Formal Interpretation NFPA 10. Portable Fire Extinguishers Edition
|
|
|
- Sabina Lester
- 9 years ago
- Views:
Transcription
1 Reference: and F.I. No.: Background:, subsection requires that fire extinguishers be provided for the protection of cooking appliances that use combustible cooking media (vegetable or animal oils and fats) be listed and labeled for Class K fires. Subsection requires class K fire extinguishers be provided for hazards where there is a potential for fires involving combustible cooking media (vegetable or animal oils and fats). Based on these two requirements, there is confusion with regard to requiring class K extinguishers for stove top cooking. Questions No. 1: Do subsections and require class K extinguishers to be installed for commercial fryers employing combustible cooking media (vegetable or animal oils and fats)? Answer: Yes Questions No. 2: Do subsections and require class K extinguishers to be installed for a griddle? Answer: Yes Questions No. 3: Do subsections and require class K extinguishers to be installed for a stove top frying pan? Answer: Yes Issue Edition: 2002 Reference: and Issue Date: July 7, 2005 Effective Date: July 27, 2005 Copyright 2013 All Rights Reserved
2 Reference: F.I. No.: Background: Where a hazard is protected by an automatic fire protection system, a placard shall be conspicuously placed near the extinguisher that states that the fire protection system shall be actuated prior to using the fire extinguisher. Question: Is it the intent of the Committee that the instructions on this placard apply to all Class K fires including those other than the deep fryer fires? Issue Edition: 1998 Reference: Issue Date: January 22, 2002 Effective Date: February 11, 2002 Copyright 2013 All Rights Reserved
3 Reference: , , F.I. No: 84-2 Background: During regular maintenance of fire extinguishers in an apartment building, it was found that extinguishers were provided on the main or ground level floor and not on the second floor or basement level. The apartment proprietors explained that the rationale for not providing extinguishers on the second or basement level was that the extinguishers on the main level are within the 75-ft maximum travel distance, if the stairway is included in the calculations. Question: Does prohibit the inclusion of a flight(s) of stairs in the calculation of travel distance? Travel distance is intended to reflect the time it takes to respond with an extinguisher to a fire emergency. A staircase slows down response time. Furthermore, there could well be interference to obtaining and transporting the extinguisher from tenants vacating the premises. Paragraph states, Fire extinguishers shall be conspicuously located where they will be readily accessible and immediately available in the event of fire, and states, Fire extinguishers shall not be obstructed or obscured from view. Extinguishers located on another floor do not meet the intent of these paragraphs. Issue Edition: 1984 Reference: 3-2.1, Date: October 1984 Copyright 2013 All Rights Reserved
4 Reference: , , 7.3.1, F.I. No.: Background: Some people claim that a maintenance procedure that does not require internal maintenance is essentially the same as a monthly inspection procedure, so only minimal knowledge is required and no special training. Some people claim persons performing the external examination required by need special training, the manufacturer s maintenance manual, repair parts, and appropriate servicing equipment. Question: Subsection requires all extinguishers be examined externally on an annual basis. Subsection requires certain extinguishers to be examined only internally. Are individuals conducting only the external maintenance required to be trained and certified in accordance with and ? Issue Edition: 1998 Reference: 4-1.4, 4-4.1, and Issue Date: December 15, 1998 Effective Date: January 4, 1999 Copyright 2013 All Rights Reserved
5 Reference: F.I. No.: Background: Some people interpret to mean that it is acceptable either to do maintenance at yearly intervals or to do maintenance when an inspection specifically indicates the need. Either program will satisfy requirements. Question: Is it the intent of that all fire extinguishers should be subjected to maintenance at a maximum interval of not more than 1 year? Issue Edition: 1998 Reference: Issue Date: December 15, 1998 Effective Date: January 4, 1999 Copyright 2013 All Rights Reserved
