TECHNICAL SPECIFICATIONS
|
|
|
- Erika Fitzgerald
- 9 years ago
- Views:
Transcription
1 TECHNICAL SPECIFICATIONS INTRODUCTION This specification covers the minimum requirements for the engineering, procurement, installation and commissioning of the HVAC system to be provided inside the new LIBRARY building at IACS. 1.0 STANDARD SPECIFICATION 1.1 Scope of Work The complete scope of work shall cover supply, erection, testing and commissioning of the entire HVAC system as detailed under specification. 1.2 Basis of Design The entire system has been based and designed on climatological data available as given under Basis of Design and Scheme. 1.3 Terms and Definitions The followings terms have been used in the tender specifications, drawings etc. ISI : Bureau of Indian Standards. ASHRAE : American Society of Heating Refrigeration & Air-conditioning Engineers, USA. B.S. : British Standards. CMH : Cubic Meter per Hour. RPM : Revolutions per Minute. BTU/Hr. : British Thermal Unit per Hour. Kcal/Hr. : Kilo Calories per Hour. HZ : Hertz. H.P. : Horse Power SAG : Supply Air Grills. SAD : Supply Air Diffuser. SAF : Supply Air Filters. FD : Fire Damper. VCD : Volume Control Damper. RAD : Return Air Damper. FAD : Fresh Air Damper. RH : Relative Humidity. DB : Dry Bulb Temperature. WB : Wet Bulb Temperature. DP : Drain Point. 75
2 1.4 The codes, regulation as detailed below shall be followed in this contract :- 1. Safety code for air-conditioning (revised) amendment 1 : IS 659 : 1964 (reaffirmed 1991) 2. Safety code for mechanical Refrigeration : IS 660 : 1963 (reaffirmed 1991) 3. Testing of refrigeration compressors : IS 5111 : Aircooled heat exchangers (amendment 1) : IS : 1983 (reaffirmed 1991) 5. Packaged Air-conditioner(amendment 1991) : IS 8148 : 1976 (reaffirmed 1991) 6. Thermostats for use in refrigeration etc. : IS : 1965 (reaffirmed 1991) 7. Metal Duct Work : IS 655 : 1963 (reaffirmed 1991) 8. Steel for general structural purpose : IS 2062 : Refrigeration : As per ASHRAE / ISI Airconditioning & Refrigeration Air-conditioning institute Standards. 10. Hot Dip Zinc Coated Steel Tubes : IS 4736 : Colour code for the identification of pipe lines : IS 2379 : Specific requirements for the direct switching of the individual motors. 13. PVC insulated ( HD) Electric Cables for working voltage up including 1100 Volts. : IS 4064 ( Part II) 1978 : IS : 1554 ( Part I) 14. HRC Cartridge fuse links upto 650 Volts. : IS 2208 : Starter : IS 8554 ( Part I) Inspection and testing of installation : IS 732 ( Part III) Galvanized steel wire for fencing : IS 277 : Three phase induction motors : IS : PVC insulated ( heavy duty ) cables for working voltage up to 1.1. KV and up to 11 KV Grade respectively. 20. Code for practice for electrical wiring installations. : IS 1554 : 1981 Part I & II : IS 732 : Code for practice for earthing : IS
3 22. Specification for single phase small A/C & universal motors : IS : Circuit breaker A.C : IS 2516 : 1980 Part I & II 24. Contactors for A.C for voltage upto 1100 V. : IS 2959 : Low voltage switch gear and control gear assemblies. 26. Code of practice for selection of starters for AC induction motors : IS 8623 : 1993 Part I & II : IS Specification for cables glands : IS Code for selection, installation & maintenance of switch gear and control gear. : IS :1982 Part I to IV 29. Conduits for electrical installations : IS 9537 : 1981 Part I to IV 30. Permissible limits of noise level for rotating electrical machines. 31. Code of practice for installation and maintenance of motors : IS : 1987 : IS 3106 : HRC catridge fuse links upto 650 volts : IS : PVC insulated ( heavy duty) electric cables for working voltage upto & including 1100 watts. 34. Method for testing Panel type air filters for AC purposes. 35. Unbounded glass wool for thermal insulation (1st. Revision) 36. Expanded polystrene for thermal insulation purposes. ( 1st. revision) : IS ; 1554 ( Part I) : IS 7613 : 1975 (reaffirmed1991) : IS 3690 : 1974 : IS 4671 ; 1984 (reaffirmed) 1.5 Safety Codes The following IS codes shall be followed: Safety code for mechanical refrigeration : IS 660 Safety code for air conditioning : IS 659 Safety code for scaffolds & ladders : IS 3696 Code of practice for fire precaution in Welding & cutting operations Code for safety procedures and practices In electrical works : IS 3016 : IS
4 Code of practice for safety and health Requirements in electrical & gas welding And cutting operations. : IS Spacs All shop drawings shall be prepared by the A.C Contractor after examining the architectural & AC drawings. 2.0 DESIGN CONDITIONS The design parameters to be used for detailed design of the air conditioning system as follows: 2.1 Outside Ambient Conditions Summer : DB: 40 o C (105 o F) & WB: o C (83 o F). Monsoon: DB: 32.2 o C (90 o F) & WB: 30 o C (86 o F). Equipment performs to the above ambient conditions and not fail in conditions of 43 o C DB (dry bulb). 2.2 Inside Design Condition: Room Temperature : 23 o C o C Relative Humidity : 55% + 5% Detail Input conditions are mentioned below: Sl. No. A.C space Area (Sft) Lighting (W/sft) Occupancy Equipment (KW) Fresh Air (cfm) Sensible Load (BTU/ hr) Total load (BTU/ hr) ADP (of) Dehmfd Air (cfm) Rem arks First floor Library , , , DESIGN PARAMETES 3.1 Ducting work a) Method of Duct Design Equal friction method : b) Maximum air velocity in supply duct FPM : c) Maximum air velocity in return duct FPM : d) Friction loss in duct (maxm) MM Wg in 100 Mt run : 6.66 e) Maximum Velocity at supply air grill outlet FPM :
