FIRE SAFETY CONCERN ON OPEN KITCHEN IN SMALL RESIDENTIAL UNITS OF TALL BUILDINGS
|
|
|
- Marshall Fisher
- 9 years ago
- Views:
Transcription
1 , Volume 10, Number 3, p.58-62, 2011 FIRE SAFETY CONCERN ON OPEN KITCHEN IN SMALL RESIDENTIAL UNITS OF TALL BUILDINGS W.K. Chow Research Centre for Fire Engineering, Department of Building Services Engineering The Hong Kong Polytechnic University, Hong Kong, China (Received 3 May 2011; Accepted 8 July 2011) ABSTRACT Open kitchens have been designed for many small residential units in tall buildings in Southeast Asia. This open design, without enclosing the kitchen with fire resisting walls has failed to comply with building fire safety codes in places like Hong Kong. Performance-based design was adopted to determine fire safety provisions. Gas cookers with flames are not allowed. Additional fire protection systems such as water mist suppression or dry powder systems have to be provided above the stoves, though studies on kitchen fire physical hazards with and without fire resisting walls were not reported in the literature. A survey on fire load density indicated that large amounts of combustibles are stored in small residential units. Experiments with electric induction cookers indicated that the cooking oil in a frying pan can be ignited within ten minutes. Fire would spread out from the open kitchen to burn up all stored combustibles in the residential unit to give a big fire. There are queries on whether such open kitchens in tall buildings are really safe when there is an accidental fire. Aspects of big open kitchen fires both with and without fire resisting walls in small residential units of tall buildings should be further explored. Fire dynamics must be applied to study the possibility of onsetting flashover upon igniting the cooking oil and burning adjacent combustibles. There might be new fire phenomena such as the air pumping effect of the plume and flame whirling motion in an open kitchen to give big disasters. Full-scale burning tests should be carried out to confirm identified scenarios; to justify the model predictions; and to observe any new physical fire phenomena. Performance of the specified suppression systems including water mist and dry powder suppression systems in big fires must be evaluated. 1. INTRODUCTION Many tall residential buildings over 200 m in height with small units of floor area less than 30 m 2 have been built in dense urban areas in Southeast Asia [1,2]. Fire resisting walls are required to enclose the kitchens. To utilize space more effectively in such a small residential unit, open kitchens have been designed. Although this design failed to comply with the usual building fire safety codes, some projects have been approved by virtue of a performance-based design (PBD) [3,4], known as fire engineering approach in Hong Kong [5]. Three conditions are commonly imposed in the associated PBD design for open kitchens. Firstly, gas cookers cannot be used, and only flameless electric induction cookers are allowed. Secondly, additional fire suppression systems including water mist [6] or dry powder [7] systems are specified for installation. The systems are supposed to act on the stove fire and prevent it from growing large. The residential unit owner cannot take out the system, nor change the cooking stove without approval from the government. Thirdly, the estate management office has to sign an undertaking to implement the approved fire safety management procedures [4,8] specified in the performancebased design report. Open kitchen is included in the new code [9] with additional fire safety provisions on fire detectors, sprinklers and fire resistance walls proposed by the Authorities. However, the performance of open kitchen fires in small units of tall buildings were not studied in detail using fire dynamics tools. Kitchen fire physical hazards with and without fire resisting walls were not even compared [10]. Only the spread of smoke from the open kitchen to areas outside the residential unit was predicted by fire models [11,12]. Results on carbon monoxide concentration, heat flux and visibility were used to justify the available and required safe egress times only as far as the staircase. The provision of additional water mist suppression or dry powder systems targeted to suppress small fires at an early stage might not work as expected if the fire grows big. No experimental data from full-scale burning tests has been made available to support the above specifications. 58
2 Survey [13] on the fire load density in Hong Kong indicated that large quantities of combustibles are stored in residential units. As surveyed by Chow and associates earlier [14,15], the fire load density is particularly high for small units of floor area less than 30 m 2. More combustibles are stored by stacking the stuff up. A very high fire load density above the upper limit of 1135 MJm -2 specified in the local code [16] results. Further, cooking oil can be ignited easily even when using induction cookers [17]. The burning of all combustibles in a big post-flashover fire needs to be studied. There are deep concerns on fire safety for open kitchens in tall residential buildings. Some citizens in such existing buildings with open kitchens are worrying about having big accidental fires if the fire installation systems cannot suppress the small stove fire at the early stage. New fire issues applying to open kitchen fires and the associated protection required for small units in residential buildings should be studied [18]. 