Service manual. MIV V4+ Mini
|
|
|
- Lynne Bridges
- 9 years ago
- Views:
Transcription
1 Service manual MIV V4+ Mini DC INVERTER R410A ~220V, 1Ph, 50Hz MVUH120A-VA1 MVUH140A-VA1 MVUH160A-VA1
2 Contents Part 1 General Information... 1 Part 2 Outdoor Units... 9 Part 3 Installation... 55
3 Part 1 General Information 1. Product Line-up menclature Features... 4 General Information 1
4 1. Product Line-up Outdoor Units Model name Dimension body(mm) Net/Gross weight (kg) Power supply MVUH120A-VA1 MVUH140A-VA1 MVUH160A-VA1 Width: 900 Height: 1327 Depth: 320 Width: 900 Height: 1327 Depth: 320 Width: 900 Height: 1327 Depth: / ~240V-1ph 50Hz 95/ ~240V-1ph 50Hz 100/ ~240V-1ph 50Hz 2 General Information
5 2. menclature 2.1 Outdoor unit: MVUH120A VA1 Power 1-1 phase, 50 Hz 3-3 phases, 50 Hz Refrigerant A - R410A B - R22 Inverter (in)v(erter) - inverter S(tandard) on/off Model A Z Capacity index kw*10 The main feature of the system air cooled: C(ooling) cooling only H(eat pump) cooling and heating R(ecovery) heat recovery, 3-pipe water cooled: Q(ooling) cooling only W(ater) cooling and heating (reco)v(ery) heat recovery, 3-pipe Identifier of the outdoor unit (o)u(tdoor) Manufacturer s brand and class of the system M(idea) V(RF) General Information 3
6 2.2 Indoor unit: MVC28A VA1 Design features (may be absent) For example: G(rey), W (hite) color Power 1-1 phase, 50 Hz 3-3 phases, 50 Hz Refrigerant A - R410A B - R22 Inverter (in)v(erter) - inverter S(tandard) - on/off Model A Z Capacity index kw*10 Type of the indoor unit W(all) - wall (ca)s(sette) cassette 600x600 C(assette) - cassette (o)n(e way) 1-way cassette T(wo way) 2-way cassette L(ow) low static pressure duct M(edium) medium static pressure duct H(igh) - high static pressure duct (fle)x ceiling & floor F(loor standing) floor standing (колонный) E(floor-standing exposed) floor standing exposed D console Manufacturer s brand and class of the system M(idea) V(RF) 4 General Information
7 3. Features 1 Widely application The Full DC Inverter mini VRF system is a highly efficient solution for small commercial buildings requiring heating and cooling of up to 8 zones with one outdoor unit. Such as villa, restaurant, school etc. Midea offers a variety indoor unit, more than 100 models of 15 types. Capacity ranges are from 2.2Kw to 14Kw. it is full compliance with residential and light commercial place. Our systems can operate up to 130% of capacity which allows any system to be designed to the customers and applications needs. General Information 5
8 2 High efficiency and Energy-saving DC inverter Mini VRF realized the industry's top class energy efficiency with cooling and heating COP by adoption of Brushless Reluctance DC compressor control,dc Fan motor and improved heat exchanger performance with a new design. 2.1 High efficiency DC inverter Double rotor compressor, saving power 25% High efficiency DC inverter Optimize compressor start-up technology Wider operating frequency range Compact structure Better balance and lower vibration The AC load ratio of building is 30%-75%,the area is 55%, most of the AC runs in the mid load, so the mid load operation ratio control the whole year AC running charge. Centralizing winding Distributing winding Smooth sine wave DC Inverter Motor uses 180 sine wave vector drive technology to ensure transducer to output smooth curve, which show motor rotor speed to run smooth. While, common frequency motor outputs smooth wave not to precisely show motor speed, so its efficiency is low. Common smooth wave Sine Wave DC inverter 6 General Information
9 2.2 High efficiency DC Fan motor, saving power 50% According to the running load and pressure, it controls the speed of DC fun to achieve the min. energy consume, to reach the best effect. Used across entire range of models. Efficiency improvement by up to 45% especially at low speed. High Pressure Motor rotor speed waves among ±5r, and can rapidly match DC Inverter Compressor to output, and enhance efficiency in part load. Optically design the fan shape and air designed deflector, which increase the air volume and reduce the running noise. CF 3 Convenient for installation and service 3.1 Easy piping connection Branch pipe and Four divergence box is available for Full DC inverter system. And Midea offers Four direction to connect copper pipe and wiring, Front out pipe Side out pipe Back out pipe Undersurface out pipe General Information 7
10 Front side Left side Rear side Button side Easy installation Branch pipe and four divergence box are both available for Full DC inverter system, can be selected according to customs variety requests. 3.2 Auto addressing Addressing outdoor units and indoor units are automatically done just by pressing the button of the controller. The outdoor unit can automatically distribute the address to indoor units without any manual settings. Wireless controller can enquiry and modify every indoor units address Need to set manually one by one Improved Auto-Identified or set by remote controller It is possible to enable the shared use of the wiring between indoor & outdoor units, as well the centralized control. Connect ammeter and CCM02 and NIM06 to Mini VRF to achieve power consumption calculation. 8 General Information
11 Part 2 Outdoor Units 1. Specifications Dimensions Service Space Piping Diagrams Wiring Diagrams Field Wiring Capacity Tables Electric Characteristics Sound Levels Operation Limits Troubleshooting Outdoor units 9
12 1. Specifications Model MVUH120A-VA1 MVUH140A-VA1 MVUH160A-VA1 Power supply V-Ph-Hz V~50Hz V~50Hz V~50Hz Cooling Heating Capacity kw Input kw Capacity kw Input kw Max. input consumption W Max. current A Compressor Outdoor fan motor Outdoor fan Outdoor coil Model TNB306FPGMC TNB306FPGMC LNB42FSCMC Type Scroll Scroll Scroll Brand MITSUBISHI MITSUBISHI MITSUBISHI Capacity Btu/h Input W Rated current(rla) A Crankcase W Refrigerant oil ml FV50S 870ml+630ml FV50S 870ml+630ml FV50S 1400ml+250ml Model WZDK100-38G WZDK100-38G WZDK100-38G Type ACmotor ACmotor ACmotor Brand Panasonic Panasonic Panasonic Insulation class E E E Safe class IP23 IP23 IP23 Input W 2*100 2*100 2*100 Output W 2*85 2*85 2*85 Rated current A 2*0.9 2*0.9 2*0.9 Speed r/min Material ASG20 ASG20 ASG20 Type Axial fan Axial fan Axial fan Diameter mm Height mm Number of rows Tube pitch(a)x row pitch(b) mm 25.4/ * *22 Fin spacing mm Fin type (code) Hydrophilic aluminum Tube outside dia.and type mm Ф7.94 Ф7.94 Ф7.94 Inner groove tube Inner groove tube Inner groove tube Coil length x height mm 1276* * *870 Number of circuits Outdoor air flow m 3 /h Outndoor sound level(sound pressure level ) db(a) 57/54 57/54 57/54 Outdoor unit Dimension(W*H*D) mm 900*1327* *1327* *1327*320 Packing (W*H*D) mm 1030*1456* *1456* *1456*435 Net/Gross weight kg 95/106 95/ /111 Refrigerant Type R410A R410A R410A 10 Outdoor units
13 Charged volume g Electron expansion Electron expansion Electron expansion Throttle type valve valve valve Design pressure MPa 4.4/ / /2.6 Liquid side/ Gas side mm Ф9.52/Ф15.9 Ф9.52/Ф15.9 Ф9.52/Ф15.9 Max. refrigerant Refrigerant piping Connection wiring pipe length m Max. difference in level m Power wiring mm 2 5 core x core x core x 4.0 Signal wiring mm core shielded wire x core shielded wire x 3 core shielded wire x Ambient temp (Cooling -15~48)(Heating -15~27) tes: 1. The cooling conditions: indoor temp.: 27 C DB (80.6 F), 19 C WB (60 F) outdoor temp.: 35 C DB (95 F) equivalent pipe length: 5m drop length: 0m. 2. The heating conditions: indoor temp.: 20 C DB (68 F), 15 C WB (44.6 F) outdoor temp.: 7 C DB (42.8 F) equivalent pipe length: 5m drop length: 0m. 3. Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.0m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. The above data may be changed without notice for future improvement on quality and performance. Outdoor units 11
14 2. Dimensions Unit: mm Outdoor units
15 > Service Space Single unit installation (Wall or obstacle) Air inlet >300 Air inlet >300 >600 Maintain channel Air outlet Parallel connect the two units or above >300 >600 >2000 Parallel connect the front with rear sides >2000 >500 >3000 >3000 >300 Outdoor units 13
16 4. Piping Diagrams High pressure switch Electronic expansion valve Evaporator Electronic expansion valve Oil separator Condenser High pressure liquid accumulator can Compressor Oil return Capillary Low pressure switch Low pressure liquid accumulator can 14 Outdoor units
17 5. Wiring Diagrams Outdoor units 15
18 6. Field Wiring L N P Q E Outdoor Unit Power Supply 2 3x4.0mm Power Supply To CCM 3-Shielded wise 2 (3x0.5mm ) wire distribution box To other indoor unit 3x1.0mm 2 L N P Q E X Y E L N P Q E X Y E Indoor Unit Indoor Unit Indoor Unit Power ( V~ 50Hz) 1 Phase Outdoor Unit Switch / Circuit breaker Power wiring (outdoor) Communication Bus Power ( V~ 50Hz) 1-Phase Indoor Unit Switch / Circuit breaker Power wiring (indoor) Indoor Unit wire distribution box Indoor Unit in broken line table, users can purchase the Central control montior when necessary. Central control monitor (CCM) Computer Single phase indoor unit WHITE BLUE BLACK YELLOW GRAY BLACK Display board L N X Y E P Q E Y/G XT1 XT3 Wire controller Indoor Unit Power V~50Hz To Central Control Monitor (CCM) COMM. BUS To Outdoor COMM.BUS Please use 3-core shielded wire, and connect the shielded layer to Grounding To wire controller The reserved wire control function is indicated in broken line table, users can purchase the wire controller when necessary. 16 Outdoor units
19 7. Capacity Tables MVUH120A-VA1 Cooling Combinati on (%) (Capacity index) 130% 120% 110% Outdoor Indoor temperature( C WB) Air temperatu re( C TC PI TC PI TC PI TC PI TC PI TC PI TC PI DB) kw kw kw kw kw kw kw kw kw kw kw kw kw kw Outdoor units 17
20 % % % % Outdoor units
21 60% 50% te: 1. is shown as reference 2. In cooling mode, avoid the outdoor air temperature range from degree C, when selecting the models 3. The above table shows the average value of conditions may operate 4. It is recommended to connect less than 130% Outdoor units 19
22 Heating Combinati on (%) (Capacity index) 130% 120% 110% 100% Outdoor Air temperature( C DB) Indoor temperature( C WB) TC PI TC PI TC PI TC PI TC PI TC PI C DB C kw kw kw kw kw kw kw kw kw kw kw kw Outdoor units
23 90% 80% 70% Outdoor units 21
24 60% 50% te: 1. is shown as reference 2. In heating mode, avoid the outdoor air temperature range from -15 to -20 degree C, when selecting the models 3. The above table shows the average value of conditions may operate 4. It is recommended to connect less than 130% 22 Outdoor units
25 MVUH140A-VA1 Cooling Combinati on (%) (Capacity index) 130% 120% 110% 100% Outdoor Air temperatu re( C DB) Indoor temperature( C WB) TC PI TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw kw kw Outdoor units 23
26 90% 80% 70% Outdoor units
27 60% 50% te: 1. is shown as reference 2. In cooling mode, avoid the outdoor air temperature range from degree C, when selecting the models 3. The above table shows the average value of conditions may operate 4. It is recommended to connect less than 130% Outdoor units 25
28 Heating Combinatio n (%) (Capacity index) 130% 120% 110% 100% Outdoor Air temperature ( C DB) Indoor temperature( C WB) TC PI TC PI TC PI TC PI TC PI TC PI C DB C WB kw kw kw kw kw kw kw kw kw kw kw kw Outdoor units
29 90% 80% 70% Outdoor units 27
30 60% 50% te: 1. is shown as reference 2. In heating mode, avoid the outdoor air temperature range from -15 to -20 degree C, when selecting the models 3. The above table shows the average value of conditions may operate 4. It is recommended to connect less than 130% 28 Outdoor units
31 MVUH160A-VA1 Cooling Combinati on (%) (Capacity index) 130% 120% 110% 100% Outdoor Air temperatu re( C DB) Indoor temperature( C WB) TC PI TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw kw kw Outdoor units 29
32 90% 80% 70% Outdoor units 3.12
33 60% 50% te: 1. is shown as reference 2. In cooling mode, avoid the outdoor air temperature range from degree C, when selecting the models 3. The above table shows the average value of conditions may operate 4. It is recommended to connect less than 130% Outdoor units 31
34 Heating Combinatio n (%) (Capacity index) 130% 120% 110% 100% Outdoor Air temperature ( C DB) Indoor temperature( C WB) TC PI TC PI TC PI TC PI TC PI TC PI C DB C WB kw kw kw kw kw kw kw kw kw kw kw kw Outdoor units
35 90% 80% 70% Outdoor units 33
36 60% 50% te: 1. is shown as reference 2. In heating mode, avoid the outdoor air temperature range from -15 to -20 degree C, when selecting the models 3. The above table shows the average value of conditions may operate 4. It is recommended to connect less than 130% 34 Outdoor units
37 8. Electric Characteristics Model Outdoor Unit Power Supply Compressor OFM Hz Voltage Min. Max. TOCA MFA RLA kw FLA MVUH120A-VA V 198V 242V 30 30A MVUH140A-VA V 198V 242V 30 30A MVUH160A-VA V 198V 242V 30 30A Remark: TOCA: Total Over-current Amps. (A) MFA: Max. Fuse Amps. (A) RLA: Rated Locked Amps. (A) OFM: Outdoor Fan Motor. FLA: Full Load Amps. (A) KW: Rated Motor Output (KW) Outdoor units 35
38 9. Sound Levels ise level db(a) Model High speed Low speed MVUH120A-VA MVUH140A-VA MVUH160A-VA Outdoor units
39 10. Operation Limits Cooling Heating 45 Outdoor temperature( DB) Range for continuous operation Outdoor temperature( DB) Range for continuous operation Indoor temperature( WB) Indoor temperature( WB) Outdoor units 37
40 11. Troubleshooting 11.1 Troubles and causes of air conditioner If one of the following malfunctions occur, stop operation, shut off the power, and contact with your dealer. The operation lamp is flashing rapidly (twice every second) This lamp is still flashing rapidly after turn off the power and turn on again. Remote controller receives malfunction or the button does not work well. A safety device such as a fuse, a breaker frequently actuates. Obstacles and water enter the unit. Water leaks from indoor unit. Other malfunctions. If the system does not properly operate except the above mentioned cases or the above mentioned malfunctions is evident, investigate the system according to the following procedures. Symptoms Causes Solution Unit does not start Air flowing normally but completely can it cooling Units start or stop frequently Units start or stop frequently Low cooling effect Low heating effect Power failure. Power switch is off. Fuse of power switch may have burned. Batteries of remote controller exhausted or other problem of controller. Temperature is not set correctly. Be in 3 minutes protection of compressor Refrigerant is too little or too much. Air or no concreting gas in the refrigerating circuit. Compressor is malfunction. Voltage is too high or too low. System circuit is blocked. Refrigerant is too little or too much. Air or no concreting gas in the refrigerating circuit. Compressor is malfunction. Voltage is too high or too low. System circuit is blocked. Outdoor unit and indoor unit heat exchanger is dirty. The air filter is dirty. Inlet/outlet of indoor/outdoor units is blocked. Doors and windows are open. Sunlight directly shine. Too much heat resource. Outdoor temp. is too high. Leakage of refrigerant or lack of refrigerant. Outdoor temperature is lower than 7 C Doors and windows not completely closed. Leakage of refrigerant or lack of refrigerant. Wait for the comeback of power.. Switch on the power. Relocation. Replace the batteries or check the controller. Set the temperature properly. Wait. Check leakage, and rightly recharge refrigerant. Vacuum and recharge refrigerant. Maintenance or change compressor. Install manostat. Find reasons and solution. Check leakage, and rightly recharge refrigerant. Vacuum and recharge refrigerant. Maintenance or change compressor. Install manostat. Find reasons and solution. Clean the heat exchanger. Clean the air filter. Eliminate all dirties and make air smooth. Close doors and windows. Make curtains in order to shelter from sunshine. Reduce heat source. AC cooling capacity reduces normal). Check leakage and rightly recharge Refrigerant. Use heating device. Close doors and windows. Check leakage and rightly recharge refrigerant. 38 Outdoor units
41 11.2 Troubles and causes of remote controller Before asking for serving or repairing, check the following points. Symptoms Causes Solution The fan speed can not be changed. The remote controller signal is not transmitted even when the ON/OFF button is pushed. The TEMP.Indicator does not come on. The indication on the display disappears after a lapse of time. The TIMER ON indicator goes off after a lapse of certain time. receiving tone sounds from the indoor unit even when the ON/OFF button is pressed. Check whether the MODE indicated on the display is "AUTO" Check whether the MODE indicated on the display is "DRY" Check whether the batteries in the remote controller are exhausted. Check whether the MODE indicated on the display is FAN ONLY Check whether the timer operation has come to an end when the TIMER OFF is indicated on the display. Check whether the timer operation is started when the TIMER ON is indicated on the display. Check whether the signal transmitter of the remote controller is properly directed to the infrared signal receiver of the indoor unit when the ON/OFF button is pressed. When the automatic mode is selected, the air conditioner will automatically change the fan speed. When dry operation is selected,the air conditioner automatically change the fan speed. The fan speed can be selected during "COOL", "FAN ONLY", and "HEAT" The power supply is off. The temperature cannot be set during FAN mode. The air conditioner operation will stop up to the set time Up to the set time, the air conditioner will automatically start and the appropriate indicator will go off. Directly transmit the signal transmitter of the remote controller to the infrared signal receiver of the indoor unit, and then repeatly push the ON/OFF button twice. Outdoor units 39
42 1 Indoor/outdoor communication malfunction Indoor/outdoor communication malfunction Short circuit or open circuit of communication wire P, Q and E Exist Check communication wire (generally measuring resistance between P, Q and E) OK Repetition of address code to indoor unit Irregular connection of communication wire (causing E2 error and indefinite variation or reduction in the number of indoor units) OK Some indoor units are not power-on (reduction in the number of indoor units) Communication wire is not in serial connection (such as star connection or parallel connection) Communication wires does not be separated from Power wires, causing interference There are other electronic magnetic interference sources nearby, such as transformer, strong solar light and so on Exist Rule out interference source, or add shielding and filters OK Communication wire is too long, exceeding specified value. Exceed Make proper regulation or strengthen signal OK Chip fault, or chip foot sheds off, or chip is inverted (correct mode is semicircular bent alignment) Error Reinstall chip, or install other chip with same model on the faulty unit, to check whether there is something wrong with chip. OK OK Main board error: For example, getting wet Replace main board 40 Outdoor units
43 11.3 Malfunction Code of Outdoor unit Display E0 E2 E3 E4 E5 E6 E7 E8 P0 P1 P2 P3 P4 P5 P6 P7 P8 Malfunction or Protection EEPROM malfunction Communication fault of the outdoor chip and the indoor chip Communication fault of 9177and IPDU T3, T4 sensor fault Voltage protection fault Direct-current fan fault Heating fan fault in the area A lasts for 5 minutes There are two times E6 fault in 10 minutes (recovery after power off) The Heat sink high temperature protection High pressure protection Low pressure protection Compressor current protection Discharge temperature protection Outdoor condenser T3 high temperature protection IPDU modules protection Evaporator T2 high temperature protection Typhoon protection(recovery after Typhoon) 1) E0 malfunction LED indicates E0 EEPROM malfunction Judge 1: Check whether the EEPROM()is inserted well Insert the EEPROM well Replace outdoor main board Outdoor units 41
44 2) E2 malfunction LED indicates E2 Communication malfunction between indoor/outdoor units Judge 1: Check whether the indoor unit power is on Turn on the indoor unit power Judge 2: Check whether the signal wiring is shield cable or whether the shield cable is grounded Adopt the shield cable/ shield cable grounded Judge 3: Check whether the signal wiring between the indoor and outdoor units is wrong polarity? Connect the signal wiring correctly Judge 4: Check whether the signal wiring between the indoor and outdoor units is broken? Replace the broken wiring Indoor or outdoor main board is broken, replace the main board until the malfunction is disappear 42 Outdoor units
45 3) E3 malfunction LED indicates E3 Communication malfunction in outdoor PCB Check whether the indicator lights LED1 on the main board 2 are flashing Replace the oudoor main board 2 Check whether the connecting wiring between the IPM module and the CN1 on the main board 2 is break off Disconnect the connecting wiring between the IPM module and the CN1 on the main board2, use the multimeter to measure the voltage between the IPM module CN1 port s 3 and 4 pillar, check whether it is 5V, (the third pillar on the main board labels +5V) Insert the connecting wiring well over again I Replace outdoor main board2 Check whether the connecting wiring between the IPM module positive pole and the CN12 on the power board is break off Insert the connecting wiring well over again Use the multimeter to measure whether the voltage between the P and the N on the power board is between +(277V~345)V Replace the IPM module Replace the power board Outdoor units 43
46 4) E4 malfunction LED indicates E4 Judge 1: condenser s middle temp. sensor (T3) are malfunction Check whether the wiring of the condenser s middle temp. sensor (T3) are break off Connect the wiring well Check whether the resistance of condenser s middle temp. sensor (T3) is wrong refer to the Annex 1 Replace condenser s middle temp. sensor (T3) Judge 2: Outdoor ambient temp. sensor (T4) is malfunction Check whether the wiring of the outdoor ambient temperature sensor (T4) is break off Connect the wiring well Check whether the resistance of outdoor ambient temperature sensor (T4) is wrong refer to the Annex 1 Replace outdoor ambient temperature sensor (T4) Replace PCB 44 Outdoor units
47 5) E5 malfunction LED indicates E5 Outdoor unit voltage protection Check the voltage of outdoor unit power supply, whether the voltage between L1 and N is about V Check the power supply Replace the filter board, and then check whether the system can run normally Trouble is solved Replace outdoor main board Outdoor units 45
48 6) E6 malfunction LED indicates E6 Outdoor unit fan motor malfunction Judge 1:Check the wiring connected is right according the wiring diagram Connect wiring right according the wiring diagram Judge 2: DC power supply voltage is normal Check the Voltage between DC fan motors red terminal and black terminal is V at stand by state. Judge 3DC fan motor power supply is normal, Check the Voltage between DC fan motors white terminal and black terminal is 15V at stand by state. Judge 4:outdoor unit is running after indoor unit start 3mins later Change Module Check the voltage of the fan motor between yellow terminal and black terminal is more than 2.4V Check the power supply of PFC is V IPM Replace motor Replace PFC module fan Replace main board 46 Outdoor units
49 7) E7 malfunction When LED indicates E7, please connect local branch company. 8) P0 Protection Recovery the compressor stop three minutes later for temperature reduced. LED indicates P0 Heat sink high temperature protection Stop unit and waiting for Three minutes for temperature reduced, restart unit again. Unit is running normally Outdoor units 47
50 9) P1 malfunction LED indicates P1 High pressure protection Judge 1: Whether the wiring between the high pressure switch and main control board is connected well or correctly Connect it well Judge 2: Whether the high pressure switch is broken Validate: Short connect the high pressure switch socket, check whether the system can run normally Replace high pressure switch Check whether the refrigerant system is ok Judge 3: Check whether the outdoor ambient temperature is too high Stop the unit Judge 4: Check whether the outdoor unit is bad ventilation Make the outdoor unit ventilate well Judge 5: Check whether the heat exchanger is dirty Clean the heat exchanger Judge 6: Check whether the refrigerant pipe is blocked Drop refrigerant, then use the high pressure nitrogen or refrigerant to blow pipe, vacuumize and add the refrigerant again Replace outdoor main board 48 Outdoor units
51 10) P2 malfunction LED indicates P2 Low pressure protection Judge 1: The wiring between the low pressure switch and main control board is connected well or correctly Connect it well Judge 2: Whether the low pressure switch is broken Validate: Short connect the low pressure switch socket, check whether the system can run normally Replace low pressure switch Check whether the refrigerant system is ok Judge 3: Check whether the outdoor ambient temperature is too low Stop the unit Judge 4: The refrigerant of the system is leakage Validate: Connect the pressure gauge to the gauge joint of the system, check whether the pressure is lower than 0.15MPa Leak hunting: charge nitrogen or refrigerant to the system, if the leakage is serious, there will be distinct gas leakage cici sound; if the leakage is little, use the suds(mixture of water and abluent is also ok, if it can make bubble) or electronic leak detector. Judge 5: The refrigerant pipe is blocked Drop refrigerant, then use the high pressure nitrogen or refrigerant to blow pipe, vacuumize and add the refrigerant again Replace outdoor main board Outdoor units 49
52 11) P3 malfunction LED indicates P3 Outdoor unit current protection Judge 1: Check whether the input current of the power supply wire is more than 30A Check whether the refrigerant system is ok Replace the filter board, then check whether the system can run normally Replace outdoor PCB Trouble is solved Judge 2: Check whether the outdoor ambient temperature is too high Stop the unit Judge 3: Check whether the outdoor unit is bad ventilation Make the outdoor unit ventilate well Judge 4: Check whether the heat exchanger is dirty Clean the heat exchanger Judge 5: The refrigerant pipe is blocked Drop refrigerant, then use the high pressure nitrogen or refrigerant to blow pipe, vacuumize and add the refrigerant again Replace outdoor main board 50 Outdoor units
53 12) P4 malfunction When compressor discharge temperature is more than 115 C, the unit will stop, and unit runs again when compressor discharge temperature is less than 90 C. LED indicates P4 Compressor discharge temperature protection Check whether the compressor discharge temp. more than 115 C? Check whether the wiring connection is right between compressor discharge temp. sensor and PCB according to wiring diagrams Judge: The discharge temp. sensor is broken Correct the wiring connection Check whether the refrigerant is leakage Stop leaking and add refrigerant Validate: Check whether the resistance of compressor discharge temp. sensor is right refer to the Annex 2 Replace the compressor discharge temp. sensor Replace outdoor main board Outdoor units 51
54 13) P5 malfunction When condenser high temp. is more than 65 C, the unit will stop, and unit runs again when outdoor pipe temp. less than 52 C. LED indicates P5 Condenser high temperature protection Check whether the condenser temperature is more than 65 C Check whether the resistance of condenser temp. sensor is correct refer to the Annex 1 Replace the temperature sensor Replace outdoor PCB Stop the unit Judge1: The outdoor temp. is too high(more than 43) Clean the heat exchanger Judge 2: Check whether the heat exchanger is dirty Drop refrigerant, then use the high pressure nitrogen or refrigerant to blow pipe, vacuumize and add the refrigerant again Judge 3: The refrigerant pipe is blocked Replace outdoor PCB 52 Outdoor units
55 14) P6 malfunction LED indicates P6 IPDU modules protection Check whether the voltage range of P-N on IPM module is normal? DC V Check whether the input power supply is correct? V,1N, 50Hz Regulate it to correct, then check whether the system can work normally? Check whether the connecting line between main board and the IPM module is connected tightly Connect it tightly, check ok or not? Check whether the power supply line is connected correctly and tightly Connect it correctly and tightly, check ok or not? Check whether the connecting line of the compressor is connected tightly Connect it tightly, check ok or not? Check whether the lines in E-part box are connected tightly Connect it tightly, check ok or not? Replace the IPM module, check whether the system can work normally? Trouble is solved Check whether the three phase bridge is normal? Replace the three phase bridge Replace the main board, check whether the system can work normally? Check whether the 3300µF/400V electrolytic capacitor is normal? Trouble is solved Replace this electrolytic capacitor Replace the compressor, check whether the system can work normally? Trouble is solved Outdoor units 53
56 15) P7 malfunction LED indicates P7 Judge1: T2 Evaporator High temperature protection Check:Indoor unit Evaporator temperature is high Recovery when temperature is down Judge2:Temperature sensor port connected is right Connect wiring well Replace temperature sensor and check the system is running normally Unit recovery Replace main board 54 Outdoor units
57 Part 3 Installation 1. Summarize of Installation Outdoor Units Installation Installation of Refrigerant Pipe Processing & Installation of Drainage Pipe Insulation Work Electric Installation Test Running Precautions on Refrigerant Leakage Installation 55
58 1. Summarize of Installation 1.1 Installation Procedure 56 Installation
59 1.2 Install indoor units Procedure: Confirm installation position Label installation position Install hooks Install indoor units te: (1) The hook must strong enough to sustain the weight of indoor unit. (2) Check the models of indoor units before installation. (3) Pay attention to the main devices, such as the pipeline. (4) Hold enough places for maintenance. 1.3 Refrigerant pipe Procedure: Install indoor units Install pipe Weld Add Nitrogen Temporary pipeline Flush Pressure test Vacuum dry 1.4 Drainage pipe Procedure: Install indoor units Connect drainpipe Check water leakage Drainpipe heat-insulation and test-run te: It is no need to insulate the drainpipe if you choose the plastic pipe as drainpipe. 1.5 Electric wiring (1) Please select power supply for indoor unit and outdoor unit separately. Both indoor units and outdoor units should be grounded well. (2) The power supply should have specified branch circuit with leakage protector and manual switch. (3) Please put the connective wiring system between indoor unit and outdoor unit with refrigerant piping system together. (4) Power wiring should be done by professional electrician and complied with relevant National Electric Standard. (5) The power supply, leakage protector and manual of all the indoor units connecting to the same outdoor unit should be universal. (Please set all the indoor unit power supply of one system into the same circuit.) (6) It is suggested to use 3-core shielded wire as signal wire between indoor and outdoor units, multi-core wire is unavailable. Pay attention to the consistency. When signal wire parallel to the power wire, please keep enough distance (about 300mm at least) to prevent interference. (7) The power wire and signal wire can t be enlaced together. 1.6 Lay the indoor pipeline te: Collocate the air-outlet reasonably to prevent airflow short-circuit. Check the static pressure whether in the allowable range. The air filters should be easy to unpick and wash. Do pressure test on pipeline. Installation 57
60 1.7 Heat-insulation Procedure: Refrigerant pipe work Check the heat-insulated part Pressure test Heat-insulation work te: For welding part, flare part and branch pipe, heat-insulation work must be done after finished the pressure test. 1.8 Install outdoor unit te: (1) Gutter must be set around the foundation to drain the condensation water. (2) When installing outdoor units at the roof, please check the strength of the roof and pay attention not to destroy the waterproof of the roof. 1.9 Recharge refrigerant Procedure: Calculate the added volume according to liquid pipe length Recharge refrigerant te: Please calculate the additional amount of refrigerant according to the formula that we supply to you, and the calculation result must be correct 1.10 Main points of test running and debugging Please check the following issues before turning on the power: (1) Vacuum dry: Make sure the vacuum degree accord with our requirement about (2) Wiring: Includes the power wiring and communication wiring; Recheck the connection according to our corresponding wire diagrams. Especially, please remember our communication wire is polar; it means you must connect the communication wire correspondingly to the terminal block. (3) Additional charge of refrigerant: Recheck the calculation formula and recalculate the total recharge volume according to our supplied formula. (4) Open the stop-valve of gas and liquid pipe with Allen key; Check leakage of stop-valve with soap water. Please confirm whether the outdoor unit has been connected to the power for 12hr before start test running. Test running: Turn on all of the indoor units with cooling mode and set the temperature in 17degree with high fan speed first, after the system operated, test following operation parameters of the system, including indoor units and outdoor units parameters. 58 Installation
61 > Outdoor Units Installation 2.1 Installation place Please keep away from the following place, or malfunction of the machine may be caused: There is combustible gas leakage. There is much oil (including engine oil) ingredient. There is salty air surrounding (near the coast) There is caustic gas (the sulfide, for example) existing in the air (near a hot spring) A place the heat air expelled out from the outdoor unit can reach your neighbor s window. A place that the noise interferes your neighbors everyday life A place that is too weak to bear the weight of the unit Uneven place. Insufficient ventilation place. Near a private power station or high Frequency equipment. Install indoor unit, outdoor unit, power cord and connecting wire at least 1m away from TV set or radio to prevent noise The insulation of the metal parts of the building and the air conditioner should comply with the regulation of National Electric Standard. CAUTION Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from televisions and radios. This is to prevent image interference and noise in those electrical appliances. (ise may be generated depending on the conditions under which the electric wave is generated, even if 1 meter is kept.) 2.2 Installation space Single unit installation (Wall or obstacle) Air inlet >300 Air inlet >300 >600 Maintain channel Air outlet Parallel connect the two units or above >300 >600 >2000 Parallel connect the front with rear sides >2000 >500 >3000 >3000 >300 Installation 59
62 >60cm 2.3 Moving and installation mm Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling. Never hold the inlet of the outdoor unit to prevent it from deforming. Do not touch the fan with hands or other objects. Do not lean it more than 45, and do not lay it sidelong. Make concrete foundation according to the specifications of the outdoor units.(refer to below Fig) Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind. (refer to below Fig) Fix with bolt NOTE All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you purchased (depend on model).the actual shape shall Prevail. 60 Installation
63 3. Installation of Refrigerant Pipe CAUTION To prevent the refrigerant piping from oxidizing inside when welding, it is necessary to charge nitrogen, or oxide will chock the circulation system. 3.1 Using Branch pipe Length and Drop Height Permitted of the Refrigerant piping Outdoor unit Drop Height between Indoor unit and outdoor Unit L The first Line Branch Pipe 1 L 3 L 2 Maximum Piping Equivalent Length (From the first Line branch pipe) Maximum piping Equivalent Length L 4 L5 L6 A B C D E Indoor Unit to Indoor Unit Drop Height Indoor Unit Pipe Length Drop Height Maximum Piping(L) Total Pipe Length (Actual) Actual Length Equivalent Length Permitted value 100m 45m 50m Piping L1+L2+L3+L4+L5+L6 +A+B+C+D+E L1+L3+L4+L5+L6+ E Pipe length (from the first line branch to farthest indoor unit) 20m L3+L4+L5+L6+E Indoor Unit outdoor unit Drop Height Outdoor Unit Up 30m / Outdoor Unit Down 20m / Indoor Unit to Indoor Unit Drop Height 8m / te: Conversion of the equivalent length: Convert into the direct pipe length according to branch Junction 0.5m/l Installation 61
