EMERGENCY LIGHTING DESIGN GUIDE
|
|
|
- Amberly Harmon
- 9 years ago
- Views:
Transcription
1 LEGAL REQUIREMENTS The main reason for installing an emergency lighting system is to enable the building to meet fire safety legislation in a way that is visually acceptable and meets the user s needs for ease of operation and maintenance. Consequently it is important to establish all the relevant legal requirements for emergency lighting and fire alarm systems before commencing the design these should ideally be agreed between the system designer, user, fire authority, building control officer and system installer. The main legislative requirements are: THE BUILDING REGULATIONS 2000 These regulations detail the design and construction characteristics of a building. Approved Document B details the fire safety requirements for new buildings and the major refurbishment of eisting premises. Table 9 of this document shows the locations that must be provided with emergency lighting. It now defines that in addition to escape routes, all open areas larger than 60m 2 must be illuminated in the event of the failure of the normal lighting supply. It also clarifies that emergency lighting is needed for all parts of schools that either do not have natural light or are used outside normal school hours. The regulations require that systems comply with BS , the code of practice for emergency lighting. THE FIRE PRECAUTIONS (WORKPLACE) REGULATIONS 1997 This directive controls the way that the building will be used and the equipment and systems needed to safeguard the occupants. The legal requirement is that - Emergency routes and eits requiring illumination must be provided with emergency lighting of adequate intensity in case the lighting fails. The law is eplained and the rules for compliance are given in a joint Home Office and Health & Safety Eecutive document - FIRE SAFETY - An employer s guide. Main points from the guide are: The employer has legal responsibility for compliance Although the legislation uses and modifies the Fire Precautions Act 1971, it now covers all premises where people are employed Any site with five or more employees must keep a formal record of Fire Risk Assessment. This should evaluate the site and detail the measures taken to ensure the safety of the premises If the premises already have a fire certificate to the latest standards the employer still needs to provide a risk assessment, but it is unlikely that they will need any additional equipment. If however the fire certificate was issued prior to 1999, when BS was revised, the risk assessment needs to check whether improvements are needed to meet the latest standard 441 Step 1 Identify fire hazards - such as sources of ignition, fuel or work processes Step 2 Identify the location of people at risk in the case of fire Step 3 Step 4 Step 5 Step 6 Evaluate the risks to check whether eisting fire safety measures are adequate, including: - Control of ignition and fuel sources - Fire detection and warning - Means of escape and the provision of emergency lighting - Means of fighting fire - Maintenance and testing of fire precautions - Fire safety training of employees Carry out any improvements needed Record findings and action taken Keep the assessment under review - revise provisions if the situation changes
2 442 THE FIRE PRECAUTIONS (WORKPLACE) REGULATIONS 1997 (cont d) From this directive there are a number of points that are of major importance to emergency lighting system design. The evaluation of areas with a fire risk assists when deciding which areas need protection, e.g. a school chemical laboratory may be smaller than 60m 2 but still need emergency lighting, as combustible materials and sources of ignition would be present The assessment of the location of employees and any visitors to the site assist in determining the most appropriate escape routes The guidance to the directive gives detailed requirements for the suitability of escape routes and calls for the installation of emergency lighting to be in accordance with BS It recommends that advice on the installation should be given by a competent person who specialises in emergency lighting systems Continued maintenance and testing must be correctly carried out, to comply with the directive The equipment used must be capable of being demonstrated as of adequate quality. Compliance with the appropriate British Standard, or other approved third party scheme, gives evidence of this. The standard for luminaires is BS EN ICEL 1001 registration endorses the spacing data of these luminaires. The standard for central battery systems is BS EN Note: When the premises are being assessed for risk, shortcomings in other areas of fire protection can be compensated for by improved levels of emergency lighting and fire alarms. Compliance with BS5266-1:1999 is deemed to comply with these requirements. EMERGENCY LIGHTING - SYSTEM DESIGN This section provides guidance on system design to meet BS 5266 Parts 1 and 7: 1999 and so achieve compliance with legislation DESIGN OBJECTIVE BS 5266, when referring to the provision of Escape Lighting in section 4.2, requires that when the supply to all or part of the normal lighting in occupied premises fails, escape lighting is required to fulfil the following function: (a) To indicate clearly and unambiguously the escape routes. (b) To provide illumination along such routes to allow safe movement towards and through the eits provided. (c) To ensure that fire alarm call points and fire fighting equipment provided along escape routes can be readily located. (d) To permit operations concerned with safety measures. BS recommends that discussions should be held prior to commencing the design, to establish the areas to be covered, the method of operation, the testing regime and the most suitable type of system. These discussions should include the owner or occupier of the premises, the system designer, the installer, the supplier of the equipment and the fire authority. Note: BS5266 will be revised during 2004 following the publication of EN For up to date information visit our website at Alternatively visit the British Standards Institute website, at THE HEALTH AND SAFETY (SAFETY SIGNS AND SIGNALS) REGULATIONS 1996 This regulation requires the adequate provision of signs protected by emergency lighting. It details that signs should be located at all final eits and also on the escape routes at any location where the route may be in doubt. OTHER REQUIREMENTS In addition to fire safety legislation, some workplaces require a licence from the Local Authority, including theatres and cinemas, sport stadiums and premises for public entertainment, music, dancing, gambling and the sale of alcohol. Other premises must be registered with the Local Authority and be inspected by the Fire Authority, including nursing homes, children's homes, residential care homes and independent schools. Both licensed and registered premises have to pass a fire inspection to confirm that they have systems complying with BS for the emergency lighting and BS 5839 for fire equipment. Records of a system are now essential to maintain the validity of approvals and licences.
