1 1 TRANSFORMER ON-LINE DEHYDRATION, DEGASSING AND ULTRAFILTRATION FOR VERY HEAVY WORKING CONDITIONS VACUUM SEPARATOR VS-06 A version 2008 CLIMABOX ON POWER RECOVERY OF OIL DIELECTRIC STRENGTH REMOTE PROCESS MONITORING AND CONTROL MINIMUM SUPERVISION OR MAINTENANCE Copyright: Fa. Ing. Altmann, 2008
2 Drying of transformers ORIGINAL BROCHURE The presence of moisture in the transformer, to whatever degree, does actual harm to insulation which is, in fact permanent damage. Drying methods only substantially reduce that deterioration. Vacuum Separator VS-06 is intended for mobile and preferably preventative use on transformers with more than 2-2.5% water content in the cellulose, with particle contamination and excess gas. The quick restoration of safe dielectric conditions also forms part of the concept. The system can be installed regardless of the size of the transformer. Main features of VS-06 Moisture, gas and particles content can be reduced to the level of a new transformer Quick restoration of dielectric strength of oil No impact on the insulating oil properties, no over-drying of the transformer No disconnection of the transformer under treatment, normally not even during the installation of a separator Installation and service with minimum manpower and energy Direct check of dehydration efficiency by volumetric measurement of the separated water Remote monitoring & control of the drying process Application of advanced and patented technologies like hydraulic piston for vacuum building and bubble bed for moisture separation HOW MUCH MOISTURE IS TOO MUCH MOISTURE? Moisture enters the transformer either through external contamination, or is generated internally by the oxidation (ageing) of insulants. In either case, practically all the water present in the transformer (over 98%) is contained in solid insulants because the cellulose has very strong affinity with the water. Figure 1 shows the equilibrium relationship between the water content in the oil Cw (ppm) and cellulose Cp (weight %) at different operational temperatures. 2 Fig.1 Moisture equilibrium chart (Nielsen diagram TRACONAL 2005 ) Example: 10MVA Transformer, 700 kg cellulose, 6000 kg oil Sampling temperature 50C, Cw = 30 ppm of water in the oil Cp = 2.9% weight percent of water in the cellulose. Total amount of water in the cellulose: 700 x = 20.3 kg Total amount of water in the oil : 6000 x = 0.18 kg If one wishes to reduce the moisture to acceptable 2% boundary then: 700 x ( ) = 6.3 kg water must be removed from the transformer. The effect of moisture on the transformer is summarized in Table 1.
3 Cp Transformer condition (weight % in paper) 0.5 new or highly dried 2.0 acceptable condition 3.3 paper starts to deteriorate 4.5 flashover possible at 90C 7.0 flashover possible at 50C 8.0 who knows? In order to avoid the deterioration of solid insulants, the moisture content should be kept under 2%. If the moisture level is suspected to exceed 2%, the transformer should be dehydrated as a matter of preventive maintenance. For basic information about moisture impact at dielectric of the transformer See / TRACONAL or / News. 3 WHAT IS A LIQUID PISTON? The Liquid Piston is created by rising and falling oil level which is caused by the cyclic operation of the robust gear pump. The first stage (evacuation) is schematically shown on the left. The oil is drawn from the apparatus by the gear pump. The sinking oil level acts as a piston and creates the basic vacuum necessary to separate gases and vapours from the oil The second stage (compression) is schematically shown on the right. The run of the gear pump is reversed and the liberated gas-vapour mixture is gradually compressed by the rising oil level (upward motion of the liquid piston). When the pressure rises, at first the condensation of oil vapours takes place Only this way can be guaranteed no-impact on oil properties under on-line long-term dehydration of a transformer condensed light fractions are automatically mixed back in the oil. Subsequently, the gases are relieved via the non-return valve into atmosphere. This process continues until the whole apparatus is filled with oil, then the gear pump is switched on into direct run again and a new evacuation stage begins. HOW ARE VAPOURS AND GASES SEPARATED FROM OIL? Vacuum, appropriate temperature and large interfacial area are essential for efficient separation. Contaminated oil from the transformer is locally adjusted to an optimum temperature and the hot oil and the gas (previously separated from oil) get mixed in a vacuum via ejector in order to produce bubbles with a large interfacial area (bubble bed). The intense diffusion of the moisture from the oil is enhanced by minimizing the partial pressure of the water vapour. This is achieved by undercooling the carrier gas to condense and freeze-out all traces of moisture prior to mixing with the contaminated oil. Dissolved gases and vapours diffuse into bubbles which are then agglomerated, collected and broken.the water vapour is collected in the form of ice in the freezing trap, and periodically defrosted and collected as a liquid in the water trap. Note that only a simplified scheme is shown here for clarity.
