1 MIDDLESEX COUNTY COLLEGE FIRE & SECURITY ALARM SYSTEMS SECTION C - TABLE OF CONTENTS SECTION TITLE PAGE 1. Scope of Work... C-2 2. Materials... C-3 3. Installation/Execution... C-3 4. Qualifications... C-3 5. Site Clean-Up... C-4 6. Time Constraints... C-4 7. Term... C-5 8. Work Hours... C-5 9. Guarantee... C Additional Information... C Security Alarms... C Fire Alarms... C-7-16 C-1
2 1. SCOPE OF WORK The purpose of these specifications is the completion of a service type contract for a twelve (12) month period. After the execution of the contract, the Contractor shall provide emergency, maintenance and small job services defined by plans and/or narrative issued for each job, based on unit bid prices. Invoices will be paid for actual labor and materials used. All invoices must have supporting documentation attached. This work will be performed at the main Middlesex County College campus in Edison, New Jersey and New Brunswick Center in New Brunswick, New Jersey. This contract is not intended to cover large capital projects which may include work on the College s site utilities during this service contract period. The Contractor shall supply the labor, materials, and equipment required to perform the annual testing and inspection of the fire and security systems at Middlesex County College's campus in Edison, New Jersey. The systems shall be tested annually as required by the New Jersey Uniform Fire Code (N.J.A.C. 5:70,3.2 (a) 5, F-513.1) in accordance with the recommended practices of NFPA 72., 2002 edition. This will include any smoke evacuation systems, flow switches, HVAC equipment, etc. that are an integral part of the fire alarm system. A listing of the alarm system components for each of the buildings included in this service contract is attached. Provide necessary manpower to conduct annual campus alarm testing on the Martin Luther King Holiday, January 19, 2015 and President s Day Holiday on February 16, Upon the completion of testing, a full written test report including a comprehensive outline of all associated devices as well as a certificate shall be submitted to the College s Facilities Management Department. The contractor will provide annual recommendations of updates and improvements to the system components to increase reliability of the overall system. Please note that all testing shall be coordinated as not to disrupt the daily class schedule or administrative functions of the Campuses. The facilities owned by Middlesex County College related to this contract include, but are not limited to fire and security alarm systems. C-2
3 BASE BID The Base Bid is to include the rates for all of the emergency, maintenance and small job work as described in this specification and per attached list of equipment. 2. MATERIALS The materials used under this contract shall be as specified on the drawings and in the specifications, be of a quality acceptable to the Engineer and meet applicable codes. 3. INSTALLATION/EXECUTION Plans and specifications of the equipment and systems throughout the campus shall be provided by the College to the Contractor when available and requested by the Contractor. The accuracy of this information is not guaranteed by the College. It shall be the responsibility of the Contractor to verify this information and be fully familiar with the equipment and systems on campus and to proceed with all work in a safe and cost effective manner. All work shall be performed by skilled mechanics in a workmanlike manner typical of the trades involved. No work shall be performed under conditions unsuitable for best results. Proper care shall be taken to protect all areas surrounding the work area so as not to cause damage. Work that will interfere with classes that are in session will be rescheduled during night hours or weekends when classes are not in session. The contractor will be responsible for notifying the College Police Department of any work or possible alarm conditions they encounter during the performance of this contract. 4. QUALIFICATIONS The Contractor shall include in the bid, verification that the work will be performed by mechanics properly trained for the work required and licensed if required by the State of New Jersey. Additionally, it is required that the staff of the Contractor contains at least one NICET Level III Certified Technician who shall be responsible for all work performed. Simplex certified or equivalently trained technicians are required for repair work. The Contractor shall include in the bid a listing of a minimum of five (5) projects and/or service contracts similar in scope to this contract which have been successfully completed or currently in existence. The listing must include the firms for which the service was performed, a description of the work and the name and phone number of a reference for each who may be contacted by the College. C-3
4 The bidder is also required to submit with their bid a valid Fire Alarm Certification issued by the Division of Fire Safety in the State of N.J. and an electrical contractor s license issued by the Board of Examiners of Electrical Contractors of the State of N.J. Division of Consumer Affairs to verify that they are licensed to practice in New Jersey. 5. SITE CLEANUP The Contractor shall be responsible for keeping the premises free from accumulation of waste materials and rubbish and for the removal of waste materials from the campus each time service is performed. 6. TIME CONSTRAINTS A. Emergency Work Emergency work requires a specific response to the Facilities Management Department, Building 229, within two (2) hours of notice by telephone to the Contractor s emergency number and the ability of the Contractor to mobilize and man the job with sufficient forces to complete the work in a timely fashion. The Contractor shall provide an emergency service dispatch telephone number that is staffed twenty-four (24) hours a day and seven (7) days a week. The emergency service number will not be an answering machine or pager number. B. Maintenance Work and Small Jobs Maintenance work and small jobs shall be initiated in the form of a request for a not-to-exceed cost from the College s Facilities Management Department. The Contractor shall review any plans that may be provided and inspect the job site in order to provide a written cost quote based upon the unit costs provided in the bid. The Contractor shall be ready to man this type of work with sufficient forces to complete the work in a timely fashion after notice to proceed has been issued by the Executive Director of Facilities Management. The Contractor shall report to the Facilities Management Department, Building 229, prior to beginning work. C-4
5 7. TERM Pursuant to N.J.S.A.18A:64A-25.18, the College shall award the contract or reject all bids within 60 days from the opening of the bids. The contract shall cover the fiscal year 2014 (July 1, 2013 through June 30, 2014). The College reserves the right to terminate the contract at any time during the contract period with thirty (30) days written notification for poor service or failure to comply with the terms of this bid as solely judged by the College. 8. WORK HOURS Regular working hours are form 8:00 AM to 4:30 PM on Monday through Friday. All other hours are considered overtime. If the Contractor s regular and overtime hours differ from this, the Contractor shall indicate them in the bid for approval by the College. All work associated with this contract shall be coordinated through the Facilities Management Office located on the Edison campus. The Contractor shall also include in the bid a listing of the holidays observed by the Contractor for which a premium holiday rate would be invoiced. 9. GUARANTEE The Contractor is required to guarantee all materials and workmanship for a period of twelve (12) months beginning at the satisfactory completion of each job. 10. ADDITIONAL INFORMATION/SITE VISIT Site visits can be scheduled through Facilities Maintenance Director but must be done in a manner to minimize disruption of the educational environment. Additional information may be obtained from the following individuals: Facility/Specifications: Dan Fuchs Associate Director of Buildings and Systems (732) (732) Fax Proposal: David Fricke Director of Purchasing and Inventory (732) (732) Fax C-5
6 SECURITY ALARMS EQUIPMENT College Center PC550 1 Digital Security Control Alarm System PC500RK 1 Keypad Johnson Learning MC-6A 2 United Security Center Products Alarm Panel CC1-1 4 Napco Security System Main Hall PC Digital Security Control Alarm System Physical Ed. Center Mark 5000R 1 Napco Security System PC Digital Security Control Alarm System West Hall Ackron/Model DKIIA 2 Security System C-6
7 FIRE ALARM EQUIPMENT BILLY JOHNSON HALL: List of Equipment (SIMPLEX ALARM SYSTEM) MODEL No. Serial QTY DESCRIPTION None 1 Fire Alarms & Voice Control System 24 Zone - With Battery Stand By - Solid State Modules as Listed Below to Complete Control Functions Required Series Class "B" - 8 Zone Master Controller Two (2) Class "B" Signal Circuits (Indicating Appliance Cir.) Two (SPDT) Auxiliary Control Relays One (SPDT) Auxiliary Trouble Relay City Connection. Automatic Charger & Standby Battery. Power Supply 5 24VDC Output - Power Limited Series Eight (8) Zone Modules for Zone Initiating Device Circuits - Class "B" (16 Zone Total) Series Six (6) Circuit Modules Indicating Appliance Ckt Four (4) DPDT Contact for Auxiliary Functions Redundant Tone Generator Ah Batteries Dual 25W Amplifier With Power Supply Hand Held Microphone & Enclosure Master Telephone & Enclosure Standard Voice Message Set Point Graphic Interface Annunciated 16 Point Red-Yellow LED C-7
8 /8 Momentary Switches Red LED /16 Position Maintained Switches - Red - Green LED Single Channel Audio Control Switch Station - Single Action - Semi-Flush Door Release Unit 24VDC Wall Mounted Area Low Profile Electric Smoke Detector With It's Respective Base # Two (2) Wire Photo Electric Duct Detector With Sampling Tube 48" & Remote "RED" Alarm LED Combination Rate of Rise & Fixed Temp. 135 degreef Remote Fire Fighters Telephone Jack Flush Mounted Speaker With Box Flush Mounted Speaker With Box & Tile Bridge For Ceiling Mount & Title Bridge For Ceiling Mount Surface Speaker For Mounting On To Below Listed A/V Flasher A/V Flasher Unit FAA Graphic Display (WSA) BLUE COLT BOOKSTORE: MODEL No. Serial QTY DESCRIPTION None 1 Fire Alarm Control Panel Configuration Node Master Controller Version 8 Software C-8
9 Modular 4120 Network IFC Card Unit Package Fiber Optic Comm Media Module VDC Battery 18AH LCD Annunciator MTR Bell 24V 6 Red MB-G6-24R V/O 24VDC 15CD Red 1 HZ Modular Adapter for4904red A/V 24VDC 15CD RED 1 HZ Horiz Pull Station MapII D/A Pull Station Flush Trim Supervised IAM SSD Photo Sensor SSD Sensor Base SSD Sensor Duct Housing w/relay Sampling Tube 49" SSD Photo Sensor CHAMBERS HALL: 4208 H Fire Alarm Control Panel H Stations Bells Heat Detectors Heat Detectors Photoelectric Detectors Smoke Detectors System Electronics Dialer Bell Bell C-9
10 COLLEGE CENTER: LCD Annunciator GL8-BL-LX-SR-MD24D-1 1 Graphic Annuciator Pull Stations sensor 224 Photo Electric Smokes base Duct Smoke detectors with Remote key switches Addressable heat detectors base 20 fixed temp & 26 rate of rise Ansul System detectors Speakers/Strobes Strobe Only CRABIEL HALL: Fire Alarm Control Panel LCD Annunciator Addressable smoke/heat base Addressable smoke sensor Addressable heat sensor Addressable pull station Addressable monitor module Addressable control module Addressable speaker/strobe Addressable strobe only MTWP-2475W-FR 4 Weatherproof horn/strobe IOB-R 4 Weatherproof horn/strobe box Addressable duct detector Duct detector test switch Duct detector sampling tube Batteries Battery Shelf EAST HALL: GE VS1 N/A 1 Fire Alarm Control Panel GE GSAM278 5 Pull Station GE VPS 27 Smoke Detectors GE VHFD 6 Heat Detectors GE MGC FR HDUM 8 Horn Strobes GE WG4RF HUMC 3 Exterior Horn Strobes C-10
11 EAST HALL ANNEX: Quickstart Miretone Fire Alarm Control Panel Ademco Dialer Pull Station Horn Strobe Thermo Detectors Monitor Star Control EDISON HALL: S Fire Alarm Control Panel Stations Bells Bell Kirkland 1 Annunciator Smoke Detectors Duct Detectors Stations Horns Lights S Annunciator FACILITIES MAINTENANCE: None 1 Simplex #4010 Control Panel Supervised IAM Horn/Strobe MC Red Skirt, Horn/Strobe Red Battery 12.7 AH Fire Alarm Control Panel 250 Point City Circuit Card Expansion Power Supply 120 Volt GATEWAY: 4208X H Fire Alarm Control Panel 4293 D Master Annunciator Remote Building Panel Add to Existing NDU/Miniplex Circuit Class B Style Y Relays, 2 Amps w/feedback C-11
12 Power Limited 8A Power Supply Fiber-Optic Comm Media Module Mapnet II Addressable/Truealarm LCD Annunciator MTR Bell 24V 6" Red MB-G6-24-R V/O 24VDC 15CD Red 1 HZ Modular Adapter for 4904, Red A/V 24VDC 15CD Red 1 HZ Horiz Pull Station MapII D/A Pull Station Flush Trim Supervised IAM SSD Photo Sensor SSD Sensor Base SSD Sensor Duct Housing w/relay Sampling Tube 49" SSD Photo Sensor Stations Fixed Temp Detectors Bells Bell C-12
13 JOHNSON LEARNING CENTER: 4100 BJ Fire Alarm Control Panel Smoke Detectors - Halon Systems Bells Graphic Annunciator Pull Stations Heat Detectors L'HOMMEDIEU HALL: F Fire Alarm Control Panel D A Annunciator Pull Stations Bells Heat Detectors Heat Detectors Bell FM998 8 Magnetic Door Holders Smoke Detectors System Electronic Dialer LIBRARY: S Fire Alarm Control Panel Bells Bell Thermo Detectors Thermo Detector S Annunciator Monitor Star Control Drill Box MAIN HALL: Fire Alarm Control Panel Ademco Dialer Bells Stations D Annunciator Heat Detectors Monitor Control STR C-13
14 NEW BRUNSWICK CAREER CENTER MODEL No. SERIAL QTY DESCRIPTION FACP 8 IDC 4 NAC Beige Mini-Horn W/ADA Strobe 24VDC R A/V 15CD Red Standard QA Pull Station S/A, INOO Heat Detector 135 ROR For Base SSD Photo Sensor Detector SSD 2-Wire DET REM LED Base SSD Detector Duct Housing SSD Photo Detector Sampling Tube 73" AFMKT CCDACT for Point NAC/Relay Module Expansion Power Supply Point IDC Module Class B Battery 10 AH Backbox Beige NEW STUDIO THEATER: U Preconfig. Domestic 120V Power Distribution Module 120V Blank Display Module Expansion Bay (Phase 10 Only) XPS Power, 3 NACS, 120VAC Event Reporting DACT Indicator Only 2Bay Glass Factory Built-Main Configured Station, SA, Address, IDNET SSD Photo Sensor C-14
15 SSD Sensor Base SSD Heat Sensor SSD Sensor Base Speakers/Strobes LCD Enunciator NORTH HALL: MIR-QS4-5-R Ademco AR Fire Alarm Control Panel SA Annunciator Panel Ademco Dialer Pull Station Bells Thermo Detectors Thermo Detectors Monitor Star Control PERFORMING ARTS CENTER: 4208 F Fire Alarm Control Panel Pull Stations Sensor Photo Electric Smokes Base Duct Detectors W/Remote Indicators Base Heat Detectors-Rate Of Rise Base Speakers/Strobes (Visual Only) Strobes PHYSICAL EDUCATION CENTER: S Fire Alarm Control Panel Stations U Annunciator Smoke Detector (Ceiling) Smoke Detector (Duct) Horns Lights C-15
16 RARITAN HALL: Fire Alarm Control Panel Pull Stations X Annunciator Thermo Detectors Smoke Detector Bells 4001 I-19359DL 1 Fire Alarm Panel WEST HALL: 4208 D Fire Alarm Control Panel D 6 Pull Stations Heat Detectors Heat Detectors Heat Detectors Bells Bells Ademco Dialer C-16
SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description
INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's
SECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM
KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
C. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work
GE Security Small Building Life Safety Solutions Affordable FireShield Conventional Fire Alarm Control Panels imagination at work cost Location: Environment: Solution: Flower shop Finely decorated, gentle
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
FIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
FIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?
5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,
INVITATION FOR BID NO. B-12-33-12. BID DUE DATE: Tuesday, May 24, 2011@ 10:00 AM. [ Edited for Size by Mountainbell9845 Informational use only 4 13]
INVITATION FOR BID NO. B-12-33-12 BID DUE DATE: Tuesday, May 24, 2011@ 10:00 AM [ Edited for Size by Mountainbell9845 Informational use only 4 13] 1 Simplex 4002 H53336 Fire Alarm Panel Adminis. 1 System
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION
SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled
FIRE ALARM APPLICATION
FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.
GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems
Security Systems Intrusion Alarm
Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted
Life Alarm Fire Alarm Controls
FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET UL, ULC Listed FM Approved MEA Approved* Life Alarm Fire Alarm Controls Fire Alarm Controls 4005 Series Fire Alarm Control Panels Eight through Thirty-Six
EDWARDS SIGNAL SOLUTIONS www.edwards-signals.com DISTRIBUTED BY: Lee Dan Communications, Inc. www.leedan.com [email protected] Toll-Free: 800-231-1414
EDWARDS SIGNAL SOLUTIONS www.edwards-signals.com DISTRIBUTED BY: Lee Dan Communications, Inc. www.leedan.com [email protected] Toll-Free: 800-231-1414 Fire Alarm CONTROL S y s t e m s CONVENTIONAL FIRE ALARM
INTELLIGENT FIRE ALARM CONTROL UNITS. MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit. Features. Description
INTELLIGENT FIRE ALARM CONTROL UNITS MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit Description Secutron s MMX-2017-12NDS Network Fire Alarm Control Unit offers modular components to meet a
Module 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.
SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description
SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped
SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM
SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14
City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire
INSPECTION AND TESTING FORM
INSPECTION AND TESTING FORM SERVICE ORGANIZATION PROPERTY NAME (USER) DATE: 08-04-15 TIME: 8:00 Name: Siemens Industries Inc. Name: Kcvtcs Madisonville Tech, School Bldg. Address: 2700 Stanley Gault Pkwy
REQUEST FOR PROPOSAL FOR: Fire and Security Alarm Service and Monitoring
MCC13-04 REQUEST FOR PROPOSAL FOR: Fire and Security Alarm Service and Monitoring Manchester Community College PURPOSE: The purpose of this REQUEST FOR PROPOSAL is to establish a contract for Manchester
University of Houston Master Construction Specifications Insert Project Name
SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section
Module 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
DTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
Fire Alarm Submittal Requirements and Acceptance Testing
Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 [email protected] Fire Alarm Submittal Requirements and Acceptance Testing To all Registered
INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM S7010 S7010 7165-1477:111
INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM BBX-FXMNSR Description BBX-5014R Mircom s FleX-Net TM Series Network Fire Alarm Control Panels offer modular components to meet a wide variety of applications.
SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System with automatic detection and control. The work described in this
FIRE ALARM SYSTEM Section 16750 Page 1
FIRE ALARM SYSTEM Section 16750 Page 1 PART 1 - GENERAL 1.1 REQUIREMENTS A. Provide a complete operational, stand-alone local protective signaling system in each defined building as indicated on the contract
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
SECTION 16700 FIRE ALARM SYSTEM
SECTION 16700 FIRE ALARM SYSTEM PART ONE: GENERAL 1.1 GENERAL REQUIREMENTS A. Definition of Work : This section of the specification includes the furnishing, installation, connection and testing of the
DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES 28 31 00
SECTION 28 31 00 FIRE DETECTION AND ALARM GENERAL This section deals with the fire alarm system, including the control panel and integral equipment, wiring and circuitry, initiating devices, indicating
ENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a
A. This Standard outlines the requirements for an addressable fire detection and alarm system.
1.00 GENERAL 1.01 Scope: A. This Standard outlines the requirements for an addressable fire detection and alarm system. B. This Standard consists of all materials, equipment and services necessary and
Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14
North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST
Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 25-POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1. DESCRIPTION: A. This section of the specification
INTELLIGENT FIRE ALARM CONTROL UNITS MMX-MNS TM
INTELLIGENT FIRE ALARM CONTROL UNITS MMX-MNS TM Intelligent Fire Alarm & Emergency Communications Network MMX-LOC MMX-BBX-FXMNS Description Secutron s MMX TM Series Mass Notification System (MNS) is designed
Invitation to Bid FIRE ALARM & DETECTION SYSTEM
Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066
JULY 2013 UCB STANDARDS 16720-1
SECTION 16720 FIRE ALARM AND DETECTION SYSTEMS PART 1 GENERAL 1.01 Reference A. Related Sections 1. Section 15300 Fire Protection 2. Section 15950 Controls 3. Division 16 Electrical 4. Division 14 - Conveying
University Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
B. All Fire Detection and Alarm design and installation shall comply with the most current and adopted version of NFPA 72.
28 31 00 PART 1 - GENERAL 1.01 SCOPE A. Background: Washington State University has agreements with Simplex- Grinnell and Siemens Industry, Inc. to provide Fire Detection and Alarm (FDA) systems for the
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
The Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
28 3111 Voice Annunicated Fire Alarm System Page 1 of 26
Last Update: December 8, 2014 Consultant s Handbook Page 1 of 26 A. General: 1. Voice annunciated, intelligent, addressable fire alarm systems at BSU are used in all residence halls, high rise buildings
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
CATALOG NUMBER. Features. Description
VOICE EVACUATION SYSTEM QX000 SERIES Description Mircom s QX000 Series is a multichannel zoned audio system that allows the operator to selectively page from a central location to any of the system s audible
FAST, INTELLIGENT FIRE ALARM SYSTEMS THAT DELIVER IT ALL
FAST, INTELLIGENT FIRE ALARM SYSTEMS THAT DELIVER IT ALL NOT YOUR STANDARD FIRE ALARM PANEL FLEXIBILITY, SPEED, INTELLIGENCE CyberCat the digital, peer-to-peer bi-directional, communication system that
FIRE DETECTION AND ALARM
FIRE DETECTION AND ALARM GENERAL INFORMATION 1.1 In general, follow the guidelines below when designing and specifying addressable fire alarm systems. Unless specifically indicated otherwise, these guidelines
25 Years of Manufacturing Excellence INFINITY. The Intelligent 2 Wire Fire Detection System for Professionals
INFINITY The Intelligent 2 Wire Fire Detection System for Professionals Infinity ID 2 The intelligent 2 wire fire detection system for professionals In a nutshell Zeta Alarm Systems is proud to introduce
Fire Alarm Systems Permit Packet. City of Greer Fire Department
Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting
Engineer s Project Number: 298-1062 Section 28 31 00 Page 1 FIRE ALARM AND DETECTION SYSTEMS
Engineer s Project Number: 298-1062 Section 28 31 00 Page 1 SECTION 28 31 00 PART 1 GENERAL 01 SUMMARY A. This Section covers fire alarm systems, including initiating devices, notification appliances,
NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S7010 7165-1477:111
NETWORK FIRE ALARM CONTROL PANEL FX-2003-12NDS Description Mircom s FleX-Net Series is a powerful intelligent networkable fire alarm solution designed with many levels of flexibility to meet virtually
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
Project No. 4 Analysis of Active Fire Alarm Systems in WTC 1 & 2. Robert J. Keough Rolf Jensen & Associates Raymond A. Grill, P.E.
Project No. 4 Analysis of Active Fire Alarm Systems in WTC 1 & 2 Robert J. Keough Rolf Jensen & Associates Raymond A. Grill, P.E., FSFPE Arup Fire Objectives Document the design and installation of the
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
REQUEST FOR PROPOSAL FOR: Fire Alarm Testing & Fire/Security System Monitoring
NHTI14-72 REQUEST FOR PROPOSAL FOR: Fire Alarm Testing & Fire/Security System Monitoring NHTI Concord s Community College PURPOSE: The purpose of this REQUEST FOR PROPOSAL is to establish a contract for
TrueAlarm Fire Alarm Controls
OPERATOR INTERFACE PANEL PULL TO OPEN DOOR IS NORMAL 12:35:15 am M 29 JAN 96 PRIORITY 2 SIGNALS SUPERVISORY TROUBLE D AL ARM SUPV AC K NOWLEDGE EMERGENCY OPERATING INSTRUCTIS OR TROUBLE CDITI: - INDICATOR
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
COMMISSIONING OF FIRE ALARM SYSTEMS
COMMISSIONING OF FIRE ALARM SYSTEMS OWNER FURNISHED The owner directly contracts an independent third party commissioning agent for this project. This Commissioning Plan has been included for reference
SUPPRESSION CONTROL PANELS
SUPPRESSION CONTROL PANELS Fire-Lite s new UL 864 Ninth Edition listed releasing panels are designed with the latest in microprocessor technology to meet the most demanding conventional releasing applications.
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015
Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 13860 (283100) FIRE ALARM SYSTEM The following standard shall be followed for the design of University
FIRE ALARM AND EMERGENCY VOICE EVACUATION SYSTEM
FIRE ALARM AND EMERGENCY VOICE EVACUATION SYSTEM PART 1.0 - GENERAL 1.1 DESCRIPTION: A. This section of the specifications includes the furnishing, installation, and connection of a multiprocessor controlled,
FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
SAFEPATH 4 Facility Communications System & Expansion Options
Notification SAFEPATH 4 Facility Communications System & Expansion Options SPB-320 SP40S SPB-80/4 SPB-160 SPRM SP4Z-A/B SP-SVC SP4-TZC Page SP40S Facility Communications System 2-4 Expansion Options SAFEPATH
FIRE DETECTION AND ALARM
Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program
TrueAlarm Fire Alarm Systems
TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es
FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION
Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus