Inspection Report Condominium Association Property Address:
|
|
|
- Ada Powell
- 10 years ago
- Views:
Transcription
1 Inspection Report Condominium Association Property Address: 2468 Moldy Row Chicago IL Not The Real Building
2 Domicile Consulting Dan Cullen IL Home Inspector License Expiration Date November W. Vernon Park Place Unit C Chicago IL
3 Table of Contents Cover Page... 0 Table of Contents... 0 Intro Page... 0 I 4 POINT Inspection5 Summary... 0 Invoice... 0 Agreement... 0
4 Date: 10/1/2011 Time: 09:00 AM Report ID: Property: 2468 Moldy Row Chicago IL Customer: Condominium Association Comment Key or Definitions Real Estate Professional: The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property. Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear. Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting. Not Present (NP) = This item, component or unit is not in this home or building. Repair or Replace (RR) = The item, component or unit is not functioning as intended or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement. TYPE OF STRUCTURE: Low Rise Condominium Extra Info: : Six Condominium Units APPROXIMATE AGE OF STRUCTURE: Under 10 Years STRUCTURE FACES: West CLIENT PRESENT?: Yes RADON TEST?: No WATER QUALITY TEST?: No WEATHER CONDITIONS: Clear AMBIENT TEMPERATURE: Below 60...A/C not operated due to risk of equipment damage. NUMBER OF STORIES: Three story, with Basement EXTERIOR WALL CONSTRUCTION: Masonry EXTERIOR WALL CLADDING MATERIAL: : Face Brick on West Facade. Jumbo Brick on North, East, and South Facades. FOUNDATION: Full basement (Finished coverings), Foundation Not Fully Visible FOUNDATION MATERIAL: : Poured Concrete
5 I. 4 POINT Inspection This report reflects the findings of a limited scope moisture intrusion investigation performed at the request of the client named herein. The purpose of the investigation was to determine the cause of the moisture intrusion that has become evident in several areas of the interior condominium spaces. The inspection used only non-invasive techniques and therefore the concealed areas of the exterior wall assembly (wall cavities, wall framing, insulation, vapor retarders, etc.) could not be viewed. Bulk moisture can travel in unpredictable ways inside the space between the exterior wall cladding and the interior wall finishes. For these reasons, it is critically important to follow best construction practices regarding all exterior roof covering and wall cladding details so that the general risk for bulk moisture penetration into the wall assembly is reduced. This report is an attempt to compare the existing exterior wall and roof details against best practices in the industry and to make recommendations for repairs that will reduce the risk for ongoing moisture intrusion. This home inspection is being conducted in accordance with the State of Illinois Home Inspector Licensing Act and following the American Society of Home Inspectors guidelines. No pest control, lead paint, asbestos, mold, or other types of testing are being performed. This is a visual inspection of readily accessible systems and components of the home. Some items or areas may not be inspected if they are blocked by furniture or stored items. The home inspector makes no guarantees regarding any of the home's systems or components. The inspection is performed in good faith and is a 'snapshot in time'; it is does NOT constitute a prediction that the home will perform adequately in the future. Only non-invasive processes are used in the course of the inspection. Seasonal changes such as wind-driven rain, ice, and humidity may bring some defects to light that were not noted during your home inspection. Basements and attics that were dry at the time of the inspection can be damp or leak in later weeks or months. If you discover any adverse conditions in the home after your Domicile Consulting inspection, please call us immediately for a re-inspection and free consultation. Your inspection fee will be refunded without question if you are unhappy with the inspection for any reason, provided the buyer/client signs a 'hold harmless' agreement when accepting the refunded fee. No guarantees or warranties are provided in connection with the home inspection. Any disputes that cannot be resolved by the inspector and the client will be submitted jointly to the American Arbitration Association for a decision. Styles & Materials ROOF COVERINGS: Composition (Asphalt or Fiberglass) Shingles Modified Bitumen Rooftop decking prevented a full inspection of the roof covering. ROOF VIEWED: Roof Was Walked A. EXTERIOR WALLS, GROUNDS, CHIMNEYS, ETC. Comments: Not Functioning or in need of repair Inspection Items A. Picture 1 Front Exterior Stairs (1) The joint between the poured concrete front steps and the adjacent masonry piers should be separated by a caulked capillary break so that moisture and melting salts are not drawn into the masonry walls. Failure to provide such a break will result in saturation of the masonry piers and make them subject to freeze/thaw damage. It is further recommended that the masonry piers on either side of the concrete steps be cleaned and then sealed using a high-quality silane or siloxane-based masonry water repellent in order to reduce the rate of moisture absorption as well as the absorption of ice melting compounds which can result in ongoing and accelerating deterioration of the Renaissance stone and the brick masonry units.
6 A. Picture 3 Properly Tooled Sealant Joint With Backer Rod A. Picture 2 Aged and Deteriorated Caulking (2) The application of the exterior sealants, a.k.a. caulking, was originally improper and is now also deteriorating. It is recommended that plans be made for a near-term removal and replacement of the exterior sealant joints. In order for the sealant joints to prevent drafts, repel moisture, absorb movement, and maintain durability high-quality materials inappropriate methods must be used. Please refer to the referenced article regarding exterior sealants. Caulking Basics A. Picture 4 Limestone Mortar Joint (3) The mortar joints at the corners of the stone window sills and between all limestone copings/sills should be raked out and sealed instead with a high-quality masonry caulking compound to reduce the risk of moisture saturation, moisture intrusion to the interior, and damage to the brick masonry below the sill.
7 A. Picture 5 Incomplete Movement Joint (4) The masonry wall movement joints do not extend to the bottom of the foundation wall as is dictated by industry standards. Further review of the exterior wall movement joints by a qualified masonry restoration contractor is recommended in order to determine if completion of the joints is feasible and advisable. No obvious cracking or signs of stress were noted at the lower termination of the incomplete movement joints despite their improper configuration. A. Picture 6 Improperly Configured Wall Penetrations (5) The openings in the masonry wall that allow the passage of the PVC vent piping are improperly configured and are therefore prone to allowing moisture intrusion. The openings are too large and are sealed with relatively brittle cement mortar instead of a flexible and adhesive material such as urethane caulk. Further evaluation and repair of the PVC vent piping wall penetrations by a qualified masonry restoration contractor is recommended; ideally, the vent piping would pass through neatly cored brick masonry units via openings that are slightly larger than the PVC piping themselves. This would allow the application of a properly configured sealant joint.
8 A. Picture 7 Wanton and Willful Negligence (6) A damaged brick was noted at the lower north exterior masonry wall which is a result of careless drilling. That individual brick should be replaced by a qualified masonry contractor. The penetration through the individual brick masonry unit should be drilled carefully to prevent 'blow-out'. A. Picture 8 Incomplete Sealant Joint (7) The top edge of the steel deck ledgers should be properly sealed with high-quality caulking compound in order to reduce the risk for moisture entrapment and moisture intrusion through the through-wall ledger bolts.
9 A. Picture 9 Unsealed Air-Conditioning Refrigerant Line Penetration A. Picture 10 Feeder Conduit (8) The exterior wall penetrations for the air-conditioning refrigerant lines and the electrical feeder conduits should be sealed using backer rod and urethane caulk or the equivalent in order to reduce the risk for drafts, energy losses, moisture intrusion, and pest entry into the structure.
