Element D Services Heating, Ventilating, and Air Conditioning

Size: px
Start display at page:

Download "Element D Services Heating, Ventilating, and Air Conditioning"

Transcription

1 PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3042 on exhaust and ventilation with specific criteria for projects involving design of Laboratory Exhaust and Systems. B. Refer to Design Guideline Element D3042 for the following: 1. General design criteria related Exhaust and. 2. Special Contract Document Requirements and products applicable to the Project. PART 2 - DESIGN CRITERIA 2.01 GENERAL A. In general, laboratory exhaust systems shall comply with procedure and support room ventilation air requirements of NFPA 45, 90A, NIH, CDC, and OSHA. B. Special exhaust systems, noted below, are hazardous and shall not be housed in the same chase that houses environmental supply, return, and exhaust ducts. 1. Laboratory hood exhaust systems. 2. Biological laboratory exhaust. 3. Radioactive hot lab exhaust. 4. LN 2 freezer room exhaust system. C. All other ductwork carrying make-up air that is connected to special exhaust systems may be installed in the same chase that carries environmental supply and/or return ducts. D. Exhaust fans serving laboratory hoods shall be connected to an emergency power source LABORATORY HOOD EXHAUST FANS A. While the type of exhaust system would depend on the hood characteristics, the following features shall be incorporated into the design to avoid excessive noise levels and ensure accurate air balancing. 1. The system shall conform to OSHA Regulation 29 CFR, Part ODG OF 6

2 2. Exhaust shall be continuously monitored and an alarm system (local audible and visible alarm and an alarm at M. D. Anderson Cancer Center s central monitoring services, shall be provided for each hood and biological safety cabinet). 3. Exhaust fans shall be selected to operate at low tip speed (approximately at 50 percent of the maximum permissible tip speed) and maximum static efficiency. 4. Provide fan selection data on a performance curve and ensure that the fan discharge is directed vertically upward. 5. Design duct sizing to maintain velocity in the ductwork between 2000 and 2500 fpm. 6. Select fans with backward inclined fans. 7. Perform sound analysis for each exhaust fan and provide sound attenuation, if required. 8. To ensure design airflow is achieved on manifold and shared exhaust systems, pressure independent, factory-set, field-adjustable automatic airflow control shall be provided for each fume hood and biological safety cabinet. 9. An independent flow monitor shall be provided and alarm locally and to the building automation system (BAS). Provisions need to be incorporated in the design to allow access to the independent flow monitor. B. Each laboratory exhaust air system shall have a corresponding supply air system to comply with laboratory, hood exhaust air, and laboratory ventilation exhaust air change (AC/hr) requirements listed below: Room Description Occupied 3 AC/hr (minimum) Unoccupied AC/hr (minimum) Vacant 4 AC/hr (minimum) Fume Hood Rooms Radio Chemistry Laboratory Open Lab Traditional Lab Tissue and Culture Dark Room Storage Room Glass Wash Room Cold Room LN 2 freezer Room Notes: 1. Lab room has no fume hood. 2. Lab room has fume hood(s). Listed minimums are current. The minimums may be lowered future pending test results. 3. Occupied defined as space with personnel present during specific time. 4. Vacant defined as space that is not assigned to a lab user and that does not have equipment that generates chemicals. ODG OF 6

3 C. Actual air change rates may exceed the above stated rates to maintain temperatures in the laboratory or prevent a hazardous environment. BL3 s and Tissue Culture Rooms are exempt from the occupied and unoccupied air change rate. By definition, one AC/hr is the total of supply air and infiltration air from surrounding space provided in one hour divided by the total room volume. D. Laboratory exhaust fans and 30 percent filter banks shall be an N+1 redundant system capable of maintaining constant volume with the capacity to exhaust listed rooms at the required minimum ventilation design air change rates. E. Exhaust fans shall be direct drive and powered though the use of variable frequency drives that vary fan speeds to maintain the exhaust air requirement during exhaust air filter loading. Fan speed is determined by maintaining and airflow measurement setpoint (adjustable) from the BAS. F. The design exhaust rate through the fume hoods, radioisotope fume hoods and (BSCs) will be determined based on using restricted sash opening and maintaining a minimum face velocity of 100 fpm at any point at the open sash. 1. Laboratory chemical hood operation: Face velocities should be between 80 and 125 fpm at the working sash height with an optimum level of 100 fpm. G. Constant volume bypass type hoods will be utilized. If substantial Organic Chemistry area is included, variable volume type hoods with restricted bypasses will be utilized for those spaces. In addition to fume hoods, the BSCs, flammable storage cabinets, and acid storage cabinets will be served as follows: 1. A typical fume hood and Class II Type B1 cabinets should be included in laboratory exhaust system. 2. Class II Type B2 cabinets should have a dedicated exhaust system or they can be combined with an exhaust system that transports air from radioisotope hoods. 3. Radioisotope hoods should have a dedicated exhaust. 4. Organic chemistry hoods may also require a dedicated exhaust air system. 5. Flammable storage cabinets and acid storage cabinets will be ventilated utilizing a 2-inch galvanized pipe directly connected from the cabinet to the fume exhaust ductwork. An exhaust air valve will not be utilized for the cabinet. 6. Some of the Class II Type B2 BSCs will utilize bag-in/bag-out percent HEPA filters located on top of the BSC cabinet, and the supply air filters are within the BSCs. H. The type of filtration components that will be placed in the laboratory exhaust shall be evaluated based on the work being performed in each of the laboratories and exhaust hoods. ODG OF 6

4 I. Instruments that control air valves shall be capable of changing the state of room pressurization, which will be dependant on current and future use of the laboratory. J. Storage rooms that contain laboratory specialty gases or liquid nitrogen stored in dewars shall be ventilated and shall have the appropriate gas detection monitoring and alarm systems per OSHA requirements to protect personnel from accidental asphyxiation. K. LN 2 freezer rooms shall have air change rate as listed in this sections air change rate table. Exhaust duct shall be galvanized and routed to the general lab exhaust air energy recovery system. The bottom of exhaust air grilles shall be placed low to the floor where nitrogen gas if present in the room can be readily exhausted from the room. Supply air grilles shall be placed at ceiling heights LABORATORY EXHAUST DUCTWORK A. Specify welded stainless steel Type 316L ductwork (18 gage minimum) for exhaust air ductwork from the BSCs, laboratory glassware washer, and chemical fume hoods where corrosive chemicals may be used, and hoods that use radioactive isotopes use a Type 316 polished at weld, stainless steel. Exhaust duct from synthesis labs should be Type 316L stainless or other suitably rugged/ inert material due to the corrosive and toxic exhaust. B. Galvanized steel can be used as the construction duct material on general exhaust systems. C. Exhaust ducts used to transport air from Biological Safety Cabinets where radioisotopes are used must be labeled with the standard Caution Radiation Symbol magenta on yellow background at 20 foot intervals. Equip Biological Safety Cabinets with proper filtration components to capture potential contaminates. D. Route the exhaust duct through the building roof at a distance of 25 feet and downwind from any outside air ventilation air intake. The final location and orientation of the laboratory exhaust or outside air intake is determined from wind tunnel results. E. The allowable exhaust air stack height shall be minimum 12 feet above centerline height of air intake or roofline. The stack discharge air velocity shall be equal to or greater than 3000 fpm (3600 fpm for NIH funded project). F. Locate exhaust discharge stack where it cannot be easily reintroduced into the building outside air intakes. Research prefers to locate outside ventilation air intakes on the side of the building and not on the roof. Refer to Design Guideline Element D3041 for additional criteria on outside air intakes. G. When high plume exhaust fans are being considered in the design of a laboratory exhaust system, the A/E needs to place the plume heights, design airflow rates, static pressure requirement, and maximum brake horsepower requirements on the equipment schedule. 1. A/E shall consider wind velocities and prevailing wind direction as listed in Chapter 26 in Tables 1A, 2A and 3A of ASHRAE Handbook of Fundamentals or airport weather data. ODG OF 6

5 2.04 AIR DEVICES A. Refer to Sound Criteria in Design Guideline Element D3002. B. Exhaust square panel face Titus Omni directional diffusers with round necks shall be provided in open areas. Increase neck sizes for the diffuser since they are being used for exhaust air purposes. C. Air valves shall be used to control the exhaust airflow rates from rooms, hoods, and BSCs via feed back signals from stand alone controllers and setpoints (adjustable) from the BAS. PART 3 - SPECIAL CONTRACT DOCUMENT REQUIREMENTS 3.01 GENERAL A. Include a single line riser drawing of the general exhaust ventilation exhaust systems in the Contract Documents. This shall be initially provided in the Schematic Design Submittal. PART 4 - PRODUCTS 4.01 GENERAL A. Refer to Master Construction Specifications. B. Evaluate energy recovery units as appropriate to the application in accordance with the latest edition of ANSI/ASHRAE/IESNA C. Evaluate the use of proximity occupant sensors on each hood to reduce the open sash face velocity to 60 fpm when the workspace in front of the fume hood is not occupied. D. The preferred direct drive exhaust fans are high plume dilution mixed flow fans, where feasible. E. Evaluate and provide test data for other laboratory HVAC airflow tracking equipment Phoenix (Accel II) or Tek-Air Valves that control the temperatures and exhaust airflow rates from the individual room or spaces. These systems should be operating with BACnet open protocol and also be compatible system with the existing BAS. F. Evaluate an exhaust duct material that is capable of withstanding the corrosion products from a synthesis laboratory. G. Evaluate recirculation of air in non-laboratory areas. H. Evaluate sensible cooling in low hazard, high heat load areas. ODG OF 6

6 PART 5 - DOCUMENT REVISION HISTORY Issue Date Revision Description Revisor Initial Adoption of Element Rev Part 2 Laboratory Exhaust Hoods added Titus; Part 2.1 revised Table for Tissue Culture Room AC rate from 8 to 12 for unoccupied mode; revised to exception on AC rates lab temp, and prevent hazardous environment; revised 150 to 125 fpm; deleted B3 and Class III BSCs; revised 10 ft to12 ft on exhaust stacks; revised Air Devices; added criteria that A/E to evaluate use of duct material serving synthesis labs; deleted additional exhaust requirement for RI room. Rev Revised AC/hr values in the table of 2.02 B. including the additions of notes and editorial format changes. PDN PDN / CC Rev Added 2.01B.4., added AC/hr value in the table of 2.02 B. for LN 2 Freezer Room, revised J. and added 2.02 K.. Rev. 4 Rev. 5 PDN END OF ELEMENT D ODG OF 6

Fume Hood Questions and Answers

Fume Hood Questions and Answers Fume Hood Questions and Answers 1. When should I use a fume hood? Use a chemical fume hood anytime your work involves: Chemicals with a National Fire Protection Association (NFPA) Health rating of 3 or

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health

Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health Background Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health This document provides guidelines for the design and installation of Class

More information

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory

More information

SAM HOUSTON STATE UNIVERSITY

SAM HOUSTON STATE UNIVERSITY PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

Chemical Fume Hoods. Environmental Health and Safety 974-5084

Chemical Fume Hoods. Environmental Health and Safety 974-5084 Chemical Fume Hoods Environmental Health and Safety 974-5084 Regulatory References Prudent Practices in the Laboratory 2011 (National Research Council of The National Academies): Laboratory chemical hoods

More information

Element D Services Plumbing

Element D Services Plumbing Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

VAV Laboratory Room Airflow The Lowdown on Turndown

VAV Laboratory Room Airflow The Lowdown on Turndown Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally

More information

Laboratory Design & Construction Guidelines

Laboratory Design & Construction Guidelines Laboratory Design & Construction Guidelines Department of Environmental Health & Safety EHS-M-35 Page 1 Issue Date: 03/01/10 General Health and Safety The USC Environmental Health and Safety Department

More information

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC

More information

LABORATORY GUIDELINES AND STANDARDS

LABORATORY GUIDELINES AND STANDARDS LABORATORY GUIDELINES AND STANDARDS APPLICATION NOTE LC-125 Introduction This publication provides excerpts from some of the many guidelines and standards that pertain to the construction and operation

More information

3. Alberta Occupational Health and Safety Act, Regulation and Code, July 1, 2009.

3. Alberta Occupational Health and Safety Act, Regulation and Code, July 1, 2009. 6.3 Laboratory Spaces 6.3.1 Regulations 1. Alberta Building Code, 2006 2. Alberta Fire Code, 2006 3. Alberta Occupational Health and Safety Act, Regulation and Code, July 1, 2009. 4. Canadian Nuclear Safety

More information

Procedures for the Effective Use of Biological Safety Cabinets

Procedures for the Effective Use of Biological Safety Cabinets Procedures for the Effective Use of Biological Safety Cabinets APPROVAL DATE BY BIOHAZARDS SUBCOMMITTEE: August 10, 2012 SUPERSEDES: March 1, 2012 This corporate guideline/procedure is intended as a minimum

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

Element D Services Plumbing

Element D Services Plumbing PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL

More information

Geismar Site Reviewed: 07/05/16 Effective: 07/05/16 Supersedes: 08/04/14 Preparer: Owner: Approver: S/IH Team Leader S/IH Team Leader Manager LA Hub

Geismar Site Reviewed: 07/05/16 Effective: 07/05/16 Supersedes: 08/04/14 Preparer: Owner: Approver: S/IH Team Leader S/IH Team Leader Manager LA Hub BASF Corporation Title: LOCAL EXHAUST VENTILATION Individual Unit Function: Industrial Hygiene Procedure No.: IH-3 Page: 1 of 12 Geismar Site Reviewed: 07/05/16 Effective: 07/05/16 Supersedes: 08/04/14

More information

15850 Laboratory and Industrial Ventilation Systems

15850 Laboratory and Industrial Ventilation Systems Part 1: General 1.01 General Guidelines - The primary purpose of chemical laboratory hoods and other industrial ventilation systems is to protect the worker or researcher against exposure to hazardous

More information

LABORATORY DESIGN HANDBOOK

LABORATORY DESIGN HANDBOOK LABORATORY DESIGN HANDBOOK UNDERSTANDING, ACCELERATED LABORATORY DESIGN HANDBOOK TSI, TSI logo, are registered trademarks of TSI Incorporated. Copyright 2014 by TSI Incorporated This handbook is not intended

More information

Laboratory Standards and Guidelines

Laboratory Standards and Guidelines Laboratory Standards Copyright 2002 Phoenix Controls Corporation Newton, Massachusetts 02458 Reproduced with permission from AIA, Washington, DC 20006. From American Conference of Governmental Industrial

More information

Biosafety Level 2 (BSL-2) Safety Guidelines

Biosafety Level 2 (BSL-2) Safety Guidelines BLS-4 Biosafety Level 2 (BSL-2) Safety Guidelines BSL-3 BSL-2 BSL-1 BSL-2 builds upon BSL-1. If you work in a lab that is designated a BSL-2, the microbes used pose moderate hazards to laboratory staff

More information

Ammonia Detection System Codes and Design Specifications

Ammonia Detection System Codes and Design Specifications Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion

More information

1.2 Refrigerant Equipment. General

1.2 Refrigerant Equipment. General Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

Commercial Kitchen Fire Safety

Commercial Kitchen Fire Safety Commercial Kitchen Fire Safety Commercial grade kitchens are a common feature found in many churches today, as religious institutions are providing meals for daycares, soup kitchens, meals on wheels and

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

6 MECHANICAL HVAC SYSTEMS

6 MECHANICAL HVAC SYSTEMS Conventional Facilities Chapter 6: HVAC Systems 6-1 6 MECHANICAL HVAC SYSTEMS 6.1 Design Criteria 6.1.1 Codes and Standards The latest edition of the codes, standards, orders, and guides referred to in

More information

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng. HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains

More information

Metrics That Matter: Pam Greenley MIT EHS Associate Director greenley@mit.edu. Steve Lanou MIT Deputy Director, Sustainability slanou@mit.

Metrics That Matter: Pam Greenley MIT EHS Associate Director greenley@mit.edu. Steve Lanou MIT Deputy Director, Sustainability slanou@mit. Metrics That Matter: Energy Efficiency in Laboratories Pam Greenley MIT EHS Associate Director greenley@mit.edu Steve Lanou MIT Deputy Director, Sustainability slanou@mit.edu Today Measuring progress of

More information

Mechanical and Natural Ventilation

Mechanical and Natural Ventilation BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:

More information

Requirements for Hydrogen Storage and Use

Requirements for Hydrogen Storage and Use Requirements for Hydrogen Storage and Use I. INTRODUCTION Fire and Life-Safety Group (FLS) The following is a summary of the fire and building code requirements for the storage and use of hydrogen. These

More information

Basics of HVAC Cleaning

Basics of HVAC Cleaning Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project

More information

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

SPECIAL APPLICATIONS

SPECIAL APPLICATIONS Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction

More information

Department of Environmental Health and Safety & Emergency Management

Department of Environmental Health and Safety & Emergency Management Date: February 2014 Revision: 02 Page: 1 of 13 This Guideline is issued jointly by the Department of Environmental Health and Safety & (EHSEM) and Facilities Management to provide guidance and consistency

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN Presented to: ASHRAE YEA Illinois Chapter Specialty Environment Design Conference March 24, 2014 Jean O. Gibbons, PE, LEED AP Senior Vice President Grumman/Butkus

More information

Fan Applications & System Guide

Fan Applications & System Guide Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation

More information

Spray Booth Guideline

Spray Booth Guideline Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Radiant Panels and Chilled Sails. www.price-hvac.com

Radiant Panels and Chilled Sails. www.price-hvac.com Radiant Panels and Chilled Sails www.price-hvac.com Radiant Panels and Chilled Sails Introduction Radiant panels use thermal radiation to modify surface temperatures in order to provide sensible cooling

More information

CE6500 Energy Recovery Ventilator

CE6500 Energy Recovery Ventilator ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

HVAC. Kitchen Exhaust. rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier!

HVAC. Kitchen Exhaust. rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier! HVAC & Kitchen Exhaust The Heart of Restaurant HVAC rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier! 1 CKV Design: Just not that easy! There is no piece of equipment in the commercial

More information

PULASKI AND DUBLIN MIDDLE SCHOOLS

PULASKI AND DUBLIN MIDDLE SCHOOLS PULASKI AND DUBLIN MIDDLE SCHOOLS HVAC/ ELECTRICAL/ WINDOW REPLACEMENT STUDY DUBLIN MIDDLE SCHOOL REPORT BY: PULASKI MIDDLE SCHOOL P.C. Plaza Suite 1 10 Church Avenue SE Roanoke, VA 24011-2104 540.342.6001

More information

Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION

Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION LARS OLANDER, LORRAINE CONROY, ILPO KULMALA, RICHARD P. GARRISON, MICHAEL ELLENBECKER, BERNHARD BIEGERT, BERNARD FLETCHER, HOWARD D.

More information

Risk Assessment: Biosafety Cabinet

Risk Assessment: Biosafety Cabinet Risk Assessment: Biosafety Cabinet Biosafety cabinets (BSCs) serve as primary containment devices for operations involving potential splashes, spills or aerosolization of hazardous biological materials.

More information

DRYER VENTING SPECIFICATIONS DRYER SAFETY

DRYER VENTING SPECIFICATIONS DRYER SAFETY DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting

More information

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder. Page 1 of 5 COMPRESSED GASES A compressed gas is defined as any mixture of gases in a container with a pressure exceeding 40 psi. at 70 o F, or 104 psi. at 130 o F; or any flammable liquid with an absolute

More information

FDNY C14 Certificate of Fitness Quiz

FDNY C14 Certificate of Fitness Quiz FDNY C14 Certificate of Fitness Quiz Name: Date: 1. Who issues a New York City laboratory permit? a) Department of Environmental Protection (DEP) b) Department of Environmental Conservation (DEC) c) Occupational

More information

All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.

All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal. 2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other

More information

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories Basis of Design This section applies to the design and installation of ductwork, air terminal boxes, air outlets and inlets, volume dampers, pressure relief dampers, smoke/fire dampers, and smoke/fire

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

HVAC Systems in Schools & Commercial Buildings and Radon

HVAC Systems in Schools & Commercial Buildings and Radon HVAC Systems in Schools & Commercial Buildings and Radon References US EPA Radon Prevention in the Design and Construction of Schools and Other Large Buildings http://www.epa.gov/ordntrnt/ord/nrmrl/pubs/1993/air/

More information

School of Human Ecology Building UW Madison, Wisconsin. By Arnold & O Sheridan, Inc. A&O Project No. 001175 Draft Report 01/12/01 revised

School of Human Ecology Building UW Madison, Wisconsin. By Arnold & O Sheridan, Inc. A&O Project No. 001175 Draft Report 01/12/01 revised School of Human Ecology Building UW Madison, Wisconsin By Arnold & O Sheridan, Inc. A&O Project No. 001175 Draft Report 01/12/01 revised HEATING, VENTILATING AND AIR CONDITIONING SYSTEM REPORT Introduction

More information

Stanford Laboratory Standard & Design Guide TABLE OF CONTENTS

Stanford Laboratory Standard & Design Guide TABLE OF CONTENTS Section 1.1: VENTILATION TABLE OF CONTENTS Page A. Regulations, Standards and References 1.1-3 B. Scope 1.1-3 C. General Ventilation Considerations 1.1-3 D. Negative Pressurization 1.1-6 E. Supply Air

More information

Preliminary Final Proposal

Preliminary Final Proposal 1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

Fläkt Woods Building Future

Fläkt Woods Building Future Energy, Expertise and Environment with Fläkt Woods Fläkt Woods Building Future Saving energy in building ventilation You must save 20% on energy before 2020. Following the Kyoto protocol the European Union

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

OSHA and Welding Exhaust

OSHA and Welding Exhaust OSHA and Welding Exhaust The following has been taken directly from OSHA s General Industry Standards and Interpretations, Part 1910, Subpart Q Welding, Cutting, and Brazing. We have omitted irrelevant

More information

Subject: Magnet Safety. Overview: Environmental Health & Safety Policy/Procedure Effective Date: July 29, 2011

Subject: Magnet Safety. Overview: Environmental Health & Safety Policy/Procedure Effective Date: July 29, 2011 Subject: Magnet Safety Environmental Health & Safety Policy/Procedure Overview: The purpose of this document is to define and clarify policies associated with the use of magnets and magnetic fields at

More information

Particularly Hazardous Substances (PHS) Standard Operating Procedure (SOP)

Particularly Hazardous Substances (PHS) Standard Operating Procedure (SOP) Particularly Hazardous Substances (PHS) Standard Operating Procedure (SOP) Formaldehyde, formalin, paraformaldehyde solutions, and paraformaldehyde solids Principal Investigator: Room & Building #: Department:

More information

LOW-PRESSURE-DROP HVAC DESIGN FOR LABORATORIES

LOW-PRESSURE-DROP HVAC DESIGN FOR LABORATORIES L a b o r a t o r i e s f o r t h e 2 1 s t C e n t u r y : B e s t P r a c t i c e s LOW-PRESSURE-DROP HVAC DESIGN FOR LABORATORIES Introduction Laboratory ventilation systems are designed to isolate

More information

Basic Selection & Proper Application of Overhead Air Distribution Devices

Basic Selection & Proper Application of Overhead Air Distribution Devices Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return

More information

BOSTON COLLEGE ENVIRONMENTAL HEALTH AND SAFETY LABORATORY GUIDE FOR RENOVATIONS, REMODELS, MOVES AND TERMINATIONS

BOSTON COLLEGE ENVIRONMENTAL HEALTH AND SAFETY LABORATORY GUIDE FOR RENOVATIONS, REMODELS, MOVES AND TERMINATIONS BOSTON COLLEGE ENVIRONMENTAL HEALTH AND SAFETY LABORATORY GUIDE FOR RENOVATIONS, REMODELS, MOVES AND TERMINATIONS I. Policy for Termination of Laboratory Use of Hazardous Materials The Principal Investigator

More information

The Data Center Dilemma - A Case Study

The Data Center Dilemma - A Case Study Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: mail@cleanroom-solutions.co.uk W: www.cleanroom-solutions.co.uk

Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: mail@cleanroom-solutions.co.uk W: www.cleanroom-solutions.co.uk Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: mail@cleanroom-solutions.co.uk W: Introduction Cleanroom Solutions Ltd has a wealth of experience together with a solid track record in the

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

Case Studies: Infrared Heating in Industrial Applications

Case Studies: Infrared Heating in Industrial Applications Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000

More information

HVAC Basic Science - System Capacity

HVAC Basic Science - System Capacity HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

Mechanical Rooftop Custom Capabilities

Mechanical Rooftop Custom Capabilities Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition

More information

FIRE DAMPER APPLICATION GUIDE

FIRE DAMPER APPLICATION GUIDE FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire

More information

Fume Hood Program 2003-2011. UNH Office of Environmental Health and Safety. All rights reserved.

Fume Hood Program 2003-2011. UNH Office of Environmental Health and Safety. All rights reserved. Fume Hood Program 2003-2011. UNH Office of Environmental Health and Safety. All rights reserved. UNH Fume Hood Program Page 1 Table of Contents I. INTRODUCTION... 4 II. GOAL... 5 III. LABORATORY FUME HOODS

More information

White Paper. Best Practices for Gas Monitoring in the Commercial Kitchen

White Paper. Best Practices for Gas Monitoring in the Commercial Kitchen White Paper Best Practices for Gas Monitoring in the Commercial Kitchen Enhancing Kitchen Safety through Strategic Gas Monitoring Overview Commercial kitchens are one of the most hazardous commercial building

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Energy-Efficient Laboratory Design

Energy-Efficient Laboratory Design 2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 5, May 2005). This article may not be

More information

Energy Efficiency HOSPITALITY. www.energia.ie

Energy Efficiency HOSPITALITY. www.energia.ie Energy Efficiency HOSPITALITY www.energia.ie Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could make a real

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

National System of Garage Ventilation s Engineering Guide

National System of Garage Ventilation s Engineering Guide National System of Garage Ventilation s Engineering Guide In designing a fume removal system, it is extremely important to determine the following: 1. Type of apparatus to be exhausted (i.e. gasoline,

More information

Acoustical Design Guidelines for HVAC Systems in Schools

Acoustical Design Guidelines for HVAC Systems in Schools Acoustical Design Guidelines for HVAC Systems in Schools Seminar 9, ASHRAE Summer Meeting Albuquerque, New Mexico Sponsor: TC 2.6 Sound and Vibration Robert M. Lilkendey Associate Principal Consultant

More information

Current as of 11/10/08 1 of 1

Current as of 11/10/08 1 of 1 BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that

More information

University of Tennessee Safety Guidelines

University of Tennessee Safety Guidelines University of Tennessee Safety Guidelines Guideline Subject: Compressed Gases and Cryogenics Safety Guidelines Approval Date: 10/1/15 (Rev. 1) Next Scheduled Review: 10/1/19 Date Effective: 1/01/09 Contact

More information

CCFC 22 nd Annual Conference Session #15

CCFC 22 nd Annual Conference Session #15 CCFC 22 nd Annual Conference Session #15 Optimally Operating Chemistry and Biology Laboratory Facilities w/ Advanced Science Curricula in a College Campus Robert Jenkins Director of Facilities San Bernardino

More information

The Basics of Commercial Kitchen Exhaust Cleaning

The Basics of Commercial Kitchen Exhaust Cleaning The Basics of Commercial Kitchen Exhaust Cleaning ANSI/IKECA C 10 ANSI/IKECA C 10: Standard for Cleaning of Commercial Exhaust Systems IKECA Introduces the Kitchen Exhaust Cleaning Industry s First American

More information

Technical Specifications for West Campus Data Center HVAC System

Technical Specifications for West Campus Data Center HVAC System Technical Specifications for West Campus Data Center HVAC System I. Mechanical Systems Requirements A. HVAC Primary Data Centers, Automation HVAC is to be provided on a 24 hours per day, 365 days per year

More information

Laboratory Ventilation Safety. J. Scott Ward

Laboratory Ventilation Safety. J. Scott Ward Laboratory Ventilation Safety J. Scott Ward In 1925, Laboratory Construction Company was born. The first product was a Kjeldahl Nitrogen Determination Apparatus. We may have shortened our name, but we

More information

FINAL December 2012 SECTION 233100 DUCTWORK

FINAL December 2012 SECTION 233100 DUCTWORK SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insula tion shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation

More information

LOCATING AIR INTAKES AND EXHAUSTS

LOCATING AIR INTAKES AND EXHAUSTS LOCATING AIR INTAKES AND EXHAUSTS Summary New ASHRAE standards require an investigation of local ambient air quality and documentation of design assumptions and calculations on measures taken to control

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Cooktop Low-Profile Ventilation Hoods

Cooktop Low-Profile Ventilation Hoods INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............

More information

A. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.

A. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment. SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel

More information