Saving Heating Costs In Warehouses

Size: px
Start display at page:

Download "Saving Heating Costs In Warehouses"

Transcription

1 2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 12, December 2005). This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. Saving Heating Costs In Warehouses By Richard Aynsley, Ph.D., Member ASHRAE T he cost of fuels used for heating large shipping and receiving Twarehouses has increased dramatically. This increase has stimu- lated interest in destratifi cation as a means to improving heating method ignores the influence of infiltration, ventilation or other sources of heat within the space, such as lighting, people and machinery. More complex methods attempt to account for these influences. Heat losses due to ventilation and infiltration can amount to 20% to 50% of the total heat loss from a building. 1 Not accounting for this heat loss due to ventilation in estimating energy savings from destratification can lead to significant errors. What is needed is a relatively simple method that can produce estimates within 10% of measured values using readily available data. The purchase cost and operating cost of fans used to destratify the air also is needed to assess the cost benefit of installing and operating the fans. energy effi ciency. The simplest methods for estimating winter energy savings from destratification in shipping and receiving warehouses focus on the difference in air temperature between floor level and underside of the roof. They assume that after destratification the air temperature is uniform within the space. The estimate of energy savings is the difference between heat lost through the roof at the two temperature differences before and after destratification. This Simplified Estimation of Destratification Savings An example of the most commonly used method for estimating energy savings from destratification follows. Gas consumed by the forced-air gas furnaces during an 89-day period from February through April 2003 was 19,542 About the Author Richard Aynsley, Ph.D., is director of research and development at Big Ass Fan Company, Lexington, Ky. 4 6 A S H R A E J o u r n a l a s h r a e. o r g D e c e m b e r

2 dekatherm. During these 89 days, the heating degree days were 2,220 over a base of 65 F (18 C), and the average outdoor air temperature was 41 F (5 C). The indoor thermostat temperature was maintained at 65 F (18 C). Before destratification the air temperature at the underside of the roof deck 29.5 ft (9 m) above floor level was 89 F (32 C). The roof is estimated to have an average heat transfer coefficient of 0.13 Btu/h ft 2 F (0.74 W/(m 2 K)). The temperature difference before destratification, t t bd, is the difference between the underside of the roof deck, measured on-site, and the average outdoor heating season temperature from climatic records for the location. For the example, this is (89 41) or 48 F (9 C). The temperature difference after destratification, t t ad, is the estimated difference between the underside of the roof deck, taken as the average of air temperatures at floor and roof deck, and the average outdoor heating season temperature from climatic records for the location. For the example, this difference is (( )/2) 41 or 36 F (2 C). The heat lost through the roof before destratification,, is calculated using Equation 1. = (1) = , = 361,920 Btu/h Heat loss through the roof before destratification U = Average heat transfer coefficient for the roof (Btu/h ft 2 F) A = Area of roof (ft 2 ) t i o = Temperature difference through roof before destratification ( F) The heat lost through the roof after destratification, q ad, is calculated with Equation 2. = = , = 271,440 Btu/h (2) Heat loss through the roof before destratification U = Average heat transfer coefficient for the roof (Btu/h ft 2 F) A = Area of roof (ft 2 ) t t ad = Temperature difference through roof after destrattification ( F) The seasonal gas fuel saved, FS, due to destratification is calculated using Equation 3. FS (3) = 2136 (361, ,440)/(100, ) = 2761 dekatherm = Seasonal gas fuel saved due to destratification in dekatherm hrs hs = Heating season hours for the location Q g = Caloric value for natural gas fuel, typically 100,000 Btu/dekatherm η = The efficiency of the gas furnace, typically 0.7 This gas fuel saved can be expressed as a percentage of the gas used before destratification or 100 2,761/19,542 = 14.1%. This method does not account for heat losses due to ventilation, or infiltration through the building envelope, or indoor heat gains from lighting, people and machinery. For large, single-story buildings such as shipping and receiving warehouses, the roof surface typically offers the largest surface for heat loss. While the heat loss by conduction through the walls is relatively constant, the heat transfer by conduction through the roof can vary significantly. In winter, this is due mainly to the insulating effects of accumulated snow, wind, and radiant heat exchange with the sky. It is often difficult to assign a value for the thermal conductivity for envelope elements in existing buildings used in this method. Detailed construction drawings or specifications are rarely available, and often do not represent how the building was actually built. In any case, roof insulation often varies in thickness to provide a slope for rainwater drainage to outlets. Older insulation can be compromised by absorption of moisture, or by compaction of insulation over time. A Better Approach to Estimating Destratification Savings A better way exists to estimate winter heating savings due to destratification. Occupants of existing buildings usually have well-documented data on the amount of gas used during a heating season from their utility company invoices. These invoices also often have the degree days of heating associated with each billing period. If heating degree data is not provided on invoices, it can be obtained from local climate records along with the average outdoor air temperature during a particular period of time. These data can be used to calculate the overall rate of heat loss through the building envelope over a given period. Pignet and Saxena 2 recommend: Btu/h F (4) U = Seasonal gas fuel saved due to destratification in dekatherm A = Heating season hours for the location = Caloric value for natural gas fuel, typically 100,000 Btu/dekatherm t i = Average indoor air temperature ( F) t o = Average outdoor air temperature ( F) The amount of heat released inside the building from sources other than the furnaces, such as lighting, people and machinery, can be estimated as indicated earlier. This is important because, during the warmer winter months, if the thermostat setting is maintained, heat from sources other than the furnaces will provide a larger proportion of the heating to the building. The amount of heat released by various types of lighting D e c e m b e r A S H R A E J o u r n a l 4 7