2. LITERATURE REVIEW Although there has been much work on kitchen ventilation, thermal plumes, exhaust hoods and fire detection [e.g ], very little concerns kitchen fires. A fire originating from kitchen stoves in a two-storey duplex house was studied by fire models [24]. The critical event was the onset of flashover in the kitchen. Fire spread to the entire house within one minute. In addition, a workshop [25] on residential kitchen fires was held at the Building and Fire Research Laboratory (BFRL), National Institute of Standards and Technology (NIST) in USA in Over 30 participants from professional societies, research laboratories, fire departments, insurance companies and others attended to discuss the existing test methods, technologies, and research and development on residential fire protection. Statistics for kitchen fires in USA was reported. An average annual value of 125,500 home fires started in the kitchen, including confined cooking fires from 1999 to 2002, leading to an average of 460 deaths per year. Although 9% of the fires extended beyond the kitchen, 70% of fatalities were due to this small percentage of kitchen fires. This gives a warning signal to residential units with open kitchens. Fire officers then summed up their firefighting experience, and suggested that installing a single sprinkler would control kitchen fires effectively. Residential range-top fire suppression systems have been proposed and tested by the Underwriters Laboratories Standards UL 300A [26]. Studies on hazard mitigation of kitchen fires at BFRL, NIST were then reported [24]. Kitchen fire hazard characterization and the protection of typical cooking oil fires on stoves by both active and passive fire systems were studied using limited full-scale burning tests. Two points for further research were identified in this workshop : protecting the kitchen fire from spreading; and suppressing the kitchen fire. These two conclusions support in-depth study on open kitchen fires. General fire safety of kitchens in restaurants and hotels and associated fire safety systems has been studied [27-31]. Fire load density for kitchens in residential buildings, hotels and restaurants has been surveyed. Regulations, codes, design guides, practices and safety requirements on fire and ventilation in kitchens have been reviewed thoroughly. Fire safety in Chinese kitchens was studied with fire models. Kitchen fire safety in a hotel group in Hong Kong was studied. As most kitchen fires started from Chinese woks on the stoves, heat release rates in burning such woks in accidental fires have been measured by the oxygen consumption method. Performance of sprinkler and water mist system in kitchens with woks under small fires were evaluated preliminarily. Results of this project were applied to the design of fire safety provisions in the kitchens of large hotel groups in the Far East. However, such results cannot be applied to open kitchen fires in small residential units in tall buildings. Possible ignition of cooking oil while using the specified electric induction cookers in kitchen was studied [17]. However, the study only measured flame temperature, flame shape and flame length. The heat release rate of the cooking oil was not measured and the effect of fire suppression systems was not evaluated. Some of the observed phenomena, such as the ignition of cooking oil within 10 minutes by the electric induction cooker, need to be further justified. Note that similar tests [25,26,29-31] showed that the ignition of cooking oil by gas cookers took 75 to 180 minutes. 3. HAZARDOUS SCENARIOS The fire scenario [32] in a residential unit depends on the amount of fuel, materials stored, storage arrangements and ventilation provisions. An earlier survey showed that the fire load in a small residential unit can be very high. Typical fire scenarios are proposed to be worked out by first understanding the combustibles content. Ignition possibilities, including frying food with electric induction cookers, will then be investigated. 59
3 Bench-scale experiments studying cooking oil fires should be reviewed [17,24-26,29-31]. The possibility of the onset of flashover in residential units can then be analyzed based on empirical expressions reported in the literature [33,34]. Fire behaviour of combustibles under postflashover fires [35] in a small residential unit is suggested to be burnt by imposing a high thermal radiation heat flux on all combustibles. An open kitchen design would provide sufficient air for combustion, and possess no fire resisting walls to block heat and mass transfer. Air pumping action [36], in addition, would give higher air rate leading to sustained combustion of the ignited objects. 