions, details of failures, inspections, maintenance, extensions, modifications, overhauls and diagnostic tests of a specific GIS [user] Feedback on service experience of equipment type [original equipment manufacturer OEM] Information on availability of spare parts and technicians [OEM] 19

20 Equipment information & status Evolution of GIS technology 20

21 History of GIS Standards Year History 1965 No standards available for GIS and designs relied heavily on equipment standards 1975 IEC 517 GIS 1 st edition 1977 Amendment No. 1, partial discharge (PD) included 1982 Amendment No. 2, focus on enclosures 1983 Amendment No. 3, internal arc testing 1986 IEC 517 GIS 2 nd edition, integration of amendments 1990 IEC 517 GIS 3 rd edition, technical update and reference to other relevant IEC standards, e.g. IEC Common specifications for high-voltage switchgear and control gear 2003 IEC st edition, reduction of gas leakage from 1 to 0.5% per annum, additional site test requirements 2011 IEC nd edition, addition of service continuity considerations 21

22 Maintenance Strategies for GIS Corrective maintenance - Run to failure Corrective maintenance is defined as the maintenance carried out after fault recognition and intended to put an item into a state in which it can perform a required function It is not recommended to use this maintenance strategy for GIS because it can lead to severe outages which will be unacceptable in transmission systems 22

23 Maintenance Strategies for GIS Preventive maintenance: In contrast to corrective maintenance, preventive maintenance aims to avoid equipment failures by taking appropriate action. Defined as maintenance carried out at predetermined intervals [time based] or according to prescribed criteria [condition based &/or reliability centered] and intended to reduce the probability of failure or the degradation of the functioning of an item This is the recommended maintenance strategy for all installed GIS and generally applied 23

24 Support of long time installed GIS The long service life of GIS leads to the following challenges: Knowledge and expertise Spare parts (availability, holding policy, secondary equipment) Maintenance and repair Extension Need for consultancy services 24

25 Support of long time installed GIS Further Examples: 25

26 Support of long time installed GIS Life part of substation during maintenance of single bays 26

27 Support of long time installed GIS Refurbishment of GIS build in

28 Support of long time installed GIS 28

29 Evaluation process for residual life options 29

30 Life Limiting Factors & Condition Assessment Ageing and deterioration mechanisms on the following subjects are discussed in the technical brochure and the tutorial: Circuit breakers, Load break switches High-speed earthing switches Disconnectors and (maintenance) earthing switches Insulation including SF 6 Enclosures Auxiliary equipment and accessories Process applied: Life limiting factors (description, discussion, evolution) Diagnostic techniques (how to detect and assess) 30

31 Life Limiting Factors & Condition Assessment Mechanical lifetime for circuit breakers is defined by the permitted number of off-load switching operations. New IEC-standards define two classes for mechanical endurance: class M1 (2 000 operations) and class M2 ( operations), but earlier requirements were significantly lower (1 000 operations). Diagnostic techniques: Circuit-breakers I mechanical wear Measurement of charging time, contact timing, static contact resistance, travel records, trip coil current, vibration analysis The number of operations and actual endurance class can give an initial idea of possible mechanical wear. 31

32 Life Limiting Factors & Condition Assessment Circuit-breakers II mechanical wear Example: travel records, normal travel curves (broken lines) and schematic examples of abnormal contact travel recordings (solid lines) from an open operation a) Delay in release mechanism, e.g. due to poorly lubricated release latches b) Low contact speed, e.g. due to reduced energy in operating mechanism c) Poor damping, e.g. due to defective dash pot d) Too low insulation distance in open position, e.g. due to incorrect assembly 32

33 Life Limiting Factors & Condition Assessment Circuit-breakers III electrical wear Electrical wear in contact system: Contact erosion and nozzle ablation caused by interruption of fault currents Limit of electrical wear is seldom reached Contact wear can be detected by: Visual inspection (requires opening of the GIS) Slow motion resistance measurements as shown to the right Contact resistance as a function of contact travel 33

34 Life Limiting Factors & Condition Assessment Circuit-breakers IV grading capacitors Grading capacitors in multi-break circuit breakers have shown various mechanical and electrical problems, some of them can lead to failures such as: Dielectric breakdown (breaking small inductive currents) Partial discharge caused by bad connections (metal band) Leaks (oil out or SF 6 into grading capacitor) Diagnosis by: Visual inspection Partial discharge measurements 34