10 A. Picture 11 Missing Flashing A. Picture 12 Proper Flashing Detail A. Picture 13 Substandard Cement Mortar (9) The masonry wall flashings are either missing or improperly installed. The flashings should protrude from the wall by at least 1/4" at the following locations: the top of the foundation wall; above the masonry pockets where the floor joists are set into the concrete block; above and below every window and door. Missing or improperly installed wall flashing can
11 allow moisture to enter the home and cause rot, mold growth, and structural damage. The exterior masonry walls of this structure should be evaluated and repaired by a licensed and competent masonry contractor. Since retrofitting of missing or improperly installed masonry wall flashing is both disruptive and expensive, it may be advisable for the condominium association to deal with this issue on a case-by-case basis. If and when bulk moisture intrusion becomes evident at the top or sides of the interior window openings then retrofitting of the missing flashings should be seriously considered. A. Picture 14 Mortar Gap A. Picture 15 Re-Pointing Sequence (10) The quality of the brick masonry mortar joints is substandard. Areas of the mortar appear to contain excessive amounts of sand and are not properly tooled; improperly or inadequately applied cement mortar in a brick masonry wall often leads to excess moisture saturation by the brick masonry units and, after prolonged or wind driven rains, leads to bulk moisture intrusion to the moisture sensitive interior wall components like insulation, drywall, and wood framing. It is
12 the inspector's opinion that the masonry walls would benefit greatly from grinding out of the mortar joints and re-pointing. This process is expensive and is disruptive; however, it can be performed on a wall by wall basis in order to allow for easier budgeting. The application of clear masonry sealants is a poor substitute for properly configured and tooled mortar joints. Further consultation with one or more masonry restoration contractors is recommended so that the condominium association can plan and budget for this process. A. Picture 16 Rear Basement Entry Door (11) Evidence of past moisture intrusion was noted at the rear basement exterior entry doors. It is recommended that the cracked and loose mortar bed below the limestone sills be replaced by a qualified masonry restoration contractor. It is also recommended that the gap between the aluminum door threshold and the limestone sill be neatly and professionally sealed using the appropriate caulking compound. A. Picture 17 Improper Door Installation (12) Exterior doors and windows in a masonry wall should be recessed approximately 1.5" to 2" in order to protect the wood components from the weather. The exterior rear entry doors at the basement, first floor, and second-floor have been improperly installed and stand outboard of the masonry wall. This puts them at much greater risk for moisture damage. It is recommended that the aluminum flashing be installed over the top of the protruding door trim in order to protect from moisture intrusion and moisture damage.
13 A. Picture 18 Improper Limestone Coping And Flashing Details A. Picture 19 Correctly Configured/Installed Coping A. Picture 21 Improper Parapet Capping Detail A. Picture 20 Caulk Smear (13) A number of defects were noted in the masonry wall flashing details in the area of the limestone parapet capping. The individual limestone blocks do not sufficiently overhang the concrete masonry units and brick masonry units below. The drip groove at the outside edges of the stone is missing. The cheap vinyl flashing (not approved for exposure to UV light) has been left exposed at some locations. At other areas the flashing has been cut back flush to the wall and has resulted in gaps/openings that can easily allow both wind-driven rain and capillary suction to draw moisture into the masonry wall below the flashing. The urethane sealant between the individual limestone blocks has been smeared over cement mortar and will not perform as intended. The limestone parapet capping should be removed and reinstalled according to best practices and industry standards and is detailed in the attached Brick Industry Association's Technical Notes #7. Please refer specifically to Figure 18 for a comparison between the 'as built' details and the industry standard.
14 A. Picture 22 Missing and Smeared Caulk at Scupper Opening A. Picture 23 Loose Flap of Roofing Membrane At Scupper Opening
15 A. Picture 24 Correct Scupper Configuration
16 A. Picture 25 Risk for Moisture Penetration at Scupper (14) The design and the condition of the through-wall scuppers are inconsistent with best practices and industry standards. The loose roof membrane at the through-wall opening is prone to allowing moisture entrapment, moisture intrusion, and moisture damage. The successively smeared applications of caulking around the brick opening will not perform the intended function of moisture resistance. Each of the through-wall scuppers should be repaired by a qualified roofing contractor. Repair should include removal and replacement of the existing caulk/sealant joints and securing of all roof membranes in and around the scupper. Plans should be made for the eventual reconfiguration of the sheet-metal details around the through-wall scuppers by a qualified contractor.
17 A. Picture 26 Improper Vinyl Siding Penetration A. Picture 27 Vinyl Siding Mounting Blocks A. Picture 28 Improper Vinyl Siding Penetrations A. Picture 29 Installation of Vinyl Siding Mounting Blocks Recommended (15) It is recommended that all of the exterior wall penetrations be made through the pre-formed vinyl siding mounting blocks that are manufactured for this purpose. The mounting blocks are self-flashing and reduce the risk for moisture intrusion. They also allow the siding to expand and contract around the mounting block thereby reducing the risk for siding damage, sealant failure, etc. Repair by a qualified siding specialist is recommended.
18 A. Picture 30 Projecting Soldier Course at Arch Top Window (16) The projecting soldier courses of brick masonry on the exterior walls present an increased risk for moisture intrusion and moisture damage. The flat ledges at the top of the soldier courses result in increased moisture contact time and reduced drainage. Further evaluation by a qualified masonry restoration contractor is recommended however, it is the inspectors opinion that the flat ledge at the masonry soldier courses should be repaired by the application of a cove of either mortar or caulk so that moisture is encouraged to flow away from these flat surfaces. A. Picture 31 Loose Siding (17) A number of defects were noted regarding the installation of the vinyl siding over the penthouse walls. It is recommended that the condominium association plan for the replacement of the existing vinyl siding in order to ensure the long-term moisture resistant performance of the exterior wall cladding. Cement board siding, Kynar coated metal panels, or similarly weather resistant materials are recommended.
19 A. Picture 32 Mortar Cracking at Concrete Masonry Units Of the Inner Parapet (18) It is recommended that the cracking at the mortar joints of the inner parapet be repaired by grinding out and repointing. These cracks appear due to moisture saturation and freeze/thaw cycling resulting from improper parapet capping details. B. ROOF COVERING, ROOF FLASHINGS, ROOF DRAINAGE. Comments: Not Functioning or in need of repair B. Picture 1 "Deck of Card" (1) The rooftop decks are supported by loose wooden blocks, many of which have become displaced. This creates a risk for damage to both the deck structure as well as to the roof covering. The deck will need to be completely disassembled and reassembled by a qualified contractor in order to reduce the risk for ongoing damage. The deck frame would, ideally, be supported by opposing bearing walls and would not rest directly on the roof covering or roof surface. If space or budget constraints prevent such a support system then the deck bearing points should be lined up directly over and on top of the roof framing trusses below. This will prevent deflection and damage to the plywood roof sheathing. The roof membrane must be protected from keen edges and from heavy loads imposed upon small surface areas. Also, the deck framing should not block the prompt flow of roof run-off from reaching the gutters or scupper drains.
