Committee Input No. 113-NFPA [ Global Input ]
|
|
- Anthony Hampton
- 7 years ago
- Views:
Transcription
1 National Fire Protection Association Report of /11/2015 9:51 AM Committee Input No. 113-NFPA [ Global Input ] Task Group Motion: Create a global revision on gauges in Chapter 13 consolidating all other chapter references gauge and move frequencies [move to monthly and quarterly inspections]. 13.X.1.1 Gauges- Inspection. 13.X Gauges on dry and preaction systems shall be inspected weekly to visually verify that they appear to be undamaged, in good working condition, and display normal air and water supply pressure. 13.X Where supervised, gauges on dry and preaction systems shall be inspected quarterly to visually verify that they appear to be undamaged, in good working condition, and display normal air and water supply pressure. 13.X Gauges on wet and deluge systems shall be inspected quarterly to ensure that normal water pressures are being maintained. 13.X.1.2 For dry pipe or preaction systems protecting freezers with two air pressure gauges on the air line(s) between the compressor and the dry pipe or preaction valve, the air pressure gauge near the compressor shall be compared monthly to the pressure gauge above the dry pipe or preaction valve. 13.X.1.2.1* When the gauge near the compressor is reading higher than the gauge near the dry pipe valve, the air line in service shall be taken out of service, and the alternate air line opened to equalize the pressure. 13.X The air line taken out of service shall be internally inspected, shall have all ice blockage removed, and shall be reassembled for use as a future alternate air line. 13.X.1.3 Gauges- Testing. 13.X Gauges shall be replaced every 5 years or tested by comparison with a calibrated gauge. 13.X Gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced. 13.X Where multiple system risers are supplied by a common water supply source with gauges located at the same elevation, and the gauges for all systems read within 3 percent of the other(s), only one gauge shall be required to be tested to determine if replacement is required. A. 13.X Normal water supply pressure could be a pressure reading that is too high or too lowrelative to what would reasonably be expected to be found based on system design information, knowledge of the connected water supply, and/or reading data based on a series of past inspections. Normal pressure includes pressure expected to be found on a system to adequately supply the supplied fire sprinkler system. For example, a gage found reading a pressure close to or below a sprinkler system demand listed on the design placard would not be expected to be normal as, the system could have a water supply issue. Normal water supply pressure on a gage above an alarm or system check valve may be higher than that of a gauge below as a result of trapped pressure surges. This can be typical in buildings with trapped air and located close to metal deck roofs without air conditioning. Gridded systems also have a high probability of excess pressure development thus the reason, NFPA 13, Standard for the Installation of Sprinkler Systems requires relief valves on such systems. A.13.X (RELOCATE A HERE) Submitter Information Verification Submitter Full Name: Matthew Klaus Organization: National Fire Protection Assoc Street Address: City: State: Zip:
2 National Fire Protection Association Report of /11/2015 9:51 AM Submittal Date: Sun Nov 09 07:41:35 EST 2014 Committee Statement Committee Statement: Response Message: Creating a new section dedicated to gauge inspections and testing referenced by all chapters will simplify document use and maintenance by the TC.
3 National Fire Protection Association Report of /11/2015 9:51 AM Committee Input No. 114-NFPA [ Global Input ] Move frequency for all tank inspections to quarterly when supervised in accordance with NFPA 72. Non-supervised systems will remain as written with weekly inspections Submitter Information Verification Submitter Full Name: Matthew Klaus Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Sun Nov 09 07:50:14 EST 2014 Committee Statement Committee Statement: Response Message: This requires at least one inspection during heating season. Although not part of this standard, this revised frequency give incentive for monitoring which has a proven record. The TG recommends revising NFPA 25 to a monthly & quarterly frequency based document with single-point references where justified to minimize variation conflicts and increase general use.
4 National Fire Protection Association Report of /11/2015 9:51 AM Committee Input No. 115-NFPA [ Global Input ] Revise heating season reference to cold weather and add annex discussion: Annex verbiage: Cold weather is defined as temperatures that with reasonable engineering may create the potential for system damage and/or hidden performance issues. Submitter Information Verification Submitter Full Name: Matthew Klaus Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Sun Nov 09 07:51:07 EST 2014 Committee Statement Committee Statement: Response Message: The references to heating season and cold weather are somewhat vague and vary geographically. Adding annex text to better describe these concepts would make the standard easier to apply and enforce.
5 National Fire Protection Association Report of /11/2015 9:51 AM Committee Input No. 116-NFPA [ Global Input ] Move frequency for tank water temperature inspections to quarterly. Submitter Information Verification Submitter Full Name: Matthew Klaus Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Sun Nov 09 07:56:59 EST 2014 Committee Statement Committee Statement: Response Message: This is recommended as there is little justification for monthly testing. The TG recommends revising NFPA 25 to a monthly & quarterly frequency based document with single-point references where justified to minimize variation conflicts and increase general use.
6 National Fire Protection Association Report of /11/2015 9:51 AM Committee Input No. 117-NFPA [ Global Input ] Revise valve inspection section to read: Inspection All valves shall be inspected weekly Valves secured with locks in accordance with applicable NFPA standards shall be permitted to be inspected monthly Valves electrically supervised and compliance with in this standard shall be permitted to be inspected quarterly Control valve supervisory alarm devices shall be inspected quarterly to verify that they are free of physical damage After any alterations or repairs, an inspection shall be made by the property owner or designated representative to ensure that the system is in service and all valves are in the normal position and properly sealed, locked, or electrically supervised. Submitter Information Verification Submitter Full Name: Matthew Klaus Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Sun Nov 09 07:57:46 EST 2014 Committee Statement Committee Statement: Response Message: Is there any data to support not moving to quarterly inspections from monthly? Were valves involved in impairments from NFPRF project supervised? How many impaired valves that were found were supervised? This section needs to be reviewed and further substantiated.
7 National Fire Protection Association Report of /11/2015 9:51 AM Committee Input No. 118-NFPA [ Global Input ] * Alarm valves and system riser check valves shall be externally inspected quarterly and shall verify the following: (1) The gauges indicate normal supply water pressure is being maintained. (2) The valve is free of physical damage. (3) All valves are in the appropriate open or closed position. (4) The retarding chamber or alarm drains are not leaking. Submitter Information Verification Submitter Full Name: Matthew Klaus Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Sun Nov 09 07:59:27 EST 2014 Committee Statement Committee Statement: Response Message: Damage is a very rare event and failure is typically open. How do these get damaged- i.e. what is justification for monthly?
8 National Fire Protection Association Report of /11/2015 9:51 AM Committee Input No. 119-NFPA [ Global Input ] Change BFA inspection frequency to quarterly. Submitter Information Verification Submitter Full Name: Matthew Klaus Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Sun Nov 09 08:01:13 EST 2014 Committee Statement Committee Statement: Response Message: IF CI 117 is converted into a Second Revision, the inspection frequency for BFAs should also be modified to correlate with that change.
9 National Fire Protection Association Report of /11/2015 9:51 AM Committee Input No. 120-NFPA [ Global Input ] Revise to read as follows: If approved locking caps or locking plugs are installed, inspections shall be annual. Submitter Information Verification Submitter Full Name: Matthew Klaus Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Sun Nov 09 08:03:52 EST 2014 Committee Statement Committee Statement: Response Message: Locking type Knox caps give added protection and, only fire departments have access. The risk of theft is much less.
10 National Fire Protection Association Report 0 of 14 2/11/2015 9:51 AM Committee Input No. 124-NFPA [ Global Input ] Delete the following sections: Section (including subsections and annex) Section (including subsections and annex) Annex E (entire annex chapter) Submitter Information Verification Submitter Full Name: Matthew Klaus Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Sun Dec 07 16:37:09 EST 2014 Committee Statement Committee Statement: Response Message: On December 9th-10th, 2013, in Chicago, IL the NFPA Fire Protection Research Foundation conducted a workshop titled Addressing the Performance of Sprinkler Systems: NFPA 25 and Other Strategies. There was discussion that NFPA 25 should be strictly a wear and tear document. In addition, a number of attendees at the workshop stated since the main focus of NFPA 25 should be wear and tear issues, they recommended that the design evaluations and hazard analysis requirements pertaining to changes in occupancy, use or process, hazard, or the materials used or stored in a building be removed from NFPA 25 and be proposed to be relocated in NFPA 101/5000, NFPA 1, the IBC and IFC. Based on this recommendation from the subject workshop, this CI proposes to delete Sections and and all accompanying Annex material for public consideration in an effort to solicit public comments on this important subject.
11 National Fire Protection Association Report 1 of 14 2/11/2015 9:51 AM Committee Input No. 129-NFPA [ Global Input ] Revise as follows: * The property owner or designated representative shall correct or repair deficiencies or impairments that are found during the inspection, test, and maintenance required by this standard.,and that are found or observed at any time. Submitter Information Verification Submitter Full Name: Matthew Klaus Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Mon Dec 08 09:02:25 EST 2014 Committee Statement Committee Statement: Response Message: The current text doesn t require that corrections or repairs be made if a problem is found or observed outside of the ITM requirements of this standard. There are many problems found or observed on systems during normal activities in a building such as a fire department walk through, or a bid review walkthrough, that should prompt notification to the building owner that corrections or repairs are needed.
12 National Fire Protection Association Report 2 of 14 2/11/2015 9:51 AM Committee Input No. 132-NFPA [ Global Input ] A Recalled products should be replaced or remedied. Remedies include entrance into a program for scheduled replacement. Such replacement or remedial product should be installed in accordance with the manufacturer s instructions and the appropriate NFPA installation standards. A recalled product is a product subject to a statute or administrative regulation specifically requiring the manufacturer, importer, distributor, wholesaler, or retailer of a product, or any combination of such entities, to recall the product, or a product voluntarily recalled by a combination of such entities. Needed corrections and repairs should be classified as an impairment, critical deficiency, or noncritical deficiency according to the effect on the fire protection system and the nature of the hazard protected. Impairments should be corrected or repaired immediately. The process of correcting or repairing an impairment should begin as soon as the impairment is discovered. Impairments are the highest priority problem found during inspection, testing, and maintenance and should be corrected as soon as possible. If the necessary parts are on hand the correction or repair can be accomplished in a matter of a few hours. However, in many cases it may take several days to order repair parts, have them shipped, and schedule manpower to make the repair. The fire protection system cannot provide an adequate response to a fire, and implementation of impairment procedures outlined in Chapter 15 is required until the impairment is corrected. Critical deficiencies need to be corrected in a timely fashion should be corrected or repaired within 30 days. The process of correcting or repairing a critical deficiency should begin as soon as it is discovered and with a sense of urgency. If the necessary parts are on hand the correction or repair can be accomplished in a matter of a few hours. However, in many cases it may take several days to order repair parts, have them shipped, and schedule manpower to make the repair. There are very few instances when a critical deficiency cannot be corrected or repaired within 30 days. If the correction or repair can t be accomplished within 30 days, the AHJ should be notified and permission obtained for an exception to this requirement. The fire protection system is still capable of performing, but its performance can be impacted and the implementation of impairment procedures might not be needed. However, special consideration must be given to the hazard in the determination of the classification. A deficiency that is critical for one hazard might be an impairment in another. Non-Critical deficiencies should be corrected or repaired within 90 days. Non-critical deficiencies do not have an effect on system performance and therefore correcting or repairing them is allowed to take longer. If the correction or repair can t be accomplished within 90 days, the AHJ should be notified and permission obtained for an exception to this requirement. Noncritical deficiencies do not affect the performance of the fire protection system but should be corrected in a reasonable time period so that the system can be properly inspected, tested, and maintained. Assembly occupancies, health care facilities, prisons, high rise buildings, other occupancies where the life safety exposure is significant, or facilities that cannot be evacuated in a timely manner require special consideration. As an example, a nonfunctioning waterflow alarm might be considered a critical deficiency in a storage warehouse but an impairment in a hospital. High hazard occupancies where early response to a fire is critical also require special consideration. A small number of painted sprinklers could be considered an impairment for a system protecting a high hazard occupancy but might be considered a critical deficiency in a metal working shop. Classifications of needed corrections and repairs are shown in Table A Submitter Information Verification Submitter Full Name: Matthew Klaus Organization: National Fire Protection Assoc Street Address:
13 National Fire Protection Association Report 3 of 14 2/11/2015 9:51 AM City: State: Zip: Submittal Date: Mon Dec 08 09:12:46 EST 2014 Committee Statement Committee Statement: Response Message: There s a need to provide some guidance for all parties involved in Inspection, testing, and maintenance on how quickly impairments, critical deficiencies, and non-critical deficiencies should be repaired. The previous text being deleted is very confusing and should not be included in NFPA 25. This subjective language should be considered if a performance based ITM program is being presented for approval
14 National Fire Protection Association Report 4 of 14 2/11/2015 9:51 AM Committee Input No. 63-NFPA [ Global Input ] See attached document for reformattin CI. Supplemental Information File Name CI_63_Table_Formatting.docx Description Submitter Information Verification Submitter Full Name: Matt Klaus Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Nov 05 18:56:20 EST 2014 Committee Statement Committee Statement: This CI is editorial in Nature and is intended to create a common structure to the ITM Summary tables at the beginning of each chapter. This CI fundamentally does 3 things: 1)Rather than referencing a specific section when sending the user outside of the chapter, the tables will simply reference the Chapter number. 2Reorganizes the table alphabetically 3)Creates consistency throughout the tables. Response Message:
15 Chapter 6 Standpipe and Hose Systems 6.1 General Minimum Requirements This chapter shall provide the minimum requirements for the routine inspection, testing, and maintenance of standpipe and hose systems Table shall be used for the inspection, testing, and maintenance of all types and classes of standpipe and hose systems. Table Summary of Standpipe and Hose Systems Inspection, Testing, and Maintenance Inspection Item Frequency Reference Control valves Chapter 13 Cabinets NFPA 1962 Fire Department Connection Gauges (automatic and semiautomatic dry standpipe systems Gauges (automatic dry standpipe systems) Chapter 13 Quarterly Weekly/monthly , Hose NPFA 1962 Hose Connections Chapter 13 Hose nozzles NFPA 1962 Hose Storage devices NFPA 1962 Hose valves Chapter 13 Hydraulic design information sign Annually Piping Annually Pressure control valves Chapter 13 Pressure reducing valves Chapter 13
16 Pressure-regulating devices Chapter 13 Test Control valves Chapter 13 Flow test 5 years Hose NFPA 1962 Hose connections Chapter 13 Hose storage devices NFPA 1962 Hose valves Chapter 13 Hydrostatic 5 years Main drain Chapter 13 Pressure control valves Chapter 13 Pressure reducing valves Supervisory signal devices (except valve supervisory switches) Chapter 13 Chapter 13 System valves Chapter 13 Valve supervisory devices Chapter 13 Waterflow alarms Chapter 13 Maintenance Hose connections Annually Chapter 13 Valves (all types) Chapter 13 Table Standpipe and Hose Systems Component/Checkpoint Hose Connections Cap missing Fire hose connection damaged Valve handles missing Cap gaskets missing or deteriorated Replace Repair Replace Replace Corrective Action
17 Valve leaking Visible obstructions Restricting device missing Manual, semiautomatic, or dry standpipe valve does not operate smoothly Piping Damaged piping Missing or damaged pipe support device Damaged supervisory signal initiating device Hose Close or repair Remove Replace Lubricate or repair Repair Repair or replace Repair or replace Mildew, cuts, abrasions, and deterioration evident Replace with listed lined, jacketed hose Coupling damaged Gaskets missing or deteriorated Incompatible threads on coupling Hose not connected to hose rack nipple or valve Replace or repair Replace Replace or provide thread adapter Connect Hose Nozzle Hose nozzle missing Gasket missing or deteriorated Obstructions Nozzle does not operate smoothly Hose Storage Device Difficult to operate Damaged Obstruction Hose improperly racked or rolled Nozzle clip in place and nozzle correctly contained? If enclosed in cabinet, will hose rack swing out at least 90 degrees? Cabinet Corroded or damaged parts Difficult to open Cabinet door will not open fully Door glazing cracked or broken Replace with listed nozzle Replace Remove Repair or replace Repair or replace Repair or replace Remove Remove Replace if necessary Repair or remove any obstructions Repair or replace parts; replace entire cabinet if necessary Repair Repair or move obstructions Replace
18 If cabinet is break-glass type, is lock functioning properly? Glass break device missing or not attached Not properly identified as containing fire equipment Visible obstructions All valves, hose, nozzles, fire extinguisher, etc., easily accessible Repair or replace Replace or attach Provide identification Remove Remove any material not related * Checkpoints and corrective actions outlined in Table shall be followed to determine that components are free of conditions that adversely affect system operation. (Address examples in Annex) Renumber remaining sections as needed Valves and fire department connections shall be inspected, tested, and maintained in accordance with Chapter The procedures outlined in Chapter 14 shall be followed where there is a need to conduct an obstruction investigation Where the inspection, testing, and maintenance of standpipe and hose systems results or involves a system that is out of service, the impairment procedures outlined in Chapter 15 shall be followed Where approved by the authority having jurisdiction, existing hose shall be permitted to be removed and shall not be recorded as a deficiency. 6.2 Inspection Components. Components of standpipe and hose systems shall be visually inspected as specified in Table Gauges Gauges on automatic wet and semiautomatic dry standpipe systems shall be inspected quarterly to ensure that they are in good condition and that normal water supply pressure is being maintained Gauges on automatic dry standpipe systems shall be inspected weekly to ensure that normal air or nitrogen and water pressure are being maintained Where air pressure supervision is connected to a constantly attended location, gauges shall be inspected monthly * Hydraulic Design Information Sign. The hydraulic design information sign for standpipe systems shall be inspected annually to verify that it is provided, attached securely, and legible A hydraulic design information sign that is missing or illegible shall be replaced.
19 A standpipe system that was not sized by hydraulic design shall have a hydraulic design information sign that reads Pipe Schedule System. 6.3 Testing. Where water damage is a possibility, an air test shall be conducted on the system at 25 psi (1.7 bar) prior to introducing water to the system Flow Tests * A flow test shall be conducted every 5 years on all Class I and Class III standpipe systems to verify that the required flow and pressure are available at the hydraulically most remote hose valve outlet(s) while flowing the standpipe system demand Where a flow test of the hydraulically most remote outlet(s) is not practical, the authority having jurisdiction shall be consulted for the appropriate location for the test * The standpipe system demand shall include 500 gpm (1892 L/min) for the first standpipe and 250 gpm (946 L/min) for each additional standpipe until the total system demand is simultaneously flowing * The 250 gpm (946 L/min) required from each additional standpipe shall be allowed to be flowed from the most convenient hose valve on that standpipe * Where the 250 gpm (946 L/min) cannot be flowed from each additional standpipe, the authority having jurisdiction shall determine where the additional flow can be taken The standpipe system demand shall be based on the design criteria in effect at the time of the installation Where the standpipe system demand cannot be determined, the authority having jurisdiction shall determine the standpipe system demand The actual test method(s) and performance criteria shall be discussed in advance with the authority having jurisdiction Standpipes, sprinkler connections to standpipes, or hose stations equipped with pressure-reducing valves or pressure-regulating valves shall have these valves inspected, tested, and maintained in accordance with the requirements of Chapter A main drain test shall be performed on all standpipe systems with automatic water supplies in accordance with the requirements of Chapter The test shall be performed at the low point drain for each standpipe or the main drain test connection where the supply main enters the building (when provided) Pressure gauges shall be provided for the test and shall be maintained in accordance with Hydrostatic Tests * Hydrostatic tests of not less than 200 psi (13.8 bar) pressure for 2 hours, or at 50 psi (3.4 bar) in excess of the maximum pressure, where maximum pressure is in excess of 150 psi
20 (10.3 bar), shall be conducted every 5 years on manual standpipe systems and semiautomatic dry standpipe systems, including piping in the fire department connection Manual wet standpipes that are part of a combined sprinkler/standpipe system shall not be required to be tested in accordance with The hydrostatic test pressure shall be measured at the low elevation point of the individual system or zone being tested The inside standpipe piping shall show no leakage Waterflow Alarm and Supervisory Alarm Devices Where provided, waterflow alarm and supervisory alarm devices shall be tested in accordance with Chapter Where freezing conditions necessitate a delay in testing, tests shall be performed as soon as weather allows * Gauges Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge Gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced. 6.4 Maintenance Maintenance and repairs shall be in accordance with and Table Equipment that does not pass the inspection or testing requirements shall be repaired and tested again or replaced. 6.5 Component Action Requirements Whenever components in standpipe and hose systems are adjusted, repaired, reconditioned, or replaced, the actions required in Table shall be performed. Chapter 7 Private Fire Service Mains 7.1 General.
21 7.1.1 Minimum Requirements This chapter shall provide the minimum requirements for the routine inspection, testing, and maintenance of private fire service mains and their appurtenances Table shall be used for the inspection, testing, and maintenance of all private fire service mains. Table Summary of Private Fire Service Main Inspection, Testing, and Maintenance Inspection Item Frequency Reference Hose houses Quarterly Hydrants (dry barrel and wall) Annually and after each operation Hydrants (wet barrel) Annually and after each operation Mainline strainers Annually and after each significant flow Monitor nozzles Semiannually Piping (exposed) Annually Test Piping flow 5 years Hydrants Annually Monitor nozzles Annually Maintenance Hydrants Annually Monitor nozzles Annually Valves and Connections. Valves and fire department connections shall be inspected, tested, and maintained in accordance with Chapter 13. Chapter 9 Water Storage Tanks 9.1* General.
22 9.1.1 Minimum Requirements This chapter shall provide the minimum requirements for the routine inspection, testing, and maintenance of water storage tanks dedicated to fire protection use Table shall be used for inspection, testing, and maintenance of all water storage tanks. Table Summary of Water Storage Tank Inspection, Testing, and Maintenance Inspection Item Frequency Reference Air pressure tanks without their air pressure source supervised Air pressure tanks that have their air pressure source supervised Monthly Quarterly Control valves Chapter 13 Check valves Chapter 13 Exterior all tanks Quarterly Expansion joints Annually Hoops and grillage Annually Painted/coated/insulated surfaces Annually Support structure Quarterly Surrounding area Quarterly Heating system tanks with supervised low temperature alarms connected to constantly attended location Heating system tanks without supervised low temperature alarms connected to constantly attended location Interior tanks without corrosion protection Weekly* Daily* years Interior all other tanks 5 years Ring type foundations 3 years/5 years
23 Heating system 3 years/5 years Anti-vortex plate 3 years/5 years Temperature alarms connected to constantly attended location Temperature alarms not connected to constantly attended location Water level tanks equipped with supervised water level alarms connected to constantly attended location Water level tanks without supervised water level alarms connected to constantly attended location Water temperature low temperature alarms connected to constantly attended location Water temperature low temperature alarms not connected to constantly attended location Monthly* Weekly* Quarterly Monthly Monthly Weekly Test Control valves Chapter 13 Interior (steel tanks) 3 years/5 years 9.2.7, High temperature limit switches Monthly* Level indicators 5 years Low water temperature alarms Monthly* Pressure gauges 5 years Tank heating system Prior to heating season Water level alarms Semiannually Maintenance Control valves Chapter 13 Check valves Chapter 13 Embankment-supported coated fabric (ESCF) Water level * Cold weather/heating season only.
24 Chapter 10 Water Spray Fixed Systems 10.1* General Minimum Requirements This chapter shall provide the minimum requirements for the routine inspection, testing, and maintenance of water spray protection from fixed nozzle systems only Table shall be used for the inspection, testing, and maintenance of fixed nozzle water spray systems. Table Summary of Water Spray Fixed System Inspection, Testing, and Maintenance Inspection Item Frequency Reference Backflow preventers Chapter 13 Check valves Chapter 13 Control valves Weekly (sealed) Chapter 13 Control valves Monthly (locked, supervised) Chapter 13 Deluge valves , Chapter 13 Detection systems NFPA 72 Detector check valves Chapter 13 Drainage Quarterly Electric motors , Chapter 8 Engine drives , Chapter 8 Fire pumps , Chapter 8 Fittings Quarterly , Fittings (rubber-gasketed) Quarterly , A Gravity tanks , Chapter 9 Hangers Annually and after each system activation Heat (deluge valve house) Daily/weekly , Chapter 13
25 Nozzles Pipe Annually and after each system activation Annually and after each system activation , , , , , , , Pressure tanks , Chapter 9 Steam drivers , Chapter 8 Strainers Manufacturer's instruction Suction tanks , Chapter 9 Supports Quarterly , , Water supply piping , UHSWSS detectors Monthly UHSWSS controllers Each shift UHSWSS valves Each shift Operational Test Backflow preventers Chapter 13 Check valves Chapter 13 Control valves Annually Chapter Deluge valves , Chapter 13 Detection systems NFPA 72 Detector check valves Chapter 13 Electric motors , Chapter 8 Engine drives , Chapter 8 Fire pumps , Chapter 8 Flushing Annually , Section 10.3 (flushing of connection to riser, part of annual test) Gravity tanks , Chapter 9 Main drain test Annually Manual release Annually , Nozzles Annually , , Section 10.3 Pressure tanks Section 10.2, Chapter 9 Steam drivers , Chapter 8 Strainers Annually , , Suction tanks , Chapter 9 Waterflow alarms Quarterly Chapter 5 Water spray system test Annually Section 10.3, Chapter 13 Water supply flow test 7.3.1
26 UHSWSS Annually Section 10.4 Maintenance Backflow preventers Chapter 13 Check valves Chapter 13 Control valves Chapter 13 Deluge valves , Chapter 13 Detection systems NFPA 72 Detector check valves Chapter 13 Electric motors , Chapter 8 Engine drives , Chapter 8 Fire pumps , Chapter 8 Gravity tanks , Chapter 9 Pressure tanks , Chapter 9 Steam drivers , Chapter 8 Strainers Annually , , Strainers (baskets/screen) 5 years , , A Suction tanks , Chapter 9 Chapter 11 Foam-Water Sprinkler Systems 11.1 General Minimum Requirements This chapter shall provide the minimum requirements for the routine inspection, testing, and maintenance of foam-water systems Table shall be used for the inspection, testing, and maintenance of foam water systems.
27 Inspection Table Summary of Foam-Water Sprinkler System Inspection, Testing, and Maintenance System/Component Frequency Reference Automatic detection equipment , NFPA 72 Backflow preventers Chapter 13 Control valves Chapter 13 Deluge/preaction valves , Chapter 13 Discharge device location (spray nozzle) Monthly Discharge device position (sprinkler) Annually Discharge device position (spray nozzle) Monthly Drainage in system area Quarterly Foam concentrate strainer(s) Quarterly Fittings Annually Fire pumps Chapter 8 Hangers/supports Annually Piping Annually Proportioning systems Annually Waterflow devices Quarterly Water storage tanks Chapter 9 Water supply piping Test Automatic detection equipment NFPA 72 Backflow preventers Chapter 13 Control valves Chapter 13 Deluge/preaction valves Chapter 13 Discharge device location Annually Discharge device position Annually Discharge device obstruction Annually Fire Pumps Chapter 8 Foam concentrate strainers Annually Foam-water solution Annually Foam-water system (complete) Annually Manual actuation devices Annually
28 Proportioning systems all Annually Waterflow devices Quarterly/semiannually Water supply piping Chapter 10 Strainer(s) mainline See Chapter Water supply tank(s) See Chapter 9 Water supply flow test 5 years Maintenance Automatic detection equipment , NFPA 72 Backflow preventers Chapter 13 Check valves Chapter 13 Control valves Chapter 13 Deluge/preaction valves Chapter 13 Fire pumps Chapter 8 Foam concentrate pump operation Monthly , Foam concentrate strainer(s) Quarterly Section 11.4 Foam concentrate samples Annually Pressure vacuum vents 5 years Proportioning systems standard pressure type Standard pressure type Ball drip (automatic type) drain valves 5 years Foam concentrate tank drain and flush 10 years Corrosion and hydrostatic test 10 years Bladder tank type Sight glass 10 years Foam concentrate tank hydrostatic test Line type Foam concentrate tank corrosion and pickup pipes Foam concentrate tank drain and flush Standard balanced pressure type 10 years years years Foam concentrate pump(s) 5 years (see Note)
29 Balancing valve diaphragm 5 years Foam concentrate tank 10 years In-line balanced pressure type Foam concentrate pump(s) 5 years (see Note) Balancing valve diaphragm 5 years Foam concentrate tank 10 years Strainers mainline Chapter 10 Water supply Annually Water supply tanks Chapter 9 Note: Also refer to manufacturer s instructions and frequency. Maintenance intervals other than preventive maintenance are not provided, as they depend on the results of the visual inspections and operational tests. For foam-water systems in aircraft hangars, refer to the inspection, test, and maintenance requirements of NFPA 409, Standard on Aircraft Hangars, Table Chapter 13 Valves, Valve Components, and Trim 13.1* General Minimum Requirements This chapter shall provide the minimum requirements for the routine inspection, testing, and maintenance of valves, valve components, and trim Table shall be used for the inspection, testing, and maintenance of valves, valve components, and trim. Table Summary of Valves, Valve Components, and Trim Inspection, Testing, and Maintenance Inspection Item Frequency Reference
30 Alarm valves Interior 5 years Strainers, filters, orifices 5 years Backflow prevention assemblies Check valves Control Valves Reduced pressure type weekly/monthly Reduced pressure detectors weekly/monthly Interior 5 years Sealed Weekly Locked or electrically supervised Valve Supervisory Signal Initiating Device Dry Pipe Valves/ Quick-Opening Devices Monthly Quarterly Gauges Weekly/monthly , Enclosure (during cold weather) Daily/weekly Exterior Monthly Interior Annually Strainers, filters, orifices 5 years Fire department connections Quarterly Preaction/Deluge valves Enclosure Daily/weekly Exterior Monthly Interior Annually/5 years Strainers, filters, orifices 5 years Pressure-Reducing and Relief Valves Sprinkler systems Quarterly Hose connections Annually Hose racks Annually Fire pump casing relief valves Weekly , Fire pump pressure relief valves Weekly , Valve supervisory signal initiating device Quarterly
31 Backflow prevention assemblies Annually Control Valves Position Annually Operation Annually Supervisory Semiannually Dry Pipe Valves/ Quick-Opening Devices Air leakage 3 years Priming water Quarterly Low air pressure alarm Quarterly Quick-opening devices Quarterly Trip test Annually Full flow trip test 3 years Gauges 5 years Main drains Annually/quarterly , , Preaction/deluge valves Air leakage 3 years Full flow Annually Low air pressure alarms Quarterly/annually , Priming water Quarterly Pressure-Reducing and Relief Valves Sprinkler systems 5 years Circulation relief Annually Pressure relief valves Annually Hose connections 5 years Hose racks 5 years Waterflow alarms Quarterly/semiannually Maintenance Control Valves Annually Dry pipe valves/quick-opening devices Annually Preaction/Deluge Valves Annually This CI is editorial in Nature and is intended to create a common structure to the ITM Summary tables at the beginning of each chapter. This revision fundamentally does 3 things: 1)Rather than referencing a specific section when sending the user outside of the chapter, the tables will simply reference the Chapter number.
32 2Rreorganizes the table alphabetically 3)Creates consistency throughout the tables.
LAWS AND REGULATIONS for AUTOMATIC EXTINGUISHING SYSTEMS
DEPARTMENT OF FORESTRY AND FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING DIVISION LAWS AND REGULATIONS for AUTOMATIC EXTINGUISHING SYSTEMS AUTOMATIC EXTINGUISHING SYSTEM PROGRAM 1131
More informationMAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND
More informationInspection and Testing of Water-Based Systems
Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based
More informationINSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
More informationRisk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems
Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Introduction Fire protection systems are provided in or at a building to safeguard the lives of building
More informationALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
More informationFIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
More informationCHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined
Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority
More informationAutomatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
More informationModel: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
More informationFire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationImportant Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
More informationBERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
More informationBERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
More informationTransformer Deluge Systems
Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is
More informationINSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationSELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
More informationMaintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
More informationTECHNICAL DATA. Dry 122a. November 12, 2013
Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationFire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more
FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended
More informationCommercial Fire Inspections
Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated
More informationDepending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
More information3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide
", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,
More informationNFPA 25 FAQs. 1. When inspecting an old system (60 years or older), when/where does NFPA 25 require a system to be upgraded to present standards?
NFPA 25 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued
More informationFIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE
ACCEPTANCE INSPECTION AND TESTING PROCEDURE Wet Pipe Sprinkler Systems...2 Dry Pipe Sprinkler Systems...2 Clean Agent Fire Extinguishing System...4 Total Flooding Systems...4 Fire Dampers...5 Smoke Dampers...5
More informationPotter Electric Sprinkler Monitoring Training Manual
R Potter Electric Sprinkler Monitoring Training Manual 1 #8704200D 2 Contents Foreword... 4 Introduction... 5 Fire Alarm Signals... 6 Types Of Sprinkler Systems... 7 Wet Pipe Sprinkler Systems... 8 Straight
More informationInspection, Testing and Preventive Maintenance
Fire Protection Systems and Equipment Introduction HSB Professional Loss Control Two Crossroads Drive Bedminster, NJ 07921 1-800-472-1866 www.hsbplc.com The owners and operators of industrial plants, shopping
More informationSPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST
SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following
More informationEXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
More informationSprinkler system types
Sprinkler system types Wet Wet type systems are the most common type of sprinkler system that is installed. A wet pipe system has water in the pipes in the ambient or normal condition and has heat responsive
More informationTECHNICAL ADVISORY BULLETIN
RISK CONTROL AND CLAIM ADVOCACY PRACTICE TECHNICAL ADVISORY BULLETIN November 2014 www.willis.com FIRE PUMP TESTING Fire pumps are a critical part of a fire protection system, especially when they are
More informationInspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
More informationUNIFIED FACILITIES CRITERIA (UFC) OPERATION AND MAINTENANCE: INSPECTION, TESTING, AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
UNIFIED FACILITIES CRITERIA (UFC) OPERATION AND MAINTENANCE: INSPECTION, TESTING, AND MAINTENANCE OF FIRE PROTECTION SYSTEMS APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED UNIFIED FACILITIES CRITERIA
More informationNFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
More informationMERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS
MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth
More informationFIRE SAFETY PLAN FOR KITCHENER, ONTARIO
FIRE SAFETY PLAN FOR KITCHENER, ONTARIO Additional information of fire safety plans may be found at our website at www.kitchener.ca/fire.htm. Before submission, please read and change all sections to address
More informationSecond Revision No. 9-NFPA 120-2014 [ Global Comment ] Submitter Information Verification. Committee Statement 5/30/2014 8:36 AM
of 37 5/30/2014 8:36 AM Second Revision No. 9-NFPA 120-2014 [ Global Comment ] Change title of 5.3.7 to Self-Propelled Equipment Submitter Information Verification Submitter Full Name: [ Not Specified
More informationLAWS AND REGULATIONS for AUTOMATIC EXTINGUISHING SYSTEMS
DEPARTMENT OF FORESTRY AND FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING DIVISION LAWS AND REGULATIONS for AUTOMATIC EXTINGUISHING SYSTEMS AUTOMATIC EXTINGUISHING SYSTEM PROGRAM 1131
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationSecond Revision No. 106-NFPA 72-2014 [ Global Comment ] Supplemental Information. Submitter Information Verification. Committee Statement
of 1 9/22/2014 2:03 PM Second Revision No. 106-NFPA 72-2014 [ Global Comment ] Revise Figures A.17.6.3.1.1(c) and A.17.7.5.4.2.2(a) to replace the smoke detector symbol (a hexagon with a whisp of smoke)
More informationOREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
More informationFPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS
FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS To be used in conjunction with the Fire Protection Association Australia FPS4-2000: Agreement
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationTRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007
TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES 301.010 ANNUAL SERVICE TEST FOR FIRE HOSE EFFECTIVE: OCTOBER 2007 The Department will test all fire hose annually. The testing of fire hose determines its serviceability.
More informationFeatures. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)
Features 1. Differential latching clapper-type, lightweight, dependable construction. 2. Low Air Pressurized System, psi -to- 2 psi (0.6 bar -to- 1.9 bar) Max 3. Reset externally. Cover removal is not
More informationInspection and Testing Program Fire Protection Equipment
I. Introduction Inspection and Testing Program Fire Protection Equipment State of Minnesota Emergencies seldom give warning before they strike. Thus, it is essential that fire protection equipment be inspected,
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
More informationCHAPTER. Fire Pumps FIRE PUMP OVERVIEW. Fire Pump Unit Defined. Fire Pump Unit Responsibility
Fire Pumps CHAPTER 4 Commissioning of fire pumps is much more involved than commissioning of most other systems and must be completed correctly to verify operation of this critical equipment. This chapter
More informationOPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES
OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES Reference: National Fire Protection Association (NFPA) Pamphlet No. 58 Liquefied Petroleum Gas Code, 2001, Chapter 11 Type of Facility: Petroleum
More informationProgram No. 1.6.1. Section Heading
ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,
More informationELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
More informationI-768 FireLock NXT Dry Valve
HANG THESE INSTRUCTIONS ON THE INSTALLED VALVE FOR EASY FUTURE REFERENCE WARNING WARNING Failure to follow instructions and warnings can cause product failure, resulting in serious personal injury and
More informationPLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
More informationAppendix B Forms for Inspection, Testing, and Maintenance
Appendix B Forms for Inspection, Testing, and Maintenance This appendix is not a part of the requirements of this NFPA document but is included for informational purposes only. Forms need to be complete
More informationClark County Fire Prevention
Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF
More informationSix Monthly Servicing of Fire Extinguisher on Commercial Vessels.
