Fire Alarm Systems Technical Note 1 - Installation and Design Guidance (Ref: QM_OHSD_FS008)

Size: px
Start display at page:

Download "Fire Alarm Systems Technical Note 1 - Installation and Design Guidance (Ref: QM_OHSD_FS008)"

Transcription

1 Occupational Health and Safety Directorate Fire Alarm Systems Technical Note 1 - Installation and Design Guidance (Ref: QM_OHSD_FS008) QM_OHSD_FS008_Fire Alarm Systems-Technical Note 1- Installation and Guidance-Academic Buildings Status: Live June 2013 Author: Dennis Brown

2 Introduction

3 1.0 Introduction The following document is for the benefit of all parties concerned in the specification, design, installation, commissioning and handover of fire alarm systems in any building that is part of Queen Mary University of London s (QMUL) demise. The maintenance of all QMUL s existing fire alarm systems, although not explicitly addressed in this guidance note, should be carried out in accordance with BS 5839: Part 1, 2013 Fire detection and fire alarm systems for buildings Part 1: Code of practice for system Design, Installation, Commissioning and Maintenance of systems in non-domestic premises and under the instruction of the relevant campus maintenance manager. This document outlines industry guidance and best practice in addition to providing a general over view of QMUL s fire safety objectives when installing fire detection and will help ensure communality of systems across all campuses. It also aims to ensure that all new & refurbished fire alarm systems meet the relevant design guidance documents to afford all occupants a highest practicable level of safety in the event of fire. 2.0 Statement of Intent 2.1 The provision of a fire alarm system and a method to give warning to building occupants in the event of an outbreak of fire is a legal requirement. The addition of automatic fire detection (AFD) is very often desirable to assist in early detection, provide warning to occupants, benefit property protection and in some instances act as a compensatory feature for a lack of fire protection or where an extended travel distance maybe present within building. Therefore, the design, complexity and cost of a fire alarm system including both capital and whole life maintenance costs, will need to be considered carefully in the project design phase. 2.2 The following information will be of assistance to design consultants, project managers and contractors employed by QMUL or its agents. It is to be regarded as a general statement of requirements and is in addition to any British Standard recommendation or other instructions received from either the local fire service authority, building control authorities or college insurers. 3.0 Design Standards 3.1 Fire detection systems for all academic buildings with no sleeping risk should be designed, installed and commissioned in accordance with BS 5839: Part 1, A2:2008:2013 Fire detection and fire alarm systems for buildings Part 1: Code of practice for system Design, Installation, Commissioning and Maintenance of systems in non-domestic premises: and all relevant devices, control and indicating equipment and power supplies shall meet the relevant guidance in the BS EN 54 series. It is a mandatory requirement of QMUL that the company appointed to design, install, commission and maintain fire alarm systems in any Queen Mary building is not only competent to do so but can demonstrate their competence by way of a third party certification scheme. Two such schemes that QMUL will accept is the British Approvals of Fire 3.2 Unwanted Alarms QMUL is committed to reducing unwanted fire alarm signals in all of its buildings and has several initiatives in place: such as

4 covering detectors and changing detection from smoke to fixed heat during construction or other works which could cause an alarm. More information can be found in the document Fire Safety Guidance for Project Managers. All those responsible for Project Management, should ensure that provisional resources and time are provided to employ the Universities appointed fire alarm Maintenance Company to undertake this task before any construction works commence in any building. Subsequently, fire alarm system designers should take considerable care to ensure that their fire alarm design proposal continues to reduce unwanted fire alarms through consideration and understanding of room/space function where the detection is to be provided. This will help substantially reduce the potential for unwanted alarms. In all cases the principles in BS 5839: Part 1, A2:2008:2013 Fire detection and fire alarm systems for buildings Part 1: Code of practice for system Design, Installation, Commissioning and Maintenance of systems in non- domestic premises; Section 3: Limitation of false alarms should be followed 4.0 General Requirements 4.1 All new fire alarm systems provided in College properties must use standard equipment and open protocols to ensure communality of systems, efficient maintenance, control of software and engineering access. No other fire alarm panels or systems will be acceptable unless written permission of QMUL s Electrical Maintenance Manager and Fire Safety Team is obtained. 4.2 Loop Capacity- In accordance with good engineering practice all addressable system loops should be designed so that numbers of devices on each loop is limited to ensure there is approximately 20% spare capacity on each loop. This will allow for a degree of flexibility were significant design changes occur to the building. 5.0 Design Issues Fire Detection Category and Type 5.1 The design fire safety objective for all Queen Mary academic buildings fire alarm systems is, as a minimum, to give early warning of fire to all occupants in the building by informing them that smoke has entered part of the escape route. This will allow lone workers who may be located in the building outside normal working hours to escape in all circumstances. During normal working hours there will inevitably be a large number of persons present in each of the buildings who could raise the fire alarm manually. Subsequently all new and refurbished fire alarm systems are to meet a minimum standard of BS 5839 Part 1: Type L4M and a maximum standard of Type L3M provision for automatic fire detection. The extent of L3 coverage required should be identified during the design phase and should be done in consultation with QMUL Fire Safety Advisers with consideration of relevant local authority guidance documents**. Additional smoke detection to category type L5M may be considered for specific areas (high risk/ intrinsic value) or where part of an engineered solution. This requirement again should be identified during the risk assessment process and in all cases the QMUL Fire Safety Advisers should be consulted. To mitigate the risk of arson all toilets that DO NOT open onto the escape route i.e. where smoke detection is fitted as in accordance with the minimum L4M system, then the