20 B. Picture 2 Creates That Roofing Material B. Picture 3 Cant Strip at Roof Crease (2) Modified bitumen roofing membrane should not be creased at a 90 angle due to the risk for cracking, leaking, and damage. The use of cant strips at the roof to sidewall transition is required by both the roofing manufacturer as well as industry standards. It is recommended that the creases at the roof to sidewall transitions be evaluated by a qualified roofing contractor. It is the inspectors opinion that the most cost-effective approach to reducing the risk for ongoing damage and leaking at these locations is to regularly monitor these creases and to apply additional roof coating as needed until the installation of a new roof covering becomes necessary. B. Picture 4 Risk for Damage to Roof Covering (3) The installation of one or more sacrificial layers of roofing material is recommended underneath the rather keen edges of the air-conditioning bases at the rooftop. During hot weather, the modified bitumen roof material will soften and that, combined with the weight and vibration of the condensing unit, can result in scarring, damage and leaking of the roof covering.
21 B. Picture 5 Improper Shingle Application (4) Multiple areas of improper roof shingle application were noted above the sloped cathedral ceilings at units 3S And 3N. The shingle rain guides and the shingle butt joints have been lined up over one another in multiple areas. These defects greatly increase the risk for leaking and damage. Since the existing composition shingle roof covering is at or near the end of its service life, it is recommended that shingle replacement, rather than repair, be performed. Further evaluation by a qualified roofing contractor is recommended. B. Picture 7 Low Slope Roof Vent B. Picture 6 Inappropriate Installation (5) The aluminum breathers noted on this roof are not intended to serve as venting devices for the roof plenum. These devices have very little net free vent area and are incapable of venting the potentially large volumes of trapped heat and moisture inside the roof plenum. Inadequate ventilation of the roof plenum can result in condensation, mold growth, excess energy usage, and reduced indoor air comfort during the cooling season. It is recommended that the existing undersized and inappropriate breathers be replaced with high-quality roof vents designed for low slope roof applications.
22 B. Picture 8 Spongy Roof Sheathing (6) Areas of apparently deteriorated roof sheathing were noted at the low slope roof area between units 3N and 3S. These areas should be further evaluated and repaired as needed in the course of the recommended roof covering replacement.
23 B. Picture 9 Unsealed Roof Membrane B. Picture 10 Improperly Detailed Edge Metal Flashing
24 B. Picture 11 Proper Edge Metal Flashing Detail (7) A number of defects were noted at the modified bitumen roof covering over the upper levels of units 3N and 3S. The failure to seal the modified bitumen roof covering at the gutter edge greatly increases the risk for moisture damage from ice damming. The material used as edge metal flashing is not approved for this use and is not properly installed. It is recommended that this roof covering be repaired as soon as possible and replaced as soon as practical.
25 B. Picture 12 Loose Vent Pipe (8) The PVC vent pipe at the Southeast corner of Unit 3N's rooftop deck is loose and therefore at risk for allowing moisture intrusion. It is recommended that the PVC piping penetration through the roof covering be evaluated and repaired as needed by a qualified roofing contractor. C. ELECTRICAL SYSTEM, GROUNDING, CONNECTED DEVICES AND FIXTURES Comments: Not Functioning or in need of repair C. Picture 1 Improper Electrical Connection C. Picture 2 Correct Way to Secure Grounding Electrode Conductor The connection between the driven ground rod and the grounding electrode conductor at the rear basement is improper and unsafe. The grounding electrode conductor should be secured by the screw terminal and should not be squeezed between the clamp and the rod. Repair by a qualified electrician is recommended in order to help ensure the safe and effective bonding and grounding of the electrical system. D. INSULATION, VENTILATION, ATTICS, ETC. Comments: Not Functioning or in need of repair
26 D. Picture 1 Mold-like Substances on Underside of Roof Sheathing Mold-like substances were noted on surface/s of this home. Mold growth results from moisture on organic strata and is first and foremost a moisture problem. The source of the moisture that is the proximal cause of the mold-growth should be found and eliminated before final remediation is performed. Initial remediative steps may be advisable in order to reduce the release of mold spores, fungal fragments, and mycotoxins during the moisture investigation and repair process. Small areas of mold (10 square feet or less) can be remediated by the homeowner successfully. An EPA approved mildewcide with residual mold inhibiting properties (Concrobium Brand) can be found at major home improvement stores. Relatively non-porous surfaces such as tile, laminate, concrete, etc. should be surface cleaned with this type of product and kept dry. Semi-porous surfaces such as wood framing and sheathing can also be cleaned in this manner if fungal growth hasn't degraded the material significantly. Porous surfaces such as paper-faced gypsum drywall, cellulose insulation, etc. should be removed and replaced. Air sampling and bulk sampling for mold is typically not required for successful remediation. For routine assessments in which the goal is to identify possible mold contamination problems before remediation, it is usually unnecessary to collect and analyze air or settled dust samples for mold analysis because decisions about appropriate intervention strategies can typically be made on the basis of a visual inspection. Also, sampling and analysis costs can be relatively high and the interpretation of results is not straightforward. Air and dust monitoring may, however, be necessary in certain situations, including 1) if an individual has been diagnosed with a disease associated with fungal exposure through inhalation, 2) if it is suspected that the ventilation systems are contaminated, or 3) if the presence of mold is suspected but cannot be identified by a visual inspection or bulk sampling. E. INTERIORS AND FINISHES Comments: Not Functioning or in need of repair
27 E. Picture 1 Round Top Window (1) The drywall at the round top interior window returns has been applied directly over the masonry structure. This presents a strong risk for condensation, moisture damage, and mold growth. It is recommended that the drywall finishes at the round top window returns be removed, that all gaps in the arched rough masonry opening be sealed, and that the interior window returns be finished with a non-moisture sensitive material. The use of paper faced or paper backed drywall is not recommended at these locations. Green Board is only marginally more mold resistant than common drywall. The use of non-paper faced gypsum wall board is recommended. Fiberglass Faced Gypsum Wallboard
28 E. Picture 2 Cathedral ceiling at Unit 3N E. Picture 3 Mold Growth at Underside of Roof Sheathing E. Picture 4 Improper Insulation Installation
29 E. Picture 5 Faulty Insulation/Ventilation at Cathedral Ceiling Diagram (2) The cathedral ceilings at units 3N and 3S are not properly ventilated and are prone to recurring condensation events, mold growth, wood rot, etc. The individual framing channels across the cathedral ceiling are lacking adequate air intake openings at the lower termination of the rafters. This omission results in air stagnation and excess contact time between warm and moist interior air leakage and the cold underside of the OSB roof sheathing during the heating season. Also, the type of roof ridge vent used at this location is prone to allowing wind driven rain to enter the framing voids of the cathedral ceiling. The repeated deterioration of the drywall tape at the peak of the cathedral ceiling is evidence of this process taking place. Also, the fiberglass batt insulation at the cathedral ceiling rafter channels is not been properly installed and is prone to allowing excess warmth and moisture above the insulation layer. These construction defects have combined to create high moisture conditions conducive to mold growth within the individual rafter channels. It is the inspectors opinion that the most cost-effective (both in the long-term and short-term) approach to repairing the defects and remediating the damage at the cathedral ceilings is to remove the existing drywall at the slopes of the cathedral ceilings; remove the fiberglass insulation; remove the continuous ridge vent and perform the required roof patching; apply open cell polyurethane spray foam insulation against the underside of the roof decking and between the individual cathedral ceiling roof rafters; and to install a new drywall ceiling finish. The question of mold remediation should be considered in consultation with the insulation contractor and a qualified indoor air quality specialist once the drywall has been removed and the full extent of any mold growth can be determined. Care will be required at the ceiling can lights in order to prevent air leakage into the framing cavity and to also prevent any possibility for hot surface ignition of combustible materials. All of the recommendations for repairs or alterations that are contained in this report should be performed by licensed and competent contractors with expertise in the appropriate trade or specialty. It is recommended that the repairs/alterations be completed prior to closing. The contractor/s who perform the recommended repairs at the seller's direction should provide the buyer/client with all appropriate documentation regarding the materials and methods used in the work. A list of contractors who have been rated and recommended by consumers can be found at Prepared Using HomeGauge : Licensed To Domicile Consulting
30 Summary Domicile Consulting 1033 W. Vernon Park Place Unit C Chicago IL Customer Condominium Association Address 2468 Moldy Row Chicago IL The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or appear to warrant further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report. I. 4 POINT Inspection General Summary EXTERIOR WALLS, GROUNDS, CHIMNEYS, ETC. Not Functioning or in need of repair 1. (1) The joint between the poured concrete front steps and the adjacent masonry piers should be separated by a caulked capillary break so that moisture and melting salts are not drawn into the masonry walls. Failure to provide such a break will result in saturation of the masonry piers and make them subject to freeze/thaw damage. It is further recommended that the masonry piers on either side of the concrete steps be cleaned and then sealed using a high-quality silane or siloxane-based masonry water repellent in order to reduce the rate of moisture absorption as well as the absorption of ice melting compounds which can result in ongoing and accelerating deterioration of the Renaissance stone and the brick masonry units. 2. (2) The application of the exterior sealants, a.k.a. caulking, was originally improper and is now also deteriorating. It is recommended that plans be made for a near-term removal and replacement of the exterior sealant joints. In order for the sealant joints to prevent drafts, repel moisture, absorb movement, and maintain durability high-quality materials inappropriate methods must be used. Please refer to the referenced article regarding exterior sealants. Caulking Basics 3. (3) The mortar joints at the corners of the stone window sills and between all limestone copings/sills should be raked out and sealed instead with a high-quality masonry caulking compound to reduce the risk of moisture saturation, moisture intrusion to the interior, and damage to the brick masonry below the sill. 4. (4) The masonry wall movement joints do not extend to the bottom of the foundation wall as is dictated by industry standards. Further review of the exterior wall movement joints by a qualified masonry restoration contractor is
31 recommended in order to determine if completion of the joints is feasible and advisable. No obvious cracking or signs of stress were noted at the lower termination of the incomplete movement joints despite their improper configuration. 5. (5) The openings in the masonry wall that allow the passage of the PVC vent piping are improperly configured and are therefore prone to allowing moisture intrusion. The openings are too large and are sealed with relatively brittle cement mortar instead of a flexible and adhesive material such as urethane caulk. Further evaluation and repair of the PVC vent piping wall penetrations by a qualified masonry restoration contractor is recommended; ideally, the vent piping would pass through neatly cored brick masonry units via openings that are slightly larger than the PVC piping themselves. This would allow the application of a properly configured sealant joint. 6. (6) A damaged brick was noted at the lower north exterior masonry wall which is a result of careless drilling. That individual brick should be replaced by a qualified masonry contractor. The penetration through the individual brick masonry unit should be drilled carefully to prevent 'blow-out'. 7. (7) The top edge of the steel deck ledgers should be properly sealed with high-quality caulking compound in order to reduce the risk for moisture entrapment and moisture intrusion through the through-wall ledger bolts. 8. (8) The exterior wall penetrations for the air-conditioning refrigerant lines and the electrical feeder conduits should be sealed using backer rod and urethane caulk or the equivalent in order to reduce the risk for drafts, energy losses, moisture intrusion, and pest entry into the structure. 9. (9) The masonry wall flashings are either missing or improperly installed. The flashings should protrude from the wall by at least 1/4" at the following locations: the top of the foundation wall; above the masonry pockets where the floor joists are set into the concrete block; above and below every window and door. Missing or improperly installed wall flashing can allow moisture to enter the home and cause rot, mold growth, and structural damage. The exterior masonry walls of this structure should be evaluated and repaired by a licensed and competent masonry contractor. Since retrofitting of missing or improperly installed masonry wall flashing is both disruptive and expensive, it may be advisable for the condominium association to deal with this issue on a case-by-case basis. If and when bulk moisture intrusion becomes evident at the top or sides of the interior window openings then retrofitting of the missing flashings should be seriously considered. 10. (10) The quality of the brick masonry mortar joints is substandard. Areas of the mortar appear to contain excessive amounts of sand and are not properly tooled; improperly or inadequately applied cement mortar in a brick masonry wall often leads to excess moisture saturation by the brick masonry units and, after prolonged or wind driven rains, leads to bulk moisture intrusion to the moisture sensitive interior wall components like insulation, drywall, and wood framing. It is the inspector's opinion that the masonry walls would benefit greatly from grinding out of the mortar joints and re-pointing. This process is expensive and is disruptive; however, it can be performed on a wall by wall basis in order to allow for easier budgeting. The application of clear masonry sealants is a poor substitute for properly configured and tooled mortar joints. Further consultation with one or more masonry restoration contractors is recommended so that the condominium association can plan and budget for this process. 11. (11) Evidence of past moisture intrusion was noted at the rear basement exterior entry doors. It is recommended that the cracked and loose mortar bed below the limestone sills be replaced by a qualified masonry restoration contractor. It is also recommended that the gap between the aluminum door threshold and the limestone sill be neatly and professionally sealed using the appropriate caulking compound. 12. (12) Exterior doors and windows in a masonry wall should be recessed approximately 1.5" to 2" in order to protect the wood components from the weather. The exterior rear entry doors at the basement, first floor, and second-floor have been improperly installed and stand outboard of the masonry wall. This puts them at much greater risk for moisture damage. It is recommended that the aluminum flashing be installed over the top of the protruding door trim in order to protect from moisture intrusion and moisture damage. 13. (13) A number of defects were noted in the masonry wall flashing details in the area of the limestone parapet capping. The individual limestone blocks do not sufficiently overhang the concrete masonry units and brick masonry units below. The drip groove at the outside edges of the stone is missing.