3 fixtures, appliances and occupants can be calculated from data in Chapter 29 of the 2001 ASHRAE Handbook Fundamentals. 3 Heat from sources other than the furnaces, such as lighting, machinery and people, in the example warehouse during the sample heating season, is about 3.2 Btu/hr ft 2 (10 W/m 2 ). For a 24- hour, three-shift operation during the sample heating season of 89 days, the heat released is 396,441,600 Btu ( kj). From Equation 4: UA = (1,367,940, ,441,600) / ( ) = 49,010,600 Btu/h F The reduced heat load, q ad, due to destratification is calculated using Equation 5. q ad = (UA) (t ibd t iad ) (5) = 49,010,600 (77 65) = 588,127,200 Btu/h q ad = Reduced heat load after destratification UA = Lumped time-averaged heat loss rate for the building envelope (Btu/h F) t ibd = average indoor air temperature before destratification ( F) t iad = Average indoor air temperature after destratification (thermostat F) This is converted to the equivalent quantity of gas G q (dekatherm), by dividing by the caloric value of the gas per dekatherm and the heating system efficiency (0.7). G q Q g G = Equivalent quantity of gas Q = Caloric value for gas Roof/Ceiling η = Efficiency of the heating appliance Expressing this as a percentage of the gas used before destratification, or 100 8,402/19,542 = 43% Estimating Average Indoor Air Temperature A critical factor in destratification is the mixing of indoor air to an even temperature. When this is done, the difference between the temperature of air near floor level and at the underside of the roof deck is usually no more than 1 F (0.6 C). Before destratification, the difference between the temperature of air near floor level and at the underside of the roof deck can be up to 30 F (17 C). Most simple methods for estimating winter energy savings from destratification use a linear profile for air temperature with height above floor level. In reality the air temperature profile often is not linear. The vertical profile of air temperature inside a space is strongly influenced by the distribution and height of heat sources in the building. Most U.S. shipping and receiving warehouses use a number of natural gas-fired forced air furnaces mounted about 20 ft (6 Outlet (6) Height (H) H Floor m) above floor level. On-site measurements were made of the air temperatures in a 33 ft (10 m) high shipping and receiving warehouse with two forced air gas furnaces. These measurements indicated that air temperature was constant to at least 5 ft (1.5 m) below the roof deck (Figure 1 ). 4 shows various temperature profiles for heated spaces. On-site measurements suggest that the vertical profile of air temperature was similar to a D profile. Average indoor air temperature in a space with a D-type vertical profile of air temperature, after thorough mixing, can be estimated by taking the average of two temperature-weighted volumes of the indoor vertical profile of temperature above and below the horizontal part of the profile that aligns with the height of the furnaces above the floor. Whenever possible, it is advisable to measure the vertical profile of air temperature on-site. A New Method for Estimating Destratification Savings In a departure from the method suggested by Pignet and Saxena, 2 the writer suggests that averages of indoor air temperature, t iad, after thorough mixing should reflect the characteristics of the vertical profile of indoor air temperature. In the case study with forced air furnaces well below the underside of roof, this can be done by using Equation 7, to account approximately for the D type vertical profile of air temperature. = ((89 58, ) + (65 58,000 22))/ ( 58,000 ( )) = F 4 8 A S H R A E J o u r n a l a s h r a e. o r g D e c e m b e r H h H o Increasing Air Temperature E A: Heat supplied evenly and close to fl oor level. B: Heat supplied evenly in the space and air is well mixed. C: Heat is supplied evenly in the room with little air mixing. D: Heat is supplied from ceiling or upper part of walls with little air mixing. E: Heat is from a concentrated source in the upper part of the space with little air mixing after. 4 H is the ceiling height H h is the height of heater H o is the height of ventilation outlet Figure 1: Characteristic vertical profiles of indoor air temperature determined by location of warm air supply and mixing. 4 C B A D (7)

