Definition: Balanced System
|
|
- Judith Dixon
- 7 years ago
- Views:
Transcription
1 Definition: Balanced System A BALANCED SYSTEM A balanced system in water side terms can be defined as one in which the terminal unit flow rates are adequate, under design circumstances, to maintain satisfactory heat transfer capability. Source: ASHRAE Systems Handbook
2 Definition: Manual Balancing A manual balance valve creates a fixed resistance in a circuit to insure design flow to all heat transfer devices in the system under full load conditions, usually by throttling flow. Fluid takes the path of least resistance so we have to force water out to the end of the piping circuit, and select a pump to overcome that head loss.
3 MANUAL BALANCING Circuit Setter Type (Manual)
4 MANUAL BALANCING Venturi Type (Manual) (Ball Valve for Throttling Purposes) Manually Adjusted by TAB Contractor Pressure and Temperature Ports Integral Ball Valve Type
5 MANUAL BALANCING Spring for mechanical play tightening Handwheel with digital indication (80 setting positions) Draining kit can be installed during operation 5
6 Definition: Automatic Flow Control AUTOMATIC FLOW CONTROL: A balancing device that prevents the flow rate from exceeding design flow, while absorbing dynamic pressure changes in the system. Real function is to act as a FLOW LIMITING DEVICE
7 Automatic Balancing CARTRIDGE / PISTON Various sizes available from 1/2 3 Accuracy ± 5 percent
8 Limitations In a Variable Flow System with Modulating Control. Neither Balancing Valve Allows us To:
9 Definition: Balanced System A BALANCED SYSTEM A balanced system in water side terms can be defined as one in which the terminal units receive the required flow rates under all operating conditions to maintain maximum heat transfer capability.
10 Definition: Balanced System A BALANCED SYSTEM A balanced system in water side terms can be defined as one in which the terminal unit flow rates are adequate, under design circumstances, to maintain satisfactory heat transfer capability. Source: ASHRAE Systems Handbook
11 Balancing for Variable Flow Systems Variable Speed Drive Sensor Placement Valve Authority Balancing
12 PUMPING COSTS VARIABLE SPEED PUMPS REDUCE PUMPING COSTS BY AVOIDING AN INCREASE OF THE PUMP HEAD WHEN THE FLOW DIMINISHES. Cost ~ Pump Head x Flow Pump head Pump head Savings Flow Flow
13 VARIABLE SPEED PUMPS H H Flow Flow H Flow
14 DIRECT MEASURE OF THE PUMP HEAD? ΔP A ΔP sensor is used to measure the pump head. At the location of the ΔP sensor, the available pressure will be kept constant. Where is the best location?
15 DP SENSOR AT THE END OF THE CIRCUIT ΔP Maximum pump energy saving When control valves shut, there is not enough available pressure for the first circuits. ΔP Is this the best location?
16 DP SENSOR AT THE MIDDLE OF THE CIRCUIT ΔP Improved situation The first unit does not receive enough pressure at low flow (when control valves shut). ΔP Is this a problem?
17 DP SENSOR AT THE BEGINNING OF THE CIRCUIT ΔP Best mode from operating condition point of view? Available pressure is always high enough for all circuits and for all operating conditions. ΔP