35 Life Limiting Factors & Condition Assessment Insulation I: SF 6 -gas quality Life limiting factors: no ageing of the gas itself Decomposition products present in the gas indicates defects like overheated contacts or partial discharges Decomposition of the gas starts at temperatures > C (>200C if Cu is present) Decomposition products can be detected by gas testing: on site or in laboratory by gas measuring devices 35

36 Life Limiting Factors & Condition Assessment Insulation II: SF 6 -gas quality Humidity in the gas has a limited influence on the insulation property of the gas itself, but may condense on surfaces of insulation parts and may lead to flashover Humidity contributes to the formation of corrosive decomposition products Humidity can be detected by dew-point measurements Adsorbers in the gas compartments can adsorb decomposition products and humidity SF 6 collecting device in service 36

37 Decomposition of SF6 and Subsequent Reactions (WG B3.25 TB 567) 37

38 Decomposition of SF6 and Subsequent Reactions Discharge channel Fragmented SF 6 molecules will react with materials in the contacts to produce metal fluorides and CF 4 Will react with contaminants such as H 2 O and O 2 to produce decomposition products containing oxygen such as SO 2 F 2 Surface reactions SF 4 with H 2 O to produce SOF 2 and HF HF with metal oxides to produce metal fluorides 38

39 Decomposition of SF6 and Subsequent Reactions Gaseous decomposition SOF 2 and SO 2 are the most abundant SOF 2 produced by the reaction of SF 4 and H 2 O SO 2 produced by the reaction of SOF 2 and H 2 O Solid decomposition products are AlF 3, CuF 2 and WF 6 39

40 Decomposition of SF6 General Conclusion: very complex process which is influenced by The type of discharge The energy involved The type of vessel The presence of contaminants The contact materials 40

41 Life Limiting Factors & Condition Assessment Insulation III: Particles Particles in the gas may reduce the insulating performance and cause flashovers Particles can be generated from moving parts like conductor sliding contacts and contacts in switching devices. Particles can be detected by: UHF and acoustic measurements 41

42 Life Limiting Factors & Condition Assessment Insulation IV: Particles Example UHF measurement Example acoustic measurement 42

43 Life Limiting Factors & Condition Assessment Insulation V: SF 6 gas leakage SF 6 gas leakage affects the gas density and also environmental aspects are to be considered Leakage rate in new IEC-standards: max 0,5 % per year from any single compartment Leakage origin and causes: seals, pipework, flange corrosion. Old GIS with controlled pressure system should be replaced by closed pressure systems 43

44 Life Limiting Factors & Condition Assessment Insulation VI: SF 6 gas leakage Leakage is detected by gas density monitors (mechanical pressure gauge or electronic sensors) Location of leakage can be found by negative ion capture detectors, electron capture detectors or other methods 44

45 Life Limiting Factors & Condition Assessment Insulation VII: Filters Filters are applied to adsorb moisture and decomposition products Filters are for the service period until opening for maintenance. Lifetime of filters in circuit-breaker compartments will depend on the value of cumulative breaking currents Gas quality measurements may give indications of the remaining filter lifetime 45

46 Life Limiting Factors & Condition Assessment Corrosion of metallic housings is the main concern especially flanges can be affected due to moisture ingress Outdoor substations in aggressive atmosphere are particularly exposed Corrosion leads to SF6 leakage Enclosures I: Metallic housing Example of flange corrosion 46

47 Life Limiting Factors & Condition Assessment Enclosures II: SF 6 gas seals Seals are subject to aging: main factors are material, temperature, UV, exposure to oxygen and combination. Aging may lead to SF6 leakages Typically EPDM is used for gas seals. If the seal is not disturbed, it is not a life limiting factor even when aged Dynamic seals are also exposed to mechanical wear and corrosion of metallic parts may occur Seals must be replaced after opening of the gas compartment Defects can be detected/monitored by leakage detection Compression set measurement can help to asses the performance of seals 47

48 Life Limiting Factors & Condition Assessment Enclosures III: Pressure relief device Two types of disk material are typically used in GIS: graphite and metallic. Graphite was widely used in early designs. Life limiting factors: corrosion and fatigue which can lead to SF6 gas leakage and/or reduction of the operating pressure. Detection is possible by visual inspection, leakage monitoring or by laboratory examinations It is recommended to replace graphite disks if the GIS compartment is refurbished. 48