6 Reference: F.I. No: 84-5 Background: Subsection states: Where required by another section of this standard, maintenance procedures shall include the procedures detailed in the manufacturer s service manual and a thorough examination of the basic elements of the fire extinguisher, including the following: (1) Mechanical parts of all fire extinguishers (2) Extinguishing agent (3) Expelling means (4) Physical condition Referring now to Annex I, Table I.1(a), Mechanical Parts Maintenance Checklist, calls for a check of Gas Tube and Siphon or Pickup Tube and Table I.1(b ), Agent and Expelling Means Maintenance Checklist, calls for a check of Agent Condition (contamination, caking, or wrong agent). Question: To do the above two check points, is it the intent to require emptying, annually, a cartridgeoperated dry chemical extinguisher? Answer: No. Issue Edition: 1984 Reference: Date: March 1986 Copyright 2013 All Rights Reserved
7 Reference: 7.9.2, F.I. No: 84-3 Background: A system has been submitted to a laboratory for listing that is intended for the rebuilding of 2 ½-gallon, stainless steel, stored-pressure, water fire extinguishers that were manufactured in 1964 or later. The extinguishers would be thoroughly inspected and tested, fitted with a new hose and solid AFFF cartridge nozzle, and relabeled. No modifications would be made to the internal parts of the extinguisher, and the extinguisher charge remains exactly as originally designed. The entire operation would be subjected to follow-up inspections by the testing laboratory and accomplished only at locations authorized by the laboratory. The rating of the extinguisher is upgraded from 2-A to 3-A:40-B, thus providing the owner of the extinguisher with a significant increase in fire extinguishing capability. A laboratory has accepted the system for test but is unlikely to list it until the question of possible conflict with and is answered. Question 1: Is it the intent of and to prohibit field alteration or conversion of listed portable extinguishers from one type to another? Issue Edition: 1984 Reference: Date: January 1985 Reissued to correct error: January 1986 Copyright 2013 All Rights Reserved
8 Reference: F.I. No: 84-1 Background: A 12-year testing interval has been used when portable CO 2 fire extinguishers have not been discharged. Consequently, this procedure has saved a considerable amount of time and money. Question: Is it the intent of that all portable CO 2 fire extinguishers be hydrostatically tested every 5 years, regardless of whether or not they have been discharged? Issue Edition: 1984 Reference: 5-2 Date: June 1984 Copyright 2013 All Rights Reserved
Model Safety Program
Model Safety Program DATE: SUBJECT: Fire Extinguisher Program REGULATORY STANDARD: OSHA 29 CFR 1910.157 NFPA 10 RESPONSIBILITY: The company Safety Officer is. He/she is solely responsible for all facets
PLAN SUBMITTAL REQUIREMENTS FOR KITCHEN HOOD AND DUCT EXTINGUISHING SYSTEMS
March 1996 PLAN SUBMITTAL REQUIREMENTS FOR KITCHEN HOOD AND DUCT EXTINGUISHING SYSTEMS PLAN REVIEW 1. Submit a completed permit application and a minimum of three sets of shopquality plans and calculations
FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES
FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES Fire and Life-Safety Group (FLS) FLS has organized the following information to act as a guideline/checklist for any inspection, maintenance,
UL 300 Standard. RS 1021 (9/13) 2013 Nationwide Mutual Insurance Company Page 1 of 6 All Rights Reserved
Summary Fire test standard UL 300 has been a major factor in significant changes in how commercial cooking operations are protected from fire. This report looks at the background of UL 300 and changes
Automatic fire-extinguishing systems for commercial cooking
Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and
Commercial Kitchen Fire Safety
Commercial Kitchen Fire Safety Commercial grade kitchens are a common feature found in many churches today, as religious institutions are providing meals for daycares, soup kitchens, meals on wheels and
PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve
INFORMATION BULLETIN Bulletin No. 2005-01 Bureau of Fire Prevention Date: June 10, 2005 Revised: March 8, 2007
SAN FRANCISCO FIRE DEPARTMENT DIVISION OF FIRE PREVENTION & INVESTIGATION INFORMATION BULLETIN Bulletin No. 2005-01 Bureau of Fire Prevention Date: June 10, 2005 Revised: March 8, 2007 SUBJECT: Fire Department
EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS
GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS 1.0 PURPOSE 1.1 To provide an overview of fire extinguisher use
All You Ever Wanted to Know About Fire Extinguishers...
