1 HVAC Duct Construction Bob Wasilewski Project Manager, Technical Resources SMACNA
2 HVAC Duct Construction Standards WHAT? WHY? HOW?
3 Today's Program 1 st 2 nd Edition HVAC-DCS Review Joints and Limitations Transverse Joints & Reinforcements Use of the Pressure Class Tables Tie Rod Addendum
4 Documents Preceding 2nd Edition HVAC-DCS Low Velocity Systems Duct Manual First Edition 1959 Second Edition 1963 Third Edition 1967 Low Velocity Duct Construction Standard 1969
5 Documents Preceding 2nd Edition HVAC-DCS Low Pressure Duct Construction Standard Fifth Edition 1976 High Velocity Duct Systems Manual First Edition 1965 High Velocity Duct Construction Standards Second Edition 1969
6 Documents Preceding 2nd Edition HVAC-DCS High Pressure Duct Construction Standards Third Edition 1975 Duct Liner Application Standard First Edition 1971 Second Edition 1975
7 Documents Preceding 2nd Edition HVAC-DCS Flexible Duct Installation Standards First Edition 1979 Second Edition 1980 HVAC Duct Construction Standards -- Metal and Flexible First Edition 1985
8 Major Changes from First Edition GENERAL Text edited to be more reader-friendly Reading aids added Static pressure only as the basis for duct construction classification -- velocity levels deleted (Table 1-1)
9 Major Changes from First Edition Chapter 7 revised to facilitate use for equivalent and comparable tests and ratings Model project specification added Reminders to designers to show all required fire, smoke, radiation and volume control dampers on contract drawings are accented
10 Major Changes from First Edition Boiler breeching omitted Volume damper construction is more specific Lead radiation shielding added Metrics are included Air terminal runouts and supports are revised
11 Major Changes from First Edition RECTANGULAR DUCT REVISIONS Negative pressure construction given for 4", 6", and 10" w.g. Six feet reinforcement schedules added Reinforcement schedules extended to 120" width
12 Major Changes from First Edition Tie rod alternatives expanded for both positive and negative pressures TDC and TDF joint systems included and rated as T-25a and T-25b joints T-24a joint added as a modification of T-24
13 Major Changes from First Edition Use of 26 gage added for 4", 6" and 10" pressures Trapeze hanger tables expanded to cover the 120" width range Duct liner pin schedule adjusted Infrequently used joints (T-4, 8, 17, 18, 19, 20 and 23) omitted
14 Major Changes from First Edition Round, Flexible and Oval Duct Revisions Duct pressure classes revised to be positive and negative at 2", 4" and 10" w.g. Crimped joint connection length changed from 1" to 2" Rectangular branch taps into round added for straight or 45 degree lead-in-entry
15 Major Changes from First Edition Type 1 reinforcement of oval duct now has an internal tie rod (based on ASHRAE test program) Maximum support spacing for round flexible duct and connector changed from 10 feet to 5 feet Additional riser support details are provided
16 DUCT SYSTEMS SIZINGS FITTINGS, ETC. FIRE/SMOKE PROTECTION CODE COMPLIANCE DUCT CONSTRUCTION CODE COMPLIANCE SMACNA HVAC-DCS 2 ND ED INSPECTION CODE COMPLIANCE
17 DUCT SYSTEMS ENGINEER Design Considerations: CFM Static Pressure Duct Size Fitting Type Construction Pressure Class CONTRACTOR Construction Considerations: Panel Thickness (Gage) Pressure Class (as specified) Panel Width/Height Joint Type/Spacing Intermediate Reinforcement Type/Spacing
18 DEPENDENT VARIABLES
19 REGULAR DUCTS Maximum Deflection Joint and Reinf. 1/4" on 48" w. W/200 on 49"-120" Sheet: 3/8" on 12" Dn. 1/2" on 13"-18" 5/8"on 19"-24" 3/4" on 25"-84" 1" on 85"-120" Maximum Test Pressure Lab: Class Rating + 50% Field: Class Rating + 25% Tolerance: +7.5% Tolerance: +10%
20 Duct Systems Used for the movement of air in HVAC/Exhaust systems Ducts are classified based on maximum operating pressure 0.5" w.g. positive or negative 1.0" w.g. positive or negative 2.0" w.g. positive or negative
21 Duct Systems (Continued) Ducts are classified based on maximum operating pressure 3.0" w.g. positive or negative 4.0" w.g. positive or negative 6.0" w.g. positive or negative 10.0" w.g. positive or negative
22
23 TABLE 1-2 STANDARD DUCT SEALING REQUIREMENTS
24
25
26
27
28
29
30
31
32
33
34
35
36
37 EXAMPLE 1 Duct Size 24" x 24" Pressure Class 2" w.g. Sheet Stock Joints/Reinforcements 8 ft / 4 ft Standing S
38
39
40 EXAMPLE 2 Duct Size 42" x 24" Pressure Class 3" w.g. 5 ft Coil Line Joints/Reinforcements 5 ft / 2 ½ ft TDC or TDF
41
42
43
44 MIDPANEL TIE ROD (MPT) ½" w.g. - 6" w.g. 37" - 96" Duct Dimension Rectangular Duct
45 Mid Panel Tie Rod Addendum Joints All Tie Rods Threaded Rod or Tubing/Conduit with Threaded Insert Additional Application Tables, Qualifications and Reader Aids Included
46
47
48
49
50
51 FIGURE 1-3 TIE ROD ATTACHMENTS
52 FIGURE 1-4 TRANSVERSE (GIRTH) JOINTS
53 FIGURE 1-4 TRANSVERSE (GIRTH) JOINTS
54 FIGURE 1-4A SPECIAL JOINT PROFILES
55 FIGURE 1-5 LONGITUDINAL SEAMS RECTANGULAR DUCT
56 TABLE 1-24 UNREINFORCED DUCT (WALL THICKNESS)
57 TABLE 1-25 T-1 FLAT DRIVE ACCEPTED AS REINFORCEMENT
58 FIGURE 1-7 UNREINFORCED DUCT
59 FIGURE 1-8 CROSSBROKEN DUCT & BEADED DUCT
60 FIGURE 1-9 DUCT REINFORCED ON TWO SIDES
61 FIGURE 1-10 DUCT REINFORCED ON ALL SIDES
62 FIGURE 1-12 DUCT OVER 120" (3048 MM) WIDE
63 FIGURE 1-15 CORNER CLOSURES - FLANGES
64 FIGURE 2-22 DUCT LINER INTERRUPTION
65 TABLE 3-2A ROUND DUCT GAGE UNREINFORCED POSITIVE PRESSURE
66 TABLE 3-2B ROUND DUCT GAGE NEGATIVE PRESSURE
67 FIGURE 3-1 SEAMS ROUND DUCT AND FITTINGS
68 FIG. 3-2 TRANSVERSE JOINTS ROUND DUCT
69 FIGURE 3-6 FLAT OVAL DUCTS
70 FIGURE 3-9 FLEXIBLE DUCT SUPPORTS
71 FIGURE 3-10 FLEXIBLE DUCT SUPPORTS
72 TABLE 4-1 RECTANGULAR DUCT HANGERS MIN. SIZE
73 TABLE 4-2 MINIMUM HANGER SIZES FOR ROUND DUCT
74 FIGURE 4-4 LOWER HANGER ATTACHMENTS
75 Questions & Answers
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible
More informationDuct Leakage Testing. Ken Helfers, TSI Inc. 2011, TSI Incorporated
Duct Leakage Testing Ken Helfers, TSI Inc. Agenda Need for duct leakage testing Duct leakage testing standards and regulations Performing duct leakage testing Why Test Ducts for Leakage? Conserve energy
More informationHVAC Air Duct Leakage. Eli P. Howard, III Group Director Technical Resources SMACNA
HVAC Air Duct Leakage Eli P. Howard, III Group Director Technical Resources SMACNA Key Variables that Affect the Amount of Leakage Static Pressure Amount of Duct Openings in the Duct Surface Seams, Joints,
More informationFSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS
3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 INSTALLATION INSTRUCTIONS FSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS 11/2 HOUR UL555 RATED UL555S LEAKAGE RATED
More informationEFFICIENT DUCT SYSTEM DESIGN
DUCT ACOUSTICAL EFFICIENT EFFICIENT DUCT SYSTEM DESIGN WHY SPIRAL DUCT SHOULD BE YOUR FIRST CHOICE 2 Aesthetically Pleasing & Easier to install Low air leakage Low pressure drop Lower air distribution
More information4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
More informationFINAL December 2012 SECTION 233100 DUCTWORK
SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insula tion shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation
More informationDuct Fabrication Specifications. Duct Construction SUBURBAN SHEET METAL LTD. Page 1 of 43. Mailing Address P.O. Box 739 Kennedale, TX 76060
