A. Submit in accordance with Division 1 and Section
|
|
- Bryce Carpenter
- 7 years ago
- Views:
Transcription
1 SECTION HVAC SHEET METAL DUCTWORK PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division 1 Specification Sections, and the Mechanical General Requirements Section apply to work of this Section, as if repeated herein DEFINITIONS A. Ductwork sizes on Drawings state inside clear dimensions. For acoustically lined and internally insulated ductwork, maintain ductwork sizes inside lining or insulation REFERENCES A. Fabricate ductwork in accordance with latest edition of SMACNA HVAC Duct Construction Standards and ASHRAE handbooks unless more stringently detailed. B. Construct ductwork to conform to NFPA 90 A, Air Conditioning and Ventilating Systems and NFPA 96, Standard for the Installation of Equipment for the Removal of Smoke and Grease-Laden Vapors from Commercial Cooking Equipment, latest edition. [C. Ductwork shall be seismically supported and braced per the SMACNA "Guidelines for Seismic Restraints of Mechanical Systems and Plumbing Piping Systems." 1.04 SUBMITTALS A. Submit in accordance with Division 1 and Section B. Submit typical shop standards and/or SMACNA details for each class of duct specified, including particulates such as gauge sizes, welds, joint details, and fitting configurations prior to start of work.
2 C. Submit written report confirming ductwork has been fabricated and installed in accordance with SMACNA standards. D. Submit shop drawings of ductwork only when it is necessary to deviate from the design drawings FLOW DIAGRAMS A. Predicated upon Project magnitude, Construction Documents may include flow diagrams as a part of the working Drawings. These flow diagrams are not for the purpose of giving physical dimensions or locations but rather to make clear the interconnections, by the duct systems, of the various units of the process. If an item is shown on either the flow diagram or the Drawings, but not on both, it will be assumed that the contractor has included such item in his estimate of the cost of the work and that he shall provide same. PART 2 - PRODUCTS 2.01 ACCEPTABLE MANUFACTURERS A. Manufactured Round and Oval Ductwork: 2.02 MATERIALS 1. Buckley 2. Spiral Metal Corporation 3. United Sheet Metal 4. Metal Manufacturing 5. PAR, Inc. 6. Spiro-Fab, Inc. A. Galvanized Ductwork: Fabricated using galvanized steel sheet of lock forming quality, having zinc coating of 1.25 ounces per square foot for each side per ASTM A 525, G 90. All ductwork, supports, and reinforcement to be galvanized unless otherwise noted. B. Steel ductwork (kitchen grease removal): 16 gauge, welded steel. C. Support Materials: Provide galvanized angle iron, channels, stays, and rods. Do not use raw steel. D. Fasteners: Use galvanized rivets and bolts throughout; sheet metal screws are acceptable on low pressure ducts only.
3 E. Proprietary Duct Joint Systems: "Ductmate 35" consisting entirely of metal components. PVC components will not be acceptable. F. Sealant Material: Water and fire resistant, compatible with mating materials DUCT CONSTRUCTION CLASSIFICATIONS A. General: Construct and seal ductwork in accordance with SMACNA pressure classifications and seal classes listed for ductwork systems involved. B. Rectangular Ductwork: 1. +1" WG Class with Seal Class C: Supply air ductwork downstream of fan coils " WG Class with Seal Class B: Return air ductwork, general exhaust ductwork. C. Round or Oval Ductwork: Same as rectangular ductwork except do not use round ductwork in negative static pressure greater than -2" WG or oval ductwork in any negative static pressure applications whatsoever. D. Materials: Use galvanized steel sheet for all applications listed except use steel in constructing ductwork for kitchen hood exhaust systems. Provide kitchen hood exhaust system per NFPA SHEET METAL PLENUMS A. Construct plenums and equipment casings in accordance with Section 6 of SMACNA standards except that sheet metal shall be 16 gauge minimum throughout. PART 3 - EXECUTION 3.01 FABRICATION A. No variation of duct configuration or sizes permitted except by written permission of the Architect. B. Complete metal ducts within themselves with no single partition between ducts. Open corners are not acceptable.