All You Ever Wanted to Know About Fire Extinguishers... There are basically four different types or classes of fire extinguishers, each of which extinguishes specific types of fire. Newer fire extinguishers
Errata has been identified as follows:
2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page
The Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
2014 Limited Plan Submittal Checklist
City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
Code Compliance Guideline: Swimming Pool Chemicals
A publication of Fairfax County, Virginia CODE COMPLIANCE GUIDELINE SWIMMING POOL CHEMICALS AND FIRE SAFETY REQUIREMENTS RELATED TO POOL OPERATIONS This publication outlines the Fire Prevention Code requirements
MONARCH FIRE PROTECTION DISTRICT
MONARCH FIRE PROTECTION DISTRICT 13725 OLIVE BLVD., CHESTERFIELD, MO 63017 314-514-0900, EXT. 309 [email protected] www.monarchfpd.org TENT / BOOTH REQUIREMENTS To help insure the safety, health
Grasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment
Grasshoppers Rugby Football Sports and Social Club The Fire Risk Assessment Revision 1 Dated: 15th February 2013 CONTENTS 1. PREMISES DETAILS 2. PREMISES PLAN 3. HAZARDS 4. HISTORY 5. MITIGATING THE EFFECTS
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
How To Write A Fire Risk Assessment
Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes
Six Monthly Servicing of Fire Extinguisher on Commercial Vessels.
Marine Safety Notice to Industry Number: 34 Date of Issue: 17 January 2012 Six Monthly Servicing of Fire Extinguisher on Commercial Vessels. This Notice to Industry is to clarify the requirements for the
Portable Fire Extinguisher Presentation
Slide 1 Fire Extinguisher Training A requirement of all Clemson University Employees as mandated by OSHA: Portable fire extinguishers. - 1910.157 Welcome to the Clemson University Online Fire Extinguisher
Fire Extinguishers. A Health and Safety Guideline for Your Workplace. Fire Extinguishing Methods. Introduction. Types of Extinguishers
A Health and Safety Guideline for Your Workplace Introduction Fire extinguishers are designed to put out or control small fires. A small fire, if not checked immediately, will soon spread out of control.
Fire Extinguishing Systems -- OSHA Standards 1910.160-1910.163 1
ABE276 Fire Extinguishing Systems -- OSHA Standards 1910.160-1910.163 1 Carol J. Lehtola, Charles M. Brown, and William J. Becker 2 The Impact of Safety on Florida Agriculture Florida agriculture, including
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
Maintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
NATIONAL FIRE ALARM AND SIGNALING CODE
GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
G-704-0 SPECIFICATION: GAS METER AND REGULATOR INSTALLATION REQUIREMENTS. 3 and Gas Yellow Book. REVISIONS: (See ) 1/15/14 5 Years
LAST REVIEW DATE: REVIEW CYCLE: 1/15/14 5 Years SPECIFICATION: TITLE: VOLUME: G-704-0 3 and Gas Yellow Book REVISIONS: (See ) 1) This specification is being issued for the first time. G-704-0 Gas Operations
(1) Acceptable means having been inspected by the Commissioner or his/her representative and approved for the intended usage.
RULES AND REGULATIONS FOR INSTALLATION, INSPECTION, RECHARGING, REPAIRING, SERVICING AND TESTING OF PORTABLE FIRE EXTINGUISHERS OR FIRE SUPPRESSION SYSTEMS CHAPTER 120-3-23 TABLE OF CONTENTS 120-3-23-.01
FIRE CODE INTERPRETATION
FIRE CODE INTERPRETATION February 2014 FCI-14-02 Page 1 of 6 ISSUE: Fixed Fire Suppression & Exhaust Systems Cooking A number of queries from owners, designers and safety codes officers have been received
FIRE RISK ASSESSMENT
The Regulatory Reform (Fire Safety) Order 2005 FIRE RISK ASSESSMENT Employer or other responsible person Name of Premises Address Post Code Telephone N o Name of Assessor(s) Date of Assessment Date of
COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET
COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET Colorado Springs Fire Department Division of the Fire Marshal February 2014 Table of Contents PURPOSE... 3 SCOPE... 3 DEFINITIONS... 3 GUIDELINES...