64 3.1.2 Pipe size selection Selection of the refrigerant pipe Type of the pipe Connecting part. Main pipe Between outdoor branch joint and first branch joint 1 Indoor main pipe Between indoor branch joint 2 Indoor pipe Between branch part and indoor unit How to choose the Branch part and the refrigerant pipe? According the total capacity of outdoor units to select the dimension of main pipe 1: Refrigerant R410A Remarks Capacity of outdoor unit (kw) Gas side Liquid side 12 Φ15.9 Φ Φ15.9 Φ Φ15.9 Φ9.52 A converter pipe is needed for the connection between first branch joint and outdoor unit. tes: Branch header must be connected with indoor units directly, the further branch connection is not allowed The maximum connection of indoor units: Capacity of Maximum Quantity of Sum capacity of indoor unit Capacity of outdoor unit (kw) Outdoor unit Indoor unit (kw) (horsepower) %~130% %~130% %~130% According the capacity of indoor units to select indoor main pipe 2, main pipe 3 and branch joint: A: the total capacity and the gas side/liquid side pipe of indoor units Down side indoor unit capacity A (x 100W) Liquid side mm Gas side mm Name of indoor unit branch pipe A<166 Φ9.5 Φ19.1 FQZHN A<230 Φ9.5 Φ22.2 FQZHN Modification main pipe 1: According to the and step of calculation result, If the main pipe dimension according to outdoor capacity selection result are different from indoor capacity selection result, so the main pipe dimension you should selection bigger pipe. 62 Installation
65 Connecting method Gas side Liquid side 4, 5,6 HP Outdoor unit Flaring nut Flaring nut The dimension of branch part Branch list 3.2 Using four divergence box Length and Drop Height Permitted of the Refrigerant piping Outdoor unit 20m Drop height between indoor unit and outdoor unit L1 A L2 Four divergence box B L3 L5 D L4 8m Indoor Unit to Indoor Unit Drop Height Indoor unit te: The divergence box should be placed between the indoor and outdoor units. Forbid to connect another divergence boxes to a indoor unit. Installation 63
66 L1 Four divergence box L5 L2 L3 Four divergence box L4 A B. Total Pipe Length (Actual) Permitted value 100m Piping L1+L2+L3+L4+L5 Pipe Length Drop Height Maximum Piping(L) 45m 50m L1+L2,,L1+L3, L1+ L4,L1+L5 Pipe length (from divergence box to indoor unit pipe) 20m L2,L3,L4,L5 Indoor Unit outdoor unit Drop Height Outdoor Unit Up 20m / Outdoor Unit Down 20m / Indoor Unit to Indoor Unit Drop Height 8m / Outdoor side Indoor side Four divergence box Liquid side Gas side Liquid side Gas side mm mm mm mm Φ9.5 Φ15.9 Φ6.4 Φ12.7 te: Model limitation: Each Indoor unit capacity 7100W Four divergence box dimension Dimension Φ15.9 Φ Φ Φ25 Φ6.4 Unit: mm 64 Installation
67 Installation instruction Thermal insulation pipe (pay attention to thermal insulation work) Hoisting bar Thermal insulation pipe Connect to the outdoor unit Connect to 1-4 set indoor unit Hoisting ceiling Hoisting bar Divergence box 3.3 Refrigerant Amount to be added Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit connection. Table 6-8 Liquid Side Piping Diameter Refrigerant to be added Per meter Piping kg kg kg kg kg kg NOTE: Additional refrigerant volume of branch pipe is 0.1kg per item (Consider the liquid side of branch pipe only) Installation 65
68 4. Processing & Installation of Drainage Pipe 4.1 Gradients and Supporting Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as possible and eliminate the air bubble The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/100 and prevent bending. Refer to the following table for the specification of the prop stand. Diameter Distance between the prop stands Hard PVC pipe 25~40mm 1.5~2m Precautions The diameter of drainpipe should meet the drainage requirement at least. The drainpipe should be heat-insulated to prevent atomization. Drainpipe should be installed before installing indoor unit. After powering on, there is some water in water-receiver plate. Please check if the drain pump can act correctly. All connection should be firm. Wipe color on PVC pipe to note connection. Climbing, horizontal and bending conditions are prohibited. The dimension of drainpipe can t less than the connecting dimension of indoor drainpipe. Heat-insulation should be done well to prevent condensation. Indoor units with different drainage type can t share one convergent drainpipe. Drainpipe Installation for four divergence box. Hoisting ceiling Hoisting bar Divergence box m Gradient:higher than 1/100 Level Drain pipe a. Drainpipe from main body must be wrapped by insulation tube evenly, and bound by tighten band for obstructing air getting in and coagulation. b. Prevent from water backflow into unit inside during shutdown, the drain pipe shall place down side and drain water to outdoor (drain side), the gradient of the drain pipe should be higher than (1/100), without salient and water remain. c. When connecting drainpipe, don t drag the pipe that would pull the main unit. For this, please arrange bearing points every 0.8 to 1.0 meter to avoid pipe be bended. 4.2 Drainpipe Trap For condenser water outlets on the chassis for slection display as the follow figure. Outlet for power and connecting pipes Reserve water outlet (Need to knock open) Reserve water outlet (With rubber stopper) Water Outlet 66 Installation
69 4.2.1 If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap Every indoor unit needs one drainpipe trap A plug should be designed to do cleaning. Plug Plug 50cm 50cm 50cm 50cm 4.3 Upward drainage (drain pump) For Four-way cassette (compact) For Four-way cassette 4.4 Convergent drainage The number of indoor units should be as small as possible to prevent the traverse main pipe overlong Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system. Selection the diameter Number of connecting indoor units Calculate drainage volume Select the diameter Installation 67
70 Calculate allowed volume =Total cooling capacity of indoor units (HP) 2 (l/ hr) Allowed volume(lean 1/100) (l/ hr) I.D. (mm) Thick Hard PVC Hard PVC 14< Hard PVC 88< Hard PVC 175< Hard PVC 334< Connect Drainage pipe from four divergence box Connect to the outdoor unit Connect to indoor unit Connect to drainage pipe If it necessary to connect drainage pipe to another side, it need to convert water tank Drainage test Drainage without drain pump After finishing drainpipe installation, pour some water into the water plate to check if the water flows smoothly. 68 Installation
71 4.5.2 Drainage with drain pump Poke the Water Level Switch, remove the cover, and use water pipe to pour 2000ml water into the water plate through the water inlet Turn on the power to cooling operation. Check the pump s operation and switch on the Water Level Switch. Check the pump s sound and look into the transparent hard pipe in the outlet at the same time to check if the water can discharge normally Stop the air conditioner running, turn off the power, and put back the cover. Stop the air conditioner. After 3 minutes, check if it has abnormity. If the collocation of drainpipes is illogical, the water will flow back overfull, which will cause the alarm lamp flashes, even circumfluence from the water plate. Keep on pouring water until it gives an alarm signal for high water level, check if the pump drains water at once. If the water level can t fall below the alarmed water level after 3 minutes, the air conditioner will stop (means this indoor unit stops, stand-by, but the outdoor unit still work if there is capacity requirement). Turn off the power and drain the remained water, then turn on the air conditioner. te: the drain stopper in the main water plate is for maintenance. Stuff up the drain stopper to prevent water leakage. Installation 69
72 5. Insulation Work 5.1 Insulation material and thickness Insulation material Insulation material should adopt the material, which is able to endure the pipe s temperature: no less than 70 in the high-pressure side, no less than 120 in the low-pressure side (For the cooling type machine, no requirements at the low-pressure side.) Example: Heat pump type----heat-resistant Polyethylene foam (withstand above 120 ) Cooling only type---- Polyethylene foam (withstand above 100 ) Thickness choice for insulation material Insulation material thickness is as follows: Refrigerant pipe Pipe diameter (mm) Adiabatic material thickness 10mm 15mm 20mm Drainage pipe Inner diameter mm 5.2 Refrigerant pipe insulation Work Procedure Before laying the pipes, the non-jointing parts and non-connection parts should be heat insulated. After the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat insulated Select the branch pipes model according to the Model Selection Guide and the downstream indoor unit capacity. According to the actual piping size and cut off the needless parts with special tools such as cutter. Branch pipe part Connection Cut off the part from middle site Field pipe Pay attention to the distance of straight horizontal pipe a. The straight horizontal pipe s distance between two adjacent branch pipes should 1m. b. Distance between two adjacent branches should 1m. c. The straight horizontal pipe s distance which indoor unit connecting behind the branch pipe should 0.5m. The MIN. length of straight pipe connected to four divergence box 70 Installation
73 >1m Indoor unit Outdoor unit >0.5m >1m >0.5m Four divergence box a. The distance between outdoor unit and the nearest of straight pipe need to be >1m. b. The distance between the divergence input terminal and the nearest turning site of straight pipe need to be >1m. c. The distance between the divergence output terminal and the nearest turning site of straight pipe need to be >0.5m. d. The distance between indoor unit and the nearest turning site of straight pipe need to be >0.5m. Pay attention to lay horizontally and vertically. ±10 Direction A Direction B ±10 A horizontally incline angle should not larger than 10. ±10 B Vertical A Insulation for non-jointing parts and non-connection parts Wrong Gas pipe and liquid pipe should not be put together to insulate Insulate the gas pipe (Cooling only) Right Insulate the gas pipe and the liquid pipe Installation 71
74 For construction convenience, before laying pipes, use insulation material to insulate the pipes to be deal with, at the same time, at two tips of the pipe, Remain some length not to be insulated, in order to be welded and check the leakage after laying the pipes. Insulate for the jointing area, expanding area and the flange area Insulate for the jointing area, expanding area and the flange area should be done after checking leakage of the pipes Make sure there s no clearance in the joining part of the accessorial insulation material and local preparative insulation material. Enswathe disposal After insulation of the pipes, do the enswathe disposal with binding belt, make sure it s tight. te: When use four divergence box, the un-connected inlet pipe needs to be sealed up Connect to indoor unit If the indoor unit pipe size is larger than four divergence box indoor side pipe size,it need to change small adaptor to bigger one. 72 Installation
75 Drainage pipe insulation The connection part should be insulated, or else water will be condensing at the non-insulation part. 5.4 te The jointing area, expanding area and the flange area should be heat insulated after passing the pressure test The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually Use the attached heat-insulation material to insulate the pipe connections (pipes tie-in,expand nut ) of the indoor unit. Installation 73
76 6. Electric Installation CAUTION Please select power source for indoor unit and outdoor unit respectively The power supply has specified branch circuit with leakage protector and manual switch. Indoor unit connect with power supply which is V~50Hz. Outdoor unit connect with power supply which is V~ 50Hz (Please set all the indoor unit power of one system into the same branch circuit.) Please put the connective wire system between indoor unit and outdoor unit with the refrigerant system together. Use 3-core screened wire as indoor and outdoor control wire. The installation should comply with relevant national electric standard. Power wiring should be engaged by specialized electrician. 6.1 Outdoor Unit Wiring The Specification of Power Table 6-1 Outdoor Unit power Capacity Phase Frequency and Voltage 12kW-14kW 1N phase V~ 50Hz Power Wiring(mm 2 ) 3-core X 4.0 Circuit Breaker/Fuse (A) 40 Indoor unit/outdoor unit Signal wire (Weak electric signal) (mm 2 ) 3-core shielded wire 3X0.5 CAUTION A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation. Power ( V~ 50Hz) 1 Phase Outdoor Unit Switch / Circuit breaker Power wiring (outdoor) Communication Bus Power ( V~ 50Hz) 1-Phase Switch / Circuit breaker Indoor Unit Power wiring (indoor) Indoor Unit wire distribution box Indoor Unit in broken line table, users can purchase the Central control montior when necessary. Central control monitor (CCM) Computer Fig Installation
77 L N P Q E Outdoor Unit Power Supply 2 3x4.0mm Power Supply To CCM 3-Shielded wise 2 (3x0.5mm ) wire distribution box To other indoor unit 3x1.0mm 2 L N P Q E X Y E L N P Q E X Y E Indoor Unit Indoor Unit Indoor Unit Fig.6-2 CAUTION The reserved function is indicated in broken line table, users can select it when necessary. Indoor/Outdoor Unit Signal Wire Connect the wire according to their numbers. Wrong connection may cause malfunction. Wiring Connection Seal the wiring connection with the insulation material, or the condensing dew will be caused. NOTE The air-conditioners can connect with Central Control Monitor (CCM). Before operation, please wiring correctly and set system the air-conditioners can connect with Central Control Monitor (CCM). Before operation, please wiring correctly and set system Single phase indoor unit WHITE BLUE BLACK YELLOW GRAY BLACK Display board L N X Y E P Q E Y/G XT1 XT3 Wire controller Indoor Unit Power V~50Hz To Central Control Monitor (CCM) COMM. BUS To Outdoor COMM.BUS Please use 3-core shielded wire, and connect the shielded layer to Grounding To wire controller The reserved wire control function is indicated in broken line table, users can purchase the wire controller when necessary. Fig.6-3 Installation 75
78 6.2 Indoor Unit Wiring Power Supply Table 6-2 indoor Unit power Capacity (Kw) 1.8~16 Phase Frequency and Voltage Power Wiring(mm 2 ) 1- phase V~ 50Hz 3-core 1.0 Circuit Breaker (A) 15 Indoor unit/outdoor unit Signal wire (Weak electric signal) (mm 2 ) 3-core shielded wire 3X Signal wire is 3-core, polarized wire. Use 3-core shield wire to prevent interference. The grounding method now is grounding the closed end of the shield wire and opening (insulating) at the end. Shield is to be grounded. 2. The control between outdoor unit and indoor unit is BUS type. An address is set on field during the installation. CAUTION The wire diameter and continuous length is under the condition that the voltage vibration is within 2%. If the continuous length is exceed showing value, choose the wire diameter follow relevant regulation. 76 Installation
79 Indoor unit power supply wiring Indoor Power Supply Circuit Breaker Manual swtich Wire Distribution Box Indoor Unit Fig.6-4 CAUTION 1. Refrigerant piping system, indoor unit-indoor unit connection signal wires and indoor unit-outdoor unit connection signal wire are in the same system. 2. When power cord is parallel with signal wire, please put them into separate wire distribution pipes, and leave a proper distance. (Reference distance: It is 300mm when current capacity of power cord is less than 10A, or 500mm when 50A). Please use shield wire as indoor unit/outdoor unit signal wire. Indoor/Outdoor unit signal wire wiring Outdoor Unit Close end of the connection shielded wire Indoor/Outdoor Unit Signal Wire (open) in broken line table, users can purchase the wire controller when necessary. Fig.6-5 Installation 77
80 7. Test Running Operate according to gist for test running on the electric control box cover. CAUTION Test running cannot start until the outdoor unit has been connected to the power for 12hr. Test running cannot start until all the valves are affirmed open. Never make the forced running. (Or the protector sits back, danger will occur.) 78 Installation
81 8. Precautions on Refrigerant Leakage This air conditioner (A/C) adopts innocuous and nonflammable refrigerant. The locating room of the A/C should big enough that any refrigerant leakage is unable to reach critical thickness. So certain essential action can be taken on time. Refrigerant critical thickness: 0.44[kg/m] for R410A. Confirm the critical thickness through follow steps, and take necessary actions. 1. Calculate the sum of the charge volume (A[kg]) Total Refrigerant volume of 10HP=factory refrigerant volume + super addition 2. Calculate the indoor cubage (B[m]) (as the minimum cubage. 3. Calculate the refrigerant thickness A[kg] critical thickness 3 B[m ] Counter measure against over high thickness 1. Install mechanical ventilator to reduce the refrigerant thickness under critical level. (ventilate regularly) 2. Install leak alarm facility related to mechanical ventilator if you cannot regularly ventilate. Outdoor unit Indoor unit Room full of leak refrigerant (All refrigerant has run up) b. Leak alarm related to mechanical ventilator Indoor unit (Leak hunting siren should be installed in places easily keep refrigerant) A. Ventilation peristome NOTE Please press constraint cool button to carry out refrigerant recycling process. Keep the low pressure above 0.2MPa; otherwise compressor may be burnt out. Installation 79
Contents. Part 1 General Information... 1. Part 2 Outdoor Units... 9. Part 3 Installation... 50. Part 4 Troubleshooting 73
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF Contents Part 1 General Information... 1 Part 2 Outdoor Units... 9 Part 3 Installation... 50 Part 4 Troubleshooting 73 Part 5 Control System... 100 Manufacture
Appendix - Controllers 179
Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2
DM13-01.01.01en. Service manual MIV V5 HEAT PUMP DC INVERTER R410A MVUH252B-VA3 MVUH280B-VA3 MVUH335B-VA3 MVUH400B-VA3 MVUH450B-VA3 MVUH500B-VA3
DM13-01.01.01en Service manual MIV V5 HEAT PUMP DC INVERTER R410A MVUH252B-VA3 MVUH280B-VA3 MVUH335B-VA3 MVUH400B-VA3 MVUH450B-VA3 MVUH500B-VA3 Contents Part 1 General Information... 1 Part 2 Selection
FULL DC INVERTER SYSTEMS
FULL DC INVERTER SYSTEMS INDIDUAL AND MODULAR DESIGN & FLEXIBLE COMBINATION commercial air conditioners SDV4 2011/2012 AIR CONDITIONING 1 WELCOME TO THE WORLD of SINCLAIR AIR CONDITIONERS Company operation
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
HP switch LP switch Discharge thermo Comp. Surface thermo
1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer
technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy
LG Air conditioning Company Multi V Water Ⅱ Air Conditioning Academy 1.1 What is Multi V Water II? High Performance Prospect rights Water pipe Refrigerant pipe Indoor unit Beautiful Exterior Convenience
Air Conditioners Technical Data
Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/
SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the
SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability
PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories
1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/
1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/ ISO 9001 ISO 14001 Certified number : 01 100 89394 Certified number : 01 104 9245101 Fujitsu General (Thailand) Co.,
Unico Inverter. Unique and efficient.