4. HAZARD ASSESSMENT Hazard assessments based on the identified scenarios will be carried out with empirical formula derived from analytical study of the fire scenarios and fire models. Some cases will be backed up by full-scale burning tests to justify the model predictions. Literature [e.g. 33,34,37,38] on modelling heat release rates for kitchen arrangements will be taken as the starting point. The total heat release rate in a kitchen is first estimated using the principle of superposition [37,38] in combining the heat release rates curves of the furnishings and finishes deduced from a cone calorimeter. The results from full-scale burning tests will then be used to model overall heat release rates when those kitchen combustibles are burnt. A scenario based on common geometry of the open kitchen in Hong Kong should be considered. The electric induction cooker with cooking oil will be taken as the fire source. A fire will be started from the burning of cooking oil in a wok with reference to UL300A [26]. 5. PERFORMANCE EVALUATION OF INSTALLED SYSTEMS Performance of the permitted water mist and dry powder systems [16,17] in controlling flashover big fires must be evaluated. Experiment is suggested to be carried out in a room calorimeter with heat release rate measured [11,12]. A big fire scenario in a typical open kitchen arrangement without fire suppression system operating would be burnt first. Operation of the adopted water mist system [16], and the dry powder system [17] in this fire scenario are then tested. For each test, gas temperature distributions and heat fluxes at the floor levels are measured first. The key fire parameters of burning duration, peak heat release rates and maximum heat flux can then be deduced. The effects of water sprays and dry powder on the burning objects can then be studied from the measured air temperatures, heat fluxes and heat release rates in a similar fashion to other reported work [11,12,38]. Reductions in peak heat release rates due to the suppression system, and maximum heat flux can be assessed. The extinguishing time, if any, will be measured. Fire spread from the open kitchen to the residential unit will be studied numerically. 6. CONCLUSION All concerns raised above on open kitchen fires should be considered. More importantly, the effect of a fire resisting wall for enclosing the kitchen and the degree of protection provided by the current suppression system must be further justified with full-scale burning tests. Appropriate design guides and fire safety management procedures promoting adequate fire safety for open kitchens in small units of tall residential buildings can then be recommended. Note that there are on-going researches on kitchen fires all over the world [39]. ACKNOWLEDGEMENT This work described in this paper was supported by a grant from the Research Grants Council of the Hong Kong Special Administrative Region, China for the project Aspects of Open Kitchen Fires in Tall Buildings and Protection Alternatives (PolyU 5136/11E) with account number B-Q27R. REFERENCES 1. W.K. Chow, Several points to note in performance-based design for fire safety provisions in Hong Kong, Plenary talk, The National Symposium on Fire Safety Science and Engineering, China Fire Protection Association, Beijing. China, October (2010). 2. Centaline Property, 3. W.K. Chow, A preliminary discussion on engineering performance-based fire codes in the Hong Kong Special Administrative Region, International Journal on Engineering Performance- Based Fire Codes, Vol. 1, No. 1, pp (1999). 4. CIBSE, Guide E: Fire engineering, The Chartered Institution of Building Services Engineers, London, UK (2010). 60
4 5. PNAP 204 Practice note for authorized persons and registered structural engineers: Guide to fire engineering approach, first issued in March (Re-issued under new categorization in August 2009 as Practice note for authorized persons, registered structural engineers and registered geotechnical engineers), Buildings Department, Hong Kong Special Administrative Region, April (2009). 6. The Guardian III, Owner s manual for installation, operation and maintenance, Model G300-A Wet chemical extinguisher unit, G310A-A (2007) caf a cb72/G3-manual.aspx 7. The Guardian, Owner s manual for installation, operation and maintenance. Model 1384-A Wet chemical extinguisher unit. NO S. (2000). e b17-a9da-b2ef /guardian-i- Manual.aspx 8. W.K. Chow, Building fire safety in the Far East, Architectural Science Review, Vol. 48, No. 4, pp (2005). 9. Draft Code of Practice for Fire Safety discussed in the 13 th Steering Committee Meeting held on 6 May 2011, Clause C13.4 for the requirements on open kitchen design. Fire Safety Committee and Advisory Committee for the Fire Safety (Buildings) Ordinance and the Fire Safety (Commercial Premises) Ordinance, Buildings Department, Government of the Hong Kong Special Administrative Region. 10. W.K. Chow, Assessing construction elements with lower fire resistance rating under big fires, Journal of Applied Fire Science, Vol. 14, No. 4, pp ( ). 11. W.W. Jones, R.D. Peacock, G.P. Forney and P.A. Reneke CFAST Consolidated Model of Fire Growth and Smoke Transport (version 6) - Technical reference guide, NISTSP 1026, National Institute of Standards and Technology, US Department of Commerce, May (2008). 12. K.B. McGrattan, S. Hostikka, J.E. Floyd, H.R. Baum and R.G. Rehm, Fire Dynamics Simulator (version 5): Technical reference guide, NIST special publication , Building and Fire Research Laboratory, National Institute of Standards and Technology, Gaithersburg, Maryland, USA, October (2007). 13. Arup research brochure, Ove Arup Hong Kong, December (2010). 14. W.K. Chow, Carmen C.S. Fong and Kenny S.M. Kong, Fire load survey for offices in a university, International Journal for Housing Science and Its Applications, Vol. 30, No. 3, pp (2006). 