18 BASIC SYSTEM & DESIGN ASSUMPTIONS Control valve Delta P equal to coil Delta P Head Loss through each coil is identical for each circuit at 4 psi Balance Valve at index circuit has 2 psi Maximum Delta P of pump 40 psi DP Transmitter on index circuit 10 psi Each Circuit Has Design Flow of 100 gpm
19 APPLICATION BASIC SYSTEM DP Pressure Differential Sensor Circuit 4 10 psi Coil # gpm Δp=4 psi 10 psi Circuit 3 20 psi Coil #3 Circuit 2 30 psi Coil #2 30 psi Circuit 1 40 psi Coil #1 40 psi VFD Pump Chiller
20 CALCULATE BALANCE VALVE PRESSURE DROP TO OBTAIN DESIRED DESIGN CONDITION Circuit 1 = (40-4-4) = 32 psid Circuit 2 = (30-4-4) = 22 psid Circuit 3 = (20-4-4) = 18 psid Circuit 4 = (10-4-4) = 2 psid
21 APPLICATION BASIC SYSTEM DP Pressure Differential Sensor Circuit 4 10 psi 2 psi Coil # gpm Δp=4 psi 10 psi Circuit 3 20 psi 12 psi Coil #3 Circuit 2 30 psi 22 psi Coil #2 30 psi Circuit 1 40 psi 32 psi Coil #1 40 psi VFD Pump Chiller
22 CALCULATE CIRCUIT Cv Cv = GPM/ P Circuit gpm@ 40 psid = 15.9 Circuit gpm@ 30 psid = 18.2 Circuit gpm@ 20 psid = 22.2 Circuit gpm@ 10 psid = 31.3
23 APPLICATION BASIC SYSTEM Circuit 4 10 psi DP Pressure Differential Sensor Δp=2 psi Coil # gpm Δp=4 psi 10 psi Cv=31.3 Circuit 3 20 psi Δp=18 psi Coil #3 20 psi Cv=22.2 Circuit 2 30 psi Δp=22 psi Coil #2 30 psi Cv=18.2 Circuit 1 40 psi Δp=32 psi Coil #1 40 psi Cv=15.9 VFD Pump Chiller
24 DESIGN PROBLEM DESIGN PROBLEM It is possible to STARVE the coil closest to the pump under partial load conditions
25 HOW?? Low flow In Circuits 2 through 4 would result in Delta P in Circuit 1 being not much more than DP trasmitter setting of 10 psi 10 psi Cv= psi Cv= 22.2 Circuit 1 Cv = 15.9 OR SQRT(10/40) 30 psi Cv= psi Cv= 15.9
26 APPLICATION BASIC SYSTEM Circuit 4 10 psi DP Pressure Differential Sensor Δp=2 psi Coil # gpm Δp=4 psi 10 psi Cv= 31.3 Circuit 3 20 psi Δp=12 psi Coil #3 20 psi Cv= 22.2 Circuit 2 30 psi Δp=22 psi Coil #2 Circuit 1 40 psi VFD Pump Δp=32 psi Coil #1 Chiller 40 psi Cv= X 10 = 51 gpm
27 MANUAL BALANCE Circuit FLOW At DP Setting 10 PSID FLOW At Max DP Cv@10 PSID = 51 GPM 100% Cv@10 PSID = 58 GPM 100% Cv@10 PSID = 71 GPM 100% Cv@10 PSID = 100 GPM 100%
28 SO HOW MIGHT THIS PROBLEM BE FIXED
29 System Corrections INCREASE SENSOR SETTING
30 APPLICATION BASIC SYSTEM Circuit 4 10 psi 20 Pressure Differential PSI Sensor Δp=2 psi Coil # gpm Δp=4 psi 10 psi Cv= 31.3 Circuit 3 20 psi Δp=12 psi Coil #3 20 psi Cv= 22.2 Circuit 2 30 psi Δp=22 psi Coil #2 Circuit 1 40 psi VFD Pump Δp=32 psi Coil #1 Chiller 40 psi Cv= X 20 = 71 gpm
31 System Corrections MOVE SENSOR
32 APPLICATION BASIC SYSTEM Circuit 4 10 psi DP Pressure Differential Sensor Δp=2 psi Coil # gpm Δp=4 psi 10 psi Cv= 31.3 Circuit 3 20 psi Δp=12 psi Coil #3 20 psi Cv= 22.2 Circuit 2 30 psi Δp=22 psi Coil #2 Circuit 1 40 psi VFD Pump Δp=32 psi Coil #1 Chiller 40 psi Cv= X 20 = 71 gpm
33 System Corrections ADD MULTIPLE SENSORS
34 APPLICATION BASIC SYSTEM Circuit 4 10 psi DP Pressure Differential Sensor Δp=2 psi Coil # gpm Δp=4 psi 10 psi Cv= 31.3 Circuit 3 20 psi Δp=12 psi Coil #3 20 psi Cv= 22.2 Circuit 2 30 psi Δp=22 psi Coil #2 Circuit 1 40 psi VFD Pump Δp=32 psi Coil #1 Chiller 40 psi Cv= X 40 = 100 gpm
35 System Corrections REDUCE FRICTION LOSS IN DISTRIBUTION PIPING