5 toilet should be fitted with smoke detection to ensure any outbreak of fire will be detected. In particular areas of some buildings a specific category of fire alarm system is required as a compensatory feature for a deviation away from prescriptive fire safety design guidance. QMUL Fire Safety Advisers should be consulted about any change to a building s fire alarm system. **LFEPA Guidance Note GN48-Electro-Magentic Door Holders 5.2 Only fire detection equipment and peripheral devices manufactured and tested by Apollo Fire Detectors Ltd are to be used for all new fire alarm systems. This will ensure communality of systems across all Queen Mary University of London Estate. 5.3 Details can be found at: All new fire alarm systems will be hard wired. However, there may be some instances in which wireless systems need to be adopted, but written confirmation is provided by the relevant maintenance manager and Fire Safety Advisers where necessary. 5.4 Only Apollo XP95 Optical Smoke Detection should be used in escape routes, as systems installed in all academic buildings will be of an L category as per BS 5839 Part 1: All buildings and projects must be assessed specifically for the risk(s) present and the designer should, in all cases, select the most appropriate type of detector through consultation with the individual buildings occupiers, Project Managers and where required, QMUL Fire Safety Advisers. Designers should follow the principles and guidance provided in BS 5839 Part 1: 2013 (Para & 21.2.). The fire alarm system design process must involve a building survey and a visual inspection of every area to be covered to ensure the correct type of detection is provided. 5.5 In areas where there is an obvious risk of false alarms, including high risk laboratories, persistent dusty or dirty conditions and/or where materials or liquids that may not produce large quantities of smoke when ignited are present then the following types of detector heads should be considered: Apollo XP 95 Multi-Sensor detector heads or equivalent should be used in all laboratories/workshops and plant rooms. This will allow for clean burning fires to be detected and also allow for the operation thresholds to be extended or programmed to operate on heat only during normal working hours, if required to prevent unwanted false alarms. Fixed temperature heat detectors at 56ºC, 75ºC or 90ºC should be used only if there is a high ambient temperature, such as commercial kitchens, furnace rooms, combustion labs etc or in tea points if this requirement is identified at the design stage.

6 Ultra-violet/Infra-red flame detectors should also be considered for labs and areas where gases such as hydrogen are in use. This detection would be in addition to the detection provided for the rest of the room. 5.6 In some academic buildings it may be necessary to install multi sensor detectors which offer various settings/modes to ensure any local environmental conditions do not contribute to false alarms but still satisfy the fire safety design objective in that particular building. Examples of areas that may benefit from this type of detector would be areas that use smoke machines and other theatrical effects. In some licenced areas with public access and/or which sell alcohol it may also be possible to provide different modes on the fire alarm panel by selecting a specific mode on each multi sensor that can be adopted to ensure any fire alarm activation will not adversely impact the licenced event as long as a sufficiently high level of fire safety management can be provided. Subsequently, multi sensors such as Apollo Discovery multi-sensing heads may be used which can be programmed to meet the local conditions by selecting the appropriate mode and subsequently changing the ratio of heat to smoke detection. Apollo Discovery heads have five settings as per: Mode 1 Most sensitive setting using both Heat & Smoke monitoring and reacting at around less than 3% obscuration of the optical head. Mode 2 - Optical sensing setting only and reacting at around less than 3% obscuration of the optical head. Mode 3 Medium sensitivity setting using both Heat & Smoke monitoring and reacting at around less than 3% obscuration of the optical head. Mode 4 Least sensitive setting using both Heat & Smoke monitoring and reacting at around less than 5% obscuration of the optical head this is the recommended setting for laboratories and periphery kitchen areas where XP(% thresholds are likely to be exceeded Mode 5 Heat sensing setting only and reacting to at around less than 3% obscuration of the optical head 6.0 Design Issues Fire Alarm Panels 6.1 Only Fire Alarm Panels which use Open Protocol and have been agreed with the Estates Electrical Maintenance Manager must be used. All but very small systems should be fully addressable. The following fire alarm panel manufacturer should be considered in the first instance as they are currently the only manufacturer to provide advanced software programming that can meet QMUL s Unwanted Fire Alarm Reduction strategy, but advice must also be sought from the Electrical Maintenance Manager. Advanced Electronic Ltd (See: Generally, the panel should be compatible and capable of using and switching between all modes of Apollo detection heads including XP95 and Discovery using alarm confirmation facilities. In addition, where necessary,