15. C.L. Chow and W.K. Chow, Fire safety aspects of refuge floors in supertall buildings with computational fluid dynamics, Journal of Civil Engineering and Management, Vol. 15, No. 3, pp (2009). 16. Code of Practice for Minimum Fire Service Installations and Equipment and Inspection, Testing and Maintenance of Installations and Equipment, Fire Services Department, Hong Kong Special Administrative Region, July (2005). 17. A.K.K. Wong, Experimental study of induction cooker for fire hazard, MSc dissertation, The Hong Kong Polytechnic University, Hong Kong (2009). 18. W.K. Chow, Points of concern in performancebased design for fire safety provisions in Hong Kong, Talk at Nanjing University of Technology, Nanjing, Jiangsu, China, 13 April (2011). 19. R.M. Kelso and C. Rousseau, Kitchen ventilation, ASHRAE Journal, Vol. 37, No. 9, September (1995). 20. Che-Ming Chiang, Chi-Ming Lai, Po-Cheng Chou and Yen-Yi Li, The influence of an architectural design alternative (transoms) on indoor air environment in conventional kitchens in Taiwan, Building and Environment, Vol., 35, No. 7, pp (2000). 21. Q.Y. Xie, H.Y. Yuan and H.L. Guo, Experimental analysis on false alarms of fire detectors by cooking fumes, Journal of Fire Sciences, Vol. 22, No. 4, pp (2004). 22. Risto Kosonen, Hannu Koskela and Pekka Saarinen, Thermal plumes of kitchen appliances: Cooking mode, Energy and Buildings, Vol. 38, No. 10, pp (2006). 23. J.A.T. Halls, Ultra low resolution thermal imaging for kitchen hazard detection: A technology feasibility study, 4th International Conference on Smart Homes and Health Telematics, June 2006, Belfast, Ireland, Smart Homes and Beyond, Assistive Technology Research Series, 19, pp (2006). 24. D. Madrzykowski, G.P. Forney and W.D. Walton, Simulation of the dynamics of a fire in a two-story duplex Iowa, December 22, 1999, NISTIR 6854, Building and Fire Research Laboratory, National Institute of Standards and Technology, Gaithersburg, MD, USA, January (2002). 25. D. Madrzykowski, A. Hamins and S. Mehta, Residential kitchen fire suppression research needs: Workshop proceedings, NIST Special Publication 1066, US Department of Commerce, National Institute of Standards and Technology, Gaithersburg, MD, February (2007). 26. UL300A Outline of investigation for extinguishing system units for residential range top cooking surfaces - Issue 3, Underwriters Laboratories Inc., Northbrook, Illinois, USA (2006). 27. W.K. Chow, Zone model simulations of fires in Chinese restaurants in Hong Kong, Journal of Fire Sciences, Vol. 13, No. 3, pp (1995). 28. W.K. Chow, Use of the ARGOS fire risk analysis model for studying Chinese restaurant fires, Fire and Materials, Vol. 19, No. 4, pp (1995). 61
5 29. H.H. Wu, W.K. Chow, G.W. Zou, H. Dong and Y. Gao, Performance evaluation of fire services installation in kitchens of big hotels, BUEE2006, 8 th International Symposium on Building and Urban Environmental Engineering, held at Tokyo Institute of Technology, Tokyo, Japan, July 2006, p (2006). 30. H.H. Wu, A critical study on the fire safety for big hotels in Hong Kong, PhD thesis, Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong (2006). 31. W.K. Chow and H.H. Wu, Measured heat release rate in Chinese kitchen wok fires, Poster paper at 10th International IAFSS Symposium, University of Maryland, College Park, Maryland, USA, June (2011). 32. G.V. Hadjisophocleous and E. Zalok, Development of design fires for performancebased fire safety designs, Invited Lecture, Fire Safety Science - Proceedings of the Ninth International Symposium, September 2008, Karlsruhe, Germany (2008). 33. W.K. Chow, Review on heat release rate for fires in small retail shops, Journal of Applied Fire Science, Vol. 10, No. 2, pp (2001). 34. F.W. Mowrer and R.B. Williamson Methods to characteristic heat release rate data, Fire Safety Journal, Vol. 16, No. 5, pp (1990). 35. W.K. Chow, Necessity of testing combustibles under well-developed fires, Journal of Fire Sciences, Vol. 26, No. 4, pp (2008). 36. T.Z. Harmathy, Fire safety design and concrete (Concrete design and construction series), Longman Scientific & Technical, Essex, England (1993). 37. B. Sundström (editor), Fire safety of upholstered furniture, Final report on the CBUF Research Programme, Interscience Communication Ltd, London, UK (1995). 38. W.K. Chow, Combining heat release rates of combustibles, Journal of Applied Fire Science, Vol. 17, No. 3, pp ( ). 39. K.H. Almand, Fire Protection Research Foundation, National Fire Protection Association, Quincy, MA, USA - Private communication, July (2011). 62
Design Fire in Performance-based Fire Safety Design for Green and Sustainable Buildings
Design Fire in Performance-based Fire Safety Design for Green and Sustainable Buildings W.K. Chow Areas of Strength: Fire Safety Engineering, Research Centre for Fire Engineering, Department of Building
A PRELIMINARY REVIEW ON BUILDING FIRE CODES AND APPLICATION PROCEDURE FOR NEW PROJECTS IN CHINA
, Volume 8, Number 3, p.88-98, 2006 A PRELIMINARY REVIEW ON BUILDING FIRE CODES AND APPLICATION PROCEDURE FOR NEW PROJECTS IN CHINA W.K. Chow and L.H. Hu Research Centre for Fire Engineering, Department
CFAST Consolidated Model of Fire Growth and Smoke Transport (Version 6) Software Development and Model Evaluation Guide
NIST Special Publication 86r December Revision CFAST Consolidated Model of Fire Growth and Smoke Transport (Version 6) Software Development and Model Evaluation Guide Richard D. Peacock Paul A. Reneke
