SECTION FIRE PROTECTION. B. Section Mechanical Operation and Maintenance Manuals
|
|
- George Melton
- 7 years ago
- Views:
Transcription
1 Building 4 Archive Remodel Page 1 of 5 SECTION Part 1 - General FIRE PROTECTION 1.01 RELATED SECTIONS A. Section General Mechanical Provisions B. Section Mechanical Operation and Maintenance Manuals 1.02 SCOPE OF WORK A. Provide complete design and engineering, shop drawings, and installation for reconfiguration of the existing wet pipe sprinkler system to provide full coverage of the remodel area. The fire protection system shall fully comply with the following requirements: 1. Latest adopted edition of NFPA 13 - Installation of Sprinkler Systems 2. Local or regional standards / ordinances B. Coverage shall also include, but not be limited to, the following: 1. Concealed spaces with combustible construction SYSTEM ENGINEERING AND QUALITY ASSURANCE A. Fire Protection engineering and design shall be performed by, or under the direct supervision of, a currently licensed Oregon Professional Engineer. Submittal packages (drawings, calculations) shall bear the signed seal of the supervising engineer. B. The Fire Protection System engineer/designer: 1. Shall be familiar with and comply with documented standards and ordinances required by the local authority having jurisdiction. 2. Shall be responsible for verifying design and field conditions prior to submitting shop drawings for preliminary approval. Field conditions include, but are not limited to, areas subject to freezing or ambient temperatures less than 40 deg. F, available ceiling space, and obstructions such as structural elements. C. Piping shall be concealed above new ceilings except as noted on Drawings. Where no ceilings occur, pipe routing and head locations are subject to review and approval by Architect at time of preliminary system drawings SHOP DRAWINGS, PRODUCT DATA, OPERATION & MAINTENANCE DATA A. Submittals required for the products listed in the Product Table, in accordance with Section Operation & Maintenance Information required as indicated in the Product Table in accordance with Section B. Operation & Maintenance Information requirements indicated by number designation as follows. Refer to Section for a description of each type of information. 1. Shop Drawings (submittal data) 2. Product Data (submittal data) 3. Manufacturer's Operation Manuals
2 Building 4 Archive Remodel Page 2 of 5 4. Manufacturer s Service and Lubrication Requirements 5. Service Contracts and Field Start-up Reports 6. Cleaning, Certification, and Test Reports 7. System Information 8. Warranties PRODUCT TABLE Pipe, fittings, hangers, and joining systems. Sprinkler Heads. Indicate head response type and listed coverage area. Prepare a complete set of system drawings showing: (1) System Type(s) and sizing method(s) used. (2) Pipe runs, pipe sizes, valves, flow switches, and drains. (3) Schedule of proposed products for each pipe size, fire protection system type, and area served. (4) Hydraulic reference points and remote design areas, referenced to calculations. (5) List of symbols and abbreviations used. (6) Head locations and types in relationship to structure, lights, diffusers, speakers, and other architectural elements. Include head types lights, diffusers, speakers and other architectural elements in Symbols List. (7) Supply riser location and detail. (8) Location and height of fire department connections. (9) Flexible assemblies and seismic loops at pipes crossing building expansion and seismic joints. (10)Manufacturer's model number and location of equipment. Operation & Maintenance Information C. Submit Shop Drawings as follows: 1. Submit system drawings to Architect for preliminary review and comments. 2. If comments are received, make noted changes and resubmit to Architect for review. 3. Following Architect final review, submit final drawings to the local/state Fire Marshal for approval. 4. After receiving approval from the local/state Fire Marshal, submit the drawings with Fire Marshal s approval stamp to the Architect. 5. Provide Architect a copy of transmittal letter documenting submittal to Owner's insurance carrier. Part 2 - Products 2.01 GENERAL A. Products shall be UL listed and FM approved for the purpose and system specified PIPE AND FITTINGS A. Sprinkler Systems:
3 Building 4 Archive Remodel Page 3 of 5 1. Pipe and fittings shall conform to NFPA Pipe and fittings for preaction and dry pipe systems shall be hot dipped galvanized in accordance with ASTM-A Proprietary pipe, listed and installed in accordance with NFPA 13, shall be limited to the following products: a. Allied Dyna-Flo / Super Flo b. Allied Dyna-Thread / Super SPRINKLER HEADS A. General: 1. FM approval not required for enamel coated heads where noted. 2. Provide required head response type and coverage area for spaces as indicated in Fire Protection System Plan on Drawings 3. Provide proper temperature rating in accordance with NFPA Provide quick-response type heads where permitted by Code. B. Manufacturer: Tyco Fire Products, Viking, Standard, Reliable, or approved. C. Upright: 1. Finish: a. Concealed: Standard brass. b. Exposed: Polished chrome. 2. Application: Exposed piping and concealed spaces. D. Wet Pendant: 1. Finish: a. Concealed: Standard brass. b. Exposed: Polished chrome. 2. Application: Exposed piping and concealed spaces. E. Semi-Recessed Wet Pendant: 1. Finish: Polished chrome head and escutcheon. 2. Application: Acoustical tile ceiling areas. F. Upright/Pendant Sidewall: 1. Deflector: Directional discharge designed for upright or pendant operation. 2. Finish: Polished chrome. G. Horizontal Sidewall: 1. Deflector: Directional discharge designed for horizontal sidewall operation. 2. Finish: Polished chrome. H. Sprinkler Head Escutcheons: 1. Matched escutcheon listed for use with the specific sprinkler head and manufactured by the same manufacturer VALVES A. Gate Valves, 2 inch and smaller:
4 Building 4 Archive Remodel Page 4 of PIPE SUPPORTS 1. Bronze construction 2. Threaded ends A. Ring Hangers for Pipe Sizes 3 inch and smaller: 1. Type: Carbon steel band, adjustable, with knurled swivel nut. 2. Finish: Zinc plated. 3. Approvals: UL and FM. 4. For uninsulated copper piping: Equivalent to model specified, with addition of copper plating, neoprene coating, or PVC coating. 5. Manufacturer: a. Anvil Fig. 69. b. B-Line Fig. B c. Super Strut C-727. d. PHD Model 151. e. Erico/Michigan Model 100. f. Tolco Fig. 2, Fig. 200 for sizes 2 and smaller. B. Hanger Rods: 1. Materials: Carbon Steel. 2. Finish: a. Indoors: Zinc plated. b. Outdoors or Wet Areas: Hot dip galvanized. c. Diameter: Meet or exceed NFPA requirements. C. Wall supports & Trapeze Assemblies: 1. Description: Field fabricate of manufactured channel components. 2. Pipe Supports: U-bolt, U-strap, or roller type components in accordance with those specified herein and compatible with manufactured channel system. 3. Trapeze Size: As published by manufacturer for span and total weight supported. Provide sizing criteria with product data submittal. 4. Manufacturer: Unistrut, Super-Strut, B-Line, Erico/Michigan, or approved. Part 3 - Execution 3.01 INSTALLATION A. Install pipe plumb, parallel, and true to building structural system. Where possible, use full 20 ft. lengths. B. Install hangers at branch line connections to cross mains and as required by NFPA 13. C. Coordinate piping and head locations with structure, ductwork, plumbing, lighting, and other electrical work. D. Coordinate sprinkler head locations with architectural reflected ceiling plans. Center heads both ways in ceiling tile.
5 Building 4 Archive Remodel Page 5 of INSPECTION AND TESTS A. Arrange and pay for inspection and tests required by the authorities and agencies to obtain complete and final acceptance of system. B. Piping: Rough-in hydrostatically tested and witnessed by the Fire Marshal or his assigned deputy. C. Inspections: 1. At completion of work and again before end of years guarantee 2. Operate control valves 3. Lubricate operating stems 4. Lubricate fire department connections 5. Repair any leaks D. Provide certificate in duplicate of Fire Marshal's acceptance. END OF SECTION
Clark County Fire Prevention
Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF
More informationSECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
More informationSECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment
More informationQuick response concealed horizontal sidewall sprinkler
January 1, 2011 Sprinkler 63a 1. DESCRIPTION Viking Quick Response Concealed Horizontal Sidewall Sprinkler VK408 is a small solder link and lever spray sprinkler designed for installation on concealed
More informationModel SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description
Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary s, Standard are
More informationModel KFR56 Series Quick Response Standard Spray
Bulletin 036 Model KFR56 Series Quick Response Standard Spray Bulletin 036 Model KFR56 Sprinkler Types Standard Upright Standard Pendent Horizontal Sidewall Model KFR56 Sprinkler Types Pendent F1/F2/FP
More informationesfr pendent sprinkler vk510 (k25.2)
January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition
More informationSeries TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description
Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall s Quick and Standard Response (Light Hazard) General Description TYCO Series TY-FRB 5.6 and
More informationESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA
December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas
More informationModel/Sprinkler Identification Numbers
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-L 5.6 and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description
More informationTECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013
Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge
More informationFACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING 21 11 00
211100_flexheadin_01_MS_0409 5/22/09 PTC 56 Lowland Street Holliston, MA 01746 Phone: (800) 829-6975 Phone: (508) 893-9596 Fax: (508) 893-6020 E-mail: sales1@flexhead.com www.flexhead.com This MANU-SPEC
More informationMERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS
MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth
More informationAutomatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
More informationSprinkler Identification Numbers
Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 K-factor Horizontal Quick Response, Standard Coverage General Description described in this data sheet are quick response -standard coverage, decorative
More informationSeries DS-1 Dry-Type Sprinklers 5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description
Worldwide Contacts www.tyco-fire.com Series DS-1 Dry-Type Sprinklers 5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description TYCO Series DS-1 Dry-Type Sprinklers, 5.6
More informationSprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts. www.tyco-fire.com
Worldwide Contacts www.tyco-fire.com Model EC-HS 80 K-factor, Quick Response Extended Coverage Horizontal Sidewall Sprinklers Installations per VdS CEA 400, Annex E, LH/OH General Description The Model
More informationViking Residential Sprinkler Installation Guide
Viking Residential Sprinkler Installation Guide January, 2009 Trusted Above AllT M www.flowbusiness.cl Sprinkler RES1 January 9, 2009 1. DESCRIPTION Viking residential automatic sprinklers are equipped
More informationPLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
More informationPIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant
More informationSeries ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description IMPORTANT Always refer
More informationSprinkler Guards Model C Model D
Bulletin 208 Rev. M Sprinkler Guards Model C Model D Bulletin 208 Rev. M Model C Sprinkler Guards Model C Series sprinkler guards are designed to be assembled onto installed sprinklers. They are constructed
More informationRESIDENTIAL SPRINKLER INSTALLATION GUIDE
RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,
More informationSeries TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description
Worldwide Contacts www.tyco-fire.com Series 2.8,.2,.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description The TYCO Series, 2.8,.2,.6, 8.0 K-factor,
More informationAntifreeze Solutions in Residential Fire Sprinkler Systems
Antifreeze Solutions in Residential Fire Sprinkler Systems The 2013 edition of NFPA 13D, as amended by TIA 13 1, discourages the use of antifreeze solutions within residential fire sprinkler systems unless
More informationSprinkler Identification Numbers (SINs) Technical Data
Worldwide Contacts www.tyco-fire.com Series DS-1 5.6 K-factor, Dry-type Sprinklers Pendent, Upright, and Horizontal Sidewall Standard Response, Standard Coverage General Description TYCO Series DS-1 5.6K
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationSECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such
More informationDesign & Construction Standards, Revised January 2013 5.21.30-1
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.
More informationFire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting
More informationModel F1FR Series Quick Response Glass Bulb Sprinklers
Model F1FR56 Sprinkler Types Standard Spray Standard Spray Conventional / Vertical Sidewall Model F1FR56 Recessed Sprinkler Types Standard Spray Model F1FR56 Concealed Sprinkler Types Standard Spray Model
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationC I T Y O F S E L M A F I R E D E P A R T M E N T
C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:
More informationSECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 230529 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Steel pipe hangers and supports. 2. Metal framing systems. 3. Thermal-hanger shield inserts. 4. Fastener systems.
More informationA. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.
SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationLAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
More informationFighting Fire in Sprinklered Buildings. Student Guide
Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction
More informationSeries TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-FRL 5.6 and 8.0 K-factor Extended Horizontal Sidewall s Quick & Standard (Light Hazard) General Description The Series TY-FRL, 5.6,
More informationAll work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
More informationNFPA 25 FAQs. 1. When inspecting an old system (60 years or older), when/where does NFPA 25 require a system to be upgraded to present standards?
NFPA 25 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationType D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description
Worldwide Contacts www.tyco-fire.com Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description The TYCO Type D3 PROTECTO- SPRAY Nozzles are open (non-automatic) directional
More informationModel WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description
Worldwide Contacts www.tyco-fire.com Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description The TYCO Model WS Specific Application Window
More informationType EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description
Worldwide Contacts www.tyco-fire.com Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description The TYCO Type EA-1 PROTECTO- SPRAY Directional Spray Nozzles are automatic
More informationFIRING RANGE PHASE 1 DESIGN 224500-1
FIRING RANGE PHASE 1 DESIGN 224500-1 SECTION 224500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationEngineering Specifications
PUREFLOW PEX PRODUCTS PART 1 GENERAL 1.1 SUMMARY 1.1.1 This specification covers Branch & Main, Parallel Water Distribution Systems (MANABLOC), Cross-linked Polyethylene tubing and fittings using PEX Press
More informationSECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES
SECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
More informationRoland Garcia Pearland Fire Department
Roland Garcia Pearland Fire Department NFPA13D Texas Legislation Conflicting Views - Fire Service and Home Builders Incentives offered in the ICC Detect and control residential fires Prevent injury and
More informationModel: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
More informationSelect Radiators Installation Guide
Select Radiators Installation Guide Table of Contents Informational Symbols...3 Before You Begin...4 Select Rough-In... 5 Connection Installation...6 Optional Piping Arrangements...7 Conventional Wall
More informationModel F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description
Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed
More informationFIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
More informationIDENTIFICATION BROCHURE FOR Central RESIDENTIAL WET SPRINKLERS
IDENTIFICATION BROCHURE FOR Central RESIDENTIAL WET SPRINKLERS 1 INTRODUCTION TO THE VOLUNTARY REPLACEMENT PROGRAM This brochure provides information that will assist you in identifying whether the sprinklers
More informationSECTION 260536 - CABLE TRAYS. A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system.
SECTION 260536 - CABLE TRAYS PART 1 - GENERAL SECTION INCLUDES: A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system. B. Cable tray systems are defined to include, but
More informationSELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
More informationSECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
More informationTECHNICAL DATA. Dry 122a. November 12, 2013
Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model
More informationViking Residential Sprinkler Installation Guide
Viking Residential Sprinkler Installation Guide Trusted bove ll TM www.vikinggroupinc.com Sprinkler RES1 1. DESCRIPTION Viking residential automatic s are equipped with a fast response heat-sensitive operating
More informationTECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER 1.800.591.9360 TECHNICAL ASSISTANCE FAX: 1.626.855.4894
ACORN SAFETY P.O. BOX 3527 CITY OF INDUSTRY, CA 9744-0527 UNITED STATES OF AMERICA WWW.ACORNSAFETY.COM INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FREEZE RESISTANT WALL MOUNTED EMERGENCY EYEWASH
More informationBLADDER SURGE CONTROL SYSTEM
PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures
More informationBERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
More informationInstallation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK IN-LINE SERIES: 2-5 & 7 GALLON VERTICAL SERIES: 14-20-25-32-36-52-65-86-96-119 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON NO LEAD NO LEAD: The weighted average of
More informationSECTION 221413 FACILITY STORM DRAINAGE PIPING
SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationA. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.
SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationExtended Coverage Sprinklers
Extended Coverage Sprinklers Welcome ASPE Wally Barker Sprinkler Systems 101 MATERIALS OF CONSTRUCTION The components that make up a sprinkler head are: Frame or casting Deflector Fusible element or frangible
More informationFire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
More informationSECTION 33 12 19 FIRE HYDRANTS
SECTION 33 12 19 FIRE HYDRANTS PART 1: GENERAL 1.01 SCOPE A. Fire hydrants. B. Adjustment of fire hydrants and gate valves. 1.02 SUBMITTALS A. Conform to requirements of Section 01 33 00 - Submittals.
More informationEFSN Training i Module 1. 90 Minutes
Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler
More informationSECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
More informationINSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
More informationTECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2.
May 3, 2013 Foam 138a 1. DESCRIPTION Chemguard Water Powered Oscillating Monitors are designed to automatically discharge over a specific design area upon system activation. These are suitable for use
More informationKODAK VERSAMARK, INC.
KODAK VERSAMARK, INC. PREPARED BY : Gary Rowland 6/6/06 Kodak Versamark, Inc. 3000 Research Blvd. Dayton, Ohio 45420 APPROVED BY : Fire Suppression System Inspection, Testing and Maintenance SHEET 1 OF
More informationC. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
More informationInstallation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK Safety Instructions Installation Warranty IN-LINE SERIES: 2-5 & 7 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON VERTICAL SERIES: 14-20-32-36-52-86-96-119 GALLON KEEP
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationModel F156 Sprinkler Types. Model F156 Recessed Sprinkler Types. Model F142, F1XLH & F128 Sprinkler Types
Bulletin 013 Rev. M Models F1 Series Standard Response s Bulletin 013 Rev. M Model F156 Types Standard Upright Standard Pendent Conventional Vertical Sidewall Model F156 Recessed Types Pendent/F1/F2/FP
More informationNFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,
More informationTechnical Data. Installation
Technical Services: Tel: (800) 81-91 / Fax: (800) 791-5500 Model 51 (1) Riser Manifold 1-1/ thru 6 Inch (DN40 thru DN150) For NFPA 1 Sprinkler Systems General Description The Figure 51 (1) Riser Manifolds
More informationSTANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2
STANDARD for Plumbing, Heating, Hot Water, Cold Water & Electrical work undertaken by owners within the building known as Sussex Lodge London W2 & 16 Stanhope Terrace London W2 BPME Consulting Engineers
More informationWhat to Expect From the Examination. How to Study the Plumbing Codes
Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.
More informationMAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND
More informationASME/ANSI B16.1-1998 - Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B16.3-1998 - Malleable Iron Threaded Fittings ASME/ANSI B16.
ASME/ANSI B16.1-1998 - Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B16.3-1998 - Malleable Iron Threaded Fittings ASME/ANSI B16.4-1998 - Cast Iron Threaded Fittings ASME/ANSI B16.5-1996 - Pipe
More informationWhen Should Examination Preparation Begin?
Texas State Board of Plumbing Examiners Tradesman Plumber-Limited Licensee Examination Review Course The following Examination Review Course is designed to assist a registered Plumber s Apprentice in preparing
More informationCLEAR-DIVISIONS CENTERFOLD
CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in
More informationUniversity Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
More informationPOSITION STATEMENT THE ENGINEER AND THE ENGINEERING TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS. July 28, 2008
SOCIETY OF FIRE PROTECTION ENGINEERS (SFPE) NATIONAL SOCIETY OF PROFESSIONAL ENGINEERS (NSPE) NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET) POSITION STATEMENT THE ENGINEER AND
More informationFire Protection System Requirements Bulletin
Fire Protection System Requirements Bulletin FIRE PROTECTION DESIGN REQUIREMENTS FOR TENANTS (Revised 5-20-16) Simon requires all tenants to use a property specific pre-approved fire sprinkler contractor
More informationLS 2540 SEWER LATERALS AND INSPECTION TEES
LS 2540 SEWER LATERALS AND INSPECTION TEES A. Summary B. Submittals C. Site Information D. Sewer Pipe and Fittings E. Lateral Locations F. Lateral Installation G. Inspection Tee Installation H. Removal
More informationB. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationSteel Fire Sprinkler Pipe
Steel Fire Sprinkler Pipe Wheatland Tube Fire Sprinkler Products Wheatland Tube began producing steel fire sprinkler pipe in 1931, and today offers the most complete line of products in the industry. Engineers
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationChapter 7 Plumbing Connections
Chapter 7 Plumbing Connections 7-1 General All plumbing equipment and installations must be designed, constructed, and installed in accordance with this code and where not specific, to the applicable provisions
More informationNFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?
NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued
More information