3 STAGE 1 LOCATE LUMINAIRES AT MANDATORY POINTS OF EMPHASIS Initial design is conducted by situating luminaires to reveal specific hazards and highlight safety equipment and signs, in addition to providing illumination to assist safe travel along the escape route. This should be performed regardless of whether it is an emergency escape route or an open (anti-panic) area. Only when this is accomplished should the type of luminaire or its light output be considered. BS5266 Pt 7: 1999 requires that the luminaires sited at points of emphasis must comply with BS EN Specific locations where a luminaire must be provided are: 443 At each eit door All safety eit signs Outside and near each final eit Near stairs so that each tread receives direct light Near any other change of floor level At each change of direction At each intersection of corridors Note - the term near means within 2 metres measured horizontally Near each first aid post Near each piece of fire fighting equipment and call point
4 STAGE 2 ENSURE THAT EXIT SIGNS ARE OF CORRECT FORMAT AND SIZE Section 4.1 of BS5266 Pt 7 states that Signs which are provided at all eits intended to be used in an emergency and along escape routes shall be illuminated to indicate unambiguously the route of escape to a point of safety. Where direct sight of an emergency eit is not possible, an illuminated directional sign (or series of signs) shall be provided to assist progression towards the emergency eit. 444 Sign formats should not be mied - BS2560: 1975 Old-style signs now obsolete. Should have been replaced by December BS 5499 Pt 1 Signs are still acceptable, if they are already in the building - European Signs Directive Format This came into force on 1st April 1996, under The Signs Directive If there is any doubt as to the most appropriate format of sign, guidance should be obtained from the local Fire Authority. EXIT EXIT Maimum viewing distances For all format of safety signs the maimum viewing distances and luminance conditions are given in BS 5266 pt7/en 1838 Signs can be either internally illuminated, such as eit boes or edge lit emergency luminaires with a screened sign that have a controlled illuminance, or painted signs with an eternal emergency light illuminating them. Maimum viewing distances are: Internally illuminated signs the panel height Eternally illuminated signs the panel height h <200 h h <100 h Illumination requirements The sign must conform to the colours of ISO 3864, which defines that eit and first aid signs must be white with green as the contrast colour. The ratio of luminance of the white colour to the green colour must be between 5:1 and 15:1. The minimum luminance of any 10mm patch area on the sign must be greater than 2cd/m 2 and the ratio of maimum to minimum luminance shall be less than 10:1 for either colour contrast of the colours must be between 5:1 and 15:1 min luminance = 2cd/m ratio of luminance shall be less than 10:1 for either colour 2 Note: Internally illuminated eit signs are pre-tested to ensure they meet these requirements, provided that they comply with EN If the sign is designed to be eternally illuminated, considerable care must be taken by the system designer to see that these conditions are met. Even though an emergency luminaire must be sited within 2 metres from the sign (see stage 1) calculations should still be made to check that the sign is adequately illuminated.
5 STAGE 3 LOCATE LUMINAIRES AT THE FOLLOWING ESSENTIAL AREAS IN THE BUILDINGS Locate luminaires at the following essential areas in the buildings. These locations are not part of the escape route but because of their risk they require protection by emergency lighting. a) Lift cars - although only in eceptional circumstances will they be part of the escape route, do present a problem in that the public may be trapped in them in the event of a supply failure. c) Escalators - to enable users to get off them safely. e) Covered car parks - the normal pedestrian routes should be provided with non-maintained luminaires of at least 1 hour duration. 445 b) Toilets - all toilets for the disabled and facilities eceeding 8m 2 floor area or without borrowed lights. d) Motor generator, control or plant rooms - require battery supplied emergency lighting to assist any maintenance or operating personnel in the event of failure.
6 STAGE 4 ESCAPE ROUTE LIGHTING When the points of emphasis have been covered, it is essential to provide any additional luminaires to ensure that minimum illuminance levels are met to enable the routes to be used safely. In addition, every compartment on the escape route must have at least two luminaires, to provide some light in the event of luminaire failure. Light Level Requirements BS 5266 Pt 7: 1999 (EN1838) calls for a minimum of 1 lu anywhere on the centre line of the escape route for normal risks. A uniformity ratio of 40:1 maimum to minimum must not be eceeded. This illuminance must be provided must be provided for the full duration and life of the system. 50% of the illuminance must be available within 5 seconds and the full value within 60 seconds of supply failure. 446 Note: The UK has an A deviation which continues to allow a 0.2 lu minimum value for routes that will be permanently unobstructed. It should be noted that this puts a heavy burden on the user to ensure routes are kept clear even in an emergency. For this reason it is recommended that the 1 lu level should always be used. Photometric Design Emergency Escape Routes The use of spacing tables or a suitable computer program provides the information to determine whether luminaires are needed in addition to those for the points of emphasis (see data section), to provide the minimum required level of illumination on the escape routes. To ensure that the design will meet the required levels at all times the data is de-rated, as required by the standard, to cover the following factors: i. Reduction in light as the battery voltage reduces during discharge. ii. Aging of lamps in maintained circuits iii. The effects of dirt (Spacing tables use a figure of 80%). PHOTOMETRIC DATA Britelite Escape route 2m wide Open (anti-panic) area 1 lu min 0.5 lu min Luminaire Mounting Lu level type height (m) directly under Self-contained NM M Eample - luminaire spacing along escape route ceiling 2.5m ceiling 2.5m 11m 22m 11m 11m 11m Locate luminaires at mandatory Points of emphasis Add additional luminaire to achieve 1 lu minimum
7 STAGE 5 OPEN (ANTI-PANIC) CORE AREAS Areas larger than 60m 2, open areas with an escape route passing through them, or hazards identified by the building risk assessment all require emergency lighting. The current standard is easy to design for and to verify, promoting systems that provide good uniformity rather than ones that use a few large output luminaires. Light Level Requirements BS5266 Pt 7/EN calls for 0.5 lu minimum of the empty core area, which ecludes a border of 0.5m of the perimeter of the area. Spacing tables or a suitable computer program provide simple and accurate data that can easily be used. The spacing tables for 0.5 lu are de-rated on the same basis as those for escape routes. They can also be used as a guide for initial selection of the location of luminaires when using a computer program If using standard mains luminaires fitted with an emergency conversion kit, typical data is shown on pages The data details the polar distribution for common types of luminaires, from which a suitable match should be selected. The factors considered should be the shape of the polar curve and the scale, which is shown by the nadir intensity. Alternatively, a computer program can be used and the light outputs of the appropriate kit can be used with the actual distribution data of the luminaire chosen. Spacing data Specific data is available for self-contained dedicated emergency luminaires. This can be found on each of the individual product entries in this catalogue and repeated in the section after this design guide. 447 Luminaire spacing in open (anti-panic) core areas 0.5 metre border (core area ecludes a border of 0.5m of the perimeter of the area) Minimum points - at which 0.5 lu is obtained
8 448 STAGE 6 HIGH RISK TASK AREA LIGHTING Areas of high physical risk, or the control rooms of dangerous plant and production lines, need emergency lighting to enable them to be shut down safely. BS5266 Part 1: 1999 defines that emergency lighting should provide 10% of the normal lighting level at the hazard, with a minimum of 15 Lu. (In practice this minimum is unlikely ever to be a problem, as it would only be valid if the risk area had a normal illumination level less than 150 lu). DESIGN PROCEDURES Reaching the light levels needed would normally be achieved by using a conversion of the normal luminaire, or by using a tungsten projector unit. If conversion units are selected, a direct ratio can be obtained by the Ballast Lumen Factor (BLF). i.e. to achieve 10% of normal use either: - Emergency units with a BLF of 10% are needed for each fitting in the area - Emergency units with a BLF of 20% are needed for every other fitting - Emergency units with a BLF of 100% are needed for one in 10 fittings Care is needed to ensure that a reasonably uniform distribution is achieved by whatever combination of luminaire and conversion kit used. If tungsten projector units are selected, a co-efficient of utilisation calculation has to be performed for the required value. STAGE 7 CONTROL Non-maintained luminaires must be activated by failure of supply to the normal lighting. They must therefore be connected an unswitched live taken from the local normal lighting final circuit. Once the design has been completed it becomes apparent that the performance of the luminaire depends as much on the light distribution as it does the light output available. Consequently it becomes essential that luminaire types specified for a particular design do not get changed without a re-appraisal of the photometric design. L N Normal lighting Emergency lighting TESTING AND LOG BOOK The Fire Precautions (Workplace) Regulations 1997 require that appropriate testing is performed to maintain compliance of the system. The system should include adequate facilities for testing and recording the system condition. These need to be appropriate for the specific site and should be considered as part of the system design. Discussions with the user or system designer should identify: - The calibre and reliability of staff available to do the testing - The level of difficulty in performing the test - If discharge tests need to be done outside normal working hours, or phased so only alternate luminaires are tested in buildings that are permanently occupied The testing requirements in the code of practice are: Function test All emergency luminaires should be tested be breaking the supply to them and checking that they operate satisfactorily. The supply must then be restored and the charging indicators must be seen to be operating correctly. This test must be performed at least once per month and the results logged Discharge test The luminaires must be tested for their full rated duration period and checked for satisfactory operation. The supply must then be restored and the charging indicators rechecked. This test must be performed at least annually and the results logged Note: BS : 1999 allows a one hour test to be performed as an alternative every si months for the first 3 years of the system, but the guidance document to the Fire Precaution Regulations calls for the annual test at all stages of equipment life.