C u r r i c u l u m V i t a e Lee K. McCarthy, P.E., IAAI-CFI, CFEI Fire Protection Engineer. Professional Practice. Employment History
C u r r i c u l u m V i t a e, IAAI-CFI, CFEI Fire Protection Engineer Professional Practice Lee McCarthy is a licensed professional engineer with more than 7 years of experience in the areas of fire and
Appraisal of Passive and Active Fire Protection Systems in Student s Accommodation
MATEC Web of Conferences 10, 06002 (2014) DOI: 10.1051/ matecconf/ 20141006002 C Owned by the authors, published by EDP Sciences, 2014 Appraisal of Passive and Active Fire Protection Systems in Student
Proposed fire safety strategy on airport terminals. Candy M.Y. Ng and W.K. Chow*
Int. J. Risk Assessment and Management, Vol. 5, No. 1, 2005 95 Proposed fire safety strategy on airport terminals Candy M.Y. Ng and W.K. Chow* Research Centre for Fire Engineering, Department of Building
The Collection of Topics which Comprise Fire Protection Engineering
The Collection of Topics which Comprise Fire Protection Engineering FCIA Key Biscayne, FL November 12, 2009 Jim Milke, Professor and Assoc. Chair Department of Fire Protection Engineering University of
UL 300 Standard. RS 1021 (9/13) 2013 Nationwide Mutual Insurance Company Page 1 of 6 All Rights Reserved
Summary Fire test standard UL 300 has been a major factor in significant changes in how commercial cooking operations are protected from fire. This report looks at the background of UL 300 and changes
Fire Safety Risk Assessment
1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept
Piotr Tofiło a,*, Marek Konecki b, Jerzy Gałaj c, Waldemar Jaskółowski d, Norbert Tuśnio e, Marcin Cisek f
Available online at www.sciencedirect.com Procedia Engineering 57 (2013 ) 1156 1165 11th International Conference on Modern Building Materials, Structures and Techniques, MBMST 2013 Expert System for Building
Teaching Fire Science and Fire Protection Engineering to Building Engineering Students 1
Teaching Fire Science and Fire Protection Engineering to Building Engineering Students 1 Abstract: David Torvi, Ph.D., P.Eng. Research Officer Fire Risk Management Program Institute for Research in Construction
NEW SCIENCE FIRE SAFETY ARTICLE INNOVATING FIRE ATTACK TACTICS SUMMER 2013 UL.COM/NEWSCIENCE
NEW SCIENCE FIRE SAFETY ARTICLE INNOVATING FIRE ATTACK TACTICS SUMMER 2013 UL.COM/NEWSCIENCE NEW SCIENCE FIRE SAFETY OVERVIEW UL s dedicated team of scientists, engineers and researchers is creating New
Watermist fire suppression systems for commercial low hazard occupancies
Watermist fire suppression systems for commercial low hazard occupancies Watermist fire protection systems are fire suppression systems that have emerged as an alternative fire safety solution for specific
Development of Seismic-induced Fire Risk Assessment Method for a Building
Development of Seismic-induced Fire Risk Assessment Method for a Building AI SEKIZAWA National Research Institute of Fire and Disaster 3-14-1, Nakahara, Mitaka, Tokyo 181-8633, Japan [email protected]
Commercial Kitchen Fire Safety
Commercial Kitchen Fire Safety Commercial grade kitchens are a common feature found in many churches today, as religious institutions are providing meals for daycares, soup kitchens, meals on wheels and
Fire Safety Requirements for Child Care Centre
Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,
Influence of fire source locations on the actuation of wet-type sprinklers in an office fire
Influence of fire source locations on the actuation of wet-type sprinklers in an office fire Ko-Jen Chen 1 Chun-Ta Tzeng 2 Chi-ming Lai 3 Abstract An experiment is conducted on a full-scale model office
Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings
Building Control Householder Guidance Leaflet No. 29 Fire detection in dwellings This leaflet is one of a series produced by the Hertfordshire Building Control Technical Forum GUIDANCE NOTE FOR HOME OWNERS
Fire detection in kitchens
Fire detection in kitchens Protection of people, business continuity and reputation Large cooking vessels, frying pans, and deep frying vats present a very serious fire hazard in commercial kitchens. This
St. John s University
St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica
Fire Development and Fire Behavior Indicators
Battalion Chief Ed Hartin, MS, EFO, MIFireE, CFO Introduction Building Factors, Smoke, Air Track, Heat, and Flame (B-SAHF) are critical fire behavior indicators. Understanding the indicators is important,
FIRE SAFETY RISK ASSESSMENT
FIRE SAFETY RISK ASSESSMENT For small single occupancy premises Premises Hertco Ltd ACME House, Old London Road, Hertford SG17 7LD Fire Safety Risk Assessment for Small Premises Introduction Regulatory
Fire and Rescue Service Operational Guidance. GRA 5.8 flashover, backdraught and fire gas ignitions
Fire and Rescue Service Operational Guidance GRA 5.8 flashover, backdraught and fire gas ignitions Generic Risk Assessment 5.8 Flashover, backdraught and fire gas ignitions August 2009 London: TSO Published
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
Fire safety for landlords
Fire safety for landlords Acting Acting to to Protect & Save Are you a landlord and confused about your responsibilities towards fire safety? The law and regulations can often seem complicated and grey.
An Overview of the International Road Tunnel Fire Detection Research Project
An Overview of the International Road Tunnel Fire Detection Research Project Introduction Z. Liu 1, A. Kashef, G. Lougheed, J. Z. Su and N. Benichou Fire Research Program, Institute for Research in Construction
Fire Safety Risk Assessment Checklist for Residential Care Premises
Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or
THE HONG KONG INSTITUTION OF ENGINEERS 香 港 工 程 師 學 會. Admission Requirements for the Fire Discipline (Normal Route) Item Description Remarks
Admission Requirements for the Fire Discipline (Normal Route) Item Description Remarks Age Academic requirements (either (a), (b), (c) or (d) ) 25 minimum The academic requirement for Member in the Fire
Fire-Rated Glass and Glazing START
Fire-Rated Glass and Glazing START www.pilkington.com/fire Fire-Rated Glass and Glazing Pilkington Fire Protection Glass North America 946 Kane Street, Suite A Toledo, OH 43612 Provider Number: J200 Course
FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES
FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES P.L. Senez*, K.D. Calder, Hsing H (Isabella) Li Sereca Fire Consulting Ltd., Canada INTRODUCTION
DEPARTMENT OF CIVIL AND ENVIRONMENTAL ENGINEERING A SHORT COURSE. Fire and Explosion Investigations. May 11-13, 2005
DEPARTMENT OF CIVIL AND ENVIRONMENTAL ENGINEERING A SHORT COURSE Fire and Explosion Investigations May 11-13, 2005 Room 5050 - Minto Building Carleton University 1125 Colonel By Drive Ottawa, Ontario,
Challenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection
Challenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection Z. G. Liu *, A. Kashef, G. Lougheed, and A. K. Kim Fire Research Program, Institute for Research in Construction National
BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
Fire Safety PROCEDURES January 2011
Fire Safety PROCEDURES January 2011 [email protected] Campus Phones EMERGENCY Dial 911 Fire Safety Service is the focal point for the coordinated administration of the University Fire Safety program and
Automatic fire-extinguishing systems for commercial cooking
Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and
Action required (Please tick) If you answered YES, record Action Points at STEP 4
RECORD OF FIRE SAFETY RISK ASSESSMENT Building Name & Use: Address: Postcode: Name of person(s) with fire safety duties: Name and contact details of assessor: Date of Assessment: 6 th February 2011 Laurel
ON MOST schemes, the architectural design of. Flexible strategy. Case study. The Forum
Flexible strategy ON MOST schemes, the architectural design of a building is influenced by fire engineering strategy. This could be in the form of visual, physical elements such as fire doors, fire curtains,
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
Alarm Time Analysis. (s)
Performance of Dual Photoelectric/Ionization Smoke Alarms in Full-Scale Fire Tests Thomas Cleary Building and Fire Research Laboratory National Institute of Standards and Technology Gaithersburg, MD (31)
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
IFE Level 4 Certificate in Fire Science and Fire Safety (HL)
IFE Level 4 Certificate in Fire Science and Fire Safety (HL) Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the prevention and detection of fire in premises and
HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008
HSE information sheet Fire and explosion hazards in offshore gas turbines Offshore Information Sheet No. 10/2008 Contents Introduction.. 2 Background of gas turbine incidents in the UK offshore sector...2
For use by landlords of small premises Premises Address
fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):
REVIEW ON FIRE REGULATIONS FOR NEW HIGH-RISE COMMERCIAL BUILDINGS IN HONG KONG AND A BRIEF COMPARISON WITH THOSE IN OVERSEAS
, Volume 3, Number 1, p.25-51, 2001 REVIEW ON FIRE REGULATIONS FOR NEW HIGH-RISE COMMERCIAL BUILDINGS IN HONG KONG AND A BRIEF COMPARISON WITH THOSE IN OVERSEAS W.Y. Hung and W.K. Chow Department of Building
DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple
CHAPTER SEVEN L. Glicksman and J. Lin (eds), Sustainable Urban Housing in China, 116-123 2006 Springer. Printed in the Netherlands. DESIGN OF NATURAL VENTILATION WITH CFD Qingyan Chen INTRODUCTION As the
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
One united company. Advancing fire protection.