36 APPLICATION BASIC SYSTEM Circuit 4 10 psi DP Pressure Differential Sensor Δp=2 psi Coil # gpm Δp=4 psi 10 psi Cv= 31.3 Circuit 3 20 psi Δp=12 psi Coil #3 20 psi Cv= 22.2 Circuit 2 30 psi Δp=22 psi Coil #2 Circuit 1 40 psi VFD Pump Δp=32 psi Coil #1 Chiller 40 psi Cv= X 10 = 51 gpm
37 Pipe sizing Criteria for sizing pipes are different from country to country but all have a common basis: Using small pipe sizes decreases the investment cost but increases the pumping costs, circulation noise and Dp variations with the load. Low circulation velocities cause deposit of heavier particles that can cause clogging by accumulation. Particle transport creates other problems for equipments where high circulation velocities are used. Consequently the generally used procedure consists in selecting the smallest pipe size that satisfies both a maximum linear pressure drop and a maximum velocity: Max linear pressure drop is around: Scandinavia Eastern Europe Western Europe China USA 100 Pa/m Pa/m Pa/m Pa/m 400 Pa/m Max velocities are usually between 1 and 2 m/s. For noise reasons, a maximum velocity of 0.5 m/s is considered inside residential buildings in some countries. In USA, the maximum velocity can be up to 3 m/s in large pipes. 37
38 WHAT WOULD BE THE WORST POSSIBLE SOLUTION TO THE PROBLEM
39 APPLICATION BASIC SYSTEM Circuit 4 10 psi DP Pressure Differential Sensor Δp=2 psi Coil # gpm Δp=4 psi 10 psi Cv= 31.3 Circuit 3 20 psi Δp=12 psi Coil #3 20 psi Cv= 22.2 Circuit 2 30 psi Δp=22 psi Coil #2 Circuit 1 40 psi VFD Pump Δp=32 psi Coil #1 Chiller 40 psi Cv= X 10 = 51 gpm
40 WHY NOT ELIMINATE THE BALANCE VALVE?
41 ASSUMPTION NO. 1 NO CHANGE TO THE CONTROL VALVES SAME Cv and DESIGN PRESSURE DROP
42 APPLICATION BASIC SYSTEM Circuit 4 8 psi DP Pressure Differential Sensor Δp=0 psi Coil # gpm Δp=4 psi 8psi Circuit 3 18 psi Δp=0psi Coil #3 18 psi Circuit 2 28 psi Δp=0 psi Coil #2 Circuit 1 38 psi VFD Pump Δp=0psi Coil #1 Δp= 19 psi Chiller Δp= 19 psi 38 psi 50 X 19 = 218 gpm
43 Assumption No 2 SIZE THE CONTROL VALVE TO COMPENSATE FOR THE REQIUIRED PRESSURE DROP OF BALANCE VALVE AT DESIGN FLOW
44 APPLICATION BASIC SYSTEM Circuit 4 8 psi DP Pressure Differential Sensor Δp=0 psi Coil # gpm Δp=4 psi Cv=50 8psi Circuit 3 18 psi Δp=0psi Coil #3 Δp= 14 psi Cv= psi Circuit 2 28 psi Δp=0 psi Coil #2 Δp= 24 psi Cv=20.44 Circuit 1 38 psi VFD Pump Δp=0psi Coil #1 Chiller Δp= 34 psi Cv= psi 16.2X 8 = 46 gpm
45 Why Not EliminateThe Balance Valve? Assumption No 1 No change in the design pressure drop of the control valve will result in immediate overflow at coils closest to the pump and potential underflow in coils further from the pump especially at start up. Other issues might include low delta T and noise due to excessive velocities. Assumption No 2 A change in design pressure drop of the control valve in theory could balance the system at design flow but we still experience issues with starving coils closest to pump under part load. Although in theory it is possible to balance by changing design pressure drop/ Cv of each control valve, the reality is that most manufactures do not offer multiple Cv s to match design flows. Every control valve would have a different Cv.