7 the panel should have adjustable time to alarm and be programmable to meet local conditions. 7.0 Design Issues Manual Call out points 7.1 The following Manual Call Points (MCPs) should be used for all systems: Apollo XP95 KAC Alarm Company Limited 7.2 In areas prone to vandalism and maliciousness, such as Student Union Bars or areas and/or buildings that have historically suffered from a high rate of unwanted fire alarm signals, anti tamper security covers, commonly referred to as screamer devices may be fitted to each call point in consultation with Fire Safety Adivers Examples of such devices can be found at: Design Issues Sounders 8.1 There must be a single tone throughout the building. Any changes or replacements to the fire alarm system involving sounders must be matched to existing. Experience has found that it is necessary to have higher sounder level in an attempt to further engage and motivate some staff and students to evacuate. Therefore, Queen Mary, University of London requires a higher standard of audibility than BS 5839 Part 1: 2013 for sounder coverage. As such the average sounder level throughout the building should meet or exceed 75 db (A) in all areas. Often the British Standard minimum sounder levels are not adequate for this task and furthermore, fire doors can reduce sounder levels by up to 30 db (A) when closed. The levels within the staircase can be maintained at 60 db (A). Consideration should be given to reducing the sounder levels even further in the vicinity of both Disabled Refuge Outstations and Master stations to enable two-way communication and as a result of a risk assessment and after consultation with Fire Safety Advisers; if this facility is required, then a Verification Certificate can be issued. 8.2 The following standard sounders should be considered: Apollo loop driven sounders or equivalent which should have a defaulted maximum setting of 90+dB (A) Fulleon further information at: Standard 8 or 10 ringing bells, where appropriate. 8.3 Project Managers, Consultants and Contractors should consider contingency funds from the project to be allocated at pre-contract, to ensure that additional sounders can be installed at commissioning should the sound pressure coverage fall below acceptable levels in any particular area. 8.4 At the commissioning of the system (regardless of the size of installation), a sound pressure check MUST be carried out, with sound levels being recorded on a log sheet. The log is to be submitted with the Commissioning Certificate.Any shortfall is to be increased with the addition of extra sounders to the area.

8 8.5 Visual Alarms Visual alarms are to be provided (visual flashing Red strobe lights or LED technology) in the following locations: Noisy environments such as workshops/plant rooms/roof plant rooms etc. Environments where audible alarms are not appropriate (Control Rooms/Motion Suites/Sound or Anechoic Booths etc). Where Disabled or Hearing Impaired Persons may use facilities, such as WC s. Note this is all WC s and not just the disabled toilet. To identify and locate the main Fire Alarm Panel particularly in properties with identical frontage, where the panel location is not obvious or in the normal location of the main entrance area 9.0 Design Issues Facilities for Hearing Impaired 9.1 QMUL has specific policy and procedures for accommodating people with disabilities. Please discus with the Disability and Dyslexia Service and the QMUL Fire Safety Advisers. It will not be necessary to provide blanket coverage of a building with supplementary visual alarms due to the on-going installation of Deaf Watch systems in all academic buildings Deign Issues Fire Resistant Cabling 10.1 All cables used in the installation of Fire Alarms Systems, are to meet the requirements of BS 6387 and 7629 in design, construction and installation All cables shall be coloured Red, unless there are overriding aesthetic reasons for white to be used. Special attention is to be paid to the terminating of cables to ensure that earth faults are eliminated The following cables should be used in all instances: FP 200 Gold MICC cabling is required where routes provide mission critical signals, or pass through high risk or vulnerable areas (as required under BS 5839 Part 1: 2013) Fixing All fire alarm cabling is to be fixed to the structure of the building, in a cable tray or cable management system using metal ties only and usually fitted at 1m intervals. No other fixing method is acceptable. Where such cable runs penetrate fire resisting walls and floors fire stopping should be applied in accordance with the ASFP Red Book using 3 rd party certified products and be installed by 3 rd party accredited companies Design Issues Fire Alarm Batteries 11.1 It is strongly recommended that standby batteries for fire alarm systems in academic buildings should last for a minimum of 24 hours as specified in the British Standard.

