E.1.12: GROUNDING SYSTEM
|
|
- Oswin Shelton
- 7 years ago
- Views:
Transcription
1 E1-GRD-1/5 E.1.12: GROUNDING SYSTEM B.1 Technical Characteristics and Requirements B.1.1 Grounding Design Criteria a. Fault duration, sec 1 b. Total fault level (line to ground), ka 20 c. Grounding connection Exothermic d. Grid conductor 125 mm 2 tin-annealed bare copper stranded conductor e. Bonding conductor (riser) 125 mm 2 tin-annealed copper stranded conductor with 3.3kV PVC insulation f. Burial depth of grid conductor below finished grade, m 0.50 (min.) g. Equipment and structure grounding conductor connected to different grid conductors Refer to of each equipment h. Ground mat design resistance 0.5 ohms max. i. Permissible temperature rise of grid copper Conductor, o C 300 j. Ground rod 1. Type Copperweld 2. Diameter, mm Not less than Length/Section, m 3 k. Resistivity of crushed rock, (wet). ohm 3000 l. Approximate Area of substation to be covered by the ground grid Refer to Bid Drawings m. Soil resistivity (for calculation), ohmmeter By Contractor 1 B.1.2 Overhead Ground Wire a. Type 7 No. 8 AWG aluminum-clad steel wire b. Ultimate strength, not less than, kg 7,277 1 Design of grounding system is responsibility of Contractor including measurement of the actual soil resistivity.
2 E1-GRD-2/5 c. Outside diameter, mm Manufacturer s std. d. Weight of zinc coating for galvanized and aluminized steel wire if specified in item a., not less than, g/m 2 e. Weight of aluminum coating for aluminum-clad steel wire, if specified in item a., not less than, g/m f. No. of Wires 7 g. Nominal diameter of wire, mm h. Cross-sectional area, mm i. Approx. weight, kg/m k. Modulus of elasticity in kg/m 2 16,169 (final) l. Coefficient of linear expansion, x10-6 / 0 C m. Elongation in 610 mm, not less than, % By Contractor n. Resistance at 20 C, max o. Recommended length per reel, if specified, m 1,500 N/A B.1.3 B.1.4 B.1.5 B Grounding Cable for Ground Mat a. Nominal sectional area, mm mm 2 b. Construction of stranded conductor (no./dia. in mm) 19/2.68 c. Outside diameter of cable, mm 13.4 approx. d. DC Resistance at 20 0 C ohms/km e. Standard weight, kg/m f. Tin-annealed (Yes, No) Yes Bonding Conductor (Riser) a. Size, mm mm 2 b. Conductor Metal Tin Annealed Copper Stranded Wire c. Conductor shape Circular stranded d. Insulated? Yes e. Type of insulation PVC Accessories for Overhead Ground Wire Suspension Ground Wire Materials a. Type N/A b. Applied conductor(specify type of conductor used) N/A
3 E1-GRD-3/5 c. Armor rods (Specify used or not used) N/A d. Ultimate breaking strength, kg N/a e. Slip Strength, kg N/A B Tension Wire Ground Materials B Tension Clamp a. Type of Clamp Bolted b. Applied conductor (Specify type of conductor used) Aluminum-clad steel wire, 7 No. 8 AWG c. Ultimate breaking strength, kg Not less than 95% UTS of OHGW d. Slip Strength, kg 8,300 B Jumper Clamp a. Ultimate breaking strength, kg 1,500 b. Slip Strength, kg 700 c. Type Wedge Pressure Clamp B Parallel Groove Clamp a. Material Aluminum Alloy b. Type Bolted Type c. Applied conductor Aluminum clad steel wire 7/8 AWG d. Slip strength, kg Not less than 15% UTS of the applied conductor B.1.6 Cable Reel Requirements for the Ground Cable and Overhead Ground Wire a. Materials (specify wood or steel) Wood b. Returnable (Yes, No) No c. If Yes, return within no. of months after installation N/A B.2 Test and Test Report(s) Requirements B.2.1 Test Requirements a. Type test and/or design test reports required for the grounding conductor and materials to be supplied (Specify Yes or No) ** Yes ** Contractor shall place in the filled-in data submitted or will submit as appropriate.