4 4 INSTALLATION The separator can be connected to all types of transformers (i.e. open as well as sealed units). It should be located in close proximity of the transformer. All treatment utilities (vacuum and hydraulic circuits, preheater, ultrafilter control circuits etc.) are installed in the moisture tight and internal air-conditioned CLIMABOX. For detailed information See VS-06A CLIMABOX Operational Manual 2006 CLIMABOX DIMENSIONS
5 5 SPECIFICATION Power supply voltage 400 V (or on request) Power supply frequency 50 Hz (or on request) Power consumption: without oil heater 850 W with oil heater PO W maximum air condition unit 300 W Oil throughput 10 m 3 per day maximum Outlet water content 10 ppm nominal, 4 ppm minimum Outlet gas content 1% nominal, 0.3 % minimum Outlet filtering grade 1 µm Weight CLIMABOX version (separator, heater ultrafilter, external water trap etc.) Dry weight ( without oil) 520 kg ( + autotransformer + aircondition, if requested) Operating weight (oil filled) 580 kg Hydraulical connection 2 x flexible 1/2 hose Communication: faxmodem, GSM modem, LAN link, ARSCOM Internet utility Moisture reading : Vaisala humidity sensor on request PARAMETRIC REMOTE CONTROL Regardless of how efficient any method of oil dehydration might be - the first law of the dehydration of transformers always is : water removal from cellulose materials of the transformer has to be safe and effective Any on-line transformer dehydration is ultimately governed by slow diffusion of the moisture from cellulose in the oil and this process can be accelerated only by a significant increase in temperature. But the second basic law of any on-line dehydration limits the effort because : high transformer temperature high water content in oil high separation rate means low dielectric strength of oil low immediate reliability of transformer In order to avoid the lowering of the immediate SEPARATOR VS-06 A reliability of the transformer, it is necessary to tune at least two antagonistic criteria in the whole process of PCD1 dehydration PC - IBM Compatible on - line Process Control telephone or GSM modem telephone, GSM modem or LAN link PGU connector Laptop computer Printer Database terminal APT Parameters & measured data max. separating efficiency of dehydrator (max. water removal rate) dielectric strength of oil - has to be maintained or improved To achieve this target the VS-06 can be programmed directly (manually) via terminal of PCD 1 or better with the use of suitable PC or lap-top on the basis of actual and previously measured values. This way is possible not only to remotely monitor and optimize the dehydrator function but to optimize the whole dehydration process as well, by strictly controlled warming-up of the transformer. The figure on the left shows the structure of separator control systems and both connections between PCD1 and lap-top or remote PC. Communication between the PCD1 and both computers - remote user PC and lap-top is provided by the firmware of the ARS.