5 3.2 Insulation Maximum temperature rise in the supply air duct from Air-handlers outlet to farthest outlet in ºC NOISE AND VIBRATION CONTROLS 4.1 The air conditioning contractor must take all necessary precautions to have minimum noise generation and its transmission. Minimum vibration as permitted by IS relevant code shall be ensured. A few points for guidance only are given below: a) Double fire retardant flexible connections shall be provided from air discharge to outlet of air-handler to the duct. b) Vibration isolation pads of suitable thickness commensurate to loading for isolation of vibration shall be provided under all equipments. in consultation with manufacturer for proper selection of vibration isolators c) Flexible conduit connections of minimum diameter of 50mm to motors shall be provided. All loops should be large enough to allow connections to remain flexible. d) All conduit connection where conduits are 60mm or larger shall be made of 1.2 meters minimum length conduit installed in the shape of U and grossly slack to provide maximum vibration isolation. e) The floor supported piping shall be mounted on pipe supports with 7.5mm ribbed neoprene pads between the base plate of the pipes and the floors. f) All items suspended from false ceiling shall be isolated on separate hangers. g) In case of ducts, conduits, pipes & tubes the annular space between construction and penetrating element shall be sealed with sand cement plaster. h) The supply duct starting from air handling unit & plenum shall be provided with 12 mm thick acoustic lining as indicated in the tender drawings. i) The air-conditioning contractor shall take all other precautions or shall make his own arrangements even if not specified in the tender documents for eliminating high noise levels & shall minimize vibrations in all mechanical equipments without any additional cost. 5.0 GENERAL DESCRIPTION AND SPECIFICATION OF THE SYSTEM PROPOSED The air-conditioning of the IACS Kolkata shall be based on the air cooled Floor Mounted Type package unit for 1st Floor area. The 1st Floor area shall be air-conditioned by the Air Cooled Floor Mounted type packaged air conditioning unit. The Installed capacity of the A. C. Unit shall be 90 TR (approximately) (4 Nos 15 TR Air Cooled Scroll Package Unit as working + 2 Nos 15 TR unit as standby) The Condenser for the package unit shall be located outside the building and on a MS structure. The Supply air main ducting from the package Units shall be run above the false ceiling to the conditioned space as per layout enclosed with tender. The Conditioned air shall be distributed through the ceiling mounted type diffuser/ Grill as per distribution arrangement indicated in the drawings. 79
6 The return air shall be mixed with fresh air before passage over the cooling coils. The fresh air intake shall be complete with Air Intake Louvers with insect screen, & Manual & Motorized Volume Control damper. The Motorized VCD will be controlled through a CO2 Sensor and a controller. Vendor has to select the controller in such a way that, set point of CO 2 level and actual CO 2 quantum can be seen on the controller and the controller can give necessary 0-10mA output to the Motorized damper in such a way that based on the actual level of CO2 the fresh air damper will open / Close. The Controller should be such that, the minimum & Maximum value of the operating range can be adjusted in the controller. The Ductwork shall have provision for Volume control dampers for balancing the system. The entire supply air duct shall be insulated with the CLASS O ANTIMICROBIAL type 13 mm thick Nitrile rubber with Al. Foil Faced. All the Terminal Diffuser / Grill also with Al. Volume Control damper to have proper air distribution inside Conditioned area and for balancing purpose. To control the Noise level inside area as per noise level mentioned above, acoustic lining shall be provided inside the Duct up to three meters (3M) from the indoor unit mouth as mentioned in the drawing. Necessary Motorized Type Fire damper with spring return type actuator for supply air duct and Fusible link type fire damper as per UL555 shall be provided for Return air path for fire protection. Necessary electrical interlocking arrangement shall be provided with fire damper & Evaporator fan motor to shut down the AC fan on detection of fire. 5.1 Air cooled Package A. C. System Evaporator Section (Indoor unit): The evaporator fan should be with DIDW type centrifugal fan of AMCA certified having with the minimum followings: C45 carbon steel shaft Anti corrosion paint on shaft for durability Self-aligning and hermetically sealed durable ball bearings Tab-lock blades Statically and dynamically balanced to grade G4 (according to ISO 1940) The capacity of the each Evaporator fan for 16.5TR unit should be 6800 CFM. The Static pressure for the fan should