Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Size: px
Start display at page:

Download "Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000"

Transcription

1 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fire pumps where the capacity of the power source permits full voltage starting. Full voltage is applied to the motor as soon as the controller is actuated. The controller monitors, displays and records fire pump system information. Full voltage starting is simple and low cost and is preferred whenever the utility or emergency generator set will permit this type of starting. Approvals Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each controller: Voltage surge protector Main Disconnect Switch sized for connected motor horsepower and voltage Fire pump Circuit Breaker Motor contactor Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition Built-in Start and Stop push-buttons to bypass automatic start circuits Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators Single handle Isolating Disconnect Switch/Circuit Breaker mechanism POWER ON LED PUMP RUN LED PHASE FAILURE LED PHASE REVERSAL LED LOW PRESSURE LED DELUGE OPEN LED INTERLOCK ON LED TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) Minimum Run Timer / Off Delay Timer Daylight Savings Time Option Weekly Test Timer Elapsed Time Meter Digital Pressure Display 1.44M Floppy Disk Drive Data Log Event Log (3000 Events) True RMS Metering with simultaneous 3 phase display of amps and volts Disk Error message Disk Near Full message Pressure Error message Motor Over 320% message Local Start message Remote Start message Emergency Start message Fail To Start message Undervoltage message Overvoltage message Low Suction Pressure message High Speed Open Serial Communications Port NEMA Type 2 enclosure

2 SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, G NEMA Type 12 (IEC IP52) CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B psi ( bar) Pressure Transducer for Fresh Water Service -C psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure -AZ Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible Low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button and solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard PD (B)

3 Product Description Part Winding Starting Electric Fire Pump Controllers FTA1250 Description Firetrol FTA1250 Part Winding Starting Fire Pump Controllers can be used where the characteristics of the power source do not permit full voltage starting. The controller monitors, displays and records fire pump system information. When the controller is actuated by the pressure switch, START pushbutton, deluge valve contact, etc., the first contactor closes, connecting one of the motor windings to the line. During starting, the motor will draw approximately 65% of its normal locked rotor current and develop approximately 42% of its normal starting torque. After a time delay, the second contactor closes, connecting the second winding in parallel with the first. The motor then draws its normal running current and develops its rated torque. Approvals Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each controller: Voltage surge protector Main Disconnect Switch sized for connected motor horsepower and voltage Fire pump Circuit Breaker Motor contactor Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition Built-in Start and Stop push-buttons to bypass automatic start circuits Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators Single handle Isolating Disconnect Switch/Circuit Breaker mechanism POWER ON LED PUMP RUN LED PHASE FAILURE LED PHASE REVERSAL LED LOW PRESSURE LED DELUGE OPEN LED INTERLOCK ON LED TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) Minimum Run Timer / Off Delay Timer Daylight Savings Time option Weekly Test Timer Motor Acceleration Timer Elapsed Time Meter Digital Pressure Display 1.44M Floppy Disk Drive Data Log Event Log (3000 Events) True RMS Metering with simultaneous 3 phase display of amps and volts Disk Error message Disk Near Full message Pressure Error message Motor Over 320% message Local Start message Remote Start message Emergency Start message Fail To Start message Undervoltage message Overvoltage message Low Suction Pressure message High Speed Open Serial Communications Port NEMA Type 2 enclosure

4 SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, G NEMA Type 12 (IEC IP52) CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B psi ( bar) Pressure Transducer for Fresh Water Service -C psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure -AZ Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible Low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button and solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard PD (B)

5 Product Description Wye-Delta Open Transition Starting Electric Fire Pump Controllers FTA1300 Description Firetrol FTA1300 Wye-Delta, Open Transition Starting Fire Pump Controllers are used with delta-wound squirrel cage motors. FTA1300 controllers are of the open circuit transition type in which the motor circuit is opened during the transition from start to run. The controller monitors, displays and records fire pump system information. Actuating the controller by the pressure switch, START pushbutton or deluge valve contact closes the start contactor connecting the motor to the line in the wye connection. The motor will draw approximately 33% of its normal inrush current and develop approximately 33% of its normal starting torque. After a time delay, the motor is automatically reconnected in delta, applying full voltage to the motor windings. These controllers are recommended especially for use with generator sets. Approvals Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each controller: Voltage surge protector Main Disconnect Switch sized for connected motor horsepower and voltage Fire pump Circuit Breaker Motor contactor Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition Built-in Start and Stop push-buttons to bypass automatic start circuits Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators Single handle Isolating Disconnect Switch/Circuit Breaker mechanism POWER ON LED PUMP RUN LED PHASE FAILURE LED PHASE REVERSAL LED LOW PRESSURE LED DELUGE OPEN LED INTERLOCK ON LED TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) Minimum Run Timer / Off Delay Timer Daylight Savings Time option Weekly Test Timer Motor Acceleration Timer Elapsed Time Meter Digital Pressure Display 1.44M Floppy Disk Drive Data Log Event Log (3000 Events) True RMS Metering with simultaneous 3 phase display of amps and volts Disk Error message Disk Near Full message Pressure Error message Motor Over 320% message Local Start message Remote Start message Emergency Start message Fail To Start message Undervoltage message Overvoltage message Low Suction Pressure message High Speed Open Serial Communications Port NEMA Type 2 enclosure

6 SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, G NEMA Type 12 (IEC IP52) CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B psi ( bar) Pressure Transducer for Fresh Water Service -C psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure -AZ Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button with solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard PD (B)

7 Product Description Wye-Delta Closed Transition Starting Electric Fire Pump Controllers FTA1350 Description Firetrol FTA1350 Wye-Delta, Closed Transition Starting Fire Pump Controllers are used with delta-wound squirrel cage motors. FTA1350 controllers are of the closed circuit transition type in which the motor circuit remains closed during the transition from start to run. The controller monitors, displays and records fire pump system information. Actuating the controller by the pressure switch, START pushbutton or deluge valve contact closes the start contactor connecting the motor to the line in the wye connection. The motor will draw approximately 33% of its normal inrush current and develop approximately 33% of its normal starting torque. After a time delay, the motor is automatically reconnected in delta, applying full voltage to the motor windings. During this transition, a resistor is connected to each phase, minimizing line disturbances and voltage drop during starting. These controllers are recommended especially for use with generator sets. Approvals Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each controller: Voltage surge protector Main Disconnect Switch sized for connected motor horsepower and voltage Fire pump Circuit Breaker Motor contactor Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition Built-in Start and Stop push-buttons to bypass automatic start circuits Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators Single handle Isolating Disconnect Switch/Circuit Breaker mechanism POWER ON LED PUMP RUN LED PHASE FAILURE LED PHASE REVERSAL LED LOW PRESSURE LED DELUGE OPEN LED INTERLOCK ON LED TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) Minimum Run Timer / Off Delay Timer Daylight Savings Time option Weekly Test Timer Motor Acceleration Timer Elapsed Time Meter Digital Pressure Display 1.44M Floppy Disk Drive Data Log Event Log (3000 Events) True RMS Metering with simultaneous 3 phase display of amps and volts Disk Error message Disk Near Full message Pressure Error message Motor Over 320% message Local Start message Remote Start message Emergency Start message Fail To Start message Undervoltage message Overvoltage message Low Suction Pressure message High Speed Open Serial Communications Port NEMA Type 2 enclosure

8 SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, G NEMA Type 12 (IEC IP52) CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B psi ( bar) Pressure Transducer for Fresh Water Service -C psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure -AZ Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button with solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard PD (B)

9 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage when starting the pump motor. The controller monitors, displays and records fire pump system information. The circuit to the motor is not opened during the transition from start to run. While starting, the motor will draw 50% of full load starting current and supply 25% of rated torque. This method of starting minimizes line disturbances and voltage drop when starting. Approvals Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each controller: Voltage surge protector Main Disconnect Switch sized for connected motor horsepower and voltage Fire pump Circuit Breaker Motor contactor Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition Built-in Start and Stop push-buttons to bypass automatic start circuits Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators Single handle Isolating Disconnect Switch/Circuit Breaker mechanism Transition Contactor and Power Resistors POWER ON LED PUMP RUN LED PHASE FAILURE LED PHASE REVERSAL LED LOW PRESSURE LED DELUGE OPEN LED INTERLOCK ON LED TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) Minimum Run Timer / Off Delay Timer Daylight Savings Time option Weekly Test Timer Motor Acceleration Timer Elapsed Time Meter Digital Pressure Display 1.44M Floppy Disk Drive Data Log Event Log (3000 Events) True RMS Metering with simultaneous 3 phase display of amps and volts Disk Error message Disk Near Full message Pressure Error message Motor Over 320% message Local Start message Remote Start message Emergency Start message Fail To Start message Undervoltage message Overvoltage message Low Suction Pressure message High Speed Open Serial Communications Port NEMA Type 2 enclosure

10 SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, G NEMA Type 12 (IEC IP52) CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B psi ( bar) Pressure Transducer for Fresh Water Service -C psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure -AZ Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button with solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard PD (C)

11 Product Description Autotransformer Starting Electric Fire Pump Controllers FTA1800 Description Firetrol FTA1800 Autotransformer Starting Fire Pump Controllers use an autotransformer to supply reduced voltage when starting the motor. The controller is of the closed circuit type where the motor circuit remains closed during the transition from start to run resulting in minimum line disturbance. The controller monitors, displays and records fire pump system information. The autotransformer has three taps for selection of starting current and torque; 50% tap for 150% current and 25% torque, 65% tap (factory setting) for 250% current and 42% torque and the 80% tap for 384% current and 64% torque. Approvals Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each controller: Voltage surge protector Main Disconnect Switch sized for connected motor horsepower and voltage Fire pump Circuit Breaker Motor contactor Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition Built-in Start and Stop push-buttons to bypass automatic start circuits Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators Single handle Isolating Disconnect Switch/Circuit Breaker mechanism Transition Contactor and Autotransformer POWER ON LED PUMP RUN LED PHASE FAILURE LED PHASE REVERSAL LED LOW PRESSURE LED DELUGE OPEN LED INTERLOCK ON LED TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) Minimum Run Timer / Off Delay Timer Daylight Savings Time option Weekly Test Timer Motor Acceleration Timer Elapsed Time Meter Digital Pressure Display 1.44M Floppy Disk Drive Data Log Event Log (3000 Events) True RMS Metering with simultaneous 3 phase display of amps and volts Disk Error message Disk Near Full message Pressure Error message Motor Over 320% message Local Start message Remote Start message Emergency Start message Fail To Start message Undervoltage message Overvoltage message Low Suction Pressure message High Speed Open Serial Communications Port NEMA Type 2 enclosure

12 SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, G NEMA Type 12 (IEC IP52) CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B psi ( bar) Pressure Transducer for Fresh Water Service -C psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure -AZ Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button with solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard PD (C)

