Combination Starters and Distribution Units

Size: px
Start display at page:

Download "Combination Starters and Distribution Units"

Transcription

1 Combination Starters and Distribution Units Several different kinds of combination starters and distribution units can be put into a MCC. Typical combination starters and units are listed below with their standard abbreviations: Figure 1-6 High Density Unit Figure 2 - Standard Unit FVNR Full Voltage Non Reversing... D2-D5 DFVNR Dual Full Voltage Non-Reversing... D6-D7 FVC Full Voltage Contactor... D8-D9 FVR Full Voltage Reversing... D10-D11 2S1W Two Speed One Winding... D12-D13 2S2W Two Speed Two Winding... D14-D15 PW Part Winding... D16-D17 RVAT Reduced Voltage Auto-Transformer... D18-D19 YDC Reducing Voltage Wye Delta Closed Transition... D20-D21 YDO Reducing Voltage Wye Delta Open Transition... D22-D23 FCB Feeder Circuit Breaker... D24 DFCB Dual Feeder Circuit Breaker... D24 FDS FeederDisconnect Switch... D24 DFDS Dual Feeder Disconnect Switch... D24 XFMR Transformer (lighting)... D25 PNLBD Panel Board... D26 RVSS Reduced Voltage Soft Start... D26 VFD Variable Frequency Drive... D26 HFVNR High Density Full Voltage Non-Reversing... D26 D1

2 Combination Starter Ratings and Dimensions FVNR - Full Voltage Non-Reversing Unit With Fusible Switch or Circuit Breaker Standard Features Plug-in unit, Sizes 0-5. Circuit Breaker Sizes 0-5. Fusible Switch Sizes 0-4. Molded case switch, Sizes 5 and 6. Fuse clips for Class R fuses. Electrical starter seal-in contact for 3-wire control: Size 0-1, NO only. Sizes 2-4, SPST. Size 5-6, SPDT. Control circuit terminals: Type A - Connect to component terminal. Type Bd, Bt, C - Unit stationary terminal blocks. Load power terminals: Type A, Bd. - Connect to starter terminals. Type Bt, C. - Sizes 0-3, stationary blocks. Sizes 4-6, connect to starter terminals. Starters: Innova/Plus, Sizes 0-4 Bimetallic Ambient Compensated Overload Typical Schematic D2

3 Available Features - Standard Unit Size Control power transformer with fused secondary and Surge suppressor. Dual fused primary. Solid state overloads. Pull-apart control terminals. Pull-apart load terminals, Sizes 0-2. seal-in contact. Thermal magnetic circuit breaker. 4 pilot devices mounted on unit device panel. Control relay. Surge Suppressor. ETM. Handle Interlocks operate with handle. Extra starter auxillary contacts in addition to NO seal-in contact. Class J Fuse Clips. Refer to tables below for maximum size control power transformers, relays, and timer addition. Communicating devices (ASi, SIMICODE-PRO) Auxiliary Contacts Starter Extra Contacts Size Per Starter Type SPST NO or NC SPST NO or NC SPDT NO & NC FVNR with ITE MCP Type Breaker: Disconnect Ratings and Space Requirements Standard Maximum MCP Unit Control Control Maximum Horsepower Starter Frame Unit Space Transformer Transformer 200V 230V V Size Size Height Factor VA VA Relay Timer * 1* 7 1/2 7 1/ * 1* * 1* / * 1* ** / FVNR with Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Standard Maximum Fuse Unit Control Control Maximum Horsepower Starter Switch Clip Unit Space Transformer Transformer 200V 230V V Size Size Size Height Factor VA VA Relay Timer * 1* 7 1/2 7 1/ * 1* * 1* * 1* / * Either/or but not both ** Oversized for additional equipment 1 Fixed mounted unit 2 Fixed mounted unit - space behind not available 3 Starter supplied with interposing relay(s) 200, 230V applications D3

4 Combination Starter Ratings and Dimensions FVNR-High Density Full Voltage Non- Reversing Unit With Circuit Breaker Standard Features Plug-in unit, Sizes 0-1. Circuit Breakers Sizes 0-1. Starters: Innova/Plus, Sizes 0-1, ESP100 Overload Electrical starter seal-in contact for 3-wire control: Size 0-1, NO only. Control circuit terminals: Unit stationary terminal blocks. Typical Schematic D4

5 Available Features - Standard Unit Size Control power transformer with fused secondary and dual fused primary. Thermal magnetic circuit breaker. 2 pilot devices mounted on unit device panel. Surge suppressor. Internal Circuit Breaker Interlock. Extra starter auxiliary contacts in addition to NO seal-in contact. Clips. Refer to tables below for maximum size control power transformer, relays, and timer addition. Communicating devices (ASi, SIMOCODE-DP), (AS-i or SIMOCODE not available on high density units with control power transformer. Auxiliary Contacts Starter Extra Contacts Size Per Starter Type SPSTNO ornc FVNR with MCP Type Breaker: Disconnect Ratings and Space Requirements Standard Maximum MCP Unit Control Control Maximum Horsepower Starter Frame Unit Space Transformer Transformer 200V 230V V Size Size Height Factor VA VA Relay Timer / /2 7 1/ / D5