be 35mm WG. The fan motor should have belt driven type with variable pitch pulley to adjust the CFM during commissioning & maintenance. The evaporator section should have with 4R deep cooling coil and with 50mm thick Synthetic washable type pre filter with 90% efficiency down to 10 micron. The Filter & Coil face velocity should not be more than 500 FPM. Each unit should have multiple scroll compressors. The unit should also with either Thermostatic or Electronic expansion valve. The drain pan of the indoor unit should be insulated with proper sandwich insulation to protect condensation. Oppose blade type Volume control damper to be provided outside the mouth of unit with ON / OFF marking for proper controlling & adjustment of Air quantity as per design condition. Following Protections should be considered for Each Package unit: 1. Single Phase & Phase reversal protection 2. High Pressure Cut out 80
7 3. Low pressure cut out. 4. Over Voltage & Under Voltage Protection. 5. Over load trip. The Microprocessor Controller should have the following features: 1. In the power saving mode, when the compressor is off, the condenser fan should also remain off. 2. Room temperature set point and the actual room temp. to be displayed though Electronic temperature sensor. 3. Programmable operation feature for one year with real time clock. 4. Auto restart after restoration of power. 5. Fault Diagnosis feature. 6. Anti recycle feature. Condenser The Air Cooled Condenser should be with aerofoil type low power consumption fan, heat exchanger to be coated with golden anticorrosive on aluminum Fins surface. The Cooling coil to be design in such a way that the package unit can work upto 45 o C. Refrigerant Pipe: The indoor & outdoor unit to be connected with the hard drawn copper pipe of minimum 18G thickness. All the elbow & reducer should be with the same thickness of the pipe. The size of the refrigerant pipes to be done by the vendor based of actual pipe length etc. The Refrigerant pipes should be Pressure tested at 400 PSI / 200 PSI and shall hold the pressure for 24 hrs. Proper Vacuuming should be done before charging of the refrigerant. Pipe Supports All refrigerant piping shall be supported to prevent deflection, bulking and vibration. Piping shall be supported at all changes in direction and at intervals of not more than 1.2 meters on straight runs. Pipe supports and clamps shall be subject to approval of consultant. Pipe work on roofs and floors shall be supported on off-set clamps, floor. The Pipe support stands shall be bolted to the concrete slab or steel members. Vertical pipe work shall be supported with trapeze hangers with rods suspended from inserts. Condensate drain pipe supports shall be capable of vertical adjustment after installation of piping. All pipe works passing through the walls, floors and roof slabs shall be provided with pipe sleeves of adequate size to allow the passage of insulation. Electrical Cabling All the connected Power cable should be with Al. Ar. Cable of 1100 V grade & control cable should be with Cu. Ar. Cable of 1100 V grade. The minimum size of Power cable should be 4 sqmm Aluminium & for control cable 2.5 sqmm copper. The incoming supply of the MCC should be with MCCB & all outgoing feeder should be with MCB & for compressor MCCB of suitable rating. The Outdoor Structure should be such that proper maintenance is possible and isolators to be provided near condensers with necessary 81
8 interlock with package unit, so that for maintenance / emergency condensers can switch off. Noise Levels Noise level inside the conditioned area resulting from the units shall not exceed the following: - NC 35 for office area All running equipments shall be isolated from the building structure and the support isolated from other items of equipment. All the units shall have anti-vibration mountings of approved make and these shall be subject to approval of the consultant. All the Air distribution system should be designed in such a way so that inside noise level should be within NC 35. Vibration Isolators All plant shall be isolated from the building structure and the support isolated from other items of equipment. The package units shall have anti-vibration mountings of approved make subject to consultants approval. Multi-layer rubber pads with square grid convolutions on both sides, spaced with steel shims and of a thickness to suit the points of uniform loading of the plant item but of a minimum thickness of 32 mm shall be spaced not more than 750 to 1000 mm apart. 6.0 DUCTWORK STANDARD SPECIFICATION FOR AIR CIRCULATION SYSTEM This section deals with supply, erection, testing & balancing of GI sheet metal duct work and air registers conforming to specifications as given below: Material for Ducing The duct shall be fabricated out of galvanised sheet, class VIII (Zinc coating 120 gm/m²ƒnas per the parameters given below which are conforming to IS Maximum Thickness Type of Transverse Bracing Upto S-drive, pocket or bar, slips, on 2.5 m ceners None 601 to S-drive, pocket or bar, slips, on 2.5 m Centers, S-drive 25 mm pocket, or 25 mm bar slips on 2.5 m centers. 25 x 25 x 3 mm, angles, 1.2 m from joint. 82
9 751 to Drive, 25 mm pocket or 25 mm bar slips, on 2.5 m centers 40 x 40 mm angles connections to mm bar slips, with 35 x 3 mm bar reinforcing on 2.5 m centers 1501 to x 40 mm angle connections, or 40 mm bar slips, 1 m maximum centers with 35 x 3 mm bar reinforcing. 25 x 25 x 3 mm angles, 1.2 m from joint. 40 x 40 x 3 mm angles, 1.2 m from joints. 40 x 40 3 mm diagonal angles, or 40 x 40 x 3 mm angle 60 cm from joint. * Ducts 2250 mm and larger require special field study for hanging and supporting methods. In addition to above the following points should be also taken into account while fabrication of ducts. a) All ducts of size larger than 450mm shall be cross broken. b) All ducts shall be supported from the ceiling / slab by means of MS rods of dia 9mm with MS angle of size 40 x 40 x 5 mm at the bottom with neoprene pad in between the duct & MS angle. The ducts shall be suspended from the ceiling with the help of dash fasteners. Provision for necessary ancillary materials required for hanging the ducts shall be arranged by the contractor. c) The vanes shall be provided wherever required and shall be securely fastened to prevent noise & vibration. d) The rubber gasket shall be installed between duct flanges in all connections and joints. e) All flanges and supports should be primer coated. f) The flexible joints shall be fitted to the delivery side of AHU fans with Fire Retardant Double canvass. The length of flexible joints should not be less than 150 mm and not more than 300 mm between face. g) The ducting work can be modified if deemed necessary in consultation with the Engineer in Charge to suit actual site conditions in the building. h) Box Type Dampers & Splitters These dampers shall be provided in the ducting work for proper control and balancing of air distribution. All dampers shall be louver type robust construction. These dampers shall be fitted with easily accessible operating mechanism, complete with links, levers, quadrant for proper control and setting in a desired position. The position of the handle of the damper operating mechanism shall be clearly visible and shall indicate the position of the damper in the duct. All dampers, splitters shall be fabricated out of G.S. sheet of two gauges higher than the duct 83
10 piece having these fittings. Dampers shall be installed in duct at all required locations. No extra payment shall be made separately since these form part of Air Circulation System. NOTE: In case angle iron supports are not feasible to be installed for supporting the ducts due to height constraint then the contractor shall support the ducts with M.S flats of at least double the thickness of the angle iron supports. A) THE SUPPLY AND RETURN AIR GRILLS AND CEILING DIFFUSERS The supply and return air grills and ceiling diffusers shall be made of powder coated extruded aluminum sections. The supply air grills / diffusers shall be provided with screw operated opposed blade volume control device made of extruded aluminum in black anodized finish. All grills / diffusers shall have soft continuous rubber / foam gasket between the periphery of the grills / diffusers and surface on which it has to be mounted. The colour of grills / diffuser shall be as per the approval of the Engineer in Charge. B) LINEAR SUPPLY AND RETURN GRILLS The linear continuous supply / return air grills shall be made of powder coated extruded aluminum construction with fixed horizontal bars. The thickness of fixed bar louvers shall be 5mm in front and the flange shall be 20mm wide with round edges. The register shall be suitable for concealed fixing and horizontal bars of the grills shall mechanically crimp from the back to hold them. The colour of grills shall be as per the approval of the Engineer in Charge. The volume control device made of extruded aluminum construction in black anodized finish shall be provided in supply air duct collars only. C) SQUARE / RECTANGULAR CEILING DIFFUSERS The square / rectangular ceiling diffusers shall be made of powder coated extruded aluminum construction with flush fixed pattern. The diffusers shall have Anti-Smudge ring and spring loaded removable central core in various pattern for air flow direction. The diffusers shall be mounted by concealed screw fixing arrangement. The volume control device of extruded aluminum construction in black anodized finish shall be provided in supply air diffusers. The colour of diffuser shall be as per the approval of the Engineer in Charge. D) VOLUME CONTROL DEVICE The opposed blade volume control device shall be made of Powder Coated extruded aluminum construction in black anodized finish. Opposed blades shall be pivoted to extruded aluminum frame with Nylon bushes. Specially designed blade shall have an overlapping lip which shall ensure a tight closure. E) FRESH AIR INTAKE LOUVERS WITH BIRD SCREEN The fresh air intake louvers at least 50mm deep will be made of powder coated extruded aluminum construction. Bird / insect screen will be provided with the intake louvers. The blades shall be inclined at 45 degree on a 40mm blade pitch to minimize water ingress. The lowest blade of the assembly shall be extended out slightly to facilitate disposal of rain water without falling on door / wall on which it is mounted. 84