49 Life Limiting Factors & Condition Assessment Auxiliary equipment and accessories Filling interface, gas monitoring, sensors, gas piping and valves are unlikely to limit the life of GIS. SF 6 gas pipework with leakage should be removed and filling/monitoring equipment directly installed to the gas compartment 49

50 Life Limiting Factors & Condition Assessment Secondary Equipment The life expectation of the secondary equipment is generally significantly lower then for the primary GIS Electronic components of digital secondary technique have a life expectation of years, while electromechanical devices may reach longer life times. A replacement of parts or the complete secondary equipment may be considered to reach the life time of the GIS installation. This can also be supported by the request for extended functionality, communication features and protection system upgrades. 50

51 Evaluation process for residual life options 51

52 Impact of System Changes to GIS System changes may occur due to the development of the network and can be: Additional functions required Extension/Modification of bays or devices Uprating of nominal current Increase of short circuit breaking requirements Increase of system voltage Upgrading of secondary system They often require a specific residual life assessment 52

53 Evaluation process for residual life options 53

54 Life extension Life extension is a change of the asset management policy for the GIS so as to achieve an increased residual life. Changes that may be considered are: Enhanced maintenance Refurbishment Retrofit 54

55 Evaluation of options for life extension Main factors to consider when deciding upon enhanced maintenance, refurbishment, retrofit or replacement: assessed residual life and associated risks required residual life for substation costs outage time requirements technical requirements and possibilities 55

56 Options for Life Extension Enhanced maintenance Is a change of the actual maintenance process by increased frequency and/or scope of the maintenance work? Can extend the life of the GIS by reducing risk? Is always part of a preventive maintenance strategy which could be supported by enhanced diagnostics or monitoring? Is seen as a relative cost effective life extension strategy but it may only delay refurbishment actions? 56

57 Options for Life Extension Enhanced maintenance possible applications Enhanced maintenance activities: more frequently lubrication, painting, cleaning. Enhanced diagnostics: frequently executed partial discharge measurements, SF6 gas quality check, timing measurements, infrared measurements, resistance measurements, leakage measurements. Introduction of additional online monitoring. 57

58 Options for Life Extension Enhanced maintenance - example Introduction of SF 6 -online monitoring system: Online monitoring was implemented (in addition to the traditional two-level pressure/density sensors) Even SF 6 leakage which develops very slowly can be detected with the onlinesystem Online monitoring of SF 6 -density was first installed during a refurbishment/retrofit project of the oldest GIS-stations. Nowadays the installation of such systems is often used for new SF 6 -installations GIS with online SF 6 monitoring 58

59 Options for Life Extension Refurbishment A major work to return the GIS back to (or close to) original condition with no additional functionality Typically represents an investment made only once in the lifetime (normally after mid life onwards) on a subassembly which has been identified as life limiting The subassembly is dismantled, inspected, cleaned and repaired by replacement of the wearing parts Done on site or in a workshop depending on the scope of work and the need of specific tools and test devices 59

60 Options for Life Extension Refurbishment possible applications Components that would normally be considered during a major refurbishment are: SF6 gas seals (static and dynamic) weatherproofing and corrosion protection mainly for outdoor GIS and GIS in harsh environments moving parts/parts subjected to electrical/mechanical wear 60

61 Options for Life Extension Refurbishment - example A variety of procedures have been developed to deal with SF6 gas leakages caused by flange corrosion. Two examples of applying a supplemental seal are depicted below. Major benefit: No dismantling required 61

62 Options for Life Extension Retrofit Specific components or major parts are replaced with new units of an enhanced functionality and/or increased specification The enhanced functionality may consider primary or control, protection and monitoring equipment Often an upgrading/uprating of the primary GIS is associated with a retrofit of the secondary system 62

63 Options for Life Extension Retrofit possible applications Increased specification: increase of rated short circuit current or rated current, improved tightness, reach updated IEC requirements, higher number of mechanical operations Change of circuit breaker, interrupter elements or drives to more up to date technology Enhanced monitoring, control and protection systems: remote control / unmanned substation, new protection functions, additional monitoring (may also require the installation of sensors) 63

64 Options for Life Extension Retrofit example kv GIS circuit breaker drive retrofit: An unacceptable number of failures in the original hydraulic drives occurred Refurbishment or retrofit? It was considered that the fault rate would increase again in future even if all known modifications to the original drive were implemented. It was decided to replace the complete drive with current technology solution. 400 kv GIS with circuit breaker drive retrofitted 64

65 Options for Life Extension Adding a disconnector in busbar to improve availability of a 300 kv substation: Retrofit example 2 A sectionalising disconnector was installed in one busbar in a double busbar system. The modification has significantly increased the availability of the substation, as it is possible to split the busbar. Additional installed bus sectionaliser 65

66 Evaluation process for residual life options 66

67 Options for Life Extension Replacement May consider the whole GIS installation or a major part of it. Replacement is in many cases connected to an increase of functionality and enhanced specification (e.g. number of bays, Single Line Diagram, short circuit current level). Two basic options to build the new installation: On the same footprint: a stepwise approach can be used as new GIS normally require less space. Alongside the existing GIS: circuits are transferred. 67

68 Options for Life Extension Replacement example 1 Replacement of one of the first GIS: The substation was commissioned in 1968 and removed from service in It was considered to have reached the end of its life due to a lack of spare parts and unacceptable level of gas leakage. GIS upper floor with circuit breakers (1968) 145kV GIS lower floor with busbar and cable connections (1968) New 170kV GIS installation (2003) 68

69 Options for Life Extension Replacement example 2 Replacement of 400/275kV GIS Substation: For an existing 400kV single busbar GIS additional 400kV cables & future system requirements demanded a full double busbar substation and extension of the 275kV substation It was concluded that it would not be feasible to adapt or extend the existing GIS A new 16 bay 400kV GIS was build alongside the original substation and the existing circuits were reconnected to the new switchgear. The existing 400/275kV transformers were connected to the new substation by gas insulated busducts. General view of original GIS New transformer compound 69

70 Disposal & End of Life Procedures Recycling and disposal If end of service life of the GIS is reached, defined dismantling and disposal must be done. Before dismantling the GIS it is required to remove the SF 6 for reuse or recycling. Depending on the category of the gas: It can be reused directly (values within the limits given by IEC 60480), or In some cases the gas has to be treated, or Sent back to the manufacturer of SF 6 Dismantled GIS could be a source for spare parts or a high content can be recycled (Al, Cu, Fe) 70

71 Disposal & End of Life Procedures Structure of used material taken from one bay with aluminum enclosure 71

72 Recommendations to Original Equipment Manufacturers (OEM) Assure availability of documentation for installed equipment Provide failure history / statistics for installed equipment types (major / minor failures) Inform the user of changes in maintenance recommendations or other activities if any Assure lifetime support of installed equipment (assessment, maintenance, modifications, repair, spare parts) Provide solutions for extendibility of installed GIS 72

73 Recommendations to Users Consideration in the original planning phase for possible extensions, replacements and refurbishments in future Keep the documentation available about the installed equipment (technical, schematics, reports & test sheets) Collect and file documentation of equipment history including maintenance actions, operations, modifications, diagnostic results, measurements, tests carried out, minor/major failures. Inform the OEM about minor and major failures Formalize the process of updating maintenance policies and practices based on latest industry experience. Participate in future CIGRE reliability surveys 73

74 Outlook Today the limits of lifetime for GIS are not known 74

75 Conclusion The experience of the lifetime of a GIS is >45 years, therefore today s life time expectation is above 50 years Corrosion, gas leakages, specific material/design issues and in some cases mechanical and electrical wear are the main issues for deterioration Frequently inspection and subsequently maintenance actions, assessment methods, diagnostic techniques and effective quality control processes enable the expected lifetime of a GIS Life extension can often be achieved by enhanced maintenance, refurbishment or retrofit End of life: requires a complete and sustainable recovery of SF 6 replacement with a new GIS is often selected Publication: CIGRÉ TB 499 SF 6 Analysis for GIS, AIS and MTS Condition Assessment - CIGRE WG B3.25 TB