13 Product Description Solid State Starting Electric Fire Pump Controllers FTA1900 Description Firetrol FTA1900 Solid State Starting Fire Pump Controllers feature soft start, soft stop and system sensing capabilities that not only provide for reduced voltage starting, but also offer an improved level of hydromechanical performance. The controller monitors, displays and records fire pump system information. When called to run, the motor will accelerate along a ramp beginning at 40% of normal starting current with 15% of full voltage torque. When stopping, the motor will ramp down to a preset level and allow for a restart, limiting stress in the piping system. If no additional starting causes are present, the motor will continue to ramp down to a full stop. This controller helps to reduce water hammer in the system. Approvals Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each controller: Voltage surge protector Main Disconnect Switch sized for connected motor horsepower and voltage Fire pump Circuit Breaker Motor contactor Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition Built-in Start and Stop push-buttons to bypass automatic start circuits Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators Single handle Isolating Disconnect Switch/Circuit Breaker mechanism Firetrol SS/3 Solid State SCR Starter POWER ON LED PUMP RUN LED PHASE FAILURE LED PHASE REVERSAL LED LOW PRESSURE LED DELUGE OPEN LED INTERLOCK ON LED TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) Minimum Run Timer / Off Delay Timer Soft Start Bypass Timer Daylight Savings Time option Weekly Test Timer Motor Acceleration Timer Elapsed Time Meter Digital Pressure Display 1.44M Floppy Disk Drive Data Log Event Log (3000 Events) True RMS Metering with simultaneous 3 phase display of amps and volts Disk Error message Disk Near Full message Pressure Error message Motor Over 320% message Local Start message Remote Start message Emergency Start message Fail To Start message Soft Starter Overtemp message Undervoltage message Overvoltage message Low Suction Pressure message High Speed Open Serial Communications Port NEMA Type 2 enclosure

14 SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, G NEMA Type 12 (IEC IP52) CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B psi ( bar) Pressure Transducer for Fresh Water Service -C psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure -AZ Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible Relief Valve Discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button with solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard PD (B)

15 Product Description Power Transfer Switches for Electric Fire Pump Controllers FTA900 FTA950 Description Firetrol Power Transfer Switches are available completely assembled with Firetrol Electric Fire Pump Controllers; full or reduced voltage types. The power transfer switches are built in two versions: FTA900 For use when the normal power source is a utility and the emergency power source is a generator set. FTA950 For use when both the normal and emergency power sources are utilities. The entire package of power transfer switch and controller is completely factory assembled, wired, tested and shipped as a complete unit for easy field connection to the power sources and the fire pump motor. Approvals Firetrol power transfer switches are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers; UL1008, Automatic Transfer Switches; UL508, Industrial Control Equipment, CSA, Standard for Industrial Control Equipment; and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each transfer switch: Emergency power source disconnect switch sized for connected motor horsepower and voltage (FTA950 only) Fire pump circuit breaker (FTA950 only) Mark II monitors for overcurrent tripping (non-thermal) of circuit breaker and alarm indicator for phase failure/phase reversal 3-pole, double throw transfer switch mechanism, electrically operated, mechanically held Control module providing for the following: Differential voltage sensing on all phases of the normal power source Voltage sensing of the emergency power source Frequency sensing of the emergency power source Transfer time delay to compensate for momentary power outages of the normal source Retransfer from emergency to normal source is automatically delayed unless the emergency source fails Cool-down timer for unloaded running of the generator set after retransfer to the normal power source Instantaneous retransfer to normal if the emergency source fails and the normal source is available 3 second transfer restart delay to reduce current surges when transferring to or from the emergency source NO and NC engine control contacts to start the generator set when the normal power source fails Transfer Switch Normal LED Transfer Switch Emergency LED Emergency Isolating Switch Open LED Test Selector Switch Transfer By-pass Switch Silence Alarm Pushbutton Emergency Isolating Switch Open and Transfer Switch in Emergency Audible Alarms Output contacts (NO and NC) for Generator Start, Emergency Isolating Switch Open and Transfer Switch position indicators Standard Withstand Rating, emergency side only FTA900 (Generator set equipped with molded case circuit breaker) A, 22,000A RMS Sym., V; 10,000A RMS Sym., V A, 35,000A RMS Sym., V; 10,000A RMS Sym., V A, 50,000A RMS Sym., V; 10,000A RMS Sym., V FTA950 See Options NEMA Type 2 enclosure (IEC IP11)

16 Note: The withstand rating of the normal power source side of the transfer switch will be the same as the withstand rating of the fire pump controller assembled with the power transfer switch. Options The following are available as options to FTA950 Power Transfer Switches: Circuit Breaker Option -M Standard withstand rating V - 100,000 Amps, RMS Sym. -N Intermediate withstand rating V - 150,000 Amps, RMS Sym. -P High withstand rating V - 200,000 Amps, RMS Sym. -Q Standard intermediate withstand rating V - 65,000 Amps RMS Sym. -R Standard low withstand rating V - 42,000 Amps RMS Sym. Modifications The following are available as modifications to all transfer switches: Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (painted steel) (IEC IP56) -F NEMA Type 4X (#304 stainless steel) (IEC IP 56) -G NEMA Type 12 (IEC IP52) Special finish paint consult factory Special finish color consult factory Anti-condensation Space Heaters -H 120 Volt space heater -J 120 Volt space heater with thermostat -K 120 Volt space heater with humidistat -L 240 Volt space heater -M 240 Volt space heater with thermostat -N 240 Volt space heater with humidistat Alarms -EC Extra contacts for remote indication, transfer switch position -BX Contacts for remote indication, second utility source phase failure/phase reversal (FTA950 only) Miscellaneous -ED Load shed circuits -TM Microprocessor type (Group 5) control module -TN As above, with serial communications port -S Tropicalization PD900-20(A)

17 Product Description Limited Service Controllers FTA750 Description Firetrol FTA750 Limited Service Controllers may be used for the automatic control of small electrically driven fire pumps and booster pumps where they are acceptable to the authority having jurisdiction. Approvals Firetrol limited service controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each controller: Voltage surge protector Main thermal-magnetic circuit breaker for assigned motor horsepower and voltage Firetrol FTA436 Phase Failure/Phase Reversal Monitor Motor contactor Power Available Pilot Light - indicates 3-phase power available and control power normal Phase Reversal Pilot Light - illuminates when phases are reversed Control transformer with 120 volt AC - secondary unfused for controller operating logic circuits, with fuse for possible external auxiliary devices Circuitry for start by remote deluge valve or other fire protection equipment (requires normally closed, open to start remote contacts) Remote interlock circuit (requires remote normally open contact which closes to operate) Built-in Start and Stop pushbuttons to bypass automatic start circuits Minimum Run Timer for automatic stop Pressure switch, integrally mounted on a threaded bulkhead fitting with external 1/2 inch connection Field connection remote alarm terminals (normally open-close to alarm and normally closed-open to alarm) for each of the following: Pump Operating, Pump Power Failure, Phase Reversal Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition operation of emergency run mechanism results in a full voltage start of the motor NEMA Type 2 enclosure (IEC IP11) Options The following are available as options to the controllers: Timer Option -A With running period timer (auto/manual start with auto/manual shutdown, selectable) -B Without running period timer (auto/manual start with manual shutdown only) Circuit Breaker Option -A Standard withstand rating 2-20 HP, V - 10,000 Amps, RMS Sym HP, V - 18,000 Amps, RMS Sym HP, V - 14,000 Amps, RMS Sym. -B Intermediate withstand rating V - 65,000 Amps, RMS Sym V - 18,000 Amps, RMS Sym. NOTE: Standard controllers contain MERCURY filled pressure switches which are readily and visibly labeled Contains Mercury - do not put in trash. Recycle or dispose as hazardous waste. Keep cover in place. To avoid the use of Mercury, contact Firetrol or your local representative for alternative devices.

18 Modifications The following are available as modifications to the controllers: Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (painted steel) (IEC IP56) -F NEMA Type 4X (#304 stainless steel) (IEC IP56) -G NEMA Type 12 (IEC IP52) Special paint color or finish consult factory Anti-condensation Space Heaters -H 120 Volt space heater -J 120 Volt space heater with thermostat -K 120 Volt space heater with humidistat -L 240 Volt space heater -M 240 Volt space heater with thermostat -N 240 Volt space heater with humidistat Pressure Switches and Recorders -B psi ( kg/cm 2 ) pressure switch for fresh water service -C psi ( kg/cm 2 ) pressure switch for sea water/foam service -D psi ( kg/cm 2 ) pressure switch for sea water/foam service Automatic Power Transfer Switches (Refer to Publication PD975-01) FTA975 - generator set emergency supply FTA976 - second utility emergency supply Alarms -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AM Contacts for remote indication, pump fail to start -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -P Built-in alarm system (includes visible supervisory voltage normal indication and audible phase failure, phase reversal and pump run indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure Miscellaneous -A Sequential start -R Pump operating pilot light -S Tropicalization PD750-20(A)

19 Product Description Power Transfer Switches for Limited Service Controllers FTA975 FTA976 Description Firetrol Power Transfer Switches are available completely assembled with Firetrol Limited Service Controllers. The power transfer switches are built in two versions: FTA975 For use when the normal power source is a utility and the emergency power source is a generator set. FTA976 For use when both the normal and emergency power sources are utilities. The entire package of power transfer switch and controller is completely factory assembled, wired, tested and shipped as a complete unit for easy field connection to the power sources and the fire pump motor. Approvals Firetrol power transfer switches are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers; UL1008, Automatic Transfer Switches; UL508, Industrial Control Equipment, CSA, Standard for Industrial Control Equipment; and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each transfer switch: Emergency power source disconnect switch sized for connected motor horsepower and voltage (FTA975 only) molded case isolating switch (FTA976 only) thermal-magnetic circuit breaker 3-pole, double throw transfer switch mechanism, electrically operated, mechanically held Control module providing for the following: Differential voltage sensing on all phases of the normal power source Voltage sensing of the emergency power source Frequency sensing of the emergency power source Transfer time delay to compensate for momentary power outages of the normal source Retransfer from emergency to normal source is automatically delayed unless the emergency source fails Cool-down timer for unloaded running of the generator set after retransfer to the normal power source Instantaneous retransfer to normal if the emergency source fails and the normal source is available 3 second transfer restart delay to reduce current surges when transferring to or from the emergency source NO and NC engine control contacts to start the generator set when the normal power source fails Transfer Switch Normal Pilot Light Transfer Switch Emergency Pilot Light Emergency Isolating Switch Open Pilot Light Test Selector Switch Transfer By-pass Switch Silence Alarm Pushbutton Emergency Isolating Switch Open and Transfer Switch in Emergency Audible Alarms Output contacts (NO and NC) for Generator Start, Emergency Isolating Switch Open and Transfer Switch position indicators Standard Withstand Rating, emergency side only FTA975 (Generator set equipped with molded case circuit breaker) 3-30HP, V, 10,000 Amps, RMS Sym. FTA HP, V, 10,000 Amps, RMS Sym HP, V, 18,000 Amps, RMS Sym. 3-30HP, V, 14,000 Amps, RMS Sym. NEMA Type 2 (IEC IP11) enclosure Note: The withstand rating of the normal power source side of the transfer switch will be the same as the withstand rating of the fire pump controller assembled with the power transfer switch.

20 Options The following are available as options to FTA976 Power Transfer Switches: Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (#304 Stainless Steel) (IEC IP56) -G NEMA Type 12 (IEC IP52) Special paint color or finish - Consult Factory Circuit Breaker Option -B Intermediate withstand rating V - 65,000 Amps, RMS Sym V - 18,000 Amps, RMS Sym. Modifications The following are available as modifications to all transfer switches: Anti-condensation Space Heaters -H 120 Volt space heater -J 120 Volt space heater with thermostat -K 120 Volt space heater with humidistat -L 240 Volt space heater -M 240 Volt space heater with thermostat -N 240 Volt space heater with humidistat Explanation of Catalog Number FTA975-BL100B-ED Type Modifications 975 Gen Set Voltage 976 Second Utility -H Start Option -A B Automatic -F Withstand rating -B A Standard (FTA976) -C B Intermediate (FTA976) Ampere rating -D Standard (FTA975) 100 Example FTA975-BD100B-ED FTA975 Power Transfer Switch for generator set emergency power source, 100 Amp, Volts, with load shed circuits. Note Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. Alarms -BX Contacts for remote indication, second utility source phase failure/phase reversal (FTA976 only) Miscellaneous -ED Load shed circuits -TM Microprocessor type (Group 5) control module -TN As above, with serial communications port -S Tropicalization PD975-01(E)

21 Product Description High Voltage Fire Pump Controllers Volt FTA2000 Description Firetrol FTA2000 combined automatic and manual class E2 high voltage controllers are intended for starting of squirrel cage motors driving listed fire pumps. Maximum ratings are as follows: Max. HP Phase Voltage Approvals Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each controller: Isolating Switch - NEMA Rating, 7200 Volts, 400 Amps with external operating handle with electrical and mechanical interlocks to prevent opening of the high voltage compartment door with the isolating switch or the main contactor closed. Interlocks prevent opening the isolating switch with the main contactor closed. Vacuum Contactor - NEMA Rating, 7200 Volts, 400 Amps Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition Built-in Start and Stop push-buttons to bypass automatic start circuits Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators Normal-Off-Test Selector Switch - Internally mounted for functional test of control system only, requires that isolating switch be open and a separate 120 volt AC power source be supplied. POWER ON LED PUMP RUN LED PHASE FAILURE LED PHASE REVERSAL LED LOW PRESSURE LED DELUGE OPEN LED INTERLOCK ON LED Minimum Run Timer / Off Delay Timer Daylight Savings Time Option Weekly Test Timer Elapsed Time Meter Digital Pressure Display 1.44M Floppy Disk Drive Data Log Event Log (3000 Events) True RMS Metering with simultaneous 3 phase display of amps and volts Disk Error message Disk Near Full message Pressure Error message Motor Over 320% message Local Start message Remote Start message Emergency Start message Fail To Start message Undervoltage message Overvoltage message Low Suction Pressure message High Speed Open Serial Communications Port NEMA Type 2 enclosure

22 SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) -G NEMA Type 12 (IEC IP52) ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B psi ( bar) Pressure Transducer for Fresh Water Service -C psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D psi ( bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AG Built-in reservoir low alarm -AM Contacts for remote indication, pump fail to start -AW Contacts for remote indication, reservoir low -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -EG Visible Relief Valve Discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -HW Audible and visible pump fail to start alarm (Requires modification -HV) -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -BAT Volt test circuit -EP SIS Wire, sleeve wire markers and ring tongue terminals -GZ 50 Hertz operation -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging *Weekly Test Timer - Standard PD (A)

23 Product Description Diesel Engine Fire Pump Controller FTA1100 Description Firetrol combined automatic and manual Mark II based diesel engine fire pump controllers are intended for starting and monitoring fire pump diesel engines. They are available for use with 12 or 24 volt negative ground systems using lead acid or Nickel-Cadmium batteries. The controller monitors, displays and records fire pump system information. Approvals Firetrol fire pump controllers are listed by Underwriters Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment (cul), and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features The following are included as standard with each controller: Two pole AC line circuit breaker Manual-Off-Auto selector switch Manual test push-button Two manual crank push-buttons Two 10 Amp battery chargers with 4 stage charging cycle, selectable AC voltage (110 / 220), selectable DC voltage (12 / 24), and selectable battery type (Lead Acid, Ni-Cad 9/18 Cell, Ni- Cad 10/20 Cell) Door mounted display/interface panel featuring a 80 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators MAIN SWITCH IN AUTO LED ENGINE FAIL TO START LED CHARGER MALFUNCTION LED BATTERY #1 TROUBLE LED BATTERY #2 TROUBLE LED SYSTEM PRESSURE LOW LED ENGINE RUNNING LED ENGINE COOLANT TEMP HIGH LED ENGINE OIL PRESSURE LOW LED ENGINE OVERSPEED LED LOW FUEL LEVEL LED Minimum Run Timer / Off Delay Timer Daylight Savings Time Option Weekly Test Timer Engine Run Time Meter Digital Pressure Display M Floppy Disk Drive (20,000 events) Data Log Event Log (3000 events) Simultaneous Display of Battery Voltages and Charging Rates Disk Error Message Disk Near Full Message Pressure Error Message Fail to Start Message Low Suction Pressure Message Crank Cycle Status Indication (Displays Cranking Battery, Number of Starting Attempts and Crank/Rest Time Remaining) 300 psi (20.7 bars) wet parts (pressure transducer, solenoid valve, plumbing) for fresh water applications High Speed Open Serial Communications Port NEMA Type 2 enclosure

24 Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP 56) -F NEMA Type 4X (IEC IP56) #304 Stainless Steel -G NEMA Type 12 (IEC IP52) Mounting Legs -N31 Standard 12 Mounting Legs -N32 Base Mounting Legs 6 Anti-Condensation Space Heaters -H 120 Volt Space Heater -J 120 Volt Space Heater with Thermostat -K 120 Volt Space Heater with Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater with Thermostat -N 240 Volt Space Heater with Humidistat Pressure Transducers, Solenoid Valves, Plumbing -B psi ( bars) wet parts for fresh water applications -C psi ( bars) wet parts for sea water/foam or copper corrosive applications -D psi ( bars) wet parts for sea water/foam or copper corrosive applications Alarms -AC -AJ -AK -AL -AM -AN -AP -AR -AS -AT -AV Additional contacts for remote indication, engine running - 2 sets provided as standard Contacts for remote indication, engine overspeed Contacts for remote indication, low oil pressure Contacts for remote indication, high water temperature Contacts for remote indication, engine failed to start Contacts for remote indication, battery / charger failure Contacts for remote indication, main switch in manual Contacts for remote indication, main switch in off Contacts for remote indication, main switch in auto Contacts for remote indication, pump room trouble (common alarm) 1 Contacts for remote indication, low pump room temperature 1 -AW Contacts for remote indication, reservoir low 1 -AY Contacts for remote indication, low suction pressure 1 -COM Visible low suction pressure alarm with manual reset push-button 1 -CTS Built-in low suction pressure alarm panel (Includes selectable auto/ manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EE Additional contacts for remote indication, engine trouble (common alarm) - 1 set provided as standard -EF Additional contacts for remote indication, main switch mis-set (common alarm) - 1 set provided as standard -EH Contacts for remote indication, relief valve discharge 1 -EJ Visible flow meter on alarm 1 -EK Contacts for remote indication, flow meter on 1 -LC Contacts for remote indication, high fuel level 1 -LD Visible fuel spill alarm 1 -LE Contacts for remote indication, fuel spill 1 -LG Contacts for remote indication, reservoir high 1 -PE Contacts for remote indication, low system pressure Miscellaneous -AZ Low pump room temperature switch, mounted and wired -BA Volt operation -EL Series pumping, high zone controller -EM Series pumping, mid zone controller -EN Series pumping, low zone controller -S Tropicalization -ZPA Customized, annual service display message (factory programmed) -ZPB High quality impact printer with automatic paper take-up mechanism FTA1100-K1 Low fuel level switch 2 FTA1100-K volt operation (transformer) 2 Export packaging 1 - Initiating switches by others 2 - Shipped loose for installation by the customer PD (A)

25 Product Description Alarm Panels Electric Fire Pump Controllers FTA200-A FTA200-B Type B - Type B panels provide the same alarm indication as the Type A except that SUPERVISORY POWER FAILURE does not have the audible alarm feature. Only a visible alarm indication is provided. Description Firetrol FTA200 alarm panels are designed to meet the NPFA 20 specifications requiring a remote alarm panel when the pump house or pump room is not constantly attended. The alarm panel must be installed in a location that is under supervision at all times. Approvals These alarm panels are listed by Underwriter s Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls, certified by CSA, Standard for Industrial Control Equipment (cul), approved by the New York City Bureau of Electrical Control and Board of Standards and Appeals and Factory Mutual. They are designed to meet or exceed the requirements of the approving authorities listed above as well as NFPA 20, Installation of Centrifugal Fire Pumps. Standard Features The following are included as standard with each controller: Type A - Type A panels provide audible and visible alarm indication for the following conditions: Supervisory Voltage Normal Pump Operating Pump Phase Failure Pump Phase Reversal Construction - FTA200 alarm panels make use of printed circuit boards which provide reliable and trouble free service. The enclosures are NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The standard enclosure color is red. Mounted on the enclosure door are the pilot lights for visible alarm indication, the audible device for audible alarm indication, the SILENCE ALARM pushbutton and the PUSH-TO-TEST pushbutton. Each pilot light will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal condition has been corrected or the SILENCE ALARM pushbutton has been pressed. Pressing the SILENCE ALARM pushbutton will silence the audible alarm but will not extinguish the pilot light. If another alarm condition occurs the audible alarm will again sound until silenced by the SILENCE ALARM pushbutton or until the abnormal condition has been corrected. The PUSH-TO-TEST pushbutton is supplied for manually testing the pilot lights, audible alarm and output circuits. Modifications The following are available as modifications to the controllers: Special Enclosures -F NEMA Type 4X, 304 stainless (IEC IP56) -Y NEMA Type 1 (IEC IP10) Flush Mount, Painted Steel Consult Factory for other style enclosures. Additional Alarm Functions Each additional alarm function ordered will include a control relay and pilot light and will provide audible and visible alarm. There is no limit as to the number of additional alarm functions that can be supplied, however, enclosure size and weight may be affected. Consult the Factory for dimensions and shipping weights when ordering more than 2 additional alarms. Standard remote alarms may be ordered by using the Suffix Letters indicated for the corresponding alarm function on the Electric Fire Pump Controller. Alarm functions must exist in the controller to be ordered as remote alarms.

26 Standard Remote Alarms -AM Pump Fail To Start -BY Pump Overload -EG Relief Valve Discharge -EJ Flow Meter On Non-Standard Remote Alarms -BT When ordering, specify the number of alarms required, the function of each and the nameplate marking of each. Substitute Amber for Red Pilot Lights -LA To meet local code requirements. Explanation of Catalog Number FTA200-A-Y Alarm Panel Type Modification Code(s) Example - FTA200-A-Y Type A Alarm Panel with Nema Type 1, Flush Mount Enclosure. Information Required With Orders Catalog number of alarm panel Catalog number of controller to be used with alarm panel Modifications if any (give complete description) Dimensions and Shipping Weight Approx. Shipping Weight 18 lbs (8kg) Note Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. PD200-01(B)

27 Product Description Alarm Panels Diesel Engine Fire Pump Controllers FTA200-F FTA200-G Type G - Type G panels provide alarm indication for the following conditions: Supervisory Voltage Normal (Visible Only) Engine Trouble (Audible and Visible Engine Running (Audible and Visible) Main Switch Mis-Set (Audible and Visible) Pump Room Trouble (Audible and Visible) Description Firetrol FTA200 alarm panels are designed to meet the NPFA 20 specifications requiring a remote alarm panel when the pump house or pump room is not constantly attended. The alarm panel must be installed in a location that is under supervision at all times. Approvals These alarm panels are listed by Underwriter s Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls, certified by CSA, Standard for Industrial Control Equipment (cul), approved by the New York City Bureau of Electrical Control and board of Standards and Appeals and Factory Mutual. They are designed to meet or exceed the requirements of the approving authorities listed above as well as NFPA 20, Installation of Centrifugal Fire Pumps. Standard Features The following are included as standard with each controller: Type F - Type F panels provide alarm indication for the following conditions: Supervisory Voltage Normal (Visible Only) Engine Trouble (Audible and Visible) Engine Running (Audible and Visible) Main Switch Mis-Set (Audible and Visible) Construction - FTA200 alarm panels make use of printed circuit boards which provide reliable and trouble free service. The enclosures are NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The standard enclosure color is red. Mounted on the enclosure door are the pilot lights for visible alarm indication, the audible device for audible alarm indication, the SILENCE ALARM pushbutton and the PUSH-TO-TEST pushbutton. Each pilot light will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal condition has been corrected or the SILENCE ALARM pushbutton has been pressed. Pressing the SILENCE ALARM pushbutton will silence the audible alarm but will not extinguish the pilot light. If another alarm condition occurs the audible alarm will again sound until silenced by the SILENCE ALARM pushbutton or until the abnormal condition has been corrected. The PUSH-TO-TEST pushbutton is supplied for manually testing the pilot lights, audible alarm and output circuits. Modifications The following are available as modifications to the controllers: Special Enclosures -F NEMA Type 4X, 304 stainless (IEC IP56) -Y NEMA Type 1 (IEC IP10) Flush Mount, Painted Steel Consult Factory for other style enclosures. Additional Alarm Functions Each Additional alarm function ordered will include a control relay and pilot light and will provide audible and visible alarm. There is no limit as to the number of additional alarm functions that can be supplied, however, enclosure size and weight may be affected. Consult the Factory for dimensions and shipping weights when ordering more than 2 additional alarms. Standard remote alarms may be ordered by using the Suffix Letters indicated for the corresponding alarm function on the Diesel Engine Fire Pump Controller. Alarm functions must exist in the controller to be ordered as remote alarms.

28 Standard Remote Alarms -AU Low Fuel Level -AV Low Pump Room Temperature -AW Reservoir Low -AY Low Suction Pressure -AJ Engine Overspeed -AK Low Oil Pressure -AL High Water Temperature -AM Engine Failed To Start -AN Battery/Charger Failure -AP Main Switch In Manual -AR Main Switch In Off -AS Main Switch In Auto -LC High Fuel Level -LE Fuel Spill -EG Relief Valve Discharge -EJ Flow Meter On Non-Standard Remote Alarms -BT When ordering, specify the number of alarms required, the function of each and the nameplate marking of each. Substitute Amber for Red Pilot Lights -LA To meet local code requirements. Operation on Volts -BA Panel is supplied as standard for operation on volts. Explanation of Catalog Number FTA200-G-AU-LE Dimensions and Shipping Weight Approx. Shipping Weight 18 lbs. (8kg) Note Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. Alarm Panel Type Modification Code(s) Example - FTA200-G-AU-LE Type G Alarm Panel with remote alarms for Low Fuel Level and Fuel Spill. Information Required With Orders Catalog number of alarm panel Catalog number of controller to be used with alarm panel Modifications if any (give complete description) PD200-02(B)

29 Product Description Low Suction Pressure Shutdown Alarm Panels Fire Pump Controllers FTA200-D FTA200-E Mounted on the enclosure door are the pilot lights for visible alarm indication, the audible device for audible alarm indication and the SILENCE ALARM push-button. Each pilot light will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal condition has been corrected or the SILENCE ALARM push-button has been pressed. Pressing the SILENCE ALARM push-button will silence the audible alarm but will not extinguish the pilot light. If another alarm condition occurs the audible alarm will again sound until silenced by the SILENCE ALARM push-button or until the abnormal condition has been corrected. A pressure switch for monitoring the suction pressure is mounted on the side of the enclosure. Description Firetrol FTA200 low suction pressure alarm and shutdown panels are designed to be used with electric and diesel engine driven fire pump controllers. They are intended for use where a local authority mandates pump shutdown in the event of low suction pressure. Approvals These alarm panels have been approved by Factory Mutual. Standard Features The following are included as standard with each controller: Type D - Type D panels provide audible and visible alarm indication for the following conditions: Supervisory Voltage Normal Pump Controller Voltage Failure Low Suction Pressure (Automatic Reset) Type E - Type E panels provide the same alarm indication as the Type D except that LOW SUCTION PRESSURE shutdown and alarm must be manually RESET when suction pressure is restored. Modifications The following are available as modifications to the controllers: Special Enclosures -F NEMA Type 4X, 304 stainless (IEC IP56) Consult Factory for other style enclosures. Substitute Amber for Red Pilot Lights -LA To meet local code requirements. Operation on Volts -BA Panel is supplied as standard for operation on volts. 50 HZ Operation -GZ Controller is supplied to operate on 50 HZ incoming power. Construction - FTA200 alarm panels make use of printed circuit boards which provide reliable and trouble free service. The enclosures are NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The standard enclosure color is red. APPROVED

30 Explanation of Catalog Number FTA200-D-GZ Dimensions and Shipping Weight Alarm Panel Type Modification Code(s) Example - FTA200-D-GZ Type D Alarm Panel with modification to operate on 50 HZ incoming power. Information Required With Orders Catalog number of shutdown panel Catalog number of controller to be used with shutdown panel Modifications if any (give complete description) WARNING- Because NFPA 20 specifically prohibits the installation of any device in the suction piping which will restrict starting or stopping of the fire pump (See NFPA 20, Paragraph 2-9.9), Firetrol assumes no liability when Type D or E Shutdown Panels are used in connection with fire pump control equipment. Approx. Shipping Weight 20 lbs (9 kg) Note Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. PD200-03(C)

31 Product Description Jockey Pump Controllers Circuit Breaker Option -A Standard withstand capacity V - 10,000 Amps, RMS Sym V - 14,000 Amps, RMS Sym V - 14,000 Amps, RMS Sym. NOTE Consult factory for high interrupting capacity circuit breakers. Omit Minimum Run Timer -B Controller without minimum run timer Floor Mounting Legs FTA -N2 Specify when ordering FTA500 Modifications The following are available as modifications to the controllers: Description Firetrol FTA500 Jockey Pump Controllers are intended for use with fire pump systems. They are used for pressure maintenance in fire pump installations to prevent unnecessary cycling of the main fire pump. Approvals Firetrol jockey pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls, and CSA, Standard for Industrial Control Equipment. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest edition NFPA 70, National Electrical Code. Standard Features The following are included as standard with each controller: NEMA Type 2 drip-proof enclosure Horsepower rated fusible disconnect switch with fuseblock and fuses Horsepower rated motor contactor and overload relay HAND-OFF-AUTO selector switch Minimum run timer psi ( bars) Pressure switch, diaphragm style, snap action type contact and psi ( bars) adjustable differential, suitable for fresh water applications with psi ( bars) pressure gauge Options The following are available as options to the controllers: Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (painted steel) (IEC IP56) -F NEMA Type 4X (#304 stainless steel) (IEC IP56) -G NEMA Type 12 (IEC IP52) Special paint color or finish consult factory Anti-condensation Space Heaters -H 120 Volt space heater -J 120 Volt space heater with thermostat -K 120 Volt space heater with humidistat -L 240 Volt space heater -M 240 Volt space heater with thermostat -N 240 Volt space heater with humidistat Pressure Switches and Recorders -ZNY psi ( bars) pressure switch for fresh water service (Bourdon tube style, Mercury switch type) -B psi ( bars) pressure switch for fresh water service (Bourdon tube style, Mercury switch type) -C psi ( bars) pressure switch for sea water/foam service (Bourdon tube style, Mercury switch type) -D psi ( bars) pressure switch for sea water/foam service (Bourdon tube style, Mercury switch type) -SL psi ( bars) pressure recorder for fresh water service -SM psi ( bars) pressure recorder for fresh water service -SN 0-1,000 psi (0-69 bars) pressure recorder for fresh water service -SP psi ( bars) pressure recorder for sea water/foam service NOTE: Standard Jockey Pump controllers DO NOT CON- TAIN MERCURY filled pressure switches. Controllers with optional pressure switches listed above do contain mercury filled switches which are readily and visibly labeled Contains Mercury - do not put in trash. Recycle or dispose as hazardous waste. Keep cover in place.

32 -SR psi ( bars) pressure recorder for sea water/foam service -SS 0-1,000 psi (0-69 bars) pressure recorder for sea water/foam service Alarms -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AM Contacts for remote indication, pump fail to start -BY Contacts for remote indication, pump overload -BW Contacts for remote indication, pump power failure -BX Contacts for remote indication, phase reversal/phase failure Miscellaneous -BJ Power ON pilot light -BZ Elapsed time meter -S Tropicalization -BN Control circuit transformer -R Pump operating pilot light -GZ 50 Hertz operation Dimensions and Shipping Weight Explanation of Catalog Number FTA500-AF05B-B Timer Option Modifications -A With running Voltage (3 phase)* period timer -H B Without timer -A F Disconnect -B F With Fuseblock and -C Fuses Horsepower -A Circuit Breaker 1/4-50 * For single phase applications (2 HP Max.) use the following voltage codes: -D T E U G S Example FTA500-AF05B-BN FTA500 jockey pump controller, 5 HP, Volts, with modification (-BN) control circuit transformer Note Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. PD500-01(I)

33 Specifications Electric Fire Pump Controllers FTA Main Fire Pump Controller The main fire pump controller shall be a factory assembled, wired and tested unit and shall conform to all the requirements of the latest edition of NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection and NFPA 70, National Electrical Code. The controller shall be listed by Underwriters Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, and Canadian Standards Association CSA-C22.2, Standard for Industrial Control Equipment (culus), approved by Factory Mutual and approved by the City of New York for fire pump service. Starting Method The controller shall be of the combined manual and automatic type designed for: Full Voltage Starting Solid State Soft Starting Wye (Star)-Delta Open Transition Starting Wye (Star)-Delta Closed Transition Starting Part Winding Starting Primary Resistance Reduced Voltage Starting Autotransformer Reduced Voltage Starting of the fire pump motor having the horsepower, voltage, phase and frequency rating shown on the plans and drawings. The controller components shall be housed in a NEMA Type 2 (IEC IP11) drip-proof, wall mounted enclosure. Withstand Ratings (Short Circuit Current Ratings) All controller components shall be front mounted, wired and front accessible for maintenance. The minimum withstand rating of the controllers shall not be less than 100,000 Amps RMS Symmetrical at Volts*. If the available system fault current exceeds these ratings, the controllers shall be supplied with a withstand rating of 150,000 or 200,000 Amps RMS Symmetrical, as required. *Note: 100,000 Amp withstand rating not available in some larger horsepowers. Consult factory for details. Isolation Switch and Circuit Breaker The controller shall include a motor rated combination isolating disconnect switch/circuit breaker, mechanically interlocked and operated with a single, externally mounted handle. When moving the handle from OFF to ON, the interlocking mechanism shall sequence the isolating disconnect switch ON first, and then the circuit breaker. When the handle is moved from ON to OFF, the interlocking mechanism shall sequence the circuit breaker OFF first, and then the isolating disconnect switch. The isolating disconnect switch/circuit breaker shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The isolating disconnect switch/circuit breaker shall be capable of being padlocked in the OFF position for installation and maintenance safety, and shall also be capable of being locked in the ON position without affecting the tripping characteristics of the circuit breaker. The controller door shall have a locking type handle and three point cam and roller vault type hardware. The circuit breaker trip curve adjustment shall be factory set, tested and sealed for the full load amps of the connected motor. The circuit breaker shall be capable of being field tested to verify actual pick up, locked rotor, and instantaneous trip points after field installation without disturbing incoming line and load conductors. Operator Interface The fire pump controller shall feature an operator interface with user keypad. The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and pressure conditions shall be displayed with a time and date stamp. The display shall be a 2- line, 20-character, vacuum fluorescent, dot matrix type designed to allow easy viewing from all angles and in all light conditions. The display and interface shall be NEMA rated for Type 2, 3R, 4, 4X, and 12 protection and shall be fully accessible without opening the controller door. The display and user interface shall utilize multiple levels of password protection for system security. A minimum of 3 password levels shall be provided. The display shall be capable of being programmed for any language. Ammeter/Voltmeter The fire pump controller operator interface shall be capable of displaying true RMS digital motor voltage and current measurements for all three phases simultaneously. Displays requiring pushbutton and selector switches to toggle between phases or current and voltage shall not be accepted. Voltage and current shall be measured by True RMS technology to provide the most accurate measurement for all sine waves, including nonsinusoidal waveforms. Average responding meters will not be accepted. Digital Status/Alarm Messages The digital display shall indicate text messages for the status and alarm conditions of: Motor On Sequential Start Time Minimum Run Time Local Start / Off Delay Time Remote Start Fail to Start System Battery Low Under Voltage Over Voltage Locked Rotor Trip Low Suction Pressure Over Frequency Emergency Start Motor Over 320% Drive Not Installed Motor Overload Disk Error Printer Error Disk Near Full Pressure Error The Sequential Start Timer and Minimum Run Timer/ Off Delay Timer shall be displayed as numeric values reflecting the value of the remaining time.

34 LED Visual Indicators LED indicators, visible with the door closed, shall indicate: Power On Emerg. Isolating Switch Open Pump Running Low System Pressure Alarm Transfer Switch Normal Deluge Open Transfer Switch Emergency Phase Failure Phase Reversal Interlock On In addition to the standard alarm contacts required by NFPA 20, the digital display module shall have N.O. and N.C. contacts for remote indications of any digitally displayed alarm and N.O. and N.C. contacts for remote indication up to EIGHT, specified, programmable alarm. Data Logging The digital display shall monitor the system and log the following data: Motor Calls/Starts Elapsed Motor Run Time Last Trip Currents Elapsed Power On Time Last Breaker Trip Maximum Run Currents Minimum Voltages Minimum Run Currents Maximum Voltages Last Motor Run Time Last Phase Failure Last Start Currents Last Phase Reversal Min/Max Frequency Min/Max Pressure Event Recording Printer - The controller shall be equipped with a dot matrix, impact printer to record all operational and alarm events. The printer shall use standard 16# bond paper, commercially available at office supply stores. Thermal or electrostatic printers are not acceptable. The printer shall feature a mechanical take-up mechanism to prevent excessive paper buildup in the bottom of the controller during automatic operation. The printer shall automatically record all events and pressure settings. It shall allow the user to select the pressure recording frequency based upon either time or pressure deviation. If set for time based recording, the printer shall record the pressure every 30 minutes during standby and every 15 seconds during operation. Memory - The controller shall record all operational and alarm events to system memory. All events shall be time and date stamped and include an index number. The system memory shall have the capability of storing 3000 events and allow the user access to the event log via the user interface. The user shall have the ability to scroll through the stored messages in groups of 1, 10, or 100. Floppy Disk Drive - The controller shall include a floppy disk drive to save all operational and alarm events. The floppy disk drive shall have the ability to store up to 1 year s worth of data (under normal operating conditions) in individual monthly files. Each event shall be time and date stamped. The controller shall also have the capability to save settings and values to disk through the user interface. Communications - The controller shall feature two independent communications ports to allow connectivity to computers, modems, or building management systems. Solid State Pressure Transducer The controller shall be supplied with a solid state pressure transducer with a range of psi ( bar) ±1 psi. The solid state pressure switch shall be used for both display of the system pressure and control of the fire pump controller. Systems using analog pressure devices or mercury switches for operational control will not be accepted. The START, STOP and SYSTEM PRESSURE shall be digitally displayed and adjustable through the user interface. The pressure transducer shall be mounted inside the controller to prevent accidental damage. The pressure transducer shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. Operation A digitally set On Delay (Sequential Start) timer shall be provided as standard. Upon a call to start, the user interface shall display a message indicating the remaining time value of the On Delay timer. The controller shall be field programmable for manual stop automatic stop. If set for automatic stopping, the controller shall allow the user to select either a Minimum Run Timer or an Off Delay Timer. Both timers shall be programmable through the user interface. The controller shall be fully programmable to allow up to 8 custom alarm messages to be displayed on the user interface. A nonadjustable restart delay timer shall be provided to allow the residual voltage of the motor to decay prior to restarting the motor. At least 2 seconds, but no more than 3 seconds, shall elapse between stopping and restarting the pump motor. A weekly test timer shall be provided as standard. The controller shall have the ability to program the time, date, and frequency of the weekly test. In addition, the controller shall have the capability to display a preventative maintenance message for a service inspection. The message text and frequency of occurrence shall be programmable through the user interface. A Lamp Test feature shall be included. The user interface shall also have the ability to display the status of the system inputs and outputs. The controller shall not start the fire pump motor under a single-phase condition. If the motor is already running when a phase loss occurs, the controller shall continue to run the motor, but still display a Phase Failure alarm. The controller shall be manufactured by Firetrol. SP (A)

35 Specifications Fire Pump Controller Power Transfer Switches FTA Main Fire Pump Controller with Transfer Switch The main fire pump controller shall be factory assembled and wired with a power transfer switch listed by Underwriters Laboratories, Inc. for transfer switch and fire pump service. The power transfer switch shall be approved by Factory Mutual. The power transfer switch and fire pump controller shall be factory assembled, wired and tested as a single unit and shall conform to all requirements of the latest edition of NFPA 20, Centrifugal Fire Pumps and NFPA 70, National Electrical Code. Power Transfer Switch for Generator Set Emergency Power Source The power transfer switch shall be housed within the fire pump controller enclosure or in a NEMA Type 2 (IEC IP11) drip-proof enclosure attached directly to the fire pump controller. Where the power transfer switch is provided in an attached enclosure, the enclosures shall be fitted so that the assembly constitutes a single unit. The fire pump controller/power transfer switch shall be factory assembled, wired and tested as a unit prior to shipment. The power transfer switch shall include a motor rated disconnect/isolating switch capable of interrupting the motor locked rotor current. The disconnect/isolating switch shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The disconnect/isolating switch shall be capable of being padlocked in the OFF position with up to three padlocks for installation and maintenance safety, and shall also be capable of being locked in the ON position. The enclosure door shall have a locking type handle and three point cam and roller type vault hardware. A auxiliary contract shall be provided on the transfer switch to prevent starting of the emergency generator set when the transfer switch or the main fire pump controller are being serviced. The transfer switch circuitry shall be capable of sensing both the normal power source and the emergency power source. The normal power source pickup shall be set at 95% nominal voltage. The emergency power source shall be set to pick up at 90% nominal voltage and 95% nominal frequency. All voltage sensing, frequency sensing, and time delays shall be field adjustable to accommodate individual installation requirements. The transfer signal shall be delayed for one second, delaying the transfer and engine start signals so as to compensate for momentary, normal power outages. An automatic delay of three seconds shall be provided upon transfer to or from the emergency power source to allow the motor to slow sufficiently, preventing line disturbances that could trip either the generator set or fire pump circuit breakers. The transfer switch shall have TRANSFER SWITCH NORMAL, TRANSFER SWITCH EMERGENCY and EMERGENCY ISOLATING SWITCH OFF LED s, TEST and TRANSFER BYPASS switches, an audible alarm device and SILENCE ALARM pushbutton mounted on the flange of the enclosure. The power transfer switch shall be furnished with both normally open and normally closed auxiliary contacts for an engine start signal when normal power failure occurs. Auxiliary contacts shall also be provided and wired to terminals to indicate the transfer switch position. The transfer switch shall be electrically operated and mechanically held, and shall be capable of being operated by a manual transfer mechanism located on the switch. The power transfer switch shall be a Firetrol FTA900 for normal utility power and engine generator set emergency power.

36 Power Transfer Switch for Second Utility Emergency Power Source The power transfer switch shall be housed within the fire pump controller enclosure or in a NEMA Type 2 (IEC IP11) drip-proof enclosure attached directly to the fire pump controller. Where the power transfer switch is provided in an attached enclosure, the enclosures shall be fitted so that the assembly constitutes a single unit. The fire pump controller/power transfer switch shall be factory assembled, wired and tested as a unit prior to shipment. The power transfer switch shall include a motor rated combination isolating disconnect switch/circuit breaker, mechanically interlocked and operated with a single, externally mounted handle. When moving the handle from OFF to ON, the interlocking mechanism shall sequence the isolating disconnect switch closed first, and then the circuit breaker. When the handle is moved from ON to OFF, the interlocking mechanism shall sequence the circuit breaker open first, and then the isolating disconnect switch. The isolating disconnect switch/circuit breaker shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The isolating disconnect switch/circuit breaker shall be capable of being padlocked in the OFF position for installation and maintenance safety, and shall also be capable of being locked in the ON position without affecting the tripping characteristics of the circuit breaker. The enclosure door shall have a locking type handle and three point cam and roller type vault hardware. The circuit breaker trip curve adjustment shall be factory set, tested and sealed for the connected full load amps of the motor. The fire pump controller/power transfer switch shall have data logging capability for historical operation recording and to aid in annual test, service and trouble shooting. The data logging shall be accessible by front mounted interface panel and also by saving the information to supplied 1.44M floppy disk drive. The floppy disk file shall be in text (.txt) format and easily readable by most common text editing or word processing software. The circuit breaker shall be capable of being field tested to verify actual pick up, locked rotor, and instantaneous trip points after field installation without disturbing incoming line and load conductors. The transfer switch circuitry shall be capable of sensing both the normal power source and the emergency power source. The normal power source pickup shall be set at 95% nominal voltage. The emergency power source shall be set to pick up at 90% nominal voltage and 95% nominal frequency. All voltage sensing, frequency sensing, and time delays shall be field adjustable to accommodate individual installation requirements. The transfer signal shall be delayed for one second, delaying the transfer signal so as to compensate for momentary, normal power outages. An automatic delay of three seconds shall be provided upon transfer to or from the emergency power source to allow the motor to slow sufficiently, preventing line disturbances that could trip either the transfer switch or fire pump circuit breakers. The controller shall have TRANSFER SWITCH NOR- MAL, TRANSFER SWITCH EMERGENCY and EMER- GENCY ISOLATING SWITCH OFF LED s, TEST and TRANSFER BYPASS switches, an audible alarm device and SILENCE ALARM pushbutton mounted on the flange of the enclosure. To aid servicing, no indicating lights or switch devices shall be mounted on the enclosure door. Auxiliary contacts shall be provided and wired to terminals to indicate the transfer switch position. The transfer switch shall be electrically operated and mechanically held, and shall be capable of being operated by a manual transfer mechanism located on the switch. The transfer switch shall be a Firetrol FTA950 for normal utility power and second utility emergency power. Note: FTA900 and FTA950 power transfer switches are designed for use with Firetrol Electric Fire Pump Controllers, models FTA1000, FTA1250, FTA1300, FTA1350, FTA1500, FTA1800 and FTA1900. SP900-20(A)

37 Specifications Limited Service Controllers FTA750 The main fire pump controller shall be a factory assembled, wired and tested Limited Service Controller conforming to all the requirements of the latest edition of NFPA 20, Centrifugal Fire Pumps and NFPA 70, National Electrical Code. The controller shall be manufactured in the United States and be listed by Underwriters Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment (cul), approved by Factory Mutual, and approved by the City of New York for fire pump service. The controller shall be of the combined manual and automatic type suitable for full voltage starting of the fire pump motor having the horsepower, voltage, phase and frequency rating shown on the plans and drawings. The controller shall be housed in a NEMA Type 2 (IEC IP11) drip-proof, gasketed, wall mounted steel enclosure. The controller components shall include a thermal magnetic circuit breaker with a minimum withstand rating of not less than: 3-20 H.P Volts 10,000 Amps RMS Symmetrical H.P Volts 18,000 Amps RMS Symmetrical 3-30 H.P Volts 14,000 Amps RMS Symmetrical If the available fault current of the system exceeds these ratings, the controllers shall be supplied with a withstand rating as shown below: Horsepower Voltage Withstand Rating Amps RMS Sym , ,000 The circuit breaker shall have an externally mounted operating handle mechanically interlocked with the enclosure door so that entrance to the controller is not allowed with the handle in the ON position except by a hidden tool operated defeater. The circuit breaker handle shall be capable of being padlocked in the open or OFF position with up to three padlocks for installation and maintenance safety. The circuit breaker handle shall be in full control of the circuit breaker. The controller door shall have a locking type handle. The controller shall have externally mounted, on the enclosure flange, POWER ON and PHASE REVERSAL pilot lights, START and STOP pushbuttons and an EMERGENCY RUN mechanism. The START pushbutton and EMERGENCY RUN mechanism shall be separate units and not combined. The POWER ON pilot light shall be wired through contacts on the phase monitor to give true power on indication. Loss of power in any phase or loss of the control circuit transformer shall cause the light to go out. The PHASE REVERSAL pilot light shall be wired through contacts on the phase monitor to give true indication of incorrect phase angle relationships. The controller shall be supplied with a pressure switch having a range of psi (0-21 kg/cm 2 ) and with independent high and low pressure settings. The pressure switch shall be mounted inside the controller to prevent unauthorized adjustment and/or accidental damage. The pressure switch shall be directly pipe mounted to a solidly welded bulkhead pipe coupling without any other supporting members and field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. The adjustment knobs shall be capable of being sealed after final adjustment. The controller shall have a minimum run period timer set for ten minutes. The minimum run timer shall include an integral timer running pilot light to indicate when the run timer

38 FTA750 Specifications Limited Service Controllers is in the timing mode. Terminals shall be provided to field convert the controller from automatic to manual shutdown. Terminals shall be provided so that standard duty rated, normally open pushbutton stations can be wired to the controller. Terminals shall be provided so that a remote deluge valve contact may be wired to the controller to start the unit. The controller shall be supplied with interlock and shutdown circuits as standard. Individual PHASE FAILURE, PHASE RE- VERSAL and PUMP OPERATING alarm contacts shall be wired to terminals. These contacts shall be both normally open and normally closed and be electrically isolated for wiring to either remote alarm panels as supplied by the controller manufacturer, or for use with remote telephone dropout type alarm systems. A factory built in alarm shall be provided in the fire pump controller, requiring only 120 Volt supervisory power. This alarm shall give an audible alarm for PUMP OPERATING, PHASE FAILURE, or PUMP FAILURE and a visual alarm for SUPERVISORY VOLTAGE AVAILABLE. This alarm shall be electrically isolated from the remote alarm contacts so that 24 VDC or separate 120 VAC remote alarms can be utilized. All alarm contacts shall be rated 125 VAC maximum 10 amperes pilot duty. They shall also be suitable for direct switching of low energy alarm circuits 6 VDC minimum, 10 MA, 0.6 VA minimum. The control circuit transformer shall be of the molded winding construction type with built in molded terminals and shall be fuse protected from external loads. The fuse shall be installed on the transformer. The manufacturer shall test the entire controller assembly prior to shipment. This test shall include, but no be restricted to, each function the controller may be required to perform including remote alarms, remote start, automatic start with manual shutdown, automatic stop, remote deluge valve start, pressure drop start and manual start-stop. The manufacturer shall perform a high potential test of the controller power circuits at not less than two times the rated voltage plus 1000 volts. The controller shall be manufactured by Firetrol, Inc. SP750-01(H)

39 Specifications Fire Pump Controller Power Transfer Switches FTA Main Fire Pump Controller with Transfer Switch The main fire pump controller shall be factory assembled and wired with a power transfer switch listed by Underwriters Laboratories, Inc. for transfer switch and fire pump service. The power transfer switch shall be approved by Factory Mutual. The power transfer switch and fire pump controller shall be factory assembled, wired and tested as a single unit and shall conform to all requirements of the latest edition of NFPA 20, Centrifugal Fire Pumps and NFPA 70, National Electrical Code. Power Transfer Switch for Generator Set Emergency Power Source The power transfer switch shall be housed within the fire pump controller enclosure or in a NEMA Type 2 (IEC IP11) drip-proof enclosure attached directly to the fire pump controller. Where the power transfer switch is provided in an attached enclosure, the enclosures shall be fitted so that the assembly constitutes a single unit. The fire pump controller/power transfer switch shall be factory assembled, wired and tested as a unit prior to shipment. The power transfer switch shall include a motor rated disconnect/isolating switch capable of interrupting the motor locked rotor current. The disconnect/ isolating switch shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The disconnect/isolating switch shall be capable of being padlocked in the OFF position with up to three padlocks for installation and maintenance safety, and shall also be capable of being locked in the ON position. The enclosure door shall have a locking type handle and three point cam and roller type vault hardware. A auxiliary contact shall be provided on the transfer switch to prevent starting of the emergency generator set when the transfer switch or the main fire pump controller are being serviced. The transfer switch circuitry shall be capable of sensing both the normal power source and the emergency power source. The normal power source pickup shall be set at 95% nominal voltage. The emergency power source shall be set to pick up at 90% nominal voltage and 95% nominal frequency. All voltage sensing, frequency sensing, and time delays shall be field adjustable to accommodate individual installation requirements. The transfer signal shall be delayed for one second, delaying the transfer and engine start signals so as to compensate for momentary, normal power outages. An automatic delay of three seconds shall be provided upon transfer to or from the emergency power source to allow the motor to slow sufficiently, preventing line disturbances that could trip either the generator set or fire pump circuit breakers. The transfer switch shall have TRANSFER SWITCH NORMAL, TRANSFER SWITCH EMER- GENCY and EMERGENCY ISOLATING SWITCH OFF pilot lights, TEST and TRANSFER BYPASS switches, an audible alarm device and SILENCE ALARM pushbutton mounted on the flange of the enclosure. The power transfer switch shall be furnished with both normally open and normally closed auxiliary contacts for an engine start signal when normal power failure occurs. Auxiliary contacts shall also be provided and wired to terminals to indicate the transfer switch position. The transfer switch shall be electrically operated and mechanically held, and shall be capable of being operated by a manual transfer mechanism located on the switch. The power transfer switch shall be a Firetrol FTA975 for normal utility power and engine generator set emergency power.

40 FTA Specifications Fire Pump Controller Power Transfer Switches Power Transfer Switch for Second Utility Emergency Power Source The power transfer switch shall be housed within the fire pump controller enclosure or in a NEMA Type 2 (IEC IP11) drip-proof enclosure attached directly to the fire pump controller. Where the power transfer switch is provided in an attached enclosure, the enclosures shall be fitted so that the assembly constitutes a single unit. The fire pump controller/power transfer switch shall be factory assembled, wired and tested as a unit prior to shipment. The power transfer switch shall include a motor rated circuit breaker, operated with a single, externally mounted handle. The circuit breaker shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The circuit breaker shall be capable of being padlocked in the OFF position for installation and maintenance safety, and shall also be capable of being locked in the ON position without affecting the tripping characteristics of the circuit breaker. The enclosure door shall have a locking type handle and three point cam and roller type vault hardware. The transfer switch circuitry shall be capable of sensing both the normal power source and the emergency power source. The normal power source pickup shall be set at 95% nominal voltage. The emergency power source shall be set to pick up at 90% nominal voltage and 95% nominal frequency. All voltage sensing, frequency sensing, and time delays shall be field adjustable to accommodate individual installation requirements. The transfer signal shall be delayed for one second, delaying the transfer signal so as to compensate for momentary, normal power outages. An automatic delay of three seconds shall be provided upon transfer to or from the emergency power source to allow the motor to slow sufficiently, preventing line disturbances that could trip either the transfer switch or fire pump circuit breakers. The transfer switch shall have TRANSFER SWITCH NORMAL, TRANSFER SWITCH EMERGENCY and EMERGENCY ISOLATING SWITCH OFF pilot lights, TEST and TRANSFER BYPASS switches, an audible alarm device and SILENCE ALARM pushbutton mounted on the flange of the enclosure. To aid servicing, no indicating lights or switch devices shall be mounted on the enclosure door. Auxiliary contacts shall be provided and wired to terminals to indicate the transfer switch position. The transfer switch shall be electrically operated and mechanically held, and shall be capable of being operated by a manual transfer mechanism located on the switch. The transfer switch shall be a Firetrol FTA976 for normal utility power and second utility emergency power. Note: FTA975 and FTA976 power transfer switches are designed for use with Firetrol Limited Service Controllers model FTA750. SP975-01(A)

41 Specifications Diesel Engine Fire Pump Controllers FTA1100 Diesel Engine Fire Pump Controller The fire pump controller shall be a factory assembled, wired and tested unit and shall conform to all the requirements of the latest edition of NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection and NFPA 70, National Electrical Code. The controller shall be listed by Underwriters Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, and Canadian Standards Association CSA-C22.2, Standard for Industrial Control Equipment (culus) and approved by Factory Mutual. The controller shall be: 12 Volt 24 Volt The controller components shall be housed in a NEMA Type 2 (IEC IP11) drip-proof, wall mounted enclosure. Operator Interface The fire pump controller shall feature an operator interface with user keypad. The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and pressure conditions shall be displayed with a time and date stamp. The display shall be a 4- line, 20-character, vacuum fluorescent, dot matrix type designed to allow easy viewing from all angles and in all light conditions. The display and interface shall be NEMA rated for Type 2, 3R, 4, 4X, and 12 protection and shall be fully accessible without opening the controller door. The display and user interface shall utilize multiple levels of password protection for system security. A minimum of 3 password levels shall be provided. The display shall be capable of being programmed for any language. Digital Status/Alarm Messages The digital display shall indicate text messages for the status and alarm conditions of: Engine Run Sequential Start Time Minimum Run Time Crank/Rest Time - Cycle / Off Delay Time Remote Start Engine Fail to Start System Battery Low Low Suction Pressure Printer Error Drive Not Installed Manual Engine Crank Disk Error Disk Near Full Pressure Error The Sequential Start Timer, Minimum Run Timer/Off Delay Timer and Crank/Rest time shall be displayed as numeric values reflecting the value of the remaining time. LED Visual Indicators LED indicators, visible with the door closed, shall indicate: Main Switch in Auto Alarm Engine Fail to Start Charger Malfunction Battery #1 Trouble Battery #2 Trouble System Pressure Low Engine Running Engine Coolant Temperature High Engine Oil Pressure Low Engine Overspeed In addition to the standard alarm contacts required by NFPA 20, the digital display module shall have N.O. and N.C. contacts for remote indications of any digitally displayed alarm and N.O. and N.C. contacts for remote indication up to EIGHT, specified, programmable alarm. Data Logging The digital display shall monitor the system and log the following data: Motor Calls/Starts Total Engine Run Time Last Engine Run Time Last Engine Start Last High Water Temperature Last Low Oil Pressure Last Low Fuel Level Last Battery Charger Failure Last Battery Trouble Last Engine Overspeed Minimum Battery Voltages Maximum Battery Voltages Total Unit Run Time Minimum/Maximum System Pressure Event Recording Printer - The controller shall be equipped with a dot matrix, impact printer to record all operational and alarm events. The printer shall use standard 16# bond paper, commercially available at office supply stores. Thermal or electrostatic printers are not acceptable. The printer shall feature a mechanical take-up mechanism to prevent excessive paper buildup in the bottom of the controller during automatic operation. The printer shall automatically record all events and pressure settings. It shall allow the user to select the pressure recording frequency based upon either time or pressure deviation. If set for time based recording, the printer shall record the pressure every 30 minutes during standby and every 15 seconds during operation. Memory - The controller shall record all operational and alarm events to system memory. All events shall be time and date stamped and include an index number. The system memory shall have the capability of storing 3000 events and allow the user access to the event log via the user interface. The user shall have the ability to scroll through the stored messages in groups of 1, 10, or 100. Floppy Disk Drive - The controller shall include a floppy disk drive to save all operational and alarm events. The floppy disk drive shall have the ability to store up to 1 year s worth of data (under normal oper-

42 ating conditions) in individual monthly files. Each event shall be time and date stamped. The controller shall also have the capability to save settings and values to disk through the user interface. Communications - The controller shall feature two independent communications ports to allow connectivity to computers, modems, or building management systems. Solid State Pressure Transducer The controller shall be supplied with a solid state pressure transducer with a range of psi ( bar) ±1 psi. The solid state pressure switch shall be used for both display of the system pressure and control of the fire pump controller. Systems using analog pressure devices or mercury switches for operational control will not be accepted. The START, STOP and SYSTEM PRESSURE shall be digitally displayed and adjustable through the user interface. The pressure transducer shall be mounted inside the controller to prevent accidental damage. The pressure transducer shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. A Lamp Test feature shall be included. The user interface shall also have the ability to display the status of the system inputs and outputs. Battery Chargers The controller shall include two fully automatic, 200 amp hour, 4 step battery chargers. The chargers shall feature a qualification stage, in which the batteries are examined by the charger to insure that they are not defective and are capable of accepting a charge. The battery charger shall feature: Selectable AC Power Voltage Selectable Battery Voltage Selectable Battery Type Charge Cycle Reset Push-button The controller shall be a Firetrol brand. Operation A digitally set On Delay (Sequential Start) timer shall be provided as standard. Upon a call to start, the user interface shall display a message indicating the remaining time value of the On Delay timer. The controller shall be field programmable for manual stop or automatic stop. If set for automatic stopping, the controller shall allow the user to select either a Minimum Run Timer or an Off Delay Timer. Both timers shall be programmable through the user interface. The controller shall include an AC Power Loss start timer to start the engine in the event of AC Power failure. The controller shall be fully programmable to allow up to 8 custom alarm messages to be displayed on the user interface. A weekly test timer shall be provided as standard. The controller shall have the ability to program the time, date, and frequency of the weekly test. In addition, the controller shall have the capability to display a preventative maintenance message for a service inspection. The message text and frequency of occurrence shall be programmable through the user interface. SP

43 Specifications Alarm Panels FTA200 The alarm panel shall be a factory assembled, wired and tested unit and shall conform to all the requirements of the latest edition of NFPA 20, Centrifugal Fire Pumps and NFPA 70, National Electrical Code. The alarm panel shall be listed by Underwriters Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls, certified by CSA, Standard for Industrial Control Equipment (cul), approved by the New York City Bureau of Electrical Control and Board of Standards and Appeals and Factory Mutual. The alarm panel shall be low voltage DC and make use of printed circuit boards which can be easily wired together for future additional alarms. The alarm panel shall have individual pilot lights to indicate its alarm condition which shall remain lighted until the alarm condition has been corrected. The alarm panel shall also have an audible alarm which will sound when the alarm conditions occur and may be silenced by pressing a SILENCE ALARM push-button. Each alarm initiation shall be subsequent to any and all previous alarm conditions so that the silence push-button acknowledgment of any one alarm will not prevent the audible alarm from sounding on successive alarm conditions. The alarm panel shall have a PUSH-TO-TEST push-button for manually testing all pilot lights, audible alarms and output circuits (types A, B, F, G only). All alarm pilot lights and push-buttons shall be plainly marked for identification. The alarm panel shall be NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The alarm panel shall be a Firetrol FTA200 model. SP200-01(E)

44 Specifications Jockey Pump Controllers FTA500 The auxiliary jockey pump controller, if required and specified on the plans and specifications, shall be factory assembled, wired, and tested and specifically designed for this type of service. This controller shall be UL listed, and shall be of the same manufacturer as the main fire pump controller. The controller shall incorporate a full voltage magnetic starter, main disconnect switch, motor fuse block with fuses, HAND-OFF-AUTOMATIC selector switch and a pressure switch. The pressure switch shall have a range of psi ( bars) and have an adjustable differential range of psi ( bars). The pressure switch shall be of the diaphragm type utilizing snapaction type contacts. The pressure switch shall be mounted inside the controller to prevent any unauthorized adjustment and/or accidental damage. The pressure switch shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. A system pressure gauge shall be mounted with the pressure switch to assist in pressure switch adjustments and provide an indication of current system pressure. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. The controller shall have a running period timer to prevent too frequent automatic starting of the jockey pump motor. The timer shall be set to keep the motor in operation for at least one minute and interwired with the pressure switch. The disconnect switch shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The disconnect switch shall be capable of being padlocked in the OFF position with up to three padlocks for installation and maintenance safety. The minimum enclosure rating shall be NEMA Type 2 (IEC IP11), drip-proof. All pushbuttons, selector switches, pilot lights shall be NEMA Type 12, oiltight. Pilot lights (when specified) shall be transformer type. No pushbuttons or pilot lights shall be mounted on the enclosure door. The control circuit transformer (when specified) shall be of the molded winding construction type with built-in molded terminals and shall be fuse protected. The fuse shall be built into the transformer. The controller manufacturer, prior to shipment, shall hook up and test the jockey pump controller as a completed assembly. This test shall include, but not be restricted to, each function the controller may be required to perform including manual startstop, automatic start-stop and minimum run timing. The manufacturer shall perform a high potential test of the controller power circuits at not less than two times the rated voltage plus 1000 Volts. The controller shall be manufactured by Firetrol, Inc. SP500-01(I)

45 Specifications Jockey Pump Controllers Wye Delta Open Transition with Main Disconnect Switch FTA516 The auxiliary jockey pump controller, if required and specified on the plans and specifications, shall be factory assembled, wired, and tested and specifically designed for this type of service. This controller shall be UL listed, and shall be of the same manufacturer as the main fire pump controller. The controller shall incorporate a wye delta open transition starting method, control circuit transformer, main disconnect switch, motor fuse block, HAND-OFF-AUTOMATIC selector switch and pressure switch. The pressure switch shall have a range of psi ( bars) and have an adjustable differential range of psi ( bars). The pressure switch shall be of the diaphragm type utilizing snapaction type contacts. The pressure switch shall be mounted inside the controller to prevent any unauthorized adjustment and/or accidental damage. The adjustment knobs shall be capable of being sealed after final adjustment. The pressure switch shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. A system pressure gauge shall be mounted with the pressure switch to assist in pressure switch adjustments and provide an indication of current system pressure. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. The controller shall have a running period timer to prevent too frequent automatic starting of the jockey pump motor. The timer shall be set to keep the motor in operation for at least one minute and interwired with the pressure switch. The disconnect switch shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The disconnect switch shall be capable of being padlocked in the OFF position with up to three padlocks for installation and maintenance safety. The minimum enclosure rating shall be NEMA Type 2 (IEC IP11), drip-proof. All pushbuttons, selector switches, pilot lights shall be NEMA Type 12, oiltight. Pilot lights (when specified) shall be transformer type. No pushbuttons or pilot lights shall be mounted on the enclosure door. The control circuit transformer shall be of the molded winding construction type with built-in molded terminals and shall be fuse protected. The fuse shall be built into the transformer. The controller manufacturer, prior to shipment, shall hook up and test the jockey pump controller as a completed assembly. This test shall include, but not be restricted to, each function the controller may be required to perform including manual startstop, automatic start-stop and minimum run timing. The manufacturer shall perform a high potential test of the controller power circuits at not less than two times the rated voltage plus 1000 Volts. The controller shall be manufactured by Firetrol, Inc. SP516-01(C)

46 Blank

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage

More information

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE SBP1930-61 FTA1930 Digital Solid State Starting Electric Fire Pump Controllers Product Description Fire Pump Controllers for Business-Critical Continuity

More information

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Description Firetrol FTA1930 Digital Solid State Starting Fire Pump Controllers feature soft start, soft stop and

More information

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP1100J FTA1100J Diesel Engine Fire Pump Controllers Product Description Description Firetrol combined automatic and manual Mark

More information

Limited Service Fire Pump Controllers Features

Limited Service Fire Pump Controllers Features Must Be Installed Per Applicable Code and Manufacturers Recommendations Limited Service Fire Pump Controllers Features 1-1 FD20 Full Voltage - Limited Service with Plus Microprocessor Power I/O Board Transformers

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com

FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com FAIRBANKS NIJHUIS FIRE PUMPS www.fairbanksnijhuis.com FAIRBANKS NIJHUIS Long established as a leading fire pump manufacturer, Fairbanks Nijhuis offers a broad range of horizontal and vertical split case,

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw ,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted

More information

MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER

MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER Starting Serial No. "LA" This manual provides General Information, Installation, Operation, Maintenance and System Set-Up Information

More information

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE WHITE PAPER WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE EXPLANATION AND ASSISTANCE FOR APPLYING SOLID STATE SOFT STARTERS IN TRADITIONAL REDUCED VOLTAGE APPLICATIONS Introduction..............................................................2

More information

Transfer Equipment Controls

Transfer Equipment Controls Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment

More information

ASCO SERIES 185 Power Transfer Switches

ASCO SERIES 185 Power Transfer Switches ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

MANUAL FOR MODEL MP300 to MP700 ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS

MANUAL FOR MODEL MP300 to MP700 ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS MANUAL FOR MODEL MP300 to MP700 ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS Starting Serial No. "RA" This manual provides General Information, Installation, Operation, Maintenance and System Set-Up Information

More information

Limited Service Pump Controllers (Produced after July 18, 2006) Installation- Start Up - Service

Limited Service Pump Controllers (Produced after July 18, 2006) Installation- Start Up - Service Instruction Bulletin Limited Service Pump Controllers (Produced after July 18, 2006) Installation- Start Up - Service This instruction is a guide for personnel involved with Maintenance, Engineering and

More information

Fire Pump Controllers Remote Alarm Panels

Fire Pump Controllers Remote Alarm Panels Fire Pump Controllers Remote Alarm Panels Remote Alarm Panels 1.8 Remote Alarm Panels FDAP-M Electric... DFDAP-M Diesel... Product Specifications... 2 6 9 Features 1-1 DFDAP-M / FDAP-M Remote Alarm Panel

More information

Electric Motor Operator for: Gate Valves / Butterfly Valves / Plug Valves M&H VALVE

Electric Motor Operator for: Gate Valves / Butterfly Valves / Plug Valves M&H VALVE Electric Motor Operator for: Gate Valves / Butterfly Valves / Plug Valves M&H VALVE Almost every business day, M&H is assembling and testing valves with Electric Motor operators. Electric motor operator

More information

32VFD Variable Frequency Drives for Centrifugal Chillers

32VFD Variable Frequency Drives for Centrifugal Chillers 32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to

More information

Horizontal Split Case Fire Pumpset Electric Motor Driven 50 Hz

Horizontal Split Case Fire Pumpset Electric Motor Driven 50 Hz SERIES Horizontal Split Case Fire Pumpset Electric Motor Driven 50 Hz Selected Models INTRODUCTION Lubi offers LHCE series state-of-the-art fire pumpset with electric motor driven, horizontal split case

More information

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Instructions CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Catalog Number 2100-SD1 Description The Bulletin 2100 smoke detector unit is a 0.5 space factor unit for use in Bulletin

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142

More information

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

3) What is the difference between Insulating, Isolating, and Shielded Winding transformers? Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

Medium Voltage Motor Control Assemblies

Medium Voltage Motor Control Assemblies Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

Vilter motor starter solutions The NEW industry standard in motor starter packages

Vilter motor starter solutions The NEW industry standard in motor starter packages Vilter motor starter solutions The NEW industry standard in motor starter packages Electrical safety by design Built to Underwriters Laboratory (UL) 508A UL Standard for Safety for Industrial Control Panels.

More information

ETZGAR CONVEYOR COMPANY Controls Section v12.05

ETZGAR CONVEYOR COMPANY Controls Section v12.05 Section 7 Controls Page Description 7-1 Controls Index 7-2 Motor Data, Enclosure Rating and Abbreviations 7-3 Controls Safety Guidelines 7-4 Fixed Speed Controls Packages 7-5 Three Phase AC Variable Speed

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Guidelines on the Short Circuit Current Rating for Industrial Control Panels usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

Horizontal Split Case Fire Pumpset Diesel Engine Driven

Horizontal Split Case Fire Pumpset Diesel Engine Driven SERIES Horizontal Split Case Fire Pumpset Diesel Engine Driven Selected Models INTRODUCTION Lubi offers LHCD series state-of-the-art fire pumpset with diesel engine driven, horizontal split case pump.

More information

GTEC transfer switch open transition

GTEC transfer switch open transition GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility

More information

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING PART 1-GENERAL 1.01 DESCRIPTION A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width modulated (PWM) inverter designed for use on a standard NEMA

More information

Medical Air Systems: Scroll

Medical Air Systems: Scroll GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Application Engineering

Application Engineering Application Engineering February 2011 Electronic Unit Controller Table of Contents 1. Introduction and Features... 2 1.1 Technical Specifi cations... 3 1.2 Pressure Probe Error Bypass... 3 1.3 Bump Start...

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply

How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply GTEC Transfer switch open transition 40 2000 amp Description GTEC transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator

More information

*.ppt 11/2/2009 12:48 PM 1

*.ppt 11/2/2009 12:48 PM 1 Digital Compressor Controller *.ppt 11/2/2009 12:48 PM 1 Copeland Scroll Digital Controller Simple Controller That Enables OEM s To Use Digital Scrolls Relieves OEM From Developing Special Controllers

More information

How To Test A Power Switch On A Power Supply

How To Test A Power Switch On A Power Supply transfer switches Soft load Innovative, reliable, integrated solution Built with years of experience Powered with innovation Delivered with reliability A history of experience, innovation and reliability

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

Cam switches. Page. Overview 4-2. ON-OFF switches, main switches, maintenance switches 4-3. Changeover switches, reversing switches 4-5

Cam switches. Page. Overview 4-2. ON-OFF switches, main switches, maintenance switches 4-3. Changeover switches, reversing switches 4-5 Eaton Wiring Manual / Page Overview - ON-OFF switches, main switches, maintenance switches - Changeover switches, reversing switches - (Reversing) star-delta switches - Multi-Speed Switches - Interlock

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

Low Voltage Fuses For Motor Protection

Low Voltage Fuses For Motor Protection Code Requirements The NEC or CEC requires that motor branch circuits be protected against overloads and short circuits. Overload protection may be provided by fuses, overload relays or motor thermal protectors.

More information

World Class Manufacturer of Fire Pump Controllers. Diesel

World Class Manufacturer of Fire Pump Controllers. Diesel World Class Manufacturer of Fire Pump Controllers Diesel World Class Quality When there s a call to start a fire pump in an emergency situation, you need a fire pump controller that you can count on to

More information

Rotary Phase Converters

Rotary Phase Converters FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON

More information

Catalog January. Heavy industrial power applications Motor contactors and starters

Catalog January. Heavy industrial power applications Motor contactors and starters Catalog January Heavy industrial power applications Motor contactors and starters 2006 General contents 0 Heavy Industrial Power Applications Motor Contactors and Starters 1 Contactors and Starters, Type

More information

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030)

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) PART 1 - GENERAL SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) 1.01 SUMMARY This section describes the operation and control of a drip irrigation system. The major components

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

SMC FLEX QUICK START BULLETIN 150

SMC FLEX QUICK START BULLETIN 150 QUICK START SMC FLEX BULLETIN 0 This guide provides you with the basic information required to start up your SMC Flex controller. When reading this document, look for this symbol Step x to guide you through

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12 Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: [email protected] Cleaveland/Price Type TP-C2 Motor Operator

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Sentron Series Circuit Breakers

Sentron Series Circuit Breakers Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of

More information

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY PowerGate - Cost effective solutions for F 1 Horsepower Rating 001 1-40 HP (208V) 075 1-75 HP (480V) Input Voltage 2V 208-240V 4V 380-480V Disconnect

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

Electrical Systems - IQAN Digital Control System. IQAN Control System Components... 5.1.3

Electrical Systems - IQAN Digital Control System. IQAN Control System Components... 5.1.3 Section 5.1 Electrical Systems - IQAN Digital Control System IQAN Control System Components........................... 5.1.3 IQAN Operational Description: At Machine Startup.....................................

More information

PowerCommand Paralleling System Digital MasterControl

PowerCommand Paralleling System Digital MasterControl PowerCommand Paralleling System Digital MasterControl Description The PowerCommand Digital MasterControl is a systemlevel controller designed to interface directly with Cummins Power Generation PowerCommand

More information

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H. POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,

More information

EATON Diesel Plus Diesel Engine Fire Pump Controller

EATON Diesel Plus Diesel Engine Fire Pump Controller O & M Manual IM05805019K-002 Effective April 2015 EATON Diesel Plus Diesel Engine Fire Pump Controller Powering Business Worldwide O & M Manual IM05805019K-002 Effective April 2015 EATON Diesel Plus Diesel

More information

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in

More information

Specification Requirements DBL 700MX and 1000MX Series UPS

Specification Requirements DBL 700MX and 1000MX Series UPS Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions

More information

Continuous Power... Continuous Protection

Continuous Power... Continuous Protection Series 165 We Keep Your Power On Continuous Power... Continuous Protection An Automatic Transfer Switch helps prevent... Your business or home from losing power during bad weather or utility power equipment

More information

Contactor and Starter Ratings

Contactor and Starter Ratings Contactor and Starter Ratings Contactors and motor starters are rated according to size and type of load they are designed to handle. The National Electrical Manufacturers Association (NEMA) and the International

More information

SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial

SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMART500RT1U Description Tripp Lite's SMART500RT1U intelligent, line-interactive rack/tower uninterruptible

More information

SENTRA SERIES WATER UNITS. 30 to 300 F Process Temperatures. 1/2 to 7.5 HP Centrifugal Pumps (20-100 GPM) 10 to 34 KW Stainless Steel Heaters

SENTRA SERIES WATER UNITS. 30 to 300 F Process Temperatures. 1/2 to 7.5 HP Centrifugal Pumps (20-100 GPM) 10 to 34 KW Stainless Steel Heaters Temperature Control Units Water & Oil - 00 F Portable Chillers Air & Water-Cooled 0-70 F Central Chillers Air & Water-Cooled Packages & Modules 0-70 F Pump Tank Stations Chilled or Tower Water 00-00 gallons

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Centro-Matic Automatic Lubrication Systems System Controls

Centro-Matic Automatic Lubrication Systems System Controls Selecting the right controls for your automated lubrication system is one of the last steps in the design process. Several different models may be chosen to control power-operated pumps, depending on the

More information

AP/UP, AP/MIL Series. Magnetic Circuit Protectors

AP/UP, AP/MIL Series. Magnetic Circuit Protectors AP/UP, AP/MIL Series Magnetic Circuit Protectors Introduction Poles Configurations Operating Characteristics Delay Curves Specifications Decision Tables 71 72 75 76 77 78 79 AP/UP, AP/MIL Series Hydraulic

More information

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch

More information

Single Phase Soft Starter

Single Phase Soft Starter Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

Motor Protection Voltage Unbalance and Single-Phasing

Motor Protection Voltage Unbalance and Single-Phasing Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the

More information

LMR Plus Electric Fire Pump Controllers Custom Messages

LMR Plus Electric Fire Pump Controllers Custom Messages Instructions on how to save for uploading to the LMR Plus controller. Up to ten (10) different messages can be uploaded to the LMR Plus controller and displayed on the bottom (fourth line) of the LCD display.

More information

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps Operation and Maintenance Manual Model: 71028004 Applies to: Single Circuit Water-to-Water Twin Circuit Units Without DDC Controls MAMM WHSP

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

MCC Ratings. Voltage Rating

MCC Ratings. Voltage Rating MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control

More information

Product Guide AC Voltage Control Devices. Guide Guide. Popular Variable Transformers and AC Power Supplies. www.stacoenergy.com

Product Guide AC Voltage Control Devices. Guide Guide. Popular Variable Transformers and AC Power Supplies. www.stacoenergy.com Popular Variable Transformers and AC Power Supplies Product Guide AC Voltage Control Devices Guide Guide Your Tailored Power Solutions Provider TM Staco Energy Products Co. has been a leading manufacturer

More information

Safety automation solutions

Safety automation solutions Operating principle, characteristics Preventa safety s types XPS AV,, For and switch monitoring Operating principle Safety s XPS AV, and are used for monitoring circuits conforming to standards EN/ISO

More information

ATC-300 Automatic Transfer Switch Controller

ATC-300 Automatic Transfer Switch Controller ATC-300 Technical Data New Information Technical Data Page 2 Effective: May 2004 ATC-300 Introduction The Cutler-Hammer ATC-300 from Eaton s Electrical business is a comprehensive, multi-function, microprocessor-based

More information

Understanding Emergency Power Off (EPO)

Understanding Emergency Power Off (EPO) Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single

More information

SECTION 16260 STATIC UNINTERRUPTIBLE POWER SUPPLY SYSTEM

SECTION 16260 STATIC UNINTERRUPTIBLE POWER SUPPLY SYSTEM 1 0 1 0 1 SECTION 0 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Uninterruptible power supply (UPS) system. B. Related Sections include but are not necessarily limited to: 1. Owner s - Bidding

More information

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS)

SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS) SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS) PART 1: GENERAL 1.01 SCOPE OF WORK A. Under this section of the specifications, the contractor shall furnish and install a shop-fabricated 4X4 Dispersal

More information

2011 Industrial Catalog. DRIVES, PAC, PLCs. Industrial Catalog 2011. www.toshiba.com/ind

2011 Industrial Catalog. DRIVES, PAC, PLCs. Industrial Catalog 2011. www.toshiba.com/ind www.toshiba.com/ind 2011 Toshiba International Corporation Rev. 110504 Industrial Catalog 2011 13131 W. Little York Road Houston, TX 77041 Tel: 713-466-0277 Fax: 713-466-8773 US: 800-231-1412 Canada: 800-872-2792

More information