One united company. Advancing fire protection. We are Kidde Fire Systems. Kidde Fire Systems products save people and property from the dangers of fire. Our broad product offering and design expertise
MODELING THE PERFORMANCE OF FIRE PROTECTION SYSTEMS IN MODERN DATA CENTERS
MODELING THE PERFORMANCE OF FIRE PROTECTION SYSTEMS IN MODERN DATA CENTERS Richard W. Bukowski. P.E., FSFPE and Ralph Transue, P.E. Rolf Jensen and Associates, Chicago, IL 60661 USA Data Centers Society
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed
Smoke & Carbon Monoxide
A Guide to the Massachusetts Smoke & Carbon Monoxide Requirements when Selling a Oneor Two-Family Residence FIRE SERVICES Department of Fire Services PO Box 1025 Stow, MA 01775 978-567-3300 www.mass.gov/dfs
CONE CALORIMETER A TOOL FOR MEASURING HEAT RELEASE RATE
CONE CALORIMETER A TOOL FOR MEASURING HEAT RELEASE RATE Johan Lindholm, Anders Brink and Mikko Hupa Åbo Akademi Process Chemistry Centre, Biskopsgatan 8, FI-20500 Åbo, FINLAND Corresponding author: E-mail:
Pearl River Tower, Guangzhou: Fire Protection Strategies for an Energy Efficient High-Rise Building
Pearl River Tower, Guangzhou: Fire Protection Strategies for an Energy Efficient High-Rise Building Fang Li 1, James Antell, AIA, P.E. 2 and Martin Reiss, P.E., FSFPE 3 1 Vice President, China Operations,
EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS
EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS Yunlong Liu and Vivek Apte CSIRO Fire Science and Technology Laboratory PO Box 31 North Ryde, NSW 167, Australia TEL:+61 2 949
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Guide to Massachusetts Smoke & Carbon Monoxide Requirements
Guide to Massachusetts Smoke & Carbon Monoxide Requirements When Selling a One- or Two-Family Residence DEPARTMENT OF FIRE SERVICES Stephen D. Coan State Fire Marshal M.G.L. c 148 s. 26F - The Law Massachusetts
FSD Circular Letter No. 7/95 Automatic Fire Detection System - Design and Maintenance Considerations
Our Ref.: 1 5 (49) in FPB 314/07 III FIRE SERVICES DEPARTMENT FIRE PROTECTION COMMAND FIRE SERVICES HEADQUARTERS BUILDING, No. 1 Hong Chong Road, 5/F., Tsim Sha Tsui East, Kowloon, Hong Kong Your Ref.:
Put us to the test. Construction testing and building investigations services from BRE. www.bre.co.uk
Put us to the test Construction testing and building investigations services from BRE www.bre.co.uk Backed by an extraordinary range of facilities BRE prides itself on being able to answer virtually any
FIRE RISK ANALYSIS OF THE AIRPORT TERMINALS
, Volume 5, Number 4, p.103-107, 2003 FIRE RISK ANALYSIS OF THE AIRPORT TERMINALS M.Y. Ng Department of Building Serices Engineering, The Hong Kong Polytechnic Uniersity, Hong Kong, China ABSTRACT The
UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS
Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern
High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications
International Water Mist Conference, London, United Kingdom,23-24 September, 2009 High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications Fire Fighting In Civil Applications
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
MOTOR FUEL DISPENSING SAFETY
STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.
CERTIFICATE OF COMPLIANCE
CERTIFICATE OF COMPLIANCE (Smoke Detector Inspection) Smoke detectors and carbon monoxide detectors must be in the proper locations and operational. Your house must also be properly numbered in order to
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
Integrated CFD Models for Air-sampling Smoke Detection
Integrated CFD Models for Air-sampling Smoke Detection Yun Jiang 1, John Vythoulkas & Scott Wilson 2 Xtralis AG. ABSTRACT Computational Fluid Dynamic ( CFD ) modelling is becoming a powerful tool both
Global Leaders in Fire Engineering. Company Overview. Finding simple solutions to complex problems.
Company Overview Finding simple solutions to complex problems. ON M9B 6H7 AB T2H 1Z9 339941 From our offices in,, and, we serve our national and international clients by providing cost-effective solutions
Fire Risk in Metro Tunnels and Stations
Fire Risk in Metro Tunnels and Stations Hyder Consulting Presented by: Dr. Leong Poon Ir. Richard Lau 2 Dec 2005 Metro Tunnels and Stations General Characteristics Limited to metropolitan area (hence the
Fire Standards & Regulations Are you confused?