32 The cheap vinyl flashing (not approved for exposure to UV light) has been left exposed at some locations. At other areas the flashing has been cut back flush to the wall and has resulted in gaps/openings that can easily allow both wind-driven rain and capillary suction to draw moisture into the masonry wall below the flashing. The urethane sealant between the individual limestone blocks has been smeared over cement mortar and will not perform as intended. The limestone parapet capping should be removed and reinstalled according to best practices and industry standards and is detailed in the attached Brick Industry Association's Technical Notes #7. Please refer specifically to Figure 18 for a comparison between the 'as built' details and the industry standard. 14. (14) The design and the condition of the through-wall scuppers are inconsistent with best practices and industry standards. The loose roof membrane at the through-wall opening is prone to allowing moisture entrapment, moisture intrusion, and moisture damage. The successively smeared applications of caulking around the brick opening will not perform the intended function of moisture resistance. Each of the through-wall scuppers should be repaired by a qualified roofing contractor. Repair should include removal and replacement of the existing caulk/sealant joints and securing of all roof membranes in and around the scupper. Plans should be made for the eventual reconfiguration of the sheet-metal details around the through-wall scuppers by a qualified contractor. 15. (15) It is recommended that all of the exterior wall penetrations be made through the pre-formed vinyl siding mounting blocks that are manufactured for this purpose. The mounting blocks are self-flashing and reduce the risk for moisture intrusion. They also allow the siding to expand and contract around the mounting block thereby reducing the risk for siding damage, sealant failure, etc. Repair by a qualified siding specialist is recommended. 16. (16) The projecting soldier courses of brick masonry on the exterior walls present an increased risk for moisture intrusion and moisture damage. The flat ledges at the top of the soldier courses result in increased moisture contact time and reduced drainage. Further evaluation by a qualified masonry restoration contractor is recommended however, it is the inspectors opinion that the flat ledge at the masonry soldier courses should be repaired by the application of a cove of either mortar or caulk so that moisture is encouraged to flow away from these flat surfaces. 17. (17) A number of defects were noted regarding the installation of the vinyl siding over the penthouse walls. It is recommended that the condominium association plan for the replacement of the existing vinyl siding in order to ensure the long-term moisture resistant performance of the exterior wall cladding. Cement board siding, Kynar coated metal panels, or similarly weather resistant materials are recommended. 18. (18) It is recommended that the cracking at the mortar joints of the inner parapet be repaired by grinding out and repointing. These cracks appear due to moisture saturation and freeze/thaw cycling resulting from improper parapet capping details. ROOF COVERING, ROOF FLASHINGS, ROOF DRAINAGE. Not Functioning or in need of repair 19. (1) The rooftop decks are supported by loose wooden blocks, many of which have become displaced. This creates a risk for damage to both the deck structure as well as to the roof covering. The deck will need to be completely disassembled and reassembled by a qualified contractor in order to reduce the risk for ongoing damage. The deck frame would, ideally, be supported by opposing bearing walls and would not rest directly on the roof covering or roof surface. If space or budget constraints prevent such a support system then the deck bearing points should be lined up directly over and on top of the roof framing trusses below. This will prevent deflection and damage to the plywood roof sheathing. The roof membrane must be protected from keen edges and from heavy loads imposed upon small surface areas. Also, the deck framing should not block the prompt flow of roof run-off from reaching the gutters or scupper drains. 20. (2) Modified bitumen roofing membrane should not be creased at a 90 angle due to the risk for cracking, leaking, and damage. The use of cant strips at the roof to sidewall transition is required by both the roofing manufacturer as well as industry standards. It is recommended that the creases at the roof to sidewall transitions be evaluated by a qualified roofing contractor. It is the inspectors opinion that the most cost-effective approach to reducing the risk for ongoing damage and leaking at these locations is to regularly monitor these creases and to apply additional roof coating as needed until the installation of a new roof covering becomes necessary. 21. (3) The installation of one or more sacrificial layers of roofing material is recommended underneath the rather keen edges of the air-conditioning bases at the rooftop. During hot weather, the modified bitumen roof material will soften and that, combined with the weight and vibration of the condensing unit, can result in scarring, damage and leaking of the roof covering.
33 22. (4) Multiple areas of improper roof shingle application were noted above the sloped cathedral ceilings at units 3S And 3N. The shingle rain guides and the shingle butt joints have been lined up over one another in multiple areas. These defects greatly increase the risk for leaking and damage. Since the existing composition shingle roof covering is at or near the end of its service life, it is recommended that shingle replacement, rather than repair, be performed. Further evaluation by a qualified roofing contractor is recommended. 23. (5) The aluminum breathers noted on this roof are not intended to serve as venting devices for the roof plenum. These devices have very little net free vent area and are incapable of venting the potentially large volumes of trapped heat and moisture inside the roof plenum. Inadequate ventilation of the roof plenum can result in condensation, mold growth, excess energy usage, and reduced indoor air comfort during the cooling season. It is recommended that the existing undersized and inappropriate breathers be replaced with high-quality roof vents designed for low slope roof applications. 24. (6) Areas of apparently deteriorated roof sheathing were noted at the low slope roof area between units 3N and 3S. These areas should be further evaluated and repaired as needed in the course of the recommended roof covering replacement. 25. (7) A number of defects were noted at the modified bitumen roof covering over the upper levels of units 3N and 3S. The failure to seal the modified bitumen roof covering at the gutter edge greatly increases the risk for moisture damage from ice damming. The material used as edge metal flashing is not approved for this use and is not properly installed. It is recommended that this roof covering be repaired as soon as possible and replaced as soon as practical. 26. (8) The PVC vent pipe at the Southeast corner of Unit 3N's rooftop deck is loose and therefore at risk for allowing moisture intrusion. It is recommended that the PVC piping penetration through the roof covering be evaluated and repaired as needed by a qualified roofing contractor. ELECTRICAL SYSTEM, GROUNDING, CONNECTED DEVICES AND FIXTURES Not Functioning or in need of repair 27. The connection between the driven ground rod and the grounding electrode conductor at the rear basement is improper and unsafe. The grounding electrode conductor should be secured by the screw terminal and should not be squeezed between the clamp and the rod. Repair by a qualified electrician is recommended in order to help ensure the safe and effective bonding and grounding of the electrical system. INSULATION, VENTILATION, ATTICS, ETC. Not Functioning or in need of repair 28. Mold-like substances were noted on surface/s of this home. Mold growth results from moisture on organic strata and is first and foremost a moisture problem. The source of the moisture that is the proximal cause of the mold-growth should be found and eliminated before final remediation is performed. Initial remediative steps may be advisable in order to reduce the release of mold spores, fungal fragments, and mycotoxins during the moisture investigation and repair process. Small areas of mold (10 square feet or less) can be remediated by the homeowner successfully. An EPA approved mildewcide with residual mold inhibiting properties (Concrobium Brand) can be found at major home improvement stores. Relatively non-porous surfaces such as tile, laminate, concrete, etc. should be surface cleaned with this type of product and kept dry. Semi-porous surfaces such as wood framing and sheathing can also be cleaned in this manner if fungal growth hasn't degraded the material significantly. Porous surfaces such as paper-faced gypsum drywall, cellulose insulation, etc. should be removed and replaced. Air sampling and bulk sampling for mold is typically not required for successful remediation. For routine assessments in which the goal is to identify possible mold contamination problems before remediation, it is usually unnecessary to collect and analyze air or settled dust samples for mold analysis because decisions about appropriate intervention strategies can typically be made on the basis of a visual inspection. Also, sampling and analysis costs can be relatively high and the interpretation of results is not straightforward. Air and dust monitoring may, however, be necessary in certain situations, including 1) if an individual has been diagnosed with a disease associated with fungal exposure through inhalation, 2) if it is suspected that the ventilation systems are contaminated, or 3) if the presence of mold is suspected but cannot be identified by a visual inspection or bulk sampling. INTERIORS AND FINISHES Not Functioning or in need of repair 29. (1) The drywall at the round top interior window returns has been applied directly over the masonry structure. This presents a strong risk for condensation, moisture damage, and mold growth. It is recommended that the drywall finishes at the round top window returns be removed, that all gaps in the arched rough masonry opening be sealed, and that the interior window returns be finished with a non-moisture sensitive material. The use of paper faced or paper backed