9 STAGE 7 (cont d) MANUAL TESTING If manual testing is utilised, the following points should be considered: - Is a single switch to be used? Unless the whole building is to be switched off, a separate switch should be used for each final circuit. As the feed to non-maintained circuits must be taken from the switch this will probably mean that the building will have to be walked around twice, once to check the luminaires and once to check that they are recharging - Are luminaires to be individually switched? In practice, only a single walk around the building will be needed. However, the test switches could spoil the décor of the building and they must be of a type that is tamper proof. After the tests, the performance of the luminaires must be logged. COMMISSIONING CERTIFICATE BS5266 Pt 1: 1999 and the European Standard both require written declarations of compliance to be available on site for inspection. These consist of: 1. Installation quality. IEE regulations must have been conformed with and nonmaintained fittings fed from the final circuit of the normal lighting in each, as required in BS Photometric performance. Evidence of compliance with light levels has to be supplied by the system designer. Photometric tests for Cooper Lighting and Security luminaires are performed at BSI and spacing data is registered by the ICEL scheme. Therefore copies of the spacing data in this catalogue provide the verification required. 3. Declaration of a satisfactory test of operation. A log of all system tests and results must be maintained. System log books, with commissioning forms, testing forms and instructions are available from Cooper Lighting and Security. MAINTENANCE Finally, to ensure that the system remains at full operational status, essential servicing should be defined. This normally would be performed as part of the testing routine, but in the case of consumable items such as replacement lamps, spares should be provided for immediate use. AUTOMATIC TEST SYSTEMS If the costs of an engineer time and the disruption caused by manual testing are ecessive, automatic systems should be considered. Different formats are available to match particular site requirements. Cooper Lighting and Security offer two alternative testing systems: EasiCheck Particularly suited to medium to large sized installations, EasiCheck is a versatile addressable emergency lighting system that uses a central control panel to perform automatic test schedules, initiate manual tests and download event logs and test reports. It is available for use with both self-contained luminaires and central power systems. EasiCheck continuously monitors the emergency circuit, reporting faults as soon as they occur. Up to 63 panels can be networked together, ensuring EasiCheck can be utilised in the largest of projects of up to 15,750 emergency luminaires. It also has advanced software options for PC monitoring and control. EasiCheck Panel Intellem Programmer Intellem Designed for use with self-contained emergency luminaires, Intellem is a stand alone self-test system for small to medium sized installations. Intellem is available in two options. In the basic format, Self Check, the testing module self calibrates and carries out testing at predetermined intervals. Faults are precisely reported by an audible alarm and the flashing sequence of the LED indicator. The enhanced Intellem Infra-Red option adds the benefits of fleible test set up, luminaire status interrogation and initiation of manual tests, all via a hand held programmer. Both options also continuously monitor the emergency luminaires, reporting faults as soon as they occur. 449
10 EXAMPLE OF SYSTEM DESIGN i a,b,c,f&k m Acid bath g Plant room b Workshop (iv) b c&h h&f d Office (iii) h Office (i) 2 Toilet Escalator b&e 3 Office (ii) 1 Lift e&h e&h Lobby a,b & c i d
11 EXAMPLE OF SYSTEM DESIGN Stage 1 Locate luminaires at points of emphasis on escape route a At each eit door b To illuminate eit and safety signs c Near call points (some covered by a.) d Near each staircase e Change of direction (covered by b.) f Near fire fighting equipment (covered by a.) g Change of floor level h Near intersection of escape routes i Outside final eits k Near first aid points Stage 2 Eit sign location is covered by Stage 1, but it is important to check that maimum viewing distances are not eceeded and that if the normal lighting is dimmed, e.g. in cinemas, the eit signs must be permanently illuminated while the building is occupied (maintained lighting). Stage 3 Other areas, which require emergency lighting but are not on the escape route area. 1 Lift car 2 Toilet (above 8m 2 floor area) 3 Escalators 4 Plant room Stage 4 Check minimum illuminance levels on the escape routes. After selecting a suitable luminaire, e.g. Britelite, consulting the spacing table shows the number of fittings needed to provide a minimum of 1 lu on the centre line of the escape routes. Stage 5 Anti-panic open areas () apply to any areas over 60m 2 floor area, or that have an escape route passing through them. (i) Office over 60m 2-3 Britelite (ii) Office under 60m 2 - no requirement (iii) Under 60m 2, but part