1 Wind Farm Power Station (WFPS) Performance Monitoring Process Effective 1 st October 2015 MAIN CHANGES from previous version published 1 st February Changing the standard for APC in performance monitoring from ±1 MW to the greater of +/-1MW or +/-3%. 2. AAP standard: rolling 14-day of 6%, 2 or more days of 6%. 3. Performance Monitor can close any issue without the Dispatch Test after analysing the WFPS recent performance and or associated information supplied by the WFPS. WFPS Performance Monitoring Page 1 of 16
2 1. INTRODUCTION The Wind Farm Power Station (WFPS) performance monitoring process is developed and effective since 1 st February, This process follows the SEM Committee decision published on the Principles of Dispatch and the Design of the Market Schedule in the Trading and Settlement Code SEM published on 26 th August 2011 and the TSO operational policy Wind Farm Controllability Categorisation Policy published on 5 th March, Pre Requisite: All TSO connected customers in Ireland must meet standards as set out in the relevant TSO Grid Code. All DSO connected customers in Ireland must meet standards set out in the ESB Distribution Code. 1.1 WFPS Categories The Wind Farm Controllability categories apply to all TSO connected WFPS and those DSO WFPS under the Wind Farm Controllability Categorisation Policy 1 with exemptions as follows: 1. WFPS which are exempted from controllability requirements under the relevant Codes. 2. WFPS which are connected pre-grid Code or pre-distribution Code. 3. WFPS which are less than 5MW. There are 3 categories of dispatch which are implemented by the control centres in a sequential manner for curtailment or constraint events. Non categorised WFPS are exempt from curtailment/constraint. Category (i) - Category (i) is a WFPS that is not compliant with the Controllability requirements as set out by the relevant Grid Code. For WFPS with the active power control system not working, the TSO will dispatch the WFPS by the Wind Dispatch Tool. If this fails, for TSO connected WFPS, the TSO will dispatch the TSO connected WFPS by opening the circuit breaker or point of connection to the system. If this fails, for DSO connected WFPS, the TSO will request the DSO to disconnect the DSO connected WFPS by opening the circuit breaker or point of connection to the system. Category (ii) - Category (ii) is a WFPS with controllability status compliant with the Controllability Requirements as specified by the relevant Grid Code. WFPS within Category (ii) under the TSO s control will be dispatched via the TSO Wind Dispatch Tool on a pro-rata basis (pro-rata of Availability Active Power, not MEC or output). Category (iii) - Category (iii) is a WFPS which has been recently energised and has a commissioning and testing programme which has been agreed by the TSO/DSO. 1 WFPS Performance Monitoring Page 2 of 16
3 1.2 Scope of the WFPS Performance Monitoring Process This WFPS performance monitoring process is only applicable to units which are in Category (ii) as outlined above. 2. COMMUNICATION There are 3 main points of contact relevant for this performance monitoring process: 2.1 Transmission connected wind farms in ROI 2.2 Distribution connected wind farms in ROI 2.1 Transmission connected wind farm in ROI As set out in the TSO Grid Code and ESB Distribution Code, the TSO (EirGrid) is responsible for communicating performance monitoring issues directly with transmission connected WFPS. Where transmission connected WFPS in Ireland have any questions the contact address is: [email protected] 2.2 Distribution connected wind farm in ROI As set out in the ESB Distribution Code, the DSO (ESB Networks) is responsible for communicating performance monitoring issues with the distribution connected WFPS. Where distribution connected WFPS have any questions the contacts for the relevant ESB Networks person is given below: [email protected] Any queries in relation to this document, please contact the relevant TSO or DSO as per contact details above. WFPS Performance Monitoring Page 3 of 16
4 3. DAILY PERFORMANCE MONITORING PROCESS The following processes are effective on a daily basis for controllability category 2 (ii) WFPS from 01/08/2015: 3.1 Daily process applicable to TSO Connected WFPS in ROI 3.2 Daily process applicable to DSO Connected WFPS in ROI 3.3 Case examples (for demonstration purpose only) 3.1 Daily Process applicable to TSO Connected WFPS in ROI STEP DESCRIPTION TIMELINE 1 The TSO carries out performance monitoring each Business Day (BD) for the previous Day for Category (ii) WFPS. This check mainly includes identification of: A single non-compliance with an Active Power Dispatch Instruction(s). The TSO check if the WFPS has achieved the required Active Power Dispatch Instruction with the greater of an allowable tolerance of ± 1 MW or ± 3% of their registered capacity. and an inaccuracy of the Available Active Power (AAP) signal greater than the standard of 6% for 2 or more consecutive days, or a failure of the AAP signal is identified (i.e. it stops working) Following identification of the above, the TSO then investigates whether the issue is associated with a communications problem i.e. SCADA or Remote Terminal Unit (RTU). 1 BD If the issue is not associated with communications then TSO will carry out step 2. If the issue is associated with communications, the TSO will address this issue and the TSO will take no further action against the wind farm. The TSO will issue a 10 days non-compliance notice to WFPS. The WFPS will have up to 10 business days from the issuance date of the 10 days non-compliance notice to rectify and confirm resolution with the TSO. 2 The WFPS shall investigate and communicate the cause of the noncompliance and the resolution required to regain compliance to the TSO. 10 BD To clarify, during the 10 days non-compliance notice period, the WFPS may contact the TSO to discuss their case further. 2 WFPS Performance Monitoring Page 4 of 16
5 3 4 On expiry of 10 days non-compliance notice period, the WFPS will now be subject to a dispatch test by the TSO. To clarify, the timing of the dispatch testing will be dependent on wind condition and position in the queue of wind dispatch testing taking place at the time. During the period of the WFPS waiting for a dispatch test, the TSO will take into account the WFPS recent performance and or associated information supplied by the WFPS up to this point. The TSO may decide to close the 10 days non-compliance notice at any period during this step without carrying out a dispatch test. Otherwise, proceed to step 5. Dispatch test has been carried out with the WPFS. TSO will confirm the dispatch test result to the WFPS namely a Pass or a Fail. Step 2 + dispatch test date 5 PASS: WFPS will remain in category (ii) where the dispatch test was a PASS and the TSO will notify the WFPS that the non-compliance is closed and no further action is required. Dispatch test date + 10 BD FAIL: Where the test was a FAIL the TSO will proceed with the transfer of the WFPS into category (i) and notify the WFPS of effective date. Proceed to Step The WFPS will remain in category (i), once the WFPS has resolved the issue, it can request another dispatch test under the normal dispatch testing process to prove that the WFPS is now compliant. When a WFPS is deemed to have passed the dispatch test from step 6. The TSO will advise the WFPS of the effective date of moving back to category (ii). As available Step BD WFPS Performance Monitoring Page 5 of 16
6 3.2 Daily Process applicable to DSO Connected WFPS in ROI STEP DESCRIPTION TIMELINE The TSO carries out performance monitoring each Business Day (BD) for the previous Day for Category (ii) WFPS. This check mainly includes identification of: 1 and A single non-compliance with an Active Power Dispatch Instruction(s). In other words, the TSO check if the WFPS has achieved the required Active Power Dispatch Instruction with the greater of an allowable tolerance of ± 1 MW or ± 3% of their registered capacity. an inaccuracy of the Available Active Power (AAP) signal greater than the standard of 6% for 2 or more consecutive days, or a failure of the AAP signal is identified (i.e. it stops working) Following identification of the above, the TSO then investigates whether the issue is associated with a communications problem i.e. SCADA or Remote Terminal Unit (RTU). 1 BD If the issue is not associated with communications then the TSO will inform the DSO and the DSO will carry out step 2. If the issue is associated with communications, the TSO will address this issue and the TSO will take no further action against the wind farm. The DSO (ESB Networks) will issue a 10 days non-compliance notice to WFPS. The WFPS will have up to 10 business days from the issuance date of the 10 days non-compliance notice to rectify and confirm resolution with the TSO. 2 The WFPS shall investigate and communicate the cause of the noncompliance to the DSO and the resolution required to regain compliance to the TSO. 10 BD 3 To clarify, during the 10 days non-compliance notice period, the WFPS may contact the DSO to discuss their case further. On expiry of 10 days non-compliance notice period, the WFPS will now be subject to a dispatch test by the TSO. To clarify, the timing of the dispatch testing will be dependent on wind condition and position in the queue at the time. Step 2 + dispatch test date WFPS Performance Monitoring Page 6 of 16
7 During the period of the WFPS waiting for a dispatch test, the TSO will take into account the WFPS recent performance and or associated information supplied by the WFPS up to this point. 4 The TSO may decide to close the 10 days non-compliance notice at any period during this step without carrying out a dispatch test. In this case, the DSO will notify the WFPS that the issue is now closed. Otherwise, proceed to step 4. Dispatch test has been carried out with the WPFS. TSO will confirm the dispatch test result to the WFPS namely a Pass or a Fail. 5 PASS: WFPS will remain in category (ii) where the dispatch test was a PASS and the TSO will notify the WFPS that the non-compliance is closed and no further action is required. Dispatch test date + 10 BD FAIL: Where the test was a FAIL the TSO will proceed with the transfer of the WFPS into category (i) and notify the WFPS of effective date. Proceed to Step The WFPS will remain in category (i), once the WFPS has resolved the issue, it can request another dispatch test under the normal dispatch testing process to prove that the WFPS is now compliant. When a WFPS is deemed to have passed the dispatch test from step 6. The TSO will advise the WFPS of the effective date of moving back to category (ii). As available Step BD WFPS Performance Monitoring Page 7 of 16
8 Important note for following the examples below: If you are a transmission connected WFPS in ROI, your point of contact will be the TSO. If you are a distribution connected WFPS in ROI, your point of contact will be the DSO. The TSO will communicate any non-compliance to the DSO who will in turn issue the non-compliance to the relevant WFPS. 3.3 Case Example 1 An WFPS has an Available Active Power Issue SEQUENCE OF EVENT DESCRIPTION The TSO identified a Category (ii) WFPS from the daily performance monitoring process where the WFPS Available Active Power (AAP) signal had stopped working i.e. froze at a constant value. Figure 1: Available Active Power Issue with WFPS X The TSO investigates whether the issue is associated with a communications problem and found all communications signals were working at the time in question for the WFPS. The TSO or DSO will issue a 10-day non-compliance notice to the WFPS. At this point The WFPS will have up to 10 business days from the issuance date of the 10 days non-compliance notice to rectify and confirm resolution with the TSO or DSO. The WFPS shall investigate and revert back to the TSO or DSO as soon as possible the cause of the non-compliance and the resolution required to regain compliance. TIMELINE 1 BD 1 BD 10 BD 4 5 To clarify, during the 10 days non-compliance notice period, the WFPS may contact the TSO or DSO to discuss their case further. On expiry of 10 days non-compliance notice period, the WFPS is now subject to a dispatch test by the TSO. A dispatch test has been carried out by the TSO on 12 BD. 11 BD 16 BD WFPS Performance Monitoring Page 8 of 16
9 The TSO confirm the dispatch test result to the WFPS PASS: WFPS will remain in category (ii) and the TSO will notify the WFPS that the non-compliance is closed and no further action is required. WFPS revert to normal. 6 FAIL: The TSO will proceed with the transfer of the WFPS into category (i) and notify the WFPS of effective date. The WFPS should request a dispatch test following resolution. In order for the WFPS to move back to category (ii), the WFPS must pass the subsequent dispatch test Step BD Available Active Power (MW) signal freezes Available Active Power (MW) Active Power Output (MW) Figure 1: Available Active Power issue with WFPS X WFPS Performance Monitoring Page 9 of 16
10 Case Example 2 WFPS has an Active Power Dispatch Instruction Issue SEQUENCE OF EVENT DESCRIPTION The TSO identified a Category (ii) WFPS from the daily performance monitoring process where the WFPS Active Power Dispatch Instruction does not comply with the standard: A single non-compliance with an Active Power Dispatch Instruction(s). The WFPS has not achieved the required Active Power Dispatch Instruction with the greater of an allowable tolerance of ± 1 MW or ± 3% of their registered capacity. Figure 2: Active Power set point issue with WFPS Y The TSO investigates whether the issue is associated with a communications problem and found all communications signals were working at the time in question for the WFPS. The TSO or DSO will issue a 10-day non-compliance notice to the WFPS. At this point The WFPS will have up to 10 business days from the issuance date of the 10 days non-compliance notice to rectify and confirm resolution with the TSO or DSO. TIMELINE 1 BD 1 BD 10 BD The WFPS shall investigate and revert back to the TSO or DSO as soon as possible the cause of the non-compliance and the resolution required to regain compliance. 4 To clarify, during the 10 days non-compliance notice period, the WFPS may contact the TOS or DSO to discuss their case further. On expiry of 10 days non-compliance notice period, the WFPS is now subject to a dispatch test by the TSO. 11 BD 5 A dispatch test has been carried out by the TSO on 12 BD. 12 BD 6 The TSO confirm the dispatch test result to the WFPS Step BD PASS: WFPS will remain in category (ii) and the TSO will notify the WFPS that the non-compliance is closed and no further action is required. WFPS revert to normal. FAIL: The TSO will proceed with the transfer of the WFPS into category (i) and notify the WFPS of effective date. The WFPS should request a dispatch test following resolution. In order for the WFPS to move back to category (ii), the WFPS must pass the subsequent dispatch test. WFPS Performance Monitoring Page 10 of 16
11 Available Active Power (MW) Active Power Output (MW) Active Power Setpoint (MW) Active Power Setpoint Feedback (MW) Figure 2: Active Power set point issue with WFPS Y WFPS Performance Monitoring Page 11 of 16
12 4. MONTHLY PERFORMANCE MONITORING The TSO prepares a monthly Performance Monitoring reports on all category (ii) WFPS. A summary report will be issue to the WFPS on a monthly basis. The purpose of this report is to performance monitor: The Available Active Power signal quality is within the required standard 3 (6%) as this is not covered in the WFPS performance monitoring daily process. The WFPS achieves the required Active Power dispatch instruction with the greater of an allowable tolerance of ± 1 MW or ± 3% of their registered capacity. The following process applies to all category (ii) WFPS effective from 01/08/2015: 3.4 TSO Connected WFPS Monthly Process applicable to TSO Connected WFPS in ROI STEP DESCRIPTION TIMELINE 1 TSO will issue a summary of the reports including any actions required to the WFPS from the monthly process. There is no further action required from the WFPS if there is no performance issue reported. Month End +10 BD 2 The TSO in the monthly process checks for: and A single non-compliance with an Active Power Dispatch Instruction(s). The TSO checks if the WFPS has achieved the required Active Power Dispatch Instruction with the greater of an allowable tolerance of ± 1 MW or ± 3% of their registered capacity. an inaccuracy of the Available Active Power (AAP) signal greater than the standard of 6% for 2 or more consecutive days, or a failure of the AAP signal is identified (i.e. it stops working) Following identification of the above, the TSO then investigates whether the issue is associated with a communications problem i.e. SCADA or Remote Terminal Unit (RTU). Month End +10 BD If the issue is not associated with communications then TSO will carry out step 3. 3 If the issue is associated with communications, the TSO will address this issue and the TSO will take no further action against the wind farm. The TSO will issue a 10 days non-compliance notice to WFPS. Month End + 10 BD WFPS Performance Monitoring Page 12 of 16
13 The WFPS will have up to 10 business days from the issuance date of the 10 days non-compliance notice to rectify and confirm resolution with the TSO. The WFPS shall investigate and revert back to the TSO as soon as possible the cause of the noncompliance and the resolution required to regain compliance. 4 To clarify, during the 10 days non-compliance notice period, the WFPS may contact the TSO to discuss their case further. On expiry of 10 days non-compliance notice period, the WFPS will now be subject to a dispatch test by the TSO. To clarify, the timing of the dispatch testing will be dependent on wind condition and position in the queue at the time. Step 3 + dispatch test date 5 During the period the WFPS is waiting for a dispatch test, the TSO will take into account the WFPS recent performance and or associated information supplied by the WFPS up to this point. The TSO may decide to close the 10 days non-compliance notice at any period during this step without carrying out a dispatch test. Otherwise, proceed to step 6. 7 Dispatch test has been carried out with the WPFS. TSO will confirm the dispatch test result to the WFPS namely a Pass or a Fail. PASS: WFPS will remain in category (ii) where the dispatch test was a PASS and the TSO will notify the WFPS that the non-compliance is closed and no further action is required. Dispatch test date + 10 BD FAIL: Where the test was a FAIL the TSO will proceed with the transfer of the WFPS into category (i) and notify the WFPS of effective date. Proceed to Step The WFPS will remain in category (i), once the WFPS has resolved the issue, it can request another dispatch test under the normal dispatch testing process to prove that the WFPS is now compliant. When a WFPS is deemed to have passed the dispatch test from step 8. The TSO will advise the WFPS of the effective date of moving back to category (ii). As available Step BD WFPS Performance Monitoring Page 13 of 16
14 3.5 DSO Connected WFPS Monthly Process applicable to DSO Connected WFPS in ROI STEP DESCRIPTION TIMELINE 1 TSO will issue a summary of the reports to the DSO including any actions required to the WFPS from the monthly process. The DSO will in turn communicate this to the WFPS. There is no further action required from the WFPS if there is no performance issue reported. Month End The TSO in the monthly process checks for: 2 and A single non-compliance with an Active Power Dispatch Instruction(s). In other words, the TSO check if the WFPS has achieved the required Active Power Dispatch Instruction with the greater of an allowable tolerance of ± 1 MW or ± 3% of their registered capacity. an inaccuracy of the Available Active Power (AAP) signal greater than the standard of 6% for 2 or more consecutive days, or a failure of the AAP signal is identified (i.e. it stops working) Month End Following identification of the above, the TSO then investigates whether the issue is associated with a communications problem i.e. SCADA or Remote Terminal Unit (RTU). If the issue is not associated with communications then TSO will carry out step 3. If the issue is associated with communications then TSO will take no further action. The DSO will issue a 10 days non-compliance notice to WFPS. Month End + 10 BD 3 The WFPS will have up to 10 business days from the issuance date of the 10 days non-compliance notice to rectify and confirm resolution with the TSO. The WFPS shall investigate and revert back to the TSO as soon as possible the cause of the noncompliance and the resolution required to regain compliance. To clarify, during the 10 days non-compliance notice period, the WFPS may contact the TSO to discuss their case further. WFPS Performance Monitoring Page 14 of 16
15 4 On expiry of 10 days non-compliance notice period, the WFPS will now be subject to a dispatch test by the TSO. To clarify, the timing of the dispatch testing will be dependent on wind condition and position in the queue at the time. Step 3 + dispatch test date 5 During the period the WFPS is waiting for a dispatch test, the TSO will take into account the WFPS recent performance and or associated information supplied by the WFPS up to this point. The TSO may decide to close the 10 days non-compliance notice at any period during this step without carrying out a dispatch test. Otherwise, proceed to step 6. Dispatch test has been carried out with the WPFS. TSO will confirm the dispatch test result to the WFPS namely a Pass or a Fail. 6 PASS: WFPS will remain in category (ii) where the dispatch test was a PASS and the TSO will notify the WFPS that the non-compliance is closed and no further action is required. Dispatch test date + 10 BD FAIL: Where the test was a FAIL the TSO will proceed with the transfer of the WFPS into category (i) and notify the WFPS of effective date. Proceed to Step 7. 7 The WFPS will remain in category (i), once the WFPS has resolved the issue, it can request another dispatch test under the normal dispatch testing process to prove that the WFPS is now compliant. As available 8 When a WFPS is deemed to have passed the dispatch test from step 7. The TSO will advise the WFPS of the effective date of moving back to category (ii). Step BD As noted in section 3 the daily performance monitoring process only identifies when the Available Active Power signals stops working 3 WFPS Performance Monitoring Page 15 of 16
16 4 PUBLICATION AND CHANGE CONTROL This document is developed jointly by TSO and DSO. It will be reviewed as required to maintain the effectiveness of the TSO Grid Code and ESB Distribution Code. I s s u e D a t e R e c o r d o f a m e n d m e n t s V / 0 1 / V e r s i o n 1 V / 0 6 / V e r s i o n 2 This document can be found on EirGrid website: ESB Networks website: 5 ABBREVIATIONS WFPS TSO DSO APC AAP SEM ROI ESB BD Wind Farm Power Station Transmission System Operator Distribution System Operator Active Power Control Available Active Power Single Electricity Market Republic of Ireland Electricity Supply Board Business day WFPS Performance Monitoring Page 16 of 16
Post Operational Readiness. Operational Services and Performance
Post Operational Readiness Confirmation i Post Operations Certificate 19 th November 2012 Dave Carroll Operational Services and Performance EirGrid Overview Process Pre-Requisites 1. Performance Monitoring
Priority Dispatch in Real Time Operation. Marie Hayden
Priority Dispatch in Real Time Operation Marie Hayden Presentation Reasons for dispatching units with Priority Dispatch Changes in approach with SEM-62 Who has Priority Dispatch Today? Unit Type MW Interconnector
Contestability on the Distribution System ESB Networks Key Principles and Processes Paper
Contestability on the Distribution System ESB Networks Key Principles and Processes Paper Revision Date: 01/09/2010 Revision No.: 0 Document No: DOC-090211-BGY Issued by: ESB Networks Ltd. Approved by:
Context: significant penetration of DG = increased risks for system security
Distributed Generation: towards an effective contribution to power system security IEEE Tampa GM 2007: Panel on Impact of Dispersed Generation on Power System structure & security Bruno Meyer Outline Context:
A GUIDE TO. Connecting Renewable and CHP Electricity Generators to the Electricity Network
A GUIDE TO Connecting Renewable and CHP Electricity Generators to the Electricity Network A Guide to Connecting Renewable and CHP Electricity Generators to the Electricity Network October 2008 Guide prepared
ENTSO-E Network Code on Emergency and Restoration
ENTSO-E Network Code on Emergency and Restoration Notice 25 March 2015 This Network Code represents ENTSO-E s final proposals in line with the ACER Framework Guidelines on Electricity System Operation
Single Electricity Market. Principles of Dispatch and the Design of the Market Schedule in the Trading and Settlement Code
Single Electricity Market Principles of Dispatch and the Design of the Market Schedule in the Trading and Settlement Code SEM Committee Decision Paper 26 th August 2011 SEM-11-062 EXCECUTIVE SUMMARY The
ENTSO-E Network Code on Emergency and Restoration
ENTSO-E Network Code on Emergency and Restoration 25 March 2015 Notice This Network Code represents ENTSO-E s final proposals in line with the ACER Framework Guidelines on Electricity System Operation
55 Amendment of section 1 (interpretation) of the VAT Act 1972
54 Interpretation (Part 3) This section contains definitions of the legal citations used in Part 3. This is a conventional provision in Finance Acts. It allows abbreviated terms to be used in reference
ALSTOM Grid s solution
NETWORK MANAGEMENT SOLUTIONS Integrating renewable energy resources ALSTOM Grid s solution As a global solutions provider for a sustainable energy future, ALSTOM is strongly committed to the development
Market Growth and New Regulations Demand Network Modernization
CASE ESB NETWORKS: POLE TOP COMMUNICATION INCREASES EFFICIENCY IN IRELAND Viola s solution for remotely operating pole-top reclosers and switches increases reliability, cuts operating costs and helps to
Determination of 2010 Transmission Allowed Revenue and Use of System Tariffs
Determination of 2010 Transmission Allowed Revenue and Use of System Tariffs DOCUMENT TYPE: REFERENCE: DATE PUBLISHED: QUERIES TO: Determination Paper CER/09/140 2 September 2009 Jamie Burke ([email protected])
CLASS Voltage Regulation Scheme. 27 February 2014
CLASS Voltage Regulation Scheme 27 February 2014 Functional Specifications and Voltage Regulation Scheme for the Autonomous Substation Controllers (ASCs) Date: 27 February 2014 Page 2 of 26 Table of Contents
ATTACHMENT G. Network Operating Agreement
ATTACHMENT G Network Operating Agreement 1. PURPOSE OF NETWORK OPERATING AGREEMENT The purpose of this Agreement is to identify contractual requirements related to Network Integration Transmission Service
COMPLIANCE REVIEW OF 2006/07 ASSET MANAGEMENT PLAN. Top Energy Limited
PB ASSOCIATES COMPLIANCE REVIEW OF 2006/07 ASSET MANAGEMENT PLAN Prepared for PB Associates Quality System: Document Identifier : 153162 Top Energy Final Report Revision : 2 Report Status : Final Date
ENTSO-E Working Draft Network Code on Emergency and Restoration
ENTSO-E Working Draft Network Code on Emergency and Restoration DRAFT FOR THE FOURTH PUBLIC WORKSHOP Notice 22 January 2015 This document reflects the status of the work of Transmission System Operator
Domestic Customer Tariff Breakdown - RoI Note this is approximate due to tariff and consumption variations
Guide to Electricity price formation in Ireland and Northern Ireland The numbers The average household consumes 4,300 kwh 1 of electricity per annum in Ireland and 4,100 in Northern Ireland. At an average
References... 4. Appendices... 5. I. INTRODUCTION... 6 A. Background... 6 B. Standards... 6
ISO New England Operating Procedure No. 14 - Technical Requirements for Generators, Demand Resources, Asset Related Demands and Alternative Technology Regulation Resources Effective Date: January 29, 2015
Benefits of a Modern SCADA Protocol DNP3 vs Modbus
Benefits of a Modern SCADA Protocol DNP3 vs Modbus November 07 Benefits of using modern protocols for SCADA A protocol is simply the rules that govern the data transfer between parts of a control system.
Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.
Generation Interconnection System Impact Study Report For PJM Generation Interconnection Request Queue Position X1-114 Sandyston January 2012 Preface The intent of the System Impact Study is to determine
Technical Requirements for Renewable Energy Systems Connected to the Low Voltage (LV) Network via Inverters
Technical Requirements for Renewable Energy Systems Connected to the Low Voltage (LV) Network via Inverters Specification Number: HPC-9FJ-12-0001-2012 CONTENTS 1 Introduction... 6 1.1 Context... 6 1.2
ELECTRICITY SUPPLY BOARD (a body corporate established in Ireland under the Electricity (Supply) Acts 1927-2004 of Ireland)
OFFERING CIRCULAR SUPPLEMENT ELECTRICITY SUPPLY BOARD (a body corporate established in Ireland under the Electricity (Supply) Acts 1927-2004 of Ireland) ESB FINANCE LIMITED (a private company incorporated
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING
Different types of electricity markets modelled using PLEXOS Integrated Energy Model The UK Balancing Market example
Different types of electricity markets modelled using PLEXOS Integrated Energy Model The UK Balancing Market example Peny Panagiotakopoulou, Senior Power Systems Consultant, Energy Exemplar Europe Overview
:שמאת Avram Kelman [[email protected]] Eli Lavy :אל. Role of Administrator :נושא
:שמאת בשם [[email protected]] Carol Crilly Avram Kelman [[email protected]] 2010 18:53 מאי 04 שלישי יום :נשלח :אל :נושא Eli Lavy Role of Administrator Dear Eli I set out below a note replying to
New Brunswick Electricity Business Rules
New Brunswick Electricity Business Rules Table of Contents Chapter 1 Chapter 2 Chapter 3 Chapter 4 Administration and Participation Transmission Planning and Connections Reliable Operations Billing and
ABB Network Manager in Endesa s Energy Management Center
D. G. GESTIÓN DE LA ENERGÍA D. Energía y Logística S. D. Mercados de Contado y Operación Automatic Generation Control (AGC) in Endesa 09 10 13 ABB Network Manager in Endesa s Energy Management Center Contents
MIROMAR TITLE COMPANY, LLC. Best Practices Manual
MIROMAR TITLE COMPANY, LLC Best Practices Manual January 1, 2016 Table of Contents Company Organization Introduction of Best Practices Pillar One Licensing Pillar Two Escrow Account Controls Pillar Three
A new electricity market for Northern Ireland and Ireland from 2016 - Integrated Single Electricity Market (I-SEM)
A new electricity market for Northern Ireland and Ireland from 2016 - Integrated Single Electricity Market (I-SEM) Non-technical summary High level design Draft Decision Paper SEM -14-047 June 2014 1 INTRODUCTION
Renewable Energy Growth Drivers Ireland Embedding Small Scale Renewables and Windpower in Ireland by way of early Smart Grid Clusters
Renewable Energy Growth Drivers Ireland Embedding Small Scale Renewables and Windpower in Ireland by way of early Smart Grid Clusters Presented By Dudley Stewart C. Eng. Micro Electricity Generation Association
Approved Partner Programme. Professional, Practical, Proven. www.accountingtechniciansireland.ie
Approved Partner Programme Professional, Practical, Proven www.accountingtechniciansireland.ie Professional, Practical, Proven Approved Partner Programme Accounting Technicians Ireland Approved Partner
Oncor s Pioneering Transmission Dynamic Line Rating (DLR) Demonstration Lays Foundation for Follow-On Deployments
Oncor s Pioneering Transmission Dynamic Line Rating (DLR) Demonstration Lays Foundation for Follow-On Deployments 1. Summary Oncor Electric Delivery Company (Oncor) successfully demonstrated a fully integrated
TERMS AND CONDITIONS
Virginia Electric and Power Company TERMS AND CONDITIONS XXIV. GENERATOR INTERCONNECTION STANDARD Electric generator interconnection service includes only the ability to interconnect an electric generator
AN GARDA SIOCHANA POLICY ON MONITORED INTRUDER ALARMS
AN GARDA SIOCHANA POLICY ON MONITORED INTRUDER ALARMS 1 AN GARDA SIOCHANA POLICY ON MONITORED INTRUDER ALARMS... 3 1. Introduction... 3 2. Policy Operation... 5 2.1 Withdrawal of Garda Response... 5 2.2
Transmission Planning in the ERCOT Interconnection
Transmission Planning in the ERCOT Interconnection Warren Lasher Manager, Long-Term Planning and Policy Department of Energy Electricity Advisory Committee The ERCOT Interconnection The ERCOT Region is
Proposal Concerning Modifications to LIPA s Tariff for Electric Service
Proposal Concerning Modifications to LIPA s Tariff for Electric Service Requested Action: Staff proposes to modify LIPA s Tariff for Electric Service ( Tariff ) with regard to small generator interconnection
Pass Through Costs for Business Electricity Customers from 1 st October 2015
Pass Through Costs for Business Electricity Customers from 1 st October 2015 DOCUMENT TYPE: Information Note REFERENCE: CER 15/226 DATE PUBLISHED: 22 nd September 2015 The Commission for Energy Regulation,
FEDERATION EUROPEENNE DE LA MANUTENTION Product Group. industrial trucks. A brief guide for identification of noncompliant. - Exhaust Emission -
FEDERATION EUROPEENNE DE LA MANUTENTION Product Group Industrial Trucks FEM A brief guide for identification of noncompliant industrial trucks 11.2010 (E) - Exhaust Emission - I n d e x 1 Introduction...
Renewable Energy Interconnection Requirements for the US. IEEE PES Meeting Denver, CO July 26-30, 2015 J. Charles Smith, Executive Director, UVIG
1 Renewable Energy Interconnection Requirements for the US IEEE PES Meeting Denver, CO July 26-30, 2015 J. Charles Smith, Executive Director, UVIG 2 Outline of Topics Background and Introduction NERC Integrating
Revenue Metering Requirements Manual
NEW YORK INDEPENDENT SYSTEM OPERATOR MANUAL 25 Revenue Metering Requirements Manual August 2013 Version: 1.0 Effective Date: 09/04/2013 Committee Acceptance: July 27, 2005 This document was prepared by:
INTRODUCTION OF PHASE 2 OF AN GARDA SÍOCHÁNA POLICY ON MONITORED INTRUDER ALARMS.
INTRODUCTION OF PHASE 2 OF AN GARDA SÍOCHÁNA POLICY ON MONITORED INTRUDER ALARMS. The Garda Siochana Intruder Alarm Policy is aimed at keeping to a minimum the number of false alarm calls passed to An
Generation and Transmission Interconnection Process
PJM Manual 14A Generation and Transmission Interconnection Process Revision: 18 Effective Date: January 28, 2016 Prepared by Planning Division Generation Interconnection Department PJM 2016 Table of Contents
Customer Charter. Networks. Networks. www.esb.ie
www.esb.ie Dear Customer ESB has always been committed to putting the needs of our customers first. This is reflected in our 12 Service Guarantees that were first introduced in our Customer Charter some
GLOSSARY. Glossary of Terms for Capacity Based Demand Response PUBLIC. Issue 3.0 GOT-1
PUBLIC GOT-1 GLOSSARY Glossary of Terms for Capacity Based Demand Response Issue 3.0 This document provides a glossary of terms with definitions used in the Capacity Based Demand Response program. Public
ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe
NETWORKS ESB Networks Response to ERGEG Consultation on Voltage Quality Regulation in Europe Date: 22 February 2007 Distribution System Operator ESB Networks Page 1 of 12 Contents 1.0 INTRODUCTION...3
Digital Metering: a key enabling factor to foster RES development
RES4MED Days, Rabat September 16th, 2014 Digital Metering: a key enabling factor to foster RES development Simone Aibino Area Manager Europe, Mediterranean Countries & USA CESI SpA Consulting Division
Analysis of requirements in selected Grid Codes. Willi Christiansen & David T. Johnsen
Analysis of requirements in selected Grid Codes This page was intentionally left blank 1 Preface This report has been submitted to Ørsted DTU, Section of Electric power Engineering, Technical University
Demand Response FAQs
1 Under the current CAISO tariff, assuming it would otherwise meet the requirements under the CAISO tariff and business practice manuals to do so, can the Load associated with a retail meter participate
DELHI ELECTRICITY REGULATORY COMMISSION
DELHI ELECTRICITY REGULATORY COMMISSION DELHI ELECTRICITY REGULATORY COMMISSION (RENEWABLE PURCHASE OBLIGATION AND RENEWABLE ENERGY CERTIFICATE FRAMEWORK IMPLEMENTATION) REGULATIONS, 2011 No. Dated:. NOTIFICATION
PROCEDURE. Part 3.1: Metering Service Provider (MSP) Registration, Revocation, and Deregistration PUBLIC. Market Manual 3: Metering. Issue 14.
PUBLIC MDP_PRO_0007 PROCEDURE Market Manual 3: Metering Part 3.1: Metering Service Provider (MSP) Registration, Revocation, and Deregistration Issue 14.0 This document provides an overview of the steps
CURTAILABLE RATE PROGRAM FOR INDIVIDUAL CUSTOMER LOADS
Page 1 of 16 CURTAILABLE RATE PROGRAM FOR INDIVIDUAL CUSTOMER LOADS PROPOSED TERMS AND CONDITIONS January 2015 Page 2 of 16 TABLE OF CONTENTS 1. Definitions... 3 2. Curtailable Load Options... 6 3. Nomination
Single Electricity Market (SEM) and interaction with EMIR. Central Bank of Ireland
Single Electricity Market (SEM) and interaction with EMIR Central Bank of Ireland 11 th July 2014 About EAI Overview of SEM and its Participants The market is a gross mandatory pool and consists of generators
CONCEPT STUDY ON FAST CHARGING STATION DESIGN
EDISON Deliverable D4.4.1, D4.4.2, D4.5.1, D4.5.2, ELECTRIC VEHICLES IN A DISTRIBUTED AND INTEGRATED MARKET USING SUSTAINABLE ENERGY AND OPEN NETWORKS CONCEPT STUDY ON FAST CHARGING STATION DESIGN Type:
D 6.4 and D7.4 Draft topics of EEGI Implementation Plan 2016-2018 Revision: Definitive
Project no.: 282794 Project acronym GRID+ Project title: Supporting the Development of the European Electricity Grids Initiative (EEGI) Instrument: Coordination and support action Thematic priority: ENERGY.2011.7.3-1:
RIG Acceptance Test (RAT) Procedures
RIG Acceptance Test (RAT) Procedures RIG Acceptance Test (RAT) Procedure 0 Print Date 2 /20/2007 REVISION HISTORY REVISON NO. DATE DESCRIPTION 1.0 Initial Release 0 Update Logo and Links i RIG Acceptance
Key Concepts Of Distributed Generation
Key Concepts Of Distributed Generation National Grid - April 29, 2015 International Association of Electrical Inspectors Western Massachusetts Chapter - Springfield MA Bob Moran, Jim Kehrer, Patti Cox,
SCADA Systems Automate Electrical Distribution
SCADA Systems Automate Electrical Distribution PC-based supervisory control and data acquisition systems increase uptime, cut costs and improve utilization. A White Paper from InduSoft Fabio Terezinho
Phase Attribute Identification using GPS Technology
Phase Attribute Identification using GPS Technology Date 11 June 2009 John Sinclair Power Quality Manager Slide 1 Topics of Discussion Remote Phase Identification How it works Principals of operation Benefits
-1- PSEG-LI Update of LIPA SGIP Full Docw-NYISO reqmts above 10 MW 10-27-14
PSEG-Long Island Smart Grid Small Generator Interconnection Procedures for New Distributed Resources 20 MW or Less Connected in Parallel with LIPA s Radial Distribution Systems -1- PSEG-LI Update of LIPA
Multi-Faceted Solution for Managing Flexibility with High Penetration of Renewable Resources
Multi-Faceted Solution for Managing Flexibility with High Penetration of Renewable Resources FERC Technical Conference Increasing RT & DA Market Efficiency Through Improved Software June 24 26, 2013 Nivad
Operating the power system while enabling more renewables : which solutions?
Operating the power system while enabling more renewables : which solutions? Sébastien GRENARD EDF R&D 22/06/2010 New environment for power systems design and operation European targets and attractive
IRAS e-tax Guide. Deduction for Statutory and Regulatory Expenses
IRAS e-tax Guide Deduction for Statutory and Regulatory Expenses Published by Inland Revenue Authority of Singapore Published on 12 Sep 2014 Disclaimers: IRAS shall not be responsible or held accountable
Guidelines for Large Photovoltaic System Integration
1 Guidelines for Large Photovoltaic System Integration Silviu Darie, PhD(EE), PE(EE) Abstract- The paper summarizes the result of a research project funded by the Department of Energy (DOE) in collaboration
Operational Security Network Code
Amstelveenseweg 998 1081 JS Amsterdam Phone: + 31 20 520 7970 Fax: + 31 346 283 258 Email: [email protected] Website: www.efet.org Operational Security Network Code Public consultation 3 November 2012
DRAFT KERALA STATE ELECTRICITY REGULATORY COMMISSION, NOTICE. No. 442/CT/2014/KSERC Dated, Thiruvananthapuram 31 st March, 2015
DRAFT 31.3.2015 KERALA STATE ELECTRICITY REGULATORY COMMISSION, NOTICE 442/CT/2014/KSERC Dated, Thiruvananthapuram 31 st March, 2015 The Kerala State Electricity Regulatory Commission hereby publishes
INTELLIGENT DISTRIBUTION NETWORK ANALYSIS AND INFORMATION ARCHITECTURE DESIGN
INTELLIGENT DISTRIBUTION NETWORK ANALYSIS AND INFORMATION ARCHITECTURE DESIGN Yun CHEN SMEPC,State Grid China [email protected] ABSTRACT From the background of intelligent distribution network construction,
COMMENTS OF THE SOLAR ALLIANCE NEW JERSEY INTERCONNECTION RULES APRIL 29 TH, 2011
COMMENTS OF THE SOLAR ALLIANCE NEW JERSEY INTERCONNECTION RULES APRIL 29 TH, 2011 I. Background The Solar Alliance is a group of approximately 30 of the largest photovoltaic (PV) solar development and
G8 - Contracts for Difference Metering
PUBLIC G8 - Contracts for Difference Metering EMRS Guidance EMR Settlement Limited Version 1.0 12 October 2015 CONTENTS Change Amendment Record...4 1. Introduction...5 2. Purpose...5 3. What is the Electrical
How To Measure An Rsp
Rule 003 (Formerly EUB Directive 003) Regulated Service Provider (RSP) Service Standard and Reliability Performance, Monitoring, and Reporting Rules The Alberta Utilities Commission (AUC/Commission) has
OPERATING PROCEDURE IT CHANGE MANAGEMENT PROCEDURES MANUAL. PREPARED BY: AEMO DOCUMENT NO: Enter Document ID VERSION NO: 6.
OPERATING PROCEDURE IT CHANGE MANAGEMENT PROCEDURES MANUAL PREPARED BY: AEMO DOCUMENT NO: Enter Document ID VERSION NO: 6.6 STATUS FINAL Approvals The undersigned have approved the release of Version 6.6
NOTE - This document is provided for guidance only and does not purport to be a legal interpretation. PERSONAL INSOLVENCY ACT 2012
Background to and purpose of the Act PERSONAL INSOLVENCY ACT 2012 EXPLANATORY MEMORANDUM The Act provides for the reform of personal insolvency law and will introduce the following new non-judicial debt
FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003
F R C C FRCC Standards Handbook FRCC Automatic Underfrequency Load Shedding Program Revision Date: July 2003 FRCC Underfrequency Load Shedding Program Modification and Approval Process Requests to modify
Future grid infrastructure Field tests of LVDC distribution
Future grid infrastructure Field tests of LVDC distribution LUT LVDC Research Group: Andrey Lana, Pasi Nuutinen, Antti Pinomaa, Tero Kaipia, Pasi Peltoniemi, Aleksi Mattsson, Jarmo Partanen Introduction
Communicate: Data Service Level Agreement. Author: Service Date: October 13. Communicate: Data Service Level Agreementv1.
Communicate: Data Service Level Agreement Author: Service Date: October 13 Communicate: Data Service Level Agreementv1.1 Page 1 of 12 Contents 1. Scope 3 2. Service Definitions 3 3. Service Provision 3
Electricity in Egypt
T: (+20) 2 3760 4592 F: (+20) 2 3760 4593 A: 16 Hussein Wassef Street, Messaha Square Dokki, Giza, Egypt 12311 www.ide.com.eg Electricity in Egypt Policy and Regulatory Reform November 2015 Electricity
Monitoring the Operation of Wind Turbines Alex Robertson, Vestas Northern Europe
Monitoring the Operation of Wind Turbines Alex Robertson, Vestas Northern Europe Renewable Efficient Energy II Conference, 21.03.2012, Vaasa, Finland Modern wind power plant produce more data than ever
Table of Contents. Real-Time Reliability Must Run Unit Commitment and Dispatch (Formerly G-203) Operating Procedure
No. 2310 Table of Contents Purpose... 2 1. Responsibilities... 2 2. Scope/Applicability... 2 2.1 Background... 2 2.2 Scope / Applicability... 2 3. Detail... 3 3.1 Energy Dispatching... 3 3.1.2 Real-Time
METERING CODE. Energy Market Authority of Singapore
METERING CODE Energy Market Authority of Singapore TABLE OF CONTENTS 1 GENERAL AND ADMINISTRATIVE PROVISIONS...1 1.1 Purpose of this Code...1 1.2 To Whom this Code Applies...1 1.3 Prohibition...1 1.4 Definitions...1
946 CMR: MASSACHUSETTS DEVELOPMENT FINANCE AGENCY 946 CMR 7.00: DEVENS REGIONAL ENTERPRISE ZONE FIRE AND POLICE RULES
946 CMR 7.00: DEVENS REGIONAL ENTERPRISE ZONE FIRE AND POLICE RULES Section 7.01: Scope and Purpose 7.02: Definitions - Fire and Police Alarms 7.03: Duties of Fire Chief 7.04: Smoke Detectors in Certain
The Legal Helpdesk. Rules on grid access and priority dispatch for renewable energy in Europe
The Legal Helpdesk Rules on grid access and priority dispatch for renewable energy in Europe Dr. Dörte Fouquet, Rechtsanwältin, Partner, BBH Jana Viktoria Nysten, LL.M., Advocaat, Attorney at law, BBH
Single Electricity Market. Acquisition of NIE plc, NIE Powerteam and allied businesses by ESBNI Ltd
Single Electricity Market Acquisition of NIE plc, NIE Powerteam and allied businesses by ESBNI Ltd Decision Paper & Consultation on Licence Modifications 19 January 2011 SEM-12-003 Introduction 1. In July
Market Manual Changes for Settlement of Capacity Based DR. Demand Response Working Group August 6, 2014
Market Manual Changes for Settlement of Capacity Based DR Demand Response Working Group August 6, 2014 Agenda Overview Market Manuals for DR Settlement Settlement Data Requirements M&V Baseline Methodology
EWE's approach to double grid connection capacity by using DERflexibility
EWE's approach to double grid connection capacity by using DERflexibility Marcus Merkel, EWE NETZ GmbH Co-operation workshop of Energy 2013.7.1 projects Aachen, 19 March 2015 EWE approach is in line with
Big Data in Smart Grid. Guangyi Liu China Electric Power Research Institute
Big Data in Smart Grid Guangyi Liu China Electric Power Research Institute 1 Outline 一 二 Sources and Feature of Big Data in Smart Grid Use Scenarios of Big Data in Smart Grid 2 Sources of Big Data in Smart