Duct Fabrication Specifications & Duct Construction Page 1 of 43 STATIC PRESSURE CLASS (INCHES (Pa) W.G.) Mailing Address TABLE 1-1 PRESSURE CLASSIFICATION FOR DUCTWORK +1/2-1/2 +1-1 +2-2 +3-3 +4-4 +6-6
More informationFIRE DAMPER APPLICATION GUIDE
FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire
More informationSECTION 15190 HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section 15010.
SECTION 15190 HVAC INSULATION PART ONE - GENERAL PART 1 - GENERAL 1.01 DESCRIPTION A. All work specified in this Section is subject to the provisions of Section 15010. B. All insulation products shall
More informationHOTCHKISS AIR SUPPLY Heating, Ventilating & Air Movement Equipment
HOTCHKISS AIR SUPPLY Heating, Ventilating & Air Movement Equipment F l a t O v a l T u b e a n d F i t t i n g s Introduction Hotchkiss Flat Oval ductwork offers all the advantages of rectangular ducts
More informationSECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
More informationAir-side Systems: Air Duct Design
BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Air-side Systems: Air Duct Design Dr. Sam C M Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
More informationLife Safety Dampers Selection and Application Manual. Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers
Life Safety Dampers Selection and Application Manual Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers May 2014 1 2 Table of Contents HOW TO USE THIS MANUAL DAMPER APPLICATION
More informationHVAC Air Duct Leakage. November 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA
HVAC Air Duct Leakage November 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA Learning Objectives Understand the difference between System leakage and Duct leakage Understand
More informationAcoustical Design Guidelines for HVAC Systems in Schools
Acoustical Design Guidelines for HVAC Systems in Schools Seminar 9, ASHRAE Summer Meeting Albuquerque, New Mexico Sponsor: TC 2.6 Sound and Vibration Robert M. Lilkendey Associate Principal Consultant
More informationExhaust Calculation Booklet
Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: techsupport@amdry.com ADC Part No. 450450 Exhaust
More informationDUCT SYSTEMS CHAPTER 6
CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter
More informationWTW SWANTM. Linear slot air diffusers of wall-to-wall design for ceilings
SWANTM WTW Linear slot air diffusers of wall-to-wall design for ceilings Quick facts Wall-to-wall installation Diffuser face of light aluminium design 2, 3 or slots Horizontal/vertical air distribution
More informationDesign Calculation or Analysis Cover Sheet. Complete only applicable items. 1 060-M8C-VCTO-00600-000-00B
SSC Design Calculation or Analysis Cover Sheet Complete only applicable items. ENG.20070612.0009 1. QA:QA 2. Page 1 3. System 4. Document Identifier Surface Nuclear Confinement HVAC System 5. Title CRCF
More informationCHAPTER 6 DUCT SYSTEMS
CHAPTER 6 DUCT SYSTEMS SECTION MC 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this
More informationSTANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS
ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the
More informationsecurity products metric sizes Redefine your comfort zone. www.titus-hvac.com
metric sizes secure lethal objects monitoring areas suicide deterrent Redefine your comfort zone. www.titus-hvac.com humid areas prevents corrosion minimum security medium security maximum security Table
More informationINDEX. Chapter8. air master. Perforated Ceiling Diffusers
Chapter8 INDEX A. Perforated ceiling diffuser 1. Perforated ceiling diffuser with plenum box..: APCD+P...8.1. Perforated ceiling diffuser with damper....: APCD...8. Standard sizes...8. Fixing details...8.