Unico Inverter. Unique and efficient. INTERNATIONAL PATENT PENDING The first fixed air conditioner without outdoor unit featuring DC Inverter technology. Great performance, reduced consumption. Designed
Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75
Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER
Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0
Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view
Versati Air to Water Heat Pump
Versati Air to Water Heat Pump VERSATI DC Inverter Multifunctional Air To Water Heat Pump Nowadays, people are increasingly focusing on heating costs as well as environmental issues. Traditional heating
CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description
Description Compact air/water heat pump for outside installation. With suction gas cooled rotary compressor. With extensive aluminium/cu lamellar tube evaporator and PVC Titanium condenser. Axial fan Refrigerant
TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO.
TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA
Hitachi Air Conditioning. Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE
Hitachi Air Conditioning Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE Contents Page 04 Product Range 08-09 RAC Summit Wall Mounted 10 RAC Shirokuma Wall mounted 11 RAC S Series - Wall
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE
INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE Fujitsu General realizes considerable energy saving operations by the Heat pump heating system using the ambient
Technical service manual
GD Midea Refrigeration Equipment Co.,Ltd ODMI-A-1202 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual R410A Multi DC inverter 220~240V-1Ph-50Hz Outdoor units Models M2OC-14HRDN1 M2OC-14HRDN1-Q
LG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.
AquaFREE System Technical Catalogue Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.5/6)H(1/3) Specifications in this manual are subject to change without notice
Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes
Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
Split units TH with hermetic compressors
Split units TH with compressors Refrigeration units in split variant. Available with screw or solder terminal. Condensing unit with sound insulated weatherproof housing for outdoor installation. Split
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
NEW 3-PIPE ECOi MF2 SERIES
NEW 3-PIPE ECOi MF2 SERIES SIMULTANEOUS HEATING AND COOLING VRF SYSTEM Internet Control Ready INTERNET CONTROL NEW Energy Environmentally friendly refrigerant R410A Down to -20 ºC in heating mode OUTDOOR
AquaFREE system. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE
AquaFREE system Technical Catalogue Outdoor units: RAS(3~5)HVRNE RAS(4/5)HRNE Indoor units: RWM(3~5)FSN1E RWM(3~5)FSN1E(4.5/6)H(1/3) RWM(3~5)FSN1ES1 RWM(3~5)FSN1E(4.5/6)SH(1/3) Specifications in this
Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV
Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV TABLE OF CONTENTS RX-JV/GV 1 Features.............................................................
INVERTER IN-CEILING CASSETTE. Ideal for various applications including the lounge, family room, restaurants, hotels, offices and meeting rooms.
INVERTER IN-CEILING CASSETTE Ideal for various applications including the lounge, family room, restaurants, hotels, offices and meeting rooms. INVERTER TECHNOLOGY PFC Control in Power Input DC Inverter
Refrigeration Compressed Air Dryer Buran Ultrapulse
Refrigeration Compressed Air Dryer Buran Ultrapulse There is more to compressed air than just compressing air Compressed air is an indispensable source of operating and processing power in all areas of
CRAC Precision climate control units for data centres
CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have
CoolTeg Plus Chilled Water (CW) version: AC-TCW
version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420
marine/bespoke split applications
split applications marine/bespoke evaporators, condensers and split air conditioning systems suitable for a multitude of applications such as coastal, extreme high and low ambients, harsh dusty environments
Heat Pump Product Brochure 2015/2016. Premier Series Hi-Wall Split Systems. Everyday Comfort
Heat Pump Product Brochure 2015/2016 Premier Series Hi-Wall Split Systems Everyday Comfort Everyday Innovation We design with you in mind. You ll find that Haier Heat Pump units are quiet, efficient and
KSV70HRF. KSV70HRF - 7.1kW Split System Air Conditioner - Reverse Cycle
KSV70HRF RRP AUS $1,709.00 Split System Reverse Cycle air conditioner featuring inverter technology, clean front with LED display, Bio and active carbon filter, 2 way auto swing (up, down), remote (7.1kW
Super Modular Multi Design Manual HFC R-410A. Indoor unit. Outdoor unit
Ref.-No. SMMS02-AE-10-05 Indoor unit 4-way ceiling cassette MMU-AP0091H, AP0121H, AP0151H, MMU-AP0181H, AP0241H, AP0271H, MMU-AP0301H, AP0361H, AP0481H MMU-AP0561H 2-way ceiling cassette MMU-AP0071WH,
Air Conditioning for Small and Medium-size Buildings
Air Conditioning for Small and Medium-size Buildings Defining a HIGHER standard The all-new MiNi-SMMS air conditioner lineup lets you cool or warm as many as 12 *1 rooms with a single system. Outdoor units
Submitted to Reference Approval Construction Unit Designation Schedule #
SUBMITTAL AQV09JA High Wall 9,000 Btu/h Heat Pump Nom Cooling Capacity (Btu/h) 9,000 SEER 20.0 Cool Capacity Range (Btu/h) 3,100 to 11,900 Nom Heating Capacity (Btu/h) 11,950 HSPF 10.0 Heating COP 3.7
AIR-CONDITIONER SPLIT TYPE
FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,
CAB LCAB HACAB RMP/AMP CC CY/YY RVP CUSTOM CU
GENERAL PURPOSE (ORDINARY) LOCATION Custom Controls provides the petro-chemical and offshore industries with HVAC equipment of the highest quality and reliability on the market at an economical price.
DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS
DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS AN EXCELLENT CHOICE IN COOLING, COMFORT AND CONVENIENCE Why choose a Mini-Split system? Installing
Air Conditioning For Large Buildings
Air Conditioning For Large Buildings Index Introduction 3 Industry leading energy savings 6 New smart & sensitive VRF control 10 Industry leading layout flexibility 14 Other features 18 Outdoor units Outdoor
Development and testing of a multi-type air conditioner without using AC inverters
Energy Conversion and Management 46 (2005) 373 383 www.elsevier.com/locate/enconman Development and testing of a multi-type air conditioner without using AC inverters Shih-Cheng Hu *, Rong-Hwa Yang Department
The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity
Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings
Models Utopia ES Utopia IVX Utopia DC Inverter Utopia Fixed Speed Utopia Centrifugal
Utopia Split Systems Models Utopia ES (7.1-14 kw) Utopia IVX (7.1-30 kw) Utopia DC Inverter (5-14 kw) Utopia Fixed Speed (6.3-12.5 kw) Utopia Centrifugal (12.5-25 kw) Contents Company Profile 4 Utopia
Earth can hardly wait for a change in the atmosphere. Nor can we. By making air conditioning supremely energy-efficient, quiet, easy to install, and
1 Earth can hardly wait for a change in the atmosphere. Nor can we. By making air conditioning supremely energy-efficient, quiet, easy to install, and cost-effective, Toshiba aims at the heart of growing
SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2
SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-
SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM
hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &
hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE AUTONOMOUS AIR CONDITIONERS O ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 72-17 AUTONOMOUS AIR CONDITIONERS
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
SALES BULLETIN. Key Features. New 7 Series Under Ceiling Indoor Units
SALES BULLETIN Key Features 1. Chassis completely re designed 2. Increased product range, now includes 6HP model 3. New features to enable easy installation a. Easy access hanger b. Easier wiring connections
D SERIES MODULAR AIR-COOLED SCROLL CHILLER. TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43
D SERIES MODULAR AIR-COOLED SCROLL CHILLER TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43 CONTENTS 1.MODELS LIST... 3 2.NOMENCLATURE... 3 3.FEATURES... 3 4.PRODUCT
Cold Room & Refrigeration System (Casserole Assembly) No of units: 1
Technical Specifications Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 For chiller storage of all sorts of items Chiller storage temperature: 2-5 C Provides excellent thermal efficiency
FTQ. Daikin Inverter Ducted Heat Pump
FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative
sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved
Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section
SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL CSKS12NB41 & CZ18BT1U + CUKS12NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)
FBQ. DC Duct Heat Pump or Cooling Only
FBQ DC Duct Heat Pump or Cooling Only EXPERTISE AND INNOVATION Daikin s FBQ DC Duct systems offer a powerful solution, compact in design and easily concealed in a ceiling. With both cooling only and heat
Pioneer in sustainability
Pioneer in sustainability Over 100 years ago Carrier helped pioneer a new industry, and in the last two decades we have pioneered environmentally sensitive products with a reduced impact on the environment.
ChapterⅠ Introduction to Products
AI RCONDI TI ONI NG SYSTEMS Model s : UMATCH I NVERTER Ser vi cemanual Ser vi cemanual ChapterⅠ Introduction to Products 1. Kinds of Products Universal outdoor unit Duct type Floor ceiling type Cassette
GREE, MAKING BETTER AIR CONDITIONERS
GREE ELECTRIC APPLIANCES,INC.OF ZHUHAI Add:Jinji RD.Qianshan Zhuhai 519070,Guangdong,China Tel: (+86-756)8614883 Fax: (+86-756)8627140 Email: [email protected] http://www.gree.com.cn Heat Pump Water Heater
DUCTED AIR CONDITIONING SOLUTIONS
DUCTED AIR CONDITIONING SOLUTIONS H I G H E N E R G Y E F F I C I E N C Y B A C K E D B Y A 5 Y E A R F U L L P A R T S & L A B O U R W A R R A N T Y DUCTED RANGE WHY CHOOSE FUJITSU? AUSTRALIA S FAVOURITE
DESIGN & TECHNICAL MANUAL
AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LECA AS G09LECA AS G12LECA AS G14LECA OUTDOOR AO G07LEC AO G09LEC AO G12LEC AO G14LEC 1. INDOOR UNIT : AS G07LECA AS G09LECA AS
ELECTRIC CENTRAL HEATING FLOW BOILER
ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
UR...3 URX CF...7 URHE CF...11. Heat recovery unit. Heat recovery unit with refrigerant circuit(442-1947 cfm)
UR...3 Heat recovery unit URX CF...7 Heat recovery unit with refrigerant circuit(442-1947 cfm) URHE CF...11 High efficiency heat recovery unit with refrigeration circuit(588-1942 cfm) UR Heat recovery
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
U-MATCH Air Conditioners. Service Manual. T1/R410a/50Hz
U-MATCH Air Conditioners Service Manual T1/R410a/50Hz GREE ELECTRIC APPLIANCES INC. OF ZHUHAI 1 CONTENTS PRODUCT...2 1 MODELS LIST...2 1.1 Outdoor Unit...2 1.2 Indoor Unit...3 2 NOMENCLATURE...4 3 FUNCTION...5
TWE+TTA TWE+TWA 6.25-20 T.R.
TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.
FTXS. Wall Mount Heat Pump or Cooling Only
FTXS Wall Mount Heat Pump or Cooling Only EXPERTISE AND INNOVATION Daikin s FTXS SkyAir systems feature streamlined, wall mounted indoor units paired with quietly compact outdoor units. Available in both
SERVICE MANUAL. Domestic Air Conditioner. Model. Feature HW-05LN03
Domestic Air Conditioner SERVICE MANUAL Model HW-05LN03 Feature Anti-mold filter Mechanical control Easy clean filters Slide chassis 4-way airflow direction 2 cool settings, 2 fan settings Serial Number:
Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español
Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions
Gree Solar Hybrid Hi Wall Inverter Air Conditioner
Gree Solar Hybrid Hi Wall Inverter Air Conditioner Utilize the natural power of the sun to heat or cool your home. Find out more at www.greeonline.com Why Choose a Solar Hybrid Inverter? The new Gree Solar
Chilled Water Precision Air Conditioner For Critical Application
AIRSYS-P-SC-OPTIMA-HD-E1304V01.2 HD Chilled Water Precision Air Conditioner For Critical Application Cooling capacity: 42.1kW~161.5kW OPTIMA product family is designed for medium to large data center.
Technical data. Danfoss DHP-A
Technical data Danfoss DHP-A An air heat pump which produces both heat and hot water Can operate efficiently down to -0 C Danfoss TWS tank gives plenty of hot water quickly and with low operating costs
Condensing unit type EPSILON-ECHOS LE Technical information manual
Condensing unit type EPSILON-ECHOS LE Technical information manual 2 > EPSILON ECHOS Water chiller > EPSILON ECHOS /HP Reversible heat pump > EPSILON ECHOS /ST Water chiller with storage tank and pumps
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM97 CM7 CM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CM97
More than Air Conditioning. Catalogue 2004/2005. Air Conditioning Program R 407C R 410A
More than Air Conditioning Catalogue 2004/2005 Air Conditioning Program R 407C R 410A MITSUBISHI ELECTRIC Air Conditioning Systems As one of the world s leading technology companies, MITSUBISHI ELECTRIC
How To Make A High Efficiency Thermostat
Zoning with Variable Speed Mini-Split Systems Fujitsu Service Training Welcome - Thank you for attending Did you know? In 1940 only 42% of homes in the US had central heating In 1970 20% of homes had central
Technical service manual 2009
MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual 2009 KSIM MULTI ZONE SERIES R410A DC Inverter multi Series Models KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 CONTENT 1. Product features
Inverter Air Conditioning for Light Commercial Use
Inverter Air Conditioning for Light Commercial Use 02 Cost Saving Comfort An efficient use of time 03 SDISuper Digital Inverter Very efficient energy consumption Keeps down operating costs Heater operation
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : AEMI0AH AEMIAHB AEMIAH AEMI0AH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.k.k.0k Outdoor Model No. AEMI0AH AEMIAHB AEMIAH
SERVICE MANUAL. Hisense Corporation DC INVERTER AIR CONDITIONER UNIT:
DC INVERTER AIR CONDITIONER SERVICE MANUAL V:3.0 UNIT: AUD-18UX4SGKL AUD-24UX4SZLH AUD-36UX4SAMH AUD-48UX6SPHH AUD-60UX6SPHH AUD-18UX4SZKL1 AUD-24UX4SALH1 AUD-36UX4SAMH1 AUV-18UR4SZA1 AUV-24UR4SAA1 AUV-36UR4SAB1
Test Report issued under the responsibility of:
Test Report issued under the responsibility of: TEST REPORT EHPA-DACH Testing Regulation Supplemental requirements for granting the international quality label for heat pumps Testing of Air/Water Heat
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
AIR CONDITIONER INSTALLATION MANUAL
INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by
CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE
Order No. PHAAM1003090C3 Outdoor Unit CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE Air Conditioner Please file and use this manual together with the service manual for Model No. CS-E7LKEW CU-E7LKE CS-E7LKEW