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
Hydrostatic Testing of Aviation Components
Hydrostatic Testing of Aviation Components 1) What is Cylinder Requalification? a. The process of inspecting and testing pressure cylinders i. Pressure cylinders must be inspected and tested at specific
MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations
REGULATORY REFORM (FIRE SAFETY) ORDER 2005. Fire Risk Assessment. 145 Drury Lane Covent Garden London WC2B 5TA
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 Fire Risk Assessment 145 Drury Lane Covent Garden London WC2B 5TA Annex A (informative) Model pro-forma for documentation of the fire risk assessment for premises
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM
Fire Safety PROCEDURES January 2011
Fire Safety PROCEDURES January 2011 [email protected] Campus Phones EMERGENCY Dial 911 Fire Safety Service is the focal point for the coordinated administration of the University Fire Safety program and
EACH CLASS of fire A, B, C, or D has a different source. Some
Classes of Fires and Types of Extinguishers EACH CLASS of fire A, B, C, or D has a different source. Some principles apply to putting out all fires. However, certain procedures and products are used only
FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT This template has been provided to assist the Responsible Person with the preparation of a Fire Risk Assessment and is not intended for commercial
Notes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems
Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These
Busting the UL 300 Money Myth
WHITE PAPER Busting the UL 300 Money Myth Four Reasons You Can t Wait to Upgrade to a UL 300 Fire Suppression System One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 / www.ansul.com
OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.
1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310
SPECIAL CLAUSES/WARRANTIES THESE ARE OPERATIVE ONLY IF SHOWN IN THE SCHEDULE OR IN AN ENDORSEMENTFORMING PART OF THE SCHEDULE
SPECIAL CLAUSES/WARRANTIES THESE ARE OPERATIVE ONLY IF SHOWN IN THE SCHEDULE OR IN AN ENDORSEMENTFORMING PART OF THE SCHEDULE CL2 - Pipe and Tank Lagging Warranty Underwriters will not be liable for loss
Queen's University Environmental Health and Safety
April, 2009 1 SOP-Chem-08 1.0 Introduction This document is intended as a guide to the Queen s University requirements for handling and storing flammable and combustible material in non-laboratories areas.
Waste Oil Collection / Storage
ENVIRONMENTAL & REGULATORY SERVICES Storage Tank Regulation Section P. O. Box 7837 Madison, Wisconsin 53707-7837 TDD #: (608) 264-8777 http://www.commerce.state.wi.us http://www.wisconsin.gov Jim Doyle,
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
Minnesota State Department of Public Safety
Minnesota State Department of Public Safety 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us Inspection
Georgia State Amendments to the International Fire Code (2012 Edition)
Georgia State Amendments to the International Fire Code (2012 Edition) Georgia Department of Community Affairs Community Development Division 60 Executive Park South, N.E. Atlanta, Georgia 30329-2231 (404)
Fire Extinguishers Water Extinguishers
Water Extinguishers Water extinguishers are suitable for Class A fires caused by combustion of solid materials such as wood, paper, straw, textiles and coal etc. Water additive extinguishers use an environmentally
OREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
NFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
FIRE SAFETY RECORD OF TESTS LOGBOOK
FIRE SAFETY RECORD OF TESTS LOGBOOK PREMISES ADDRESS: Responsible person AN INTRODUCTION TO YOUR LOG BOOK The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person for a premises to
Greater Manchester Fire and Rescue Service
Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
ANSUL. Restaurant Fire Suppression Systems ANSUL UL 300 ANSUL. LOW ph
Restaurant Fire Suppression Systems UL 300 LOW ph The Ansul R-102 System. State-of-the-art in restaurant fire protection. Meeting the fire protection challenge. In 1962, Ansul recognized that there was
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers
Name of Business. Record 1- Approved Food Suppliers List
Record 1- Approved Food Suppliers List Supplier No. Details of Supplier (Name, address, contact details) Product Description Approved Supplier Date approved Corrective Action Reject suppliers that do not
THE GAS UTILITIES S AND THE JAPAN GAS ASSOCIATION S EFFORTS TO IMPROVE SAFETY
THE GAS UTILITIES S AND THE JAPAN GAS ASSOCIATION S EFFORTS TO IMPROVE SAFETY Kunihiro Hara Assistant Manager of Safety Technology Sec.,Gas Technology Dept., The Japan Gas Association 1. City Gas Safety
Zurich Small Business - Restaurant Supplemental Information Bailey-Yorkshire Insurance Associates 781-362-1000
General Information 1) Named Insured: 2) Quote Number Effective Date: 3) Other Named Insureds: Relationship: 4) Website Address: 5) Are there other Commercial Policies insured or pending with Zurich Small
Permit Application for Mobile Food Truck
Date Received / / Office Use Only By: Date Approved / / By: Comp # Element Type: Entered By: Annual Permit Fee: Check #: Receipt #: AMANDA #: Permit Application for Mobile Food Truck NOTE: This application
EXTINGUISHER. The purpose of this module is to sensitize firefighters on the subject of extinguishers.