More informationDuct Design. Presented by Dave Janquart
Duct Design Presented by Dave Janquart Overview of Topics Duct design Duct insulation SMACNA Standards Factors Influencing Duct Design Equipment Losses Air Velocity Duct Material Duct Size & Shape Length
More informationPART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
More informationDRYER VENTING SPECIFICATIONS DRYER SAFETY
DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting
More informationHVAC - How to Size and Design Ducts
HVAC - How to Size and Design Ducts Course No: M06-032 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
More informationROOF TOP MOUNTED Air Handler Specification
ROOF TOP MOUNTED Air Handler Specification PART 1: GENERAL (Model RT) Mechanical Specification 1.01 WORK INCLUDED A. Provide complete air handling unit(s) suitable for outdoor installation. Contractor
More informationSECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such
More informationSheet Metal Products for the HVAC Industry
2 0 1 2 P R O D U C T C A T A L O G Sheet Metal Products for the HVAC Industry Quality Products Since 1989 A B O U T R O Y A L M E T A L P R O D U C T S About Royal Metal Products Royal Metal Products
More informationQuality Regulations for Profiles
Quality Regulations for Profiles September 2010 Quality Regulations for Profiles Page 2/42 Contents Preface... 4 1. Terms and Definitions... 5 1.1 Third parties... 5 1.2 Independent laboratories... 5 1.3
More informationANSI/AHRI Standard 880 (I-P) with Addendum 1. 2011 Standard for Performance Rating of Air Terminals
ANSI/AHRI Standard 880 (I-P) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:
More informationSECTION 233000 HVAC AIR DISTRIBUTION
1320 / Talent Community Center 233000-1 HVAC AIR DISTRIBUTION SECTION 233000 HVAC AIR DISTRIBUTION PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Ductwork. 2. Ductwork accessories. 3. Fans. 4. Air
More informationCURTAIN TYPE FIRE DAMPERS
URTAIN TYPE FIRE urtain Fire Damper Basics Definition of a Fire Damper: The National Fire Protection Association (NFPA) Standard 9A defines a fire damper as "a device, installed in an air distribution
More informationSeptember 1, 2003 CONCRETE MANUAL 5-694.900 CONCRETE PAVEMENT REHABILITATION 5-694.900
September 1, 2003 CONCRETE MANUAL 5-694.900 5-694.901 GENERAL CONCRETE PAVEMENT REHABILITATION 5-694.900 Concrete Pavement Rehabilitation is an extremely valuable tool of the Minnesota Department of Transportation
More informationTable of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..
Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
More informationSAM HOUSTON STATE UNIVERSITY
PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the
More informationServices Enclosures and Protected Shafts - Maintaining Compartmentation
Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping
More informationHYLINER AKS HDPE LINING
HYLINER AKS HDPE LINING FOR CONCRETE PIPE Manufactured from HDPE Available in white and black Sheets up to 3 m width D1.12 HyLiner AKS HDPE Lining for Concrete Pipe October 2013 0800 WE PIPE (93 7473)
More informationIsover HVAC Application Handbook Installing fire protection insulation to metal ductwork
Isover HVAC Application Handbook Installing fire protection insulation to metal ductwork HVAC - Fire protection of metal ductwork Fire protection Thermal insulation Isover ULTIMATE TM Protect - Fire protection
More informationHVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings
SUCCESS WITH 2012 IECC DELAWARE Recommended Practices for Optimized Energy Savings for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED VERSION 2015.1.0 CHECKLIST: JOB READY 1. 2.