4 E1-GRD-4/5 b. Measurement of ground grid resistance after completion of grounding system to be measured before and after connection of the external ground wires of the transmission line to the substation ground system. (Specify Yes or No) Yes B.3 Auxiliary Power Supply B.3.1 No auxiliary power supply is required.. B.4 Spare Parts B.4.1 No particular spares and spare parts are required for the grounding system. The completeness of the grounding system with measurement (step and touch potential and required ground resistance) shall be the responsibility of the Contractor before its handling-over to the Employer. B.5 Tools B.5.1 All tools, i.e. compression tools for compressing the various type of grounding connections, tools required for the installation of wedge pressure clamp, etc. necessary for completing the works for the grounding system shall be the responsibility of the Contractor before its turn over to the Employer. B.6 Other Technical Requirements for the Grounding System B.6.1 The grounding is hereby referred to Paragraph of the Technical Specification whereby resistivity measurement including step and touch potential will be carried out and designed by the Contractor. In order to minimize the effect of seasonal variations of the earth resistance and the interruption of the overhead ground wire, the grounding system shall be designed for the worst condition, i.e. the overhead ground wire connection shall not be considered including that of the existing overhead ground wire connection. All works, labor and materials necessary for the complete, safety and efficient grounding system for the substations shall be included in the pay item for Grounding Materials for the Substation in the Bid Price Schedules for the substation. C. Other Technical Data to be Filled-in by Contractor C.1 The Contractor furnished data and information are included in this Specification to indicate the guaranteed performance data, predicted performance, interface requirements and construction features of all Contractor furnished equipment. The accuracy of such information and the compatibility of such information with overall performance requirements specified by Employer are the sole responsibility of the Contractor.
5 E1-GRD-5/5 C.2 Environmental Considerations C.2.1 In accordance with Paragraph of the General Technical Requirements and the Technical Data Sheets of Section E.1.1, the operating environment for this installation _(will, will not ) affect the life expectancy of the components used in this equipment. If there will be an effect, the following components will be affected as follows: Component Effect C.3 Other Technical Data for the Grounding Equipment and Materials a. Country of Origin 1. Overhead ground wire 2. Copper ground conductor 3. Ground rods 4. Shield wire accessoreis: a. Tension clamps b. Suspension clamp c. Parallel groove d. Lightning rods 5. Grounding connector materials b. Manufacturers 1. Overhead ground wire 2. Copper ground conductor 3. Ground rods 4. Shield wire accessories: a. Tension clamps b. Suspension clamp c. Parallel groove d. Lightning rods 5. Grounding connector materials c. Weight of heaviest crate to be shipped, kg d. Size of largest piece to be shipped (L x H x W), mm Contractor s Data
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
More informationTS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING
TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET
More informationSTREETLIGHT SYSTEM GROUNDING AND BONDING
Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial
More informationTECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR
TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR 1.1.0 SCOPE : This specification covers design, manufacture, testing at manufacture s works before
More informationNetwork Standard Advice No. 1420C 9/6/2011
Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides
More informationRAILWAY CATENARY SYSTEMS. Components and Systems for the Electrification of Railway Lines. ibemo
Connectors, Clamps, Compensating Devices, Insulators and Safety Equipment for Overhead Catenary Lines RAILWAY CATENARY SYSTEMS Components and Systems for the Electrification of Railway Lines. Welcome to
More informationNORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS
SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications
More informationGUY-GRIP Dead-end NOMENCLATURE GENERAL INFORMATION SAFETY CONSIDERATIONS 19-2. (440) 461-5200 inquiries@preformed.com www.preformed.
GUY-GRIP Dead-end NOMENCLATURE Cross-over Marks*: (A) Indicate starting point for application on smaller diameter fittings described on the reverse side of this page. (B) Indicates alternate starting point
More informationEARTHING SYSTEM CALCULATION
BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references
More informationFLEXIBLE COPPER & ALUMINIUM CONNECTIONS. Product Range 1 VGL - ALLIED CONNECTORS
Product Range ROUND STRANDED COPPER CABLE Electrolytic Copper / Oxygen Free Copper Conforms to DIN 46438 Standards Finish: Bare Copper / Tinned / Silver-plated ROUND BRAID / ROUND STRANDED CABLE WITH OVERALL
More informationHOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12
SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications
More informationSAES-P-111 28 January, 2004 Grounding. Electrical Systems Designs & Automation Standards Committee Members
Engineering Standard 28 January, 2004 Electrical Systems Designs & Automation Standards Committee Members Ishwait, Basel A., Chairman Al-Hamrani, Majed M., Vice Chairman Almadi, Soliman M. Badrani, Hamed
More informationHyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
More informationUGVCL/SP/591/11KV HT AB CABLE
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched
More informationAirdac CNE and SNE, 600/1000V, Polyethylene Sheath, SANS 1507, NRS 063 & NRS 017
Airdac CNE and SNE, 600/1000V, Polyethylene Sheath, SANS 1507, NRS 063 & NRS 017 Conductor: Hard Drawn Copper Conductor Class 2 Insulation: LV-XLPE Phase Color Code(SNE): Red, Black & Bare Copper Phase
More informationKNOW YOUR OPTIONS: 230 KV POWER CABLES
KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common
More informationCables, Cable Laying & Accessories Manual
Distribution Business Cables, Cable Laying & Accessories Manual Database ref: File Ref: Title Page & Revision Log For Cables & Access v4 - Nov 2003.doc Manual Name: Cables & Accessories Manual Version
More informationCommunication, Signal & Data Cables
Communication, Signal & Data Cables Used for indoor installation and interconnection of transmission, telephone, telegraph and electronic equipment as well as media equipments www.alfanar.com Communication
More informationSection 5 161 kv Power Cables
Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper
More informationPressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
More informationFault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
More informationKNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE
Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both
More informationELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS
Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document
More informationGulf Cable & Electrical Ind. Co.
CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC
More informationEARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
More informationSchedule-4(A3) Page 1 of 5. Specification No.: JPL/KWTL/A3 (Package-A3) To: Bidder's Name & Address
Specification : JPL/KWTL/A3 (Package-A3) Page 1 of 5 Tower Package (Package-A3) for 400 kv D/C (Quad Bundle) Karcham Wangtoo Abdullapur Line Part III associated with Karcham Wangtoo HEP Transmission System
More informationVIPERFLEX ELECTRIC CABLE
VIPERFLEX Flexible Low Voltage Electric Cable - 0.6/1kV (Rubber insulated) H07 RN-F & H07 BN-F Single Core 2-Core 2-Core and Earth 3-Core and Earth 4-Core and Earth Multi-Core and Earth H07 RCN-F & H07
More informationGUIDELINES HAS/PDC/DESIGN DIVISION TITLE
SECTION 270526 TELECOMMUNICATIONS GROUNDING & BONDING (-TAB) PART 1 GENERAL 1.01 SCOPE SUMMARY Designer shall provide a detailed narrative of the tasks to be performed under this specification section.
More informationCONFLEX ELECTRIC CABLE
CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard
More informationproduces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.
www.ppcinsulators.com The very Best. The very Best. That s what we deliver. ong od Insulators Only a company that develops, produces and delivers products worldwide can provide the optimal solution for
More informationIRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
More informationSUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS
SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS PRIMARY METER POLE ELECTRIC SYSTEM BULLETIN No. 753 JUNE 1993, 2 ND PRINTING APRIL 2002 (Supersedes issue dated March 1983 and incorporates Nov.