EXTINGUISHER INTRODUCTION Fire extinguishers are essential fire suppression tools that firefighters us in the initial stage of a fire and against this background, it is important to be knowledgeable of
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS
Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
Building Permit, Fire Inspection and Operating Permit Fee Schedule
Chenango County Code Enforcement Building Permit, Fire Inspection and Operating Permit Fee Schedule Building Permit Exceptions: Buildings being used solely for the purpose of agriculture. As per Agricultural,
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
MOBILE FOOD A GUIDE TO PERMITTING IN ALBUQUERQUE
MOBILE FOOD A GUIDE TO PERMITTING IN ALBUQUERQUE PAVE THE WAY FOR SUCCESS WHAT YOU NEED TO KNOW TO PERMIT AND OPERATE A MOBILE FOOD UNIT IN ALBUQERQUE. PERMITS AND FEES Mobile food units are required to
Fire Safety Risk Assessment
1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 23.00: ISSUANCE OF CERTIFICATES FOR THE SERVICING OF PORTABLE FIRE EXTINGUISHERS AND THE INSTALLING AND SERVICING OF FIXED FIRE EXTINGUISHING SYSTEMS Section 23.01: Purpose 23.02: Applicability
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
The terms hazard and risk are often used, which we define as the following:
Fire Safety Last updated in October 2010 This information sheet aims to give safety reps a basic understanding of fire safety and fire risk assessments under the current law. More detailed information
Section III Hazardous Materials Management
Section III Hazardous Materials Management This section of the Everyday Hazmat User s Training Guide covers various types of hazardous materials commonly found in the USDA Forest Service. Federal regulations
MAINTENANCE OF SMALL WATER SUPPLY, SANITATION AND IRRIGATION SCHEMES
MAINTENANCE OF SMALL WATER SUPPLY, SANITATION AND IRRIGATION SCHEMES John van Rijn INDEVELOPMENT MAINTENANCE OF SMALL WATER SUPPLY, SANITATION AND IRRIGATION SCHEMES Any part of this publication may be
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
PACKAGED FIRE TUBE BOILER
SAMPLE PREVENTIVE MAINTENANCE MANUAL PACKAGED FIRE TUBE BOILER 1 CONTENTS Introduction 1 Intention 2 Organisational setup 3 Boiler Fault reporting & Repair progression 4 Preventive Maintenance Schedules
Restaurant & café guide
'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers
OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES
OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES Reference: National Fire Protection Association (NFPA) Pamphlet No. 58 Liquefied Petroleum Gas Code, 2001, Chapter 11 Type of Facility: Petroleum
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
Formal Interpretation NFPA 30. Flammable and Combustible Liquids Code. 2012 Edition
Reference: 1.1, Scope F.I. 84-4 Background: Tank trailers and semi-trailers are loaded with flammable or combustible liquid and moved to a storage yard. There, the tank vehicles may be kept for days, weeks,
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
HOT WORK PERMIT PROCEDURES
COLUMBIA UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY HOT WORK PERMIT PROCEDURES COLUMBIA UNIVERSITY MEDICAL CENTER February 2010 1 TABLE OF CONTENTS A. PURPOSE 3 B. SCOPE 3 C. POLICIES AND PROCEDURES 3-4
CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance
CIBSE Guide M: Maintenance engineering and management compliance legislation and guidance Types of System/Plant Action required Frequency by Type of Fire and Smoke Fire extinguishers Discharge (not CO
SUBCHAPTER 17 FIRE ALARM, DETECTION AND EXTINGUISHING EQUIPMENT
[Sub-Art. or Sec.]* SUBCHAPTER 17 FIRE ALARM, DETECTION AND EXTINGUISHING EQUIPMENT TABLE OF CONTENTS Art. or Sec.** [1700.0] Art. 1 General [1700.1] 923 Scope [1700.2] 924 Standards [1700.3] 925 Definitions
An inventory of hazardous materials used in your workplace will prove useful.
Introduction Fire Protection is an organized approach designed to prevent fires. In the event of a fire, a fire protection program will help prevent or minimize personal injuries, losses, and harm to the
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
Fire Safety Log Book
Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton
The following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
Restaurant and Café Risk Management Guide. Don t Risk It!
property & liability Restaurant and Café Risk Management Guide Don t Risk It! About Lumley Insurance Lumley Insurance has extensive experience in restaurant insurance and risk management. This experience
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression