TECHNICAL REVIEW OF SECONDARY CONTAINMENT SYSTEM TECHNOLOGY FOR ALASKA
|
|
|
- Trevor Jones
- 10 years ago
- Views:
Transcription
1 Final Report to STATE OF ALASKA DEPARTMENT OF ENVIRONMENTAL CONSERVATION DIVISION OF SPILL PREVENTION AND RESPONSE TECHNICAL REVIEW OF SECONDARY CONTAINMENT SYSTEM TECHNOLOGY FOR ALASKA May 1, 1998 Steven L. Anderson, P. E. Project Engineer Charles F. Cobb, P. E. Steven R. Thompson, P. E. Senior Engineer Principal Distribution: ADEC - 70 copies
2 May 1, i TABLE OF CONTENTS Page 1. INTRODUCTION Background Elements of Report Guide to Use of This Report Scope and Limitations of Report Disclaimer TYPES OF SECONDARY CONTAINMENT SYSTEMS Existing Systems In Alaska Typical Secondary Containment System Materials Geomembranes Compacted Soil Natural Soils Bentonite Admixture Soil Bedrock Permafrost Soils Steel Concrete Shotcrete Masonry Bituminous Liners Sprayed On Synthetics Alternative Materials or Methods Other Soil Admixtures Geosynthetic Clay Liners Cut-off Walls Grouting Other Concepts Remote Storage TECHNICAL ISSUES FOR ALASKA Design Permeability Chemical Resistance Durability Penetrations and Connections Other Design Issues Construction Constructability Construction Process Operation and Maintenance SECONDARY CONTAINMENT SYSTEM PERFORMANCE MONITORING Failure Mechanisms...44
3 May 1, ii Maintenance Inspection and Testing SECONDARY CONTAINMENT SYSTEM EVALUATION RESEARCH AND REFERENCES Research Methodology List of References...52 List of Tables Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Categories of Secondary Containment System Materials Secondary Containment System Technical Matrix Geomembrane Polymers for Secondary Containment Concrete and Masonry Surface Treatments Relative Permeability of Masonry Units Comparison of Sprayed On Synthetics Effects of Portland Cement on Soil Permeability Relative Corrosivity of Soils List of Figures Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Secondary Containment System (SCS) Featuring Concrete and Asphalt SCS Featuring Sprayed-on Synthetic SCS Featuring Permafrost SCS Featuring Natural and Compacted Soil SCS Featuring Geomembrane SCS Featuring Compacted Soil SCS Featuring Remote Storage Permeabilities of Compacted Soil Permeabilities of Natural Soil Hydraulic Conductivity in Consolidated and Unconsolidated Aquifers Permeability of Sand-Bentonite Mixtures Permafrost in Alaska Typical Geosynthetic Clay Liners Cut-off Walls Soil Grain Size vs. Grout Type Climatic Data for Alaska Typical Penetrations and Connections List of Appendices Appendix A Appendix B Appendix C Secondary Containment System Technical Detail Sheets Definition of Impermeable and Sufficiently Impermeable Secondary Containment System Visual Inspection Checklist
4 May 1, INTRODUCTION This report is intended to be a reference document for performing technical reviews of external secondary containment systems for spill prevention at above ground oil storage tank facilities in Alaska. This report provides: A general review of the types of secondary containment systems that might be used or proposed at a particular facility, including pros and cons; A review of technical issues that are important for the design and construction of a secondary containment system in Alaska, including a detailed list of technical information for a variety of systems; A discussion of failure mechanisms, maintenance, inspection, and testing issues that are important for monitoring the performance of a system; A list of additional information that may be required to conduct a complete evaluation of a specific secondary containment system. Regulators, operators, and other interested parties should find the report useful for several purposes. By studying this report, the reader will become familiar with the concept of secondary containment and the variety of materials and techniques that may be used, individually or in combinations, to contain a spill. The technical and performance information herein will allow regulators to determine if enough information is provided in an Oil Spill Contingency Plan to evaluate the sufficiency of the system, and if the operator has adequately planned to maintain a functional system. Operators will be able to identify a variety of alternatives that could be used to provide secondary containment, and the technical issues that need to be addressed during the design, construction, and operation of the system. While useful for designing or evaluating secondary containment systems, this report is not intended to be a complete listing of all design, construction, or operation considerations that may need to be addressed, or lead to a specific conclusion regarding the acceptability of an existing or proposed system for meeting the intent of any regulations. The reader is advised to consult an experienced professional engineer, in cooperation with the appropriate regulatory agency familiar with the actual conditions at the proposed site, for specific designs or evaluations. 1.1 Background Effective May 14, 1992, the Alaska Department of Environmental Conservation (ADEC) implemented comprehensively revised oil pollution prevention regulations under 18 AAC 75. These regulations required regulated industry operators to comply with secondary containment provisions as soon as possible, but no later than January 1, However, operators were allowed to pursue alternate compliance schedules if they could demonstrate substantial cause for the delay in implementation. Waivers of certain requirements were
5 May 1, offered if an operator could demonstrate that an equivalent level of protection could be achieved using a technology or procedure other than that required by the regulations. 18 AAC 75 requires secondary containment systems to be sufficiently impermeable to the substance being stored to protect groundwater from contamination and to contain a discharge until it can be detected and cleaned up. This performance based standard left some operators uncertain whether their existing system met the intent of the regulations, and left other operators faced with significant economic burdens in order to comply. Consequently, a number of owners and operators chose to pursue alternate compliance schedules and attempted to demonstrate that their existing systems met the intent of the regulations. Others questioned the effectiveness of the regulations and lobbied for their repeal. Some owners argued that they would incur additional problems as a result of compliance. In late 1993, the ADEC initiated an external workgroup that consisted of governmental agencies, industry owners and operators, and other interested parties. The purpose of the external workgroup was to discuss the issues surrounding the secondary containment requirements, and determine the best approach to resolving the problems that were identified. A result of this workgroup was an ADEC contract to develop a guidance document to assist the industry in complying with the secondary containment regulations. However, the contract was not satisfactorily completed and it was terminated in April of The ADEC then assembled an internal workgroup that consisted of members of various programs within the agency that were interested in resolving the secondary containment issues. Consequently, the ADEC developed the White Paper on Secondary Containment dated March 11, 1996 (White Paper), to respond to concerns over the secondary containment requirements, examine alternative solutions, and present a recommended course of action for the Department. The White Paper concluded that the current regulations provide the desired level of environmental protection and provide sufficient flexibility to address the problems faced by the industry. It was recommended that the current regulations be retained and that guidance documents be prepared to address areas of confusion and clarify the options available for compliance. The ADEC was then faced with performing technical evaluations of various alternatives proposed by operators to provide a sufficiently impermeable secondary containment system or an equivalent level of protection. To assist in this effort, the ADEC awarded a contract to Inc. (GAI), under which this report has been prepared, to conduct research and perform a technical review of secondary containment systems with an emphasis on impermeability and durability issues. The purpose of this review was to develop technical information about a variety of secondary containment systems at both existing facilities and at potential future facilities in order to provide the ADEC and storage tank owners and operators with a reference document on secondary containment systems. This report is the product of that review. A brief discussion of the major elements of this
6 May 1, report follows, including a guide on how to use this report, as well as a discussion on the scope and limitations of its use. 1.2 Elements of Report Section 1, Introduction contains a preview of the report, a review of the background of issues surrounding secondary containment systems in Alaska, and the scope and limitations of this report. Section 2, Types of Secondary Containment Systems presents a discussion of secondary containment systems used in Alaska, a description of typical and alternative materials used in key components of secondary containment systems, and a discussion of secondary containment systems that utilize a remote storage system. Section 3, Technical Issues for Secondary Containment Systems in Alaska contains discussions about design, construction, operation and maintenance issues that are important or unique to Alaska. Section 4, Performance Monitoring contains discussions about potential failure mechanisms, maintenance issues, inspections, and testing for secondary containment systems. Section 5, Secondary Containment System Evaluation lists additional information that may be required to evaluate a secondary containment system for compliance with State of Alaska regulations. Section 6, References contains a description of the research methodology and a listing of reference documents used in the development of this report. Appendix A contains individual technical detail sheets (TDS) for each of the materials discussed in Section 2. These sheets provide a limited amount of specific information for issues discussed in Section 3 and 4. Appendix B contains definitions of impermeable and sufficiently impermeable from State of Alaska regulations. Appendix C contains a checklist for a visual inspection of a secondary containment system. 1.3 Guide to Use of This Report Secondary containment systems often consist of several different types of materials that are assembled in various configurations to produce a system that is designed to contain a spill from a storage tank. Consequently, a variety of systems could be assembled to accomplish secondary containment. In order to conduct a limited technical review in an objective
7 May 1, manner, this report differentiates secondary containment systems based on categories of materials or methods used to provide the barrier to the migration of liquids that spill from the storage tanks or piping within the secondary containment area. If more than one type of material or method is used in a particular secondary containment system, the reader must assemble the various technical discussions contained in this report into a specific review of the particular system. This idea is discussed in additional detail in Section 2. The categories of secondary containment system materials that are reviewed in this report are listed on Table 1. Section 2 contains a general discussion of each category of material, including a list of the pros and cons of using the material in a secondary containment system. Table 2 contains a matrix that indicates the technical and performance items that are especially important for each of the categories of secondary containment system materials that are listed on Table 1 and reviewed in Section 2. Appendix A contains a Technical Detail Sheet (TDS) for each of these materials. The TDS for a particular category of material provides succinct information for the applicable technical and performance items indicated on Table 2. After reading the general discussion presented in Section 2, the reader can scan Table 2 to see which technical and performance items are critical for that material. Additional information can then be obtained by referring to the appropriate section of the particular TDS. Detailed discussions of technical and performance considerations for secondary containment systems in Alaska are discussed in Sections 3 and 4, respectively. Other information that may be required in order to perform a complete evaluation or design is listed in Section Scope and Limitations of Report The scope of this report involved the following three primary tasks: Conduct a technical review of the various secondary containment system technologies currently in use in Alaska, including a review of design, construction, operation, and maintenance issues for the system. Conduct research to find alternative secondary containment systems that have not yet been used in Alaska and conduct a technical review of the alternatives. Compile information that may be useful for monitoring the performance of secondary containment systems over the passage of time. This scope of work was clarified by the ADEC after a preliminary report prepared by GAI that consisted of a review of the work completed to date by the ADEC regarding secondary containment system impermeability issues, and a summary of the work proposed to complete the contract. GAI and the ADEC worked closely together in several meetings as
8 May 1, the project developed in order to keep the development of this report in line with the expectations and needs of the ADEC. Some limitations on the depth and applicability of this report became apparent as the project developed. Because of the large variety of materials used in the components of a secondary containment system, and the number of combinations of components that may be assembled, this report looks at the various secondary containment systems based on the unique attributes of the portion of the system used as a barrier to the migration of a spilled liquid. Certain aspects of secondary containment systems for tank farms have been excluded from the review, either because the information is readily available and easily applied, or because the elements are sufficiently complex and technical to be beyond the scope of this report. Those aspects specifically excluded from the scope of work include the following: Tank farm secondary containment system configurations necessary to meet codes such as National Fire Protection Association (NFPA) 30, Uniform Fire Code or other regulations; Double walled or diked steel tanks; Double bottomed tanks, or internal or external tank coatings or linings; Secondary containment systems for underground storage tanks; Secondary containment systems for offshore facilities. As previously mentioned, this report is intended to be a reference document to assist in performing technical reviews of external secondary containment systems for above ground oil storage tanks. While useful for designing or evaluating secondary containment systems, it is not intended to be a complete listing of all design, construction, or operation considerations that may need to be addressed, or lead to a specific conclusion regarding the acceptability of an existing or proposed system for meeting the intent of any regulations. 1.5 Disclaimer This reported is not intended to endorse, recommend, or approve of any of the materials, methods, illustrations, or concepts for providing secondary containment at a storage tank facility that are represented herein. No warranty regarding suitability of purpose is expressed or implied.
Secondary Containment of Large Aboveground Storage Tanks
Secondary Containment of Large Aboveground Storage Tanks Technology corner Posted / Last update: 01-08-1999 Publication: Petroleum Equipment & Technology Archive Issued: August 1999 Author: Myers Philip
PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT
PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT PREVENTING GROUNDWATER POLLUTION IS EVERYONE S JOB! Even if our drinking water comes from rivers, lakes, or reservoirs, we need to be mindful of
Well Site Spill Protection: Impacts, Trends and Technologies for Preventing Releases to Water Sources
Well Site Spill Protection: Impacts, Trends and Technologies for Preventing Releases to Water Sources Presented by: Tekla Taylor, R.G. and Archie Filshill, Ph.D. InterGEO Services, now a part of Golder
UltraTech International, Inc. Canadian Secondary Containment Requirements
UltraTech International, Inc. 11542 Davis Creek Court Jacksonville, Florida 32256 Canadian Secondary Containment Requirements The Canadian Council of Ministers of the Environment (CCME) is the major intergovernmental
The Fuel Storage Tank Regulations 2009
The Fuel Storage Tank Regulations 2009 October 2009 ED/RO1/015 The Fuel Storage Tank Regulations Issued by: The Regulation and Supervision Bureau for the water, wastewater and electricity sector in the
Application for the Construction or Installation of Aboveground Storage Tank (AST) Systems or Associated Underground or Over-water Piping Systems
Page 1 of 5 Application for the Construction or Installation of Aboveground Storage Tank (AST) Systems or Associated Underground or Over-water Piping Systems New Hampshire Department of Environmental Services
Radioactive Waste Storage Facility and Tank System Design Criteria Standards
UCRL-AR-133355 Rev 1 Radioactive Waste Storage Facility and Tank System Design Criteria Standards John Wood Rich Michalik Karen Doiron May 1999 DISCLAIMER This document was prepared as an account of work
DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY. August 2012
DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY August 2012 SECTION 2 The storage requirements in Directive 055 apply to upstream petroleum facilities, well sites, and pipelines
DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY
DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY FREQUENTLY ASKED QUESTIONS (FAQ) Question: Do fuel tanks fall under the requirements of Directive 055? No. For storage of fuels (e.g.,
Used Oil Guidance. Tank and Secondary Containment Requirements For Used Oil Processors
Used Oil Guidance Tank and Secondary Containment Requirements For Used Oil Processors Washington State Department of Ecology Publication Number 05-04-016 November 2005 For more information The Washington
Secondary Containment: Regulations & BMPs. Beth Powell Vice-President and General Manager New Pig Energy [email protected]
Secondary Containment: Regulations & BMPs Beth Powell Vice-President and General Manager New Pig Energy [email protected] Federal Secondary Containment Safeguarding method in addition to the primary
COMPLIANCE MANAGEMENT STRATEGIES. Presented by: Megan Kazmierczak, ECS Eclipse
COMPLIANCE MANAGEMENT STRATEGIES Presented by: Megan Kazmierczak, ECS Eclipse AST vs. UST Compliance requirements Aboveground Storage Tanks (ASTs): Misconception that ASTs are unregulated Most are subject
Section A SPCC Plan Implementation Checklist This section of the report addresses compliance with certain requirements of Federal Regulations 40 CFR 112. I. STATUS OF SPCC PLAN (40 CFR 112.3) YES NO A.
Outdoor Liquid Container Storage
Outdoor Liquid Container Storage SC-31 Objectives Cover Contain Educate Reduce/Minimize Description Accidental releases of materials from above ground liquid storage tanks, drums, and dumpsters present
District of Columbia Municipal Regulations UNDERGROUND STORAGE TANKS: GENERAL PROVISIONS 5500 COMPLIANCE WITH OTHER DISTRICT LAWS
CHAPTER 55 UNDERGROUND STORAGE TANKS: GENERAL PROVISIONS Section 5500 Compliance with Other District Laws 5501 Applicability of UST Regulations 5502 Partial Applicability of UST Regulations to Particular
Fact sheet 6: for farmers
Fact sheet 6: for farmers Fuel Oil Storage February 2011 Are you planning to substantially alter your fuel oil store, or add a new one? If so, this fact sheet will help you meet the requirements of The
Secondary Containment Systems for Aboveground Storage Tanks
New York tate Department of Environmental Conservation Division of pills Management 50WolfRoad Albany,NewYork12233-3750 Telephone: (518) 457-4351 FAX: (518)457-4332 MEMORANDUM eptember 28, 1994 To: Regional
Construction Materials Testing. Classes of Test
Construction Materials Testing Classes of Test February 2014 Copyright National Association of Testing Authorities, Australia 2014 This publication is protected by copyright under the Commonwealth of Australia
SAMPLE FRACTION MITIGATION CONTINGENCY PLAN FOR DIRECTIONAL DRILLING
SAMPLE FRACTION MITIGATION CONTINGENCY PLAN FOR DIRECTIONAL DRILLING 1 TABLE OF CONTENTS 1.0 Introduction and Purpose 3 2.0 Description of Work 3 3.0 Site Supervisor/Foremen Responsibilities 4 4.0 Equipment
Contingency Plan. Facility Name
Contingency Plan Facility Name This plan is reviewed annually and amended whenever changes occur that will significantly affect the ability of this facility to respond to an emergency situation. This includes
Fact sheet 6: for farmers
Fact sheet 6: for farmers Fuel Oil Storage June 2013 Are you planning to substantially alter your fuel oil store, or add a new one? If so, this fact sheet will help you meet the requirements of The Water
CONTAMINANT SOURCES. JUNE 1998 Printed on recycled paper
Rural Wellhead Protection Protection Fact Sheet Fact Sheet CONTAMINANT SOURCES JUNE 1998 Printed on recycled paper INTRODUCTION More than 75 percent of Wyoming s population relies on groundwater for part
Pollution Prevention And Best Management Practices For Dry Cleaners Operating In Broward County
FORWARD In 1991, the Broward County Environmental Protection and Growth Management Department, who was then known as the Department of Natural Resource Protection (DNRP), initiated the development of Pollution
Spill Prevention, Control and Countermeasure (SPCC) Rule
Spill Prevention, Control and Countermeasure (SPCC) Rule Code of Federal Regulations Title 40 CFR Part 112 Training Guide for Oil and Fuel handlers on Farms 1 Purpose of SPCC Rule To prevent oil discharges
Shop Fabricated Aboveground Tank Construction Standards
Shop Fabricated Aboveground Tank Construction Standards Wayne Geyer Steel Tank Institute Fourth Biennial Freshwater Spills Symposium 2002 March 19-12, 2002 Cleveland, OH One key to clean freshwater is
APPENDIX G Materials Storage and Handling Guidelines
APPENDIX G Materials Storage and Handling Guidelines 1.0 INTRODUCTION Operations at Austin-Bergstrom International Airport (ABIA) comprise several different industrial activities including aircraft, ground
A Guide to Structural Waterproofing
A Guide to Structural Waterproofing Part One Waterproofing Protection For Below Ground Structures 1 2012 W. R. Grace & Co Benjamin J. Brooks Table of Contents Grace Around The World Reference Material
TECHNICAL SPECIFICATIONS CEMENT-BENTONITE SLURRY TRENCH CUTOFF WALL
TECHNICAL SPECIFICATIONS CEMENT-BENTONITE SLURRY TRENCH CUTOFF WALL SCOPE This section of the specifications includes requirements for the Slurry Trench Cutoff Wall and related work as indicated on the
How To Safely Handle A Spill
WD DWGB 22 6 2010 Best Management Practices for Fueling and Maintenance of Excavation and Earthmoving Equipment Env Wq 401, Best Management Practices for Groundwater Protection, applies to a variety of
Contingency Plan Template. Hazardous Materials and Waste Management Division (303) 692-3300
Contingency Plan Template Hazardous Materials and Waste Management Division (303) 692-3300 October 2008 Contingency Plan A Large Quantity Generator of hazardous waste must have a written contingency plan
September 2008 AFC 4.6.2.1.(2) Page 1 of 5. Maximum Size and Aggregate Capacities of Aboveground Storage Tank Systems at Fuel Dispensing Stations
FIRE CODE VARIANCE September 2008 AFC 4.6.2.1.(2) Page 1 of 5 ISSUE Maximum Size and Aggregate Capacities of Aboveground Storage Tank Systems at Fuel Dispensing Stations The Alberta Fire Code (AFC) limits
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or
AN AEM TOOL FOR THE EVALUATION OF UNDESIGNED WASTE STORAGE FACILITIES
AN AEM TOOL FOR THE EVALUATION OF UNDESIGNED WASTE STORAGE FACILITIES REFERENCE National Handbook of Conservation Practices Code NY313 Waste Storage Facility. INTRODUCTION CAFO permits require an Agricultural
Spill Prevention, Control and Countermeasure (SPCC)
Spill Prevention, Control and Countermeasure (SPCC) History Original promulgation 1973, effective 1974 Codified in 40 CFR 112 (EPA Jurisdiction) Proposed rulemaking 1991, 1993 and 1997 Amended July 17,
Application for Approval to Construct or Upgrade and Operate a Storage Facility October 2015 CSB CSB13001
Application for Approval to Construct or Upgrade and Operate a Storage Facility October 2015 CSB CSB13001 In accordance with the Hazardous Substances and Waste Dangerous Goods Regulations, I hereby apply
the French experience
VLLW disposal and management of large volume of slightly contaminated materials the French experience Nicolas Solente Very Low Level Waste disposal in France The CIRES facility in Morvilliers VLLW waste
OIL STORAGE REQUIREMENTS OF THE SPCC REGULATIONS. Christopher J. Ecsedy, P.E. Fuss & O'Neill, Inc. 146 Hartford Road Manchester, CT 06040
ABSTRACT OIL STORAGE REQUIREMENTS OF THE SPCC REGULATIONS Christopher J. Ecsedy, P.E. Fuss & O'Neill, Inc. 146 Hartford Road Manchester, CT 06040 The SPCC regulations entail numerous requirements for the
A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS
A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS What is a groundwater protection plan? A groundwater protection plan identifies the activities being conducted that can pollute groundwater and
APPROVED. PXP 2009 Tank Leak Detection and Containment at Inglewood Oil Field. Baldwin Hills CSD Conditions L.18. and E.29.e.
PXP 2009 Tank Leak Detection and Containment at Inglewood Oil Field Baldwin Hills CSD Conditions L.18. and E.29.e. WORKING DRAFT SUBJECT TO CHANGE BASED ON COUNTY REVIEW AND ACCEPTANCE Prepared for: May
Ingredion ANZ Pty Ltd
Ingredion ANZ Pty Ltd 170 Epping Road, Lane Cove, NSW 2066 EPL: 518 Page 1 of 8 1. Purpose and Background POLLUTION INCIDENT RESPONSE The purpose of this Pollution Incident Response Management Plan (PIRMP)
Fuel Storage Who to ask: tank farm owners/operators
Fuel Storage Fuel Storage Who to ask: tank farm owners/operators 89. How many tank farms are there in the village and who owns them? Fuel tank farm The questions in the following section should be answered
Spill Prevention, Control and Countermeasure (SPCC) Training
Spill Prevention, Control and Countermeasure (SPCC) Training Fort Jackson 2015 Origins of SPCC Regulatory History 1972 Clean Water Act Oil Pollution Act of 1990 Spill Prevention Control and Countermeasures
Tanks: What's in store?
Tanks: What's in store? Technical and regulatory developments in tank construction prompt changes; operations and maintenance receive greater emphasis. Chemical Processing magazine By Wayne Geyer Tanks
Assessing Your Petroleum Product Storage Facilities
Assessing Your Petroleum Product Storage Facilities Protecting Your Water Quality Through a Farm & Home Assessment Why should you be concerned? Aboveground and underground storage of liquid petroleum products
ABOVE-GROUND STORAGE TANKS
ABOVE-GROUND STORAGE TANKS Above-ground storage tanks in Georgia are regulated by the State Fire Marshall and by the EPA. Above-ground tanks containing 1,100 gallons or less do not require any secondary
Appendix N Framework Spill Prevention, Containment, and Countermeasures Plan Prepared by: Idaho Power Company 1221 W Idaho Street Boise, ID 83702
Appendix N Framework Spill Prevention, Containment, and Countermeasures Plan Prepared by: Idaho Power Company 1221 W Idaho Street Boise, ID 83702 November 2011 TABLE OF CONTENTS 1.0 PURPOSE... 1 2.0 RESPONSIBILITY
Pervious Pavers. By: Rich Lahren. Hebron Brick & Block Supply
Pervious Pavers By: Rich Lahren Hebron Brick & Block Supply Stormwater Management and Control Issues Past emphasis was on flood control Today s emphasis is also on pollution More impermeable areas are
Extraction Oil and Gas, LLC. Diamond Valley Central Oil Terminal Waste Management Plan
Extraction Oil and Gas, LLC. Diamond Valley Central Oil Terminal Waste Management Plan Scope: This Extraction Oil and Gas Waste Management Plan has been prepared to provide operations personnel at the
FARM A SYST Farmstead Assessment System. Drinking Water Well Condition
G3536 1W FARM A SYST Farmstead Assessment System Worksheet #1 Assessing the Risk of Groundwater Contamination from Why should I be concerned? Drinking Water Well Condition About 95 percent of this country
FUELING AND FUEL STORAGE
FUELING AND FUEL STORAGE BENCHMARK Implement spill prevention measures whenever fuel is handled or stored. Report, minimize, contain and clean up spills that do occur. FUELING BMPS Spills of diesel, oil,
MAINE DEPARTMENT OF ENVIRONMENTAL PROTECTION
Oxford Hills Bus Garage 36 Brown St, Norway, ME Oil Storage Inspection 2/20/14 CONDITIONS OBSERVED Underground Oil Storage: 12,000 gallon underground oil storage tank (split 10,000 gallon diesel/2,000
CGA Standard Practices Series. Article 600 Standard for Pozzolan Enhanced Grouts Used in Annular Seals & Well Destruction
California Groundwater Association An NGWA Affiliate State PO Box 14369 Santa Rosa CA 95402 707-578-4408 fax: 707-546-4906 email: [email protected] website: www.groundh2o.org CGA Standard Practices Series
constructive solutions Fosroc total waterproofing protection of below-ground structures
constructive solutions Fosroc total waterproofing protection of below-ground structures Our profile Since the company s beginnings over 50 years ago, Fosroc has developed into an International leader in
CHAPTER 13 LAND DISPOSAL
CHAPTER 13 LAND DISPOSAL Supplemental Questions: Which of Shakespeare's plays is the source of the opening quote? The Tempest [1611-1612],Act: I, Scene: i, Line: 70. 13-1. Cite four reasons landfills remain
9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES. Hunter Underground Systems
9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES Hunter Underground Systems 9.01 General 9.02 Surface water Drainage 9.03 Groundwater Drainage 9.04 Dispersal of Septic Tank Effluent 9.01 The use of
Repair or Replacement - Band-Aids vs. Surgery
Repair or Replacement - Band-Aids vs. Surgery Using RCP for the Replacement of Failed or Undersized Culverts www.concrete-pipe.org Introduction and Background Our Nation s infrastructure owners are facing
Petroleum Tanks at Municipal Facilities
January/February 2013 Petroleum Tanks at Municipal Facilities This document was reprinted with permission from the New York Association of Towns Talk of the Towns/Topics magazine January/February 2013
Frequent Mishaps and Solutions with Regulated Aboveground Storage Tanks in Pennsylvania
Frequent Mishaps and Solutions with Regulated Aboveground Storage Tanks in Pennsylvania NISTM 4 th Annual Pennsylvania Storage Tank Conference April 25, 2013 Overview Common regulated ASTs missed Performance
PRESENT ISSUES FOR CENTRE DE LA MANCHE DISPOSAL FACILITY
PRESENT ISSUES FOR CENTRE DE LA MANCHE DISPOSAL FACILITY M. DUTZER, J.P. VERVIALLE, P. CHARTON Andra - Agence Nationale pour la Gestion des Déchets Radioactifs 1-7 rue Jean Monnet, 92298 Châtenay-Malabry
Critical Regulations SUMMARY OF. Stormwater Management Regulations (National Pollutant Discharge Elimination System or "NPDES ) 40 CFR 122.
SUMMARY OF Critical Regulations Stormwater Management Regulations (National Pollutant Discharge Elimination System or "NPDES ) 40 CFR 122.26 Spill Prevention, Control, and Countermeasures Rule (SPCC) 40
Suffolk County Department of Health Services. Division of Environmental Quality
Suffolk County Department of Health Services Division of Environmental Quality Guidelines For the Construction of Storage Areas for Portable Containers ~~~~ Clare B. Bradley, M.D., M.P.H. Suffolk County
Spill Control Prevention Plan (SCPP)
Spill Control Prevention Plan (SCPP) FACILITY INFORMATION PLEASE PRINT Facility Name: Mailing Address: Physical address if different: Owner Name: Owner Address: Primary Contact Name: Work Phone Number:
OREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
C. Section 014510 TESTING LABORATORY SERVICE.
SECTION 014500 QUALITY CONTROL PART 1 GENERAL 1.01 RELATED REQUIREMENTS A. Drawings and General Provisions of Contract, including General and Special Conditions and other Division 1 Specification Sections,
STRUCTURES. 1.1. Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL.
STRUCTURES 1. General. Critical structures may impact the integrity of a flood control project in several manners such as the excavation for construction of the structure, the type of foundation, backfill
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN XXXX FARM (CITY OR COUNTY), MICHIGAN CONTACT (NAME), OWNER CERTIFICATION: I hereby certify that I have examined the facility, and being familiar with the
SECTION 02150 REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section 02250.
02150-1 of 6 SECTION 02150 REMOVAL OR ABANDONMENT OF EXISTING 02150.01 GENERAL A. Description Removal or abandonment of existing utilities and underground structures shall include, but not necessarily
Farm Fuel Tank Safety Guide
Farm Fuel Tank Safety Guide This brochure is provided by North Dakota Department of Emergency Services, your Local Emergency Planning Committee, and the State Emergency Response Commission along with assistance
Treatment of a surface or structure to resist the passage of water in the absence of hydrostatic pressure. presence of hydrostatic pressure.
Recommend Approval: Team Leader Date Division Chief Date Approved: Director Date Maryland Department of Transportation State Highway Administration Office of Materials Technology MARYLAND STANDARD METHOD
Underground Storage Tanks
Underground Storage Tanks An Informational and Guidance Document for the University Community. Please contact Yale Environmental Health and Safety for latest Regulatory Requirements. A typical UST installation
TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe
TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe TN 5.14 February 2010 Introduction It may be at times necessary, in an aging infrastructure, to rehabilitate drainage and sanitary lines
Hazardous Waste Accumulation, Storage, & Labeling
Nadine Deak, Kalamazoo District Office 269-567-3592 or [email protected] Jenny Bennett, Gaylord District Office 989-705-2421 or [email protected] Hazardous Waste Accumulation, Storage, & Labeling
Arctic King Fuel Tanks meet the Environment Canada TECHNICAL REQUIREMENTS FOR COLLAPSIBLE FABRIC STORAGE TANKS (BLADDERS) - December 17, 2009
Arctic King Fuel Tanks meet the Environment Canada TECHNICAL REQUIREMENTS FOR COLLAPSIBLE FABRIC STORAGE TANKS (BLADDERS) - December 17, 2009 1. Fuel Bladders a. The fuel bladder should be manufactured
Spill Prevention, Control, and Countermeasures (SPCC) Regulations Update
Spill Prevention, Control, and Countermeasures (SPCC) Regulations Update The current deadline for most facilities (including typical mining and aggregate operations) is November 10, 2011. All facilities
Vapor Corrosion Inhibitors (VCIs) for Storage Tanks Corrosion Controlled Cost Controlled
Vapor Corrosion Inhibitors (VCIs) for Storage Tanks Corrosion Controlled Cost Controlled Presented by Kelly Baker, Zerust Oil & Gas Efim Lyublinski, Monique Posner, Terry Natale, Yefim Vaks, Ronnie Singh
ACTIVITY NAME. Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas
ACTIVITY NAME Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas CY 2014 BOTTOM LINE UP FRONT To prevent oil discharges
CHAPTER 10 POLLUTION PREVENTION PLAN
CHAPTER 10 10.1 INTRODUCTION Virginia Stormwater Management Program (VSMP) land-disturbing activities covered under the General Construction Permit (GCP) are required to develop a Stormwater Pollution
Temporary Batch Plants
Categories EC SE TC WE NS WM Erosion Control Sediment Control Tracking Control Wind Erosion Control Non-Stormwater Management Control Waste Management and Materials Pollution Control Legend: Primary Category
The following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
Domestic heating Fuel storage tanks
Domestic heating Fuel storage tanks Oil leaks Prevention and action www.west-norfolk.gov.uk Environmental Health and Housing Borough Council of King s Lynn & West Norfolk, King s Court, Chapel Street,
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
Spill Prevention, Control and Countermeasure Plan (SPCC) Program
United States Environmental Protection Agency Office of Emergency Management August 2013 www.epa.gov/emergencies Spill Prevention, Control and Countermeasure Plan (SPCC) Program Bulk Storage Container
Design, Construction and Maintenance of Permeable Pavements Case Studies and Technical Resources Robert Bowers, P. Eng.
Design, Construction and Maintenance of Permeable Pavements Case Studies and Technical Resources Robert Bowers, P. Eng. Source: CH2M Hill The Presenter Robert Bowers, P.Eng., LEED GA [email protected] Director
Cardok Sàrl CP37 CH-1295 Tannay Switzerland Phone: 0041 22 77 66 051 [email protected]
CARDOK CARLIFT Fast access to underground garages Fast, Silent, Discreet, Design, High-Tech Installation to replace an access ramp on private property Dimensions: (Built to measure, all dimensions can
History of the SPCC Rule
2010 SPCC Training SPCC Rule History of the SPCC Rule The SPCC plan is a document required under the clean water act (CWA) It became effective in 1972 and has changed little in 32 years. The rule was formally
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
The Pipelines Regulations, 2000
PIPELINES, 2000 P-12.1 REG 1 1 The Pipelines Regulations, 2000 being Chapter P-12.1 Reg 1 (effective April 1, 2000) as amended by the Statutes of Saskatchewan, 2014, c.21. NOTE: This consolidation is not
Steel Tank Institute AST Inspections. Dana Schmidt, PE STI/SPFA
Steel Tank Institute AST Inspections Dana Schmidt, PE STI/SPFA Agenda Brief review of SPCC Rule SPCC relevance to small tanks and small facilities. SP001 Standard for Inspection of Aboveground Storage
Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction
T e c h n i c a l n o t e Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction Number J450 February 2009 Controlling against moisture damage in structures depends upon proper system
SILICON VALLEY CLEAN WATER. May 2015
SILICON VALLEY CLEAN WATER May 2015 Slug Discharge Control and Spill Containment Guidelines This document was revised and used with the permission of the Los Angeles County Sanitation District, Industrial
Natural Resources Conservation Authority Guidelines for Secondary Containment of Hazardous Liquids stored Above-ground
Natural Resources Conservation Authority Guidelines for Secondary Containment of Hazardous Liquids stored Above-ground December 2011 Table of Contents Definition of Terms... 2 Requirements for Secondary
SECTION XXXXXX TECHNICAL SPECIFICATIONS FOR INSTALLATION OF PROTECTIVE COATINGS FOR MANHOLES, WETWELLS, AND OTHER SANITARY SEWER STRUCTURES
1.00 PART 1 GENERAL 1.01 SCOPE A. It is the intent of this contract to install a 100% solids epoxy monolithic coating to the walls, benches and inverts of all manholes and the specified surfaces of other
June 2007 CHAPTER 7 - CULVERTS 7.0 CHAPTER 7 - CULVERTS 7.1 GENERAL
7.0 7.1 GENERAL For the purpose of this manual, culverts are defined as structures that are completely surrounded by soil and located below the surface of the roadway parallel to the general direction