4 C. Lap metal ducts in direction of air flow. Hammer down edges and slips to leave smooth duct interior. D. Fabricate tees, bends, and elbows with radius of not less than 1-1/2 times width of duct on center line. Where rectangular elbows are used, provide turning vanes. All mitered elbows shall have single thickness turning vanes; dual wall airfoil type blades are not acceptable. E. Increase duct sizes gradually, not exceeding 15" divergence wherever possible. Maximum divergence upstream of equipment to be 30" and 45" convergence downstream. F. Rigidly construct metal ducts with joints mechanically tight, substantially airtight, braced and stiffened so as not to breathe, rattle, vibrate, or sag. Seal duct joints and connections with sealant as ducts are being assembled. G. Provide necessary baffling in mixed air plenums to ensure good mixed air temperature. H. Fabricate round and oval duct fittings with spiral or continuously welded seams. Joints shall be 4" slip type, cemented, brazed, or electric welded. Prime coat welded joints. Fabricate elbows of 5-piece construction. Provide standard 45 degree takeoffs unless otherwise indicated. I. Reinforce plenum or casing door frames with galvanized steel angles tied to horizontal and vertical plenum supporting angles. Install hinged access doors for access to equipment, for cleaning, and inspection. J. Fabricate seams and joints in kitchen hood exhaust and dishwasher exhaust ductwork liquid tight with continuous external welds INSTALLATION A. Provide openings in ductwork to accommodate thermometers and controllers. Provide pitot tube openings for testing of systems, complete with metal cam with spring device or screw to ensure against air leakage. Where openings are provided in insulated ductwork, install insulation material inside a metal ring.
5 B. Mount duct-type smoke detectors on the ductwork under this Section of the Specifications. All mounting arrangements, holes cut into ductwork, sealing of openings along with ceiling and access doors for each duct-type detector shall be provided under this Section of the Specifications. Duct detectors along with all sampling tubes and accessories shall be furnished under Division 16. C. Clean ductwork as it is installed to remove dirt and dust. During installation, close duct openings and open ends with temporary covers to keep construction duct out of the duct systems. D. Construct ductwork with sufficient clearance around equipment to allow normal operating and maintenance activities of equipment. E. At each point where ducts pass through partitions, seal joints around duct with noncombustible material. F. Where manufactured duct joint systems such as "Ductmate" are employed, install components in strict accordance with the manufacturer's recommendations. Bolt metal corner pieces except where bolting access is restricted, in which case metal corner clips shall be used. G. Install ducts and supports in accordance with SMACNA standards. Adequately attach hangers to the building structure. Refer to Section H. Prior to operation or test and balance, clean duct systems with high power vacuum machines. Protect equipment which may be harmed by excessive dirt with filters, or bypass during cleaning. Provide adequate access into ductwork for cleaning purposes. **END OF SECTION**
FINAL December 2012 SECTION 233100 DUCTWORK
SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insula tion shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation
More informationPART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
More informationSECTION 233000 HVAC AIR DISTRIBUTION
1320 / Talent Community Center 233000-1 HVAC AIR DISTRIBUTION SECTION 233000 HVAC AIR DISTRIBUTION PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Ductwork. 2. Ductwork accessories. 3. Fans. 4. Air
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationAABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
More informationSECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment
More informationFSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS
3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 INSTALLATION INSTRUCTIONS FSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS 11/2 HOUR UL555 RATED UL555S LEAKAGE RATED
More informationLife Safety Dampers Selection and Application Manual. Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers
Life Safety Dampers Selection and Application Manual Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers May 2014 1 2 Table of Contents HOW TO USE THIS MANUAL DAMPER APPLICATION
More informationSECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
More informationSubpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
More informationHVAC Air Duct Leakage. Eli P. Howard, III Group Director Technical Resources SMACNA
HVAC Air Duct Leakage Eli P. Howard, III Group Director Technical Resources SMACNA Key Variables that Affect the Amount of Leakage Static Pressure Amount of Duct Openings in the Duct Surface Seams, Joints,
More informationDESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible
More informationPreformed Metal Roofing and Siding
Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision
More informationDENVER MODEL 30 X 30 SPECIFICATIONS
DENVER MODEL 30 X 30 SPECIFICATIONS Dimensions: Roof Dimensions 30-0 x 30-0 (4) Columns (Center to Center) 25-6½ x 25-6½ Minimum Clearance 8-0 Roof Height @ Peak Dependent on Col. Ht. Hip Roof 4:12 pitch
More informationSECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
More informationSECTION 15190 HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section 15010.
SECTION 15190 HVAC INSULATION PART ONE - GENERAL PART 1 - GENERAL 1.01 DESCRIPTION A. All work specified in this Section is subject to the provisions of Section 15010. B. All insulation products shall
More informationAll work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
More informationRoof Curbs, Extensions and Equipment Supports
Roof s, Extensions and Equipment Supports December 2012 Roof Page s, Header Extensions and Equipment Supports Table of Contents Model GPI Standard and Optional Construction Features... 3 Model Number Code....
More informationAir-side Systems: Air Duct Design
BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Air-side Systems: Air Duct Design Dr. Sam C M Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
More informationSECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING
SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION PART 1 - GENERAL 1.1 SUMMARY A. Section includes cleaning of interior surfaces of HVAC equipment. The HVAC equipment cleaning work includes the following: 1. Air
More informationSECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions
More informationAir-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
More informationB. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationROOF TOP MOUNTED Air Handler Specification
ROOF TOP MOUNTED Air Handler Specification PART 1: GENERAL (Model RT) Mechanical Specification 1.01 WORK INCLUDED A. Provide complete air handling unit(s) suitable for outdoor installation. Contractor
More informationSECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
More informationCOLORADO MODEL. 35 x 65 SPECIFICATIONS
COLORADO MODEL 35 x 65 SPECIFICATIONS Dimensions: Roof Dimensions 35-0 x 65-0 Column Dimensions (center to center) 31-0 x 30-6 Minimum Clearance 14-0 Roof Height @ Peak ±18-8 Curved Roof ±42-6 radius Square
More informationSECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK
SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. This section covers the pre-finished, pre-fabricated Architectural standing seam roof system. All metal trim,
More informationDESIGN CLARIFICATION (DC)
DESIGN CLARIFICATION (DC) Owner: Victor Valley Wastewater Reclamation Authority Date: 03/03/2015 Contractor: W M Lyles Carollo Project No.: 8299A.20 Project Name: Subregional WRPs DC No.: 001 DC Title:
More informationAcumen Enterprises, Inc.
Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter
More informationSECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationDIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION
More informationFIRE DAMPER APPLICATION GUIDE
FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire
More informationFire Barrier Duct Wrap 15A
3 Fire Barrier Duct Wrap 15A Commerical Kitchen Grease Duct Fire Protection System Product Data and Installation Instructions Compliance 1998 Edition Complies with International Mechanical Code Complies
More informationSpray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
More informationSECTION 02630 STORM DRAINAGE SYSTEM
SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE
More informationMechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories
Basis of Design This section applies to the design and installation of ductwork, air terminal boxes, air outlets and inlets, volume dampers, pressure relief dampers, smoke/fire dampers, and smoke/fire
More informationIsover HVAC Application Handbook Installing fire protection insulation to metal ductwork
Isover HVAC Application Handbook Installing fire protection insulation to metal ductwork HVAC - Fire protection of metal ductwork Fire protection Thermal insulation Isover ULTIMATE TM Protect - Fire protection
More informationCITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU MECHANICAL PLAN REVIEW CHECKLIST
CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU MECHANICAL PLAN REVIEW CHECKLIST PROJECT NO.: BMEC DATE: STATUS: INFORMATION PROJECT ADDRESS: WORK DESCRIPTION: APPLICANT
More informationPOWERS Controls No. 4 Pneumatic Damper Actuator
POWERS Controls No. 4 Pneumatic Damper Actuator Technical Instructions Document No. 155-032P25 AP 331-2 Actuator Assembly 331-2929 Typical Actuator Assembly 331-2904 Typical Actuator Assembly 331-3000
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationDesign Information. Designing Your Dust Collection System. Typical dust or fume collection system
Design Information Designing Your Dust Collection System There are five simple steps to designing an effective and efficient dust collection system. 1. Draw a floor plan of your shop Important Terms to
More information4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
More informationThe Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems
The Butler MR-24 Standing Seam Roof Difference A comparison between metal roof systems Roof Systems Necessities Weathertight (don t leak!) Low maintenance Weathertightness Roof clips, seams, panel alignment
More informationSPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION 238221 - BLOWER COIL UNITS
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationSECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such
More informationBasics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
More informationWe urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.
Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden
More informationDIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS
DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including general and supplementary conditions and other Division 1
More informationTable of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..
Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
More informationDUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES
DUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES Sheet Metal and Air Conditioning Contractors National Association, Inc. 4201 Lafayette Center Drive Chantilly, VA 20151-1209 DUCT CLEANLINESS FOR NEW CONSTRUCTION
More informationpresents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve
More informationHVAC Duct Construction. Bob Wasilewski Project Manager, Technical Resources SMACNA
HVAC Duct Construction Bob Wasilewski Project Manager, Technical Resources SMACNA HVAC Duct Construction Standards WHAT? WHY? HOW? Today's Program 1 st 2 nd Edition HVAC-DCS Review Joints and Limitations
More informationServices Enclosures and Protected Shafts - Maintaining Compartmentation
Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping
More informationSTRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM
Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally
More informationVentilation Solutions Kitchens. fantech
Ventilation Solutions Kitchens 2 Kitchens Today s kitchens have become much more than a place for cooking and food preparation. The kitchen is the heart of the home. It s the center of activity for the
More informationTable of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide
Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
More informationDIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION
SECTION 230713- ALUMAGUARD ENGINEER SPECIFICATION DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,
More informationCity of San Diego, CWP Guidelines
PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,
More informationSeries 18 Pass Thru Air Lock Cleanroom Entry System
OPERATION & MAINTENANCE INSTRUCTIONS FOR Series 18 Pass Thru Air Lock Cleanroom Entry System SOLUTIONS BUILT TO YOUR SPECIFICATIONS 8605 Wyoming Ave. N. Minneapolis MN 55445 fax: 763.425.2004 e-mail: sales@cleanairproducts.com
More informationA. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.
SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel
More informationDuct Fabrication Specifications. Duct Construction SUBURBAN SHEET METAL LTD. Page 1 of 43. Mailing Address P.O. Box 739 Kennedale, TX 76060
Duct Fabrication Specifications & Duct Construction Page 1 of 43 STATIC PRESSURE CLASS (INCHES (Pa) W.G.) Mailing Address TABLE 1-1 PRESSURE CLASSIFICATION FOR DUCTWORK +1/2-1/2 +1-1 +2-2 +3-3 +4-4 +6-6
More informationHOTCHKISS AIR SUPPLY Heating, Ventilating & Air Movement Equipment
HOTCHKISS AIR SUPPLY Heating, Ventilating & Air Movement Equipment F l a t O v a l T u b e a n d F i t t i n g s Introduction Hotchkiss Flat Oval ductwork offers all the advantages of rectangular ducts
More informationSTANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS
ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the
More informationDIVISION 23 - HVAC 23 30 00 HVAC Air Distribution
PART 1 - GENERAL 1.01 GENERAL CRITERIA A. General Design Criteria 1. System standards require that buildings be fully ducted (supply, exhaust and return air). 2. Provide positive exhaust ventilation for
More informationExhaust Calculation Booklet
Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: techsupport@amdry.com ADC Part No. 450450 Exhaust
More informationComponents HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
More informationSTANDARD FOR NON-FIRE RATED ROLLING DOORS
ANSI/DASMA 203-2004 AMERICAN NATIONAL STANDARD STANDARD FOR NON-FIRE RATED ROLLING DOORS Door & Access Systems Manufacturers Association, International Sponsor: 1300 Sumner Ave Cleveland, Ohio 44115-2851
More informationSECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
More informationSECTION 15936 AIR INLETS AND OUTLETS
SECTION 15936 AIR INLETS AND OUTLETS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Diffusers. 2. Registers. 3. Grilles. 4. Louvers. 5. Lowered Penthouses. 6. Gravity Roof Hoods. 7. Gravity Roof
More informationSERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
More informationA D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, 2012. All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA
Page 1 of 10, Addendum No. 3 Temporary Garage Structure City of Chelsea, MA November 5, 2012 CBI Job No.: 12055-A A D D E N D U M # 3 DATE: November 5, 2012 TO: FROM: PROJECT: All Bidders Jenne dos Santos,
More informationPLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
More informationThe EDGE Self-Sealing Round Duct System
The EDGE Self-Sealing Round Duct System Stamped Fittings, Inc., 217 Lenox Ave., Elmira Heights, NY 14903 Ph: 607.733.9988 www.stampedfittings.com Submittal Sheet The EDGE Features, Benefits & Materials
More informationSection 2100-Trenching and Tunneling
SECTION 5200 - STORM SEWER PART 1 - GENERAL 1.01 SCOPE: This Section covers installation of storm sewer mains and culverts. Topics include permits and fees, trench widths, pipe laying, bedding, initial
More informationPRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS
PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133
More informationNADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS
NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS National Air Duct Cleaners Association 1518 K Street, N.W. Suite 503 Washington, DC 20005 (202)
More informationMark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
More informationcity of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
More informationSECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
More informationSECTION 23 34 13. A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer.