46 SO WHAT OTHER OPTIONS MIGHT WE HAVE?
47 AutoFlow AUTOFLOW
48 APPLICATION BASIC SYSTEM Circuit 4 10 psi DP Pressure Differential Sensor Δp=2 psi Coil # gpm Δp=4 psi 10 psi Cv= Variable Circuit 3 20 psi Δp=12 psi Coil #3 20 psi Cv= Variable Circuit 2 30 psi Δp=22 psi Coil #2 30 psi Cv= Variable Circuit 1 40 psi VFD Pump Δp=32 psi Coil #1 Chiller 40 psi Cv= Variable 31.6 x 10 = 100 gpm
49 Automatic Balancing
50 Automatic Balancing
51 Automatic Balancing
52 Automatic Balancing
53 Commercial - small part but key effect Balancing valves cost less than 1% of project cost yet massively effect performance of all major equipment Chillers Cooling Towers Pumps Control System AHUs & FCUs Air Duct 2 way valves Pipe & General fittings Contracting Labour Consulting Balancing Valves
54 WHAT HAVE WE STILL OVERLOOKED?
55 VALVE AUTHORITY
56 WHAT IS VALVE AUTHORITY? WHAT HAPPENS IF WE HAVE POOR VALVE AUTHORITY?
57 Valve Authority - A A = the ratio of the ΔP across the control valve when it is wide open as a percentage of the ΔP across total branch or control valve closed The higher the authority the better - ASHRAE Systems Handbook and most control valve manuals recommend that it be 25 to 50% for HVAC applications
58 2-WAY CONTROL VALVE AUTHORITY Control valve authority should not be lower than 0.25 Control valves and controllability
59 STANDARD APPLICATION WITH 2-WAY VALVES AND MANUAL BALANCE VALVES Circuit 4 10 psi DP Pressure Differential Sensor Δp=2 psi Coil # gpm Δp=4 psi Authority A = 4/10 = 0.4 Circuit 3 20 psi Δp=12 psi Coil #3 A = 4/20 = 0.2 Circuit 2 30 psi Δp=22 psi Coil #2 A = 4/30 = 0.14 Circuit 1 40 psi Δp=32 psi Coil #1 A = 4/40 = 0.1 VFD Pump Chiller
60 Sizing with Authority Method Circuit 4 10 psi DP Pressure Differential Sensor Δp=2 psi Coil # gpm Δp=4 psi Authority A = 4/10 = 0.4 Circuit 3 20 psi Δp=6 psi Coil #3 Δp= 10 psi A = 10/20 = 0.5 Circuit 2 30 psi Δp=16 psi Coil #2 Δp= 10 psi A = 10/30 = 0.33 Circuit 1 40 psi Δp=26 psi Coil #1 Δp= 10 psi A = 10/40 = 0.25 VFD Pump Chiller
61 Sizing with Authority Method If we sized control valves for proper valve authority We may still not achieve design flow on coils closest to pump, even with AutoFlow
62 Sizing with Authority Method BUT We achieve approximately 90% heat transfer under worst conditions We maximize pump savings by turning down pump head under low flow conditions from 40 psi to 10 psi We actually improve valve authority in most circuits at part load I assumed some one would actually go through the process of calculating Cv s for each control valve
63 Alternative ALTERNATIVE PRESSURE INDEPENDENT CONTROL
64 Total Flow Control Match the flow to the load in every heat transfer device at all operating points, without excess flow Eliminate Low Delta T s Maximize Turndown on V/S Pumps Eliminate Flow Starvation at Coils Minimize Energy Usage
65 Pressure Independent Control Technically the best solution for controllability Regulator combined valves constitute an excellent alternative
66 PICV Overview H1=H2 H2 L2 L1 L3 H1 Ball Valve Design
67 50% Flow = 80% Heat Transfer
68 Dp stabilization on a control valve CONVERT ATC TO PRESSURE INDEPENDENT YC DA 516
69 Differential pressure controllers In order to preserve the authority of the control valves, limit noise close-off problems, a Dp controller is installed at the start of circuits.
70 70 Dp control at the inlet of buildings (sub-stations) YC DA 516 Sub-stations
71 Dp control per branch/floor 71 YC One Δp controller for each branch DA 5156 Excellent performance/cost ratio.
72 Forces in inline Dp controller Sm p1 p2 Fs p2 p3 p1 - pressure upstream the load p2 pressure downstream the load (taken inside the DP controller) p3 pressure downstream DP controller Fs spring force Sm diaphragm surface / area Equation: Δp = p1 p2 = Fs / Sm Only the seat moves, while plug is fixed, so p3 does not play the part in equation
73 Production and Distribution PRODUCTION AND DISTRIBUTION
74 Compatibility between flows false solutions "Pushing" the distribution pump as a reaction to complaints makes the problem worse It increases the flow incompatibility and therefore the mixing Supply water temperature increases further in cooling and decreases further in heating 150% 200% % 100% % A 150% 100% A 200% 50 Need of balancing in 74
75 Compatibility between flows false solutions Adding a production unit possibly solves compatibility issue but at the cost of an unnecessary production unit It is not a good solution because the problem is not a problem of lack of installed capacity, it is a problem of too high flow in the distribution 150% 150% 50% 0% 100% 150% 150% 150% Need of balancing in 75
76 Compatibility between flows false solutions Decreasing the set-point of the production unit can compensate for the incompatibility but at the cost of higher energy consumption 150% 150% % 50% C 100% A 150% 100% A 150% Need of balancing in 76
77
78
Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009
Applying Pressure Independent Control Valves in H.V.A.C. Systems A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 1 Introduction I know, as building design consultants, so much of your effort
More informationFrequently Asked Questions
Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.
More informationA u t o m at i c B a l a n c i n g
A u t oflow A u t o m at i c B a l a n c i n g B e n e f i t s o f A u t o m at i c B a l a n c i n g System equipment, such as chillers and individual terminal units, is the heart of any HVAC system.
More informationBuilding Performance With District Cooling
Reprinting this proof for distribution or posting on web sites is not permitted. Authors may request permission to reprint or post on their web site once the fi nal version has been published. A reprint
More informationMichael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.
ASGMT / Averaging Pitot Tube Flow Measurement Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc. Averaging Pitot Tube Meters Introduction
More informationThe Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control
The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control Chenggang Liu Research Associate Homer L. Bruner, Jr., CEM Mechanical Systems
More informationChokes. Types Reasons Basics of Operations Application
Chokes Types Reasons Basics of Operations Application Most Common Chokes Positive: Fixed orifice Disassemble to change bean Adjustable Provides variable orifice size through external adjustment Schematic
More informationDemand Based Static Pressure Reset Control for Laboratories
LLC Demand Based Static Pressure Reset Control for Laboratories Laboratories are generally the largest users of energy in any facility. Whether in a pharmaceutical research facility, a university or a
More informationCommissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
More informationCALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB
Compact automatic flow rate regulator with polymer cartridge 127 series REGISTERED BS EN ISO 9001:2000 Cert. n FM 21654 UNI EN ISO 9001:2000 Cert. n 0003 CALEFFI 01166/09 GB Function The AUTOFLOW devices
More informationMaterial taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001
Pressure Control Chapter 3 Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001 Introduction Pressure control is a key element in the design of any circuit. Used correctly, it can
More informationTadahiro Yasuda. Introduction. Overview of Criterion D200. Feature Article
F e a t u r e A r t i c l e Feature Article Development of a High Accuracy, Fast Response Mass Flow Module Utilizing Pressure Measurement with a Laminar Flow Element (Resistive Element) Criterion D200
More informationHVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
More informationKU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
More informationPressure Drop Basics & Valve Sizing
Pressure Drop Basics & Valve Sizing What is Pressure Drop? The difference in pressure between two points in a system, caused by resistance to flow. What Pressure Drop is Not? Pressure drop is pressure
More informationNEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
More informationAeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson
Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology HWEA 2011 Conference Craig S. Johnson Presentation Overview Introduction Aeration Air & Digester gas challenges Gas flow metering
More informationHIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants
HIGH PERFORMANCE CHILLED WATER SYSTEMS EarthWise HVAC Simon Ho e: Simon.Ho@irco.com 2012 EarthWise HVAC High Performance CHW Plants Low Flow Low Temperature Systems Variable Flow Systems Variable CHW Variable
More informationCOUNTERBALANCE VALVES
COUNTERBALANCE VALVES Introduction They are modulating valves which allow free flow into the actuator and then block the reverse flow until they feel a pilot pressure inversely proportional to the load
More informationLECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS
LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS 1. Define an accumulator and explain its function A hydraulic accumulator is a device that stores the potential energy of an incompressible fluid
More informationCHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute
More informationPRESSURE REDUCER AND RELIEF VALVES WITH METALLIC BELLOW FOR WATER STEAM
PRESSURE REDUCER AND RELIEF VALVES WITH METALLIC BELLOW FOR WATER STEAM PRESSURE REDUCER AND RELIEF VALVES These devices are used to reduce and control a gaseous flow pressure (air, steam, gas ). The PRESSURE
More informationCentrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
More informationChilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationIDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.
IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION. Pre-Project Details Hawaiian Community College Campus consisting of 16 individual buildings totaling 308,000 sq.ft of conditioned space.