6 Combination Starter Ratings and Dimensions Dual FVNR-Full Voltage Non-Reversing Unit With Fusible Switch or Circuit Breaker Standard Features Plug-in unit Size 0 and 1 MCP or thermal magnetic circuit breaker Innova/Plus Starters - Bimetallic OL Relay Control circuit terminals: Type A - Connect to component terminal. Type Bd, Bt, C - Unit stationary terminal blocks Load power terminals: Type A, Bd, Bt, C Electrical starter seal-in contact for 3-wire control: Size 0-1, NO only. Qualifications Extra capacity control power transformer not available. Current limiter attachment not available. No room for relays or timers. Maximum of four pilot devices per dual unit. Maximum of 12 control and 3 power terminal points per starter Circuit breaker type disconnect only. Fusible disconnect not available. TYPICAL SCHEMATIC D6

7 Available Features - Standard Unit Size Ambient Compensated Bimetal Overloads. Standard capacity control power transformer with fused primary and secondary. Solid state overload. Pull-apart control terminals. Pull-apart load terminals. Thermal magnetic circuit breaker. Barrier between starters. Surge suppressors. Handle interlocks operate with handle. Extra starter auxiliary contacts in addition to NO seal-in contact. Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Starter Extra Contacts Size Per Starter Type SPST NO or NC Dual FVNR with MCP Type Breaker: Disconnect Ratings and Space Requirements Standard Maximum MCP Unit Control Control Maximum Horsepower Starter Frame Unit Space Transformer Transformer 200V 230V V Size Size Height Factor VA VA Relay Timer / /2 7 1/ / D7

8 Combination Contactor Ratings and Dimensions With Fusible Switch or Circuit Breaker Standard Features Thermal magnetic circuit breaker. Plug-in unit, Sizes 0-5. Fusible Switch Sizes 0-4. Molded case switch, Sizes 5 and 6. Fuse clips for Class R fuses. Contactor: Innova/Plus, Sizes 0-4 Electrical starter seal-in contact for 3-wire control: Size 0-1, NO only. Size 2-4, SPST. Size 5-6, SPDT. Control circuit terminals: Type A - Connect to component terminals. Type Bd, Bt, C - Unit stationary terminal blocks. Load power terminals: Type A, Bd - Connect to starter terminals. Type Bt, C - Sizes 0-3, stationary blocks. - Sizes 4-6, connect to starter terminals. TYPICAL SCHEMATIC D8

9 Available Features - Standard Unit Size Control power transformer with fused secondary, and dual fused primary. Pull-apart control terminals. Pull-apart load terminals, Sizes pilot devices mounted on unit device panel. Control relay. Surge suppressor. ETM Handle interlocks operate with handle. Extra starter auxillary contacts in addition to NO seal-in contact. Class J fuse clips. Refer to tables for maximum size control power transformer, relays, and timer addition. Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Starter Extra Contacts Size Per Starter Type SPST NO or NC SPST NO or NC SPDT NO & NC Full Voltage Contactor with Circuit Breaker Disconnect Ratings and Space Requirements Circuit Standard Maximum Maximum KW Breaker Unit Control Control Resistance Heating Leads Contactor Frame Unit Space Transformer Transformer 200V 230V 460V 575V Size Size Height Factor VA VA Relay Timer * 1* * 1* * 1* / * 1* ** / Full Voltage Contactor with Fusible Switch (refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Standard Maximum Fuse Unit Control Control Maximum Horsepower Contactor Switch Clip Unit Space Transformer Transformer 200V 230V 460V 575V Size Size Size Height Factor VA VA Relay Timer * 1* * 1* * 1* * 1* * 1* * Either/or but not both ** Oversized for additional equipment 1 Fixed mounted unit 2 Fixed mounted unit - Space behind not available 3 Starter supplied with interposing relay(s) 200, 230V applications D9

10 Combination Starter Ratings and Dimensions FVR-Full Voltage Reversing Unit With Fusible Switch or Circuit Breaker Standard Features Plug-in unit, Sizes 0-4 with HMCP, Sizes 0-3 with fusible switch. Circuit Breakers Sizes 0-5. Fusible switches, Sizes 0-4. Molded case switches Sizes 5-6. Fuse clips for Class R fuses. Electrical starter seal-in contact for 3-wire control: Size 0-1, NO only. Size 2-4, SPST. Size 5-6, SPDT. NC reversing electrical interlock per contactor. Mechanical interlock on contactors. Bimetallic Ambient Compensated Overload Starter: Innova/Plus, Sizes 0-1 with vertical mechanical interlock. Innova/Plus, Sizes 2-4 with horizontal mechanical interlock. Bimetallic OL Control circuit terminals: Type A-Connect to component terminal. Type Bd, Bt, C-Unit stationary terminal blocks. Load power terminals: Type A, Bd-Connect to starter terminals. Type Bt, C-Sizes 0-3, stationary blocks. Sizes 4-6, connect to starter terminals. Typical Schematic D10

11 Available Features-Standard Unit Size Control power transformer with fused secondary and dual fused primary. Solid state overload. Pull-apart control terminals. Pull-apart load terminals, Sizes 0-2. Thermal magnetic circuit breakers. 4-pilot devices mounted on unit device panel. Control relay (2). Surge suppressors. ETM. Handle interlocks operate with handle. Extra starter auxiliary contacts in addition to NO maintaining seal-in contact and NC electrical interlock. Class J fuse clips. Refer to tables below for maximum size control power tranformer, relays, and timer additions. Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Starter Extra Contacts Size Per Starter Type SPST NO or NC SPST NO or NC SPDT NO & NC FVR with MCP Type Breaker: Disconnect Ratings and Space Requirements Standard Maximum MCP Unit Control Control Maximum Horsepower Starter Frame Unit Space Transformer Transformer 200V 230V V Size Size Height Factor VA VA Relay Timer / * 1* 7 1/2 7 1/ / * 1* / / FVR with Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Standard Maximum Fuse Unit Control Control Maximum Horsepower Starter Switch Clip Unit Space Transformer Transformer 200V 230V V Size Size Size Height Factor VA VA Relay Timer / * 1 * 7 1/2 7 1/ / * 1 * / x * Either/or but not both a Fixed mounted unit Fixed mounted unit-space behind not available Starter supplied with interposing relay(s) V applications D11

12 Combination Starter Ratings and Dimensions 2S1W - Two Speed - One Winding Reconnectable Consequent Pole Unit with Fusible Switch or Circuit Breaker Standard Features Plug-in unit, Sizes 0-4 with MCP, Sizes 0-3 with fusible switch. Circuit Breaker, Sizes 0-5. Fusible switch Sizes 0-4. Molded case switch size 5. Fuse clips for Class R fuses. Electrical starter interlocks-interlock supplied as required for selective control and to electrically interlock starters. seal-in contact. Size 0-1, NO only. Sizes 2-4, SPST. Size 5 SPDT. Mechanically interlocked starters. Innova/Plus, Sizes 0-4. Bimetallic Ambient Compensated Overload 5-pole starter and 3-pole starter horizontally interlocked. Size 2 vertical reversing starter and separate starter. Size 3-4 horizontal reversing starter and separate starter. Control circuit terminals: Type A-Connect to component terminal. Type Bd, Bt, C-Unit stationary terminal blocks. Load power terminals: Type A, Bd-Connect to starter terminals. Type Bt, C-Sizes 0-3, stationary blocks. Size 4 and larger, connect to starter terminals. Typical Schematic D12

13 Available Features-Standard Unit Size Solid state overload. Control power transformer with fused secondary and dual fused primary. Pull-apart control terminals. Pull-apart load terminals Size 0-2. Thermal magnetic circuit breakers. 4-pilot devices mounted on unit device panel. Handle interlock operates with handle. Extra starter auxiliary contacts vary per size of starter. Relays will be supplied if number of available contacts is exceeded. Compelling control starts on low speed only. Push Stop before transferring from higher to lower speed. ETM. Progressive control. Automatic starting on low speed and automatic transfer to fast; stops before transferring from fast to slow. Automatic deceleration. Class J fuse clips. Refer to tables below for maximum size control power transformer, relays, and timer additions. Control relay (1). Surge suppressors. Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Extra Contact Extra Contact Starter Constant or Variable Torque Constant Horsepower Size High/Low High/Low Type 0-1 0/2 2/0 SPSTNO ornc 2-4 4/2 2/4 SPSTNO ornc 5 4/2 2/4 SPDT NO & NC 2S1W with MCP Type Breaker: Disconnect Ratings and Space Requirements Standard Maximum Constant or Variable Constant MCP Unit Control Control Torque Horsepower Starter Frame Unit Space Transformer Transformer 200V 230V V 200V 230V V Size Size Height Factor VA VA Relay Timer /2 7 1/ / / / x S1W with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Standard Maximum Constant orvariable Constant Fuse Unit Control Control Torque Horsepower Starter Switch Clip Unit Space Transformer Transformer 200V 230V V 200V 230V V Size Size Size Height Factor VA VA Relay Timer /2 7 1/ / / x Fixed mounted unit 3 Starter supplied with interposing relay(s) 200 & 230V applications D13

14 Combination Starter Ratings and Dimensions 2S2W - Two Speed - Two Winding Unit With Fusible Switch or Circuit Breaker Standard Features Plug-in unit, Sizes 0-4 with circuit breakers, Sizes 0-3 with fusible switch. Circuit Breaker, Sizes 0-5. Fusible switch Sizes 0-4. Molded case switches, Sizes 5. Fuse clips for Class R fuses. Electrical starter interlocks - supplied as required for selective control and to electrically interlock starters. Seal-in contact: Sizes 0-1, NO only. Sizes 2-4, SPST. Size 5, SPDT. Bimetallic Ambient Compensated Overload Mechanical interlock on starters. Starters: Innova/Plus, Sizes 0-4. Sizes 0-4: Innova/Plus consisting of 2 starters horizontally interlocked. Sizes 5: 2 starters with vertical mechanical interlock. Control circuit terminals: Type A - Connect to component terminal. Type Bd, Bt, C - Unit stationary - terminal blocks. Load power terminals: Type A, Bd - Connect to starter terminals. Type Bt, C - Sizes 0-3, stationary blocks. Size 4 and larger, connect to starter terminals. Typical Schematic D14

15 Available Features - Standard Unit Size Solid state overload. Control power transformer with fused secondary, and dual fused primary. Pull-apart control terminals. Pull-apart load terminals. Sizes 0-2. Thermal magnetic circuit breakers. 4 pilot devices mounted on unit device panel. Handle interlock operates with handle. Extra starter auxiliary contacts vary per size of starter. Relays will be supplied if number of available auxiliary contacts are exceeded. Compelling control starts on low speed only. Push Stop before transferring from high to low speed. Progressive control. Automatic starting on low speed and automatic transfer to fast. Stops before transferring from fast to slow. Automatic deceleration. Class J fuse clips. Refer to tables below for maximum size control power transformer, relays, and timer additions. Control relay (1). Surge suppressors. ETM. Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Starter Extra Contacts Size Hi/Low Type 0-1 3/3 SPST NO or NC 2-4 2/2 SPST NO or NC 5 2/2 SPDT NO & NC 2S2W with MCP Type Breaker: Disconnect Ratings and Space Requirements Standard Maximum Constant or Variable MCP Unit Control Control Torque Constant Horsepower Starter Frame Unit Space Transformer Transformer 200V 230V V 200V 230V V Size Size Height Factor VA VA Relay Timer /2 7 1/ / / / / x S2W with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Standard Maximum Constant or Variable Fuse Unit Control Control Torque Constant Horsepower Starter Switch Clip Unit Space Transf. Transf. 200V 230V V 200V 230V V Size Size Size Height Factor VA VA Relay 55BA /2 7 1/ / / / x Fixed mounted unit 3 Starter supplied with interposing relay(s) 200 & 230V applications D15

16 Combination Starter Ratings And Dimensions PW - Full Voltage Part Winding Unit with Fusible Switch or Circuit Breaker Standard Features Plug-in units. Sizes 0-4, circuit breaker. Sizes 0-4, fusible switch. Thermal magnetic breaker, Sizes 0-5. Fusible switches. Sizes 0-3. Molded case switches, Sizes 4-5.Molded case switch, Size 4, on 230V.Fuse clips for Class R fuses. Starters: Innova/Plus: 0-4. Bimetallic Ambient Compensated Overload Electrical starter interlocks-no interlock supplied on 1M for 3 wire control. Sizes 1, NO only. Sizes 2-4, SPST. Sizes 5, SPDT. Control circuit terminals: Type A - Connect to component terminal. Type Bd, Bt, C - Unit stationary terminal blocks. Load power terminals: Type A, Bd - Connect to starter terminals. Type Bt, C - Sizes 0-3, stationary blocks. Sizes 4-5 connect to starter. Typical Schematic D16

17 Available Features-Standard Unit Size Control power transformer-fused secondary and dual fused primary. Pull-apart control terminals. Solid state overload. Pull-apart load terminals, Sizes pilot devices mounted on unit device panel. Handle interlock operates with handle. Control relay. Surge suppressors. Extra starter auxiliary contacts in addition to NO seal-in contact. Class J fuse clips. Refer to tables below for maximum size control power transformer, relays, and timer additions. Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Starter Extra Contacts Size Per Starter Type SPST NO or NC SPST NO or NC 5 3 SPST NO or NC PW with Circuit Breaker: Disconnect Ratings and Space Requirements Circuit Standard Maximum Breaker Unit Control Control Maximum Horsepower Starter Frame Unit Space Transformer Transformer Timer 200V 230V V Size Size Height Factor VA VA Relay 55BA / PW with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Standard Maximum Fuse Unit Control Control Maximum Horsepower Starter Switch Clip Unit Space Transformer Transformer Timer 200V 230V V Size Size Size Height Factor VA VA Relay 55BA / x Fixed mounted unit 3 Starter supplied with interposing relay(s) 200 & 230V applications D17

18 Combination Starter Ratings and Dimensions RVAT - Reduced Voltage Auto-Transformer Unit with Fusible Switch or Circuit Breaker Standard Features Fixed mounted units, Sizes 2-6. Fusible switch Sizes 0-4. Molded case switches, Sizes 5-6. Fuse clips sized for time delay fuses. Class R. Starter: Innova/Plus, Sizes 2-4. Starter (R) and contactor (1S) with mechanical interlock. 3 pole contactor (2S). Bimetallic Ambient Compensated Overloads. Auto Transformer NEMA medium duty 3 coil: 50%, 65%, 80% taps. Class F insulation (minimum). Mounted across bottom of structure. Electrical starter interlocks-no on (2S); (R) for 3 wire control. Sizes 2-4, SPST. Sizes 5-6, SPDT. Control circuit terminals: Type A - Connect to component terminal. Type Bd, Bt, C - Unit stationary terminal blocks. Load power terminals. Type A, Bd - connect to starter terminals. Type Bt, C - Sizes 0-3, stationary blocks. Sizes 4-6, connect to starter terminals. Typical Schematic D18

19 Available Features-Standard Unit Size Control power transformer-fused secondary and dual fused primary. Pull-apart control terminal. Pull-apart load terminals, Sizes 0-2. Solid state overload. Thermal-magnetic circuit breakers. Extra starter auxiliary contacts, 2S or R (relay used). Surge suppressors. Class J fuse clips. Refer to tables below for maximum size control power transformer, relays, and timer additions. Communicating devices (ASi, SIMOCODE-PRO) RVAT with MCP Type Breaker: Disconnect Ratings and Space Requirements Standard Maximum MCP Unit Control Control Maximum Horsepower Starter Frame Unit Space Transformer Transformer 200V 230V V Size Size Height Factor VA VA Relay Timer / / / X X X RVAT with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Standard Maximum Fuse Unit Control Control Maximum Horsepower Starter Switch Clip Unit Space Transformer Transformer 200V 230V V Size Size Size Height Factor VA VA Relay Timer / x x x Fixed mounted unit 2 Fixed mounted unit - space behind not available 3 Starter supplied with interposing relay(s) 4 Requires 20 deep structure 200 & 230V applications D19

20 Combination Starter Ratings And Dimensions YDC - Reduced Voltage Wye Delta Closed Transition Standard Features Plug-in units. Sizes 0-6, circuit breaker. Sizes 0-5, fusible switch. Fusible switches. Sizes 0-3. Molded case switches, Sizes 4-5. Starters: Innova/Plus: 0-4. Bimetallic Ambient Compensated Overloads Control circuit terminals: Type A-Connect to component terminal. Type Bd, Bt, C-Unit stationary terminal blocks. Electrical starter interlocks-no interlock For 3 wire control. Sizes 2-4, SPST. Sizes 5-6, SPDT. Load power terminals: Type A, Bd - Connect to starter terminals. Type Bt, C - Sizes 0-3, stationary blocks. Sizes 4-6 connect to starter. TYPICAL SCHEMATIC D20

21 Available Features-Standard Unit Size Control power transformer-fused secondary and dual fused primary. Pull-apart control terminals. Solid state overload. Phase Failure Relay Pull-apart load terminals, SIzes pilot devices mounted on unit device panel. Handle interlock operates with handle. Control relay. Surge suppressors. Extra starter auxiliary contacts in addition to NO seal-in contact. Class J fuse clips. Refer to tables below for maximum size control power transformer, relays, and timer additions. Auxiliary Contacts Starter Extra Contacts Size Per Starter Type SPST NO or NC SPST NO or NC YDC with Circuit Breaker: Disconnect Ratings and Space Requirements Circuit Standard Maximum Breaker Unit Control Control Maximum Horsepower Starter Frame Unit Space Transformer Transformer 200V 230V V Size Size Height Factor VA VA Relay Timer / / x x x YDC with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Standard Maximum Fuse Unit Control Control Maximum Horsepower Starter Switch Clip Unit Space Transformer Transformer 200V 230V V Size Size Size Height Factor VA VA Relay Timer x Fixed mounted unit 2 Starter supplied with interposing relay(s) D21

22 Combination Starter Ratings And Dimensions YDO - Reduced Voltage Wye Delta Open Transition Standard Features Sizes 0-6, circuit breaker. Sizes 0-5, fusible switch. Fusible switches. Sizes 0-3. Molded case switches, Sizes 4-5. Starters: Innova/Plus: 0-4. Bimetal Ambient Compensated Overloads TYPICAL SCHEMATIC Control circuit terminals: Type A-Connect to component terminal. Type Bd, Bt, C-Unit stationary terminal blocks. Electrical starter interlocks-no interlock For 3 wire control. Sizes 2-4, SPST. Sizes 5-6, SPDT. Load power terminals: Type A, Bd - Connect to starter terminals. Type Bt, C - Sizes 0-3, stationary blocks. Sizes 4-6 connect to starter. D22

23 Available Features-Standard Unit Size Control power transformer-fused secondary and dual fused primary. Pull-apart control terminals. Solid state overload. Phase Failure Relay Pull-apart load terminals, SIzes pilot devices mounted on unit device panel. Handle interlock operates with handle. Control relay Surge suppressors. Extra starter auxiliary contacts in addition to NO seal-in contact. Class J fuse clips. Refer to tables below for maximum size control power transformer, relays, and timer additions. Auxiliary Contacts Starter Extra Contacts Size Per Starter Type SPSTNO ornc SPSTNO ornc YDO with Circuit Breaker: Disconnect Ratings and Space Requirements Circuit Standard Maximum Breaker Unit Control Control Maximum Horsepower Starter Frame Unit Space Transformer Transformer 200V 230V V Size Size Height Factor VA VA Relay Timer / / x x x YDO with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Standard Maximum Fuse Unit Control Control Maximum Horsepower Starter Switch Clip Unit Space Transformer Transformer 200V 230V V Size Size Size Height Factor VA VA Relay Timer x Fixed mounted unit 3 Starter supplied with interposing relay(s) D23

24 FeederTap Circuit Breakers These breakers are thermal magnetic type and feed lighting or power circuits. 125A and 250A frame breakers are mounted in plug-in units. Higher rated breakers are fixed mounted. (See chart on page G6 for short circuit ratings and type of circuit breakers available.) FeederTap Fusible Switches Fusible feeder switches, 30A through 200A, are mounted in plug-in units. Switches above 200A are fixed mounted and consist of molded-case switches and separate fuse blocks. Dual-mounted fusible switches are available, 30A and 60A, with clips of same rating. Fuse clips are Class RK dimensions for A. Dual mounted 125A frame breakers may be mounted in a 12 plug-in unit with a common door. Circuit breakers Fusible disconnect switch FeederTap Circuit Breakers and Fusible Switches: Disconnect Ratings and Space Requirements Unit Fuse Unit Max. Height Switch Clip Height Frame Trip Rating Size Size Amps 1CB 2CB (A.) Amps 1 Sw. 2 SW Fixed mounted unit. 2 Requires load terminal blocks. 3 Stab opening at top of unit not available in rear. D24

25 Distribution Units A Motor Control Center is principally intended to house multiple combination starters for the control of electrical motors. It is often convenient to include a limited number of power distribution units. These units consist of the following: Transformers Feeder tap circuit breakers Feeder tap fusible disconnects Lighting panels Transformer Protection - Lighting and Master Control Primary protection is required, per NEC sizes as follows: (lp = transformer primary currents.) 125% lp for lp greater than 9A. 167% lp for lp less than 9A. 300% lp for lp less than 2A. In addition to primary protection, secondary protection must be supplied if the transformer secondary is 3 or 4 wire (dual voltage). Secondary protection is not required if the transformer is 2 wire (single voltage secondary). Description of Standard Transformers Single Phase Transformers 1KVA thru 2KVA 240/480V Primary 120V Secondary 50/60 Hz Transformer Ratings and Space Requirements Single Phase Transformers: 1KVA and 2KVA sizes with 120V secondary can be mountedin a single 12 plug-in unit with a primary circuit breaker or fusible disconnect. 3KVA and larger sizes are mounted in bottom of section. 20KVA or larger sizes require 20 deep sections. 3KVA thru 5KVA 240/480V Primary 240/120V Secondary 50/60 Hz 7 1/2, 10, 15, 25, 30KVA 240/480V Primary with (2) 2 1/2% FCAN and (4) 2 1/2% FCBM Taps 240/120V Secondary, 60 Hz 220C insulation, 150C rise Three Phase Transformer 6 to 15 KVA 480V Primary with (2) 5% FCBN taps 208/120V Y - connected Secondary KVA 480V Primary with (2) 2 1/2% FCAN and (40) 2 1/2% FCBN taps 208/120V Y - connected Secondary 220C insulation, 150C rise 3 Phase Transformers: All three phase transformers require 20 deep sections, must be mounted in the bottom, and will not have vertical bus in that compartment. Refer to page B22 for conduit entry. All 3KVA and larger single phase and all three phase transformers are mounted approximately 5 inches above the structure base channel sills. Single Phase Transformer 480/240V - 120/240V Secondary 60 Hz Transformer Primary Breaker KVA Unit Size Trip Amps Rating Height * 240V 480V Note: No vertical bus behind or below. 5.0KVA and larger. 20KVA or larger requires 20 deep structures. * Does not include 6 bottom wireway space. Three Phase Transformer 480V Primary - 208/120V Secondary 60 Hz Primary Breaker KVA Unit Size Trip Amps Rating Height * 480V Note: All three phase transformers require 20 deep structures and 20 wide doors. D25

26 Panel Board Panel Boards Full size bolt-on breakers - 1, 2, and 3 pole - 15 to 100A. 1 phase 3 wire - 120/240 volt or 3 phase 4 wire - 120/208 volt 3 phase 4 wire - 380/220 volt 3 phase 4 wire - 480/277 volt Aluminum bus and 225A depending on number of circuits. Main lug only and 225A Main circuit breaker and 225A - 12 to 42 circuits. Disconnect Ratings and Space Requirements: Circuit Breaker Panel Boards Main Bus Unit Number Breaker Rating Height Circuits Type (Amps) (Amps) (Inches) 18 1Ø-3W Ø-3W Ø-3W Ø-4W Ø-4W Ø-4W Ø-3W Ø-3W Ø-3W Ø-4W Ø-4W Ø-4W ,000A 240V short circuit rating. UL listed. D26

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

MCC Ratings. Voltage Rating

MCC Ratings. Voltage Rating MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control

More information

Catalog January. Heavy industrial power applications Motor contactors and starters

Catalog January. Heavy industrial power applications Motor contactors and starters Catalog January Heavy industrial power applications Motor contactors and starters 2006 General contents 0 Heavy Industrial Power Applications Motor Contactors and Starters 1 Contactors and Starters, Type

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

Glossary of Common Crane Ter ms:

Glossary of Common Crane Ter ms: Glossary of Common Crane Ter ms: 26 Adjustable brakes: Electro-mechanical device to control crane deceleration. Bridge beam: Traveling beam connected to end trucks - supports trolley hoist and load. Bumpers:

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

Circuit Breakers. Next Generation of Protection Capabilities

Circuit Breakers. Next Generation of Protection Capabilities Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many

More information

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80 Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com Switches & Pilot Lights Display Lights NRC series circuit breakers offer circuit protection which is far superior to using fuses in applications containing relay circuits, motor circuits, heater circuits,

More information

Distribution Dry Type Transformers

Distribution Dry Type Transformers 8 TRASFORMERS Distribution Dry Type Transformers Table (Contact Sales office for List Price) (commonly used) 1a. 115 C Rise F 1b. 80 C Rise B 4. Wall Brackets1 W 6. Low noise XdB below std. LX Type bg

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

Comparison of NEMA and IEC schematic diagrams

Comparison of NEMA and IEC schematic diagrams Cross-Reference MZ081001EN Comparison of NEMA and IEC schematic diagrams General With the increasing emphasis on globalization, many industries are now looking to all parts of the world to produce, market,

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose

More information

D-Line Contactors, Overload Relays and Accessories

D-Line Contactors, Overload Relays and Accessories D-Line Contactors, Overload Relays and Accessories Class 850 CONTENTS Description......................................................Page General Information...............................................

More information

Medium Voltage Motor Control Assemblies

Medium Voltage Motor Control Assemblies Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fire pumps

More information

tiastar Motor Control Center Catalog and Application Guide

tiastar Motor Control Center Catalog and Application Guide tiastar TM Motor Control Center Catalog and Application Guide Table of Contents Introduction tiastar MCC 4 Product Features and Benefits 6 tiastar Arc Resistant MCC 8 Key Innovations of Arc Resistant MCC

More information

Buck - Boost Transformers

Buck - Boost Transformers Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

Cable/Conduit Conversion

Cable/Conduit Conversion Cable/Conduit Conversion Busway can be used in many applications where cable and conduit are more commonly used. The question arises, Why use busway instead of conventional cable and conduit? Benefits

More information

Tmax MCCBs. Molded case circuit breakers. Tmax

Tmax MCCBs. Molded case circuit breakers. Tmax Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high

More information

IEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide

IEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide - long al and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide range coils +0% to -30% Finger safe terminals Four-pole versions available NO + NC and

More information

US Breaker Brand 3 Pole AC Contactors (Square D Telemecanique LC1 Replacements)

US Breaker Brand 3 Pole AC Contactors (Square D Telemecanique LC1 Replacements) 4 NC1 D09-D18 NC1 -D32 US Breaker Brand 3 Pole AC Contactors (Square D Telemecanique LC1 Replacements) Standards: UL508, CSA C22.2, IEC 60947, and CE Marked Integral DIN Rail & Base Mounting in One Compact

More information

PSR The compact range Description

PSR The compact range Description Description The PSR range is the most compact of all the ABB softstarter ranges, thereby making it possible to fit many devices into the same enclosure. The system concept with Manual Motor Starters provides