of escape route from office (ii) - 2 Britelite fittings, either as compartment of escape route or an open anti-panic area (iv) Workshop 4m high - 3 Britelite + 1 DQX - 5 cell conversion unit for high risk (m) or 4 DQX - 5 cell conversion units (Use of conversion units is dependent on suitable mains luminaires being used). Stage 6 High risk lighting requirement for an acid bath (m) is included in the design for stage 5. If a conversion of a mains luminaire is not suitable, a high power tungsten projector, such as Beamlite could be used instead. WIRING INSTALLATION The wiring of emergency luminaires should generally be in accordance with normal wiring practice (I.E.E. Wiring Regulations), statutory requirements applicable to the type of building, local by-laws and regulations. The supply for self contained luminaires should be taken from the unswitched local light source Cabling used when installing self-contained emergency luminaires should be of a similar type to that used for the normal mains light. In the event of a fire, if the cabling used for the emergency luminaires has greater protection, there may be a chance of the normal lighting failing and the emergency lighting remaining in the normal mode (i.e. inoperative). Hence it is recommended that self-contained emergency luminaires are wired in PVC insulated cable. The supply to self-contained luminaires should be such as to prevent unauthorised disconnection, but should incorporate suitable means for simulating a mains failure for test purposes. The source of supply should be from the same local fuse as the normal lighting, so that in the event of a fuse failure causing the normal lighting to be etinguished, the emergency lighting is brought into operation in the same locality. Non - maintained installation L N mains lighting fuse tamper proof test switch Maintained or sustained installation L N mains lighting fuse tamper proof test switch Wiring details maintained lighting control switch N L N L1 L2 to mains lighting to additional emergency luminaires non-maintained emergency luminaire to mains lighting to additional emergency luminaires maintained emergency luminaire 451
Guidance for Electrical Contractors on Emergency Lighting Legislation
Guidance for Electrical Contractors on Emergency Lighting Legislation Issued in the interests of safety by in conjunction with the Industry Committee for Emergency Lighting ECA / ICEL Guidance For Electrical
Emergency Lighting Practices in the UAE. Richard Caple MSc MSLL Lighting Applications Manager SLL Vice President
Emergency Lighting Practices in the UAE Richard Caple MSc MSLL Lighting Applications Manager SLL Vice President Agenda UAE emergency lighting requirements Emergency systems and luminaires Emergency lighting
EMERGENCY LIGHTING - UCL GENERAL DESIGN GUIDANCE
Fire Safety Technical Guide EMERGENCY LIGHTING - UCL GENERAL DESIGN GUIDANCE Reference: A. British Standard 5266-1 Emergency Lighting - Code of Practice for the emergency lighting of premises; B. BS 5266-7
Emergency Lighting Guide
FROM SOURCE TO SITE Emergency Lighting Guide July 2013 Head Office 21B Cranborne Industrial Estate Cranborne Road Potters Bar Hertfordshire EN6 3JN Orlight Design Studio & Showroom The Plaza 535 Kings
ELECTRICIAN S GUIDE TO EMERGENCY LIGHTING. Fully updated to BS 5266-1:2011. electrician s guide
ELECTRICIAN S GUIDE TO EMERGENCY LIGHTING Fully updated to BS 5266-1:2011 electrician s guide Published by The Institution of Engineering and Technology, London, United Kingdom The Institution of Engineering
A Guide To BS5266. The design, installation and wiring of emergency lighting systems
A Guide To BS5266 The design, installation and wiring of emergency lighting systems 2 Extra Low Voltage LED Technology Low Maintenance Intelligent Simple Installation Graphics Software Hochiki Europe (UK)
Fire Safety Log Book
Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton
FIRE SAFETY PRECAUTIONS
FIRE SAFETY PRECAUTIONS LOG BOOK PLEASE KEEP AVAILABLE 1 Business Name Premises Information Building / Unit Number Property Name Road: (Address Line 1) (Address Line 2) Locality: Town: Post Code: Name
How To Write A Fire Risk Assessment
Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes
Fire Safety Requirements for Child Care Centre
Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,
Greater Manchester Fire and Rescue Service
Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY
FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie
FIRE SAFETY REGISTER Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie 1 CONTENTS Section Title Page 1.0 Introduction 3 2.0 Guidance for the completion
FIRE RISK ASSESSMENT PRINCIPLES A GUIDE FOR LICENSED PREMISES
NFG27 FIRE RISK ASSESSMENT PRINCIPLES A GUIDE FOR LICENSED PREMISES The Workplace Fire Precautions Legislation brings together existing Health & Safety and Fire Legislation to form a set of dedicated Fire
BS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS
1 FIRE ALARMS IN DWELLINGS By John Ware IN THE UK around 80% of all fire deaths and injuries occur in dwellings, a total of 450 to 500 deaths and 14,000 injuries per annum, according to BS 5839-6: 2004.
AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839
AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What
Fire precautions in dwellings. Private sector housing Providing homes building communities
Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared
UPP Residential Services Fire Risk Assessment
UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This
Emergency Voice Communication Systems
Emergency Voice Communication Systems Frequently sked uestions What is an Emergency Voice Communication System? Emergency Voice Communication System is the generic technical term to cover Fire Fighting
GENERAL FIRE SAFETY TERMS & DEFINITIONS
UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:
I.S. 3218 :2013 Fire Detection & Alarm Systems
I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System
Guidance Document on Fire Safety Signs and Notices FIA Guidance for the Fire Protection Industry
Guidance Document on Fire Safety Signs and Notices FIA Guidance for the Fire Protection Industry This Guidance Note is intended as a general guidance and is not a substitute for detailed advice in specific
I.S. 3218 :2013 Fire Detection & Alarm Systems
I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System
5-8.1.4* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness.
NFPA 101 Life Safety Code Section 5-8 Illumination of Means of Egress 5-8.1 General. 5-8.1* Illumination of means of egress shall be provided in accordance with this section for every building and structure
FIRE SAFETY RECORD OF TESTS LOGBOOK
FIRE SAFETY RECORD OF TESTS LOGBOOK PREMISES ADDRESS: Responsible person AN INTRODUCTION TO YOUR LOG BOOK The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person for a premises to
NEW FIRE SAFETY LEGISLATION
NEW FIRE SAFETY LEGISLATION The Fire and Rescue Services (Northern Ireland) Order 2006 The Fire Safety Regulations (Northern Ireland) 2010 Fire Safety legislation changed A SHORT GUIDE TO MAKING YOUR PREMISES
Standard the the Raising
Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction
Section 6 Fire Detection and Alarm Systems Russell Porteous Chief Executive Officer Firewize Services
Section 6 Fire Detection and Alarm Systems Russell Porteous Chief Executive Officer Firewize Services General Information Section 6 of AS1851-2012 covers: Fire Detection and Alarms Systems Electrical Detection
FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS
Fire Safety Technical Guide FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS 1.0. Introduction 1.1. Furniture and furnishings may significantly increase fire spread in rooms and those circulation spaces,
HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS
ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS USER MANUAL USER MANUAL ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS INTRODUCTION The (HA-841K) is a complete
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers
FIRE DETECTION AND ALARM SYSTEMS
HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some
Recommendations to improve the safety of existing lifts
Recommendations to improve the safety of existing lifts Lift & Escalator Industry Association Lift Safety an introduction Lifts are amongst the very few modes of transport available for continuous unsupervised
GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA)
GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) Chapter 1 : Definitions clause 1.2.10 : circulation space OLD CLAUSE A space mainly used as means of access between a room or protected shaft
Fire Safety Risk Assessment Checklist for Residential Care Premises
Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or
IFE Level 4 Certificate in Fire Science and Fire Safety (HL)
IFE Level 4 Certificate in Fire Science and Fire Safety (HL) Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the prevention and detection of fire in premises and
Fire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
Fire Alarm system Installation Guide
Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this
LETTINGS POLICY. Claverham Community College. Adopted by the Governing Body on. Date. Signed
LETTINGS POLICY Claverham Community College Adopted by the Governing Body on Date Signed Claverham Community College Lettings Policy Contents Conditions governing the hiring of School Premises 1. General
Grasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment
Grasshoppers Rugby Football Sports and Social Club The Fire Risk Assessment Revision 1 Dated: 15th February 2013 CONTENTS 1. PREMISES DETAILS 2. PREMISES PLAN 3. HAZARDS 4. HISTORY 5. MITIGATING THE EFFECTS
USER GUIDE SERIES 4250 AUDIO ALARM CONFIRMATION SYSTEM CONTROL UNIT
USER GUIDE SERIES 4250 AUDIO ALARM CONFIRMATION SYSTEM CONTROL UNIT CONTENTS Page INTRODUCTION... 2 Security conditions... 3 Full Set (Fully armed)... 3 Part Set (Partially armed)... 3 Unset (Disarmed)...
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed
Service Level Agreement (SLA)
Hertford College, Oxford Service Level Agreement (SLA) For Maintenance, Risk Management, and Domestic Accommodation Services At Hertford College, its residential annexes and non- residential properties
The terms hazard and risk are often used, which we define as the following:
Fire Safety Last updated in October 2010 This information sheet aims to give safety reps a basic understanding of fire safety and fire risk assessments under the current law. More detailed information
Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book:
Fire Safety Log Book Premises Name: Premises Address: Date From: Date To: Location of Log Book: CONTENTS PART 1 FIRE SAFETY ADVICE 1 PART 2 FIRE PRECAUTIONS 2 Section 1 Guidance on Fire Risks and Preventative
REGULATORY REFORM (FIRE SAFETY) ORDER 2005. Fire Risk Assessment. 145 Drury Lane Covent Garden London WC2B 5TA
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 Fire Risk Assessment 145 Drury Lane Covent Garden London WC2B 5TA Annex A (informative) Model pro-forma for documentation of the fire risk assessment for premises
CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1
CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL user manual & log book Approved Document No. DFU7001020 Rev 1 CONTENTS Safety...3 Important information regarding the safe use of this fire alarm panel
SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS
Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses
1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS
Fire Risk assessment 1.0 APPOINTMENTS 1.1 Responsible Person. In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO) the School s Head, Mrs J M Miles is appointed as the Responsible Person
Workplace Health, Safety & Welfare
Relevant Legislation Workplace (Health, Safety and Welfare) Regulations 1992 Construction (Design & Management) Regulations 2015 Provision & Use of Work Equipment Regulations 1998 (PUWER) Lifting Operations
ACCESS AUDIT OF WESTPORT HOUSE
ACCESS AUDIT OF WESTPORT HOUSE Large sign on the highway to indicate the entrance to Purbeck District Council Large and wide entrance Entrance showing sign for opening times Entrance sign Main entrance
This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink.