More informationIncorporating V2.3. Product spec >>> > Series ECG - Egg Crate Grilles. > Series ECG45-45 Egg Crate Grilles
Incorporating V2.3 Product spec >>> > Series ECG - Egg Crate Grilles > Series ECG45-45 Egg Crate Grilles Grilles Egg crate Recommended for: Wall, ceiling & duct Extract Overview Industry standard extract
More informationHVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades
Success with 2015 IECC Northeast & Mid-Atlantic Checklist for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED TEMPLATE 2015.1.0 PAGE 1 CHECKLIST: JOB READY 1. 2. 3. 4. 5. 6. 7. 8.
More informationFire Barrier Duct Wrap 15A
3 Fire Barrier Duct Wrap 15A Commerical Kitchen Grease Duct Fire Protection System Product Data and Installation Instructions Compliance 1998 Edition Complies with International Mechanical Code Complies
More informationAIR CONDITIONING PRODUCTS COMPANY
Quality Products Fixed Louvers AIR CONDITIONING PRODUCTS COMPANY all Shutter Backdraft Damper Ceiling Shutter Motorized Damper Fixed Louver Ga le Shutter Drainable Louver Supply Damper Fiberglass Shutter
More informationHVAC Ducting - Principles and Fundamentals
PDHonline Course M246 (4 PDH) HVAC Ducting - Principles and Fundamentals Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088
More informationLindab Representative s Handbook
Lindab Representative s Handbook Table of Contents NOTICE!... 3 Revisions... 4 Navigating Lindab... 5 Lindab Lingo... 6 Contact List... 7 History of Lindab... 8 The Lindab Concept... 8 Marketing and Sales
More informationThis permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).
CITY OF MILPITAS Building & Safety Department 455 E. Calaveras Blvd. Milpitas, CA 95035 408-586-3240 www.ci.milpitas.ca.gov RESIDENTIAL AIR CONDITIONING, REPLACEMENT 1. PERMIT INFORMATION: The replacement
More informationFRP AQUATIC DUCTWORK COMPONENTS LEADERS IN FIBERGLASS REINFORCED PLASTIC DUCT PRODUCTS
Perry Fiberglass Products, Inc. FRP AQUATIC DUCTWORK COMPONENTS LEADERS IN FIBERGLASS REINFORCED PLASTIC DUCT PRODUCTS PERRY FIBERGLASS Perry Fiberglass Products, Inc. is a leading manufacturer of high
More informationAISI CHEMICAL COMPOSITION LIMITS: Nonresulphurized Carbon Steels
AISI CHEMICAL COMPOSITION LIMITS: Nonresulphurized Carbon Steels AISI No. 1008 1010 1012 1015 1016 1017 1018 1019 1020 1021 1022 1023 1024 10 1026 1027 1029 10 1035 1036 1037 1038 1039 10 1041 1042 1043
More informationGUIDELINE ON THROUGH-PENETRATION FIRESTOPPING
GUIDELINE ON THROUGH-PENETRATION FIRESTOPPING SECOND EDITION AUGUST 2007 SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION, INC. 4201 Lafayette Center Drive Chantilly, VA 20151-1209 www.smacna.org
More informationMechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories
Basis of Design This section applies to the design and installation of ductwork, air terminal boxes, air outlets and inlets, volume dampers, pressure relief dampers, smoke/fire dampers, and smoke/fire
More informationplenum slot diffusers
light powered Redefine your comfort zone. www.titus-hvac.com dual-function smart logic light powered energy solutions Table of Contents PLENUM SLOT IFFUSERS products Plenum Slot iffusers Products... 4
More informationThis digital document created and presented by Richard Fleetwood. He is the. Civil Defense Now! (http://www.survivalring.org/cd-main.htm) websites.
This digital document created and presented by Richard Fleetwood. He is the founder, author, producer, and webmaster of the SurvivalRing (http://www.survivalring.org) and Civil Defense Now! (http://www.survivalring.org/cd-main.htm)
More informationvav retrofit terminals
retrofit Redefine your comfort zone. www.titus-hvac.com energy solutions Table of Contents products Application Icons Key... 2 VAV Retrofit Terminals roducts... 3 external round duct series EXX, ECX and
More informationAMPSEAL* Automotive Plug Connector and Header Assembly
AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2
More informationTable of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide
Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
More informationSECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment
More informationBasics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
More informationDUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES
DUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES Sheet Metal and Air Conditioning Contractors National Association, Inc. 4201 Lafayette Center Drive Chantilly, VA 20151-1209 DUCT CLEANLINESS FOR NEW CONSTRUCTION
More informationBelow are detailed instructions for using the EMS load calculator.
