The Seasonal Efficiency of Multi-Boiler and Multi-Chiller Installations
|
|
|
- Georgiana Cameron
- 10 years ago
- Views:
Transcription
1 The Seasonal Efficiency of Multi-Boiler and Multi-Chiller Installations Roger Hitchin, Technical Director, BRE Environment BRE, Garston, Watford WD25 9XX, United Kingdom Tel +44 (0) Fax +44 (0) Simon Law, Faber Maunsell Topic The paper relates to two of the conference topics: HVAC and the Directive on Energy Performance in Buildings Keywords Seasonal efficiency, boilers, chillers, energy certification Abstract The Energy Performance Certification requirements of the Energy Performance of Buildings Directive highlight the need to have repeatable, robust but easy to use methods of assessing the annual efficiency of HVAC systems. This is also an important issue for energy-efficient system design in general. System efficiency depends on the efficiency of heat generators (usually boilers) and cold generators (often chillers) - as well as many other heat distribution and control factors. This paper focuses on the calculation of the annual heat (or cold) generator efficiency of multi-boiler (or multichiller) systems. Standardised methods exist for estimating the annual efficiency of boilers (or chillers) in systems with only one heat (or cold) generator: The UK SEDBUK rating for boilers, and the American IPLV rating and the proposed European ESEER value for chillers are examples of such rating systems. These produce product ratings for operation under standardised conditions. However, many larger systems have multiple boilers or chillers, and these product ratings are of limited value in these circumstances. In addition, the standardised assumptions of sizing and climate may not apply in every situation. Detailed energy simulations provide one means of estimating annual performance, but are too complex for many buildings, or for the early stages of design. This paper describes a simpler procedure for calculating the seasonal performance of multi-boiler or multi-chiller heat or cold generation systems, taking account of the part-load characteristics of the individual heat or cold generators, their sizing, and the load distribution of the building. It inevitably requires some information about the part-load performance of the heat or cold generators, but is sufficiently flexible to accommodate different levels of data. For example, it can be used with the boiler part-load tests required for compliance with the European Boiler Efficiency Directive or the chiller partload tests proposed by Eurovent for their certification system. The individual heat or cold generators do not need to be identical. Building load information can be specific to a particular design and climate, if this is available: alternatively standard distributions can be defined for regulatory purposes. 1
2 The Seasonal Efficiency of Multi-Boiler and Multi-Chiller Installations Roger Hitchin, Building Research Establishment Simon Law, Faber Maunsell Introduction Estimates of HVAC system seasonal efficiency are required whenever annual energy consumption is calculated notably within the requirements of the European EPBD. (1) An important part of the calculation of seasonal system efficiency is the specific issue of the seasonal efficiency of heat generators (usually boilers) and cold generators (commonly chillers). This paper offers a framework for carrying out such calculations and discusses its practical application. Much of the content has been developed within three activities: - the development of draft European standards to support the EPBD (2) - the development of application tools for UK implementation of Article 3 of the Directive (11) - a multi-partner study of part-load issues relating to HVAC plant (3) This paper first describes the theoretical background and then discusses different implementation options, depending on the extent of data availability. Finally a short worked example is presented. For clarity the paper will focus on chillers, though the principles are equally applicable to boilers and to room air-conditioners. For boilers some of the issues that arise with chillers are absent. The general principles could also be applied to other situations where performance depends non-linearly on weather conditions for example, to heat recovery systems. 1. Basic Principles The ratio between the annual cooling load placed on a chiller and its corresponding energy consumption is its seasonal efficiency or, more accurately, seasonal energy efficiency ratio (SEER). However, this ratio is not constant for a given chiller, but depends on a number of other factors that vary with the application. In particular, the efficiency of a chiller varies significantly with the load placed on it and with the temperature to which heat is rejected. For many chillers, the efficiency at part-load is less than at full load though for others, the opposite is true. Generally, efficiency increases as heat rejection temperature falls. The two effects are usually of comparable size. For air-cooled equipment, the heat rejection temperature is closely linked to ambient air temperature but, for liquid-cooled equipment the temperature variations clearly depend on the source of the cooling fluid. Seasonal performance indices for single chillers exist in the form of the American Integrated Part Load Value (IPLV) (4) and the proposed European Seasonal Energy Efficiency Ratio (ESEER) (5). Each of these is a weighted average of several part-load efficiencies measured under different partload conditions and heat rejection temperatures see Table 1. The primary purpose of these indices is for product labeling to allow the easy identification of chillers of differing seasonal efficiency. For this reason, they need to be product- rather than application- specific and therefore to use a fixed set of weightings of the different part-load EERs. For building energy calculations this can be misleading when the load patterns or climate of the application are substantially different from those that underlie the standard weightings (6). For example, the implications of the application of the ESEER ratings in the UK were discussed at the previous IEECB conference (7). 2
3 Table 1 Comparison of IPLV and proposed ESEER for air-cooled chillers % part load ESEER Temperature C Weighting IPLV Temperature C Weighting IPLV and ESEER implicitly assume the use a of a single chiller, carefully sized to match the peak cooling load of a building. In practice, larger systems will commonly contain more than one chiller (or boiler) and the total installed capacity is rarely an exact match to the building load. The section below describes the basic theory that underlies these indices and shows how the same principles can be extended to energy calculations that reflect building characteristics and use, climate, and the number and sizing of chillers installed. 2. Theory 2.1. The Objective To calculate the energy consumption of a chiller or a set of chillers in an air-conditioning system, given knowledge of: - the cooling demands placed on it (or them) - the energy efficiency under a number of part-load conditions. The same processes can also be applied to complete cooling systems and to heating systems Combination of Load Frequencies and Part-load Performance Measurements Over some period of time the cooling demand on a chiller is L (kwh). During this period, energy C (kwh) is used to meet this demand. Efficiency is defined as L/C. The inverse, Energy Input Ratio EIR is often more convenient to use. Then C = EIR.L Clearly, over some longer period of time the total consumption is simply the sum of the consumption during different time periods. 2 Σ C = Σ ( EIR.L) and we can define an overall EIR as Σ C / Σ L = Σ (EIR.L) / Σ L Note that, if we express the equation in terms of efficiency instead of EIR, the overall efficiency is the harmonic mean of the individual efficiencies. (That is the reciprocal of the sum of the reciprocals) 1 For many boilers, efficiency at 30% and 100% of rated output is known in order to comply with the Boiler Efficiency Directive. Ambient temperature is not an issue. 2 For simplicity subscripts denoting the range over which summations are made are not shown 3
4 More generally, when L is zero, there may still be an energy consumption. In this case EIR is infinite and efficiency zero (irrespective of the size of the no-load consumption). Denote such zero-load consumption as C o. Σ C = Σ (EIR.L) + Σ C o and overall EIR is ((Σ EIR.L) + Σ (C o )) / Σ L EIR is a function of L and of heat rejection temperature: for air-cooled chillers outdoor temperature. This calculation can, in principle, be carried out for each individual time step (say each hour) within the calculation period of interest. It can be simplified by determining the frequency of occurrence of each level of demand (and temperature) during the period of concern. This is the basis of bin analysis. For example a bin might be defined as containing the number of hourly occurrences of a cooling load between 35% and 40% of the design cooling load of the building that are coincident with ambient air temperature between 24 C and 26 C. Denote the frequency with which each condition occurs as F, and associate a value of EIR with each bin. Then (noting that the summation is now over frequency classes rather than hours) Σ C = Σ (F.EIR.L) + F o.c o The frequencies and the demands may be further combined to generate demand weightings, W = F.L Σ C = Σ (W.EIR) + F o. C o 2.3 Seasonal performance indices Seasonal performance indices can be calculated in the form of an overall EIR, for the period, that is: (Σ (F.EIR.L) + F o. C o ) / Σ L or (Σ W.EIR) + F 0. C o ) / Σ L The overall seasonal EER is the reciprocal of this overall EIR A mean partial-load factor can be defined as PLV av = SEER/EER This approach, combined with standardized part-load EIRs for different types of chiller, and for singlechiller systems where the chiller is carefully matched to the peak load, is used in reference (10) 2.4 Calculation of Representative EIRs Each bin has to have an associated EIR value. However, each bin has a finite size (for example, from 45% load to 55% load) within which there may be significant variations of EIR especially if the bin size is large. Strictly speaking, the EIR for each bin should be calculated from the distribution of loads within the bin in the same way as the seasonal figure is calculated from the bin data. Pragmatically, it is rarely possible to do this, and it is necessary to estimate EIR by, for example, taking a value that represents the mid-point of the bin range, or the average of the values at the two bounding conditions for the bin. 4
5 2.5 Multiple Chillers For systems with multiple chillers, a combined EIR value must be calculated for each bin, representing a combined EIR of all the operating chillers (and the load conditions on each for example, one chiller at full output and a second one at 50% of full output). Note that this is not obtained by averaging EERs (unless the harmonic average is used) but by adding consumptions and determining the combined total consumption. The later worked example illustrates this. 2.6 Calculations for systems The same theory may be applied to complete systems. In this case, it is convenient to subdivide the energy into two classes: auxiliary energy A (kwh) that is used principally for energy transfer (fans and pumps) and for controls; and direct consumption, C (kwh) (used for the generation of heating or cooling by chillers, boilers and their ancillary equipment). For system calculations, direct consumption depends not only on the on the efficiency of conversion of fuel or electricity to heat (or cold) but also on the efficiency of distribution of heat (or cold). System EIR may be defined as the ratio between the total cooling (or heating) demands in the spaces being conditioned and the energy consumed by chillers or boilers. Auxiliary energy will be calculated separately (for example as a multiple of installed fan power and operating hours). 3 Some distribution systems alter the frequency distribution of loads placed on chillers for example by switching to full fresh air and no chiller operation when outdoor air temperatures are sufficiently low. 3. Practical Application 3.1 Background Ideally the theory would be applied to data that are specific to the building and system under consideration, to the actual or expected pattern of use, and to the local climate. This requires detailed information on chiller performance 4 over a wide range of conditions, and detailed estimates of building cooling demand from detailed simulation, for example. Such detailed information is rarely available, and simplifications have to be made. This section describes how this may be done in ways that are consistent with various levels of available data. Simplifications fall into two related areas: chiller information and bin definitions. Simplifications inevitably reduce the resolution of the calculation. However, the basic data will always be uncertain to some degree, and high theoretical resolution does not necessarily mean more precise or reliable results. For many applications, consistency of approach will be more important than fine degrees of apparent accuracy. For energy performance certification purposes, standardized assumptions will be necessary. Figure 1 summarises the suggested hierarchy of decisions and simplifications. 3.2 Simplification of Load Frequency Data Draft CEN standards (2) distinguish between dynamic building energy calculations, typically at hourly intervals, and simplified methods than generally work with monthly time intervals. When building cooling demands are calculated on an hourly basis, the production of hourly bins (of joint demand and ambient temperature) is straightforward. Alternatively the calculated hourly loads 3 Alternatively, EIR could be defined to include both direct and auxiliary energy consumption. 4 Either from manufacturers data or by detailed modelling. The characteristic time constants of chillers and packaged air-conditioners are usually such that it is difficult to define efficiency meaningfully for periods much less than, say ten minutes, while for some equipment, the variations of performance with load can be difficult to represent over periods much in excess of an hour. 5
6 can be used directly with chiller performance data if this is available. For standardised energy calculations, standardised weather data are obviously required. When cooling demands are calculated monthly or annually a standardised set of load frequencies (or demand weightings) can be used. These could be generated in several ways, of which computer simulations of characteristic buildings under standardised weather conditions are perhaps the most satisfactory. Clearly, these standardised demand frequencies will best match those of the building under consideration if the simulations are for a similar building with a similar air-conditioning system, similar pattern of use and located in a similar climate. Do you have a full performance map for each chiller? Yes Do you have hourly load figures for the building for the appropriate weather? Yes Detailed calculation of seasonal efficiency, taking account of load and heat rejection temperatures No No Extract part-load performance figures corresponding to the regional ambient temperatures from chiller performance map. Simplified calculation of seasonal efficiency as described in paper, using regional ambient temperatures and regional standard weightings Do you have part-load performance figures for the specified chiller at regional ambient temperatures? Yes Do you have hourly load figures for the building for the appropriate weather? No No Yes Simplified calculation of seasonal efficiency as described in paper, using regional ambient temperatures and building-specific weightings Do you have chiller part-load performance at Eurovent ambient temperatures? Yes Simplified calculation of seasonal efficiency as described in paper, using Eurovent ambient temperatures with regional standard weightings. May make generic correction if data are available. No Do you have chiller full-load performance at ISO standard conditions? Yes Use a generic chiller model as described in the paper, or part-load coefficients if available. No Use a chiller full-load EER of 2.25 kw/kw. (Comment:according to Eurovent figures about 80% of products on the market are better than this) Figure 1. Hierarchy of simplification decisions Since the efficiency of air-cooled chillers depends on ambient air temperature, the demand frequencies should ideally be accompanied by associated ambient air temperatures. Failing this, it may be possible to estimate ambient temperatures from the demand figures the two variables are 6
7 usually correlated, though imperfectly. The implications of inappropriate temperatures are discussed in the section dealing with chiller performance simplifications. The EECCAC project (6) derived load frequency distributions from building energy simulations for a wide range of system types at three sites: London, Milan and Seville. As (7) points out, the loads placed on the chiller system can vary with the type of cooling system installed, as well as with weather and building design and use. Similar building energy simulations (using a different simulation tool) have been carried out for a wider range of building designs (though all offices) and locations, but for fewer systems, in the UK (3). Figure 2 shows a sample distribution for an office in London, with a 4-pipe fan-coil cooling system. 30% % Cooling energy (delivered) 25% 20% 15% 10% 5% 0% < 12.5% 12.5 to 25% 25 to 37.5% 37.5 to 50% 50 to 62.5% 62.5 to 75% 75 to 87.5% > 87.5% Building cooling load Figure 2. Example building load distribution. 3.3 Approximation of Chiller Performance Data Ideally the chiller performance should be evaluated at each time step of the cooling demand calculation. This requires a full (and reliable) performance map for the chiller(s) that are installed or proposed. Some manufacturers are able to provide this information, but it is not always publicly available nor independently verified. If a full chiller performance map does not exist, measurements under standard full-load conditions and some part-load conditions may be available. The EECCAC project concluded that a minimum of four demand weightings (each associated with an ambient temperature representing the mean value associated with these load conditions) was necessary to distinguish between chillers of differing performance. The US IPLV rating (4) also uses four part-load conditions. Values were determined by the EECAC project for a range of climates and systems. For a fan-coil system located in London, they were: Table 2 Example Demand Ratings Relative frequency of occurrence (% of operating hours) 7 Cooling demand as percentage of design load Relative demand weighting (frequency of occurrence x proportional demand ) Mean ambient temperature associated with demand 60.8% 25% 42.3 % % 50% 48.5 % % 75% 8.7 % % 100% 0.5 % 27.6
8 There are several existing and proposed sources of chiller performance information under conditions other than full load standard test conditions. For example Eurovent is proposing to include part-load tests into its certification programme (5). Draft CEN standard prcen/ts describes part-load tests, as does Italian standard UNI ARI standard defines four part-load tests required for the ARI IPLV rating; and the EECCAC project proposes European tests equivalent to the ARI tests. The particular temperature conditions prescribed for the part-load tests will not be appropriate for all climates (7) and cannot apply to each individual chiller in a multi-chiller installation with the chillers operating in sequence. Manufacturers may be able to provide sufficient information to interpolate to appropriate national or regional temperatures, where these are known. If this is not possible, data relating to the wrong temperatures has to be accepted. A limited number of calculations on the impact of using ESEER temperatures which reflect Southern European conditions in the UK suggests that the error will be of the order of 5% to 10%. As it will always be in the same direction (better efficiencies, reflecting the lower summer temperatures in the UK), the impact on equipment selection choices is probably not great. (With the caveat that chillers with free-cooling capability might be under-valued). Sometimes only full-load performance under standard test conditions is known. For many chillers this information is available from Eurovent Certification, most readily accessed via Under these conditions, part-load performance values have to be estimated using generic models. For example using the procedure previously used in ARI standards (8) (current ARI standards require part-load testing), or that proposed by Bettani et al (9). Reference (10) contains standardized part load performance factors for several types of chiller and room conditioner. When no information is known about the chiller (for example in existing systems or in the initial stages of design), it will be necessary to use a default value for full-load performance, and apply the generic part-load estimates mentioned above. From Eurovent certification data the EER of the average European air-cooled air-conditioning chiller is about 2.5. Approximately 80% of chillers have values above 2.25, so this could be a suitable default assumption 3.4 Suggested Data Sources This section summarises key points from figure 1 and from the preceding discussion. EER values: in order of preference: 1. Part (and full-) load EERs measured under climatic conditions appropriate to the application. For example, suitable ambient temperatures have been defined for London, Seville and Milan by the SAVE project EECCAC. Some manufacturers have full performance maps of equipment that includes this level of detail, but this information is not always publicly available or independently verified. 2. Part (and full-) load EERs measured under standardised conditions, even though these are not an ideal match for the local climate. Eurovent intends to require such measurements at 25%, 50%, 75% 100% rated output for standardised European conditions for its certification scheme. (ref) 3. Measured full load EER in accordance with CEN (and ISO) standards, with default assumptions for part-load performance. Load frequency distributions: in order of preference 1. Building and system-specific distributions calculated typically from hourly values Standard national or regional values. For example, the weightings derived for London, Seville and Milan by the SAVE project EECCAC.
9 4. Illustrative Example of Estimation of Seasonal EER This example illustrates the processes of: - determining load frequency distributions - determining multi-chiller EER from data for single chillers - mapping the chiller rating data onto the load frequency distribution - estimating seasonal EER The general principles illustrated here are applicable to any set of chiller or boiler part-load conditions and sizing. In practice it may be convenient to build the process into software such as a spreadsheet. Suggestions for data sources are made at the end of this section. 4.1 Load frequency distributions Either from load calculations for a specific building, or a standard national or regional assumption, we have a frequency distribution of different fractional cooling loads (where 1 = the peak load). For energy calculations, we need to convert this into an energy demand distribution, by multiplying the frequency by the part-load fraction. This generates a load-weighted distribution. In the chart below, the frequency distribution for an office in the UK is shown as a broken line, and the load-weighted distribution as a solid line. Normalised load distributions Normalised frequency Fractional load frequency load weighted Figure 3: Normalised Load Distribution For later stages in the calculation, it is convenient to convert the load-weighted distribution into a cumulative distribution as shown below. 9
10 Normalised cumulative load distributions Normalised frequency Fractional load frequency load weighted Figure 4: Normalised Cumulative Load Distributions 4.2 Combined chiller performance In the example, we assume two identical chillers, each capable of providing 75% of the peak load, operating in sequence, each with part-load performance values of Table 3: % part-load EER With two chillers we therefore have eight combinations for which we can calculate an EER. 5 These are shown in the table below. Because the example system is oversized, three of the conditions are for loads in excess of the peak load. When both chillers are operating, the combined EER is determined by dividing the relative demand on each chiller by the appropriate EER, summing the total consumption and dividing the result by the total demand. Thus with 1 chiller operating at 100% output and the other at 25%, we have Chiller 1 consumption = 1/2.8 = Chiller 2 consumption = 0.25/2 = Total consumption = Combined EER = 1.25/0.482 = If the chillers do not operate in sequence, the procedure has to be modified accordingly. 10
11 Table 4: Chiller 1 Chiller 2 Chiller 1 EER Chiller 2 EER Combined EER fractional load fractional load 0 0 N/A N/A N/A N/A N/A N/A N/A Mapping the chiller ratings on to the load frequency Each of these chiller rating points maps onto the building s load frequency distribution, as shown in Figure 5 as solid vertical lines: Rating points cumulative load frequency fractional load Figure 5: We need to associate each rating point with some proportion of the cooling energy demand. We do this by first finding the building fractional load that is midway between each chiller rating point. This divides the frequency distribution into a number of bands, each of which contains one chiller rating point. (The lowest band has a lower limit of zero building load). This is illustrated in Figure 6, where the band boundaries are shown as broken vertical lines. 11
12 1.000 Energy Bands cumulative load frequency fractional load Figure 6 The weighting for each rating point is the difference of the cumulative loads at each of the two boundary conditions. (It may be necessary to interpolate between known values of the load frequency distribution to determine these values). We then have to divide each demand weighting by the appropriate EER to calculate the total consumption and can then derive the seasonal EER. The process is illustrated in the table below. Table 5: Chiller 1 fractional load 12 Chiller 2 fractional load Building fractional demand Demand weighting for the demand level Combined EER Energy consumption N/A N/A 2.76 N/A N/A 2.80 N/A Total (normalised) energy consumption = Combined seasonal EER = 1/ = References 1. Directive 2002/91/EC 2. Ventilation for buildings Calculation of room temperatures and of load and energy for buildings with room conditioning systems pren (annexe I). CEN Seasonal Efficiency Ratings for non-domestic HVAC plant. DTI Partners in Innovation project 39/3/720. Faber Maunsell ARI Standard 550/ Standard for Water Chilling Packages using the Vapour Compression Cycle, 1998, Air-Conditioning and Refrigeration Institute, USA 5. Eurovent-Cecomaf Review no 69, November 2004
13 6. J Adnot et al Energy Efficiency of Central air-conditioning systems in Europe, International Conference on Improving Energy Efficiency in Commercial Buildings IEECB 04 Frankfurt April Roger Hitchin et al, Air Conditioning Energy Efficiency Issues: Why is the UK different? International Conference on Improving Energy Efficiency in Commercial Buildings IEECB 04 Frankfurt April Previous versions of ARI standards 55/590 and 210/ Bettani et al., Simplified Models to simulate Part Load Performances of Air-conditioning Equipment, Eighth International IBPSA Conference, Eindhoven August Energetische Bewertung von Gebauden Berechnung des Nutz-, End- und Primarenergiebedarfs fur Heizung, Kuhlung, Luftung, Trinkwarmwasser und Beleuchtung Teil 7: Energiebedarf von Raumlufttechnik- und Klimakaltesystemen fur Nichtwohnungsbau. DIN V ,
HVAC Efficiency Definitions
HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the
Boiler efficiency for community heating in SAP
Technical Papers supporting SAP 2009 Boiler efficiency for community heating in SAP Reference no. STP09/B06 Date last amended 26 March 2009 Date originated 28 May 2008 Author(s) John Hayton and Alan Shiret,
AN APPLICATION MANUAL FOR BUILDING ENERGY AND ENVIRONMENTAL MODELLING
AN APPLICATION MANUAL FOR BUILDING ENERGY AND ENVIRONMENTAL MODELLING D. Bartholomew *, J. Hand #, S. Irving &, K. Lomas %, L. McElroy # F. Parand $, D. Robinson $ and P. Strachan # * DBA, # University
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
Appendix C. Minimum Equipment Efficiency Standards
Appendix C Minimum Equipment Efficiency Standards Appendix C: Minimum Equipment Efficiency Standards This Appendix is an overview of building and equipment standards in the State of California that have
Application of Building Energy Simulation to Air-conditioning Design
Hui, S. C. M. and K. P. Cheung, 1998. Application of building energy simulation to air-conditioning design, In Proc. of the Mainland-Hong Kong HVAC Seminar '98, 23-25 March 1998, Beijing, pp. 12-20. (in
Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *
Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS
WORKING DOCUMENT ON Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS WORKING DOCUMENT in the framework of the implementation of
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Large Energy Savings Per Installation VFDs for Large Chillers
This article was published in ASHRAE Journal, June 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.tiaxllc.com.
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
Florida Power & Light Company. Business Heating Ventilation & Air Conditioning ( HVAC ) Program Standards. Effective: November 9, 2015
Florida Power & Light Company Business Heating Ventilation & Air Conditioning ( HVAC ) Program Standards Effective: November 9, 2015 Table of Contents Eligibility Requirements - Chiller... 2 Rebate Amount
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction What is DNSS EcoSave? The Daikin Network Service System (DNSS EcoSave) is a Daikin developed internet based remote
THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power
THE EUROPEAN GREEN BUILDING PROGRAMME Technical Module on Combined Heat and Power Contents Foreword...1 1. Introduction...2 2. Inventory of the CHP system...3 3. Assessment of technical energy saving measures...5
Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets
2 Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets - Extending Use of New Heat Pump System in Cold Regions
Daikin Altherma Hybrid Heat Pump
your comfort. our world. Daikin Altherma Hybrid Heat Pump Smart heating technology for the best of both worlds Heating Integrated Solutions Ventilation Air Conditioning Refrigeration Forward thinking About
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
Information Guide Domestic Air Source Heat Pumps
Information Guide Domestic Air Source Heat Pumps Issue 41 Domestic Air Source Heat Pumps This is an independent guide produced by Mitsubishi Electric to enhance the knowledge of its customers and provide
POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747
POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609
New energy evaluating methodology of Air conditioner and Heat pump
New energy evaluating methodology of Air conditioner and Heat pump The 3 rd Conference Research and Development of Heat Pump and Thermal Storage Technologies in Industrial and Residential Sectors 8 October
Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75
Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER
A benchmarking guide adapted to air conditioning based on electricity bills
Technical guides for owner/manager of an air conditioning system: volume 7 A benchmarking guide adapted to air conditioning based on electricity bills 1 Team France (Project coordinator) Armines - Mines
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings
PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings Version 2006.1 AUSTRALIAN BUILDING CODES BOARD JANUARY 2006 TABLE OF CONTENTS Foreword 1. Scope 2. Purpose and context
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
Program Overview. Free intelligent thermostat and gateway device ($150 - $200 value)
Program Overview What is mpowered? mpowered is an energy conservation program that offers customers advanced technologies and tools to help lower their bills through automated and more strategic utilization
ALONE. small scale solar cooling device Project No TREN FP7EN 218952. Project No TREN/FP7EN/218952 ALONE. small scale solar cooling device
Project No TREN/FP7EN/218952 ALONE small scale solar cooling device Collaborative Project Small or Medium-scale Focused Research Project DELIVERABLE D5.2 Start date of the project: October 2008, Duration:
Modeling Guide for Daikin VRV in EnergyPro 6
Modeling Guide for Daikin VRV in EnergyPro 6 Table of Contents Introduction... 1 Program Installation... 2 Importing Designated VRV Product File... 3 System Modeling... 6 Modeling air-cooled outdoor units...
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
Percent per Degree Rule of Thumb for Refrigeration Cycle Improvement
7 Percent per Degree Rule of Thumb for Refrigeration Cycle Improvement Steve Doty, PE, CEM [email protected] ABSTRACT A value of 1-1.5% power reduction per degree Fahrenheit (F) has been used successfully
Daikin Altherma Hybrid Heat Pump
Daikin Altherma Hybrid Heat Pump Smart technology for the best of both worlds NATIONAL HEAT PUMP 19 JUNE 2014 ICC BIRMINGHAM WINNER Forward thinking Now is the time to rethink the way we heat our homes
Refrigerant Choices for Commercial Refrigeration. Finding the Right Balance
Refrigerant Choices for Commercial Refrigeration Finding the Right Balance 2 CONTENTS 1. Executive Summary 1.1. Introduction 4 1.2. Glossary of terms 5 5. Cases configuration 5.1. Introduction 17 5.2.
Daikin Altherma hybrid heat pump. The natural combination
Daikin Altherma hybrid heat pump The natural combination Daikin Altherma hybrid heat pump, the natural combination Why choose Daikin Altherma hybrid heat pump? What the customer wants: more energy efficient
European actions to improve the energy efficiency of buildings. Olli Seppänen, professor Federation of European Heating and Airconditioning
European actions to improve the energy efficiency of buildings Olli Seppänen, professor Federation of European Heating and Airconditioning Associations 1 Climate Action: Energy for a Changing World On
Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump
s.doty 10-2014 White Paper #30 Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump System Switches Fuels Automatically for Economy. What is an Air-Source Heat Pump? A heat pump is a modified air conditioning
Electrical Efficiency Modeling for Data Centers
Electrical Efficiency Modeling for Data Centers By Neil Rasmussen White Paper #113 Revision 1 Executive Summary Conventional models for estimating electrical efficiency of data centers are grossly inaccurate
Understanding Heating Seasonal Performance Factors for Heat Pumps
Understanding Heating Seasonal Performance Factors for Heat Pumps Paul W. Francisco, University of Illinois, Building Research Council Larry Palmiter and David Baylon, Ecotope, Inc. ABSTRACT The heating
Heating & Cooling Efficiency
Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart
Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice
Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice A truly international certification The Eurovent Certification Programmes are managed by an autonomous
DAikin Altherma low temperature heat pump. end user leaflet
DAikin Altherma low temperature heat pump HEATING, COOLING & DOMESTIC HOT WATER end user leaflet 2 The natural choice D 3 in1: heating, cooling and hot water Daikin Altherma is a total heating and domestic
Non-Domestic Building Services Compliance Guide
Non-Domestic Building Services Compliance Guide 2013 edition for use in England* * Note: Any reference to the Building Regulations in this guide is to the Building Regulations 2010 in England (as amended).
forair optimal air environments ResidentialPresentation
forair optimal air environments ResidentialPresentation Quick Fact Countless neighborhood residents never recognize their home air conditioning system works roughly 3,000+ hours each year. In order to
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Sustainable construction criteria to evaluate the thermal indoor climate - further development of the BNB assessment tool and practical implementation
Fraunhofer Institute for Building Physics IBP Directors Univ. Prof. Dr. Ing. Gerd Hauser Univ. Prof. Dr. Ing. Klaus Sedlbauer Holzkirchen Branch Fraunhoferstrasse 10 83626 Valley / Germany IBP-Abstract
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. AFFORDABLE SOLUTIONS FROM AMERISTAR. We know that heating and cooling systems can be a major investment for homeowners. Our goal is
ENERGY SAVING BY COOPERATIVE OPERATION BETWEEN DISTRICT HEATING AND COOLING PLANT AND BUILDING HVAC SYSTEM
Proceedings of Building Simulation 211: ENERGY SAVING BY COOPERATIVE OPERATION BETWEEN DISTRICT HEATING AND COOLING PLANT AND BUILDING HVAC SYSTEM Yoshitaka Uno 1, Shinya Nagae 1, Yoshiyuki Shimoda 1 1
Market Potential Study for Water Heater Demand Management
Market Potential Study for Water Heater Demand Management Rebecca Farrell Troutfetter, Frontier Associates LLC, Austin, TX INTRODUCTION Water heating represents between 13 and 17 percent of residential
Degree-days: theory and application
Degree-days: theory and application TM41: 2006 The Chartered Institution of Building Services Engineers 222 Balham High Road, London SW12 9BS CIBSE The rights of publication or translation are reserved.
By Donald Fisher, P.Eng., Associate Member ASHRAE
By Donald Fisher, P.Eng., Associate Member ASHRAE Decisions to purchase a commercial kitchen ventilation (CKV) system often are based on rule-of-thumb estimates using a $/cfm index (i.e., annual energy
Thermal Coupling Of Cooling and Heating Systems
This article was published in ASHRAE Journal, February 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new
Data Center Ultra-Efficient chilled water system optimization White paper File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new Data Center - Ultra-Efficient white paper 3 abstract The primary
2015 C&I HVAC RETROFIT APPLICATION FOR PRESCRIPTIVE REBATES
2015 C&I HVAC RETROFIT APPLICATION FOR PRESCRIPTIVE REBATES WELCOME TO THE POWER MOVES C&I HVAC RETROFIT PROGRAM. We look forward to working with you. If you have questions after reading this application,
HVAC System Optimization
UNITED TECHNOLOGIES CARRIER CORPORATION HVAC System Optimization MAXIMIZING PERFORMANCE, ENERGY SAVINGS & COMFORT Revitalize Your Building s System Sometime between the initial purchase and the need to
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
R 60 DoMC-01 rev.1 Additional requirements from the United States. Accuracy class III L. Revision number Date of the revision Nature of the revision
R 60 DoMC-01 rev.1 Additional requirements from the United States Accuracy class III L Revision number Date of the revision Nature of the revision Rev.0 29/09/2006 Initial document Rev.1 03/03/2014 Update
Performance Testing of Solar Combisytems
Performance Testing of Solar Combisytems Comparison of the CTSS with the ACDC Procedure A Report of IEA SHC - Task 26 Solar Combisystems November 2002 Harald Drück Stephan Bachmann Performance Testing
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
Daikin Altherma Hybrid Heat Pump
your comfort. our world. Daikin Altherma Hybrid Heat Pump The natural combination Heating Integrated Solutions Ventilation Air Conditioning Refrigeration About Daikin Forward thinking... Daikin has a worldwide
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
The natural ombination
The natural ombination DAIKIN ALTHERMA HYBRID HEAT PUMP 2 A new pportunity in residential heating! There is a growing demand from home owners to replace heating systems, especially replacing of gas boilers,
Simplified Procedure For Estimating Air- Conditioning Cooling Load In Ghana
Simplified Procedure For Estimating Air- Conditioning Cooling Load In Ghana Felix A. Uba, YesuenyeagbeA. K. Fiagbeand Emmanuel A. Sarsah Abstract: Undersized or oversized air conditioning equipment leads
Daikin Altherma. hybrid heat pump. The natural combination
Daikin Altherma hybrid heat pump The natural combination Why choose Daikin? As an industry leader, Daikin combines broad experience, technical innovation and responsive customer service to help you meet
EnergyPro Building Energy Analysis. Assisted Living Building
EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the
By Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
A heat pump system with a latent heat storage utilizing seawater installed in an aquarium
Energy and Buildings xxx (2005) xxx xxx www.elsevier.com/locate/enbuild A heat pump system with a latent heat storage utilizing seawater installed in an aquarium Satoru Okamoto * Department of Mathematics
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
The natural ombination
The natural ombination DAikin Altherma Hybrid heat pump system The future is now The new hybrid system Heat pump solution for gas boiler replacement market Daikin Altherma hybrid combines heat pump technology
Best Practice Guide BPGCS007
Best Practice Guide BPGCS007 ENERGY MANAGEMENT Introduction: With rising fuel costs, opening of electricity and gas markets to alternate suppliers and climate change, the requirement to monitor and reduce
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Alternatives to regular inspection of heating and air-conditioning systems for the EPBD: evaluation and comparison. Bruce Young.
Bruce Young Alternatives to regular inspection of heating and air-conditioning systems for the EPBD: evaluation and comparison July 2014 www.epbd-ca.eu Alternatives to regular inspection of heating and
Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications
Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Kavita A. Vallabhaneni U. S. Government commitment to reduce greenhouse gas emissions can have a significant impact
REFRIGERATOR AND AIR-CONDITIONER TESTING IN THE REPUBLIC OF KOREA
REFRIGERATOR AND AIR-CONDITIONER TESTING IN THE REPUBLIC OF KOREA Junyoung Choi Korea Testing Laboratory, Republic of Korea ENERGY LABELING PROGRAM Korea has a limited natural resources, This, together
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is
SAP 2012 IN A NUTSHELL
SAP 2012 IN A NUTSHELL The consultation version of the SAP 2012 methodology was published by the Department of Energy and Climate Change (DECC) on January 4th 2012. This article from Dyfrig Hughes of National
HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING. Campus du Sart Tilman, B49, B-4000 Liège, Belgium
HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING Cleide Aparecida Silva 1, [email protected] Stéphane Bertagnolio 1, [email protected]
Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers
HEAT RECOVERY FROM CHILLED WATER SYSTEMS Applications for Heat Reclaim Chillers April 2008 TABLE OF CONTENTS INTRODUCTION... 3 WASTE HEAT SOURCES... 3,4 Capturing Sufficient Heat for Useful Purposes...
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent
APPLICATION OF DATA MINING TECHNIQUES FOR BUILDING SIMULATION PERFORMANCE PREDICTION ANALYSIS. email [email protected]
Eighth International IBPSA Conference Eindhoven, Netherlands August -4, 2003 APPLICATION OF DATA MINING TECHNIQUES FOR BUILDING SIMULATION PERFORMANCE PREDICTION Christoph Morbitzer, Paul Strachan 2 and
English version. Manual for Determination of Combined Heat and Power (CHP)
CEN/CENELEC WORKSHOP CWA 45547 September 2004 AGREEMENT ICS 27.100 English version Manual for Determination of Combined Heat and Power (CHP) This CEN/CENELEC Workshop Agreement has been drafted and approved