6 6 Contacts Producer: ARS - ALTMANN RECOVERY SYSTEMS Machova Domazlice Czech Republic tel.: , fax.: handy: [email protected] OUR PARTNERS Fa. Andreas Henghuber ARS - Altmann Systems Oberhausbach 2 D Hebertsfelden Germany Tel. +49(0) Fax.. +49(0) mob: +49(0) [email protected] Wuhan HengCheng Eletricpower Tech. Co.Ltd. 802 Room 5 Building Wuhan, Hubei P.R.of China Responsible person: Yan Jie Tel.: Fax.: Handy: Web site: [email protected] MTC Power Technology Ltd. Kallipoleos and Ifigenias I, Office 501, Amaral 30 Nicosia 1055, CYPRUS, EU [email protected] Fax: +357 (22) METRACO Ltd. (Europe) Altmann Systems Longbridge House, 3 Downing Street Farnham, Surrey GU9 7 PA England Tel/Fax / 57 Mob: [email protected] VH Ingeniería Ing. Luiggi 719- Bahia Blanca Bahia Blanca Buenos Aires CPA (B8000JUO) Argentina Contact person: Victor Vercellino tel.: handy: [email protected] Boston Home Inc. Industrial Supply 168 Apo St., Sta. Mesa Heights Quezon City, Philippines Tel Fax Responsible person: Bernard Tiongson
7 7 Typical applications of the VS-06 Climabox Indonesia: Installation of VS-06 Climabox at block transformer Improvement of Tx dielectric Germany: 250 MVA Transformer
8 VS06 Climabox (and Online DGA) controlled life-extention of aged transformer ORIGINAL BROCHURE 8
ThermoSorb Desiccant Dryers
ThermoSorb Desiccant Dryers Sierra Why dry compressed air? Contamination reduces efficiency The air we breathe contains contamination in the form of water vapour and airborne particles. During the compression
PVS 185, 600, 1200, 1800, 2700 Series Portable Purification Systems
185, 600, 1200, 1800, 2700 Series Portable Purification Systems FEATURING Global Filtration Technology PRINCIPLES OF OPERATION Contaminated oil is drawn into the Parker Portable Purification System by
Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -
Doc. : 08C00031_e Date : 10.02.2009 Page : 1 / 9 ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric - (Preliminary) Doc. : 08C00031_e
MOLECULAR DRAG PUMPS MDP SERIES
MOLECULAR DRAG PUMPS MDP SERIES MOLECULAR DRAG PUMPS MDP SERIES If you need: to replace a rotary vane pump with a dry pump for an application at 10-3 a turbopump that can operate up to 10 a pump that can
DGA - Method in the Past and for the Future
DGA - Method in the Past and for the Future Page 2 May 2012 1970 1973 Doerenburg introduced the differentiation between electrical and thermal failure mode and introduced ratios for fault gases with similar
Electrical Maintenance Workshop
Electrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003 Transformer Maintenance & Testing Purpose This presentation provides an overview of the major considerations
CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
clean and quiet dental
clean and quiet dental clean air for your dental clinic JUN-AIR introduced the first compressor almost 50 years ago and started the development of the technology and design, which has made JUN-AIR compressors
ThermoStar Refrigeration Air Dryers
ThermoStar Refrigeration Air Dryers Why dry compressed air? Contamination Reduces Efficiency The air we breathe contains contamination in the form of water vapour and airborne particles. These problems
ETC -SV. Class 0 oil-free compressed air through catalysis
Innovation QUALITy Reliability Worldwide ETC -SV Class 0 oil-free compressed air through catalysis The way to oil-free compressed air The ETC operating principle Through the process of catalytic oxidation,
TECHNICAL SPECIFICATION. StirLIN-1 Economy Liquid Nitrogen System
TECHNICAL SPECIFICATION StirLIN-1 Economy Liquid Nitrogen System Reference 80 8120_01 Issue Date August 1, 2015 1. INTRODUCTION Since more than sixty years Stirling Cryogenics has designed and manufactured
SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES
SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES Filippo Turra Product Manager Cooling Technology INTRODUCTION
06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
Soil Suction. Total Suction
Soil Suction Total Suction Total soil suction is defined in terms of the free energy or the relative vapor pressure (relative humidity) of the soil moisture. Ψ = v RT ln v w 0ω v u v 0 ( u ) u = partial
Automatic Back-Flushing Filter AutoFilt RF9.
Automatic Back-Flushing Filter AutoFilt RF9. AutoFilt RF9 Clearing the Way. The Challenge: In response to the Tier III standard which will come into effect in 2016, the International Maritime Organization
How To Get A Passive House
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product
PVS Series - Models 185, 600, 1200, 1800 and 2700
PVS Series - Models 185, 600, 1200, 1800 and 2700 Reduce the catastrophic results of water contamination Eliminate water from the hydraulic system The PVS Series Portable Purification Systems, available
Research on the Air Conditioning Water Heater System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric
LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS
LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS 1. Define an accumulator and explain its function A hydraulic accumulator is a device that stores the potential energy of an incompressible fluid
KNC Model 3666 Automatic Pressure Calibration System
KNC Model 3666 Automatic Pressure Calibration System Product Description The Model 3666 Automatic Pressure Calibration (APC) System by King Nutronics Corporation is a portable secondary standards laboratory
High Vacuum Transformer Oil Purification Systems (HVTOPS) & Dielectric Oil Purification Systems (DOPS)
High Vacuum Transformer Oil Purification Systems (HVTOPS) & Dielectric Oil Purification Systems (DOPS) To achieve optimal dielectric strength and insulating performance inside of transformers and circuit
Chapter Test A. States of Matter MULTIPLE CHOICE. a fixed amount of STAs2 a. a solid. b. a liquid. c. a gas. d. any type of matter.