Introduction The EMS load calculator is designed to make load calculating as painless as possible. For sizing the equipment, only the first three tabs (Steps 1, 2 & 3) need to be completed. This process
More informationENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
More informationHVAC Vents & Diffusers
2 HVAC Vents & Diffusers Drywall, Stone, & Wood Applications TRUFIG can be installed in a variety of finishes and surfaces. This guide will detail the install of HVAC vents and diffusers in drywall, stone,
More informationHVAC Calculations and Duct Sizing
PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An
More informationTECHNICAL BULLETIN. Oil Canning in Metal Roof and Metal Wall Systems. What Is Oil Canning?
TECHNICAL BULLETIN Oil Canning in Metal Roof and Metal Wall Systems What Is Oil Canning? Oil Canning can be defined as visible waviness in the flat areas of metal roofing and metal wall panels. In technical
More informationBODY OF KNOWLEDGE API-570 AUTHORIZED PIPING INSPECTOR CERTIFICATION EXAMINATION
BODY OF KNOWLEDGE API-570 AUTHORIZED PIPING INSPECTOR CERTIFICATION EXAMINATION 2015 (Replaces July 2013) API Authorized Piping Inspectors must have a broad knowledge base relating to maintenance, inspection,
More informationInstallation Instructions
Installation Instructions Pedestal Models FS 500 LE FS 800 LE Insert Models IS 500 LE IS 800 LE Pecan Engineering Pty Ltd 13 Acorn Road Dry Creek South Australia 5094 Email info@pecan-eng.com.au Phone:
More informationSERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
More informationWORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1
WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1 Wallet card photocopy Inspection Authority: Signature: Date: / / Submitted For: ( Owner ) Name Address City Prov Postal code Phone ( ) Fax ( ) Designer/Signature:
More information1.2 Refrigerant Equipment. General
Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or
More informationHVAC Control & Balancing Dampers Models VCD, MBD and RBD
HVAC Control & Balancing Dampers Models VCD, MBD and RBD Selection Construction Performance H* W* August 1 2013 HVAC Control and Balancing Dampers Commercial Control Dampers are used in buildings to regulate
More informationDamper Selection and Sizing
Damper Selection and Sizing SECTION OF ENGINEERING MANUAL OF AUTOMATIC CONTROL 77-1 Contents Introduction... 3 Definitions... 3 Damper Selection... 4 Damper Types... 4 Parallel and Opposed Blade Dampers...
More informationASTM A860/A860M-09 Standard Specification for Wrought High Strength. Ferritic Steel Butt Welding Fittings. 1. Scope :- 2. Reference Documents :-
Standard Specification for Wrought High Strength Ferritic Steel Butt Welding Fittings 1. Scope :- 1.1 This specification covers wrought high strength ferritic steel butt-welding fitting of seamless and
More informationRefrigeration Installation 101
Refrigeration Installation 101 Hundreds of Installations Refrigerated Cases 2 Compressor Racks 3 Condensing Units 4 Walk-in Boxes 5 Some were done very well 6 Some had some issues... 7 8 Some seemingly
More informationINSTALLATION INSTRUCTIONS: Viewline 52 mm
-5 Safety information The product was developed, manufactured and inspected according to the basic safety requirements of EC Guidelines and state-of-the-art technology. The instrument is designed for use
More informationAMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application and Design. Ratings. Features and Control Options.