4 Month Gas Used in 2003 Gas Used in 2004 HDD in 2003 HDD in 2004 Before Destratification After Destratification Heating Season Heating Season (Dekatherm) (Dekatherm) February 10,358 6,259 1, March 5,798 4, April 3,386 2, Totals 19,542 12,702 2,220 1,960 Average 6,514 4, Table 1: Gas used and heating degree days at the facility. t iad = Average indoor air temperature (after mixing) F t ah = Air temperature above heaters ( F) A fl = Floor area of facility (ft 2 ) H ah = Height above heaters to roof (ft) t ts = Thermostat temperature setting ( F) H bh = Height below heaters to the floor (ft) The average seasonal rate of heat loss, UA, through the building envelope in Btu/ F before destratification can be calculated using Equation 4 t o, is the average outdoor air temperature for the sample heating season. The heat provided by the furnace during the sample heating season is 19,542 dekatherm times the caloric value of natural gas, 100,000 Btu/dekatherm, times the efficiency of the furnace This equals 1,367,940,000 Btu ( kj). Heat in Btu from other sources in the warehouse during the sample heating season is the heat release rate 3.18 Btu/h ft 2 (10 W/m 2 ), times the number of days in the sample heating season 89 converted to hours, times the floor area of the warehouse, 58,000 ft 2 (5388 m 2 ). This equals 393,963,840 Btu ( kj). Using Equation 4: UA = 1,367,940, ,963,840 / = 57,409,705 Btu/h F The reduced heat load, q ad, due to destratification is calculated using Equation 5. This is converted to the equivalent quantity of gas, EQG (dekatherm), by dividing by the caloric value of the gas per dekatherm and the heating system efficiency (0.7) using Equation 6. Expressing this gas fuel as a percentage of the gas used before destratification: 100 5,487/19,542 = 28%. The estimated savings over this sample heating season are 5,487 $0.8 = $4,390. The sample heating season used of 2,220 heating degree days (HDD) to a 65 F (18 C) base cannot be representative of longer term heating seasons for the local climate. An estimate can be made of the savings over a typical heating season, based on 30-year climatic data by expressing the heating demand for a heating season in terms of dekatherm/hdd. In this case the 30-year ASHRAE design season for the location is 4,871 HDD to a 65 F (18 C) base. These data are indicated for cities in the United States in the 1981 ASHRAE Handbook Fundamentals. Estimated savings for the ASHRAE heating season based on 30-year data are $4,390 4,871/2,220 = $9,632. Comparison of Estimated Energy Savings with Measured Savings The data used in the two estimates detailed earlier relate to a 58,000 ft 2 (5388 m 2 ) shipping and receiving warehouse in Middletown, N.Y. The owners of this facility collaborated in a study to evaluate the cost savings of destratification in winter. Gas consumption by the heaters along with heating degreedays (base 65 F [18 C]) were recorded for February, March, and April in 2003 before destratification fans were installed. Similar measurements were made during the same months in 2004 after destratification fans were installed. These data are shown in Table 1. The other facility-related data used here were provided by the facility owners. Given that each winter is unique, direct comparisons cannot be made. To overcome this, one can compare the quantity of fuel required to provide the same indoor condition divided by the severity of the winter season in heating degree days. In this case, for 2003, before destratification, this equals 19,542/2,220 = 8.8 dekatherm/ HDD. In 2004 after destratification, this equals 12,702/1,960 = 6.48 dekatherm/hdd. This represents a 26.4% reduction in gas used. The first method for estimating winter energy savings from destratification gave a savings of 14.1%. This was 46.6% less than actually measured in the case study. The second method by Pignet and Saxena, 2 gave a savings of 43%. This was 62.9% more than actually measured in the case study. The third method by Pignet and Saxena, 2 modified to better account for the vertical profile of indoor air temperature for gas furnaces mount on the walls gave a savings of 28%. This was 6.1% more than the measured value. This is within 10% of the measured value, a criteria often taken as acceptable for engineering estimates of this type given the limitations of the broad assumptions used. Cost of Operating Large Ceiling Fans for Destratification Energy-efficient, large, low-speed ceiling fans can be purchased principally for destratification in winter. A 58,000 ft 2 (5388 m 2 ) shipping and receiving warehouse would typically have five 24 ft (7.3 m) diameter fans operating quietly and continuously at approximately 20 rpm. Velocity at head-height 5 0 A S H R A E J o u r n a l a s h r a e. o r g D e c e m b e r

5 above the floor should be kept below 50 fpm (0.25 m/s) to avoid drafts. Cost of purchase and installation of the five large industrial ceiling fans would be approximately $30,500. At 20 rpm, each fan would use 0.1 kw of power. During the 89-day period of this study these fans would use or 1,068 kwh of electricity, costing approximately $0.06 per kwh, or $ Conclusions Three methods for estimating the winter energy savings from destratification were compared with field data for a three-month sample heating season. The first method was extremely simple but underestimated the actual savings by 46.6%. The second, more detailed engineering approach was developed by Pignet and Saxena. 2 This method failed to account for the vertical profile of indoor air temperature developed when gas furnaces are mounted high on the walls. This method overestimated the energy savings by 62.9%. The third method was the Pignet and Saxena 2 method, modified by the writer to account for vertical profiles of indoor air temperature. This method overestimated savings by 6.1%, but met the criteria of being within 10% of actual measured value. The benefit of the Pignet and Saxena 2 method is that it computes a lumped heat transfer coefficient for the building from seasonal heat loss based on heating energy used. This avoids difficulties in measuring, or otherwise determining, the heat transfer coefficient for the building envelope and other losses due to infiltration and ventilation. The modification suggested by the author to the Pignet and Saxena 2 method, better accounts for the influence of the type of vertical profile of indoor air temperature on the average indoor air temperature. Winter conditions vary from year to year. This complicates year to year comparisons of the efficiency of heating energy use. To overcome this difficulty, it is suggested that comparisons be made on the basis of fuel used per heating degree day when comparing fuel used over different heating seasons. References ASHRAE Handbook Fundamentals, Chapter 26, p Pignet, T. and U. Saxena Estimation of energy savings due to destratification of air in plants. Energy Engineering 99(1): ASHRAE Handbook Fundamentals, Chapter Andersen, K.T Design of natural ventilation by thermal buoyancy with temperature stratification. Proceedings of 6 th International Conference on Air Distribution in Rooms, ROOMVENT 98, 2: Advertisement formerly in this space. D e c e m b e r A S H R A E J o u r n a l 5 1