More informationHow To Design A Refrigeration System
AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison
More informationVAD. Variable Area Desuperheaters
Desuperheater overview Steam used in process plants can be superheated, that is, heated to a temperature above saturation. The excess of temperature above its saturation is called 'superheat'. Desuperheated
More informationBERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features
Pressure Relief/Sustaining Valve Prioritizing pressure zones Ensuring controlled pipeline fill-up Preventing pipeline emptying Pump overload & cavitation protection Safeguarding pump minimum flow Excessive
More informationPressure and Temperature Controls
Pressure and Controls Pressure Reducing Armstrong pressure reducing valves (PRVs) and temperature regulators help you manage steam, air and liquid systems safely and efficiently. And assure uninterrupted
More informationWhy and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
More informationTheory, Application, and Sizing of Air Valves
Theory, Application, and Sizing of Air Valves VAL-MATIC VALVE AND MANUFACTURING CORP. 905 RIVERSIDE DRIVE, ELMHURST, IL 60126 TEL. (630) 941-7600 FAX. (630) 941-8042 www.valmatic.com 1 THEORY, APPLICATION,
More informationSECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
More informationSPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
More informationFlow Measurement Options for Pipeline and Open Channel Flow
Flow Measurement Options for Pipeline and Open Channel Flow October 2013 Presented by Molly Skorpik - 2013 Montana Association of Dam and Canal Systems Conference Irrigation Training and Research Center
More informationConversion From Constant Flow System To Variable Flow
White Paper Conversion From Constant Flow System To Variable Flow By: Tony Egan 94.21-4/29/2010 www.armstrongintegrated.com S.A. Armstrong Limited 2010 S.A. Armstrong Limited 23 Bertrand Avenue Toronto,
More informationImpacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
More informationChilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates
Chilled Water System Commissioning: Variable Primary Flow John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. History of chilled water system configurations
More informationPressure Relief and Regulating Valves
Pressure Relief and Regulating Valves With blocked center directional valves and variable displacement pumps, or open center directional valves and fixed displacement pumps where fast response, low leakage
More informationBALANCING OF CONTROL LOOPS
1 BALANING OF ONTROL LOOPS A manual for getting the correct function of 23 conol loops used in hydronic heating and cooling systems. Here we must have a new picture. asselden Place, Melbourne, Ausalia
More informationCentral Plant Air Systems: Keeping the Heart and. Title Style. Better Buildings Summit May 2016
Central Plant Air Systems: Keeping the Heart and Click Lungs To Healthy Edit Master Title Style Better Buildings Summit May 2016 Introductions Michael Deru National Renewable Energy Laboratory New Resources
More informationEnergy and Flow Measurement for Hydronic Systems
Energy and Flow Measurement for Hydronic Systems Presented By: George Szyszko Applications Consultant MCR for ONICON Incorporated Why Measure Thermal Energy? To control something, you must first measure
More informationWater cooled chiller plant (cp/vs)
Data Center Water cooled chiller plant (cp/vs) Design Envelope File No: 9.573 Date: december 16, 2014 Supersedes: 9.573 Date: november 14, 2014 design envelope s performance improvements are among the
More informationIn-Line Air Separators
Air Elimination & Control In-Line Air Separators The AC models of air separators deliver all the quality and performance you expect from Taco products. They are built to last with shell, heads and ANSI
More informationOverview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
More informationInstallation and Commissioning Manual Solar Stations FlowCon Max Evolution II
Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II 1 For your safety Table of Contents 1 For your safety... 3 1.1 About this manual... 3 1.2 Designated use... 3 1.3 Qualification
More information- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
More informationTOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump?
KNOWLEDGE: K1.01 [3.3/3.5] P21 Which one of the following contains indications of cavitation in an operating centrifugal pump? A. Low flow rate with low discharge pressure. B. Low flow rate with high discharge
More informationAccurate Air Flow Measurement in Electronics Cooling
Accurate Air Flow Measurement in Electronics Cooling Joachim Preiss, Raouf Ismail Cambridge AccuSense, Inc. E-mail: info@degreec.com Air is the most commonly used medium to remove heat from electronics
More informationCCI 100 DPC DRAG Wellhead Production Choke Valve
CCI 100 DPC DRAG Wellhead Production Choke Valve 2 Severe service DRAG choke valve delivers precise wellhead pressure control with superior reliability and life. Improves well production time Enhances
More informationCHILLED WATER PLANT PUMPING SCHEMES. James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa
CHILLED WATER PLANT PUMPING SCHEMES James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa ABSTRACT From the advent of central chilled water plants, the system for delivering chilled water to
More informationSECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
More informationVAL-MATIC VALVE AND MANUFACTURING CORP. 905 RIVERSIDE DRIVE, ELMHURST, IL 60126 TEL. (630) 941-7600 FAX.
Cavitation in Valves VAL-MATIC VALVE AND MANUFACTURING CORP. 905 RIVERSIDE DRIVE, ELMHURST, IL 60126 TEL. (630) 941-7600 FAX. (630) 941-8042 www.valmatic.com CAVITATION IN VALVES INTRODUCTION Cavitation
More informationAKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS
AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS Products Include: 60 gpm eductors Style 3060, 3061, 3062 & 3070 95 gpm eductors Style
More informationAIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
More information85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
More informationPrincipals of Condensing Boiler System Design
Principals of Condensing Boiler System Design Dennis Jones, P.E. Member ASHRAE ABSTRACT Condensing boilers can provide significant energy savings due to operating efficiencies as high as 98% as compared
More informationDaniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008.
DAN-LIQ-TG-44-rev0208 February 2008 Daniel Liquid Control Valves Technical Guide www.daniel.com Daniel Measurement and Control Theory, Principle of Operation and Applications This brochure has been prepared
More informationREAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center hansenkl@unmc.edu 402-559- 5301 402-630-
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More informationIn-Line Filters and Coalescers with Automatic Drains
Instructions/Parts In-Line Filters and Coalescers with Automatic Drains 310611G EN Air Filter with Automatic Drain Part No. 22601, Series B Maintenance To maintain maximum filtering efficiency and to avoid
More informationIrrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology. Public Utility District No. 1 of Chelan County
Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology Public Utility District No. 1 of Chelan County This paper describes how to calculate energy saved by installing a variable
More informationTexas State University Utility Analysis. Sheri Lara, CEM, CEFP Texas State University Morgan Stinson, PE, LEED AP - EEA Todd Schmitt, PE, LEED AP EEA
Texas State University Utility Analysis Sheri Lara, CEM, CEFP Texas State University Morgan Stinson, PE, LEED AP - EEA Todd Schmitt, PE, LEED AP EEA Texas State University - San Marcos The rising STAR
More informationCalifornia Solar Initiative (CSI) Thermal Program Metering Installation Guide
California Solar Initiative (CSI) Thermal Program Metering Installation Guide Purpose: The purpose of this metering installation guide is to provide participating eligible contractors in the CSI-Thermal
More informationTaco Hydronic System Solutions Quick Start Guide
QUICK START GUIDE Taco Hydronic System Solutions Quick Start Guide Contents Help Resources...3 Introduction...4 Taco Hydronic System Solutions Work Screen Introduction...5 The basics...6 Getting Started
More informationComparing Energy Savings of Different VAV Systems
Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationOptimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
More informationTHE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT
THE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT Kazuto Otakane, Tokyo Gas Co., Ltd Katsuhito Sakai, Tokyo Gas Co., Ltd Minoru Seto, Tokyo Gas Co., Ltd 1. INTRODUCTION Tokyo Gas s new gas meter,
More informationThe Secret of Hydraulic Schematics. BTPHydraulics www.iranfluidpower.com
The Secret of Hydraulic Schematics BTPHydraulics www.iranfluidpower.com www.iranfluidpower.com Table of Contents The Secret to Reading and Interpreting Hydraulic Schematics... 1 Hydraulic System Schematics...
More informationAPC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
More informationVAD Variable Area Desuperheaters
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
More informationMustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components
Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE
More informationFlowLine Controls. An Engineer's Guide for Sizing and Specifying Pressure Independent Control Valves for Building Services
FlowLine Controls An Engineer's Guide for Sizing and Specifying Pressure Independent Control Valves for Building Services Fadi Alameddine Al Gunnarson Date: 01/10/08 I. Introduction Pressure Independent
More informationHeating Water by Direct Steam Injection
Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space
More informationC. starting positive displacement pumps with the discharge valve closed.
KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the
More informationHydraulic Trouble Shooting
Hydraulic Trouble Shooting Hydraulic systems can be very simple, such as a hand pump pumping up a small hydraulic jack, or very complex, with several pumps, complex valving, accumulators, and many cylinders
More informationASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International
ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International Presentation Overview Water Heater Piping Strategies How to size a water heater?
More informationExample Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
More informationWater Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling
Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle
More informationENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS
ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS Many mechanical energy systems are devoted to transfer of energy between two points: the source or prime mover (input) and the load (output). For chemical
More informationData Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
More informationTake the complication out of cooling. Data center cooling equipment and service from Alfa Laval
Take the complication out of cooling Data center cooling equipment and service from Alfa Laval How to make cooling less complicated As data grows, so does the demand for new data centers with increased
More information1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
More informationLife Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany
Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment
More informationTable V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
More informationOperational Overview and Controls Guide
DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)
More informationBULLETIN NO. TEH-908. Bell & Gossett R T. Hydronic System Design with the Bell & Gossett System Syzer / ON GPM FLOW
2000 BULLETIN NO. TEH-8 Bell & Gossett Hydronic System Design with the Bell & Gossett System Syzer 2 T 3 4 AT R T DIF URE TEMPERA 5 6 2M 7 8 9 10 3M 1 1M 800 600 0 400 GPM/T / ON GPM FLOW P PIPING FRICTION
More informationENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
More informationMechanical Seal Piping Plans
Mechanical Seal Piping Plans Single Seals plans 01, 02, 03, 11, 13, 14, 21, 23, 31, 32, 41 Dual Seals plans 52, 53A, 53B, 53C, 54, 55 Quench Seals plans 62, 65A, 65B, 66A, 66B Gas Seals plans 72, 74, 75,
More informationseries 5350 5351 Materials Body: 1/2, 3/4 and 1 : dezincification resistant alloy brass EN 12165 CW617N
Pre-adjustable pressure reducing valves with self-contained cartridge - series CCREDITED ISO 9 FM ISO 9 No. CLEFFI / GB replaces / GB Function Pressure reducing valves are devices which, when installed
More informationMONO BLOCK DIRECTIONAL CONTROL VALVE TS
SHIPPING: 2332 S 25TH STREET (ZIP 6815) MAILING: P.O. BOX #669 OMAHA, NE 6816 PHONE: (42) 344-4434 FAX: (42) 341-5419 HTTP://WWW.BRAND-HYD.COM MONO BLOCK DIRECTIONAL CONTROL VALVE TS TS312TSDTSTKJB TS2
More informationControl ball valves for severe services. Author: Michele Ferrante, PARCOL S.p.A., Italy
Control ball valves for severe services Author: Michele Ferrante, PARCOL S.p.A., Italy Control valves are primarily classified according to the type of their obturator motion which can be linear or rotary.
More informationFlowserve - Edward Valves Quick Closing Isolation Valves -The Equiwedge Alternative
Flowserve - Edward Valves Quick Closing Isolation Valves -The Equiwedge Alternative Problem Fast isolation of a large bore main steam or feedwater line during a pipe rupture that seals flow in both directions.
More informationAutomated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview
Automated Commissioning for Energy (ACE) Platform for Large Retail Property $62,900 dollars of energy savings identified during the first 6 weeks Overview The ability to pull large amounts of complex data
More information*Rated to 207 Bar/3000 PSI with Aluminum Body. Catalog HY15-3501/US SERIES CAVITY DESCRIPTION FLOW PRESSURE PAGE NO.
Bodies & Contents SERIES CAVITY DESCRIPTION FLOW PRESSURE PAGE NO. /GPM BAR/PSI STANDARD CHECKS D1A6... 2U... Valve Insert, Ball Type...145/38... 42/6... 5 D1B125... 2C... Valve Insert, Ball Type... 5/132...
More informationChapter 8: Flow in Pipes
Objectives 1. Have a deeper understanding of laminar and turbulent flow in pipes and the analysis of fully developed flow 2. Calculate the major and minor losses associated with pipe flow in piping networks
More informationPRESSURE REDUCING CONTROL VALVE
Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line
More informationVariTrane Duct Designer An in depth look...
VariTrane Duct Designer An in depth look... Introduction The VariTrane Duct Designer duct design program was written to help optimize design while obtaining a minimum pressure system. The program is based
More informationEnergy savings in commercial refrigeration. Low pressure control
Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary
More information