Assessment Chapter Test A States of Matter MULTIPLE CHOICE Write the letter of the correct answer in the space provided. 1. Boyle s law explains the relationship between volume and pressure for a fixed
EASIDEW PORTABLE HYGROMETER INSTALLATION, OPERATION AND MAINTENANCE MANUAL
EASIDEW PORTABLE HYGROMETER INSTALLATION, OPERATION AND MAINTENANCE MANUAL Issue February 2004 2 TABLE OF CONTENTS SECTION PAGE 1. INTRODUCTION 3 1.1 General 3 1.2 Ceramic Sensing Element 3 1.3 Calibration
Kompressoren. Adsorption Dryer AD
Kompressoren Adsorption Dryer AD Adsorption Drying: why? Modern industries require compressed air that is increasingly filtered with low dew point and condensate. Today, the equipment is more sophisticated
Solenoid valves Type EVU
Data sheet Solenoid valves EVU EVU solenoid valves are designed to fit into compact refrigeration systems. Available in direct and pilot operated versions, they can be applied in liquid, suction, and hot
Stack Sampling Stack sampling or source sampling
Stack Monitoring Stack Sampling Stack sampling or source sampling may be defined as a method of collecting representative samples of pollutant laden air/gases at the place of origin of pollutants to determine
Model 2128 AIR COMPRESSOR PUMP Operating Instructions
Model 8 AIR COMPRESSOR PUMP Operating Instructions Assembly of pump Connection to cylinder and charging ) Connect the air hose to the air cylinder and tighten with spanner. Do not over tighten. Note; the
Compressed Gas Cylinder Program
Department of Environmental Health & Safety Procedures Compressed Gas Cylinder Program March 2010 Compressed Gas Cylinder Program Page 1 of 8 Table of Contents I. Introduction II. III. IV. Policy Scope
MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump
MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................
FXA 2008. Candidates should be able to : Define and apply the concept of specific heat capacity. Select and apply the equation : E = mcδθ
UNIT G484 Module 3 4.3.3 Thermal Properties of Materials 1 Candidates should be able to : Define and apply the concept of specific heat capacity. Select and apply the equation : E = mcδθ The MASS (m) of
HYDRYER TYPE P Heat Regenerative Dryers ISO 9001 CERTIFIED
HYDRYER TYPE P Heat Regenerative Dryers ISO 9001 CERTIFIED General Air Type P Hydryer Heat Regenerative Systems Introduction General Air Type P Hydryers are electric heat regenerative dryers, designed
Everest. Leaders in Vacuum Booster Technology
This article has been compiled to understand the process of Solvent Recovery process generally carried out at low temperatures and vacuum. In many chemical processes solute is to be concentrated to high
CALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB
Compact automatic flow rate regulator with polymer cartridge 127 series REGISTERED BS EN ISO 9001:2000 Cert. n FM 21654 UNI EN ISO 9001:2000 Cert. n 0003 CALEFFI 01166/09 GB Function The AUTOFLOW devices
LMS The modular management system for condensing boilers. Control Products & Systems OEM. Answers for infrastructure.
LMS The modular management system for condensing boilers Control Products & Systems OEM Answers for infrastructure. LMS advanced electronics and proven software At times of dwindling resources, rising
Conlift1, Conlift2, Conlift2 ph+
GRUNDFOS DATA BOOKLET Conlift1, Conlift2, Conlift2 ph+ Small lifting stations 50 Hz CONLIFT1, CONLIFT2, CONLIFT2 ph+ Table of contents 1. Product overview 3 Conlift for condensate applications 3 Applications
NITROUS TRANSFER PUMP INSTRUCTIONS
NITROUS TRANSFER PUMP INSTRUCTIONS SAFETY TIPS Never directly inhale nitrous oxide. When inhaled in large quantities, nitrous oxide can cause respiratory ailments or in extreme cases, death by suffocation.