9 12.0 Design Issues Marking and Indicating of Fire Alarm Devices 12.1 Labelling All fire alarm devices are to be permanently marked using suitable adhesive labels, to indicate the device zone and address number Identification Where remote or hidden detectors/devices are placed in voids, ducts or above ceilings, a suitable LED repeater indicator is to be provided in a logical and adjacent location. The devices are to be provided with a repeater LED unit in a readily accessible location and suitably labelled. All LED indicators are to be clearly marked specifying type of device, address number and remote device location Design Issues Ceiling, Ducts, Voids and Variation Certificates 13.1 Ceiling Voids Generally, where a void is 800mm deep or more it is only to be provided with appropriate automatic fire detection (irrespective of category of system) where the designer has identified a fire risk as part of the building survey, in accordance with BS 5839: Part Note 4. Examples of such risks would be: electrical panels/generators, electrical heating systems, electrical components excluding insulated wiring or anything the system designer identifies as being a risk, to ensure that any outbreak of fire would not spread uncontrollably from one area to another due to a lack of fire compartmentation before the alarm is raised. A variation certificate should be issued by the fire alarm designer in these cases Voids For maintenance purposes any void where automatic fire detection is provided must be fully accessible and not obstructed. This means that ceiling tiles or access panels must be available directly below the detector to allow maintenance and use of a testing pole. This requires a clear vertical path from below to be maintained Ducts Any duct where automatic fire detection is provided must be fully accessible and not obstructed to allow for maintenance of the head. Access panels must be provided directly below the detector to allow maintenance and a testing pole to be used in a clear vertical path Verification Certificates Any variation must be agreed by all relevant parties, be it as a result of a risk assessment by a competent person (either a 3 rd party accredited fire alarm designer or Fire Safety Adviser) and communicated to Queen Mary by way of a variation certificate. This certificate must detail all variations from the standard BS5839-1:2013, the supporting reasons for such variations and which party (ies) requested the variation i.e. the user, the designer, installer etc.

10 Two common examples that will result in Queen Mary seeking a variation certificate from the fire alarm designer are: The requirement for detection in voids over 800mm in height to be risk assessed and blanket coverage is not to be provided. Lobbies over 1m² with no risk do not need detection unless a risk assessment indicates otherwise. Any variation must only be issued after a suitable and sufficient risk assessment has been undertaken by a competent person Design Issues Door Holders Fire Dampers and Other Automatically Released Equipment 14.1 This ancillary equipment should adhere to the recommendations of the latest edition of BS 5839: Part 3. It should be noted that door holders, commonly referred to as door hold open devices or magnetic door holders are generally not acceptable on any fire door that leads directly onto a protected stair unless a suitable and sufficient risk assessment has been carried out. This must be discussed with Fire Safety Advisers. The London Fire Brigades Guidance Note GN48 Electro-Magnetic Door Holders on the use of this type of equipment may need to be complied with subject to a specific site fire risk assessment. In some cases the provision of any door hold open device in any building that is to be provided with a new fire alarm system may, subject to a risk assessment, require a L3 category fire alarm system in the surrounding areas and rooms. Further advice can be obtained from the QMUL Fire Safety Advisers Electromagnetic door release switches are to be positioned in a clear and accessible location, for test purposes and to prevent damage to fixings by doors being pulled close against the magnetic holders Where security Access Control Systems are to be installed in a building, it will be necessary to interface them with the fire alarm system in order to ensure all doors on access control fail safe on fire alarm activation and to comply with the Local Fire and District Surveyor Authority requirements. This interface is not to be connected to the sounder circuit. Further details can be obtained from the QMUL Fire Safety Team and/or the London Fire Brigade Design Issues Provision of Audible and Visual Warning at Internal Building Boundaries Connected to Fire the Fire Alarm System 15.1 Where the means of escape (MoE) passes through a building boundary to an adjoining building it will be necessary to provide visual and audible warning signs and that must be connected to each building s fire alarm system, to prevent access into a fire situation in an adjoining building. It will also be necessary to interface such devices with each fire alarm system to meet QMUL, Local Fire and District Surveyor Authority requirements.