Marine Safety Notice to Industry Number: 34 Date of Issue: 17 January 2012 Six Monthly Servicing of Fire Extinguisher on Commercial Vessels. This Notice to Industry is to clarify the requirements for the
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
More informationModel F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description
Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed
More informationFire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment):
Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment): Fire Safety Plan Single-Stage Fire Alarm System for: (Business Name) (Business Address) Submission Date - Submitted by - Signature
More informationWet System. Technical Manual for Operation, Maintenance, and Troubleshooting
Wet System Technical Manual for Operation, Maintenance, and Troubleshooting October, 2008 Form No. F_010508 Page II October 15, 2008 Table of Contents Page I. DESCRIPTION 3 II. APPLICATIONS 4 III. REQUIREMENTS
More informationTAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
More informationChapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS
Title 153 - NEBRASKA STATE FIRE MARSHAL Chapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS Scope. Chapter 19 of Title 153 of the Nebraska Administrative Code is concerned with the certification of contractors
More informationINSPECTION, TESTING AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
GAP.12.0.1 A Publication of Global Asset Protection Services LLC INSPECTION, TESTING AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS INTRODUCTION National Fire Protection Association (NFPA) documents
More informationFighting Fire in Sprinklered Buildings. Student Guide
Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction
More informationI. Introduction. 10 minutes
I. Introduction 10 minutes Introduction (1 of 2) An uninterrupted water supply is: The primary weapon for extinguishment Essential for fire fighter safety Ensuring a dependable water supply is a critical
More informationTD01211 PIN: NX010 201007.2 nd Edition. Water Motor Alarm MODEL: NX010 TECHNICAL DATA
Water Motor Alarm MODEL: NX010 GENERAL DESCRIPTION TECHNICAL SPECIFICATIONS Model NX010 Working Water Pressure Range 5 to 175 psig 0.035 to 1.2 MPa (0.35 to 12 bar) Shipping Weight 11 lbs 5 kg Alarm Line
More informationManual Document Page Issue Date TABLE OF CONTENTS
, Manual USQ #15-1163-D ESHQ 1 of 23 TABLE OF CONTENTS 1.0 PURPOSE AND SCOPE... 2 2.0 IMPLEMENTATION... 2 3.0 STANDARD... 2 3.1 Facility Management Support Requirements... 3 3.2 Fire System Discrepancy
More informationFIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE EXAMINATION FOR THE CERTIFICATE OF FITNESS FOR S-12 CITYWIDE SPRINKLER SYSTEM
Rev: 3-27-13 FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE EXAMINATION FOR THE CERTIFICATE OF FITNESS FOR S-12 CITYWIDE SPRINKLER SYSTEM Issued 11/29/10 New York City Fire Department - All rights
More informationPreaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description
Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation /2 thru 8 Inch (DN thru DN200) General Description The DV5 Supervised Single
More informationElement D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
More informationFAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com
FAIRBANKS NIJHUIS FIRE PUMPS www.fairbanksnijhuis.com FAIRBANKS NIJHUIS Long established as a leading fire pump manufacturer, Fairbanks Nijhuis offers a broad range of horizontal and vertical split case,
More informationRAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID
More informationFire Safety Plan (Single-Stage Fire Alarm System - Small Establishment)
1 Fire Safety Plan (Single-Stage Fire Alarm System - Small Establishment) Fire Safety Plan Single-Stage Fire Alarm System (small establishment) for: (Business Name) (Business Address) The reproduction
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and
More informationSARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
More informationRhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report?
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL 1951 Smith Street, North Providence, RI 02911 Telephone: (401) 383-7717 Fax: (401) 383-8879 John E. Chartier, EFO, CFI State Fire Marshal Rhode Island State
More informationInspections Standard Operating Procedure 5 Aboveground Storage Tanks
Aboveground Storage Tanks Aboveground Storage Tank Inspection This Standard Operating Procedure describes the steps that campus units that manage aboveground oil storage tanks (ASTs) or containers must
More informationEXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
More informationBUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS
BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS Owners have numerous responsibilities as it pertains to the maintenance and operation of a building s fire safety equipment. The liabilities
More informationElement D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
More informationCHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).
More informationESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL
ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL The Viking Corporation 210 N Industrial Park Road Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:
More informationFOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS
EXAMINATION REQUIREMENTS FOR FIRE SUPPRESSION SYSTEM CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS REGULATION
More informationFire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
More informationChapter 7 Hydraulic System Troubleshooting
Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic
More informationFIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
More informationFIRE INSPECTION CHECKLIST
Applicable Base Codes FIRE INSPECTION CHECKLIST Florida Fire Prevention Code, 2010 Edition NFPA 1, Uniform Fire Code, Florida 2010 Edition NFPA 101, Life Safety Code, Florida 2010 Edition NFPA 13, 2007
More informationFire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
More informationF.Y.I. Specifying Fire Protection Systems Using Division 13
F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and
More information(Single Stage Fire Alarm System)
1 Fire Safety Plan (Single Stage Fire Alarm System) Fire Safety Plan Single Stage Fire Alarm System for: (Business Name) (Business Address) Signature of Individual Responsible For Implementing this Fire
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and
More informationOntario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
More informationEthanol Vehicle and Infrastructure Codes and Standards Citations
Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and
More information