ComPac I and ComPac II Air Conditioner Product Manual
|
|
|
- Whitney Stone
- 9 years ago
- Views:
Transcription
1 ComPac I and ComPac II Air Conditioner Product Manual Vertical Wall-Mount Air Conditioners with Front Control Box Panel Models AVP Chapter 1 Description... 5 Chapter 2 Installation Chapter 3 Start-Up Chapter 4 Troubleshooting Chapter 5 Maintenance Chapter 6 Warranty Parts List & Exploded Views Manufactured By: Marvair Division of AIRXCEL, Inc. P.O. Box 400 Cordele, Georgia Seedling Drive Cordele, Georgia (229) Fax (229) [email protected] Internet: P/ /09-18 supersedes 10/07-17
2 How To Use This Manual This manual is intended to be a guide to Marvair's ComPac line of vertical air conditioners. It contains installation, troubleshooting, maintenance, warranty, and application information. The information contained in this manual is to be used by the installer as a guide only. This manual does not supersede or circumvent any applicable national or local codes. If you are installing the ComPac unit, first read Chapter 1 and scan the entire manual before beginning the installation as described in Chapter 2. Chapter 1 contains general, descriptive information and provides an overview which can speed up the installation process and simplify troubleshooting. If a malfunction occurs, follow this troubleshooting sequence: 1. Make sure you understand how the ComPac unit works (Chapters 1 & 3). 2. Identify and correct installation errors (Chapter 2). 3. Refer to the troubleshooting information in Chapter 4. If you are still unable to correct the problem, contact the Factory at for additional assistance. Please read the following Important Safety Precautions before beginning any work. Important Safety Precautions 1. USE CARE when LIFTING or TRANSPORTING equipment. 2. TRANSPORT the UNIT UPRIGHT. Laying it down on its side may cause oil to leave the compressor and breakage or damage to other components. 3. TURN ELECTRICAL POWER OFF AT THE breaker or fuse box BEFORE installing or working on the equipment. LINE VOLTAGES ARE HAZARDOUS or LETHAL. 4. OBSERVE and COMPLY with ALL applicable PLUMBING, ELECTRICAL, and BUILDING CODES and ordinances. 5. SERVICE may be performed ONLY by QUALIFIED and EXPERIENCED PERSONS. * Wear safety goggles when servicing the refrigeration circuit * Beware of hot surfaces on refrigerant circuit components * Beware of sharp edges on sheet metal components * Use care when recovering or adding refrigerant 6. Use COMMON SENSE - BE SAFETY-CONSCIOUS This is the safety alert symbol. When you see this symbol on the ComPac unit and in the instruction manuals be alert to the potential for personal injury. Understand the signal word DANGER, WARNING and CAUTION. These words are used to identify levels of the seriousness of the hazard.! DANGER Failure to comply will result in death or severe personal injury and/or property damage.! WARNING Failure to comply could result in death or severe personal injury and/or property damage.! CAUTION Failure to comply could result in minor personal injury and/or property damage. IMPORTANT is used to point out helpful suggestions that will result in improved installation, reliability or operation. SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE. 6/09 Marvair Div. Airxcel, Inc. ComPac 6/09-18
3 WARNING If the information in these instructions are not followed exactly, a fire may result causing property damage, personal injury or loss of life. Read all instructions carefully prior to beginning the installation. Do not begin installation if you do not understand any of the instructions. Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency in accordance with these instructions and in compliance with all codes and requirements of authorities having jurisdiction. INSTALLER: Affix the instructions on the inside of the building adjacent to the thermostat. END USER: Retain these instructions for future reference. Table of Contents Chapter 1 ComPac A/C Description & Specifications 1.1 General Description Model Identification Serial Number Date Code Ratings and Specifications General Operation Electronic Control Board Mode of Operation Optional Controls Electrical Diagrams Economizer Components...16 Chapter 2 Installation 2.1 Equipment Inspection Installation Requirements Installation Materials Porting and Duct Work Fresh Air Hood Installation Bracket Installation Mounting the Unit Electrical Connections...24 Chapter 3 Start-Up 3.1 Check-Out of Cooling Cycle Check-Out of Heating Cycle A/C Testing with LL357D Chapter 4 Troubleshooting 4.1 Overview Failure Symptoms Guide Compressor Troubleshooting Control Board Diagnosis...34 ComPac 6/09-18
4 Table of Contents Chapter 5 Maintenance 5.1 Scheduled Maintenance...35 Chapter 6 Warranty 6.1 Limited Product Warranty Optional Silver Service Program...37 Parts List and Exploded Views...38 Illustrations Figure 1a. ComPac I & II A/C Dimensions - Models b. ComPac I & II A/C Dimensions - Models c. ComPac I & II A/C Dimensions - Model Figure 2. Refrigerant Circuit... 9 Figure 3a. Typical Electrical Schematic-ComPac I A/C Models w/ Electronic Control Board b. Typical Electrical Schematic-ComPac II A/C Models w/ Electronic Control Board 15 Figure 4. H205A Temperature Control Points Figure 5. H205A Control Point Adjustment Figure 6. Fresh Air Hood Installation Figure 7. Wall Mounting Detail - ComPac A/C AVP Figure 8a. Thermostat Wiring Details Figure 8b. Thermostat Connection Diagram Figure 8c. LL357D4 Wiring Detail Figure 8d. CommStat 3 Wiring Detail Tables Table 1 External Static Pressure... 6 Table 2 Ship Weight... 6 Table 3 Standard Filter Size... 6 Table 4 Minimum Clearances Table 5 Voltage Limitations Table 6 Maximum Static Pressure ComPac 6/09-18
5 Chapter 1 Description & Specifications 1.1 General Description Marvair's ComPac lines are a series of vertical wall-mounted air conditioning systems that provide heating, cooling, and ventilation for electronic equipment shelters, process control centers, and other applications with high internal heat gains. The series includes multiple sizes and nominal cooling capacities from 24,000 to 72,000 BTUH. Resistance heating elements are available in various wattages. Marvair s ComPac I & ComPac II air conditioners, models AVP24-72, feature an exclusive electronic control board. The control board consolidates several of the electrical components and improves the air conditioner s reliability. The control board replaces the blower relay, the lockout relay, the compressor time delay and the timed low pressure bypass. In addition, the control board has LED s to indicate operating status and fault conditions to assist the service technician. A complete description of functions of the control board is in Section 1.6. The ComPac I & ComPac II models are designed for easy installation and service. Major components are accessible for service beneath external panels. All units have internal disconnects (optional on 460V). Depending upon state and local code requirements, this feature may eliminate the need for an external breaker or disconnect. The ComPac I A/C has a 0-15% manual outside air damper and the ComPac II A/C has a factory installed economizer for 100% free cooling with outside air. 1.2 Model Identification The model identification number is found on the data sticker. Rating plate located on side panel. AVP ** AC * * * * Special Option Code R = Electric Reheat U = Scroll Compressor Configuration N = ComPac I A/C C = ComPac II A/C Electric Heat (kw) 00, 04, 05, 06, 08, 09, 10, 15 Power Supply A = 208/230V, 1ø, 60 Hz C = 208/230V, 3ø, 60 Hz D = 460V, 3ø, 60 Hz E = 380V, 3ø, 50 Hz F = 220V, 1ø, 50 Hz G = 220V, 3ø, 50 Hz Air Source Vertical Package *Ratings at 60 Hz. System Type = Air Conditioner Nominal Cooling* 24 = 24,000 BTUH 48 = 48,000 BTUH 30 = 29,400 BTUH 60 = 55,000 BTUH 36 = 35,000 BTUH 72 = 72,000 BTUH 42 = 41,500 BTUH 1.3 Serial Number Date Code A = January E = May J = September L = 2000 R = 2004 V = 2008 B = February F = June K = October M = 2001 S = 2005 Y = 2009 C = March G = July L = November N = 2002 T = 2006 D = April H = August M = December P = 2003 U = 2007 ComPac 6/09-18
6 1.4 Ratings & Specifications MODEL Table 1. External Static Pressure (Wet Coil) (IWG) 24 30/ MODEL LBS/KG LBS/KG LBS/KG LBS/KG LBS/KG LBS/KG COMPAC I A/C 274/ / / / / /284 COMPAC II A/C 286/ / / / / /290 Table 2. Ship Weight MODEL 24 30/36 42/48/60 72 FILTER SIZE (inches) 16 x 25 x 2 16 x 30 x 2 22 x 36-1/2 x 2 18 x 24 x 2* FILTER SIZE (mm) 406 x 635 x x 762 x x 927 x x 610 x 51 *Two filters required. Table 3. Filter Size 6 ComPac 6/09-18
7 Figure 1a. ComPac I & ComPac II A/C Dimensions- Models AVP20-36 (in inches) Figure 1b. ComPac I A/C & ComPac II A/C Dimensions- Models AVP42-60 (in inches) ComPac 6/09-18
8 Figure 1c. ComPac I A/C & ComPac II A/C Dimensions- Models AVP72 (in inches & mm) 8 ComPac 6/09-18
9 1.5 General Operation Refrigerant Cycle (Cooling Mode) The ComPac I & ComPac II A/C use R-22 refrigerant in a conventional vapor-compression refrigeration cycle to transfer heat from air in an enclosed space to the outside. A double blower assembly blows indoor air across the evaporator. Cold liquid refrigerant passing through the evaporator is boiled into gas by heat removed from the air. The warmed refrigerant gas enters the compressor where its temperature and pressure are increased. The hot refrigerant gas condenses to liquid as heat is transferred to outdoor air drawn across the condenser by the condenser fan. Liquid refrigerant is metered into the evaporator through capillary tubes to repeat the cycle. Distributor & Capillary Tubes Evaporator (Indoor Coil) Filter Drier Twin Blowers Suction Line Compressor Condenser Fan Discharge Line Heating Mode Condenser (Outdoor Coil) Figure 2. Refrigerant Circuit A wall-mounted thermostat controls the heating cycle of models which incorporate resistance heating elements. On a call for heat, the thermostat closes the heat relay to energize the indoor fan and the resistance elements. Except on units with the optional dehumidification kit, the compressor is locked out during the heating cycle. Economizer Operation (ComPac II A/C Only) The economizer is a regulated damper system with controls. The damper regulates the circulation of outside air into the enclosure (when the outdoor air conditions are suitable) to reduce the need for mechanical cooling, save energy, and extend compressor life. Depending upon the options selected, the damper responds to the enthalpy of the outdoor air. On a call for cooling from a space thermostat, it operates as follows: When the enthalpy of the outdoor air is below the set point, the outdoor air damper is proportionally open (and return air damper is proportionally closed) to maintain between 50 F and 56 F at the mixed/discharge air sensor. Integral pressure relief allows the indoor air to exit the shelter through the air conditioner. When the enthalpy of the outdoor air is above the set point, the outdoor air damper closes to its minimum position. A call for cooling from the space thermostat brings on mechanical cooling. An optional built-in adjustable minimum position potentiometer (part number 70012) controls the amount of outdoor air admitted to meet minimum ventilation requirements. 9 ComPac 6/09-18
10 1.6 Electronic Control Board Mode of Operation (AVP24-72) Normal 24 VAC power must be continuously applied to R and C. Upon a call for cooling Y and with the high pressure switch (HPS) closed, the compressor will be energized. (Note: See the delay on make feature.) The compressor will remain energized during the 3 minute timed low pressure by-pass cycle. If the low pressure switch (LPS) is open after the 3 minute by-pass cycle, the compressor will de-energize. Lock-out If either of the fault conditions (LPS or HPS) occurs twice, the control board will enter into and indicate the lockout mode. In the lockout mode, the compressor is turned off. If there is a call for indoor air flow G, the blower remains energized, the alarm output is energized and the status led will blink to indicate which fault has occurred. When the lockout condition is cleared, the unit will reset if the demand for the thermostat is removed or when the power is reset. With the control board, the user can now have either normally closed or normally open contacts by moving a wire on the control board. The ComPac air conditioners are factory wired to be normally open. Delay on Break If the compressor is de-energized due to a loss of a cooling Y call or the first fault, the unit re-start will be delayed 3 minutes from the time the contactor is de-energized. (Note: There is no delay on break if the lockout condition is reset.) Delay on Make On initial power up only, the unit will wait 0.03 to 10 minutes from the cooling Y call before allowing the contactor to energize. The delay can be adjusted by the DOM wheel on the board. Factory recommended wait is 3 minutes. Low Pressure By-Pass Time When starting, the low pressure switch (LPS) fault condition will be by-passed for 3 minutes before the contactor is de-energized. Post Purge Upon a call for indoor airflow G the blower will energize immediately. When in the cooling mode, the blower will remain energized for 10 to 90 seconds (adjustable) after the compressor has been de-energized. The time period can be changed by fan purge wheel on the board. Factory setting is 90 seconds. LED Indicator Lights COLOR TYPE STATUS DESCRIPTION Green Power Constant On 24 VAC power has been applied Red Status Constant On Normal operation Red Status 1 Blink High pressure switch has opened twice Red Status 2 Blinks Low pressure switch has opened twice 10 ComPac 6/09-18
11 Low Ambient Control The low ambient control permits cooling when outdoor ambient temperatures are low. The control uses a reverse-acting high pressure switch to cycle the condenser fan motor according to liquid refrigerant pressure conditions. Switch closure and fan operation occurs when the pressure reaches 250 PSIG. The switch opens again when the refrigerant pressure falls to 190 PSIG. Therefore, the outdoor fan always starts after the compressor, and it will cycle frequently during normal operation at low outdoor conditions. High Pressure Switch The high pressure switch is mounted on the compressor discharge line. It is electrically connected to a lockout relay which shuts down the system if the refrigerant pressure rises to 400 PSIG (AVP60 setting is 450 PSIG). This protects the unit if airflow through the condenser is blocked or if the outdoor fan motor fails. Although the contacts of the high pressure switch close when the refrigerant pressure falls to approximately 300 PSIG, the system must be manually reset once the lockout relay is activated. A manual reset is necessary to prevent harmful short-cycling. To reset switch, turn primary power off, then back on or turn thermostat system switch off, then back on. Low Pressure Switch The low pressure switch is mounted on the compressor suction line. It is designed to open if the refrigerant pressure drops to 35 PSIG; it resets when the pressure rises to 60 PSIG. The switch protects the unit if airflow through the indoor blower is impeded, if the blower motor fails, or if there is a loss of refrigerant. LEDs POST PURGE WHEEL DELAY ON MAKE (COMPRESSOR TIME DELAY) WHEEL 11 ComPac 6/09-18
12 1.7 Optional Controls & Packages Hard Start Kit Used on single phase equipment to give the compressor higher starting torque under low voltage conditions. Generally not recommended on units with scroll compressors. Extreme Duty Package The Extreme Duty Package allows selected Marvair ComPac I & ComPac II air conditioners to operate in extremely cold and hot ambient conditions. The Extreme Duty Kit is always factory installed and is available on all ComPac air conditioners. ComPac I air conditioners (non-economizer units) will operate from 0 F to 130 F (-18 to 54 C). ComPac II air conditioners (economizer units) will operate from -20 F to 130 F (-29 to 54 C). The Extreme Duty Package includes a suction line accumulator, thermal expansion valve (TXV), crankcase heater, hard start kit, an auto reset, adjustable high pressure switch and an outdoor thermostat and fan cycle switch. The fan cycle control is standard on all ComPac air conditioners and operates based upon the liquid line pressure. The outside thermostat closes whenever the outside temperature is below 50 F (10 C) and opens when the outside temperature is 50 F (10 C) or higher. Whenever the temperature is below 50 F (10 C), the fan cycle switch is in the circuit; when temperatures are 50 F (10 C) or higher, the fan cycle switch is not in the circuit. The fan cycle control is used with a TXV to prevent excessive cycling or "hunting" of the TXV. Coastal Environmental (ComPac I A/C Only) Recommended for units to be installed near an ocean or on seacoast. Includes corrosion resistant fasteners, sealed condenser fan motor, protective coating applied to all exposed internal copper in the condenser section and a protective coating on the condenser coil. Stainless Steel Cabinet (ComPac I A/C Only) All sheet metal constructed of stainless steel. Hot Gas Bypass (ComPac I A/C Only) Used in specialty applications; i.e., Magnetic Resonance Imaging (MRI) buildings, to prevent magnetic voltage disturbance caused by compressor cycling. Two hot gas bypass option packages are available to allow operation to 20 F (-7 C) or minus 20 F (-29 C). Please refer to Hot Gas Bypass Application Bulletin for details. Electric Reheat Dehumidification A humidity controller (p/n 50057) allows electric heat and cooling to operate simultaneously. Marvair air conditioners equipped with the dehumidification option allow the indoor humidity of the controlled environment to be maintained at or below a certain humidity set point. These units do not have the ability to add humidity to the building. IMPORTANT: The electrical wire and breaker or fuses must be sized for simultaneous operation of the electric heater and the air conditioner. Refer to the data sticker on the unit or the ComPac Air Conditioner Product Data Sheet for the sizing information. Dehumidification is achieved by operating mechanical cooling in conjunction with electric reheat. The strip heat is sized approximately to the sensible capacity of the total tonnage of the machine (i.e., on a 24,000 BTU unit the strip heat is sized at approximately 20,000 BTU). Because the strip heat is sized to the approximate sensible cooling capacity, only selected models are available. Operation: When the humidity rises above the set point on the humidity controller both mechanical cooling and 12 ComPac 6/09-18
13 electric reheat operate to temper the air and lower the humidity. If the temperature in the controlled environment rises above the set point of the thermostat and the unit is operating in the dehumidification mode, the call for cooling will override the call for dehumidification and the strip heat is disengaged until the thermostat is satisfied. This assures the environment temperature is maintained as first priority and humidity control is second. In applications where a shelter has redundant air conditioning units and is controlled by a lead lag controller (Marvair's LL357D4 or CommStat3 Controller), most times the dehumidification option is only necessary on one of the two units. It is possible for one unit to be operating in the cooling mode while the unit with dehumidification is operating at the same time. If the cooling unit does not maintain the shelter temperature set point, the unit with dehumidification will go into the cooling mode. It does not matter whether the unit with dehumidification is the lead or lag unit. Three Phase Voltage Monitor, Marvair Continuously measures the voltage of each of the three phases. The monitor separately senses low and high voltage, voltage unbalance including phase loss and phase reversal. An LED indicator glows when all voltages are acceptable. Automatically resets when voltages and phases are within operating tolerances. Dirty Filter Indicators A diaphragm type of indicator measures the air pressure on either side of the filter and when the pressure drops below the set point, an LED is illuminated. Minimum Potential Potentiometer Used in the ComPac II units with the factory installed economizer. The potentiometer prevents the economizer from closing completely, assuring that outside air will be brought into the shelter and exhausted whenever the indoor blower is operating. This prevents negative pressurization of the building. The minimum potential potentiometer is adjustable. 1.8 Electrical Diagrams The compressor and condenser fan are energized with a contactor controlled by a 24 VAC pilot signal. Some compressors incorporate an internal PTC crankcase heater that functions as long as primary power is available. The heater drives liquid refrigerant from the crankcase and prevents loss of lubrication caused by oil dilution. Power must be applied to the unit for 24 hours before starting the compressor. The condenser (outside fan) motor is energized by the same contactor. However, the motor is cycled on and off by the low ambient control (see low ambient control 1.6). The indoor evaporator fan motor is controlled by the fan purge on the electronic control board. 13 ComPac 6/09-18
14 TRANSFORMER 6 5 Figure 3a. Typical Electrical Schematic - ComPac I A/C, Models AVP24-72 with Electronic Control Board 14 ComPac 6/09-18
15 TRANSFORMER 5 OPTIONAL FIELD INSTALLED 270 OHMS MINIMUM POSITION POTENTIOMETER. Figure 3b. Typical Electrical Schematic - ComPac II A/C, Models AVP24-72 with Electronic Control Board 15 ComPac 6/09-18
16 1.9 Economizer Components (ComPac II A/C Only) Damper Actuator: The damper actuator is a 24V motor that modulates the position of the damper blade. It is capable of driving a full 90 degrees within 90 seconds. The assembly has a spring return to close the damper during power outage. Controls: The economizer is controlled by the H205A enthalpy control or optional dry bulb sensor. H205A Economizer Changeover Control: The H205A enthalpy controller responds to the total heat content of the outdoor air to provide changeover to outside air for free cooling. The change point (factory set at "D") is adjustable from 53 50% RH (full counterclockwise) to 78 50% RH (full clockwise). Refer to Figure 4 and Figure 5. Once the H205A has selected outside air, the mixed air sensor will limit the air temperature delivered to the space by modulating the damper blade to "mix in" a quantity of inside air to provide a constant 50 to 56 F. (Adjustable minimum potentiometer, part number 70012, is optional.) CONTROL CONTROL POINT* CURVE AT 50% RH A 72 F/23 C B 68 F/20 C C 63 F/17 C D 58 F/14.5 C Full CCW is 55 F *Approximate Deg. Figure 4. H205A Temperature Control Points 16 ComPac 6/09-18
17 The controller modulates the position of the outside air damper in response to input from the enthalpy and mixed air sensors. The controller is designed to maintain the supply air temperature between 50 to 56 F by mixing warm indoor air with cooler outdoor air. On a call for cooling from the wall-mounted thermostat, if outdoor conditions are suitable, the controller will open the damper and admit outside air (i.e., economizer cooling). If the outdoor ambient is too hot or humid, the controller will place the actuator in the closed or minimum open position and activate mechanical cooling. The compressor is locked out during the economizer cooling mode. Scaleplate and Knob 54.4 Degrees Between D C B A Index Mark on Controller Figure 5. H205A Control Point Adjustment Flat on Shaft Perpendicular to Index Mark on Controller Mixed Air Sensor: The mixed air sensor is a thermistor mounted on a bracket adjacent to the right side of the blower assembly. The thermistor senses the air temperature entering the structure, and provides a signal to the economizer controller for modulating the position of the damper. Nominal resistance of the sensor at 77 F is 3000 ohms. 17 ComPac 6/09-18
18 2.1 Equipment Inspection Concealed Damage Inspect all cartons and packages upon receipt for damage in transit. Remove cartons and check for concealed damage. Important: keep the unit upright at all times. Remove access panels and examine component parts. (Note: the "L"-shaped bottombracket is stored in the condenser air compartment. Remove it before replacing the side screen). Inspect refrigerant circuit for fractures or breaks. The presence of refrigerant oil usually indicates a rupture. If damage is apparent, immediately file a claim with the freight carrier. Units that have been turned on their sides or tops may have concealed damage to compressor motor mounts or to the oil system. If the unit is not upright, immediately file a claim for concealed damages and follow these steps: 1. Set unit upright and allow to stand for 24 hours with primary power turned on. 2. Attempt to start the compressor after 24 hours. 3. If the compressor will not start, makes excessive noise, or will not pump, return the unit to the freight carrier. 2.2 Installation Requirements Chapter 2 Installation WARNING Failure to observe and follow Warnings and Cautions and these Instructions could result in death, bodily injury or property damage. Read this manual and follow its instructions and adhere to all Cautions and Warnings in the manual and on the Marvair unit.. General 1. Inspect unit for completeness. Check for missing parts (e.g. hardware). Refer to the installation kit information in section Remove access panels and check for loose wires. Tighten screw connections. 3. Complete and mail the warranty registration card. You must consider all of the following when choosing the installation site: 1. Noise. Install the unit so that the least amount of noise will be transmitted to inhabited spaces. 2. Condensate Drainage. Condensate produced during operation must be discharged to a suitable drain. 3. Placement. A) Place the unit in a shaded area, if possible. B) Install it above ground for protection against flooding. C) The unit exhausts air. Be sure that the airflow is not impeded by shrubbery or other obstructions. D) When installing multiple units, please note the recommended clearances noted in Table Airflow Requirements: Note the minimum CFM requirements (Table 6). Keep duct lengths as short as possible. Do not obstruct airflow through the unit. 18 ComPac 6/09-18
19 Duct work should be designed and installed in accordance with all applicable safety codes and standards. Marvair strongly recommends referring to the current edition of the National Fire Protection Association Standards 90A and 90B before designing and installing duct work. The duct system must be engineered to insure sufficient air flow through the unit to prevent over-heating of the heater element. This includes proper supply duct sizing, sufficient quantity of supply registers, and adequate return and filter areas. Duct work must be of correct material and must be properly insulated. Duct work must be constructed of galvanized steel with a minimum thickness of.019 inches. Duct work must be firmly attached, secured, and sealed to prevent air leakage. See section 2.4 for additional duct work requirements. 5. Clearances: Note the minimum clearances required for proper operation and service. MODEL MIN. CLEARANCE AROUND SIDES (SINGLE UNIT) MIN. CLEARANCE BETWEEN UNITS (TWO UNITS) Table 4. Minimum Clearances MIN. SPACE ABOVE UNIT inches 18 inches 24 inches 30/36 30 inches 18 inches 24 inches 42/48/60 30 inches 30 inches 24 inches inches 30 inches 12 inches 6. Codes: Make sure your installation conforms to all applicable electrical, plumbing, building, and municipal codes. Some codes may limit installation to single story structures. 7. Electrical Supply: The power supply must have the appropriate voltage, phase, and ampacity for the model selected. Voltage must be maintained above minimum specified values listed below. Refer to the data sticker on the unit for ampacity requirements. Electrical Rating Designations* A C D Nominal Voltage 208/ / Phase Minimum Voltage Maximum Voltage * Letters refer to model number code designations. Refer to page 5. Table 5. Voltage Limitations 2.3 Installation Materials (AVP24-72) Installation Kits The ComPac I and ComPac II A/C units, models AVP24-72, are shipped with one 12 Ga. "L" shaped bottom bracket. On AVP24,30 & 36 units, there is an air intake hood packed inside each unit. If you have not yet unpacked the unit, follow the instructions in section 2.1. All units have built-in full length mounting flanges. Therefore, use of mounting brackets is not required. Kit Components - Models AVP24-72: 1. One 12 Ga. "L"-shaped bottom bracket Accessories: The package may include other factory-supplied items (optional) as follows on the next page: 19 ComPac 6/09-18
20 P/N Description S/04581 CommStat 3 Controller, Solid State Lead/Lag Controller S/07529 LL357D4, Lead/Lag Controller with T'stat & Sub-Base; Controls 2 A/C Units Digital thermostat. 1 stage heat, 1 stage cool. 7 day programmable. Fan switch: Auto & On. Auto-change over. Keypad lockout. Non-volatile program memory Digital thermostat. 2 stage heat, 2 stage cool. 7 day programmable. Fan switch: Auto & On. Auto-change over. Status LED s. Backlit display. Programmable fan. Non-volatile program memory VPG - 20S, 20 x 8" Adjustable, Aluminum, Double Deflection Supply Grill for AVP VPG - 30S, 28 x 8" Adjustable, Aluminum, Double Deflection Supply Grill for AVP VPG - 40S, 30 x 10" Adjustable, Aluminum, Double Deflection Supply Grill for AVP VPG - 20R, 20 x 12" Aluminum Return Grill for AVP VPG - 30R, 28 x 14" Aluminum Return Grill for AVP30-36 VPG - 40R, 30 x 16" Aluminum Return Grill for AVP Start Relay and Capacitor for AVP24-36 (Field Installed) (Not recommended for scroll compressors.) Additional Items Needed: Additional hardware and miscellaneous supplies (not furnished by Marvair ) are needed for installation. For example, the list below contains approximate quantities of items typically needed for mounting a unit on a wood frame wall structure. Concrete or fiberglass structures have different requirements. ComPac I and ComPac II A/C Models (10) 3/8" carriage head mounting bolts for unit mounting flanges. The length needed is typically the wall thickness plus one inch. (20) 3/8" washers (10) 3/8" hex nuts (6) 3/8" x 2-1/2" lag screws for bottom bracket Silicone Sealer to seal around cracks and openings 4-conductor low voltage multicolored wire cable (i.e. thermostat wire) Appropriate electrical supplies such as conduit, electrical boxes, fittings, wire connectors, etc. High voltage wire, sized to handle the MCA (minimum circuit ampacity) listed on the data plate. Over-Current Protection Device sized in accordance with the MFS (maximum fuse size) listed on the unit data plate. 20 ComPac 6/09-18
21 2.4 Porting and Duct Work (AVP24-72) Warning FIRE HAZARD Improper adjustment, alteration, service, maintenance or installation could cause serious injury, death and/or property damage. Installation or repairs made by unqualified persons could result in hazards to you and others. Installation MUST conform with local codes or, in the absence of local codes, with codes of all governmental authorities have jurisdiction. The information contained in this manual is intended for use by a qualified service agency that is experienced in such work, is familiar with all precautions and safety procedures required in such work, and is equipped with the proper tools and test instruments. General Information Note: The following instructions are for general guidance only. Due to the wide variety of installation possibilities, specific instructions will not be given. When in doubt, follow standard and accepted installation practices, or contact Marvair for additional assistance. Wall Openings Measure the dimensions of the supply and return ports on the unit. Cut the openings in the exterior wall for the supply and return. IMPORTANT: All units with electric heat must have one inch clearance on all four sides of the supply outlet duct flange on the unit. The one inch clearance must extend on all sides of the supply duct for the first three feet from the unit. IMPORTANT: Marvair requires a minimum of one inch from the surface of any supply ducts to combustible material for the first three feet of the duct. Ducting Extensions should be cut flush with the inside wall for applications without duct work. Applications using duct work should be designed and installed in accordance with all applicable safety codes and standards. Marvair strongly recommends referring to the current edition of the National Fire Protection Association Standards 90A and 90B before designing and installing duct work. The duct system must be engineered to insure sufficient air flow through the unit to prevent over-heating of the heater element. This includes proper supply duct sizing, sufficient quantity of supply registers, adequate return and filter area. Ductwork must be of correct material and must be properly insulated. Duct work must be constructed of galvanized steel with a minimum thickness of.019 inches for the first three feet. Ductwork must be firmly attached, secured and sealed to prevent air leakage. Do not use duct liner on inside of supply duct within 4 feet of the unit. Galvanized metal duct extensions should be used to simplify connections to duct work and grilles. Use fabric boots to prevent the transmission of vibration through the duct system. The fabric must be U.L. rated to a minimum of 197 F. Minimum Airflow Requirements The duct system must be engineered to assure sufficient air flow through the unit even under adverse conditions such as dirty filters, etc. Use Table 6 below and Table 1, CFM at External Static Pressure (Wet Coil) in section ComPac 6/09-18
22 BASIC MODEL MAXIMUM TOTAL STATIC MINIMUM FILTER AREA sq. ft. 30/ sq. ft. 42/48/60/ sq. ft. Table 6. Maximum Static Pressure (For units with 2" Pleated Filters) 2.5 Fresh Air Hood Installation (AVP ) 1. Cut and remove insulation on the inside of the lower front access panel in the shape of the rectangular opening. See Figure Insert flange on hood into opening and secure using the two #8 x 1/2 sheet metal screws supplied. Figure 6. Fresh Air Hood Installation 2.6 Bracket Installation (AVP24-72) 1. Models AVP24-72 have built-in mounting flanges. 2. Apply a bead of silicone sealer on the wall side of the bottom support brackets on the unit. Circle the mounting holes with the silicone bead. 3. Refer to Figure 7. Attach the bottom support bracket to the wall using appropriate 3/8" diameter hardware. For example, on wooden structures, use 3/8" x 2-1/2" all-thread lag screws. The screws must penetrate the center of the wall stud. Drill a pilot hole in the stud to prevent it from splitting. 22 ComPac 6/09-18
23 2.7 Mounting The Unit (AVP24-72) 1. For wiring into the back of unit, locate the lower of the two knockouts on the wall side of the unit. Drill a one inch hole in the shelter wall to match this opening. Allow sufficient clearance to run 3/4" conduit through the hole and to the unit. 2. Using an appropriate and safe lifting device, set the unit on the bottom support bracket mounted on the wall. You must stabilize the unit on the bracket with the lifting device or by some other means - the bracket alone is not sufficient. 3. Make sure that the duct flanges are properly aligned with the wall opening. Adjust as necessary. 4. Note the holes in each side flange. Using the holes for guides, drill holes through the wall with a 3/8" drill bit. Insert the 3/8" x 5" bolts through the flanges. Install nuts and washers on the inside of the shelter. Tighten the bolts to secure the unit. 5. Apply a bead of silicone where the mounting flange contacts the unit and the shelter wall. 6. On the inside of the shelter, install the wall sleeves in the supply and return air openings. The sleeves may be trimmed to fit flush with the inside wall. 7. Check the fit of each sleeve to its mating flange for possible air leaks. Apply silicone sealer to close any gaps. Install the air return and supply grilles. GRILLE SUPPLY AIR DUCT EXTENSIONS (Not Supplied with Unit) COMPAC II A/C ONLY RETURN AIR GRILLE FOAM SEAL Figure 7. ComPac I and ComPac II A/C Wall Mount Detail (AVP24-72) 23 ComPac 6/09-18
24 2.8 Electrical Connections Important All electrical work must meet the requirements of local codes and ordinances. Work should be done only by qualified persons. The ComPac units may incorporate an internal crankcase heater for compressor protection. crankcase heater must be energized for at least 24 hours prior to starting the compressor. Scroll compressors, like several other types of compressors, will only compress in one rotational direction. The direction of rotation is not an issue with single-phase compressors since they will always start and run in the proper direction. However, three phase compressors will rotate in either direction depending upon phasing of power. Since there is a chance of connecting power in such a way as to cause rotation in the reverse direction, it is imperative to confirm that the compressor is rotating in the proper direction at the initial field start-up of the system. Verification of proper rotation is made by observing that the suction pressure drops and the discharge pressure rises when the compressor is energized. An alternate method of verification for self contained system with small critical refrigerant charges, where the installation of gauges may be objectionable, can be made by monitoring the temperature of the refrigerant lines at the compressor. The temperature should rise on the discharge line while the suction line temperature decreases. Reverse rotation also results in a substantially reduced current draw when compared to tabulated values. Marvair units have either a reciprocating or scroll compressor. A reciprocation compressor is standard on the AVP24, 30 & 36 units. However, a scroll compressor is an option on these ComPac I and ComPac II air conditioners. Units with scroll compressors have a "U" in the model number. The scroll compressor is standard on all AVP42, 48, 60 & 72 units. There is no negative impact on durability caused by operating three phase compressors in the reversed direction for a short duration of time, usually defined as less than one hour. However, after several minutes of operation the compressor's internal protector will trip. The compressor will then cycle on the protector until the phasing is corrected. Reverse operation for longer than one hour may have a negative impact on the bearings. High Voltage Wiring - (Single Units) The power supply should have the proper voltage, phase, and ampacity for the selected model. 1. Size the incoming power supply lines according to Code requirements. Run the power conductors through the knockouts on the wall side of the unit, or to those adjacent to the electrical control box. Use appropriate conduit and strain reliefs. 2. Connect the wires to the input side of the internal breaker or terminal block (L1 & L2 for singlephase units; L1, L2, & L3 for three-phase models). 3. Install the ground wire on the ground lug. WARNING ELECTRICAL SHOCK HAZARD Failure to follow safety warnings exactly could result in serious injury, death, and/or property damage. Turn off electrical power at fuse box or service panel BEFORE making any electrical connections and ensure a proper ground connection is made before connecting line voltage. The 24 ComPac 6/09-18
25 4. For units designed for operation on 208/230v, 60Hz power supply, the transformer is factory wired for a 230v power supply. For a 208v power supply, remove the orange lead from the transformer and connect the red lead. Insulate the orange lead. Dual Unit Phasing For applications where one controller operates two units, e.g., the CommStat 3 or LL357D. The LL357D4 and the LL357D3 do not require unit phasing. However, if other devices are connected to the control system, phasing of the air conditioner is required. Earlier models; i.e., LL357, LL357A, LL357D2 require the unit to be properly phased. 1. Wire each unit as described in steps 1 through 4 above. 2. Test for proper phasing as follows: A. Power up the units. B. Using an AC volt meter set to the 300 volt scale, measure voltage between terminal L1 on the compressor contactor of unit #1 and terminal L1 on the compressor contactor of unit #2 If voltage is present, units are wired out of phase and must be rewired. C. If units are not in phase, turn off power and reverse the field power leads connected to the internal circuit breaker on one of the units only. D. Restore power and retest the phase (step B). When the voltage reads "0", the units are in phase. E. Turn off power and proceed. Low Voltage Wiring 1. On single units, pull the low voltage wiring (e.g., 18 gauge 4-conductor Class 2 thermostat wire) from the ComPac A/C into the thermostat / subbase assembly. See Figure 8d for connections to various thermostats. 2. Mount the thermostat on the wall of the shelter. The thermostat should be located so that the supply air from the unit does NOT blow directly on to the thermostat. Connect the thermostat to the terminal block in the ComPac air conditioner as shown in Figures 8a and 8b. 3. On dual units, refer to the Marvair LL357D4 Lead/Lag Controller Specification Sheet or CommStat 3 Controller Specification sheet. Level and install the LL357D4 or CommStat 3 subbase. Wire the two ComPac units to the Lead/Lag Controller, according to the wiring diagram on the specification sheet and as shown in Figure 8c or 8d (note: the diagram also appears on the back cover of the controller). Remote Signalling: Terminals 5 & 7(N.O.) and 6 & 7 (N.C.) on the ComPac A/C terminal board are dry contacts which can be used for remote signalling in the event of a/c cutoff on low or high pressure limit. Continuous fan operation: For continuous indoor fan operation on single units, install a jumper between terminals 8 and 3. For continuous indoor fan operation on dual units using the LL357D4, install jumper between 8 and 3 and remove jumper between 1 and 3. CommStat 3 Controller (See Figure 8c) The CommStat 3 Controller by Marvair is a solid state control package designed to operate a fully or partially redundant air conditioning system for a telecommunication cabinet or shelter. The CommStat 3 Controller is factory programmed with standard industry set points to facilitate installation. If desired, each of the set points can be quickly and easily changed in the field by the installer. 25 ComPac 6/09-18
26 It can be used with Marvair s ComPac I or II unique vertical packaged wall mount air conditioners or Marvair s environmental control units. See CommStat 3 Product Data Sheet for installation and programming instructions. LL357D4 Lead/Lag Controller (See Figure 8b) The Marvair LL357D4 is a complete control package designed to operate a fully or partially redundant air conditioning system. It consists of a two-stage heat and two-stage cool electronic thermostat and a solid state timer. It can be used with either the Marvair ComPac I vertical packaged wall mount air conditioner or our unique ComPac II air conditioner with built-in economizer. The LL357D4 provides environmental control and the security demanded by the communication shelter industry for a backup unit. The lead/lag controller insures equal wear on both air conditioners while allowing the lag unit to assist upon demand. The LL357D4 is factory wired, tested, and mounted in an enclosure for quick installation. Refer to the LL357D4 Product Data Sheet for complete installation instructions. Operational Specifications Thermostat Range: 45ºF to 90ºF (7ºC to 32ºC) Accuracy: ±1ºF (± ½ºC) Changeover Temperature Differential (separation between the heat set point and the cool set point): 2ºF to 9ºF (1.0ºC to 4.5ºC) First Stage Temperature Differential (number of degrees between the set point temperature and the turn on temperature): 1ºF to 3ºF (.5ºC to 1.5ºC) Second Stage Temperature Differential (number of degrees between when stage 1 turns on and when stage 2 turns on): 1ºF to 6ºF (.5ºC to 3.0ºC). Minimum Cool Temperature Set Point: Adjustable from 45ºF to 75ºF (7ºC to 24.0ºC). Maximum Heat Temperature Set Point: Adjustable from 55ºF to 90ºF (13ºC to 32.0ºC) Staged OFF Outputs: Air conditioners will turn off independently. Timing Device Solid state timer with both 3.5 and 7 day changeover capability. NOTE: Cut timer circuit wire to provide 3.5 day changeover. Timing accuracy ±5%. Momentary push button for accelerated manual timer advance. (9 seconds = 7 days) Light emitting diode indicates power on and identifies the lead unit. Unit Shutdown/Fire Alarm Systems Immediate shutdown of the air conditioning system can be accomplished by wiring the normally closed set of contacts in the fire extinguishing or alarm system across terminals 8 and 10 on the low voltage terminal board inside the air conditioner. Note: The factory jumper between these terminals must be removed. This function cannot be accomplished at the wall thermostat because the fan purge on the electronic control board inside the unit allows the indoor blower to operate from 10 to 90 seconds following each cool "on" cycle. NOTE: The fan purge on the electronic control board allows the indoor fan to run for approximately 10 to 90 seconds after the compressor is off. This operation provides a small improvement in system efficiency. 26 ComPac 6/09-18
27 5 WIRE WALL THERMOSTAT * G R W Y C Five (5) Conductor Color- Coded 18 Gauge Thermostat Cable (Field Supplied) NOTE: Terminals 5 & 7 are normally open dry contacts and close to indicate lockout. Terminals 6 & 7 are normally closed dry contacts and open to indicate lockout COMPAC A/C TERMINAL BLOCK *Terminals on thermostat may have RC & RH. If so, install jumper wire between RC & RH. X O G H W2 E R A Y Thermostat Humidity Controller Field Supplied Seven (7) Conductor, Color Coded 18 Gauge Thermostat Cable R Y A O G W2 C HEAT PUMP*LOW VOLTAGE SECTION *A/C s do not have O. Figure 8a. Thermostat Wiring Details 27 ComPac 6/09-18
28 MARVAIR /SIMPLE COMFORT THERMOSTAT CONNECTION DIAGRAM FOR MARVAIR MODPAC II, XCELPAC & ALL COMPAC AIR CONDITIONERS THERMOSTAT PART NUMBER 50121/ SC2010-SL R G Y W C O B 50124/ SC3001 R c R H G Y W C O B 50123/ SC5011-SL R c R H G Y W C O B 50107/ SC5811-SL R G Y 1 W 1 C Y 2 W 2 O/B MODPAC II R G Y W C LOW VOLTAGE TERMINAL BOARD ALL COMPAC UNITS LOW VOLTAGE TERMINAL BOARD POWER FAN COMPRESSOR 1 ST STAGE HEAT COMMON Figure 8b. Thermostat Connection Diagram Figure 8c. LL357D4 Wiring Diagram & Thermostat Keys 28 ComPac 6/09-18
29 E4 E3 E2 E1 THERMOSTAT SWITCH TERMINALS COMMSTAT 3 LOR G W C Y R LOR G W C Y R NC C NO POWER ALARM DRY CONTACTS LOW BLDG TEMP OUTPUT NC THERMISTOR CONTACTS #1 #2 #3 #4 (FACTORY INSTALLED) C NO NC C NO NC C NO DRY CONTACTS HIGH BLDG TEMP ALARM HP/LP LOCKOUT DRY CONTACTS DRY CONTACTS CONNECT TO NORMALLY CLOSED DRY CONTACTS FROM SMOKE ALARM SMOKE ALARM JUMPER NC SMOKE C DRY CONTACTS NO COMPAC CONNECTION DESIGNATIONS TERMINAL BOARD TERMINAL BOARD NOTE: VAC connections only. UNIT 1 UNIT 2 COMPAC CONNECTION DESIGNATIONS 2. For immediate shutdown of air conditioner upon a signal from the smoke alarm, the jumper between terminals 8 and 10 in the ComPac I and ComPac II units must be removed and a jumper placed from terminals 8 and When connecting a smoke alarm to the smoke alarm input terminals (normally closed), remove the factory installed jumper wire and install the smoke alarm leads. IF LINE VOLTAGE IS BELOW 220 VAC, USE THE 208 TRANSFORMER TAP. Figure 8d. CommStat 3 Wiring Diagram 29 ComPac 6/09-18
30 3.1 Check-Out of Cooling Cycle Chapter 3 Start-Up Important: Be sure that the crankcase heater (if used) has been energized for at least 24 hours before starting the unit(s). Double-check all electrical connections before applying power. ComPac air conditioners with scroll compressors running on 3Ø power must be checked for proper rotation during the initial start-up. Please refer to Section 2.8 for determining if the 3Ø compressors are rotating correctly. Incorrect rotation can damage the compressor and is not covered by the warranty Procedure: 1. Set the cooling temperature on the wall thermostat to a point higher than the ambient temperature. Set the heating temperature to a temperature that is lower than the ambient. 2. Set the thermostat system switch in the AUTO position. Nothing should operate at this time. 3. Set the time delay in the ComPac I or ComPac II A/C control box to three minutes. Check the changeover setting of the H205A or dry bulb sensor and reset it if needed (ComPac II A/C only). See Section Slowly lower the thermostat's cooling temperature until the switch closes. The indoor fan should operate. Once the indoor fan turns on, allow approximately three minutes for the compressor to start. Note that the outdoor fan may not come on immediately, because it is cycled by refrigerant pressures. NOTE: (ComPac II A/C only) To check the system operation under different ambient conditions, the air temperature and enthalpy sensors must be "tricked". When outdoor ambient conditions are higher than the control setting, a component cooler aerosol may be sprayed directly into the enthalpy sensor to simulate low enthalpy conditions, causing the economizer damper to open. Alternately, when outdoor conditions are lower than the set point, a source of heat such as a hair dryer can be directed on the air temperature sensor to simulate warmer conditions, which will bring on mechanical cooling and start the compressor. 5. To stop cooling, slowly raise the thermostat cooling to a temperature higher than the ambient. If the unit fails to operate, refer to the troubleshooting information in Chapter 4. Follow the same procedure for additional units. NOTE: The fan purge allows the indoor fan to run for approximately 90 seconds after the compressor is off. This operation provides a small improvement in system S.E.E.R. 3.2 Check-Out of Heating Cycle Procedure: (Applies only to units with resistance elements) 1. Raise the heating temperature to a setting which is higher than the ambient temperature. The fan and electric heat should immediately cycle on. 2. Move the system switch to the "OFF" position. All functions should stop. NOTE: (ComPac II A/C only) The damper blade should remain closed during the heating cycle (unless the minimum position potentiometer has been set for constant ventilation A fully counterclockwise position corresponds to full closure of the damper. 30 ComPac 6/09-18
31 3.3 A/C Testing with LL357D4 Note: The LL357D4 does not require the units to be in phase. Procedure: (A/C Testing with LL357D4 Lead/Lag Control for Two Units) Prior to testing the air conditioners, the LL357D4 must be correctly configured. Please refer to the LL357D4 Product Data Sheet for instructions on installing and configuring the unit. 1. Set the cooling temperature on the wall thermostat to a point higher than the ambient temperature. Set the heating temperature to a temperature that is lower than the ambient temperature. Turn the selector switch to the off position. 2. Set the time delay on unit No. 1 to 3 minutes, and No. 2 to 5 minutes. 3. Set the change over setting of the enthalpy control to the d setting (ComPac II A/C only). 4. Provide power to A/C units and turn disconnects on. 5. Check incoming power to each unit. For units designed for operation on 208/230v, 60hz power supply, the transformer is factory wired for a 230 power supply. For a 208 power supply remove the orange lead from the transformer and connect the red lead. Insulate the orange lead. 6. Cooling. Turn the selector switch on the thermostat to the auto position. Slowly lower the cooling temperature until the switch closes. The indoor fan should operate on the lead unit. Once the indoor fan turns on, allow approximately 3 to 5 minutes for the compressor to start. Note that the outdoor fan may not come on immediately because it is cycled by refrigerant pressures. Next, lower the temperature until the switch closes. Follow the above procedures for the lag unit. The green light on the lead lag control should be on. One amber light will be on to identify the lead unit. The other light should be off. If the lag unit comes on with the lead unit the light for the lag unit will not come on. You should never have all 3 lights on at one time. Allow the units to run for 2 to 3 minutes then check the temperature differential between the return air and the supply air with digital thermometer. The temperature differential should be between 12 and 20 degrees depending on ambient temperature. Next, slowly raise the cooling temperature until the switch opens. The compressor and outdoor fan should turn off. The indoor fan will continue to run for 90 seconds until the fan purge times out. Raise the temperature until the switch opens. The lead unit will shut down accordingly to the same procedures as outlines above. Note: (ComPac II A/C only) To check the system operation under different ambient conditions, the air temperature and enthalpy sensors must be tricked. When outdoor ambient conditions are higher than the control setting, a component cooler aerosol may be sprayed directly into the enthalpy sensor to stimulate low enthalpy conditions, causing the economizer damper to open. Alternately, when outdoor conditions are lower than the set point, a source of heat such as a hair dryer can be directed on the enthalpy sensor to simulate warm conditions, which will bring on mechanical cooling and start the compressor. 7. Heating. Slowly raise the heating temperature until the switch closes. The fan and electrical heat should immediately cycle on. The unit should start blowing warm air in 2 to 3 minutes. Next, raise the temperature until the switch closes. Follow the above procedures for lag unit. Hold the manual advance button in for nine seconds the lead lag lights should switch. Next, slowly lower the temperature until the switches open. The lag unit should shut down immediately. Next, slowly lower the temperature until the switch opens, the lead unit should shut down immediately. 8. Replace thermostat cover and panels on the unit. 31 ComPac 6/09-18
32 Chapter 4 Troubleshooting 4.1 Overview A comprehensive understanding of the operation of the ComPac A/C is a prerequisite to troubleshooting. Please read the Chapter 1 for basic information about the unit. Marvair's ComPac air conditioners are thoroughly tested before they are shipped from the factory. Of course, it is possible that a defect may escape undetected, or damage may have occurred during transportation. However, the great majority of problems result from installation errors. If you experience difficulties with the ComPac A/C, please review the installation steps in Chapter 2. Much time can be saved by taking a thoughtful and orderly approach to troubleshooting. Start with a visual check - are there loose wires, crimped tubing, missing parts, etc? Begin deeper analysis only after making this initial inspection. The troubleshooting information in this manual is basic. The troubleshooting section contains problem/solution charts for general problems, followed by a compressor section. Not every problem can be anticipated. If you discover a problem that is not covered in this manual, we would be very grateful if you would bring it to the attention of our service department for incorporation in future revisions. As always, please exercise caution and good judgement when servicing the ComPac A/C. Use only safe and proven service techniques. Use refrigeration goggles when servicing the refrigeration circuit. WARNING The refrigerant circuit has hot surfaces, and the electrical voltages inside of the unit may be hazardous or lethal. SERVICE MAY BE PERFORMED ONLY BY QUALIFIED AND EXPERIENCED PERSONS. 4.2 Failure Symptoms Guide PROBLEM/SYMPTOM LIKELY CAUSE(S) CORRECTION A. Unit does not run. 1. Power supply problem. 1. Check power supply for adequate phase and voltage. Check wiring to unit and external breakers or fuses. NOTE: An internal anti-short-cycle timer will prevent the unit from starting for.2 to 8 minutes following start-up. B. Unit runs for long periods or continuously; cooling is insufficient. 2. Tripped internal disconnect. 3. Shut off by external thermostat or thermostat is defective. 4. Unit off on high or low pressure limit. 5. Internal component or connection failure. 1. Dirty filter or reduced airflow 2. Low refrigerant. 3. Component failure. 2. Check internal circuit protection devices for continuity. 3. Check operation of wall-mounted thermostat. 4. Reset pressure switch. 5. Check for loose wiring. Check components for failure. 1. Check air filter(s). Check blower operation. Remove airflow restriction. 2. Check for proper charge and possible refrigerant leak. 3. Check internal components, especially compressor for proper operation. 4. Unit undersized for job. 4. Add additional units for greater capacity. 32 ComPac 6/09-18
33 PROBLEM/SYMPTOM LIKELY CAUSE(S) CORRECTION 1. Loss or restriction of airflow. C. Unit cycles on high/low pressure limit. 1. Check blower assembly for proper operation. Look for airflow restrictions, e.g.. the air filter. Check blower motor and condenser fan. D. Unit blows fuses or trips circuit breaker. 2. Restriction in refrigerant circuit. 3. Refrigerant overcharge (following field service) 4. Defective pressure control. 1. Inadequate circuit ampacity. 2. Short, loose, or improper connection in field wiring. 3. Internal short circuit. Loose or improper connection(s) in unit. 2. Check for blockage or restriction, especially filter drier and capillary tube assembly. 3. Evacuate and recharge to factory specifications. 4. Check limit cutout pressures. Control is set to actuate at approximately 35 PSIG (low pressure) and 400 PSIG (high pressure). 1. Note electrical requirements in Chapter 2 and correct as necessary. 2. Check field wiring for errors. 3. Check wiring in unit. See wiring and schematic diagrams. Test components (especially the compressor) for shorts. 4. Excessively high or low supply voltage or phase loss (3ø only). E. Water on floor near unit. 1. Obstruction in condensate line. 2. Obstruction or leak in condensate pan. 4. Note voltage range limitations specific to the compressor troubleshooting section. 1. Check for clog or restriction. 2. Check pan for leak or blockage. F. No space heating or reduced heating (units equipped with resistance elements) 3. Unit is not level. 1. Defective heating element(s). 2. Thermal limit open. 3. Defective heater relay. 4. Open thermal cut-out (TCO). 3. Level unit. 1. Check resistance element(s) for continuity. 2. Check continuity across thermal limit switch. 3. Check relay for proper operation. Replace if defective. 4. Check across TCO (adjacent to element(s)) for continuity. It is normally closed. 4.3 Compressor Troubleshooting NOTE: It is important to rule out other component failures before condemning the compressor. The following electrical tests will aid diagnosis: 1. Start-Up Voltage: Measure the voltage at the compressor terminals during start-up. The voltage must exceed the minimum shown in Table 5, section 2.2, or compressor failure is likely. A low voltage condition must be corrected. 2. Running Amperage: Connect a clip-on type ammeter to the (common) lead to the compressor. Turn on the supply voltage and energize the unit. The compressor will initially draw high amperage; it should soon drop to the RLA value or less. If the amperage stays high, check the motor winding resistances. 33 ComPac 6/09-18
34 NOTE: Feel the top of the compressor to see if it has overheated. If it is hot, the internal overload may be open. You may have to wait several hours for it to reset. 3. Motor Winding Resistances: Using a digital volt-ohm meter (VOM), measure the resistance across the compressor windings as shown below. SINGLE PHASE C R 2 R 1 R 3 > R 2 > R 1 T 1 THREE PHASE R 2 R 1 R 3 = R 2 = R 1 S R 3 R R 3 = R 2 + R 1 T 2 T 3 R 3 Resistance can be measured as shown above. Any deviation from above values could indicate a defective compressor. 4. High Voltage/Insulation Test: Test internal leakage with a megohmeter. Attach one lead to the compressor case on a bare metal tube and to each compressor terminal to test the motor windings. A short circuit at high voltages indicates a motor defect. Do not do this test under vacuum. 5. On single phase models, check the capacitor by substitution. 4.4 Control Board Diagnosis The control board (see section 1.6a for a complete description of the control board) has a red diagnostic LED which indicates the lockout fault. The control board will enter into and indicate lockout if either of the fault conditions (LPS or HPS) occur twice. The contactor must be closed before the first fault condition can be recognized by the control board. The contactor will be closed 3 minutes after the unit is energized and only if cooling is required. The first fault condition will open the contactor and shutdown the unit. The contactor on the unit that has the fault condition must be closed before the second fault condition can be recognized by the control board. The contactor on the unit with the fault condition will close after 3 minutes if the unit is still calling for cooling and if the fault condition no longer exists. If you get a second fault condition, the contactor will open and shutdown the unit. The red led will have one blink if the high pressure switch has opened twice and will have two blinks if the low pressure switch has opened twice. The unit must be in the cooling mode (compressor contactor Closed) before a fault condition can occur. 34 ComPac 6/09-18
35 5.1 Scheduled Maintenance Marvair strongly recommends that the air conditioner be serviced a minimum of twice a year once prior to the heating season and once prior to the cooling season. At this time the filters, evaporator coil, condenser coil, the cabinet, and condensate drains should be serviced as described below. Also at this time, the air conditioner should be operated in the cooling and heating cycles as described in Chapter 3, Start-Up. In addition to this seasonal check-out, the ComPac A/C should be maintained as follows: Air Filter Replace the air filter whenever it is visibly dirty. Chapter 5 Maintenance Evaporator If the evaporator becomes clogged or dirty, it may be cleaned by careful vacuuming or with a commercial evaporator cleaning spray. DO NOT use a solvent containing bleach, acetone, or flammable substances. Turn off power before cleaning.. Be careful not to wet any of the electrical components. Be sure the unit has dried before restarting. Condenser Periodically inspect the outdoor condenser coil and the cabinet air reliefs for dirt or obstructions. Remove foreign objects such as leaves, paper, etc. If the condenser coil is dirty, it may be washed off with a commercial solvent intended for this purpose. TURN OFF POWER BEFORE CLEANING! Be sure that all electrical components are thoroughly dry before restoring power. Cabinet The cabinet may be cleaned with a sponge and warm, soapy water or a mild detergent. Do not use bleach, abrasive chemicals or harmful solvents. Drains Regularly check the primary and secondary condensate drains. The secondary drain has a stand pipe (on AVP24-72). An obstruction will force water to dump into the middle of the unit and drain out the sides of the ComPac, causing discoloration of the side panels. If discoloration is noted, service the drains. If a commercial drain solvent is used, flush out the drain pan and system with plenty of fresh water to prevent corrosion. Lubrication Oiling of the condenser fan motor or the evaporator blower motor is not recommended. 35 ComPac 6/09-18
36 6.1 Limited Product Warranty Chapter 6 Warranty If any part of your Marvair Air Conditioner, Heat Pump or Unit Ventilator fails because of a manufacturing defect within fifteen months from the date of original shipment from Marvair or within twelve months from the date of original start-up, whichever is the earlier date, Marvair will furnish without charge, EXW Cordele, Georgia, the required replacement part. Any transportation, related service labor, diagnosis calls, filter, driers, and refrigerant are not included. The owner must provide proof of the date of the original start-up. The owner s registration card filed with Marvair, the contractor s invoice, the certificate of occupancy or similar document are examples of proof of the date of the original start-up. In addition, if the hermetic compressor fails because of a manufacturing defect within sixty months from the date of original shipment from Marvair, Marvair will furnish without charge, EXW Cordele, Georgia, the required replacement part. Any related service labor, diagnosis calls, filter, driers and refrigerant are not included. Marvair will pay for non-priority shipping costs of the compressor during the first twelve months of the warranty period. After the first twelve months of the warranty period, all costs of shipment and risk of loss during the shipment of the compressor shall be the responsibility of the owner. The owner of the product may ship the allegedly defective or malfunctioning product or part to Marvair, at such owner s expense, and Marvair will diagnose the defect and, if the defect is covered under this warranty, Marvair will honor its warranty and furnish the required replacement part. All costs for shipment and risk of loss during shipment of the product to Marvair and back to the owner shall be the responsibility and liability of the owner. Upon written request by an owner, Marvair may arrange for remote diagnosis of the allegedly defective or malfunctioning product or part but all costs for transportation, lodging and related expenses with regard to such diagnostic services shall be the responsibility and liability of the owner. An owner requesting performance under this Warranty shall provide reasonable access to the allegedly defective or malfunctioning product or part to Marvair and its authorized agents and employees. This warranty applies only to products purchased and retained for use within the U.S.A., Canada, and Mexico. This warranty does not cover damage caused by improper installation, misuse of equipment or negligent servicing. THIS WARRANTY CONSTITUTES THE EXCLUSIVE REMEDY OF ANY PURCHASER OF A MARVAIR HEAT PUMP OR AIR CONDITIONER AND IS IN LIEU OF ALL OTHER WAR- RANTIES, EXPRESSED OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR USE, TO THE FULLEST EXTENT PERMITTED BY LAW. IN NO EVENT SHALL ANY IMPLIED WARRANTY OF MERCHANT- ABILITY OR FITNESS FOR USE EXCEED THE TERMS OF THE APPLICABLE WARRANTY STATED ABOVE AND MARVAIR SHALL HAVE NO OTHER OBLIGATION OR LIABILITY. IN NO EVENT SHALL MARVAIR BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAM- AGES OR MONETARY DAMAGES. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE-TO-STATE. Some states do not allow limitations or exclusions, so the above limitations and exclusions may not apply to you. Rev. 6/04 Supersedes 9/02 36 ComPac 6/09-18
37 6.2 Optional Silver Service If any part of your Marvair Heat Pump or Air Conditioner fails because of a manufacturing defect within fifteen months from the date of original shipment by Marvair or within twelve months from the date of original start-up, whichever is the earlier date, Marvair will furnish without charge, EXW Cordele, Georgia, the required replacement part and pay for the related service labor to replace the failed part. The owner must provide proof of the date of the original start-up. The owner s registration card filed with Marvair, the contractor s invoice, the certificate of occupancy or similar document are examples of proof of the date of the original start-up. When service is required, it must be performed during normal working hours (8:00 a.m. to 5:00 p.m.) Monday through Friday and must be performed by Marvair personnel or their designated Service Representative. The responsibility of the Owner of the Equipment includes the following: 1. To operate the equipment according to the manufacturer s instructions. 2. To provide easy accessibility for service. 3. To check and reset circuit breaker(s) and disconnect before calling for service. (Circuit breaker(s) may be in the main service panel. The disconnect is in the Marvair unit.) 4. To keep the unit clean and free of dirt. 5. To replace filters as required. (Filters are located in the lower front panel of the Marvair unit below the indoor blower section.) 6. To keep the outdoor coil section clean and free of leaves, paper, etc. 7. To pay the charges incurred when any of the above have not been done. 8. To pay for repair or replacement of any material or part other than those within the Marvair unit or thermostat itself. In addition, if the hermetic compressor fails because of a manufacturing defect within the second through fifth year from the date of original shipment by Marvair, Marvair will furnish without charge, EXW Cordele, Georgia, the required replacement. Any transportation, related service labor, diagnosis calls, filter, driers and refrigerant are not included. The owner of the product may ship the allegedly defective or malfunctioning product or part to Marvair, at such owner s expense, and Marvair will diagnose the defect and, if the defect is covered under this warranty, Marvair will honor its warranty and furnish the required replacement part. All costs for shipment and risk of loss during shipment of the product or part to Marvair and back to the owner shall be the responsibility and liability of the owner. Upon written request by an owner, Marvair may arrange for remote diagnosis of the allegedly defective or malfunctioning product or part but all costs for transportation, lodging and related expenses with regard to such diagnostic services shall be the responsibility and liability of the owner. An owner requesting performance under this Warranty shall provide reasonable access to the allegedly defective or malfunctioning product to Marvair and its authorized agents and employees. This warranty only applies to products purchased and retained for use within the U.S.A. This warranty does not cover damage caused by improper installation, misuse of equipment or negligent servicing. THIS WARRANTY AND SERVICE POLICY CONSTITUTE THE EXCLUSIVE REMEDY OF ANY PURCHASER OF A MARVAIR HEAT PUMP OR AIR CONDITIONER AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR USE, TO THE FULL- EST EXTENT PERMITTED BY LAW. IN NO EVENT SHALL ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR USE EXCEED THE TERMS OF THE APPLICABLE WARRANTY STATED ABOVE AND MARVAIR SHALL HAVE NO OTHER OBLIGATION OR LIABILITY. IN NO EVENT SHALL MARVAIR BE LIABLE FOR INCIDENTAL OR CONSE- QUENTIAL DAMAGES OR MONETARY DAMAGES. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE-TO-STATE. Some states do not allow limitations or exclusions, so the above limitations and exclusions may not apply to you. Rev. 6/04 Supersedes 9/02 37 ComPac 6/09-18
38 EXPLODED VIEWS AND PARTS LISTS Current parts lists and exploded views of the unit can be found on our web site at Click on the Service and Parts in the menu on the left hand side of the Home page. From the drop down menu, select Exploded Views. Once here, you can select your air conditioner or heat pump. The units are grouped by model and by the refrigerant R-22 or R-410A. 38 ComPac 6/09-18
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST
INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4 & 5 Ton 2-Stage Wall Mount Heat Pumps AND W38H, W43H, W49H and W61H Single Stage Wall Mount
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Packaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
E2 Series Electric Furnaces
E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS
INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODEL: WA121 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual : 2100-234 E Supersedes: 2100-234
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
Cooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013
Bulletin 30-34 / March 2013 INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES General The information on the following pages is to provide the installer the necessary information to properly install the
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER
INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. Manual : 2100-360B Supersedes: 2100-360A File: Volume
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat
Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage
with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor
INSTALLATION, OPERATION AND MAINTENANCE MANUAL For SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor Yeomans Chicago Corporation 3905 Enterprise Court P.O. Box 6620 Aurora, IL 60598-0620 Phone:
M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS. Models: WA301, WA361. Bard Manufacturing Company Bryan, Ohio 43506
INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGED AIR CONDITIONER Models: WA30, WA36 MIS-656 Bard Manufacturing Company Bryan, Ohio 43506 Since 94...Moving ahead just as planned. Manual No.: 20-92M Supersedes:
WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS. Models: WA182, WA242. Bard Manufacturing Company, Inc.
INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGED AIR CONDITIONER Models: WA82, WA242 Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 94...Moving ahead just as planned Manual No.: 200-369E Supersedes:
AIR CONDITIONER INSTALLATION MANUAL
INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
Dehumidifier Users manual. For Models: DH45S DH65S
Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but
PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167
PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
LOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
WALL MOUNTED PACKAGED WA372. Bard Manufacturing Company Bryan, Ohio 43506. Manual No.: 2100-404 Supersedes: File: Volume III, Tab 16 Date: 04-01-02
WALL MOUNTED PACKAGED INSTALLATION AIR CONDITIONER INSTRUCTIONS Models: WA302 WA372 MIS-656 Bard Manufacturing Company Bryan, Ohio 43506 Since 94...moving ahead just as planned. Manual No.: 20-404 Supersedes:
REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:
7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: [email protected] Website: www.centrair.ca
Central Air Conditioner
Central Air Conditioner USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL AIR CONDITIONER NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER. WELCOME
Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)
TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) WARNING - HIGH VOLTAGE AC electrical circuits are connected to this heater. Do not attempt any service work on the
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
FOXAIR 60/50 ALL MODELS
FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,
OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE
OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:
UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR
3 Phase Air Conditioner Component R2A3**GHR DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
MODEL IX -WAC/HP AIR CONDITIONERS & HEAT PUMPS FOR HIGHLY CORROSIVE & HAZARDOUS AREAS
1.5, 2, 2.5, 3, 3.5, 4, 5 & 6 Ton Industrial Grade Wall Mounted Air Conditioners & Heat Pumps Unit Application Bebco Model IX-WAC/HP Industrial Grade Air Conditioners & Heat Pumps are designed as a total
READ AND SAVE THESE INSTRUCTIONS. INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC, NEC AND LOCAL ELECTRICAL CODES.
16EC SERIES UPFLOW PACKAGED TERMINAL AIR CONDITIONERS Electric Heating and Cooling Unit Cooling - Only Unit INSTALLATION & OPERATION MANUAL IMPORTANT: READ AND SAVE THESE INSTRUCTIONS. INSTALLATION AND
48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT
48/50E-4SB 48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT GAS HEAT ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED
IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White
IMPORTANT INSTRUCTIONS & OPERATING MANUAL Houston 50 Inch Electric Wall Mounted Fireplace Black / White Model Number:MFE5050BK Model Number:MFE5050WH Read these instructions carefully before attempting
COMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION
Chromalox Installation, Operation RENEWAL PARTS IDENTIFICATION Portable Industrial Unit Blower Air Type DRA and DIVISION SALES REFERENCE DATE SECTION (Supersedes P-) PF-) NOVEMBER, 00 DRA PF- -0-00 Specifications
Air Conditioning Sign-Off Sheet
Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate
Roof Top Unit. Description Model Type Use With Air Distribution Box. Heat Pump B3200 3242 3311669.018 Integral Mechanical
RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Type Number Product Number Serial Number ADB Number ADB Serial Number Date Purchased Roof Top Unit Description Model Type Use With Air Distribution Box
Models: WA182, WA242. Contents. Cabinet Components. Functional Components " Exploded View... 3 " Usage List... 4. Control Panel.
REPLACEMENT PARTS MANUAL WALL MOUNTED PACKAGE AIR CONDITIONER Models: WA182, WA242 General Notes! Revised and/or additional pages may be issued from time to time.! A complete and current manual consists
T-Series Air Conditioner T62 Model
INSTRUCTION MANUAL T-Series Air Conditioner T62 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200
NSN 4120-01-21 4-3692
*TM 9-4120-388-14 TECHNICAL MANUAL Operator s, Unit, Direct Support, And General Support Maintenance Manual AIR CONDITIONER, VERTICAL, COMPACT, 18,000 BTU/HR 208 VOLT, 3 PHASE, 50/60 HERTZ NSN 4120-01-21
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.
FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and
Table Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler
WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler Installation Operation Maintenance The WMSLW/WMBLW series is designed for installation in a closet, utility
Air Conditioning System
Owner s Information Manual Air Conditioning ystem NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the space provided. This information,
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for
Low Profile Unit Cooler
Super-Flo Now available with EC Motors High Efficiency / High Reliability Low Profile Unit Cooler Publication No. 411.4 November, 2008 S A N I T A T I O N F O U N D A T I O N A L N A T I O N Air Defrost
WALL MOUNTED SPLIT TYPE AIR CONDITIONER
WALL MOUNTED SPLIT TYPE AIR CONDITIONER MANUAL 8 OM-G12-ACSON CONTENTS - Operating Guide page 1 - G12 Remote Controller Indication page 2 - Indicator Lights page 4 - Installation of Aroma page 5 - Auto
User s Information/Installation Instructions
Outdoor Heat Pump User s Information/Installation Instructions 13 SEER R-410A High Efficiency Split System These units have been designed and tested for capacity and effi ciency in accordance with A.R.I.
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
Split System Heat Pump Product Data
Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]
ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t. www.ice-air.com
80 Hartford Avenue Mount Vernon New York 10553 Tel: 914-668-4700 EXT. 203 Fax: 914-668-5643 www.ice-air.com Wo r l d C l a s s C o m f o r t Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE
Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.
Name of Equipment Silver King Model SKMCD1P/C1 This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Manufactured exclusively for McDonald s By Silver King Refrigeration,
Cooling Capacity CFM range @.5 in. w.c. (125 Pa)
N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air
Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types
Installation Guide LR-HWLV-HVAC TouchPRO Wireless Touchscreen Thermostat System Types Gas, oil, or electric heat with air conditioning Warm air, hot water, high efficiency furnaces, heat pumps, steam,
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
T15 AIR CONDITIONER INSTRUCTION MANUAL FOR: McLean Thermal 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200
INSTRUCTION MANUAL FOR: T15 AIR CONDITIONER McLean Thermal 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleanthermal.com INSTRUCTION MANUAL TABLE OF CONTENTS
SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2
SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with
WINDOW ROOM AIR CONDITIONER
WINDOW ROOM AIR CONDITIONER Installation and Operation Manual Electromechanical Remote Control CAPACITIES 220V - 60 HZ. 12,000; 18,000; 24000 BTU/HR 220V-240V - 50 HZ. 12,000; 18,000; 24000 BTU/HR Please
OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump
R-410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H)-System, DFC4(A/H)3-Outdoor, DFF4(A/H)H-Indoor Please read the operating instructions and safety precautions carefully
OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
G670 Intermittent Pilot Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control
HP switch LP switch Discharge thermo Comp. Surface thermo
1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator
JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator The Janus Pantheon mini operator does not typically require the provision of any additional site requirements other than
Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060
4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402
TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and
Heat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477
Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.
Model Number: Serial Number: Information Manual Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters. ATTENTION: IF YOU ARE NOT A LICENSED PLUMBER OR A LICENSED
INSTALLATION INSTRUCTIONS FOR INTERNATIONAL 9000 SERIES ROOF TOP AIR CONDITIONERS
RV Products Division INSTALLATION INSTRUCTIONS FOR INTERNATIONAL 9000 SERIES ROOF TOP AIR CONDITIONERS Service Contact: Coast to Coast RV Services Pty Ltd. 20 George Young St. Auburn NSW 2144 Australia