11 The intake louvers shall be provided with factory fitted aluminum construction volume control dampers in black anodized finish. PAINTING All ducts collar / shoot behind the grills / diffuser shall be given at least two coats oil black enamel paints. TESTING The complete duct system shall be tested for air leakage & complete air distribution system shall be balanced in accordance with air quantities indicated on the approved drawing STANDARD SPECIFICATION OF THERMAL / ACOUSTIC INSULATION This section deals with supply and fixing of thermal / acoustic insulation of ducts, pipes etc. as per the specification given in this section. MATERIAL OF INSULATION The insulation material of the following kind shall be used for cold insulation. a) FOR DUCT INSULATION WITH CLASS O ANTI-MICROBIAL TYPE 13MM NITRIAL RUBBER HAVING FOLLOWING SPECIFICATION: - Insulation material shall be Closed Cell Elastomeric Nitrile Rubber - Density of Material shall be between 40 to 60 Kg/m3 - Thermal conductivity of elastomeric Nitrile rubber shall not exceed W/mK at mean temperature of 0 C - Insulation material shall have anti-microbial product, which is EPA (Environmental Protection Agency), USA approved, as an integral part of insulation that cannot be washed off or worn off. - It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi and should confirm to following standards: Fungi Resistance ASTM G21 and Bacterial resistance ASTM 2180 / ASTM G The insulation shall have fire performance such that it passes Class 1 as per BS476 Part 7 for surface spread of flame as per BS 476 and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class O Fire category as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations Material should be FM (Factory Mutual), USA approved. 85
12 - Water vapour permeability shall not exceed 1.74 x Kg / (m.s.pa), i.e. Moisture Diffusion Resistance Factor or µ value should be minimum The Insulation materials should be with self adhesive type and with Al. Foil Faced to protect against mechanical damage. The Thermal conductivity values in W/m. K of fiberglass shall confirm to following: Mean Temperature o C Density in Kg/cmt Thermal Conductivity W/m.k For Duct Lining 25 o C o C The sample of insulation material shall be submitted for approval to the Engineer in Charge and the sample shall be tested for thermal conductivity values by the contractor at his own expense. Adhesive used for setting the insulation shall be non-flammable, vapor proof, CPRX compound. INSULATION ON SHEET METAL DUCTING The thickness of insulation used on ducting shall be as detailed below: Conditioned space a) Supply Air Duct Insulated with 13 mm thick Aluminium faced Close cell Nitril Rubber The application of insulation should be carried out in workman like manner as detailed below Insulation of Ducting with Aluminium FACSD Fibre Glass a) Duct surface to be cleaned thoroughly b) To apply two coats of adhesive Compound. c) To fix factory pre-laminated aluminium faced self adhesive type close cell Nitril rubber of specified thickness. d) Fix self-adhesive aluminum tape of 50 mm width on all longitudinal / Transverse joints. e) Finally fix PVC straps of 19mm width at every 300mm centre to centre. 86
13 ACOUSTIC LINING OF DUCT The material to be used for duct lining shall be 25mm thick resin bonded fiber glass having a density of 32 Kg/m³ or 12 mm thick fibre glass rigid board of density 48 Kg/m³ & covered with 0.5 mm thick perforated aluminum sheet. The lining of initial length of the duct shall be done as shown in the tender layout drawings & shall be carried out as follows. a) Clean the duct piece thoroughly, b) To apply two coats of CRPX compound. c) Fix the fiber glass of suitable thickness & cover with fiber glass tissue paper. d) Cover the insulation board with 0.5mm thick perforated aluminium sheet with at least 20% to 25% perforations e) Secure the aluminium sheet with GI frame work with cadmium coated self taping screws with washers. Special Notes: 1. All the party should submit the Equipment rating chart at different temperature / outside condition. 2. Compressor ratting chart should be submitted along with tender for proper technical evaluation of the capacity offered. 3. Vendor should submit the technical Data Sheet & Shop drawing within 7 days from date of issue of order for necessary approval by consultant before physically start the work at site. 4. After Commissioning vendor should conduct performance testing of the entire system for 72 hrs. 5. Vendor should submit the complete operation & maintenance manual containing As Built Drawing, Do s & Don t, Operation procedure, Set points of different parameters, Catalogue & Technical details etc. 87
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
RPV - RP - RA air handling units
APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &
hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE AUTONOMOUS AIR CONDITIONERS O ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 72-17 AUTONOMOUS AIR CONDITIONERS
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
SECTION 15190 HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section 15010.