More informationNEGRP TEST SUMMARY. Joseph A. Lanzoni, November 2005
NEGRP TEST SUMMARY Joseph A. Lanzoni, November 2005 The National Electrical Grounding Research Project (NEGRP) was a project managed and sponsored by the National Fire Protection Association (NFPA) Research
More informationCHAIN-LINK FENCES BID SPECIFICATIONS DESCRIPTION
CHAIN-LINK FENCES BID SPECIFICATIONS DESCRIPTION 1 This item shall consist of furnishing and erecting Chain-Link fence in accordance with these specifications and the details shown on the plans and in
More informationSECTION 18370 SIGNAL WIRE AND CABLE
SECTION 18370 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for all cable and wire required for signal and signal power system wiring to wayside shelters, junction boxes, and factory
More informationFeatures. Picture. Specifications
Type: for level measurement Order No.: see Table 1 / Page 4 Features Picture Two wire system Piezoresistive measuring element Output signal 4-20 ma Conformity error ±0.5 % FS or Standard DIN measuring
More informationTri-Rated Flexible PVC Equipment Wire
Application: High temperature, flame retardant wire designed for use in the switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier
More informationBuilding Cables and Wires
Building Cables and Wires 4 Introduction alfanar is equipped with state-of-the-art manufacturing facilities such as latest machineries, instrumentation, quality control and testing laboratory, etc., for
More informationCable Accessories. for Extruded Dielectric Cable 69kV - 230kV Rated. Catalog Python13
Cable Accessories for Extruded Dielectric Cable 69kV - 230kV Rated Components used in cable systems 100% Tested Factory Molded For outdoor applications through 230kV For gas insulated substations and transformers
More information18 AWG thru 8 AWG Not greater than 100/30 100/30. 6 AWG thru 1/0 AWG Not greater than 200/60 100/30
Commercial Products COMMERCIAL PRODUCTS: RIGID AND IMC FITTINGS s Used to support cables in vertical raceways or risers. Relieves the strain that would be placed on terminations, the interior of panels,
More informationIEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED
More informationExclude all sales to foreign countries and all sales or transfers to other divisions or plants of your company. Survey Form 3.3.
(703) 81-3200 Electrical Connector Section - Underground Distribution Type Cable Connectors and Accessories Voting Classification (8-CC-IV) Domestic Net Sales Billed of Connectors for Residential and Medium
More informationGulf Cable & Electrical Ind. Co.
CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES Irrigation 1 Coaxial s for T.V/ Satellite Antenna etc 2 Data Transmission s - 4 pair 24 AWG 3 TELEPHONE CABLES Telephone cables CCP-LAP & CCP-LAP-SS
More informationSpecification SFTP CAT6 Network Cable 23AWG CU
Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)
More informationImplosive Connectors. for overhead transmission lines
Implosive Connectors Implosive Connectors for overhead transmission lines VP metall is situated in Raufoss Industrial Park, where you find the leading know-how in metallurgy and machining technology in
More informationArmor Rods. Armor Rods NOMENCLATURE GENERAL RECOMMENDATIONS
Armor s Transmission: Section 1 NOMENCLATURE Armor s Single Support and Double Support : Identified by S and D appearing in the length column on the catalog page. Should the maximum distance between tied
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationOutside Telephone Cable
Outside Telephone Cable Filled Core. Moisture Barrier. Description Soft copper wires insulated with high density polyethylene, foam skin or solid. Filled core, conformed by groups of pairs or by unit of
More informationHigh Voltage Systems. Today. The history of cables
High Voltage Cables High Voltage Systems Today Prysmian Cables and Systems B.V. is part of the Prysmian Group, a leading player in the industry of high-technology cables and systems for energy and telecommunications,
More informationCIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL*
Gexol CIR Crush and Impact Resistant Without External Armoring Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL n Available in Standard and Arctic Grade Jackets n Highly
More informationElectrical Code Regulation
Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county
More informationAssessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria
Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria Abstract Gabriel A. Adegboyega and Kehinde O. Odeyemi Department of Electrical and Electronic
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationGUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
More informationWhitepaper. Modular Substation Cable Termination Design. Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada
Whitepaper Modular Substation Cable Termination Design Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada Abstract The methods for cable penetrations into modular industrial substations are
More informationETHERLINE Ethernet Cable, Connectors & Tools
Ethernet Cable, ors & Tools 2 Pair 242 4 Pair 249 Industrial Ethernet ors & Tools 256 Ethernet Cable, ors & Tools ETHERNET CABLE, CONNECTORS & TOOLS Quick Select Chart 240 2 Pair 2 Pair: CAT.5/5e; Stationary
More informationEDS 02-0027 11KV TRIPLEX CABLE
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0027 ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE Network(s): EPN, LPN, SPN Summary:
More informationCorporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS
Corporate Profile MODERN ROYAL ELECTRIC Ideal Power Solution ROYAL MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS MAJOR STOCKIST >>> CATHODIC PROTECTION CABLES >>> LOW VOLTAGE CABLES >>> MEDIUM
More informationUnderground Service Requirements and Instructions
This packet includes all FKEC underground service requirements, instructions, procedures and drawings. If you are considering underground power service please review this document in its entirety (3 page
More informationRequirements for the Attachment of Communication Cable Facilities on PPL Poles
Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication
More informationSolar Power Solutions
Solar Power Solutions Wire and Cable Photovoltaic Connectors Combiner Boxes Fuses Grounding Power Connectors Physical Support Products Cable Ties Supply Chain Solutions Products. Technology. Services.
More informationPROFIBUS cable. PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications
Data Sheet 10/63-6.47-EN Rev. D PROFIBUS cable PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications PROFIBUS PA cables Non-Ex (Hazardous) applications Ex (Hazardous) applications
More informationNEW SERVICE INSTALLATION STEPS. Common Slow Downs. Other Necessary Steps
NEW SERVICE INSTALLATION STEPS Here is the step-by-step process required to fulfill your service installation request. Please take a few minutes to review the steps, become familiar with key milestones
More information800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
More informationMEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationTransmission Silicone Insulators Line Post 69 kv to 161 kv
K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 161 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines
More informationModeling of Transmission Lines
Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward
More informationPXL-250: Network Wiring
This document provides the network wiring requirements for a PXL-250 access control network. Network Requirements The PXL-250 uses a half-duplex, RS-485 communication bus. Per the RS-485 specification,
More informationCONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION
Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED
More informationCable Guide. Cables, Connectors & Tools for installation of quality networks. TRIAX - your ultimate connection
Cable Guide Cables, Connectors & Tools for installation of quality networks TRIAX - your ultimate connection A Selection of the best Triax TX Cable range optimised for digital reception Simplification
More informationChapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
More informationEast Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE
SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,
More information5.2. Overview. The better method to install solderless compression connectors on power cable
5.2 Overview The better method to install solderless compression connectors on power cable The Thomas & Betts method of installing compression connectors on power cables is designed to provide a high degree
More informationSECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such
More informationKonti Skan Replacement of Cable 1
Konti Skan Replacement of Cable 1 Presentation of the project 1 Agenda Background for the project Scope of Work for the cable delivery Eletrical Requirements Type Test Route description Time Schedule 2
More informationElectrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
More informationPower supply 142. Couplers 143. Data interfaces 144. Accessories 145
KNX system units The system components are KNX devices, which assume higher-level functions, independent of the application. They guarantee the necessary infrastructure in the building, ensuring a flawless
More informationSnow/Ice Melt Heating Cable System Gutters & Roof Drains Installation Manual Nexans TXLP/1 Series Resistance Cables
1. GENERAL INFORMATION Description Snow or ice dams that have built up on a roof can cause water damage to the interior of homes as well as damage to gutters and downspouts. This custom TXLP/1 single conductor
More informationCLAMPS CONNECTORS & EQUIPOTENTIAL RING
CLAMPS CONNECTORS & EQUIPOTENTIAL RING March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata
More informationDIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
More informationVideo Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
More informationAerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW
Complete One Stop Solution for OPGW Cable and Fittings for OPGW 53, Justice Chandra Madhav Road, Kolkata - 700020. India. Phone: 91-33-24748575 / 7565 Fax: 91-33-2476-1955 Email: sales@supremeco.com Website:
More informationAIRPORT SECURITY FENCING. A. American Society for Testing and Materials (ASTM):
SECTION 02832 AIRPORT SECURITY FENCING PART 1-GENERAL 1.1 SUMMARY A. Section includes: Construct airport security chain-link fence and gate at specified areas and conforming lines, grades, details indicated
More informationAutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