High-Voltage GIS yesterday - today - tomorrow

High-Voltage GIS yesterday - today - tomorrow High-Voltage GIS yesterday - today - tomorrow Peter Glaubitz, Siemens AG, Principal Expert GIS-Technology siemens.at/future-of-energy Table of content GIS yesterday beginning and establishment of Gas-

More information

Preliminary Results from Present Cigre Survey

Preliminary Results from Present Cigre Survey Cigre WG A3-06 HV Equipment Reliability Preliminary Results from Present Cigre Survey Gas Insulated Substations (GIS) DB status : August 2007 Focus on population cards and major failure cards (namely 2004

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

SIEMENS Transmission and Distribution

SIEMENS Transmission and Distribution TITLE Long Term Maintenance and Care for S36A E. C. Wright 02/09/04 This document is to be used in conjunction with Installation, Operation and Maintenance Schedule IOMS 635. Its aim is to provide guidance

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics

More information

PD Monitor GIS. 24/7 Partial Discharge (PD) monitoring system for Gas Insulated Switchgear. Benefits NEW PRODUCT

PD Monitor GIS. 24/7 Partial Discharge (PD) monitoring system for Gas Insulated Switchgear. Benefits NEW PRODUCT NEW PRODUCT PD Monitor GIS 24/7 Partial Discharge (PD) monitoring system for Gas Insulated Switchgear For automatic, continuous monitoring of mission critical GIS assets Benefits The most cost effective

More information

Service Power Technologies. Retrofitting A future-oriented concept in lifecycle management

Service Power Technologies. Retrofitting A future-oriented concept in lifecycle management Retrofitting A future-oriented concept in lifecycle management Retrofit solutions for gas-insulated switchgear > 50 kv to 170 kv ABB-supplied high-voltage substations generally have a service life of approx.

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy. s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage

More information

Proactive Asset Management for GIS A six step process for reducing risk, cost, and improving reliability

Proactive Asset Management for GIS A six step process for reducing risk, cost, and improving reliability White paper Proactive Asset Management for GIS A six step process for reducing risk, cost, and improving reliability Gas Insulated Substations (GIS) are often critical assets for most organizations. GIS

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

Electrical Predictive and Preventative Maintenance

Electrical Predictive and Preventative Maintenance Electrical Predictive and Preventative Maintenance Electrical and mechanical equipment is subject to failure at the worst possible time for no apparent reason. - Mose Ramieh III There are two types

More information

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker

More information

Outages Happen 24/7 So Should Monitoring / SAFEGUARD YOUR HIGH VOLTAGE ASSETS WITH VAISALA ONLINE MONITORING

Outages Happen 24/7 So Should Monitoring / SAFEGUARD YOUR HIGH VOLTAGE ASSETS WITH VAISALA ONLINE MONITORING Outages Happen 24/7 So Should Monitoring / SAFEGUARD YOUR HIGH VOLTAGE ASSETS WITH VAISALA ONLINE MONITORING A Small Investment to Generate Measurable Benefits Sometimes, solving challenges is surprisingly

More information

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Enhance Power Equipment Reliability with Predictive Maintenance Technologies Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of

More information

Advantages of Fixed Circuit Breaker Switchgear

Advantages of Fixed Circuit Breaker Switchgear Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

ABB High Voltage Service. SF 6 Gas Management Solutions Managing SF6 Services in Switchgear

ABB High Voltage Service. SF 6 Gas Management Solutions Managing SF6 Services in Switchgear ABB High Voltage Service Gas Management Solutions Managing SF6 Services in Switchgear ABB offers a complete SF6 gas management solution, in an efficient and environmentally friendly manner, from installation

More information

electrical services WWW.AU.SGS.COM/INDUSTRIAL

electrical services WWW.AU.SGS.COM/INDUSTRIAL electrical services WWW.AU.SGS.COM/INDUSTRIAL OUR PROFILE SGS offers a full range of electrical engineering services covering the commissioning test of new plant as well as the maintenance and continual

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

High Voltage Electrical Equipment Failure Diagnosis. Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd

High Voltage Electrical Equipment Failure Diagnosis. Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd High Voltage Electrical Equipment Failure Diagnosis Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd High Voltage Electrical Equipment Failure Diagnosis Definition of High Voltage

More information

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04 Circuit Breaker LTB D with Motor Drive Motor Drive ABB PP/H/HV - Page 1 Ed 2006-04 Technology Traditional technology Traditional spring operating mechanism: Closing mechanism ABB PP/H/HV - Page 2 Tripping