SECTION 15190 HVAC INSULATION PART ONE - GENERAL PART 1 - GENERAL 1.01 DESCRIPTION A. All work specified in this Section is subject to the provisions of Section 15010. B. All insulation products shall
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
INDEX. Chapter8. air master. Perforated Ceiling Diffusers
Chapter8 INDEX A. Perforated ceiling diffuser 1. Perforated ceiling diffuser with plenum box..: APCD+P...8.1. Perforated ceiling diffuser with damper....: APCD...8. Standard sizes...8. Fixing details...8.
A. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.
SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel
BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad
BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad PLEASE MARK TICK ON LEFT BOX WHICH EQUIPMENT YOU HAVE QUOTED PROPOSAL BASED ON CHINESE EQUIPMENT
B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
Modular Access Floor for Data Center. From Rack to Row to Room to Building
Modular Access Floor for Data Center From Rack to Row to Room to Building Why using Scneider Electric modular access floor in Data Centers The evolution of modern Data Centers emphasizes specific exigencies
1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None
1-Way Chilled Water Cassettes KCO 60, 90 & 120 Technical Brochure TM KCO-W.1GB Date : November 2005 Supersedes : None General Features Control valve (optional) Air vent In-tube electric heating elements
security products metric sizes Redefine your comfort zone. www.titus-hvac.com
metric sizes secure lethal objects monitoring areas suicide deterrent Redefine your comfort zone. www.titus-hvac.com humid areas prevents corrosion minimum security medium security maximum security Table
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions
Cold Room & Refrigeration System (Casserole Assembly) No of units: 1
Technical Specifications Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 For chiller storage of all sorts of items Chiller storage temperature: 2-5 C Provides excellent thermal efficiency
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
PLUG and PLAY VRV Connection
PLUG and PLAY VRV Connection All seasons Perfect c mfort Heating Air Conditioning Applied Systems Refrigeration Pricelist 2010 Air Handling Units for > VRV Indoor units and Air Handling Units on single
Mechanical Rooftop Custom Capabilities
Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
ROOF TOP MOUNTED Air Handler Specification
ROOF TOP MOUNTED Air Handler Specification PART 1: GENERAL (Model RT) Mechanical Specification 1.01 WORK INCLUDED A. Provide complete air handling unit(s) suitable for outdoor installation. Contractor
A. Section includes air conditioning units, controls and control panels.
SECTION 23 81 23 - COMPUTER-ROOM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes air conditioning units, controls and control panels. 1.2 REFERENCES A. Air-Conditioning, Heating, and
SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
SECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
BOQ SPECIFICATIONS. The Blind system consist of a coated aluminium tube of 38 mm diameter with provision of fabric clamping.
BOQ SPECIFICATIONS VERTICAL BLINDS Vertical Blinds made of glass fibre fabrics in width 5 (or 4 ). Minimum overlapping of ¾ in fabric. Top aluminium anodized rail of 1.4 mm thickness. 2 inch wide channel
Basics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
Central Air Conditioning Plants
Central Air Conditioning Plants In our department, these plants (Air cooled or water cooled) are commonly available above 10 TR up to 100 TR. These types of plants are more suitable for large installations
Commercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water
2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation
Nominal Life Expectancy for Building Components
Nominal Life Expectancy for Building Components Building System Page A. HVAC 2 B. Elevator/Escalator 6 C. Plumbing 7 D. Roofing 8 E. Electrical 10 F. Fire/Life/Safety/Security System 11 G. Interior Finishes
DSRQ - DSRSQ - DSRSQ-THERM