1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink. The unit will start automatically. Please pay particular
SECURIT 800L+ CONTROL PANEL
USER MANUAL SECURIT 800L+ CONTROL PANEL COMPANY PROFILE IntelliSense have been successfully making security products for over 20 years and lead the security industry throughout the world with many innovative
Compliance Schedules and Building Warrant of Fitness
Compliance Schedules and Building Warrant of Fitness Purpose of this guidance information The purpose of this guidance information is to help building owners and managers of commercial, industrial or communal
Overview of Fire Alarm Systems and Maintenance
Overview of Fire Alarm Systems and Maintenance By Mr. David Goh Vice President Fire Safety Managers Association Convener of Working Group for CP 10 : 2005 Er. Matthew Kwek Committee Member Fire Safety
Conventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
1. Description. 2. List of Accessories included A B C F G H
1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin. The unit will start automatically. Please pay particular attention to the following: Possible danger to
Fire Safety logbook
Raising Awareness Reducing Risk CHANGE THIS TITLE TO COMPANY NAME Property / Business Name Address Line 1 This Log book should be kept up to date and be made available for inspection by the Fire Authority
Industrial Linergy LED
Eaton s commitment to supplying energy saving innovative products is the driving force behind. follows in the tradition of highly efficient large space luminaires which have the performance and flexibility
The Electrical Safety Regulation (pre and post 1 January 2014)
The Electrical Safety Regulation (pre and post 1 January 2014) The following table provides an overview comparison between the Electrical Safety Regulation 2002 (the ESR 2002) current as at 1 July 2013
Wireless Home Security Alarm System AM 500
Wireless Home Security Alarm System AM 500 12 MONTH GUARANTEE Installation & Operating Instructions INTRODUCTION The AM500 is a simple self-contained alarm system. It protects the home by sounding a siren
9452/9453 Installation and User Guide
9452/9453 Installation and User Guide Compatible Equipment 9425 Remote Keypad 9040 Internal Sounder 660 Speech Communicator 8440 4-Channel Minicom 496330 Issue 1 1 of 10 9452/3 Introduction The 9452 and
FIRE RISK ASSESSMENT WORKED EXAMPLE
FIRE RISK ASSESSMENT WORKED EXAMPLE 1 PREMISES PARTICULARS BE-INT05 Premises Name S M Enterprises Address Small Place Medium Road Anywhere Tel no: 01234 567890 Date of Risk Assessment 1 st July 2011 Use
FIRE RISK ASSESSMENT SW13 0HA
FIRE RISK ASSESSMENT at Carmichael Court Grove Road London SW13 0HA ON BEHALF OF Farrar Property Management Date of assessment: 14/01/2013 Recommended review date: January 2015 CONTENTS 1.0 INTRODUCTION
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings
Building Control Householder Guidance Leaflet No. 29 Fire detection in dwellings This leaflet is one of a series produced by the Hertfordshire Building Control Technical Forum GUIDANCE NOTE FOR HOME OWNERS
1.1.4 The findings from Fire Risk Assessment must be incorporated into the FRAMS Action Plan to manage fire safety at each premise.
Fire Safety Policy 1.1 Policy Statement of Intent 1.1.1 Under the current UK Legislation (In England and Wales, the Regulatory Reform (Fire Safety) Order 2005, Fire (Scotland) Act 2005, Fire and Rescue
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone
16551 EMERGENCY LIGHTING SYSTEMS. C. Refer to Cornell Design & Construction Standard 16620 for Emergency Power Systems.
16551 EMERGENCY LIGHTING SYSTEMS PART 1: GENERAL 1.01 SUMMARY A. This Section provides the University guidelines for the installation of Emergency Lighting Systems. B. This standard was developed primarily
CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY
CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY This policy was written in July 2014 and will be agreed by the Board of Governors in October 2014. To be reviewed by June
The purpose of industrial lighting is to enable quick and accurate work, safely, and in a good visual environment. Points of note are:
5.4 Industry indoor Techniques General The purpose of industrial lighting is to enable quick and accurate work, safely, and in a good visual environment. Points of note are: Illuminance on the task is
Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company
RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing
section one guide to design, installation,commissioning and maintenance of fire systems in non domestic premises Consultant s Guide
section one Consultant s Guide section one section one contents About this manual Purpose Readership Electronic Format Acknowledgments 1 3 4 4 Section One: Guide to Design of Fire Systems 1. 1.1 1.1.1
Fire Policy and Procedures. Cañada Blanch Spanish School
Fire Policy and Procedures Cañada Blanch Spanish School SUMMARY 1. Introduction (p. 3) 2. Roles and responsibilities (p. 3) -- Headteacher -- Fire Team -- All staff -- Contractors 3. Fire procedures (p.