2006 Delta T Corporation dba Big Ass Fan Company

2006 Delta T Corporation dba Big Ass Fan Company Saving Energy Savings with HVLS Fans Josh Eddy LEED-AP National Sales Manager Big Ass Fans Outline Who is Big Ass Fans HVLS fan types How HVLS fans save energy HVLS fan applications How utilities are helping

More information

Residential HVAC System Sizing

Residential HVAC System Sizing Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: goss@acad.umass.edu SUMMARY Heating, ventilating and air-conditioning (HVAC)

More information

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE P (5, EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE Ronald H. Howell, Professor Luis Rosario, Graduate Student Antonio Bula, Graduate Student Department of Mechanical Engineering

More information

Certified Residential Energy Auditor (REA) Study Guide

Certified Residential Energy Auditor (REA) Study Guide Certified Residential Energy Auditor (REA) Study Guide This guide provides an overview of the Certified Residential Energy Auditor (REA) Program, including how to register for the REA Training Seminar

More information

Circulator Fan Performance Testing Standards BY CHRISTIAN TABER, BEMP, HBDP, MEMBER ASHRAE

Circulator Fan Performance Testing Standards BY CHRISTIAN TABER, BEMP, HBDP, MEMBER ASHRAE This article was published in ASHRAE Journal, September 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without

More information

White paper on the comparative energy efficiency of zoned electric heaters Convectair, Inc. / Convectair-NMT Inc. September 2004

White paper on the comparative energy efficiency of zoned electric heaters Convectair, Inc. / Convectair-NMT Inc. September 2004 White paper on the comparative energy efficiency of zoned electric heaters Convectair, Inc. / Convectair-NMT Inc. September 2004 Contents : 1. Introduction 2. Fundamentals of heating 3. Temperature distribution

More information

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial facilities commonly occupy spaces with ceilings ranging between twenty and thirty feet in height.

More information

Case Studies: Infrared Heating in Industrial Applications

Case Studies: Infrared Heating in Industrial Applications Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

Preventing Ice Dams on Roofs

Preventing Ice Dams on Roofs Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the

More information

UDSA - UDSBD unit heater

UDSA - UDSBD unit heater APPLICATIONS Heating >> FACTORIES >> WAREHOUSES >> HALLS >> SHOWROOMS >> GREENHOUSES >> RETAIL >>... UDSA - UDSBD unit heater www.reznor.eu V3 gas fired unit heater Reznor V3 unit heaters are one of the

More information

Energy Efficiency. Energy Efficient Home Cooling:

Energy Efficiency. Energy Efficient Home Cooling: Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling

More information

Simulations of Sizing and Comfort Improvements for Residential Forced-Air Heating and Cooling Systems

Simulations of Sizing and Comfort Improvements for Residential Forced-Air Heating and Cooling Systems Simulations of Sizing and Comfort Improvements for Residential Forced-Air Heating and Cooling Systems May 2002 Walker, I., Degenetais, G. and Siegel, J. Energy Performance of Buildings Group Lawrence Berkeley

More information

Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE

Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE TECHNICAL FEATURE Fundamentals at Work This article was published in ASHRAE Journal, February 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

Thermal destratification in buildings: The missing piece to the HVAC puzzle

Thermal destratification in buildings: The missing piece to the HVAC puzzle WHITE PAPER Thermal destratification in buildings: The missing piece to the HVAC puzzle January 2013 Thermal Destratification In Buildings: The missing piece to the HVAC puzzle 1. What is Thermal Destratification

More information

Understanding Heating Seasonal Performance Factors for Heat Pumps

Understanding Heating Seasonal Performance Factors for Heat Pumps Understanding Heating Seasonal Performance Factors for Heat Pumps Paul W. Francisco, University of Illinois, Building Research Council Larry Palmiter and David Baylon, Ecotope, Inc. ABSTRACT The heating

More information

THERMAL LOSSES Thermal Losses Calculations

THERMAL LOSSES Thermal Losses Calculations Calculations -1- THERMAL LOSSES Thermal Losses Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example Peak