Vacuum. How It Relates to Refrigeration And Air Conditioning Service
Vacuum How It Relates to Refrigeration And Air Conditioning Service Moisture In A Refrigeration System Visible Moisture Water Droplets Uncommon, but it can occur Invisible Moisture Water Vapor Found in
QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems
The Professional Choice in Fluid Management QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems The Olaer Group is a global player specialising in innovative, efficient system
Series description: Wilo-Drain TC 40
Series description: Wilo-Drain TC 40 H[m] Wilo-Drain TC 40 10 8 6 4 2 TC 40/8 TC 40/10 0 0 2 4 6 8 10 12 14 Q[m³/h] Design Submersible sewage pump Application Pumping heavily contaminated fluids for House/site
CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)
TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output
AdSORPTION CHILLER NAK
AdSORPTION CHILLER NAK Chilling Capacity from 50 to 430 kw Usage of Surplus Heat from 50 C Ã*%8ÃPE+Ã TECHNICAL DESCRIPTION ADSORPTION CHILLER NAK 1 INTRODUCTION... 2 2 THE PRINCIPLE OF ADSORPTION... 2
In addition to the basic models, it is also possible for the units to be outfitted with add-ons.
1-1202-EN Gear ump Units For single-line centralized lubrication systems MFE5-KW3-2 MFE5-KW6 MFE5-BW7 These units comprising the MFE Group are designed to supply the lubricant used in intermittently operated,
Product overview Air conditioning service units
Product overview Air conditioning service units 02 03 AIR CONDITIONING SERVICE UNITS FROM ROBINAIR ARE THE WORLD S MOST ADVANCED AND MOST POPULAR AIR CONDITIONING SERVICE UNITS FOR CARS; TRUCKS AND BUSSES.
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents
6 Crankcase Ventilation
6 Crankcase Ventilation Introduction... 6-3 Crankcase Ventilation Manager (CVM)... 6-5 Introduction... 6-6 CVM280B..................................... 6-7 CVM280T... 6-10 CVM424B....................................
HIGH PRESSURE TECHNOLOGY HYDRAULICS PNEUMATICS TESTING EQUIPMENT
HIGH PRESSURE TECHNOLOGY HYDRAULICS PNEUMATICS TESTING EQUIPMENT MAXIMATOR GmbH 2 MAXIMATOR has an extensive know-how concerning concept, development, construction and manufacturing of test benches and
How To Clean Water From An Ammonia Refrigeration System
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can
Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk
1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance
ON-VEHICLE INSPECTION
Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem
The Worcester Greenstar System Filter. An innovative solution for reducing system contaminants
The Worcester Greenstar System Filter An innovative solution for reducing system contaminants Protect your customer s heating system with the Greenstar System Filter Modern condensing boilers are precision
ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements
ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET:
3/2-way Solenoid Valve, direct-acting, NC or NO
3/2-way Solenoid Valve, direct-acting, NC or NO Electrical connection cable plug, Form A With or without manual override as standard Threaded port and sub-base s Impulse optional Type 6014 can be combined
BD150 INDUSTRIAL DEHUMIDIFIER USER MANUAL
BD150 INDUSTRIAL DEHUMIDIFIER USER MANUAL Drawing : - TPC337 Issue : - 2 Date : - 24/01/12 UNPACKING Thank you for deciding to purchase an EIPL Industrial dehumidifier. Like the many tens of thousands
Refrigeration Air Dryers ADQ. Capacity: 21-4200 m 3 /h
Refrigeration Air Dryers Capacity: 21-4200 m 3 /h Water Contamination in Compressed Air T he w a t er c o n t a i n e d i n a c o m p r e s s e d a i r s y s t e m w i l l va r y acc o r d i n g t o a
AVL FUEL MASS FLOW METER & FUEL TEMPERATURE CONTROL
FUEL CONSUMPTION MEASUREMENT AVL FUEL MASS FLOW METER & FUEL TEMPERATURE CONTROL Description The combination of AVL Fuel Mass Flow Meter and AVL Fuel Temperature Control is a high precise and continuous
The Second Law of Thermodynamics
The Second aw of Thermodynamics The second law of thermodynamics asserts that processes occur in a certain direction and that the energy has quality as well as quantity. The first law places no restriction
EUROPEAN COMMISSION ENTERPRISE AND INDUSTRY DIRECTORATE-GENERAL. EudraLex The Rules Governing Medicinal Products in the European Union.