Fire Standards & Regulations Are you confused? Regulatory Reform (Fire Safety) Order Local Licensing Requirements BS 5839-6: 2013 Building Regulations Document B LACORS Fire Safety Guidance Fire Alarm
Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company
RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing
Minnesota State Department of Public Safety
Minnesota State Department of Public Safety 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us Inspection
The terms hazard and risk are often used, which we define as the following:
Fire Safety Last updated in October 2010 This information sheet aims to give safety reps a basic understanding of fire safety and fire risk assessments under the current law. More detailed information
ASTM E5.11.20 Building Perimeter Fire Summary of Papers that have been written on Fire Exposures that deal with High Rise Buildings and Vision Glass
ASTM E5.11.20 Building Perimeter Fire Summary of Papers that have been written on Fire Exposures that deal with High Rise Buildings and Vision Glass Written by James C. Shriver, Director Technical Service,
Safe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
SPECIAL CLAUSES/WARRANTIES THESE ARE OPERATIVE ONLY IF SHOWN IN THE SCHEDULE OR IN AN ENDORSEMENTFORMING PART OF THE SCHEDULE
SPECIAL CLAUSES/WARRANTIES THESE ARE OPERATIVE ONLY IF SHOWN IN THE SCHEDULE OR IN AN ENDORSEMENTFORMING PART OF THE SCHEDULE CL2 - Pipe and Tank Lagging Warranty Underwriters will not be liable for loss
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone
Town of Bellingham Fire Department
Town of Bellingham Fire Department OFFICE OF THE Fire Prevention Division Captain Robidoux- [email protected] Lieutenant Bangma- [email protected] Fire Safety Inspection Guidelines for
Decree of the Ministry of the Environment on fire safety of buildings
E1 THE NATIONAL BUILDING CODE OF FINLAND 1 Fire safety of buildings Regulations and guidelines 2002 Decree of the Ministry of the Environment on fire safety of buildings Adopted in Helsinki, 12 March 2002
PLAN SUBMITTAL REQUIREMENTS FOR KITCHEN HOOD AND DUCT EXTINGUISHING SYSTEMS
March 1996 PLAN SUBMITTAL REQUIREMENTS FOR KITCHEN HOOD AND DUCT EXTINGUISHING SYSTEMS PLAN REVIEW 1. Submit a completed permit application and a minimum of three sets of shopquality plans and calculations
Restaurant & café guide
'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers
DCSS (ACB) Data Center Fire Suppression Procedures
May 18, 2015 DCSS (ACB) Data Center Fire Suppression Procedures Purpose: This document is intended for all individuals who have access to the data center at 1011 West Springfield Avenue, Advanced Computation
INITIAL ASSESSMENT OF THE IMPACT OF JET FLAME HAZARD FROM HYDROGEN CARS IN ROAD TUNNELS AND THE IMPLICATION ON HYDROGEN CAR DESIGN
INITIAL ASSESSMENT OF THE IMPACT OF JET FLAME HAZARD FROM HYDROGEN CARS IN ROAD TUNNELS AND THE IMPLICATION ON HYDROGEN CAR DESIGN Wu, Y Department of Chemical and Process Engineering, University of Sheffield,
Compliance Schedules and Building Warrant of Fitness
Compliance Schedules and Building Warrant of Fitness Purpose of this guidance information The purpose of this guidance information is to help building owners and managers of commercial, industrial or communal
FIRE DETECTION AND ALARM SYSTEMS
HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some
LESSON PLAN 4 6-8 FIRE PREVENTION AND SAFETY
The Science of Fire-Suppression and Fire-Warning Systems Activity Fire Insurance Activity Community Service Project Activity KEY TERMS AND CONCEPTS sprinkler system fire codes smoke alarm photoelectric
FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT This template has been provided to assist the Responsible Person with the preparation of a Fire Risk Assessment and is not intended for commercial
Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009
Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 By Carsten Palle, VID Fire-Fill, www.vid.eu Presented at ISTSS
Hotel Fire Safety for staff
Teaching Guide Hotel Fire Safety for staff Seattle Fire Department Fire Prevention Division Hotel Fire Safety Instructor Outline Introduction Goals: To ensure that hotel employees are knowledgeable in
Grasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment
Grasshoppers Rugby Football Sports and Social Club The Fire Risk Assessment Revision 1 Dated: 15th February 2013 CONTENTS 1. PREMISES DETAILS 2. PREMISES PLAN 3. HAZARDS 4. HISTORY 5. MITIGATING THE EFFECTS
FIRE CODE INTERPRETATION
FIRE CODE INTERPRETATION February 2014 FCI-14-02 Page 1 of 6 ISSUE: Fixed Fire Suppression & Exhaust Systems Cooking A number of queries from owners, designers and safety codes officers have been received
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
Improving fire safety through engineering (rational designs)
Improving fire safety through engineering (rational designs) Johan van den Heever Fire Safety Indaba, Cape Town 2013 'Promoting responsible fire safety in Southern Africa' 1 Introduction What is fire safety
Section 9 Major Urban Fire
Section 9 Major Urban Fire Table of Contents WHY MAJOR URBAN FIRES ARE A THREAT...9-2 HAZARD PROFILE...9-3 HISTORY OF MAJOR URBAN FIRES...9-4 POTENTIAL DAMAGES AND LOSSES...9-5 MAJOR URBAN FIRE MITIGATION
The Smoke and Carbon Monoxide Alarm (England) Regulations 2015
The Smoke and Carbon Monoxide Alarm (England) Regulations 2015 Q&A Booklet for the Private Rented Sector landlords and tenants September 2015 Department for Communities and Local Government Crown copyright,