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

Alstom Grid Services. Transformer lifecycle management GRID

Alstom Grid Services. Transformer lifecycle management GRID Alstom Grid Services Transformer lifecycle management GRID Transformer services A COMPLETE RANGE OF SOLUTIONS As a critical component of networks, the power transformer is essential to high voltage electrical

More information

GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry

GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry Brian Sparling, SMIEEE GridTech 2007, Delhi February 5-6, 2007 The

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

DC MOTOR ANALYSIS & TROUBLESHOOTING

DC MOTOR ANALYSIS & TROUBLESHOOTING DC MOTOR ANALYSIS & TROUBLESHOOTING By Don Shaw Condition assessment of DC motors requires a basic understanding of the design and operating characteristics of the various types available: the series motor,

More information

Alstom Grid Services. GIS lifecycle management GRID

Alstom Grid Services. GIS lifecycle management GRID Alstom Grid Services GIS lifecycle management GRID Gas-insulated substation services A COMPLETE RANGE OF SOLUTIONS Transmission networks are evolving into Smart Grids, integrating multiple energy sources,

More information

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850 Relion Power system protection and automation reference Extending substation life cycle with IEC 61850 Extending substation life cycle with IEC 61850 A step-by-step power system retrofit approach for optimizing

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

Extend the Life of Existing Switchgear

Extend the Life of Existing Switchgear Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...

More information

ACS INDOOR SWITCHGEAR

ACS INDOOR SWITCHGEAR ACS INDOOR SWITCHGEAR Fleet Strategy Document ACS INDOOR SWITCHGEAR 2015 2020 Fleet Strategy Transpower New Zealand Limited 2013. All rights reserved. Page 1 of 63 C O P Y R I G H T 2013 T R A N S P O

More information

Erik Backström, High Voltage breakers, After Sales & Service High voltage SF 6 live tank circuit breakers After Sales & Service Training course

Erik Backström, High Voltage breakers, After Sales & Service High voltage SF 6 live tank circuit breakers After Sales & Service Training course Erik Backström, High Voltage breakers, After Sales & Service High voltage SF 6 live tank circuit breakers After Sales & Service Training course description HPL 72,5-300 B1 with BLG1002A Level A & B Training

More information

Electrical Maintenance Workshop

Electrical Maintenance Workshop Electrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003 Transformer Maintenance & Testing Purpose This presentation provides an overview of the major considerations

More information

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Victor Lee Commercial Marketing Manager SEA Eaton Oil & Gas Solution Tech Day 2013 Eaton. All Rights Reserved. Eaton is a leading

More information

Extract of the White paper Reduce energy costs in compressed air systems by up to 60%

Extract of the White paper Reduce energy costs in compressed air systems by up to 60% Extract of the White paper Reduce energy costs in compressed air systems by up to 60% How can potential energy savings be identified? There are various measures for realising potential savings in compressed

More information

Comparison between Gas- and Air Insulated Network Concepts with the Life Cycle Cost Method

Comparison between Gas- and Air Insulated Network Concepts with the Life Cycle Cost Method Comparison between Gas- and Air Insulated Network Concepts with the Life Cycle Cost Method Ingo Jeromin, Gerd Balzer, Technische Universität Darmstadt, Jürgen Backes, Richard Huber, EnBW Regional AG Stuttgart

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring Siemens Integrated Substation Condition Monitoring System Circuit Breaker Monitoring System Description Introduction The Circuit Breaker Monitor [CBM] is only one example of the way that the Substation

More information

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens. Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

Condition Monitoring of equipment to improve quality of supply to customers by averting failures

Condition Monitoring of equipment to improve quality of supply to customers by averting failures Condition Monitoring of equipment to improve quality of supply to customers by averting failures Author & presenter: Patrick O Halloran BTECH Manager Technology Services at City Power Johannesburg Abstract

More information

(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS

(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS (PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS IS 12729:2004 IEC 60694(2002) 1.1 Scope This International Standard applies to a.c. switchgear and controlgear,

More information

Houston Service Center Medium Voltage Service and Aftermarket Solutions

Houston Service Center Medium Voltage Service and Aftermarket Solutions Houston Service Center Medium Voltage Service and Aftermarket Solutions Table of contents Introduction...3 Breaker refurbishment...4 Protective relay & control service and support...5 Power Service and

