Wind Power Generation Power Flow and Dynamic Modeling
|
|
- Calvin Golden
- 7 years ago
- Views:
Transcription
1 Wind Power Generation Power Flow and Dynamic Modeling Vadim Zheglov EnerNex, Tennessee Eduard Muljadi NREL, Golden CO UWIG-EnerNex Modeling Workshop Albany, NY July 5-6, 2011
2 Background
3 Conventional vs. Wind Power Plant Load Other Conv. Generator Load POI or Point POI of or Interconnection to the grid Collector Collector System System Station GSU Xfmr Interconnection Transmission Line Line Large Synchronous Generator Prime Mover Individual WTGs WTGs Feeders and Laterals (overhead Feeders and Laterals (overhead and/or underground) and/or underground)
4 Power Generation Conventional vs Wind Power Plant Single or multiple large (100 MW) generators. Prime mover: steam, combustion engine non-renewable fuel affected by fuel cost, politics, and pollution restrictions. Controllability: adjustable up to max limit and down to min limit. Predictability: preplanned generation based on load forecasting, influenced by human operation based on optimum operation (scheduled operation). Located relatively close to the load center. Generator: synchronous generator Fixed speed no slip: flux is controlled via exciter winding. Flux and rotor rotate synchronously. Many (hundreds) of wind turbines (1 MW 5 MW each) Prime mover: wind (wind turbine) renewable (free, natural, pollution free) Controllability: curtailment Predictability: wind variability based on wind forecasting, influenced more by nature (wind) than human, based on maximizing energy production (unscheduled operation). Located at wind resource, it may be far from the load center. Generator: Four different types (fixed speed, variable slip, variable speed, full converter) non synchronous generation Type 3 & 4: variable speed with flux oriented controller (FOC) via power converter. Rotor does not have to rotate synchronously.
5 Power Generation Types of Wind Turbine Generator Four basic topologies based on grid interface: Type 1 conventional induction generator Type 2 wound-rotor induction generator with variable rotor resistance Type 3 doubly-fed induction generator Type 4 full converter interface Type 1 Type 2 Type 3 Type 4 generator Plant Feeders PF control capacitors generator Slip power as heat loss ac to dc Plant Feeders PF control capacitors generator ac to dc dc to ac Plant Feeders generator ac to dc dc to ac full power Plant Feeders partial power
6 Power Flow Modeling Wind Turbine Generator
7 WPP Representation POI or connection to the grid Collector System Station Interconnection Transmission Line Feeders and Laterals (overhead and/or underground) Individual WTGs Collector System Equivalent R eq jx eq B eq /2 B eq /2
8 Equivalencing
9 Equivalencing
10 Pad-Mounted Transformer
11 Reactive Compensations Represented by Separate Model Type 1 and 2 WTGs are induction machines: Several stages of capacitors banks at the WTG terminals are normally applied. Net power factor at bus 5 ~ 1.0 In power flow: modeled as fixed shunt devices WTG of type 1 is approximately PF=0.9 therefore the capacitor need is about to be ½ of the power output. example, for a 100 MW WPP at full output, Q min = Q max = -50 Mvar and add a 50 Mvar shunt capacitor at the WTG terminals. Plant level reactive compensation may still be installed to meet interconnection requirements and should be explicitly represented in power flow.
12 Reactive Compensations Type 3 and Type 4 WTGs (an estimate to start depending on the terminal voltage) These WTGs are capable of adjusting power factor to a desired value within the rating of the generator and converter. They are also capable of voltage control at the interconnection point or at its terminals. External reactive power compensation is often required to meet interconnection requirements If these WTGs do not participate in voltage control, the equivalent generator should be assigned a fixed power factor, typically unity. (i.e., Q min = Q max = 0). If the WTGs do participate in voltage control, then the equivalent generator should be assigned a reactive capability approximately equal to the aggregate WTG reactive power range (i.e., Q min = - S rated tan(cos -1 (0.90); and Q max = S rated tan(cos -1 (0.95)) ). For example, consider a 100 MW WPP that employs Type 4 WTGs with specified power factor range +/-0.95 at full output. In this example, Q min should be set to -33 Mvar and Q max should be set to +33 Mvar. At an output level below rated, the reactive limits should be adjusted according to the WTG capability curve.