PART 1 GENERAL SECTION 23 34 13 HVAC FANS 1.01 SUMMARY A. Section Includes: 1. Exhaust fans. 2. Transfer fans. B. Related Documents: 1. Drawings and general provisions of the Contract, including General
More informationKITCHEN HOODS GUIDELINES
KITCHEN HOODS GUIDELINES City of Palo Alto Building Inspection Division 285 Hamilton Ave. Inspection Request: 650 329-2496 Revision Date:6/27/12 General Requirements/Checklist for: Commercial Codes Enforced:
More informationDecree of the Ministry of the Environment on fire safety of ventilation systems
THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18
More informationSECTION 07720 PREFORMED METAL STANDING SEAM ROOFING
SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING PART ONE GENERAL DESCRIPTION This section includes pre-formed standing seam metal roofing and related flashings, closures, trim and accessories including,
More informationThe Basics of Commercial Kitchen Exhaust Cleaning
The Basics of Commercial Kitchen Exhaust Cleaning ANSI/IKECA C 10 ANSI/IKECA C 10: Standard for Cleaning of Commercial Exhaust Systems IKECA Introduces the Kitchen Exhaust Cleaning Industry s First American
More informationMRI RF SHIELDING DESIGN
MRI RF SHIELDING DESIGN Nelco s MRI RF Shielding is specifically designed for the MRI industry. Our engineers have developed a shielded enclosure made entirely of nonmagnetic materials that is unsurpassed
More informationSECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes seismic restraints and other earthquake-damage-reduction measures for electrical
More informationFIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
More informationMechanical Installation
Page -1-1. INTRODUCTION AND PURPOSE 1.1. This specification covers the installation, testing and precommissioning of mechanical equipment. Work is to be performed in conjunction with the manufacturer s
More informationglass & Glazing Products
glass & Glazing Products WallMaker Create an unlimited variety of bright, beautiful and secure interior environments with the easy-to-install Stylmark WallMaker glass wall system. This versatile system
More informationRFQ # PR5006805 Replace Kitchen Equipment in the CGR
RFQ # PR5006805 Replace Kitchen Equipment in the CGR GENERAL The Consulate General of the United States of America has a requirement to furnish and install new kitchen equipment at the Consul General s
More informationWHI 90-Minute Rated Veneered Door Frame Installation Instructions
No. 940-03-10 INSTALLATION INSTRUCTIONS 90 MINUTE RATED VENEERED DOOR FRAME DOOR REQUIREMENTS: Consult the door manufacturer to make sure that the doors are qualified for the hardware to be installed,
More informationGreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
More informationCHAPTER 5 WATER HEATERS
PlumbingCode06_ch05 5/29/06 8:12 AM Page 1 CHAPTER 5 WATER HEATERS Water heaters are only a small portion of a plumbing system, but they are important, and they can be dangerous. Many plumbers take water
More informationVOLU-probe/SS. Stainless Steel Pitot Airflow Traverse Probes. Accurate airflow measurement for demanding applications
VOLU-probe/SS Stainless Steel Pitot Airflow Traverse Probes Accurate airflow measurement for demanding applications VOLU-probe/SS The VOLU-probe/SS Stainless Steel Pitot Airflow Traverse Probe is ideally
More informationINC Flexi-Sorb. Versatile Flexible Easy To Install Durable Good Noise Reduction Economical. Typical Applications
INC Flexi-Sorb Noise Control Curtain System Versatile Flexible Easy To Install Durable Good Noise Reduction Economical Our Flexi-Sorb noise control curtain product line consists of flexible, durable acoustical
More informationNoise Control. Commercial, Industrial, and Environmental Products and Solutions. www.kineticsnoise.com
Noise Control Commercial, Industrial, and Environmental Products and Solutions www.kineticsnoise.com Commercial Duct Silencers Kinetics Noise Control offers the design and engineering assistance to integrate
More information