1 New Thermal Architecture For Future Green Data Centres S. Le Masson, D. Nörtershäuser France Télécom R&D 2, Av Pierre Marzin Lannion FRANCE ; Abstract - It is now admitted that electrical power devoted to telecommunication industry will grow tremendously with the development of internet services [1] [2]. In a data centre, most of the energy supplied to the IT equipments is converted into heat and diffused in a closed volume. The energy losses through the walls are negligible, even in winter. To compensate the energy balance, an air conditioning system must be used to transfer heat power at least equal to the total equipments power. The use of free cooling can be an easy way to reduce the energy consumption. Furthermore, if the building construction is adapted (thermal inertia, thickness of the walls, flow rate ), an optimization is possible by using a night cool storage directly in the masonry. Previous studies related to small buildings have shown good results [3]. This paper describes an experimental study in order to define new conceptions of optimized telecommunication buildings.. I. INTRODUCTION In a context of growing energy demand, when the energy production has a severe impact on environment, it becomes necessary to estimate the responsibility of each economical sector, particularly telecommunications or IT (information Technology) domain. Indeed, the energy consumption of the different networks and IT equipments is far from being negligible. Even if authors do not agree on the rise [1] [2], it is now admitted that electrical power devoted to telecommunication industry will grow tremendously with the development of internet services. Thus, it is necessary to study solutions to reduce energy consumptions, particularly regarding air conditioning systems [3]. The air conditioning part represents 30 to 50% of the whole energy consumption, particularly in data centres that are strategic rooms. According to its sustainable development policy, France Telecom has developed low-consumption air conditioning systems [4] devoted to existing buildings. This document is about studies that aim at defining rules to build more efficient buildings for telecommunication centres. Actually, as it can be seen on figure 1, the energy consumption of France Telecom data centres represents 17% of the whole energy consumption. Figure 1: Distribution of energy consumption by types of networks [5] Figure 2: Distribution of energy consumption in a data centre II. DATACENTER THERMAL PROBLEM The term data centres includes all buildings, facilities, offices and rooms which contain enterprise servers, server communication equipment, cooling equipment and power equipment, and provide some form of data service (e.g. large scale mission critical facilities all the way down to small server rooms located in office buildings). The surface of these rooms can reach 1000 m² with a growing power density through the years (from 500W/m² to 2kW/m²). The figures 3 and 4 illustrate the common architecture of rooms with various equipments and various /10/$ IEEE

2 thermal dissipations (very different from one equipment to another). Figure 5: Simplified thermal problem Figure 3: Inside view of a data centre In a data centre, most of the energy supplied to the IT equipments is converted into heat and diffused in a closed volume. The energy losses through the walls are negligible, even in winter. To compensate the energy balance, an air conditioning system has to be used to transfer a heat power at least equal to the total equipments power. In summer, the air conditioning system has to remove the energy diffused through the walls plus the energy of the equipments. The use of free cooling can be an easy way to reduce the energy consumption. Furthermore, if the building construction is adapted (thermal inertia, thickness of the walls, flow rate, diffusion ), an optimization is possible by using a night cool storage directly in the masonry. Previous studies related to small buildings have shown good results [6]. Figure 4: Inside view of a data centre Up to now, data centres buildings have been constructed like residential buildings that are not intended to dissipate heat but to keep it inside. The figure 5 is a scheme of the thermal problem with internal dissipation in the building. Compared to the heat dissipated through walls or roof, the power dissipated by the equipments is huge. III NUMERICAL SIMULATIONS In a first time, a numerical model based on nodal method has been developed in order to simulate small telecommunications buildings and to deduce some constructions rules. A diagram of the thermal numerical model is represented on figure 4. The user has to enter the following input: - Temporal evolution of the external temperature - Temporal evolution of the solar heat flux - Internal power dissipated by the equipments. Geometric data (size of the building) and physical properties of each layer of the walls have to be known too. Then, the temporal evolution of the mean internal temperature can be computed. External temperature Solar heat flux Internal power Thermal model (geometrical data, physical properties) Mean internal temperature Figure 6: Numerical model

3 Numerical computations have shown that the power that can be dissipated in the building can be seriously enhanced with walls made of concrete with embedded phase change materials micro-capsules [7], and an external thermal insulation. Such a conception works only if fresh air is introduces when the external temperature remains below a limit (typically, the evening, at night and the morning). IV EXPERIMENTATIONS ON SMALL-SCALE BUILDINGS WITH PHASE CHANGE MATERIALS In order to check the promising numerical results, three small-scale models of buildings have been constructed (figures 7 and 8). 4.1 Reference model M1 The first building model will be our reference. Its conception is classical. The internal volume is 1 m 3. The floor is made of concrete (thickness=10 cm), thermally insulated on the external face with extruded polystyrene (thickness=5 cm). The making up of the concrete is: 2 volumes of sand, 2 volumes of gravels, 1 volume of Portland cement. The melting has been made with an electrical cement mixer. The walls are made of breezeblocks (thickness=20cm), put together with cement mortars.the making up of this cements mortar is: 3 volumes of sand and one volume of cement. The breezeblocks are filled with the same concrete as the floor in order to enhance the thermal mass. A removable ceiling has been used. It has the same shape and properties as the floor. All the faces of the model have been isolated with extruded polystyrene (BASF styrodur ). Figure 8 Finished M1 model Each model has an air input and an air output (Figure 5 and Figure 6) in order to ensure forced air renewal when the external temperature is below a certain level. The main goal is to use the thermal inertia of the building as a cooling storage and to use it during the hottest hours of the day. 4.2 M2 Model The M2 model is very close to M1 model, with the exception of the walls that are not filled with concrete. This modification is made to evaluate the effect of the improved thermal inertia of M M3 model with micro-encapsulate phase change material In order to improve the thermal storage capacity of the walls, micro-encapsulate phase change materials have been used. These products are made by the Microtek Company (MicroPCM product). MicroPCM s consist of an encapsulated paraffin-wax substance which absorbs and releases heat in order to maintain a regulated temperature. The particles have a typical size distribution in range of 5 40 microns (Figure 9). The phase change temperature of the PCM is 28 C for the M3 model. If the capsules are not destroyed during the concrete mixing process, this would normally lead to walls with a high storage capacity around 28 C. Figure 7 Making up of M1 model. Figure 9 Micro-encapsulate phase change material (source Microtek)

4 From a geometrical point of view, the M3 model is the same as M1 and M2. The only differences come from the mortars and concrete composition which are detailed below. The concrete of the floor and ceiling is made as follows: volumes of sand, 1.5 volumes of gravels, 2 volumes of PCM28, 1.2 volumes of cement. The cement mortar used to joint the blocks is made as follows: - 2 volumes of MicroPCM 28, 2 volumes of sand, 1 volume of cement. 4.4 Measurements under artificial climate The three models have been simultaneously tested under an artificial climate in a laboratory (Figure 10) that can recreate both external temperature and solar heat flux [8]. Température ( C) :00:00 04:48:00 09:36:00 14:24:00 19:12:00 00:00:00 04:48:00 Heure Temp Flux Figure 11. Artificial climate laboratory Each model has a ventilation system switched on from 11:30PM to 9AM in order to cool the building structure at night (this extremely simplified regulation can be used as we know a priori the external temperature) Densité de flux solaire (W/m²) Only first results can be presented. In order to simulate the power dissipated by the equipments, modified fan heaters have been used (the modification has been made to ensure a steady dissipated power over time). The temporal evolution of the slab temperatures are represented on figure 12. The ambient temperatures of the models are represented on figure Figure 10. Artificial climate laboratory The solar and temperature simulated are represented on figure 11. The solar heat flux simulation is made with incandescent lamps. The room temperature is controlled with heating units and fresh air inputs. Températures ( C) :00 12:00 0:00 12:00 0:00 12:00 Date Heure M1 Tdalle M2 Tdalle M3 Tdalle Figure 12. Evolution of slab temperatures During the period of concern, the ambient temperature reaches a maximal value of 45 C in the M2 model, in other words in the model characterized by the smaller thermal storage capacity. The M1 model leads to a lower ambient temperature (- 3 C), thanks to the concrete added in thermal blocks. At last, the model made with micro PCM leads to the lower temperature (33.6 C), which represents a lowering of 10 C compare with other models.

5 The analysis of the temperature of each model slab illustrates very clearly the thermal inertia of each structure. The temperature of the slabs of M1 and M2 models are quite similar. On the other hand, the M3 slab does not exceed 27.2 C. Températures ( C) Ventilation M1 Tamb haute M2 Tamb haute M3 Tamb haute Ventilation [2] Koomey, J. G. (2007). Estimating total power consumption by servers in the U.S. and the world, Staff Scientist, Lawrence Berkeley National Laboratory and Consulting Professor, Stanford University: 31. [3] Roth, K., F. Goldstein, et J. Kleinman, (2002) Energy consumption by office and telecommunications equipment in commercial buildings, volume i : Energy consumption baseline. Technical report, ADL. [4] S. Le Masson, J. Gautier, D. Nörtershäuser (2005) La climatisation simplifiée des commutateurs téléphoniques. Congrès SFT 2005 Reims [5] L. Souchon. TIC et Énergétique : Techniques d estimation de consommation sur la hauteur, la structure et l évolution de l impact des TIC en France. Thèse INT [6] D. Nörtershäuser, S. Le Masson Using phase change materials and efficient coldless air conditioning systems to optimize the heat management in telecom shelters IEEE-Intelec 2007 Rome. [7] D. Nörtershäuser, S. Le Masson, Optimisation du conditionnement d'air des locaux de télécommunication par utilisation de produits à changement de phase, Congrès SFT 2008, Toulouse [8] D. Nörtershäuser, S. Le Masson Clim@Lan: A powerful artificial climate facility designed to test telecommunication equipments IEEE- Intelec 2005 Berlin 18:48 23:36 4:24 9:12 Date Heure 18:48 23:36 4:24 Figure 13. Evolution ambient temperatures 9:12 These first results prove that the use of PCM to enhance the storage capacity of a building is an interesting way of lowering the energy consumption of air conditioning systems. V CONCLUSIONS According to its sustainable development policy, France Telecom has developed low energy consumptions air conditioning systems for existing buildings. In order to build more energy efficient data centres, a study has been initiated to define new conceptions of optimized telecommunication buildings. The first results clearly prove the efficiency of the PCM to enhance the storage capacity of the whole building. Actually, by lowering significantly the internal temperature, it will reduce the energy consumption of air conditioning systems.. This study shows also that the building of a data centre must be constructed carefully in order to increase the energy efficiency. Some others works must be done to improve theses results, and to optimise night cooling with an optimise ventilation instead of a simple time switch on ventilation. Tests must be done for a longer period (10 days for example) to be sure that the PCM is regenerated every night. REFERENCES [1] Mills, M., et P. Huber, 1999 Dig more coal - the pcs are coming. Forbes Magazine.

Heat and cold storage with PCM

Heat and cold storage with PCM Harald Mehling Luisa F. Cabeza Heat and cold storage with PCM An up to date introduction into basics and applications With 208 Figures and 28 Tables 4y Springer Contents 1 Basic thermodynamics of thermal

More information

ENERGY AUDIT. Project : Industrial building United Arab Emirates (Case study) Contact person (DERBIGUM):

ENERGY AUDIT. Project : Industrial building United Arab Emirates (Case study) Contact person (DERBIGUM): ENERGY AUDIT Project : Industrial building United Arab Emirates (Case study) Contact person (DERBIGUM): Leonard Fernandes DERBIGUM project reference : UAE -2014 - EA 103 Author : Daniel Heffinck (DERBIGUM)

More information

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015 EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW

More information

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)

More information

A Roof Integrated Solar Heating System Without Storage

A Roof Integrated Solar Heating System Without Storage M. and W. Saman Sustainable Energy Centre University of South Australia Mawson Lakes Boulevard, Mawson Lakes, SA 5095, Australia E-mail: martin.belusko@unisa.edu.au Abstract A prototype of a roof integrated

More information

Net Zero Station Design for The Cooper Centre for the Environmental Learning in Tucson, Arizona: Improving the performance of existing buildings

Net Zero Station Design for The Cooper Centre for the Environmental Learning in Tucson, Arizona: Improving the performance of existing buildings Net Zero Station Design for The Cooper Centre for the Environmental Learning in Tucson, Arizona: Improving the performance of existing buildings Alya Al-Hashim 1, Lena Spiric 2,and Nader Chalfoun 3 1,2

More information

Diego Ibarra Christoph Reinhart Harvard Graduate School of Design

Diego Ibarra Christoph Reinhart Harvard Graduate School of Design Building Performance Simulation for Designers - Energy DesignBuilder // EnergyPlus Tutorial #2 Load Schedules GEOMETRY LOADS RESULTS Diego Ibarra Christoph Reinhart Harvard Graduate School of Design OVERVIEW

More information

THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING. R.M.J. Bokel

THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING. R.M.J. Bokel THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING R.M.J. Bokel Department of Architecture, Delft Technical University, Delft, The Netherlands,

More information

MICROENCAPSULATED PHASE CHANGE MATERIALS (PCM) FOR BUILDING APPLICATIONS

MICROENCAPSULATED PHASE CHANGE MATERIALS (PCM) FOR BUILDING APPLICATIONS MICROENCAPSULATED PHASE CHANGE MATERIALS (PCM) FOR BUILDING APPLICATIONS C. Castellón, M. Nogués, J. Roca, M. Medrano, L. F. Cabeza Departament d Informàtica i Eng. Industrial, Universitat de Lleida Pere

More information

ENERGY REHABILITATION STUDIES OF A LARGE GROUP OF HISTORICAL BUILDINGS: A CASE STUDY

ENERGY REHABILITATION STUDIES OF A LARGE GROUP OF HISTORICAL BUILDINGS: A CASE STUDY ENERGY REHABILITATION STUDIES OF A LARGE GROUP OF HISTORICAL BUILDINGS: A CASE STUDY A. Rego-Teixeira,, R. S. Duarte, L. Brotas, P. Almeida and M. A. Brandão, INETI - Instituto Nacional de Engenharia e

More information

Use of Microencapsulated Phase Change Materials in Building Applications

Use of Microencapsulated Phase Change Materials in Building Applications Use of Microencapsulated Phase Change Materials in Building Applications C. Castellón M. Medrano, PhD J. Roca, PhD M. Nogués, PhD A. Castell L.F. Cabeza, PhD ABSTRACT Phase Change Materials (PCMs) have

More information

Adaptive strategies for office spaces in the UK climate

Adaptive strategies for office spaces in the UK climate International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate

More information

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to: PASSIVE Solar Design Solar Homes Catch the Sun Are you planning a new house? Discover how you can apply solar architecture principles to: keep your heating bills to a minimum enjoy the comfort of a warm

More information

Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi

Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi Climate and Energy Responsive Housing in Continental Climates The Suitability of Passive Houses for Iran's Dry and Cold Climate Farshad Nasrollahi Table of Contents Abstract German Abstract Introduction

More information

New technical solutions for energy efficient buildings

New technical solutions for energy efficient buildings - New technical solutions for energy efficient buildings State of the Art Report Energy efficient building design Authors: Heimo Staller, Angelika Tisch, IFZ Oct. 2010 Background In the building sector

More information

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent

More information

Institute for Renewable Energy

Institute for Renewable Energy Institute for Renewable Energy EURAC and partners European Academy Bolzano The EURAC is an innovative institute for research and scientific training in South Tyrol. Founded in 1992 as private institution,

More information

Sistema de Etiquetagem Energética de Produtos (SEEP) Energy Labeling System for Products

Sistema de Etiquetagem Energética de Produtos (SEEP) Energy Labeling System for Products Sistema de Etiquetagem Energética de Produtos (SEEP) Energy Labeling System for Products 10 reasons for an energy labeling system (1/2) The buildings sector is responsible for a considerable share of final

More information

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA

More information

Studies energy efficiency of the renewable sources use considering climate in Latvia

Studies energy efficiency of the renewable sources use considering climate in Latvia Available online at www.sciencedirect.com ScienceDirect Energy Procedia (25) www.elsevier.com/locate/procedia 6th International Building Physics Conference, IBPC 25 Studies energy efficiency of the renewable

More information

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Kai Sirén and Ala Hasan Helsinki University of Technology, Finland Corresponding email: kai.siren@tkk.fi

More information

Life Cycle Assessment of zero- emission façade construction

Life Cycle Assessment of zero- emission façade construction Life Cycle Assessment of zero- emission façade construction Speakers: Barecka, M. 1 ; Zbiciński, I. 1 ; Heim, D. 1 1 Lodz University of Technology, Lodz, Poland Abstract: In the research of zero- emission

More information

Long-Term Hygrothermal Performance of Green Roofs

Long-Term Hygrothermal Performance of Green Roofs Long-Term Hygrothermal Performance of Green Roofs D. Zirkelbach B. Schafaczek H. Künzel, PhD Member ASHRAE ABSTRACT Green roofs are becoming more and more popular because their thermal inertia, combined

More information

Energy Efficiency in Buildings

Energy Efficiency in Buildings Energy Efficiency in Buildings Supplemental Guide to SANS 10400-XA & SANS 204 V. 3.0 Registered to: The Drawing Studio Image: digitalart / FreeDigitalPhotos.net Report Date: 26 August 2014 Practice Name:

More information

Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses

Dienstleistung. Certification as Quality Approved Passive House Criteria for Residential-Use Passive Houses Passiv Haus Institut Passivhaus Dienstleistung GmbH Dr. Wolfgang Feist Rheinstr. 44/46 Rheinstr. 44/46 D-64283 Darmstadt D-64283 Darmstadt www.passiv.de www.passivhaus-info.de Certification as "Quality

More information

Investigation into the energy consumption of a data center with a thermosyphon heat exchanger

Investigation into the energy consumption of a data center with a thermosyphon heat exchanger Article Mechanical Engineering July 2011 Vol.56 No.20: 2185 2190 doi: 10.1007/s11434-011-4500-5 SPECIAL TOPICS: Investigation into the energy consumption of a data center with a thermosyphon heat exchanger

More information

Solar Heating Basics. 2007 Page 1. a lot on the shape, colour, and texture of the surrounding

Solar Heating Basics. 2007 Page 1. a lot on the shape, colour, and texture of the surrounding 2007 Page 1 Solar Heating Basics Reflected radiation is solar energy received by collectorsfrom adjacent surfaces of the building or ground. It depends a lot on the shape, colour, and texture of the surrounding

More information

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010 EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a

More information

FACTORS AFFECTING ENERGY CONSUMPTION OF BUILDINGS

FACTORS AFFECTING ENERGY CONSUMPTION OF BUILDINGS FACTORS AFFECTING ENERGY CONSUMPTION OF BUILDINGS 1 Ralf Lindberg, Professor Minna Korpi, M.Sc. Juha Vinha, Dr.Tech. June 11, 2008 Department of Civil Engineering, Tampere University of Technology 2 BACKGROUND

More information

Building envelope and heat capacity: re-discovering the thermal mass for winter energy saving

Building envelope and heat capacity: re-discovering the thermal mass for winter energy saving 346 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and Building envelope and heat capacity: re-discovering the thermal mass for winter energy saving S. Ferrari Politecnico

More information

Crawl space heat and moisture behaviour

Crawl space heat and moisture behaviour Crawl space heat and moisture behaviour Miimu Airaksinen, Dr., Technical Research Centre of Finland, VTT miimu.airaksinen@vtt.fi, www.vtt.fi KEYWORDS: crawl space, moisture, evaporation from ground, ground

More information

Determination of Thermal Conductivity of Coarse and Fine Sand Soils

Determination of Thermal Conductivity of Coarse and Fine Sand Soils Proceedings World Geothermal Congress Bali, Indonesia, - April Determination of Thermal Conductivity of Coarse and Fine Sand Soils Indra Noer Hamdhan 1 and Barry G. Clarke 2 1 Bandung National of Institute

More information

Integrated Solar Radiant Systems

Integrated Solar Radiant Systems Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant

More information

ENERGY STATEMENT for a proposed new residential care home at Great North Road, Doncaster, South Yorkshire, DN6 7EJ

ENERGY STATEMENT for a proposed new residential care home at Great North Road, Doncaster, South Yorkshire, DN6 7EJ ENERGY STATEMENT for a proposed new residential care home at Great North Road, Doncaster, South Yorkshire, DN6 7EJ Ref. No: 12/02870/FULM Contents 1. General... 2 2. Planning Condition... 2 3. Development...

More information

ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests

ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests DesignBuilder Version 1.2.0 (incorporating EnergyPlus version 1.3.0) - June 2006 1.0 Purpose The ANSI/ASHRAE Standard 140-2004

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Energy savings in the residential area are essential in

Energy savings in the residential area are essential in Overheating and insufficient heating problems in low energy houses up to now call for improvements in future Requirements for improved energy performance have shifted major focus on energy calculations

More information

Window Thermal Performance Optimization in Governmental Emirati Housing Prototype in Abu Dhabi, UAE

Window Thermal Performance Optimization in Governmental Emirati Housing Prototype in Abu Dhabi, UAE Window Thermal Performance Optimization in Governmental Emirati Housing Prototype in Abu Dhabi, UAE Abuimara, Tareq A 1 ; Tabet Aoul, Kheira A. 1 1 Department of Architectural Engineering, United Arab

More information

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code

More information

Norwegian Tax Authority - Oslo Norway

Norwegian Tax Authority - Oslo Norway 1. INTRODUCTION Norwegian Tax Authority - Oslo Norway PROJECT SUMMARY Year of construction - 1980 No previous energy renovations SPECIAL FEATURES Main topics in the renovation are: High insulated pre fabricated

More information

COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS -

COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS - pcoolingandheating COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS - Bjarne W. Olesen, Ph.D. D. F. Liedelt "Velta" Summary Due to intensive use of

More information

SIM_ZONAL: SOFTWARE EVALUATING INDOOR TEMPERATURE DISTRIBUTIONS AND AIR MOVEMENTS FOR RAPID APPRAISALS - FIRST APPLICATION TO AN CELL.

SIM_ZONAL: SOFTWARE EVALUATING INDOOR TEMPERATURE DISTRIBUTIONS AND AIR MOVEMENTS FOR RAPID APPRAISALS - FIRST APPLICATION TO AN CELL. Seventh International IBPSA Conference Rio de Janeiro, Brazil August 13-15, 2001 SIM_ZONAL: SOFTWARE EVALUATING INDOOR TEMPERATURE DISTRIBUTIONS AND AIR MOVEMENTS FOR RAPID APPRAISALS - FIRST APPLICATION

More information

Energy Efficiency. Energy Efficient Water Heating: Purchasing a new electric water heater. Hot water use has a significant impact on your bill.

Energy Efficiency. Energy Efficient Water Heating: Purchasing a new electric water heater. Hot water use has a significant impact on your bill. Energy Efficiency Energy Efficient Water Heating: Purchasing a new electric water heater. Water heating accounts for about 18 percent of your home energy bill. Only space heating and cooling account for

More information

Achieving Net Zero. Bradley Berneche, President Alouette Homes. National Marketing Committee Canadian Home Builders Association Ottawa, June 6, 2008

Achieving Net Zero. Bradley Berneche, President Alouette Homes. National Marketing Committee Canadian Home Builders Association Ottawa, June 6, 2008 Achieving Net Zero Bradley Berneche, President Alouette Homes National Marketing Committee Canadian Home Builders Association Ottawa, June 6, 2008 Overview Who Is Alouette Homes? The EQuilibrium Initiative

More information

All Electrical School

All Electrical School All Electrical School with GS in Quebec Preliminary Results Vasile MINEA Workshop on Canadian Heat Pumps & Refrigeration Activities Montreal, May 10, 2004 Hydro-Quebec Contribution Sector: Commercial,

More information

Passive Solar Design and Concepts

Passive Solar Design and Concepts Passive Solar Design and Concepts Daylighting 1 Passive Solar Heating Good architecture? The judicious use of south glazing coupled with appropriate shading and thermal mass. Summer Winter Passive solar

More information

The Importance of Building Criteria on Cooling Energy Demand of a Low Cost Residential House: Thailand Case Study

The Importance of Building Criteria on Cooling Energy Demand of a Low Cost Residential House: Thailand Case Study The Importance of Building Criteria on Cooling Energy Demand of a Low Cost Residential House: Thailand Case Study WARAPORN RATTANONGPHISAT 1,2,*, FEDERICO M. BUTERA 2, R.S. ADHIKARI 2 AND CHALERMPORN YOOPRATETH

More information

How To Improve Energy Efficiency In Brazilian Buildings

How To Improve Energy Efficiency In Brazilian Buildings Bmeister Engenharia & Consultoria Texiglass EIFS / ETICS External Thermal Insulation Composite System INFLUENCE ON THERMAL PERFORMANCE OF BUILDINGS Eng. Giorgio Solinas Sales & Operations Director Texiglass

More information

Effects of Solar Photovoltaic Panels on Roof Heat Transfer

Effects of Solar Photovoltaic Panels on Roof Heat Transfer Effects of Solar Photovoltaic Panels on Roof Heat Transfer A. Dominguez, J. Kleissl, & M. Samady, Univ of California, San Diego J. C. Luvall, NASA, Marshall Space Flight Center Building Heating, Ventilation

More information

Module 3.7. Thermal bridging

Module 3.7. Thermal bridging Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal

More information

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX Content Heating / Ventilation / Air Conditioning 3 The Right Room Climate 4 Optimised Energy Efficiency and well-being Room

More information

Market Potential Study for Water Heater Demand Management

Market Potential Study for Water Heater Demand Management Market Potential Study for Water Heater Demand Management Rebecca Farrell Troutfetter, Frontier Associates LLC, Austin, TX INTRODUCTION Water heating represents between 13 and 17 percent of residential

More information

Energy efficient home design

Energy efficient home design Energy efficient home design GUIDELINES How an energy efficient home can help you live in comfort and save money An energy efficient home is designed to provide shade and allow cooling breezes to enter

More information

EVERYDAY ENGINEERING EXAMPLES FOR SIMPLE CONCEPTS

EVERYDAY ENGINEERING EXAMPLES FOR SIMPLE CONCEPTS EVERYDAY ENGINEERING EXAMPLES FOR SIMPLE CONCEPTS Thermal Properties ENGR 3350 - Materials Science Dr. Nedim Vardar Copyright 2015 Thermal Properties of Materials Engage: MSEIP Engineering Everyday Engineering

More information

DETERMINATION OF THE HEAT STORAGE CAPACITY OF PCM AND PCM-OBJECTS AS A FUNCTION OF TEMPERATURE. E. Günther, S. Hiebler, H. Mehling

DETERMINATION OF THE HEAT STORAGE CAPACITY OF PCM AND PCM-OBJECTS AS A FUNCTION OF TEMPERATURE. E. Günther, S. Hiebler, H. Mehling DETERMINATION OF THE HEAT STORAGE CAPACITY OF PCM AND PCM-OBJECTS AS A FUNCTION OF TEMPERATURE E. Günther, S. Hiebler, H. Mehling Bavarian Center for Applied Energy Research (ZAE Bayern) Walther-Meißner-Str.

More information

Significance of Glazing Thermal Conductivity for MAC Indirect Emissions and EV Battery Performance

Significance of Glazing Thermal Conductivity for MAC Indirect Emissions and EV Battery Performance Significance of Glazing Thermal Conductivity for MAC Indirect Emissions and EV Battery Performance Steve Gasworth and Triloka Tankala SABIC Innovative Plastics sgasworth@exatec.biz steven.gasworth@sabic.com

More information

Solar Aquaponics Designing a 100% Solar Aquaponics Greenhouse

Solar Aquaponics Designing a 100% Solar Aquaponics Greenhouse Solar Aquaponics Designing a 100% Solar Aquaponics Greenhouse Dan Chiras, Ph.D. Director, The Evergreen Institute Gerald, MO 63037 www.evergreeninstitute.org Topics Creating a 100% solar operation Efficiency

More information

Delivering on innovation and market uptake. Best-in-cases of nzeb. Ramon Pascual Bucharest May 8th, 2015

Delivering on innovation and market uptake. Best-in-cases of nzeb. Ramon Pascual Bucharest May 8th, 2015 www.zebra2020.eu Delivering on innovation and market uptake. Best-in-cases of nzeb Ramon Pascual Bucharest May 8th, 2015 Outline nzeb Database Best in cases of nzeb Climates in Europe Preliminary results

More information

Efficient use of energy simulation in the early design phase

Efficient use of energy simulation in the early design phase The higher offices are not sufficiently cooled the first level offices are correctly cooled 600 W/m2 at 11h00 SOUTH facade Architectural and climatic control systems choices Efficient use of energy simulation

More information

Condensing Boiler Efficiency

Condensing Boiler Efficiency Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2

More information

Floor systems - key elements for sustainable multi-storey buildings

Floor systems - key elements for sustainable multi-storey buildings Floor systems - key elements for sustainable multi-storey buildings Döring, B., AAINA GmbH, Institute for sustainable construction Aachen, Germany (Presenting), bdo@aaina.eu; Kuhnhenne, M., RWTH Aachen,

More information

Calculating Total Cooling Requirements for Data Centers

Calculating Total Cooling Requirements for Data Centers Calculating Total Cooling Requirements for Data Centers By Neil Rasmussen White Paper #25 Revision 2 Executive Summary This document describes how to estimate heat output from Information Technology equipment

More information

Parametric Analysis of School Classroom Typologies' Energy Performance

Parametric Analysis of School Classroom Typologies' Energy Performance PLEA2013-29th Conference, Sustainable Architecture for a Renewable Future, Munich, Germany 10-12 September 2013 Parametric Analysis of School Classroom Typologies' Energy Performance MAUREEN TREBILCOCK

More information

HEAT TRANSFER ANALYSIS OF COLD STORAGE

HEAT TRANSFER ANALYSIS OF COLD STORAGE HEAT TRANSFER ANALYSIS OF COLD STORAGE Upamanyu Bangale and Samir Deshmukh Department of Mechanical Engineering, SGBA University, Amravati, India ABSTRACT India is largest producer of fruit and vegetable

More information

How To Calculate Total Cooling Requirements For Data Center

How To Calculate Total Cooling Requirements For Data Center Calculating Total Cooling Requirements for Data Centers White Paper 25 Revision 3 by Neil Rasmussen > Executive summary This document describes how to estimate heat output from information technology (IT)

More information

Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs

Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs Paul Yeaman, V I Chip Inc. Presented at the Darnell Digital Power Forum September 2007 Abstract An increasing focus on datacenter

More information

IES <Virtual Environment> Tutorial. Apache Sim (Version 6.0)

IES <Virtual Environment> Tutorial. Apache Sim (Version 6.0) IES Tutorial Apache Sim (Version 6.0) Introduction This tutorial will begin by showing you how to use the Building Template Manager (BTM) to create thermal and construction data for

More information

Windows and glazed area technologies and materials in Europe. Bertrand Cazes

Windows and glazed area technologies and materials in Europe. Bertrand Cazes Windows and glazed area technologies and materials in Europe Bertrand Cazes IEA - Building Envelope Technologies and Policies Workshop 17 Nov 2011 About Glass for Europe 4 member companies and 1associate:

More information

SIMULATION OF RADIANT COOLING PERFORMANCE WITH

SIMULATION OF RADIANT COOLING PERFORMANCE WITH SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE

More information

Small Data / Telecommunications Room on Slab Floor

Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure

More information

Building HVAC Load Profiling Using EnergyPlus

Building HVAC Load Profiling Using EnergyPlus Building HVAC Load Profiling Using EnergyPlus Dong Wang School of EEE Nanyang Technological University Singapore Email: wang0807@e.ntu.edu.sg Abhisek Ukil, Senior Member, IEEE School of EEE Nanyang Technological

More information

RESSÒ: energy efficiency urban rehabilitation

RESSÒ: energy efficiency urban rehabilitation RESSÒ: energy efficiency urban rehabilitation Authors: Bodelon, Carmen 1 ; Gascón, Eduardo 1 ; Ramon, Guillem 1 ; Obiols, Martí 1 ; Palomar, Pablo 1 ; Escoda, Quim 1 ; Prat, Sandra 1 ; Illa, Sergi 1 ;

More information

Challenging the possibilities

Challenging the possibilities Passivhus Norden 2013 Challenging the possibilities Olav Langenkamp, Architect ETH-MAA, Langenkamp.dk Architects, Tigervej 26 8400 Ebeltoft Denmark, ol@langenkamp.dk Martin Wikkelsø Brandt, Cand. Polyt.

More information

University of Rome La Sapienza Dipartimento di Ingegneria dell Informazione, Elettronica e Telecomunicazioni

University of Rome La Sapienza Dipartimento di Ingegneria dell Informazione, Elettronica e Telecomunicazioni Presented at the COMSOL Conference 2010 Paris University of Rome La Sapienza Paolo Fallavollita Salvatore Esposito Marco Balsi Department of Information Engineering, Electronics and Telecommunications

More information

RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary

RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary January 2013 TABLE OF CONTENTS INTRODUCTION... 3 GENERAL RECOMMENDATIONS... 3 Communication with customers in the field of environmental sustainability...

More information

Protocol for the Certification of Energy Simulation Software: First edition, December 2009

Protocol for the Certification of Energy Simulation Software: First edition, December 2009 Copyright Agrément South Africa, December 2009 The master copy of this document appears on the website: http://www.agrement.co.za Protocol for the Certification of Energy Simulation Software: First edition,

More information

The First Law of Thermodynamics

The First Law of Thermodynamics The First aw of Thermodynamics Q and W are process (path)-dependent. (Q W) = E int is independent of the process. E int = E int,f E int,i = Q W (first law) Q: + heat into the system; heat lost from the

More information

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation

More information

Cryosol. Ready to use cold storage fluid. Rue Henri Moissan 69310 PIERRE BENITE Tel +33 (0)4 78 50 20 05 info@kaplan-energy.com

Cryosol. Ready to use cold storage fluid. Rue Henri Moissan 69310 PIERRE BENITE Tel +33 (0)4 78 50 20 05 info@kaplan-energy.com Cryosol Ready to use cold storage fluid Rue Henri Moissan 69310 PIERRE BENITE Tel +33 (0)4 78 50 20 05 info@kaplan-energy.com Yann KAPLAN /// CRYOSOL /// PAGE 1 /// Décembre 2013 Kaplan Energy SAS KAPLAN

More information

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls PCA R&D Serial No. 415 Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls by John Gajda and Martha VanGeem 000 Portland Cement Association KEYWORDS Concrete,

More information

Exemplary Retrofitting of an Old School in Stuttgart - EROS -

Exemplary Retrofitting of an Old School in Stuttgart - EROS - Exemplary Retrofitting of an Old School in Stuttgart - EROS - City of Stuttgart, Summary The objective of the project was to demonstrate the potentials of a retrofitting process for a typical school in

More information

Holistic Approach in Delivering Government Buildings The Low Carbon Concept

Holistic Approach in Delivering Government Buildings The Low Carbon Concept International Conference on Planning for Low Carbon Cities 22 May 2009 Holistic Approach in Delivering Government Buildings The Low Carbon Concept Ir. HO Sai-king, Assistant Director (Building Services),

More information

SOLAR ENERGY How much strikes the earth? How much can my building get? When is it too much?

SOLAR ENERGY How much strikes the earth? How much can my building get? When is it too much? SOLAR ENERGY How much strikes the earth? How much can my building get? When is it too much? The sun: friend of foe? Drawing by Le Corbusier ENGS 44 Sustainable Design Benoit Cushman-Roisin 14 April 2015

More information

The Influence of Insulation Styles on the Air Conditioning Load of Japanese Multi- Family Residences

The Influence of Insulation Styles on the Air Conditioning Load of Japanese Multi- Family Residences The Influence of Insulation Styles on the Air Conditioning Load of Japanese Multi- Family Residences Yupeng Wang 1, and Hiroatsu Fukuda 2 1 Department of BCEE, Concordia University, Canada, Email: wangyupeng0628@gmail.com

More information

Protocol for the Certification of Energy Simulation Software: Second edition, September 2011

Protocol for the Certification of Energy Simulation Software: Second edition, September 2011 Copyright Agrément South Africa, September 2011 The master copy of this document appears on the website: http://www.agrement.co.za SANS 10400: The application of the National Building Regulations: Protocol

More information

The Sino-Italy Environment & Energy Building (SIEEB): A model for a new generation of sustainable buildings

The Sino-Italy Environment & Energy Building (SIEEB): A model for a new generation of sustainable buildings International Conference Passive and Low Energy Cooling 935 for the Built Environment, May 25, Santorini, Greece The Sino-Italy Environment & Energy Building (SIEEB): A model for a new generation of sustainable

More information

Micronal PCM. Intelligent Temperature Management for Buildings. A broader base for your success. www.micronal.de

Micronal PCM. Intelligent Temperature Management for Buildings. A broader base for your success. www.micronal.de A broader base for your success Polymer Dispersions for: Construction Architectural Coatings Adhesives Fiber Bonding Micronal PCM Intelligent Temperature Management for Buildings www.micronal.de 2 Micronal

More information

ENERGY BALANCE OF LOW ENERGY HOUSE WITH GHPS IN HOKKAIDO

ENERGY BALANCE OF LOW ENERGY HOUSE WITH GHPS IN HOKKAIDO ENERGY BALANCE OF LOW ENERGY HOUSE WITH GHPS IN HOKKAIDO Yasuhiro Hamada, Kiyoshi Ochifuji, Makoto Nakamura and Katsunori Nagano Division of Urban and Environmental Engineering Graduate School of Engineering,

More information

Introduction. 1. Heat Transfer. In Townsville s climate it is essential to choose building materials that perform well in our local conditions.

Introduction. 1. Heat Transfer. In Townsville s climate it is essential to choose building materials that perform well in our local conditions. In Townsville s climate it is essential to choose building materials that perform well in our local conditions. Choosing the correct materials and insulation will improve the overall thermal performance

More information

A global list. The Fortification Depot A CO 2 -reduction project

A global list. The Fortification Depot A CO 2 -reduction project The Fortification Depot A CO 2 -reduction project A global list Passive measures: Windows, glazing, solar shading Insulation of walls, roofs, floors Improving air tightness 1 A global list Technical measures:

More information

Low temperature solar assisted (heating) system based on slurry PCM

Low temperature solar assisted (heating) system based on slurry PCM ANNEX 59 - High emperature Cooling & Low emperature Heating in Buildings Riqualificazione di edifici esistenti con elevati standard energetici: metodi e tecnologie ENEA - Via G. Romano 41, 00196 Roma -

More information

Energy-Plus Primary School, Hohen Neuendorf, Germany

Energy-Plus Primary School, Hohen Neuendorf, Germany Energy-Plus Primary School, Hohen Neuendorf, Germany Ingo LÜTKEMEYER, Prof. Dipl.-Ing. Architekt BDA 1 Jens KRAUSE, Dipl. Ing. 2 Günter LÖHNERT, Dr. Ing. 3 Holger KÖNIG, Dipl.-Ing. 4 Detlef HENNINGS, Dr.

More information

Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE

Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE TECHNICAL FEATURE Fundamentals at Work This article was published in ASHRAE Journal, February 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically

More information

SELECTIVE GLAZING FOR SUN CONTROL

SELECTIVE GLAZING FOR SUN CONTROL SUN CONTROL GLAZING SELECTIVE GLAZING FOR SUN CONTROL Sun Factor 1st level performance for direct solar energy Solar energy control Solar control coating Only if the glass is exposed to sun rays! 2nd level

More information

Kerkstoel Activ Floors for concrete core activation

Kerkstoel Activ Floors for concrete core activation Kerkstoel Activ Floors for concrete core activation Built on experience, driven by innovation Concrete core activation: rational, economical and sustainable Building with concrete core activation is building

More information

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing

More information

Technical Series 05-100

Technical Series 05-100 research highlight June 2005 Technical Series 05-100 introduction House temperatures are typically set by the occupants to ensure their personal comfort. When occupants are not at home, or are asleep,

More information

The calculus and simulation of underfloor heating systems

The calculus and simulation of underfloor heating systems The calculus and simulation of underfloor heating systems DORIN CRISTIAN NĂSTAC*, IOAN CĂLDARE**, IOAN GIURCA***, CORNEL MUNTEA*** * Building Services Engineering Department, Transilvania University of

More information

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,

More information

PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING

PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING LI CHUNYING DOCTOR OF PHILOSOPHY CITY UNIVERSITY OF HONG KONG FEBRUARY 2012 CITY UNIVERSITY OF HONG KONG 香 港 城 市 大 學 Performance Evaluation of Water-flow

More information