More information

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls PCA R&D Serial No. 415 Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls by John Gajda and Martha VanGeem 000 Portland Cement Association KEYWORDS Concrete,

More information

White Paper Nest Learning Thermostat Efficiency Simulation for France. Nest Labs September 2014

White Paper Nest Learning Thermostat Efficiency Simulation for France. Nest Labs September 2014 White Paper Nest Learning Thermostat Efficiency Simulation for France Nest Labs September 2014 Introduction This white paper gives an overview of potential energy savings using the Nest Learning Thermostat

More information

HVAC Code Requirements

HVAC Code Requirements one and two family dwellings? Answer: SECTION 2001: GENERAL 2001.1 Air supply. Fuel-burning equipment shall be provided with a supply of air for fuel combustion, draft hood dilution and ventilation of

More information

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing

More information

AIRCONDITIONING Cooling Loads Calculations

AIRCONDITIONING Cooling Loads Calculations Calculations -1- AIRCONDITIONING Cooling s Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example (p. 18.37)

More information

FACTSHEET Assessing the Feasibility of Using Solar-Thermal Systems for Your Agricultural or Agri-Food Operation

FACTSHEET Assessing the Feasibility of Using Solar-Thermal Systems for Your Agricultural or Agri-Food Operation FACTSHEET Assessing the Feasibility of Using Solar-Thermal Systems for Your Agricultural or Agri-Food Operation Solar-thermal systems collect the sun's energy and convert it into heat. This energy can

More information

Improving thermal insulation of concrete sandwich panel buildings

Improving thermal insulation of concrete sandwich panel buildings Improving thermal insulation of concrete sandwich panel buildings Jørgen Munch-Andersen Danish Building Research Institute, Aalborg University LCUBE conference, Vienna 17-18 April 2007 Outline A general

More information

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Kai Sirén and Ala Hasan Helsinki University of Technology, Finland Corresponding email: kai.siren@tkk.fi

More information

HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.

HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. AFFORDABLE SOLUTIONS FROM AMERISTAR. We know that heating and cooling systems can be a major investment for homeowners. Our goal is

More information

Ceiling Fans. 1 Introduction. V entilation I nformation P aper n 13

Ceiling Fans. 1 Introduction. V entilation I nformation P aper n 13 V entilation I nformation P aper n 13 October 2007 INIVE EEIG Operating Agent and Management Boulevard Poincaré 79 B-1060 Brussels Belgium inive@bbri.be - www.inive.org International Energy Agency Energy

More information

Software Development for Cooling Load Estimation by CLTD Method

Software Development for Cooling Load Estimation by CLTD Method IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department

More information

By Donald Fisher, P.Eng., Associate Member ASHRAE

By Donald Fisher, P.Eng., Associate Member ASHRAE By Donald Fisher, P.Eng., Associate Member ASHRAE Decisions to purchase a commercial kitchen ventilation (CKV) system often are based on rule-of-thumb estimates using a $/cfm index (i.e., annual energy

More information

Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump

Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump s.doty 10-2014 White Paper #30 Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump System Switches Fuels Automatically for Economy. What is an Air-Source Heat Pump? A heat pump is a modified air conditioning

More information

When considering your heating options, keep in mind that 60% of your energy. costs are attributed to space heating. You

When considering your heating options, keep in mind that 60% of your energy. costs are attributed to space heating. You Heating Options Furnaces & Boilers September 2005 CONSUMERS GUIDE - TO HOME HEATING OPTIONS CONTENTS Heat Distribution Energy Source Boilers Proper Sizing Energy Efficiency - Standards - Rating System

More information

Energy Depot for Business Energy Audit Question Set

Energy Depot for Business Energy Audit Question Set This questionnaire matches the one you can use to perform an online energy audit of your business. You complete the online questionnaire, or if you prefer, you can print this form and answer the questions

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Field Demonstration of High-Efficiency Gas Heaters

Field Demonstration of High-Efficiency Gas Heaters October 2014 Field Demonstration of High-Efficiency Gas Heaters Prepared for Better Buildings Alliance Building Technologies Office Office of Energy Efficiency and Renewable Energy U.S. Department of Energy

More information

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,

More information

National Building Code of Canada 2010

National Building Code of Canada 2010 National Building Code of Canada 2010 Emergency Change Issued by the Canadian Commission on Building and Fire Codes The table that follows lists two emergency changes that apply to the National Building

More information

RosevilleProject. LoE _ 2 Glass Products. You can reduce your cooling energy usage by 25% or more. Here is the proof.

RosevilleProject. LoE _ 2 Glass Products. You can reduce your cooling energy usage by 25% or more. Here is the proof. RosevilleProject Glass Products You can reduce your cooling energy usage by 25% or more. Here is the proof. Hot-Button Issues Residents of California, Arizona, and Nevada don t need a weather forecast

More information

A Roof Integrated Solar Heating System Without Storage

A Roof Integrated Solar Heating System Without Storage M. and W. Saman Sustainable Energy Centre University of South Australia Mawson Lakes Boulevard, Mawson Lakes, SA 5095, Australia E-mail: martin.belusko@unisa.edu.au Abstract A prototype of a roof integrated

More information

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code

More information

Differentiating Energy Modeling Software!

Differentiating Energy Modeling Software! Differentiating Energy Modeling Software! What works, what doesn t, and when it matters! A Boulder Green Building Guild brownbag presentation by! Adam Stenftenagel! Principal! Sustainably Built! Heat Movement

More information

Heat Pumps for Cold Climates?? Yes, Indeed!

Heat Pumps for Cold Climates?? Yes, Indeed! Heat Pumps for Cold Climates?? Yes, Indeed! by Bob Zogg, Carlisle Energy Task Force (http://greencarlisle.org) August 26, 2014 This is not your parent s heat pump! The conventional wisdom is that it s

More information

EnergyPro Building Energy Analysis. Assisted Living Building

EnergyPro Building Energy Analysis. Assisted Living Building EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the

More information

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries

More information

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Ceiling/Airspace

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Ceiling/Airspace HEAT GAINS and LOSSES : ROOFS and WALLS Wall Roof Ts To Ts To Ti Ceiling/Airspace Ti Roof and wall are analyzed in the same way. In winter the heat loss is simple transmission based on the inside and outside

More information

Adaptive strategies for office spaces in the UK climate

Adaptive strategies for office spaces in the UK climate International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate

More information

SAVE ENERGY AT HOME INSULATE AND AIR SEAL

SAVE ENERGY AT HOME INSULATE AND AIR SEAL SAVE ENERGY AT HOME INSULATE AND AIR SEAL Check the roof insulation level and add insulation to maintain minimum R-38 (6 of blown cellulose or equal). Use R-19 between frame or R-10 rigid insulation for

More information

Building Energy Analysis Report

Building Energy Analysis Report Building Energy Analysis Report Report Generated by Efilm, an EnergyPlus based program. Date: 6/8/2012 Project Information Title: Building Filmed in 2012 Address: City/State/Zip: New York, NY 10001 Analyst

More information

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)

More information

SELECTIVE GLAZING FOR SUN CONTROL

SELECTIVE GLAZING FOR SUN CONTROL SUN CONTROL GLAZING SELECTIVE GLAZING FOR SUN CONTROL Sun Factor 1st level performance for direct solar energy Solar energy control Solar control coating Only if the glass is exposed to sun rays! 2nd level

More information

Protocol for the Certification of Energy Simulation Software: Second edition, September 2011

Protocol for the Certification of Energy Simulation Software: Second edition, September 2011 Copyright Agrément South Africa, September 2011 The master copy of this document appears on the website: http://www.agrement.co.za SANS 10400: The application of the National Building Regulations: Protocol

More information

Air distribution effectiveness with stratified air distribution systems

Air distribution effectiveness with stratified air distribution systems Lee, K.S., Jiang, Z., and Chen, Q. 2009 Air distribution effectiveness with stratified air distribution systems, ASHRAE Transactions, 115(2). Air distribution effectiveness with stratified air distribution

More information

Energy Efficiency in Buildings

Energy Efficiency in Buildings Energy Efficiency in Buildings Supplemental Guide to SANS 10400-XA & SANS 204 V. 3.0 Registered to: The Drawing Studio Image: digitalart / FreeDigitalPhotos.net Report Date: 26 August 2014 Practice Name:

More information

PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings

PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings Version 2006.1 AUSTRALIAN BUILDING CODES BOARD JANUARY 2006 TABLE OF CONTENTS Foreword 1. Scope 2. Purpose and context

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

Energy Efficiency for the Homeowner

Energy Efficiency for the Homeowner Efficiency for the Homeowner How to Reduce Your Home s Bills October 2009 National Mall Washington, DC A Quick Test Using Efficient Products and Practices Can: A. Make your home more affordable B. Make

More information

Alternatives for the Residential Energy Consumption Baseline

Alternatives for the Residential Energy Consumption Baseline Alternatives for the Residential Energy Consumption Baseline Executive Summary. Should the baseline for energy consumption in the Northeast Neighborhoods development area be changed from the current citywide

More information

Commercial Energy Savings Guide. www.touchstoneenergy.coop

Commercial Energy Savings Guide. www.touchstoneenergy.coop Commercial Energy Savings Guide www.touchstoneenergy.coop NRECA Pocket Savings Guide Pag.indd 1-3 2/7/05 4:19:07 PM Commercial Energy Saving Tips Notes: This guide provides basic hints on ways to reduce

More information

Whole House Dehumidification for Occupant Comfort and Energy Savings

Whole House Dehumidification for Occupant Comfort and Energy Savings Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

Before You Start an Energy Efficiency Retrofit The Building Envelope

Before You Start an Energy Efficiency Retrofit The Building Envelope ABOUT YOUR HOUSE Before You Start an Energy Efficiency Retrofit The Building Envelope The building envelope is the outer layer of the building that separates the indoor living space from the outdoor environment,