34 drywall is not recommended at these locations. Green Board is only marginally more mold resistant than common drywall. The use of non-paper faced gypsum wall board is recommended. Fiberglass Faced Gypsum Wallboard 30. (2) The cathedral ceilings at units 3N and 3S are not properly ventilated and are prone to recurring condensation events, mold growth, wood rot, etc. The individual framing channels across the cathedral ceiling are lacking adequate air intake openings at the lower termination of the rafters. This omission results in air stagnation and excess contact time between warm and moist interior air leakage and the cold underside of the OSB roof sheathing during the heating season. Also, the type of roof ridge vent used at this location is prone to allowing wind driven rain to enter the framing voids of the cathedral ceiling. The repeated deterioration of the drywall tape at the peak of the cathedral ceiling is evidence of this process taking place. Also, the fiberglass batt insulation at the cathedral ceiling rafter channels is not been properly installed and is prone to allowing excess warmth and moisture above the insulation layer. These construction defects have combined to create high moisture conditions conducive to mold growth within the individual rafter channels. It is the inspectors opinion that the most cost-effective (both in the long-term and short-term) approach to repairing the defects and remediating the damage at the cathedral ceilings is to remove the existing drywall at the slopes of the cathedral ceilings; remove the fiberglass insulation; remove the continuous ridge vent and perform the required roof patching; apply open cell polyurethane spray foam insulation against the underside of the roof decking and between the individual cathedral ceiling roof rafters; and to install a new drywall ceiling finish. The question of mold remediation should be considered in consultation with the insulation contractor and a qualified indoor air quality specialist once the drywall has been removed and the full extent of any mold growth can be determined. Care will be required at the ceiling can lights in order to prevent air leakage into the framing cavity and to also prevent any possibility for hot surface ignition of combustible materials. Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspector or other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property. Prepared Using HomeGauge : Licensed To Domicile Consulting
35 INVOICE Domicile Consulting 1033 W. Vernon Park Place Unit C Chicago IL Inspected By: Dan Cullen Inspection Date: 10/1/2011 Report ID: Customer Info: Condominium Association Inspection Property: 2468 Moldy Row Chicago IL Customer's Real Estate Professional: Inspection Fee: Service Price Amount Sub-Total Courtesy Inspection Tax $0.00 Total Price $1.00 Payment Method: Net 30 Days Payment Status: Invoice Sent Note:
36 AGREEMENT THIS IS A CONFIDENTIAL REPORT FOR THE CLIENTS NAMED HEREIN. THIS REPORT SUPERSEDES ANY ORAL COMMENTS AND DISCUSSIONS AT OR PRIOR TO THE INSPECTION. THERE ARE NO GUARANTEES OR WARRANTIES EITHER EXPRESSED OR IMPLIED IN THIS INSPECTION OR IN THE ACCOMPANYING REPORT. The purpose of this home inspection is to provide the client with a summary of the visual observations which the inspector makes regarding the portions of the premises which were in plain view and accessible at the time of the inspection. The inspector is not responsible for hidden defects or for reporting on the condition of areas that are visually inaccessible. Emphasis is placed on major expenses and on safety issues. Some less important deficiencies may be discovered, but an all-inclusive list of minor building flaws is not provided. This report is NOT a guarantee of code compliance of the building being inspected. This report is NOT a warranty of the condition of the premises, nor an opinion as to the advisability of the property for purchase. This inspection is being conducted in accordance with the standards of practice of the Home Inspector License Act of Illinois and the American Society of Home Inspectors, copies of which are available upon request. The following components are included in this inspection: structural system/foundation; exterior; roof; plumbing; heating; cooling; electric; insulation and ventilation; interior spaces; and fireplace components. All inspection methods are non-invasive and only normal operating controls will be used. A representative number of outlets, switches, and lights will be tested for operation. Furniture, appliances, personal items, stored materials, etc. are not moved for the inspection. The inspector will walk on flat roofs where conditions permit, when they are safely accessible with a 15' ladder, and where no potential exists for damage to the roof surface. Central Air Conditioning units will not be operated unless the outside temperature has been above 60 degrees for at least 24 hours prior to the inspection; doing so could damage the air conditioning equipment. Wet crawl spaces and those with either low headroom or insufficient openings are not entered but are only visually examined from the access area. Attics are entered when it is feasible and if there is sufficient space to maneuver safely in the attic. The inspector will not perform any procedures which could either lead to his/her personal injury or which could result in damage to the subject property. This may result in some items or areas not being available for inspection. Appliances and mechanical systems will be checked for proper operation during this inspection. The inspector will not light any gas equipment, nor turn on any valves, nor re-set circuit breakers or fuses. The clients are responsible for maintaining or arranging for the maintenance of their mechanical equipment after closing. The client should be aware that the equipment may still be in use until closing and it is the
37 client's responsibility to re-check all mechanical systems and appliances for proper operation within 24 hours prior to closing. Domicile Consulting Inc. does not provide any engineering, architectural, pest control, or environmental inspection services in connection with this home inspection unless otherwise agreed upon by both parties in writing. Domicile Consulting Inc. is not licensed for either asbestos or lead paint detection and makes no definitive representation as to the presence or absence of either material. All residential properties are subject to moisture related conditions that can cause mold or fungi. Domicile Consulting Inc. does not perform testing for mold or fungi; makes no representations as to their definitive presence or absence in this property; and specifically excludes them from this inspection unless otherwise agreed upon in writing by both parties. The inspection of fireplaces is limited to the firebox and those portions of the flue that are readily viewable. The inspector is not required to light any gas appliances. Many properties are being constructed with concrete block. A number of these structures are experiencing water infiltration problems as a result of improper materials and/or construction methods which may not be readily determined from a visual inspection. Domicile Consulting Inc. makes no representation as to the performance of these construction assemblies and specifically excludes them from this inspection except where otherwise indicated. Any verbal or written estimations or approximations made by the inspector regarding potential repairs of the premises are neither a firm estimate nor a bid regarding such repair work. The purchaser must contact their own agents regarding the actual price of any work to be done. It is understood and agreed that in the event of any error or omission on the part of Domicile Consulting Inc. in connection with this inspection or this report, or in the event of any claim whatsoever against Domicile Consulting Inc., that any liability of Domicile Consulting Inc., its employees, inspectors or agents shall be solely and exclusively limited to an amount no greater than the inspection fee paid. Should a claim or dispute arise relating to the inspection or to the report, Domicile Consulting Inc. shall be notified immediately in writing and shall be permitted to re-inspect the subject item. Domicile Consulting Inc. shall not be liable for differing opinions of others nor shall any claim or dispute exist to items that have been repaired or modified prior to a re-inspection of those items by Domicile Consulting Inc. Any unresolved disputes shall be submitted to and settled by binding arbitration only, in Chicago, Illinois, in accordance with the rules and regulations of the American Arbitration Association. Each covenant and agreement in this contract is a separate and independent covenant and agreement. If any term or provision shall be invalid or unenforceable, the remainder of the agreement remains valid and enforceable. The undersigned agrees to pay $ 1.00 for this inspection. SUBMITTED: IL License# Domicile Consulting Inc. Expires: 11/30/2006 THE UNDERSIGNED HAS READ AND AGREES WITH THE ABOVE AGREEMENT IN IT'S ENTIRETY: ACCEPTED: DATE: ACCEPTED: DATE: ILLINOIS HOME INSPECTOR ACT PROPERTY INSPECTION REPORT DISCLOSURE FORM
38 Dear Client, The Illinois Home Inspector License Act prohibits the inspector from disclosing any information regarding the inspection without the client's written authorization. This includes but is not limited to casual conversations or summations that may take place at the inspection as well as follow-up calls at a later date. Please take a moment to read through the following options, initial your choice/s, and sign at the bottom of the page. Provide my Real Estate Agent or Broker with any necessary information regarding the inspection. Yes No Provide the Listing Agent or the Seller with any necessary information regarding the inspection. Yes No Provide my Attorney with any necessary information regarding this inspection. Yes No Provide the Seller's Attorney with any necessary information regarding this inspection. Yes No Provide the following person/s with any necessary information regarding this inspection. Signature: Date
Inspection Report. Mr. John Homebuyer. Property Address: 123 Main Street Houston TX 77007. Front View. EDP Consulting Engineers, PLLC
Page 1 of 14 Inspection Report Mr. John Homebuyer Property Address: 123 Main Street Houston TX 77007 Front View EDP Consulting Engineers, PLLC Gerald C. Reece, PE TREC #7825 14119 Willowsong Ct Missouri
Vision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
Water Management & Damage Prevention:
Water Management & Damage Prevention: A Guide for Homeowners This article provides homeowners with basic information to make these decisions and take the appropriate actions to keep their homes dry and
Inspection Report. Condo Association. Property Address: 2222 W. Water St. Swamptown, IL. William Decker, IL Lic. # 450.0002240.