More information

SPEEDFAX TM 2011 Motor Control Centers Contents

SPEEDFAX TM 2011 Motor Control Centers Contents SPEEDFAX TM 2011 Motor Control Centers Contents Product Overview Overview of tiastar TM -2 Construction Details -3-4 Technical Dimensions and Weights -5 Wiring Classifications -6 Incoming Cable Space,

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Rotary Phase Converters

Rotary Phase Converters FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage

More information

Motor Protection Voltage Unbalance and Single-Phasing

Motor Protection Voltage Unbalance and Single-Phasing Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Overload Relay Heater Tables

Overload Relay Heater Tables Overload Relay Tables of Elements for Overload Relays Use only when motor full load current is not known. Motor amps will vary depending on the type and manufacturer of the motor. These average values,

More information

Table of Contents. Review Answers...77 Final Exam...80

Table of Contents. Review Answers...77 Final Exam...80 Table of Contents Introduction...2 Motor Control...4 Power Supplies...8 Design Standards... 12 Need for Circuit Protection... 13 Motor Control Centers...21 tiastar MCC Construction...32 tiastar Arc Resistant

More information

Sentron Series Circuit Breakers

Sentron Series Circuit Breakers Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Industrial Automation Commonly-Used Terms

Industrial Automation Commonly-Used Terms Engineering Smarter Systems Industrial Automation Commonly-Used Terms A Glossary of Industrial Automation and Control Terms LECINC.COM 1 A Accelerating Time: Across the Line Starter: Action Device: Actuator:

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Description Firetrol FTA1930 Digital Solid State Starting Fire Pump Controllers feature soft start, soft stop and

More information

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE WHITE PAPER WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE EXPLANATION AND ASSISTANCE FOR APPLYING SOLID STATE SOFT STARTERS IN TRADITIONAL REDUCED VOLTAGE APPLICATIONS Introduction..............................................................2

More information

80 Series - Modular timers 16 A. Features 80.01 80.11

80 Series - Modular timers 16 A. Features 80.01 80.11 80 Series - Modular timers 6 A 80. Multi-function and mono-function timer range - Multi-function & multi-voltage 80. - ON delay, multi-voltage 7.5 mm wide Six time scales from 0.s to 24h 35 mm rail (EN

More information

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

3) What is the difference between Insulating, Isolating, and Shielded Winding transformers? Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

BG or BGE Brake Rectifier

BG or BGE Brake Rectifier Brake Voltage Supplied from the otor There are specific instances when the brake voltage can be tapped from the motor's terminal block. The advantage of brake systems wi in this way is when power is applied

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations 12S, 14S, 15S Series Time Delay Relays and Sequencers Time Delay Relays and Sequencers The Therm-O-Disc type 12S, 14S and 15S series time delay relays and sequencers are field-proven devices for controlling

More information

How To Build A Germany Power Plant

How To Build A Germany Power Plant Medium Voltage Air Insulated Motor Control Featuring AdvanceTM Technology. Medium Voltage Motor Control Center Product Description Contemporary Design Advance TM medium voltage motor control center (MVMCC)

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C 41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers

More information

MOTOR PROTECTION AGAINST SINGLE-PHASING

MOTOR PROTECTION AGAINST SINGLE-PHASING THE SINGLE-PHASE DILEMMA: FACT OR FICTION PROTECTION AGAINST SINGLE-PHASING Bulletin PSP The Single-Phasing Issue: Fact or Fiction Overview Before discussing SINGLE-PHASING, let s take a look at some of

More information

Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers

Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Catalog 2004 Class 601 CONTENTS Description..............................................Page INTRODUCTION.............................................

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content

More information

Introduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system

Introduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system Table of Contents Introduction... 2 Distribution Systems... 4 Switchboard Definition... 9 Switchboard Construction... 12 Service Entrance Equipment... 18 Service Section... 20 Switchboard Grounding...

More information

6 Buck Boost Transformers

6 Buck Boost Transformers 6 uck oost Transformers uck-oost transformers are small, single phase, dry type distribution transformers designed and shipped as insulating/isolating transformers. They have a dual voltage primary and

More information

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Guidelines on the Short Circuit Current Rating for Industrial Control Panels usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A

More information

Instructions for Class W200, W201, Sizes 5 and 6, Three Phase Non-Reversing Magnetic Motor Starters and Contactors

Instructions for Class W200, W201, Sizes 5 and 6, Three Phase Non-Reversing Magnetic Motor Starters and Contactors I.L. 17405 Revision F Instructions for Class W200, W201, Sizes 5 and 6, Three Phase Non-Reversing Magnetic Motor Starters and Contactors RATINGS The maximum horsepower ratings of these motor controllers

More information

Replacement Parts. Starters and Contactors AC Coils. Selection. Ordering Information

Replacement Parts. Starters and Contactors AC Coils. Selection. Ordering Information Starters and Contactors AC Coils Ordering Information 4th character of starter or contactor catalog number indicates model. 17 CONTROL AC Coils For Class 14, 17, 18, 22, 25, 26, 30, 32, 36, 37, 40, 43,

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

Model 6 Export Motor Control Centers

Model 6 Export Motor Control Centers Model 6 Export Motor Control Centers Class 8998 CONTENTS Schneider Electric Brands Description Page Product Description.................................................. 3 Technical Overview..................................................

More information

How To Protect A Motor From Overcurrent

How To Protect A Motor From Overcurrent Phase ailure elays Type PS and PD Class 8430 Catalog 04 CONTENTS Description.....................................................Page Product Description and Definitions......................................