More information

PLBG/GAS SAFETY Information Bulletin

PLBG/GAS SAFETY Information Bulletin PLBG/GAS SAFETY Information Bulletin November 2012 P/G-08-02-PLBG/GAS [Rev 3] Page 1 of 11 SUBJECT: REQUIREMENTS FOR COMBINATION HEATING SYSTEMS: DUAL PURPOSE WATER (POTABLE) HEATER (COMBO UNIT) Safety

More information

AIR DISTRIBUTION FOR COMFORT AND IAQ

AIR DISTRIBUTION FOR COMFORT AND IAQ AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant

More information

Rate of Heating Analysis of Data Centers during Power Shutdown

Rate of Heating Analysis of Data Centers during Power Shutdown 2011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction,

More information

Below are detailed instructions for using the EMS load calculator.

Below are detailed instructions for using the EMS load calculator. Introduction The EMS load calculator is designed to make load calculating as painless as possible. For sizing the equipment, only the first three tabs (Steps 1, 2 & 3) need to be completed. This process

More information

Comfort Conditioning & Indoor Air Quality

Comfort Conditioning & Indoor Air Quality This article was published in ASHRAE Journal, May 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.newellinstruments.com.

More information

Flexibility, Efficiency In San Antonio Arena

Flexibility, Efficiency In San Antonio Arena 2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Mechanical and Natural Ventilation

Mechanical and Natural Ventilation BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:

More information

Calculating Heat Loss by Mark Crombie, Chromalox

Calculating Heat Loss by Mark Crombie, Chromalox Calculating Heat Loss by Mark Crombie, Chromalox Posted: January 30, 2006 This article deals with the basic principles of heat transfer and the calculations used for pipes and vessels. By understanding

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

http://www.fsec.ucf.edu/en/publications/html/fsec-pf-328-97/

http://www.fsec.ucf.edu/en/publications/html/fsec-pf-328-97/ Page 1 of 12 Reference Publication: James, P., J.E. Cummings, J. Sonne, R. Vieira, J. Klongerbo, The Effect of Residential Equipment Capacity on Energy Use, Demand, and Run-Time, ASHRAE Transactions 1997,

More information

A MAJOR STEP IN APPLIED INNOVATION. KCC Climate Management System. Powered by

A MAJOR STEP IN APPLIED INNOVATION. KCC Climate Management System. Powered by A MAJOR STEP IN APPLIED INNOVATION KCC Climate Management System Powered by KCC Climate Management System Powered by THE POWER OF DISRUPTIVE TECHNOLOGY YIELDS A CUSTOMER-FIRST HVAC DESIGN STRATEGY REDUCES

More information

ASHRAE STANDARD. Thermal Environmental Conditions for Human Occupancy. BSR/ASHRAE Standard 55P -1992R. Proposed American National Standard

ASHRAE STANDARD. Thermal Environmental Conditions for Human Occupancy. BSR/ASHRAE Standard 55P -1992R. Proposed American National Standard BSR/ASHRAE Standard 55P -1992R This draft standard will be submitted to the American National Standards Institute Board of Standards Review (BSR) for approval. ASHRAE STANDARD Proposed American National

More information

HVAC Basic Science - System Capacity

HVAC Basic Science - System Capacity HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414

More information

ENERGY STAR Data Verification Checklist

ENERGY STAR Data Verification Checklist ENERGY STAR Data Verification Checklist 86 ENERGY STAR Score 1 Sample Property Primary Function: Office Gross Floor Area (ft²): 200,000 Built: 1980 For Year Ending: 04/30/2013 Date Generated: 06/28/2013

More information

Ventilation Standard For Health Care Facilities

Ventilation Standard For Health Care Facilities The following article was published in ASHRAE Journal, October 2008. Copyright 2008 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

The Influence of Insulation Styles on the Air Conditioning Load of Japanese Multi- Family Residences

The Influence of Insulation Styles on the Air Conditioning Load of Japanese Multi- Family Residences The Influence of Insulation Styles on the Air Conditioning Load of Japanese Multi- Family Residences Yupeng Wang 1, and Hiroatsu Fukuda 2 1 Department of BCEE, Concordia University, Canada, Email: wangyupeng0628@gmail.com

More information

System Interactions in Forced-Air Heating and Cooling Systems, Part II: Continuous Fan Operation

System Interactions in Forced-Air Heating and Cooling Systems, Part II: Continuous Fan Operation System Interactions in Forced-Air Heating and Cooling Systems, Part II: Continuous Fan Operation Authors Gu, Lixing Swami, Muthusamy Fairey, Philip Original Publication Lixing Gu, Muthusamy Swami, Philip

More information

North Carolina Heating and Cooling Equipment Incentive Application

North Carolina Heating and Cooling Equipment Incentive Application North Carolina Heating and Cooling Incentive Application Questions? Call 1-866-380-9580 or visit www.duke-energy.com Email the complete, signed application with all required documents to PrescriptiveIncentives@duke-energy.com

More information

ROTEX gas hybrid heat pump. A strong team.