Page 1 of 21 Inspection Report Condo Association Property Address: Swamptown, IL Front View William Decker, IL Lic. # 450.0002240 Page 2 of 21 Date: 10/10/2008 Time: 1:00 PM Report ID: Sample 4 Property:
HOME INSPECTION CHECKLIST
CLOSING.COM LEARNING CENTER HOME INSPECTION CHECKLIST CONTENTS Attic 1 Balconies 1 Basement 1 Bathroom 2 Ceiling, Floors and Walls 2 Crawlspace 3 Decks and Porches 3 Doors and Windows 4 Drainage 4 Driveways
Water Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
www.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Building Owners Guide to a Duro-Last System!
Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof
Inspection Item COMMENTS
APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:
Home inspectors are not mold inspectors, however they do inspect for defects that
CONDENSATION IN THE WALLS Home inspectors are not mold inspectors, however they do inspect for defects that can result in mold. Mold grows in wet or damp environments. Defects that result in a wet or damp
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: 123 MAIN ST MIAMI, FL CLIENT: BUYER ID No: 2014193 DATE: 5/13/2014 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792
159 Morningside Avenue, Toronto
159 Morningside Avenue, Toronto Inspection Report February 6, 2013 159 Morningside Avenue, Toronto Inspection Report Overall Condition: This 60±-year-old home was extensively renovated and extended in
Home Inspection Report
4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 [email protected] Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:
Roof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls
A bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls CE 28 h Exterior finish materials are expected to protect the house from the elements while providing an attractive appearance.
Before You Start an Energy Efficiency Retrofit The Building Envelope
ABOUT YOUR HOUSE Before You Start an Energy Efficiency Retrofit The Building Envelope The building envelope is the outer layer of the building that separates the indoor living space from the outdoor environment,
Foundation. Foundation
Moisture Aside from structural concerns, the most important consideration for foundation design is moisture. No client wants a wet basement. No client wants a damp basement. No client wants mold in their
Common Problems with Walls
Common Problems with Walls Common Problems with Walls There are problems and concerns that are shared by all walls and siding installations. In this article, we will learn about the following commonly
CONDITION OF QUALITY ITEMS
CONDITION OF QUALITY ITEMS FOUNDATION Always look for moisture problems and any bulges or irregularities in the walls. Lines on the walls or floors may indicate water problems. Have these been cured? If
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
ROOFS - Guidance for Repair, Maintenance and Replacement
ROOFS - Guidance for Repair, Maintenance and Replacement Guilford Association Architectural Committee ROOFING Slate and tile roofs are a critical design feature of Guilford homes. The homes were designed
CENTER FOR ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program
CENTER FOR ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program Guidance Concerning Remediation and Prevention of Mold Growth and Water Damage in Public Schools/Buildings to Maintain Air
ROOFS, SNOW AND ICE DAMS
ROOFS, SNOW AND ICE DAMS The Problem Ice dams are a common roof performance problem in cold climate buildings. Simply put, they are ridges of ice and icicles caused by melt water from further up the roof
Inspection Report Atlanta Strip Mall Commercial Building Property Address:
Page 1 of 25 Inspection Report Atlanta Strip Mall Property Address: Smyrna GA 30082 Page 2 of 25 South East Building Consultants Ray Thoroman Serving the entire State of Georgia 6 678-410-3005 Page 3 of
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
Commercial Roof Management
Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
Accurate Home Inspection of Illinois. Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave., Westmont, Illinois
Accurate Home Inspection of Illinois 815-260-1727 1213 Norley st. Joliet, illinois 60435 [email protected] We Inspect to Protect!!! Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave.,
INSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
Roofing 101 - Signs that Your Roof Needs Repair/Replacement
By: Cherie Martel Roofing 101 - Signs that Your Roof Needs Repair/Replacement 1. Tell us a little bit about your company and its foundation. In 1963, Samuel T. Martel began a small family run roofing company,
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
Rehab Inspection Report Page 1
Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation
WET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION.
WET/DAMP BASEMENTS PROBLEM. IS THIS BASEMENT LEAKING OR COULD WE HAVE ANOTHER PROBLEM? Water line arching up on wall in corners of basement. Water collecting on concrete floor starting in corners. ANSWER:
Moisture Control. System Solutions to Prevent Mold
System Solutions to Prevent Mold How a systems approach to managing moisture is the most effective strategy for minimizing the growth of mold. Moisture Control Architects, designers, contractors and maintenance
Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
Property Inspection Report
Property Inspection Report LOCATED AT: 123 Address DFW, TX PREPARED EXCLUSIVELY FOR: Sample Report INSPECTED ON: Saturday, July 18, 2015 Inspector, Zach Faris - TREC #21548 INSPECT TX PROPERTY INSPECTION
How To Prevent Water Damage To A Home
Having inspected about 800 homes in the last four years, I have seen a lot of problems with many homes. Most of these problems are minor; however, there are some problems that are quite serious. One of
Minimizing Water Intrusion Through Roof Vents in High-Wind Regions
Minimizing Water Intrusion Through Roof Vents in High-Wind Regions http://www.fema.gov HURRICANE IKE RECOVERY ADVISORY Purpose: To recommend practices for minimizing water intrusion through roof vent systems
March 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202
Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Re: Prospector s Point Walkway/Façade Repairs Martin/Martin, Inc Project No.: 13.0358.S.02 Ms. McDonald: Per your request
bout your HOUSE before you start Renovating Your Basement Moisture Problems
A bout your HOUSE before you start Renovating Your Basement Moisture Problems CE 28 c Condensation of cold surfaces, efflorescence Water leak in corner on floor Mold and decay on floor joists and sill
HEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 [email protected]
HEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 [email protected] 2007 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas
5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 [email protected] INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction
Prestige Home Inspection LLC
Cover Page Prestige Home Inspection LLC IAC2/ESA - Mold Assessment and Water Damage Report 555 W. Brook ave., Client's town MI, 48059 Inspection prepared for: Client's name Inspection Date: 10/15/2012
Inspection Report. Jacksonville Krystals Inspection. Property Address: Downtown. Jacksonville FL 32204. South East Building Consultants
Page 1 of 53 Inspection Report Jacksonville Property Address: Jacksonville FL 32204 South East Building Consultants Ray Thoroman Inspecting Jacksonville FL and entire South East Page 2 of 53 Table of Contents
CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer
Self-Home Inspection Checklist
To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional
ELIGIBLE REPAIR PROJECT PARAMETERS
THE DISTRICT MUNICIPALITY OF MUSKOKA ONTARIO RENOVATES PROGRAM FOR HOMEOWNERS ELIGIBLE REPAIR PROJECT PARAMETERS 1. To have your project considered and payment processed, all projects requiring a Building
201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE
STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,
Date: March 7, 2006 Report for [removed]
Date: March 7, 2006 Report for [removed] The Preservation Resource Center Of New Orleans, in conjunction the National Trust for Historic Preservation, has conducted a condition survey of your property.