DSRQ - DSRSQ - DSRSQ-THERM Specification item: Variable geometry diffuser on 597x597 mm panel developed for rooms with high ceilings where a long throw and a high induction ratio are required. Made up
HVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
SINGLE PACKAGE VERTICAL AIR CONDITIONERS
SINGLE PACKAGE VERTICAL AIR CONDITIONERS AIR CONDITIONERS l HEAT PUMPS l ELECTRIC HEAT QUIETER BY DESIGN SIMPLE TO INSTALL CONCEALED INSTALLATION www.friedrich.com VERT-I-PAK ideal for extended stay properties,
Installation Manual CLIFC Fan & Coil Variable Speed
Installation Manual CLIFC Fan & Coil Variable Speed General Description GENERAL DESCRIPTION FANS EQUIPMENT Totally Factory assembled within the unit all piping, wiring, and required controls for operation
MODEL HSR-007 Direct Drive Rolling Steel
MODEL HSR-007 Direct Drive Rolling Steel 200 Fairview Road, Unit #2, Barrie, Ontario L4N 8Z8 Tel: 866-792-9968 or 705-792-9968 Fax: 705-735-9564 www.tnrdoors.com email: [email protected] Model HSR-007
Elegant ECM. ELEGANT ECM air conditioners allow. The range is made up of 12 models: Ceiling Air Conditioner
Elegant ECM Ceiling Air Conditioner ELEGANT ECM air conditioners allow to heat and cool very economically small and medium areas, like shops, show rooms, workshops, supermarkets. The range is made up of
COMMISSIONING OF HVAC SYSTEMS
FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
Chilled Water Fan Coil Unit. Model:HFCA Size 03~14
Chilled Water Fan Coil Unit Model:HFCA Size 03~4 The Best Choice for Comfort =The Best Results Quiet Comfort Slope coil avoid air flow perpendicular impact Low noise permanent split capacitor motor Metal
NATIONAL INSTITUTE OF BIOLOGICALS
Short Term Notice Inviting Quotations Quotations No. S.1-36/07/NIB/Engg. (Civil) Invitation to short term quotations for Repairing of damaged gypsum board false ceiling and painting with epoxy paint in
Bill of Quantities. Factory Services Date: 23.08.2010
Factory Services Date: 23.08.2010 Bill of Quantities 1. All items of work under this Contract shall be executed strictly to fulfill the requirements laid down under Basis of Design in the specifications.
Refrigeration Installation 101
Refrigeration Installation 101 Hundreds of Installations Refrigerated Cases 2 Compressor Racks 3 Condensing Units 4 Walk-in Boxes 5 Some were done very well 6 Some had some issues... 7 8 Some seemingly
UR...3 URX CF...7 URHE CF...11. Heat recovery unit. Heat recovery unit with refrigerant circuit(442-1947 cfm)
UR...3 Heat recovery unit URX CF...7 Heat recovery unit with refrigerant circuit(442-1947 cfm) URHE CF...11 High efficiency heat recovery unit with refrigeration circuit(588-1942 cfm) UR Heat recovery
TARIFF CODE and updates standard
TARIFF CODE and updates standard No HS CODE AHTN CODE PRODUCT DESCRIPTION PRODUCT TYPE STANDARDS IDENTIFIED 7207 Semi finished products of iron or non alloy steel Containing by weight less than 0.25% of
Manual piston sampler...m 11
SAMPLING Manual piston sampler...m 11 Screw sampler...prec 22...PREC 100 Slide sampler...pr 55 Rotative screw sampler...prv Piston sampler...p 11 Sampler on belt conveyor...pba Rotating cup sampler...pgr
Airline. small air handlers and extract fan units. VES Airline part of a complete range of innovative, flexible products from the HVAC experts
Lo w p r o f i l e small air handlers and extract fan units Duties to 0.55m 3 /sec Available with the Electroline fitted control panel Ceiling void friendly - unit heights from 190mm to 350mm Airline VES
BILL OF QUANTITY FOR THE WORK OF "REPAIRING OF CIVIL & PLUMBING WORKS INSIDE AND OUTSIDE OF THE WORKSHOP"
BILL OF QUANTITY FOR THE WORK OF "REPAIRING OF CIVIL & PLUMBING WORKS INSIDE AND OUTSIDE OF THE WORKSHOP" Sl. 1 DISMANTLING WORK 1.1 Stripping off worn out plaster (outside and inside) and raking out joints
VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6
- B 1 Product Detail Engineering Data... B2 Structural Support... B6 Engineering Specifications... B9 - B 2 Engineering Data REMARK: Do not use for construction. Refer to factory certified dimensions &
FIRE DAMPER APPLICATION GUIDE
FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire
Acumen Enterprises, Inc.
Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter
TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING
TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET
CEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
1.2 Refrigerant Equipment. General
Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or
Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
Operation and Installation Manual. Max Series
Operation and Installation Manual Max Series Models 95MAX 155MAX 155ECM 155MAXRX 200MAX 200MAXRX MAXTOP 195DCS 300DCS 200ERV 200ERVD New Auto Dehumidistat Function prevents unwanted use of the dehumidistat
Dehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
SWIMMING POOL AIR-HANDLING UNITS KU-DB Series
SWIMMING POOL AIR-HANDLING UNITS KU-DB Series ME20 proklima 2 SWIMMING POOL AIR-HANDLING UNITS - KU-DB Series proklima 3 TABLE OF CONTENTS 1 Introduction page 3 2 Features page 4 SWIMMING POOL AREA t =
The Embassy of the United States of America invites you to submit an offer for supply and install the following A/Cs:
RFQ number PR4877728 The Embassy of the United States of America invites you to submit an offer for supply and install the following A/Cs: A- Supplying and installing 30 high wall A/C split unit 3HP- 24,000
Grilles & Diffusers Series LFP Incorporating
Grilles & Diffusers Incorporating Series LFP Produce a stable linear throw, creating an area of clean air with minimal diffusion Perfect for areas like clean rooms and operating theatres Tile replacer
STANDARD SPECIFICATION. The followings terms have been used in the tender specifications, drawings etc.
STANDARD SPECIFICATION The followings terms have been used in the tender specifications, drawings etc. ISI ASHRAE ISHRAE ASME ASA B.S. CMH US GPM IGPM RPM BTU/Hr. Kcal/Hr. HZ H.P. Kg/Cm 2 SAG SAD SAF FD
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
CADB and CADT-D / DI / DC Series
HEAT RECOVERY UNITS CADB and CADT-D / DI / DC Series NEW The CADB, CADT heat recovery range consists of: - Self-supporting casing with extruded aluminium profile structure and beige plastic coated galvanised
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Single Package Vertical Air Conditioners. Vert-I-Pak
Single Package Vertical Air Conditioners Vert-I-Pak Installs easily in a closet for quiet operation and provides a more homelike appearance for your guests. THE EXPERTS IN ROOM AIR CONDITIONING A Better
catalog Single Package Vertical Air Conditioners and Heat Pumps
catalog Single Package Vertical Air Conditioners and Heat Pumps Catalog: SK145.00-EG1 (1008) TABLE OF CONTENTS Single Package Vertical Units Introduction...............................................................................
Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue. Photo Essay
Original HVAC Units: Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue Photo Essay One fan motor draws air from the lower section of the unit,
Packaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system
All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
ORAY PREFABRICATED GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS
GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS ~GSM SHELTER CONTAINERS ARE PROCUDED ACCORDING TO THE DEMANDED SIZE.~ (W x L x H) Page1 GENERAL FEAUTURES Environmental Conditions : Maximum outdoor temperature
TECHNICAL SPECIFICATIONS & TERMS AND CONDITIONS FOR SOLAR WATER HEATER (FPC/ETC)
TECHNICAL SPECIFICATIONS & TERMS AND CONDITIONS FOR SOLAR WATER HEATER (FPC/ETC) Prepared by Committee for Technology Assessment and Analyzing the installation of Solar Water Heater Systems in Government
FOXAIR 60/50 ALL MODELS
FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,
Cooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
SECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
marine/bespoke split applications
split applications marine/bespoke evaporators, condensers and split air conditioning systems suitable for a multitude of applications such as coastal, extreme high and low ambients, harsh dusty environments
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List
FINAL December 2012 SECTION 233100 DUCTWORK
SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insula tion shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation
2. AIRCONDITIONING AND REFRIGERATION
2. AIRCONDITIONING AND REFRIGERATION 1. INTRODUCTION Air Conditioning and Refrigeration is an important area where in lot of self-employment opportunities are available. Now a day there is hardly a house
WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013
Bulletin 30-34 / March 2013 INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES General The information on the following pages is to provide the installer the necessary information to properly install the
Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales
Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR LAUNDRY EQUIPMENT MAINTENANCE Maintenance Module 32 March 2011 issue This document has been compiled by the Engineering
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
HVAC Air Duct Leakage. Eli P. Howard, III Group Director Technical Resources SMACNA
HVAC Air Duct Leakage Eli P. Howard, III Group Director Technical Resources SMACNA Key Variables that Affect the Amount of Leakage Static Pressure Amount of Duct Openings in the Duct Surface Seams, Joints,
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible
CENTRAL AIRCONDITIONING PLANT FOR AIRCONDITIONING OF AUDITORIUM AT INDIAN INSTITUTE OF PETROLEUM, DEHRADUN.
CENTRAL AIRCONDITIONING PLANT FOR AIRCONDITIONING OF AUDITORIUM AT INDIAN INSTITUTE OF PETROLEUM, DEHRADUN. 1 0. Preamble Auditorium at Indian Institute of petroleum has seating capacity of 500 persons.
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for
SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request
SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
SECTION 23 34 13. A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer.
PART 1 GENERAL SECTION 23 34 13 HVAC FANS 1.01 SUMMARY A. Section Includes: 1. Exhaust fans. 2. Transfer fans. B. Related Documents: 1. Drawings and general provisions of the Contract, including General
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per