More informationGUARDRAIL POST STEEL
GUARDRAIL POST STEEL Guardrail posts meeting materials certification are evaluated and checked for: 1. Dimensional acceptance 2. Physical test results a. Chemical b. Physical 3. Galvanized or painted coating
More informationCable Supports. Requirements for Cable Supports in the National Electrical Code reads as follows:
QA1 General Information are used to support cables in vertical raceways or risers. Cable supports relieve the strain that would be placed on terminations, the interior of panels, or other devices to which
More informationActivity 2.3b Engineering Problem Solving Answer Key
Activity.3b Engineering roblem Solving Answer Key 1. A force of 00 lbs pushes against a rectangular plate that is 1 ft. by ft. Determine the lb lb pressure in and that the plate exerts on the ground due
More informationROLINE THE Difference
ROLINE THE Difference The products of the brand ROLINE are developed for professional users and differ in their quality substantially from comparable products in the IT environment. The high compatibility
More informationGALVANIC CATHODIC PROTECTION 1.0 CONTENTS. 1.1 Aluminium Anodes. 1.2 Zinc Anodes. 1.3 Magnesium Anodes SECTION
SECTION 1 GALVANIC CATHODIC PROTECTION 1.0 CONTENTS 1.1 Aluminium Anodes 1.1.1 Aluminium Tank Anodes 1.1.2 Aluminium Hull Anodes 1.1.3 Aluminium Platform / Jetty Anodes 1.2 Zinc Anodes 1.2.1 Zinc Tank
More informationFIELD AGING OF ETHYLENE-PROPYLENE-RUBBER (EPR) CABLES UNDER NORMAL AND ACCELERATED VOLTAGE STRESS AT MEMPHIS LIGHT, GAS AND WATER DIVISION
FIELD AGING OF ETHYLENE-PROPYLENE-RUBBER (EPR) CABLES UNDER NORMAL AND ACCELERATED VOLTAGE STRESS AT MEMPHIS LIGHT, GAS AND WATER DIVISION Philip E. Cox, PE Underground Electric Systems Engineer, Member
More informationSCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.
SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.
More informationThis presentation to be used in conjunction with:
1 This presentation to be used in conjunction with: Spec Sheets: SA-GRSP10, SA-GRSP09, SA-GRSP11 Samples in DC-GROUND-KIT 8/16/2012 2 Network Bonding and Grounding: TIA-607-B Generic Telecommunications
More informationPROFIBUS cable. for PROFIBUS-PA and -DP 10/63-6.46 EN
for PROFIBUS-PA and -DP 10/63-6.46 EN CPN 080/CPE 080-Ex PROFIBUS-PA basis cable AWG 18, 0.88 mm 2 Use For fixed installation indoor and outdoor, on racks and in conduits. Application Fieldbus cable for
More informationLEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m
FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2
More informationSTABILOY BRAND FeeDeR SOLuTIONS
STABILOY BRAND Feeder Solutions DATA CENTER Introduction General Cable understands that data centers depend heavily on a steady, reliable and scalable source of power. That is why our STABILOY Brand aluminum
More informationElectric Utility Application and Reference Guide
Electric Utility Application and Reference Guide Facility Electrical Protection Power Generation Substation Earthing/Grounding Lightning Protection Power Transmission and Distribution Accessories for Electrical
More informationcourtesy of Hunter Industries Inc. irrigation wiring guide
courtesy of Hunter Industries Inc. courtesy of Rain Bird Corporation courtesy of Hunter Industries Inc. The irrigation wiring guide C a n a d i a n E d i t i o n Why? Because you need an irrigation wire
More informationRE-ENTERABLE SPLICE CLOSURE KITS. (For Air Core None Pressurized Cable)
Triple T Broadband Public Co., Ltd. Outside Plant Standard Sector Specification No. OES-001-027-04 Issued: RE-ENTERABLE SPLICE CLOSURE KITS (For Air Core None Pressurized Cable) 1. SCOPE 1.1. This specification
More informationCABLE SPECIFICATION CAN CAB RJ45-SUBD9
CABLE SPECIFICATION All technical information contained in this document is the exclusive property of STI and may neither be used nor disclosed without its prior written consent. AAV 33801 1/8 Connector
More informationSTABILOY BRAND FeeDeR SOLuTIONS
STABILOY BRAND Feeder Solutions DATA CENTER Introduction General Cable understands that data centers depend heavily on a steady, reliable and scalable source of power. That is why our STABILOY Brand aluminum
More information