ROTEX gas hybrid heat pump. A strong team. ROTEX gas hybrid heat pump A strong team. The new ROTEX HPU hybrid gas hybrid heat pump always selects the most favourable heating mode automatically. For a long time the general opinion was that a heat

More information

Heating & Cooling Efficiency

Heating & Cooling Efficiency Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart

More information

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V III Heat Recovery VRF System)

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V III Heat Recovery VRF System) Energy Efficiency Analysis for a Multi-Story Commercial Office Building (LG Multi V III Heat Recovery VRF System) Commercial Air-Conditioning Engineering Study VRF-ES-BK-011-US 011L18 Executive Summary

More information

energy-saving checklist a guide for rental property owners

energy-saving checklist a guide for rental property owners energy-saving checklist a guide for rental property owners taking responsibility As an individual, your efficient use of energy brings benefits such as lower bills, improved comfort levels in your home

More information

RESEARCH HIGHLIGHT. Performance Assessment of a Cold-Climate Air Source Heat Pump

RESEARCH HIGHLIGHT. Performance Assessment of a Cold-Climate Air Source Heat Pump RESEARCH HIGHLIGHT December 2014 Technical Series 14-102 Performance Assessment of a Cold-Climate Air Source Heat Pump INTRODUCTION Most Canadians are familiar with air source heat pump technology in the

More information

Heating Load Calculation

Heating Load Calculation Heating Load Calculation ME 425 Air Conditioning System Design Keith E. Elder, P.E. Heating Load Calculation The heating load calculation begins with the determination of heat loss through a variety of

More information

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V Water II Heat Recovery VRF System)

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V Water II Heat Recovery VRF System) Energy Efficiency Analysis for a Multi-Story Commercial Office Building (LG Multi V Water II Heat VRF System) Commercial Air-Conditioning Engineering Study VRF-ES-BL-001-US 011M05 Executive Summary Contents

More information

New Homes EPS Modeling Frequently Asked Questions. Developed by Energy Trust of Oregon

New Homes EPS Modeling Frequently Asked Questions. Developed by Energy Trust of Oregon New Homes EPS Modeling Frequently Asked Questions Developed by Energy Trust of Oregon 1 General Questions 3 REM/Rate questions 4 -Creating custom entries 4 -Modeling Heat Pumps 5 -Modeling HRV/ERV 7 -Modeling

More information

A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING

A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING John Archibald American Solar Roofing Company 8703 Chippendale Court Annandale, Va. 22003 e-mail: jarchibald@americansolar.com

More information

ROOFS, SNOW AND ICE DAMS

ROOFS, SNOW AND ICE DAMS ROOFS, SNOW AND ICE DAMS The Problem Ice dams are a common roof performance problem in cold climate buildings. Simply put, they are ridges of ice and icicles caused by melt water from further up the roof

More information

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004]

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration

More information

Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings

Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings J A NUARY 2015 INTRODUCTION This Research Report explores best practices and approaches for reducing greenhouse gas (GHG)

More information

Florida Energy Efficiency Code For Building Construction

Florida Energy Efficiency Code For Building Construction Florida Energy iciency Code For Building Construction EnergyGauge Summit Fla/Com-2010, ective Date: March 15, 2012 -- Form 506-2010 Total Building Performance Method for Commercial Buildings PROJECT SUMMARY

More information

GEOTHERMAL HEATING AND COOLING INTRODUCTION

GEOTHERMAL HEATING AND COOLING INTRODUCTION GEOTHERMAL HEATING AND COOLING INTRODUCTION Geothermal Heating and Cooling Systems provide space conditioning -- heating, cooling, and humidity control. They may also provide water heating -- either to

More information

Technical Series 05-100

Technical Series 05-100 research highlight June 2005 Technical Series 05-100 introduction House temperatures are typically set by the occupants to ensure their personal comfort. When occupants are not at home, or are asleep,

More information

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent

More information

LOW-RISE RESIDENTIAL BUILDINGS ADDITIONS AND ALTERATIONS IN EXISTING LOW-RISE RESIDENTIAL BUILDINGS

LOW-RISE RESIDENTIAL BUILDINGS ADDITIONS AND ALTERATIONS IN EXISTING LOW-RISE RESIDENTIAL BUILDINGS SUBCHAPTER 9 LOW-RISE RESIDENTIAL BUILDINGS ADDITIONS AND ALTERATIONS IN EXISTING LOW-RISE RESIDENTIAL BUILDINGS SECTION 150.2 ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS IN EXISTING BUILDINGS

More information

SECTION EG. Engineering Guide Air Distribution. Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution.

SECTION EG. Engineering Guide Air Distribution. Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution. SECTION EG Air Distribution Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution. Space Air Diffusion AIR DISTRIBUTION ENGINEERING GUIDE Proper selection of air diffusion

More information

ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING

ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING Murray Milne, Research Professor Department of Architecture and Urban Design UCLA Los Angeles, CA 90095 milne@ucla.edu Tim Kohut, Project

More information