11 16.0 General Commissioning Requirements Design, Installation, Commissioning and College Acceptance Certificates 16.1 The provision of the appropriate design, installation and commissioning certificates containing information based on the Model Certificates shown in BS 5839 Part 1 Annex H, are to be provided by the appropriate parties. Copies of the certificates are to be issued as following: All original certificate(s) to be placed in the Operational & Maintenance (O& M) Manuals. A copy of each certificate to be issued to the Electrical Maintenance Manager. A copy of each certificate to be issued to the Queen Mary Fire Safety Team A copy of the variation certificate if appropriate to be issued as above Design Certificate is to be provided in all cases by the Design Contractor on completion of the design stage of the fire alarm Installation Certificate is to be provided in all cases by the Installing Contractor of the fire alarm system, on completion of the installation stage Commissioning Certificate Is to be provided in all cases by the Commissioning Contractor (if different from the installing contractor) on completion of the testing and commissioning stage of the fire alarm Client Acceptance Certificate (Queen Mary University of London) This is to indicate that the client has witnessed the fire alarm system in operation and that they have accepted the system that has been installed as being capableof giving warning of fire and any other design objectives including a Soak testhave been met. The fire alarm systems operation should be witnessed on site by the following QMUL personnel/key stake holders whose contact details can be found in Appendix 1; Relevant Project Manager(s) Relevant Maintenance Manager(s) Relevant Maintenance Operatives as required Representative from Security Management Fire Safety Adviser(s) This witnessing process will include certain cause and effects such as; ensuring the panel addressing is clear and correct, panel operation, grounding of lifts, activation of refuge systems, supply and extract systems shut off, motorised dampers closing, audio visual shutting down, operation of fire shutters, doors on access control and/or powered open devices failing safe in the open position (list not exhaustive).

12 This certificate, which can be found in Appendix 2 should be provided by the relevant Project or Maintenance Manager, issued and signed by all College personnel that have attended with any comments or recommendations from each key stakeholder. This certificate should then be paced in the O+M s on completion of any remedial works identified, the Acceptance Certificate can then be provided to the Commissioning Contractor Only on completion of the Acceptance Certificate witnessed by a QMUL nominated person: May a new system become the primary warning in case of fire for the building; or, Where the fire alarm system has been replaced/upgraded etc) may the old system be switched off and decommissioned. The new system can then become the primary warning in case of fire for the building Where an addressable fire alarm system is provided, the programming of the device address must be done so as to ensure that its location accurately matches the panel reading to prevent confusion by staff, contractors or the Fire Brigade in locating the device. Subsequently, the following information as a minimum should be programmed to be displayed on the panel for each device; Device number; 001, 002, 003 etc Device type; MCP/SD/HD/MS/CVSD etc Device location; room number, room/area description etc Loop number; 1,2,3, etc Zone number, 1,2,3,4,5 etc 16.8 Designers and/or commissioners are also to provide a cause and effect chart in electronic format that details the following (not exhaustive): Shut off of any externally piped gas supply such as oxygen Shut down of M+E unless essential to protect critical plant/equipment Shut down of Gas Solenoid Valve (GSV) Operation of any safety equipment such as fire curtains/smoke barriers Open or closure of any installed and interfaced fire dampers, especially those that effect the means of escape Hold-open devices or power open doors relayed to the fire alarm system that affect the means of escape from the building or the comparmentation of the building

13 16.9 As built drawings and zone chart information is to be supplied as part of the commissioning of the fire alarm system as follows: Clear fire alarm zone information in A4 Word format, is to be provided in a suitable clip frame position adjacent to the fire alarm panel. This is to provide quick reference to incident location. As Installed Drawings are to be provided on hard copy A1 sheets and an electronic AutoCAD 2004 Version format scale of 1:50, 1:100 or 1:200 as appropriate.

14 Appendix Maintenance Managers Mile End Campus Mr Ron Hodgson Room OB.1 Queens Building E1 4NS Tel: Mr. John Allum Buildings Management (Residential Properties) Varey House (ground floor) Westfield Way London E1 4PD Tel: Whitechapel Campus: Mr. Anil Gooneratne Garrod Building Turner Street E1 2AD Tel: Charterhouse Sq. Campus: Mr. Steve G. Wiles Joseph Rotblat Building Charterhouse Square London EC1M 6BQ Tel: Fire Safety Manager Queen Mary, University of London Mr. Dennis Browne 404 Bancroft Road London E1 4DH Tel: Senior Fire Safety Adviser Queen Mary, University of London Keith Vagg 404 Bancroft Road London E1 4DH Tel: Fire Safety Adviser Queen Mary, University of London David Scott 404 Bancroft Road London E1 4DH Tel:

15 Appendix 2 Queen Mary University Acceptance Certificate for the fire alarm system at: Campus: Mile End Whitechapel Charterhouse Square West Smithfield Other I/We being the competent person(s) appointed by Queen Mary University of London accept the fire alarm system and have witnessed its operation and its ability to raise the fire alarm in the aforementioned building. As a competent person, appointed by Queen Mary University of London, I can confirm that; (fire safety adviser to complete) All installation work appears to be satisfactory (visual only). The system is capable of giving a fire alarm signal and has been witnessed. All doors fitted with access control and/or power open devices fail safe in the open position. The facility for remote transmission of alarms to an alarm receiving centre appears to operate correctly (delete if not applicable). I confirm that this fire alarm system is considered acceptable to be used to provide the primary means of raising the alarm in the event of fire in the aforementioned building? Yes No Name: Position: Signature: Date:

16 It is recommended that the following work/comments/remedial works should be addressed by the fire alarm contractor before the system can be fully accepted by Queen Mary University of London: The following documents and instruction has been provided to the relevant Queen Mary University Project or Maintenance Manager; (PM or MM to complete): A hard copy of and an electronic AutoCAD compatible copy of the As fitted drawings. Operating and maintenance instructions including panel type and operation The associated fire alarm panel keys and reset codes have been provided. Sufficient representatives of the users have received training on the fire alarm system to include silencing and resetting of the system and the avoidance of false alarms. Certificates of design, installation and commissioning. A log book (if requested by Queen Mary Estates Department) It is recommended that the following work/comments/remedial works should be addressed by the fire alarm contractor before the system can be fully accepted by Queen Mary University of London:

17 The following documents and instruction has been provided to the relevant Queen Mary University Project or Maintenance Manager; (PM or MM to complete): The following persons were present during the on-site fire alarm demonstration;

18 Document Control Initial data Author: Position: Dennis Browne Fire Safety Manager Checked by: Position: Keith Vagg Senior Fire Safety Adviser Approved by: Position: Marion Richards Director of Occupational Health and Safety Status: Version 3 Live Date of Issue: May 2011 Version number Date of alteration and re-issue Details of Changes Changes made by 1 May 2012 Filename Path Darren Ford changed from QM/H&S/ December 2012 David Scott 3 June 2013 Review and changes made to whole document David Scott

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS Fire Safety Technical Guide FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (All Buildings Except Sleeping Accommodation) Contents: 1.0 Introduction... 1 2.0. UCL

More information

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE Fire Safety Technical Guide Contents FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE (Student Hals of Residences - Sleeping Accommodation) 1.0. Introduction... 1

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839 AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What

More information

Standard the the Raising

Standard the the Raising Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

Fire Alarm system Installation Guide

Fire Alarm system Installation Guide Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this

More information

Fire Safety Requirements for Child Care Centre

Fire Safety Requirements for Child Care Centre Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,

More information

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

Fire precautions in dwellings. Private sector housing Providing homes building communities

Fire precautions in dwellings. Private sector housing Providing homes building communities Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared

More information

How To Write A Fire Risk Assessment

How To Write A Fire Risk Assessment Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes

More information

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual EDA-Z5008 & Z5020 Radio Fire Alarm System User Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2EG UK Tel: 01279 635668. Fax 01279 450185 Email: eda@electrodetectors.co.uk

More information

Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings

Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings Building Control Householder Guidance Leaflet No. 29 Fire detection in dwellings This leaflet is one of a series produced by the Hertfordshire Building Control Technical Forum GUIDANCE NOTE FOR HOME OWNERS

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 1.52 & LOOP CARD 2.0 ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK #Doc No. GLT.MAN-135 TABLE OF CONTENTS WHAT TO DO IF THE

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

Fire Safety Log Book

Fire Safety Log Book Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

Call reduction guidance for false alarm/ unwanted fire signals

Call reduction guidance for false alarm/ unwanted fire signals Call reduction guidance for false alarm/ unwanted fire signals Acting to Protect & Save Introduction Devon & Somerset Fire & Rescue Service attend in excess of 20,000 incidents each year, approximately

More information

section one guide to design, installation,commissioning and maintenance of fire systems in non domestic premises Consultant s Guide

section one guide to design, installation,commissioning and maintenance of fire systems in non domestic premises Consultant s Guide section one Consultant s Guide section one section one contents About this manual Purpose Readership Electronic Format Acknowledgments 1 3 4 4 Section One: Guide to Design of Fire Systems 1. 1.1 1.1.1

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

Application Guide HMOs

Application Guide HMOs Application Guide HMOs 2 Aims of this guide 3 What is AlarmSense? 3 What is an HMO 3 Fire Protection for an HMO 3 Approved Document B 4 Mandatory Licensing 4 BS 5839 4 Categories of System 6 Application

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

Consultants Guide Issue 1 : 2012

Consultants Guide Issue 1 : 2012 Consultants Guide Issue 1 : 2012 FireClass Hillcrest Business Park Cinderbank Dudley West Midlands DY2 9AP United Kingdom Tel. +44(0)1384 453985 www.fireclass.co.uk fireclasssales@tycoint.com part one

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

Emergency Voice Communication Systems

Emergency Voice Communication Systems Emergency Voice Communication Systems Frequently sked uestions What is an Emergency Voice Communication System? Emergency Voice Communication System is the generic technical term to cover Fire Fighting

More information

CBD-233. Fire Alarm and Detection Systems

CBD-233. Fire Alarm and Detection Systems Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually

More information

Fire Standards & Regulations Are you confused?