Application and esign Thermal ispersion Air Measuring Station with VC-23 Control amper The combines the functionality of a highly accurate thermal dispersion airflow measuring station and a low leakage
More information*** MAIN VERSION OF BOM ***
*** MAIN VERSION OF BOM *** This is the main parts list for the 2013-2014 FTC game. The parts are listed in different categories (such as "Field Elements, "Hardware," "Wood," etc.). The item numbers assigned
More informationHow to Measure HVAC System Airflow
How to Measure HVAC System Airflow About National Comfort Institute National Comfort Institute is an international training Since our and beginning development in 1994 company we have trained with and
More informationDUCT SYSTEM DESIGN CONSIDERATIONS Part 1
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 by Roger M Hensley, CMS TYPES OF SUPPLY DUCT SYSTEMS There are several basic
More informationPerformance Rating of Room Fan- Coils
ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS
More informationPLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW
CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,
More informationSECTION 15936 AIR INLETS AND OUTLETS
SECTION 15936 AIR INLETS AND OUTLETS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Diffusers. 2. Registers. 3. Grilles. 4. Louvers. 5. Lowered Penthouses. 6. Gravity Roof Hoods. 7. Gravity Roof
More informationSECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
More informationGrEAT PACIFIC ELBOW COMPANY PRODUC T C ATALOG
GrEAT PACIFIC ELBOW COMPANY PRODUC T C ATALOG Setting the Standard for Premium HVAC Products since 1983 ABOUT US Great Pacific Elbow began in 1983, initially only offering adjustable elbows. Our expertise
More informationDIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION
SECTION 230713- ALUMAGUARD ENGINEER SPECIFICATION DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,
More informationNoise in the Classroom
ASHRAE JOURNAL Copyright 2000, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This posting is by permission of ASHRAE Journal. This article may not be copied nor distributed
More informationGuidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
More information2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
More informationCONCRETE REPAIR GUIDELINES. Concrete repairs can be broken down into four basic types, plus special repairs and planing.
CONCRETE REPAIR GUIDELINES Concrete repairs can be broken down into four basic types, plus special repairs and planing. Note: It is recommended that investigation into soundness of pavement be performed
More informationCopper and Copper Alloy Tube, Pipe and Fittings
Copper and Copper Alloy Tube, Pipe and Fittings COPPER and COPPER ALLOY TUBE and PIPE Seamless Copper Pipe: Copper pipe is almost pure copper manufactured to the requirements of ASTM B 42 - Standard Specification
More informationBuilt to Last. Built for Beauty. Good. Solid. Logix. TM
Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a
More informationBlast Proof Occupied Buildings
Blast Proof Occupied Buildings 1 1 Contents Presentation References Functional Specification Blast Resistant Building Basis for design Blast & impact loading Design modeling & analyses Preliminary design
More informationBlast Resistant Building BP Refinery Rotterdam
Blast Resistant Building BP Refinery Rotterdam 14 May, 2008 1 1 Contents Presentation Introduction KCI Functional Specification Blast Resistant Building Basis for design Blast & impact loading Design modeling
More informationSMA Interface Mating Dimensions (Per MIL-STD-348)
SMA Series SMA 6 SMA Interface Mating Dimensions (Per MIL-STD-348) SMA Interface Dimensions MALE Inches/Millimeters 3 Minimum Nominal Maximum LTR in. mm in. mm in. mm A.250 6.35.263 6.68.. B.1790 4.55.1808
More informationInstallation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details
D Installation Details D1 General D2 Walls D3 Ceilings D4 Reference D Installation Details D Contents D1 General Installation and Fastening Sequence for Steel Studs D1.1 Fastener Selection D1.3 D2 Walls
More informationPOWERS Controls No. 4 Pneumatic Damper Actuator
POWERS Controls No. 4 Pneumatic Damper Actuator Technical Instructions Document No. 155-032P25 AP 331-2 Actuator Assembly 331-2929 Typical Actuator Assembly 331-2904 Typical Actuator Assembly 331-3000
More informationINSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT 2003-2014 CHEVROLET/GMC VANS FOR
INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT 2003-2014 CHEVROLET/GMC VANS FOR (For NEW 2007 ALL WHITE KWIK-KITS ONLY) Warning do not attempt to install A/C units unless you are experienced with servicing
More information