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
May 5, 2010. Client Client Address. Re: Inspection Address, Chicago, Illinois. Dear Mr. Client,
PROPERTY INSPECTION PROFESSIONALS May 5, 2010 Client Client Address Re: Inspection Address, Chicago, Illinois Dear Mr. Client, On May 4, 2010, Tomacor completed a property inspection of the above referenced
bout your house before you start Renovating Your Basement Moisture Problems
A bout your house CE 28c before you start Renovating Your Basement Moisture Problems Mold and decay on floor joists and sill plates Stuffy air, high humidity, poor air circulation Water draining in from
RRIO Checklist. Use of checklist: Definitions: Limitations
CITY OF SEATTLE RENTAL REGISTRATION AND INSPECTION ORDINANCE (RRIO) RRIO Checklist Use of checklist: Property owners will use the RRIO Checklist to confirm that their rental housing properties and units
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building
South Carolina Home Inspector Standards of Practice
South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the Residential Home Inspector and outline what the Residential Home Inspector should observe, identify,
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared
MOISTURE MANAGEMENT DURING THE CONSTRUCTION PROCESS
MOISTURE MANAGEMENT DURING THE CONSTRUCTION PROCESS Ed Light 1,*, James Bailey 1, and Roger Gay 1 1 Building Dynamics, LLC, Ashton, MD (USA) *Corresponding email: [email protected] Published
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: Somewhere, FL CLIENT: GAIA GC ID No: 2015000 DATE: 12/31/2015 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792 FLORIDA
Roof Inspection. Summary Report
Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:
Exterior Repair Project. By: Kami Farahmandpour, PE, RRC, RWC, CCS, CCCA Alex Szatanek. Building Technology Consultants, PC BTC
Exterior Repair Project Glen Ellyn Public Library By: Kami Farahmandpour, PE, RRC, RWC, CCS, CCCA Alex Szatanek Outline 2010 and 2011 Roof Replacement and Facade Repair Project Review Primary Reasons for
Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing
1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize
Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000
Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,
Non Invasive Roof Leak Detection Using Infrared Thermography
Non Invasive Roof Leak Detection Using Infrared Thermography Scott Wood Four Star Cleaning and Restoration, Inc. ABSTRACT Residential roofs without attics are typically inspected for leaks by installing
Waterproofing and interior insulation for basements takes new twist in technology.
Waterproofing and interior insulation for basements takes new twist in technology. Free report reveals how to stop all call backs for basements for the life of the structure by installing these 3 low cost
Old Dominion University Mold Management Plan
OFFICE OF ENVIRONMENTAL HEALTH AND SAFETY 5255 Hampton Blvd. Spong Hall, suite 2501 Norfolk, Virginia 23529 Phone: (757) 683-4495 Fax: (757) 683-6025 Occupational Safety & Health Environmental Health Laboratory
Renovating Your Basement
building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:
Repair of Spalling and Leaking Clay Brick Building Walls
B etter buildings Repair of Spalling and Leaking Clay Brick Building Walls Overview A few years after being built in Waterloo in 1980, a condominium of three, six-storey buildings showed severe spalling
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
How To Repair A House
Assessing Structural Damages Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case
Total Home Inspection Checklist
Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
Home Warranty Inspection Report
Scope of the Inspection 1111 Sample Dr. home warranty inspection 2/30/2006 Home Warranty Inspection Report 1111 Sample Dr., Detroit, MI 48223 Inspection Date: February 30, 2006 Client: Alfred E. Neumann
EAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
Structural Assessment Report
Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive
PROFESSIONAL ENGINEERING INSPECTIONS, INC.
PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 Registered Engineering Firm #1503 http://www.profengineering.com (713) 664-1264 July 8, 2004 Mr. Simple Samson 2831 Octoberfest
bout your HOUSE before you start Renovating Your Basement Structural Issues And Soil conditions
A bout your HOUSE before you start Renovating Your Basement Structural Issues And Soil conditions CE 28 b Ground slopes towards window well No granular fill or connection to footing drain Ground floor
Sun Windows General Information Sun New Construction Window Installation Instructions
Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten
Structure Survey Findings:
Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,
Property Condition Assessment
Property Condition Assessment Business, Wisconsin Inspection Date: 8/2009 Prepared For: Business Owner Report Number: TD999909 Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
Finegan Inspection Services, Inc.
Finegan Inspection Services, Inc. Report Prepared For: Phone 513-683-0733 Fa 513-697-0163 Owners Property Address City, State, ZIP Phone FAX Owners Realtor Realty Company Phone FAX OWNER INFORMATION PROPERTY
Attic condensation during winter can
Housing Fact Sheet Causes and Cures of Attic Condensation and Roof Ice Damming Problems Attic condensation during winter can decrease the effectiveness of insulation and over time can cause significant
Why is my air conditioner dripping on my customers?
De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These
Inspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668
Inspection Report Property Address: 123 Dream Home Way Frisco, CO 80443 Prepared for: Inspector: Tim Nixon Tim Nixon Inspection date: 3/28/2014 1 of 9 General Information Property Information Address:
HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 [email protected]
HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 [email protected], 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money
EASY$ TIP SHEETS Energy Advice Saving Yukoners Money Quick Links How to check for leaks Draftproofing products Sealants Draft proofing your home Draftproofing can be a cost-effective measure you take to
Bituminous Sheet Flat Roofs: Their repair and maintenance
Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and
CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS
TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes
3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations
3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations Any penetration through the stucco that is left unsealed will allow entry of moisture. Even an average size home can have an extreme
New Jersey Property Inspections LLC NJ State Home Inspector License # 24GI00105100 27 Neshanic Drive, Ringoes NJ 08551 908-642-2112/908-788-0055
New Jersey Property Inspections LLC NJ State Home Inspector License # 24GI00105100 27 Neshanic Drive, Ringoes NJ 08551 908-642-2112/908-788-0055 PRE-INPECTION AGREEMENT READ THIS DOCUMENT CAREFULLY. IT
HomeSpec REPORT SUMMARY
HomeSpec 04/25/2007 Ms. Rachel Trujeque Re: 13038 West Plum Road Lot #1225 - Peoria, AZ. 85383 - Pre Drywall Inspection Dear Ms. Trujeque, At your request, a visual pre drywall inspection of the above