Fire Standards & Regulations Are you confused? Fire Standards & Regulations Are you confused? Regulatory Reform (Fire Safety) Order Local Licensing Requirements BS 5839-6: 2013 Building Regulations Document B LACORS Fire Safety Guidance Fire Alarm

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010

BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Page 1 of 7 PURPOSE: This Guidance

More information

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number

More information

FIRE ALARMS AND DETECTION SYSTEMS EQUIPMENT

FIRE ALARMS AND DETECTION SYSTEMS EQUIPMENT IMPERIAL COLLEGE FIRE ALARMS DETECTION SYSTEMS EQUIPMENT REVISION 1 FIRE ALARMS AND DETECTION SYSTEMS EQUIPMENT Revision Log REV. COMMENTS REVISED BY DATE CHECKED APPROVED 1 First Issue NDY 18.03.05 Notes

More information

Consultant s Guide for Designing Fire Detection & Alarm Systems

Consultant s Guide for Designing Fire Detection & Alarm Systems Consultant s Guide for Designing Fire Detection & Alarm Systems part one contents About this manual Purpose Readership Electronic Format Acknowledgments 1 3 4 4 Part One: Guide to Design of Fire Systems

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT This template has been provided to assist the Responsible Person with the preparation of a Fire Risk Assessment and is not intended for commercial

More information

FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie

FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie FIRE SAFETY REGISTER Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie 1 CONTENTS Section Title Page 1.0 Introduction 3 2.0 Guidance for the completion

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

- 5 - Table1. Maximum Compartment Volumes

- 5 - Table1. Maximum Compartment Volumes - 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

GENERAL FIRE SAFETY TERMS & DEFINITIONS

GENERAL FIRE SAFETY TERMS & DEFINITIONS UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

Analogue addressable devices

Analogue addressable devices Discovery Analogue addressable devices from Channel Safety Systems Discovery Analogue addressable devices Discovery is a range of high-specification, intelligent fire detectors that are developed to meet

More information

Fire Safety Risk Assessment

Fire Safety Risk Assessment 1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept

More information

False Alarm/Unwanted Fire Signals Reduction Guidance

False Alarm/Unwanted Fire Signals Reduction Guidance False Alarm/Unwanted Fire Signals Reduction Guidance Compiled By: South Wales Fire and Rescue Service Contents Introduction Why reduce false alarms Typical Causes Actions that can be taken Introduction

More information

Greater Manchester Fire and Rescue Service

Greater Manchester Fire and Rescue Service Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY

More information

1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS

1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS Fire Risk assessment 1.0 APPOINTMENTS 1.1 Responsible Person. In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO) the School s Head, Mrs J M Miles is appointed as the Responsible Person

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

For use by landlords of small premises Premises Address

For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Fire detection equipment

Fire detection equipment PRODUCT CATALOG Fire detection equipment www.apollo-fire.com Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980,

More information

Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition

Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building

More information

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1 CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL user manual & log book Approved Document No. DFU7001020 Rev 1 CONTENTS Safety...3 Important information regarding the safe use of this fire alarm panel

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

How To Comply With The Loss Prevention Certification Board

How To Comply With The Loss Prevention Certification Board Loss Prevention Standard LPS 1014: Issue 5.3 This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information purposes only. Its use for testing, assessment,

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14 North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

FIRE ALARM APPLICATION

FIRE ALARM APPLICATION FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:

More information

Fire Safety Risk Assessment Checklist for Residential Care Premises

Fire Safety Risk Assessment Checklist for Residential Care Premises Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

FSD Circular Letter No. 7/95 Automatic Fire Detection System - Design and Maintenance Considerations

FSD Circular Letter No. 7/95 Automatic Fire Detection System - Design and Maintenance Considerations Our Ref.: 1 5 (49) in FPB 314/07 III FIRE SERVICES DEPARTMENT FIRE PROTECTION COMMAND FIRE SERVICES HEADQUARTERS BUILDING, No. 1 Hong Chong Road, 5/F., Tsim Sha Tsui East, Kowloon, Hong Kong Your Ref.:

More information

Guide to Fire Alarm Systems

Guide to Fire Alarm Systems Guide to Fire Alarm Systems Guide to Fire Alarm Systems INDEX Introduction Page 2 When is a Fire Alarm System Required Page 2 The Fire Precautions Act 1971 & Fire Precautions (Workplace) Regulations 1997Page

More information

CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY

CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY This policy was written in July 2014 and will be agreed by the Board of Governors in October 2014. To be reviewed by June

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

To promote and protect the private residential landlord. Fire Safety Logbook. Information. Advice. Support. Services START DATE:

To promote and protect the private residential landlord. Fire Safety Logbook. Information. Advice. Support. Services START DATE: To promote and protect the private residential landlord Fire Safety Logbook Information Advice Support Services START DATE: PROPERTY DETAILS Property Address: Post Code: Licence Holder/Manager: CONTACT

More information

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently (68.52) X June 2000 Supercedes February 2000 xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM.... we look @ business differently XENEX SYSTEM ARCHITECTURE Note: This schematic is for guidance only please

More information

FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589.

FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589. FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589 Bulletin 16-12 Fire Drills This guideline was developed to assist persons

More information

Carbon Monoxide Detection in Commercial Buildings (

Carbon Monoxide Detection in Commercial Buildings ( 1 Technical Guideline for School Districts and BOCES to comply with regulations for Carbon Monoxide Detection in Commercial Buildings (Section 1228.4 of Part 1228 of Title 19 NYCRR). General: This document

More information

UPP Residential Services Fire Risk Assessment

UPP Residential Services Fire Risk Assessment UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This

More information

Fire Risk Assessment For Simple Premises

Fire Risk Assessment For Simple Premises Fire Risk Assessment For Simple Premises Responsible Person (Employer or other person having control of the relevant premises) Company / Premises Name Address of Premises Postcode Primary Use of Premises

More information

The risk assessment of fire damper installations

The risk assessment of fire damper installations The risk assessment of fire damper installations June 2010 Paul White OVERVIEW OVERVIEW The purpose of this presentation is to highlight that fire dampers form a key part of the passive fire protection

More information

Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm Systems

Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm Systems Thames House, 29 Thames Street Kingston upon Thames, Surrey, KT1 1PH Phone: +44 (0) 8549 5855 Website: www.fia.uk.com Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm

More information

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL

More information

AlarmSense 2-wire detection and alarm system. Product Guide

AlarmSense 2-wire detection and alarm system. Product Guide AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority

More information

Reducing the Risk of Fire Through Telecare Commissioning Standards. London Fire Brigade

Reducing the Risk of Fire Through Telecare Commissioning Standards. London Fire Brigade Reducing the Risk of Fire Through Telecare Commissioning Standards London Fire Brigade Sheltered Accommodation Irene - Surrey Coroner s Court 9 th May 2014 HM Coroner Richard Travers highlighted the delay

More information

Diocese of St Albans Diocesan Advisory Committee Advisory Leaflet 40. Fire Alarm Systems. A short guide to fitting them in Churches and Church Halls

Diocese of St Albans Diocesan Advisory Committee Advisory Leaflet 40. Fire Alarm Systems. A short guide to fitting them in Churches and Church Halls Diocese of St Albans Diocesan Advisory Committee Advisory Leaflet 40 Fire Alarm Systems A short guide to fitting them in Churches and Church Halls Introduction The majority of churches will not need to

More information

Fire Alarm Systems Care and Maintenance

Fire Alarm Systems Care and Maintenance April 2011 Country of Origin: United Kingdom Fire Alarm Systems Care and Maintenance Introduction A fire alarm installation is designed to provide early warning of a fire condition. To ensure that the

More information

FIRE SAFETY PRECAUTIONS

FIRE SAFETY PRECAUTIONS FIRE SAFETY PRECAUTIONS LOG BOOK PLEASE KEEP AVAILABLE 1 Business Name Premises Information Building / Unit Number Property Name Road: (Address Line 1) (Address Line 2) Locality: Town: Post Code: Name

More information

FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS

FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS 1 FIRE ALARMS IN DWELLINGS By John Ware IN THE UK around 80% of all fire deaths and injuries occur in dwellings, a total of 450 to 500 deaths and 14,000 injuries per annum, according to BS 5839-6: 2004.

More information

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons Your responsibilities if you have an automatic fire alarm A handy guide for owners and responsible persons Kent Fire and Rescue Service Contents Your responsibilities if you have an automatic fire alarm

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

USER INSTRUCTIONS CONTENTS

USER INSTRUCTIONS CONTENTS CONTENTS Full Set [1]...2 Part Set [2]...2 Night Set [3]...3 Unsetting...3 Unsetting after or during an alarm...3 Testing the system [5]...3 Isolating zones [6]...4 Reprogramming codes [8]...4 Chime facility

More information

Policy for the Management of Asbestos in the Workplace

Policy for the Management of Asbestos in the Workplace Southwark Council Management of Asbestos in the Workplace November 2011 Page 1 of 15 CONTENTS 1. INTRODUCTION... 3 2. POLICY STATEMENT... 3 3. ASBESTOS RISK CLASSIFICATION SCHEME... 5 4. SAMPLING OF ASBESTOS

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19 TECHNICAL SPECIFICATIONS Page 1 of 19 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC analogue addressable, electrically supervised, zone annunciated, fire detection and alarm system as

More information

Fire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1

Fire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1 Network Building Fire Safety Management Plan & Fire Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting

More information

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection

More information