More information

ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact

ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact Authors Carl Ejnar Sölver, ABB High Voltage Products Rasmus Larsson, ABB High Voltage Products 2 ABB ABB

More information

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,

More information

Safe and secure distribution of medium voltage with AX1

Safe and secure distribution of medium voltage with AX1 Safe and secure distribution of medium voltage with AX1 The intelligent switchgear AX1 is a modern, air-insulated switchgear that lies at the very front line of safety and security safety for operating

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

On-line PD Monitoring Makes Good Business Sense

On-line PD Monitoring Makes Good Business Sense On-line PD Monitoring Makes Good Business Sense An essential tool for asset managers to ensure reliable operation, improve maintenance efficiency and to extend the life of their electrical assets. Executive

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

Modular Systems wind portfolio overview Power Collection and Grid Connection products

Modular Systems wind portfolio overview Power Collection and Grid Connection products Modular Systems wind portfolio overview Power Collection and Grid Connection products Slide 1 Modular Systems wind portfolio Wind power - definition A wind turbine is a device that converts kinetic energy

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection Bryan Johnson Product Group Manager, MV Switchgear ABB South Africa Contents Introduction... 3 What is an internal arc

More information

Dissolved Gas Analysis Guide for Transformers Filled with Beta Fluid

Dissolved Gas Analysis Guide for Transformers Filled with Beta Fluid DSI Ventures, Inc. PHONE: (903) 526-7577 FAX: (903) 526-0021 www.dsiventures.com Dissolved Gas Analysis Guide for Transformers Filled with Beta Fluid Introduction Analysis of dissolved gases in transformer

More information

CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services

CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services SpecialistS IN ELECTRICAL SUPPORT SERVICES TO MINING, UTILITIES & industry Ampcontrol is committed to supporting our customers to maintain efficient

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed

More information

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric

More information

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H. POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,

More information

Volkswagen Jetta, Golf, GTI 1999, 2000 2.8 Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

Volkswagen Jetta, Golf, GTI 1999, 2000 2.8 Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17) 17 Engine-Lubrication (Page GR-17) Lubrication system components, removing and installing Oil filter housing, disassembling and assembling Oil pan, removing and installing Oil pressure and oil pressure

More information

Securing your electrical installations Prisma,

Securing your electrical installations Prisma, Securing your electrical installations Prisma, an optimised solution for type tested low voltage switchboards up to 3200 A Table of contents Developing installation safety 4 Prisma P * Electrical switchboards

More information

DISTRIBUTION OPERATIONS AND MAINTENANCE

DISTRIBUTION OPERATIONS AND MAINTENANCE EB-00-00 Filed: 00 Aug Page of DISTRIBUTION OPERATIONS AND MAINTENANCE PREVENTIVE MAINTENANCE Preventive Maintenance is intended to maintain or improve customer service reliability, extend equipment life

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,

More information

Effective Condition Assessment of Medium Voltage Switchgear

Effective Condition Assessment of Medium Voltage Switchgear Effective Condition Assessment of Medium Voltage Switchgear Abstract There is a general trend within electricity distribution companies and operators of large private electricity networks to extend maintenance

More information

WHAT IS INFRARED (IR) THERMOGRAPHY

WHAT IS INFRARED (IR) THERMOGRAPHY WHAT IS INFRARED (IR) THERMOGRAPHY IR Thermography is the technique of producing pictures called from the invisible thermal radiation that objects emit. This is a non-contact means of identifying electrical

More information

Electrical switchgear and safety: A concise guide for users

Electrical switchgear and safety: A concise guide for users Electrical switchgear and safety: A concise guide for users Introduction This leaflet is aimed at owners and operators of electrical switchgear in industrial and commercial organisations who have little

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

Energy Transmission and Distribution Services

Energy Transmission and Distribution Services Energy Transmission and Distribution Services Business segment presentation Asset Services Energy is an essential part of our daily lives Industry Education Mobility Workplace Entertainment Homes Healthcare

More information

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003 MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU

More information

Respecting the environment

Respecting the environment MAIN FEATURE CHAPTER I RESEARCH WITH AN EYE ON THE FUTURE Respecting the environment Low power losses and a lesser visual impact on the landscape make Gas-Insulated Lines (GIL) a very environmentally friendly