More information

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12 Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Cleaveland/Price Type TP-C2 Motor Operator

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY

More information

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Learning Module 13: Panelboards and Switchboards. 101 Basic Series Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and

More information

101 BASICS SERIES LEARNING MODULE 19: STARTERS AND CONTACTORS. Cutler-Hammer

101 BASICS SERIES LEARNING MODULE 19: STARTERS AND CONTACTORS. Cutler-Hammer 101 BASICS SERIES LEARNING MODULE 19: STARTERS AND CONTACTORS Cutler-Hammer WELCOME Welcome to Module 19, which is about starters, devices that control the use of electrical power to equipment, usually

More information

Low Voltage Fuses For Motor Protection

Low Voltage Fuses For Motor Protection Code Requirements The NEC or CEC requires that motor branch circuits be protected against overloads and short circuits. Overload protection may be provided by fuses, overload relays or motor thermal protectors.

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

32VFD Variable Frequency Drives for Centrifugal Chillers

32VFD Variable Frequency Drives for Centrifugal Chillers 32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to

More information

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,

More information

Power Plant Electrical Distribution Systems

Power Plant Electrical Distribution Systems PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

Solid-State Timer H3G

Solid-State Timer H3G ASH & ALAIN INDIA PVT LTD S-100, F.I.E.E., Okhla Industrial Area, Phase-ii, New Delhi-11000(India) Tel : 011-43797575 Fax : 011-43797574 E-mail : sales@ashalain.com Solid-State Timer Low-Cost, Plug-In

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Variable Transformers Product Design & Engineering Data

Variable Transformers Product Design & Engineering Data Variable Transformers Product Design & Engineering Data Product Design & Engineering Data Type 1010B Cutaway General Information STACO ENERGY PRODUCTS CO. is a leading manufacturer of variable transformers,

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

Electrical Symbols and Line Diagrams

Electrical Symbols and Line Diagrams Electrical Symbols and Line Diagrams Chapter 3 Material taken from Chapter 3 of One-Line Diagrams One-line diagram a diagram that uses single lines and graphic symbols to indicate the path and components

More information

Low Voltage Switchgear

Low Voltage Switchgear Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering

More information

12VDC MAGNETIC LED DIMMABLE POWER SUPPLIES SPEC SHEET DIGEST

12VDC MAGNETIC LED DIMMABLE POWER SUPPLIES SPEC SHEET DIGEST 12VDC MAGNETIC ED DIMMABE POER SUPPIES SPEC SEET DIGEST TM-30-DIM TM-50-DIM T-60-DIM TM100-DIM TM200-DIM TM300-DIM iring Diagram for TM-50-DIM and TM-100-DIM ED 12VDC MAGNETIC DIMMABE 30 POER SUPPY Smallest

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Three-phase AC circuits

Three-phase AC circuits Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for

More information

UL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training. 2002 Eaton Corporation. All rights reserved.

UL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training. 2002 Eaton Corporation. All rights reserved. UL 508A Industrial Control Panels Power Distribution and Control Lunch & Learn Training 2002 Eaton Corporation. All rights reserved. Agenda Who is UL and what role do they play? What is the UL 508A Standard?

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Modan 3000 ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER. Systems Products and Services. Motor Control Centers Modan 3000

Modan 3000 ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER. Systems Products and Services. Motor Control Centers Modan 3000 Systems Products Motor Control Centers Modan 3 Modan 3 UL / CSA ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER MODAN 3 Motor Control Centers Offer: Over 1 years of Motor Control experience

More information

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings Smart Frame Wiring Diagrams and Dimensional Drawings Smart Frame Size 60 Vac:.5-7.5 HP 08/0 Vac: 0.75- HP SPECIFICATION DATA CONTENTS Smart Frame Wiring Diagrams... Frame, Fused Disconnect Wiring Diagrams...

More information

UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL

UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL Definition of Terms / Explanations Overview of Basic Devices Construction Types acc. to UL 508 Self-Protected Combination Motor Controller

More information

Fusible Disconnect Switch

Fusible Disconnect Switch Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit

More information

Pilot-wire differential relay for lines with two or more terminals

Pilot-wire differential relay for lines with two or more terminals Pilot-wire differential relay for lines with two or more terminals Page 1 Issued: March 2003 Revision: A Data subject to change without notice Pilot-wire differential relay with RXHL 401 Features Phase

More information

Distribution Dry Type Transformers

Distribution Dry Type Transformers Distribution Dry Type s Sentron Power Centers Bolt-in Breaker Option The same economical space saving package, NEMA 3R rated enclosure, and UL listed transformer of the original Sentron Power Center but

More information

80 Series - Modular timers 16 A. Features 80.01 80.11

80 Series - Modular timers 16 A. Features 80.01 80.11 80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h

More information

tiastar and legacy Motor Control Center Aftermarket Renewal Parts Catalog

tiastar and legacy Motor Control Center Aftermarket Renewal Parts Catalog tiastar TM and legacy Motor Control Center Aftermarket Renewal Parts Catalog Table of Contents MCC Identification Guide 1 Ordering Processes 2-3 Section Parts Splice Kits 4 Drip Shield Kits 5 Structural

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

Micro Contactors. Micro Contactor Relays. Micro Contactors With Solder Pins. Coil voltages. Micro Reversing Contactor. Technical Data.

Micro Contactors. Micro Contactor Relays. Micro Contactors With Solder Pins. Coil voltages. Micro Reversing Contactor. Technical Data. Micro Contactors Micro Contactor Relays 0 Micro Contactors Micro Contactors With Solder Pins Coil voltages Micro Reversing Contactor 3 Technical Data 4 Dimensions 8 9 Micro Contactor Relays 4pole C Operated

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information