EUROPEAN COMMISSION ENTERPRISE AND INDUSTRY DIRECTORATE-GENERAL Consumer goods Pharmaceuticals Brussels, 03 February 2010 ENTR/F/2/AM/an D(2010) 3374 EudraLex The Rules Governing Medicinal Products in
Particle Measurement Technology in Practice. From Theory to Application.
Particle Measurement Technology in Practice. From Theory to Application. Page 3 1 Introduction to Particle Counting Page 19 2.4.2 General Installation Recommendations Page 3 Page 3 1.1 Physics Fundamentals
Oil-Free Screw Compressors. Water-injected Technology. Rely on GD to provide the perfect fit
Oil-Free Screw Compressors Water-injected Technology Rely on GD to provide the perfect fit Why oil-free? Don t compromise on quality If 100% clean and oil-free compressed air is a requirement for your
Technical data. Danfoss DHP-A
Technical data Danfoss DHP-A An air heat pump which produces both heat and hot water Can operate efficiently down to -0 C Danfoss TWS tank gives plenty of hot water quickly and with low operating costs
GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry
GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry Brian Sparling, SMIEEE GridTech 2007, Delhi February 5-6, 2007 The
Hydraulic control unit series 0086-372-01
Technical Product Information No. 1290 EN Hydraulic control unit series 0086-372-01 Contents Page About this Technical Product Information (TPI) 2 The ORTLINGHAUS numbering system 2 About the product 3
REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)
SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY
HR Heated HB Blower. Smart Solutions for Drying Compressed Air. Dual Tower Heat Reactivated Desiccant Air Dryer
Smart Solutions for Drying Compressed Air Dual Tower Heat Reactivated Desiccant Air Dryer HR Heated HB Blower 800.943.794 www.engineeredairproducts.com Engineered Air Products Moisture in compressed air
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 38 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia CAUSTIC AND CHEMICAL TABLE OF CONTENT
VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES
VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES PRODUCT DATA Design VC Series zone valves consist of: 2-way or 3-way valve housing available with various connection ends Spindle and cartridge
PPB Dissolved Oxygen Measurement - Calibration and Sampling Techniques
PPB Dissolved Oxygen Measurement - Calibration and Sampling Techniques Introduction The amount of dissolved oxygen in process water is continually gaining importance in many industries as a critical parameter
HOT WATER SYSTEMS. www.thermann.com.au
HOT WTER SYSTEMS www.thermann.com.au GS HOT WTER SYSTEM The Thermann 4 star Gas hot water heater can suit almost any family type. With an adjustable thermostat for safety and efficiency it allows you to
USER MANUAL HRV CONSTRUCTO 2.0ES* HRV CONSTRUCTO 1.5ES* * THESE PRODUCTS EARNED THE ENERGY STAR BY MEETING STRICT ENERGY EFFICIENCY
USER MANUAL RESIDENTIAL USE ONLY VB0175 HRV CONSTRUCTO 2.0ES* HRV CONSTRUCTO 1.5ES* * THESE PRODUCTS EARNED THE ENERGY STAR BY MEETING STRICT ENERGY EFFICIENCY GUIDELINES SET BY NATURAL RESOURCES CANADA
Charge Controller CC611/CC612 Preliminary datasheet
Preliminary datasheet Preliminary datasheet CC61x_D00xxx_00_D_XXE_preliminary/04.2015 Product description The ender charge controller CC611 is the main component of a charging point and is designed for
ultrafilter VARIOBLO Heat Regenerated Adsorption Dryer
Why drying compressed air? Compressed air is used in almost all areas of industrial manufacturing as a source of energy or processing. Compressed air needs to be dry, oilfree and clean in order to prevent
Condensate Treatment Solutions. CTS Series Eliminator II Oil-Water Separators
Condensate Treatment Solutions CTS Series Eliminator II Oil-Water Separators 2 Condensate Treatment Solutions A Cleaner Environment & Reduced Disposal Costs Compressed air is compressed and discharged
Externally Heated Desiccant Compressed Air Dryers PNEUMATIC PRODUCTS. PHD Series. pneumaticproducts-spx.com
PNEUMATIC PRODUCTS pneumaticproducts-spx.com Externally Heated Desiccant Compressed Air Dryers PHD Series PHD Series Dryers Reduce Purge Air Energy Costs PHD Series Dryers Reduce Purge Air Energy Costs
Online Infrared Flue Gas Analyzer Gasboard 3000
Online Infrared Flue Gas Analyzer Gasboard 3000 O 2 CO CO2 SO 2 NO NO x Use of measurement methods Proprietary Infrared NDIR Detectors - Micro-flow in ppm range: CO, NO, SO2, CO2 - Dual beam in % volume
Single Phase Soft Starter
Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................
DM70 Hand-Held Dewpoint Meter for Spot-Checking Applications
DM70 Hand-Held Dewpoint Meter for Spot-Checking Applications P.O. Box 26, FIN-00421 Helsinki, FINLAND Tel: +358 9 894 91 Fax: +358 9 8949 2485 Email: [email protected] www.vaisala.com The Vaisala
Adsorption air dryers ADS 1 215
Adsorption air dryers ADS 25 INDUSTRY CUSTOMER SERVICE COMPRESSED AIR AIR INTAKE 20 C 70% UR 760 mm Hg 2 grh 2 O/m 3 AIR PRESSURE 0 bar COOLING SYSTEM 30 C 00% UR 0 bar 2,8 grh 2 O/m 3 A compressor that
saving energy in comfort Factsheet Recair Enthalpy
saving energy in comfort Factsheet Recair Enthalpy Introduction Enthalpy Exchanger The enthalpy exchanger is able to transfer both sensible heat and latent heat (moisture) from the cooled to the heated
Dräger Alcotest 9510 Evidential Alcohol Measuring Device
Dräger Alcotest 9510 Evidential Alcohol Measuring Device The Dräger Alcotest 9510 is an advanced breath alcohol measuring instrument for evidential applications. It is designed to comply with national
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...
Solar air collectors for industry and larger halls N S Ø Efficient dehumidification and air heating for free... This booklet contains information about SolarVenti Industrial air solar system. The system
Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC)
Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC) VPS 504 S06 (120 VAC) is: CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter R-15 (Canada) UL
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
GAS HANDLING SYSTEMS VACUUM INSTRUMENT CORPORATION
GAS HANDLING SYSTEMS VACUUM INSTRUMENT CORPORATION 2099 Ninth Avenue Ronkonkoma, NY 11779 www.vacuuminst.com Smart Charge II An advanced gas backfill and evacuation system with built-in gross leak test.
DRYPOINT AC HP PREMIUM HIGH-PRESSURE DRYING
PREMIUM HIGH-PRESSURE DRYING HIGH QUALITY COMPRESSED AIR FROM BEKO The quality of your compressed air. RELIABLE The highest level of operational reliability is guaranteed with every product that BEKO manufactures.
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard
Type 3353 Angle Seat Valve
Type 3353 Angle Seat Valve Application On/off valve with pneumatic piston actuator Nominal size DN 15 to 50 (NPS ½ to 2) Nominal pressure PN Temperature range 10 to 180 C Globe valve with an angle seat
How To Use A Flowmeter
INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection
MANTA Piston Distributor for Oil and Fluid Grease
MANTA Piston Distributor for Oil and Fluid Grease Function Piston distributors meter out and distribute the oil delivered by an intermittently actuated pump. The quantities of oil for the individual lube
Direct steam injection humidifiers
Direct steam injection humidifiers Direct steam injection gives quality control of air humidity. Research and development in separation, the use of lightweight stainless steel combined a constant temperature
Natural gas heating versus split system heating and the current and future viability of the Natural gas network
Natural gas heating versus split system heating and the current and future viability of the Natural gas network Discussion Paper: Energy Consumer Reference Council meeting 7. August 2015 While ActewAGL
Lava. Precision Solutions. Site Planning and Installation Guide
Lava Precision Solutions Site Planning and Installation Guide TABLE OF CONTENTS Table of Contents Introduction...........................................................................................
Monitor and control the sensors through network. supported OPTEX FA CO., LTD. Remote controlling of fiber sensors. Reduces wires and saves space
CC-Link Communication Unit * FASTUS is a product brand of Optex FA. Monitor and control the sensors through network supported Remote controlling of fiber sensors Reduces wires and saves space OPTEX FA