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks

More information

DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD

DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD JOB DESCRIPTION POSITION TITLE: Air Conditioning Mechanic DEPARTMENT: Plant TITLE OF IMMEDIATE SUPERVISOR: Supervisor, Maintenance Services Position Summary

More information

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number

More information

Troubleshooting with ABS Service Data Kit

Troubleshooting with ABS Service Data Kit Troubleshooting with ABS Service Data Kit Information of how pump run data is stored in AquaTronic and can be used in service checks and trouble shooting. AquaTronic communication cable with standard USB

More information

Installation and safety instructions for AC/DC built-in devices

Installation and safety instructions for AC/DC built-in devices The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further

More information

Disconnectors and Earthing Switches 36 kv up to 800 kv

Disconnectors and Earthing Switches 36 kv up to 800 kv Power Transmission and Distribution Disconnectors and Earthing Switches 36 kv up to 800 kv Ruhrtal & Siemens: A strong and successful team We manufacture high quality high-voltage disconnectors and earthing

More information

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity

More information

Distribution Voltage Regulators

Distribution Voltage Regulators Distribution Voltage Regulators Type JFR Single Phase 2.5 to 19.9 kv Type SFR Three Phase 13.2 to 34.5 kv Power Transmission & Distribution Siemens JFR & SFR Voltage Regulators Improving Quality of Service

More information

Asset Monitoring Solutions Integrated monitoring packages for a smarter, more reliable power grid

Asset Monitoring Solutions Integrated monitoring packages for a smarter, more reliable power grid Asset Monitoring Solutions Integrated monitoring packages for a smarter, more reliable power grid Single breaker power plants Newly installed fleets The primary goal of Asset Monitoring is to provide a

More information

Medium Voltage Distribution FLUVAC. Vacuum Circuit Breaker Up to 24 kv 630 A 21 ka. Operation Maintenance Instructions. www.schneider-electric.

Medium Voltage Distribution FLUVAC. Vacuum Circuit Breaker Up to 24 kv 630 A 21 ka. Operation Maintenance Instructions. www.schneider-electric. Medium Voltage Distribution FLUVAC Vacuum Circuit Breaker Up to 24 kv 630 A 21 ka Operation Maintenance Instructions www.schneider-electric.com Contents Introduction... 3 Our Service Unit: our specialists,

More information

Kompressoren. Adsorption Dryer AD

Kompressoren. Adsorption Dryer AD Kompressoren Adsorption Dryer AD Adsorption Drying: why? Modern industries require compressed air that is increasingly filtered with low dew point and condensate. Today, the equipment is more sophisticated

More information

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET:

More information

October Safety Subject

October Safety Subject October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that

More information

Assessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO

Assessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO April 2, 2014 Assessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO Todd Goyette, P.E., POWER Engineers Mousa Hejazi, P.E., Pepco Holdings Inc. 1 Pepco Quick Facts First incorporated in

More information

CLASSIFICATION NOTES

CLASSIFICATION NOTES CLASSIFICATION NOTES Type Approval, Installation and Testing of Water Level Detectors on Bulk Carriers and Single Hold Cargo Ships other than Bulk Carriers General Information This edition of the classification

More information

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for

More information

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................

More information

MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS

MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS Gary P. Guagliardi Director Sales & Marketing HindlePower, Inc. Easton, PA Introduction This paper explores the use of mobile DC power systems for three

More information

Neve V-Series Console Restoration Technical Brief

Neve V-Series Console Restoration Technical Brief Neve V-Series Console Restoration Technical Brief by Gregory G. Davis October 2004 2004 Audio Engineering Services LLC All Rights Reserved Unauthorized duplication or re-transmission by any means without

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

Instructions for Safe Use

Instructions for Safe Use Instructions for Safe Use (Certification N:o VTT 08 ATEX 029) Thank you for choosing Slam Trans portable transformer for your job site. Purpose of this manual is to provide you all the necessary safety

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Monitoring and diagnostics

Monitoring and diagnostics Monitoring and Diagnostics Monitoring and diagnostics Analyze the past, monitor the present, and predict the future! Asset Services/Monitoring and Diagnostics Switchgear Services Transformer Services Cable

More information