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
TS510 & TS500. Installation & User Guide. Compatible Equipment
Installation & User Guide Compatible Equipment TS510 REM - Remote Keypad 9040 - Loudspeaker DC54/58 - Digital Communicator SD1+ - Speech Dialler 496525 Issue A 1 of 10 TS510 and TS500 Overview Introduction
For use by landlords of small premises Premises Address
fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):
DOSSIER EN 12464-1. 10.80 m 10.30 CONCISE DESCRIPTION OF THE STANDARD. 2nd edition, june 2012
DOSSIER EN 12464-1 10.80 m 10.30 500 500 CONCISE DESCRIPTION OF THE STANDARD 2nd edition, june 2012 500 500 Foreword EN 12464-1 is an application standard for lighting. The original standard was written
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
SECURITY SYSTEM NOTES. EMERGENCY ACTIVATION KEYS (check if enabled) PROGRAMMED FUNCTIONS
SECURITY SYSTEM NOTES Installing/Service Company For Service Call Installation Date / / Central Station Duress Code EMERGENCY ACTIVATION KEYS (check if enabled) Fire Auxiliary Emergency Police PROGRAMMED
Fire Risk Assessment Safety Checklist
Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory
BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010
Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Page 1 of 7 PURPOSE: This Guidance
For the Design, Installation, Commissioning & Maintenance of Fixed Gaseous Fire Suppression Systems
BAFE Scheme: SP203-3 Version 1: July 2008 Amendment No: 1 Fire Protection Industry Scheme, Reference SP203 Part 3 For the Design, Installation, Commissioning & Maintenance of Fixed Gaseous Fire Suppression
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
LINCOLNSHIRE FIRE AND RESCUE
LINCOLNSHIRE FIRE AND RESCUE FIRE RISK ASSESSMENT FOR SMALLER PREMISES AND THE WORKPLACE FIRE PRECAUTIONS LEGISLATION The Fire Precautions (Workplace) Regulations 1997 The Fire Precautions (Workplace)
Smoke Alarm Legislation
Is it law for residential properties to have mains powered smoke alarms installed? Residential properties that are subject to sale, rent or hire are required under the Building Regulations 2012 to install
Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition
Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building
Mobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
The Child Reminder System Installation Manual
The Child Reminder System Installation Manual Revised June, 2006 Detailed installation information can be found at www.childreminder.com. Get through your installation quickly and easily by calling 1-888-330-6786
Fire risk assessment a guide for businesses
Fire risk assessment a guide for businesses Disclaimer Cornwall Fire and Rescue Service provide this guide to assist businesses to improve fire safety in their premises, but stress the person completing
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
ACTIVE 5 ENGINEERING MANUAL
ACTIVE 5 ENGINEERING MANUAL C & K Systems Ltd C031-066 Issue 3 THE ACTIVE 5 INSTALLATION MANUAL. Date: Feb 1997 INTRODUCTION. The Active 5 is a microprocessor controlled intruder alarm panel. It features
2 4PI175 issue 1_6/01. How to unset system in alarm. Programs 1, 2 and 3. Access codes. How to operate Personal Attack
Access codes Contents Unset system indications - - - - - - - - - - - System indication - - - - - - - - - - - - Access codes - - - - - - - - - - - - - - - - How to operate Personal - - - - - - How to unset
How To Comply With The Loss Prevention Certification Board
Loss Prevention Standard LPS 1014: Issue 5.3 This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information purposes only. Its use for testing, assessment,
CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance
CIBSE Guide M: Maintenance engineering and management compliance legislation and guidance Types of System/Plant Action required Frequency by Type of Fire and Smoke Fire extinguishers Discharge (not CO
GUARDIAN REFUGE & EMERGENCY VOICE COMMUNICATION SYSTEMS
GUARDIAN REFUGE & EMERGENCY VOICE COMMUNICATION SYSTEMS All Guardian Refuge and EVC Systems are BS9999 & BS5839 Pt9. 2010 compliant, and we offer our consultants assistance for BS5839, BS9999, (Fire safety
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
Jonathan Wilson. Sector Manager (Health & Safety)
Jonathan Wilson Sector Manager (Health & Safety) OHSAS 18001:2007 Making Life Easier For Health & Safety Managers Workshop Agenda 1. Introduction 2. Why Manage Health & Safety 3. OHSAS 18001 and OHSMS