Risk Engineering Guideline
|
|
|
- Earl Allen
- 10 years ago
- Views:
Transcription
1 HDI-Gerling Risk Engineering Services Risk Engineering Guideline Fire protection in electrical equipment rooms Statistically 30 percent of all fires are caused by defects in electrical systems, devices or equipment. international
2 Adequate protection concepts within electrical rooms can reduce both the probability and severity of potential losses. Defects on electrical systems, electrical devices and equipment are still a major cause of fire. The insulation around cables and electrical equipment represents potentially a high fire load. 1 General According to common insurance industry statistics, approximately 30 % of all fires are caused by defects on electrical systems, devices or equipment. The main ignition source in this regard is defective, incorrectly installed or insufficiently dimensioned equipment, which results in a thermal overload due to the electric current. In the event of a fire, the fire might spread via cable trays. Toxic and corrosive gases are generated during these electrical fire events. As a result, authorities often define restrictions with regard to reinstallations. Delays are unavoidable due to the need for decontamination and repair. However, as no company can operate without electrical energy, electrical and electronic systems and equipment must fulfil the highest requirements in terms of availability, to reduce a larger business interruption at this risk. Fire protection in electrical equipment rooms is therefore of particular importance. The measures prescribed in national standards (for instance DIN VDE) or international standards alone are normally not sufficient to cover and safely maintain fire protection for electrical equipment and service rooms. 2 Loss examples 2.1 Chemical plant At a chemical plant where thermoplastic polymers are produced, a short circuit and an arc occurred in the lowvoltage switchgear, which ignited the insulation of the cables. Despite immediate fire fighting, two control cabinets were completely destroyed and adjoining distributors were damaged. Strong smoke caused damage to the
3 Risk Engineering Guideline: Fire protection in electrical equipment rooms 3 entire low-voltage switchgear and adjoining rooms. Due to the power failure, almost all areas of the plant experienced extended malfunctions and failures. Even when the shutdown of the polymerisation units was initiated immediately after the incident occurred, it was not possible to empty and rinse large parts of the production facilities. These areas required an extensive and time-consuming cleaning as the product in the units had solified. Consequence: The production was interrupted for several months. 2.2 Waste incineration plant A short circuit with subsequent arc caused a fire in a control cabinet of the 20 KV hazardous waste incineration plant. Starting from the control cabinet, the fire was able to spread to other control cabinets in the plant. The smoke detectors arranged in the high-voltage distributor board triggered an alarm. However, several fire brigades and huge quantities of CO₂ had to be employed to extinguish the fire. The fire caused a power failure on the entire premises. Even though the emergency diesel generator at the plant started correctly, it shut down very shortly afterwards, probably due to a short circuit in the switchgear because of the fire. The entire 20 KV plant was destroyed. The low voltage system and the compensation systems could be cleaned. The uncontrolled shutdown of the plant caused additional damage to the incineration plant. As it is frequently the case: The business interruption loss was significantly higher than that of the property damage. 2.3 Power plant An explosion that occurred in a temporary installed transformer located in the cable basement of a block-unit power station, lead to a fire with far-reaching consequences. Burning transformer oil dispersed over large areas and ignited the cables. The fire was able to spread to all areas of the switchgear building via non partitioned breaks, channels and ducts. The air conditioning system, which was only equipped with thermally triggering flap controls in the ducts, contributed significantly to the spreading of the smoke. The fire alarm system notified the plant fire brigade, but even with a short response time they could not prevent the need for the central control room to be evacuated due to dense smoke. The automatic protection functions caused the shut-down of both block-unit power stations and the external electricity supply. The entire loss (property damage, damage business interruption due to interruption in operation and damage to electronic systems) amounted to approximately 45 million. These examples of losses clearly show the far-reaching consequences that a fire in an electrical equipment room might have. Even minor damage of electrical and electronic systems may have disastrous consequences for a company. 3 Terms Electrical equipment rooms according to this risk engineering guideline comprise: High voltage systems (e. g. according to IEC ) Low voltage systems (e. g. according to IEC 60364) Any rooms that are exclusively or mainly used for operating electrical systems 4 Hazard sources/loss causes As the evaluation of loss incidents has shown, the following loss causes are the main causes of fires in electrical equipment rooms: Generation of arcing faults. Causes for this may include: Contact faults at the screw-type or clamp connections of contactors, switches and other components (e. g. due to material fatigue, metal flow at pressure points, faulty or soiled clamp connections) Creeping current due to humidity, dust, oil and coalification (creeping distances, arcing spots) Mechanical damage due to shocks, vibration stress and rodent attack Insulation faults due to ageing (brittleness), introduction of foreign matter, weather and other external influences
4 4 Risk Engineering Guideline: Fire protection in electrical equipment rooms Heat build-up due to insufficient discharge of heat, too densely arranged connections in control cabinets or of cable trays or dirt deposits on electrical equipment. Fire risk due to impermissibly high ambient temperatures Improper installation of cables and lines, e. g. by impermissibly small bending radii Impermissibly high forces at clamps or strain relief (deformation) Insufficient safety distances 5 Protective measures 5.1 Structural fire protection measures The following principles are applicable: High and low voltage switchgear must be installed in separate rooms with separate fire protection. The same applies to distribution systems, transfer stations of the public power supply, as well as process control rooms. The walls and the ceiling of the rooms should be built according to fire resistance class REI 90. (ASTM 3-houres). Only non-combustible materials shall be used as building materials. Access doors should at least comply with fire resistance class EI₂30-CS (T30-RS). Wall and ceiling penetrations for cable trays must be fire sealed by approved material. The fire seal must have the same fire resistance rating as the corresponding walls or ceilings. The same applies to ventilation ducts that must be closed with approved fire dampers. Triggering of the fire dampers must be controlled by smoke detectors. Where separate electrical service rooms share one air conditioning/ventilation system, it must be ensured by the activation of the fire dampers and the automatic disconnection that smoke remove gases cannot spread via the ventilation ducts (prevention of "cold smoke"). However, separate ventilation systems would be required for an actual redundancy. High-voltage switchgear must be provided with an outward pressure relief for deflecting the shock wave in the event of an arcing fault. The routing of third-party systems, such as pipelines, conveyor systems and the like through electrical equipment rooms should be avoided. 5.2 Plant technology Arcing fault protection Arcing faults may occur in low and high voltage switchgear and may endanger both people and property. They may be caused by overvoltage, insulation or handling faults, e. g. by bypassing electrical conductors, overloads due to defective plant components, failure to observe safety rules etc. In the event of a fault, an arc burns between the faulty phases or at grounded plant components of the switchgear. Within 20 ms (a 50 Hz AC cycle), temperatures of up to several 10,000 C and pressures of up to several bars are generated. The pressure and the heat, which causes the evaporation of metal parts, among others, may result in personal injury and also destroy the entire switchgear or the entire service room. This results in immediate business interruption, normally for an extended period. From a structural point of view, attempts can be made to protect the plant by separating adjoining sections and subdividing the sections. Here, major losses and extended downtimes are accepted. The divisions in between the individual switchgear sections are not always effective particularly during assembly and maintenance work, as doors and shutters are open. Switchgear for distributing electrical energy should therefore additionally be equipped with active protective systems. Neither normal fire alarms nor conventional protective relays can detect an arc quickly enough and switch off the respective plant component. Detection and disconnection via an earthing relay is not reliable either as the neutral connector/ground wire does not necessarily have to be affected by the arcing fault. Besides, arcing faults are resistive incidents. The current in this regard is not necessarily higher than the rated tripping current of the protective device, and will not result in tripping or extended switch-off times of the protective devices.
5 Risk Engineering Guideline: Fire protection in electrical equipment rooms 5 Arcing fault protection systems detect the arc, extinguish the arc within a few milliseconds, and disconnect the defective plant from the mains. If an arcing fault occurs, a metallic short circuit is generated in parallel to the fault location, and the arc is extinguished before the shock wave and the temperature have reached their maximums. The resulting short circuit current causes the respective power switch to disconnect the fault location from the mains power supply. Arcing fault detection systems comprise light and current sensors and electronic evaluation units. The light sensors, fibre optic cables or point sensors allow monitoring of the entire lengths of contact rails and connections systems. The arc current is measured with current transformers installed upstream of each mains power switch Plant fire protection Fire alarm system Electrical equipment rooms should be monitored by a fire alarm system with smoke detectors and alarm transmission to a permanently staffed office. Important criteria for the selection of a suitable fire alarm system include: Monitoring scope: Room monitoring (incl. raised floors and suspended ceilings) Installation monitoring (e. g. in control cabinets) required to ensure early detection Monitoring of the fresh air supply (to ensure that, in the event of a fire close by, smoke will not enter this sensitive area) What ambient conditions (e. g. ventilation system in the monitoring area) must be considered? What measures must be initiated in the event of an alarm (e. g. alarming of the fire brigade, de-energising of the affected plant components, closing of air conditioning flaps)? How secure is the system in the event of false alarms? The following detectors could be used: Point-type detectors To safeguard against false alarms, these detectors should be installed in groups of two or in two-detector dependence. Smoke aspiration system In these systems, air samples are taken continuously via a pipe system from the area to be monitored. Extraction can be done directly at the location where a fire is likely to start. These detectors feature very reliable and extremely sensitive response characteristics and are capable of detecting pyrolysis products that are generated before an actual fire breaks out. Nevertheless, their sensitivity to false alarms is still very low. Furthermore, different alarm thresholds can be defined for these systems. Fire alarm systems should by designed according to internationally recognised rules and standards (e. g. NFPA 72 National fire alarm and signaling code). Only approved systems should be used.
6 6 Risk Engineering Guideline: Fire protection in electrical equipment rooms Fire extinguishing systems Depending on the availability requirements of individual electrical equipment rooms, an automatic extinguishing system might be required in addition to the monitoring. Generally, gas extinguishing systems are preferable even though water extinguishing systems also provide adequate protection (with minor restrictions). The extinguishing system should be designed according to internationally recognised rules and standards (e. g. NFPA 12 Standard on carbone dioxide extinguishing systems). Only approved systems should be used. 5.3 Organisational fire protection measures A general smoking ban must be implemented in electrical equipment rooms and must clearly be marked by the corresponding signs. Electrical equipment rooms may not be misused for other purposes, e. g. as storage rooms, and must be kept free from any fire loads, such as e. g. transport pallets, packaging material, cables, spare parts or office supplies. Electrical equipment rooms may not be misused for different purposes, e. g. as electrical workshop or by other workplaces. Documentation, manuals and circuit diagrams should not be kept close to electrical equipment. They must be stored in separate steel plate cabinets. In view of the associated ignition hazard, the installation of private electrical appliances (e. g. coffee machines, radios, refrigerators) should be strictly prohibited. Fire and hot work must be avoided in principle. Where these are absolutely required, provision must be made for a written permit procedure that must include a form on that the necessary protective measures are defined as well as documentation of the corresponding checks during and after completion of the work. (see Risk Engineering Guideline Hot work ) These rooms must be inspected at regular intervals, e. g. in terms of housekeeping, closure of cable bulkheads etc. No unauthorised people may be allowed entry to the electrical equipment rooms, which must be prevented by suitable measures (locking of these areas). 6 Checks 6.1 Initial acceptance Also in view of the validity of warranty claims, new systems should be checked and accepted by an independent expert A thermographic inspection of the system should always form part of the acceptance (refer to 6.3). It should be done after an operating time of approx. 4 to 6 weeks (real operation). 6.2 Repeated inspection In accordance with regulations, the proper state of an electrical system must be maintained. Regular inspections of the entire system are indispensable in this regard. Normally, such inspection is prescribed by the insurance contract and must be performed routinely by an approved expert, because the latter is always neutral and independent during the inspection, is familiar with the latest standards and the special concerns of fire protection as defined in electrical system guidelines, offers advice to the clients in accordance with the requirements of the property insurance if changes, repair and new constructions are necessary, is familiar with particularities of the inspection of electrical systems in terms of material asset protection, as normal inspections (e. g. the inspection according to the accident prevention regulations of the professional associations) are normally aimed at the protection of people, and is supervised by an independent third party Fire extinguishers A sufficient number of CO₂ fire extinguishers must be installed easily visible and accessible at a central location for use by the staff for fighting incipient fires. Dry powder extinguishers are principally suitable for controlling a fire in electrical systems. However, they cause considerable secondary damage due to the released very fine and highly corrosive dry powder. CO₂ allows for extinguishing fires in electrical and electronic systems without residues. The staff should be trained in the operation of hand-held fire extinguishers to ensure that these are used quickly and effectively in an emergency.
7 Risk Engineering Guideline: Fire protection in electrical equipment rooms 7 The certification of the inspection should be stored at a safe place so that they are available if they have to be submitted to authorities or the insurance company. 6.3 Thermography The use of a thermographic camera (infrared camera) allows for inspecting electrical systems, such as distributors, control cabinets, etc. for any abnormal heating when these are energised, i. e. during the production and under nominal load conditions. Such overheating may be caused by incorrectly performed work, ageing components, loose clamps (increased transition resistances) or networks that have grown over time (incomplete circuit diagrams) and the associated gradual overload. Impermissibly high temperatures may represent a direct ignition source, or the permanent temperature overload may damage the electrical insulation and thus result in a conductor-to-conductor or short circuit (with arc). To ensure qualified inspection and assessment of the plant components, this should be done by an approved thermographer. 7 References Local standards should be complied with. Internationally recognised standards: NFPA 70 NFPA 70 B NFPA 72 NFPA 12 NFPA 2001 NATIONAL ELECTRICAL CODE Recommended practice for electrical equipment maintenance National fire alarm and signaling code Standard on carbon dioxide extinguishing systems Standard on clean agent fire extinguishing systems IEC Low voltage electrical installations IEC Power installations exceeding 1 kv a. c. IEE Wiring regulations Inspection and testing, guidance note 3
8 8 Risk Engineering Guideline: Fire protection in electrical equipment rooms About HDI Risk Consulting GmbH HDI Risk Consulting GmbH supports mid-size companies, industrial companies and corporations in loss prevention and in establishing risk management systems. HDI Risk Consulting GmbH offers customers access to about 180 engineers and experts from a wide range of different disciplines. The goal is to support companies in managing risks and working out individual, risk-based concepts for insurance cover. HDI Risk Consulting GmbH operates across the world in the segments of Fire, Motor, Engineering Insurance and Marine with particular focus on the identification and assessment of risks and the development of appropriate, individual protection concepts. HDI Risk Consulting GmbH is a wholly owned subsidiary of HDI-Gerling Industrie Versicherung AG. 403-HGST/SIFI131GB 3.14(III N) HDI Risk Consulting GmbH HDI-Platz 1 - D Hannover Phone: Fax: Internet: Imprint In charge of the content: Marcus Fellmann HDI Risk Consulting GmbH Layout: RELAY CORPORATE PUBLISHING GmbH. Printer: Lindendruck Verlagsgesellschaft mbh Pictures: istockphoto.com, mauritius images: image broker/anton luhr, united archives, wolfgang weinhäupl, matthias tunger, stock4b, panthermedia.net, fotolia.de Although we made every effort possible to ensure the accuracy of the information provided, no liability can be assumed for the currentness, correctness and completeness of the information. We neither intend, nor assume any obligation, to update or revise these statements in light of developments which differ from those anticipated.
Risk Engineering Guideline
www.hdi.global HDI Risk Consulting Risk Engineering Guideline Impairment of fire protection systems Basic protection systems should not be impaired without adequate replace compensation with provisions.
FIRE SAFETY FOR OFFICE WORKERS
FIRE SAFETY FOR OFFICE WORKERS This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program and the subject
employed to ensure the continuing reliability of critical systems.
4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Installation and safety instructions for AC/DC built-in devices
The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
Fire Protection Notice No. 9 ELECTRICAL SAFETY
Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily
CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2
IT Power Solutions CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2 Thomas B. Jones 1 Introduction Operators and managers consider outages, operational
BRANCH SOLUTION. Automatic fire extinguishing systems for paint spraying plants. Safe for certain.
BRANCH SOLUTION Automatic fire extinguishing systems for paint spraying plants Safe for certain. ISK IDENTIFYING With the extreme high degree of automation in painting technology, the risk of fire has
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Instruction manual. Electrobloc EBL 100-2
Instruction manual 0 Manual Electrobloc EBL 100-2 Electrobloc EBL 100-2 Type no. 911.503 Table of contents 1 Introduction..........................................2 2 Safety information.....................................2
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
Insulation resistance
The insulation resistance is particularly important for the prevention of damage and injury, and for the reliability of electrical systems and equipment. On the one hand it is basis for the protection
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
This Guidance Notes is prepared by the Occupational Safety and Health Branch, Labour Department. This edition July 2004
This Guidance Notes is prepared by the Occupational Safety and Health Branch, Labour Department This edition July 2004 This Guidance Notes is issued free of charge and can be obtained from offices of the
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
ADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Enhance Power Equipment Reliability with Predictive Maintenance Technologies
Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of
Firewall. Propane flame projector Safety instructions and operating manual
Firewall Propane flame projector Safety instructions and operating manual TBF-PyroTec GmbH Lichterfelder Str. 5A 21502 Geesthacht Tel.: +49(0)4152 157 9950 [email protected] www.tbf-pyrotec.de 1 Flame
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
COMMON EQUIPMENT FAILURES AND CAUSES. How breakdowns can impact the bottom line. A handy reference guide from Hartford Steam Boiler.
COMMON EQUIPMENT FAILURES AND CAUSES How breakdowns can impact the bottom line. A handy reference guide from Hartford Steam Boiler. A WORLD THAT DEPENDS ON EQUIPMENT. Businesses, institutions and municipalities
WHAT IS INFRARED (IR) THERMOGRAPHY
WHAT IS INFRARED (IR) THERMOGRAPHY IR Thermography is the technique of producing pictures called from the invisible thermal radiation that objects emit. This is a non-contact means of identifying electrical
5162 E. Working in oxygen-reduced atmospheres BGI/GUV-I 5162 E. Information
5162 E BGI/GUV-I 5162 E Information Working in oxygen-reduced atmospheres November 2013 Imprint About us Publisher: German Social Accident Insurance (DGUV) Mittelstraße 51 10117 Berlin Tel.: 030 288763800
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
Application Form for Self Storage Insurance
Note: The information contained in this report is provided by the broker for preliminary risk assessment only. A full survey, if required, will need to be carried out by the insurer. Client Details Full
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
WIND TURBINE DAMAGE PREVENTION 2014
WIND TURBINE DAMAGE PREVENTION 2014 1 WIND TURBINE DAMAGE PREVENTION 2014 Contents 1 PURPOSE... 2 2 GENERAL... 2 2.1 Technical implementation and type approval... 2 2.2 Transportation... 3 2.3 Installation...
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
Structured Cabling, Earthing & Equipotential Bonding
White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: [email protected]
Infrarot-Bewegungsmelder IP44
Infrarot-Bewegungsmelder IP44 infrared motion sensors IP44 ODA (weiß) slim ODA (schwarz) slim 95174 96000 ODA (weiß) ODA (schwarz) 95175 96001 Betriebsanleitung User s Manual User s Manual infrared motion
Decree of the Ministry of the Environment on fire safety of ventilation systems
THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18
Understanding Emergency Power Off (EPO)
Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single
How To Certify A Security Area Datacenter For A Trustworthy Site Infrastructure
The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company E.ON IT GmbH Treskowstraße 5 30457 Hannover, Germany to confirm that its security area Datacenter T7
MARULENG LOCAL MUNICIPALITY
MARULENG LOCAL MUNICIPALITY Data Centre Physical Access and Environmental Control Policy Draft: Data Centre Access Control and Environmental Policy Page 1 Version Control Version Date Author(s) Details
Decree of the Ministry of the Environment. on fire safety of garages
E4 THE NATIONAL BUILDING CODE OF FINLAND Fire safety of garages Guidelines 2005 Decree of the Ministry of the Environment on fire safety of garages Adopted in Helsinki, 22 March 2005 Pursuant to the Decision
Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
ELECTRICAL SAFETY. The standard unit for measuring electrical current.
ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety
fulfils all requirements for extended protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages.
The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company Infineon Technologies IT-Services GmbH Lakeside B05 2 9020 Klagenfurt, Österreich to confirm that its
Electrical Classification
Electrical Classification Using NFPA 70 and NFPA 499 to Classify Hazardous Locations Electrical classifications are established in accordance with the National Electrical Code, NFPA 70, also referred to
Natural Gas Safety. What You Need to Know
Natural Gas Safety What You Need to Know Knowledge is Safety Approximately 52% of all U.S. households use natural gas for Home heating Cooking Water heaters Gas logs Outdoor gas grills Our Local History
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
WASTE Application Form - Dublin Waste to Energy SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE
SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE Describe the existing or proposed measures, including emergency procedures, to minimise the impact on the environment of an accidental emission or spillage.
Electric Fryers Instruction Manual Models: 8047D, 8048D, 8049D, 8050D, 8051D 8066, 8068, 8068FL, 8073, 8073BF and 8075
Part No. 89047 Electric Fryers Instruction Manual Models: 8047D, 8048D, 8049D, 8050D, 8051D 8066, 8068, 8068FL, 8073, 8073BF and 8075 Cincinnati, OH 45241-4807 USA ELECTRIC FRYER SAFETY PRECAUTIONS Installation
TIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)
SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY
fufils all requirements for high protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages.
The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company LVM Versicherung Kolde-Ring 21 48126 Münster, Germany to confirm that its security location Data Center
Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230
Technologies Gas extinguishing systems MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 ire protection Efficient and compact MX 1230 fire extinguishing systems fight fires using Novec
Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1
Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1 Nuclear Power in Pakistan Nuclear Power Plants Capacity (MWe) Year of Commissioning In
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
Problem / Solution. The problem:
Problem / Solution Solar Photovoltaic (PV) technology has shown significant development in recent years and this has led to many UK homeowners investing in Solar PV installations. Solar electricity is
Autoclave Safety. Autoclaves are sterilizers using high pressure and high temperature steam. The potential safety risks for the operators are:
Autoclave Safety Purpose: Sterilization refers to the complete killing of all living organisms, including spores. Common sterilization techniques include the application of wet heat, dry heat, chemicals,
TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER
Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER PSUM These technical specifications determinate a range of manufactured sizes and models of fire shutters (further only shutters)
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
Evaluating Fire- and Heat-Damaged Electrical Equipment
Evaluating Fire- and Heat-Damaged Electrical Equipment www.nema.org 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to heat
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
fulfils all requirements for very high protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages.
The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company RWE IT GmbH Hyssenallee 22-30 45128 Essen, Germany to confirm that its security area Data Center Neurath
Safe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
FIRE SAFETY ONLINE TRAINING
INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
Arc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
HEALTH AND SAFETY REDUCING ACCIDENTS IN KITCHENS
HEALTH AND SAFETY REDUCING ACCIDENTS IN KITCHENS HEALTH & SAFETY UNIT SPRING 2006 CONTENTS 1. WHAT CAUSES ACCIDENTS?...2 2. WHO GETS INJURED?...2 3. SLIPS...2 4. TRIPS...3 5. SCALDS AND BURNS...3 6. MACHINERY
1 General information
1 General information 1.1 About this manual This manual describes the installation, function and operation of an integrated solar control system, which is suitable for split pressurized solar heating system.
Restaurant & café guide
'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
Factory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie
FIRE SAFETY REGISTER Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie 1 CONTENTS Section Title Page 1.0 Introduction 3 2.0 Guidance for the completion
Bradlee Boilers Ltd. Instruction Manual for starting up Bradlee Hire Boiler from Cold
Bradlee Boilers Ltd Instruction Manual for starting up Bradlee Hire Boiler from Cold To be read in conjunction with Bradlee Boiler guide to Commissioning Boilers Document Ref: HM001 1. Ensure that all
Smoke exhaust systems
1 Fire zone, e.g. hall 2 Smoke exhaust zone, separated by smoke curtains Natural and mechanical smoke extraction General information 3 Natural smoke and heat exhaust vent 4 Air inlet opening or wake max.
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
Workplace Fire Safety
Teaching Guide Workplace Fire Safety for staff Seattle Fire Department Fire Prevention Division Workplace Fire Safety Instructor Outline Introduction Goals: To ensure that employees are knowledgeable in
Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy
Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay
Ammonia Detection System Codes and Design Specifications
Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion
Routine and Emergency Boiler Operation
Routine and Emergency Boiler Operation Learning Outcome When you complete this module you will be able to: Describe the routine safe and efficient operation of a packaged boiler. Learning Objectives Here
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
RRV934. Multi-controller. Synco living
s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard
Distributed Temperature Monitoring of Energy Transmission and Distribution Systems
1 m 40000m0 range 61850 IEC spatial resolution Distributed Temperature Monitoring of Energy Transmission and Distribution Systems Ensuring a Reliable Supply of Electrical Power for Today s World www.en-sure.pro
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems
ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems Content Introduction Preventing unauthorized access by perimeter surveillance Monitoring unauthorized access by indoor surveillance