13 Reactive Power Flow I + V A - ji X + V B - All Q comes from A A V A ji X I V A > V B ; B = 0 V B = 1.0 All Q comes from B B V A ji X I V A < V B ; A = 0 V B = 1.0 A = B V A = V B Q A =Q B = 0.5 I 2 X V A = 1.0 Q A =I 2 X ; Q B = 0 V A Q B =I 2 X ; Q A = 0 V A V A V A A B I ji X V B = 1.0 Equal Q (VAR) contribution I I I V B = 1.0 I V B = 1.1 Overexcited V A > V A ; Q A =I 2 X ; Q B < 0
14 Reactive Compensations POI or connection to the grid Collector System Station Turbine close to substation Interconnection Transmission Line Turbine far from substation Individual WTGs Feeders and Laterals (overhead and/or underground) X 100 > X 1 IX 100 > IX 1
15 Practical Limit of Reactive Power Output Due to collector system effects, some WTGs in the WPP will actually reach terminal voltage limits before reaching the nameplate reactive power limits. The net effect is that actual reactive power capability could be less than the nameplate. The reactive power capability can be determined by field test or careful observation of WPP performance during abnormally high or low system voltage. For example, Figure 7 shows the results of field tests to determine the practical reactive limits of a 200 MW WPP. All measurements were made at the interconnection point. Taking into account the effect of transformer and collector system impedances, the reactive power limits of the equivalent WTG can be established. Currently, there are no industry standard guidelines for testing WPP steady-state reactive limits.
16 Practical Limit of Reactive Power Output +95 and V A V POI V inf reactor I
17 Practical Limit of Reactive Power Output V A V POI V inf I
18 Detailed Vs. Single-Machine Representations 3-phase fault, all WTGs at 12 m/sec Q WT = Validation P 34.5 kv Q 34.5 kv From «Validation of the WECC Single-Machine Equivalent Power Plant», Presented DPWPG-WG Meeting at IEEE PSCE, March Jacques Brochu, Richard Gagnon, Christian Larose, Hydro Quebec
19 Validation Q WT = Detailed Vs. Single-Machine Representations 3-phase fault, different wind speed for each feeder and 2 feeders P 34.5 kv 4 feeders = Typical 2 and 4 feeders = Typical Q 34.5 kv 1 feeder From «Validation of the WECC Single-Machine Equivalent Power Plant», Presented DPWPG-WG Meeting at IEEE PSCE, March Jacques Brochu, Richard Gagnon, Christian Larose, Hydro Quebec
20 Wind Power Plant Network Infinite Bus Ideal Gen 230 kv Line 1 R1, X1, B kv Line R2, X2, B2 34.4/230 kv station transformer Rt, Xt. Station level shunt compensation 34.5 kv collector system equivalent Re, Xe, Be 4 Turbine level shunt compensation 5 0.6/34.4kV equivalent GSU transformer Rte, Xte Gen 100 MW equivalent wind turbine generator
21 Power Flow Power Flow Prepare the network (line branches, transformers, generators, and the loads). Set the level of the loads and generations. For wind turbine generator: Type 1 and 2 set the level of real power and reactive power, set the maximum and minimum limits of the real and reactive power. set the level of capacitor compensation. Type 3 and 4 set the level of real power and reactive power, and set the maximum and minimum limits of real and reactive power Run the power flow program Observe the abnormal operation (over load lines, over/under voltage buses and make adjustments as necessary. Repeat the process for different scenarios: load change, generation change, line disconnected
22 Power Flow Data
23 Power Flow Assessment Infinite Bus Ideal Gen Fault Event 230 kv Line 1 R1, X1, B kv Line R2, X2, B2 Pre fault Condition 34.4/230 kv station transformer Rt, Xt. Station level shunt compensation 34.5 kv collector system equivalent Re, Xe, Be 4 Turbine level shunt compensation 5 0.6/34.4kV equivalent GSU transformer Rte, Xte Gen 100 MW equivalent wind turbine generator Infinite Bus Ideal Gen 230 kv Line 1 R1, X1, B kv Line R2, X2, B2 34.4/230 kv station transformer Rt, Xt. Station level shunt compensation Post fault Condition 34.5 kv collector system equivalent Re, Xe, Be Turbine level shunt compensation 0.6/34.4kV equivalent GSU transformer Rte, Xte 4 5 Gen 100 MW equivalent wind turbine generator
24 Power Flow Assessment Pre fault Condition Post fault Condition
25 Dynamic Modeling Wind Turbine Generator
26 Dynamic Modeling Needs G1 Short Circuit G2 Dynamic models are needed to study the dynamic behavior of power system. Users include system planners and operators, generation developers, equipment manufacturers, researchers, and consultants. loss of line new line Wind Power Plant (WPP) models are needed to study the impact of proposed or existing wind power plants on power system and vice versa (i.e. to keep voltage and frequency within acceptable limits). Resizing WTG wind turbine generator G3 Models need to reproduce WPP behavior during transient events such as faults/clear events, generation/load tripping, etc.
27 Dynamic Modeling Check List Check List: Prepare the power flow model and run the power flow to ensure that the pre-fault and post-fault condition results are acceptable and makes sense. For wind turbine generator: Prepare the wind turbine dynamic model to be represented If the wind turbine parameters (of the WECC generic models) are not available from the turbine manufacturers, use the default data provided by the generic models available from the WECC website If the wind turbine parameters (of the WECC generic models) of the turbines to be simulated are available from the turbine manufacturers, use the latest model parameters provided. Prepare the dynamic script of the scenario of interests and run the dynamic simulation for the contingencies fault, loss of lines, etc.) to be investigated.
28 Dynamic Modeling Time Scale Switching Transients Subsynchronous Resonance Transient Stability Oscillatory Stability Long-term Dynamics cycle 1 minute 1 hour Source: Dynamic Simulation Applications Using PSLF Short Course Note GE Energy TIME (seconds)
29 Dynamic Models WECC Generic Models Generic model development in PSSE/PSLF Complete suite of prototype models implemented PSLF PSSE Model Type Type 1 Type 2 Type 3 Type 4 Generator wt1g wt2g wt3g wt4g Excitation / Controller wt2e wt3e wt4e Turbine wt1t wt2t wt3t wt4t Pitch Controller wt1p wt2p wt3p wt4p Generic model WT1 WT2 WT3 WT4 Generator WT1G WT2G WT3G WT4G El. Controller WT2E WT3E WT4E Turbine/shaft WT12T WT12T WT3T Pitch control WT3P Pseudo Gov/: aerodynamics WT12A WT12A Current focus Model validation & refinement (e.g., freq. response) Identification of generic model parameters for different manufacturers (at NREL)
30 Dynamic Models WTG Type 1 and 2 Type 1 WTG generator Plant Feeders PF control capacitors Type 2 WTG generator Slip power as heat loss ac to dc Plant Feeders PF control capacitors
31 Dynamic Models WTG Type 3 and 4 Type 3 WTG generator ac to dc dc to ac Plant Feeders Type 4 WTG generator ac to dc dc to ac full power Plant Feeders partial power
32 Single Turbine Representation Major components of WPP Equivalent Representation: Wind Turbine Generator (WTG) Equivalent and power factor correction (PFC) caps Plant level reactive power compensation if applicable Pad-mounted Transformer Equivalent Collector System Equivalent branch. Interconnection Transmission Line Station Transformer(s) Collector System Equivalent Pad-mounted Transformer Equivalent W Wind Turbine Generator Equivalent POI or Connection to the Transmission System Plant-level - Reactive Compensation PF Correction Shunt Capacitors
33 Multiple Turbine Representation In some cases, multiple turbine representation may be appropriate, for example: To represent groups of turbines from different types or manufacturers To represent a group of turbines connected to a long line within the wind plant To represent a group turbines with different control algorithms. Interconnection Transmission Line Station Transformer(s) Collector System Equivalent #1 considered to be a long/weak line feeder Collector System Equivalent #2 Pad-mounted Transformer Equivalent #2 34 MW W WTG Equivalent #2 Type 1 Pad-mounted Transformer Equivalent #1 WTG Equivalent #1 of Type 3 Voltage controlled W 21 MW POI or Connection to the Transmission System Total Output 100 MW Pad-mounted Transformer Equivalent #3 WTG Equivalent #3 of Type 3 PF=1 W PF Correction Shunt Capacitors Collector System Equivalent #3 45 MW
34 Dynamic Model Validation Prepare the simulation carefully (i.e. the correct information must be used): type of WTG, collector system impedance, transformers, power system network, input parameters to dynamic models, control flags settings set-up, reactive power compensation at the turbine level or at the plant level. Initialize the simulation based on pre-fault condition (check v, i, p, q, f, if available). Recreate the nature of the faults if possible, otherwise use the recorded data to drive the simulation and compare the measured output to the simulated output (pre-fault, during the fault, post-fault). Represent the events for the duration of observation (any changes in wind, how many turbine were taken offline due to the fault?). Prepare the data measured to match the designed frequency range of the software used. Field data is expensive to monitor, public domain data is limited, difficult to get, and quality of data needs to be scrutinized Anticipate errors in the measurement and make the necessary correction The location of simulation should be measured at the corresponding monitored data.
35 Dynamic Model Validation Example Example of Dynamic Model Simulation versus Field Data (Type 3) Interconnection Transmission Line Station Transformer(s) Collector System Equivalent Pad-mounted Transformer Equivalent POI or Connection to the Transmission System W 91% WTGs stays on after the fault. Two Turbine Representation W 9% WTGs were dropped of line during the fault. Complete Representation (136 turbines) Interconnection Transmission Line Station Transformer(s) POI or Connection to the Transmission System 136 WTGs were represented 9% WTGs were dropped of line during the fault.
36 Dynamic Model Validation Example V and f Real Power Comparison Reactive Power Comparison Voltag e (p.u.) Time (s) V f Freq uency (p.u.) Real Power (MW) P-sim-1wtg (MW) P-measured (MW) P-sim-136WTG Time (s) Reactive Power (MVAR) Time (s) Q-sim-1wtg (MVAR) Q-measured (MVAR) Q-sim-136WTG Compare P&Q measured to P&Q simulated V and f System Generator A C B W Wind Turbine Generator Equivalent Input V and f Regulated Bus
37 Dynamic Model Validation Comparison against other model (Benchmarking) Another method to validate new model is to use another model that has been validated against field measurement as a benchmark model. Several transient fault scenarios can be performed using both models, and the results can be compared. Parameter Tuning The new model and the benchmark model may have some differences in implementation, we may have to perform parameter tuning to match the output of the benchmark model. However, one should realize that the model may not be able to match the output of the benchmark model in all transient events. Parameter Sensitivity In order to limit the number of parameters that should be tuned, parameter sensitivity analysis may need to be performed. In general important parameters are varied one by one and the sensitive parameters can be tuned to match the bench mark model.
38 Dynamic Model Validation Example Example of Model to Model Comparison (Type 2 Detailed Model vs Generic Model) Terminal Voltage Real Power Reactive Power Turbine Speed
39
Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP
Grid Interconnection & Contract Development Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Submittal Instructions Prior to submitting your application and
More informationPower System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System
More informationATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only
ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category
More informationElectric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas
Electric Power Systems An Overview Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Overview Power Generation Conventional power generation Power generation from renewables
More informationSYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
More informationPhysical Address: City: State: Zip Code:
Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (For Small Generator Facilities with Electric Nameplate Capacities of 10 MW and less) Applicant Contact
More informationApplication for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection
Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (See ARSD chapter 20:10:36 for the requirements for a Tier 2, Tier 3, or Tier 4 Interconnection.) Applicant/Interconnection
More informationUnderstanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE
Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements
More informationGeneral Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING
More informationAdvanced Protection of Distribution Networks with Distributed Generators
Date:- 8 10 March 2011 Venue: University of Manchester EES-UETP Course title Advanced Protection of Distribution Networks with Distributed Generators Peter Crossley Director of the Joule Centre School
More informationEMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID
Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group
More informationPacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP
PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection
More informationLAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University
LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University PURPOSE: The purpose of this lab is to introduce PSS/E. This lab will introduce the following aspects of PSS/E: Introduction to
More informationCO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB
More informationTypical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
More informationEffective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6
Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of
More informationBasics of Electricity
Basics of Electricity Generator Theory PJM State & Member Training Dept. PJM 2014 8/6/2013 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components
More informationVoltage Stability Improvement using Static Var Compensator in Power Systems
Leonardo Journal of Sciences ISSN 1583-0233 Issue 14, January-June 2009 p. 167-172 Voltage Stability Improvement using Static Var Compensator in Power Systems Department of Electrical/Computer Engineering,
More informationSolar Power Plant Design and Interconnection
Solar Power Plant Design and Interconnection Wind & Solar Super Session July 27, 2011 E.H. Camm, S.E. Williams S&C Electric Company Outline Introduction Utility-scale PV power plant Grounding Reactive
More information300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal
May 24 MW Variable Speed Drives for Aurélie Bocquel APCG / 4BOC4 (MW-Goldisthal 1-5-24).PPT MW Variable Speed Drives for Content Major benefits of the cyclo-converter driven doubly-fed induction machines
More informationStudy to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid
Pakistan Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid Final Report: Executive Summary - November 2015 for USAID Energy Policy
More informationTURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES
SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a
More informationChapter 3 AUTOMATIC VOLTAGE CONTROL
Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide necessary direct current to the field winding of the synchronous generator.
More informationTransmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report
Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives (Required per CPUC Decision No. C10-1328) Final Report (Submitted with Public Service s 2011 ERP) Executive Summary The objective
More informationControl Strategies of the Doubly Fed Induction Machine for Wind Energy Generation Applications
Control Strategies of the Doubly Fed Induction Machine for Wind Energy Generation Applications AUTHORS Dr. Gonzalo Abad, The University of Mondragon, SPAIN. Dr. Miguel Ángel Rodríguez, Ingeteam Transmission
More information4.1.1 Generator Owner 4.1.2 Transmission Owner that owns synchronous condenser(s)
A. Introduction 1. Title: Verification and Data Reporting of Generator Real and Reactive Power Capability and Synchronous Condenser Reactive Power Capability 2. Number: MOD-025-2 3. Purpose: To ensure
More informationControl Development and Modeling for Flexible DC Grids in Modelica
Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, andreas.olenmark@one-nordic.se.
More informationWIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
More informationFederal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...
More informationSensitivity Analysis of Waveform Distortion Assessment for Wind Plants
Sensitivity Analysis of Waveform Distortion Assessment for Wind Plants Mariana B. Pereira 1, Einar V. Larsen 2, Sebastian A. Achilles 3 Energy Consulting General Electric 1 Av. Magalhães de Castro 4800,
More informationThe design and performance of Static Var Compensators for particle accelerators
CERN-ACC-2015-0104 Karsten.Kahle@cern.ch The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,
More informationRenewable Energy Grid Integration
Renewable Energy Grid Integration Jian Sun Professor and Director Grid Integration Issues Cost, Reliability & Efficiency of Grid Interface Grid Congestion, Weak Grids Variability of Renewable Production
More informationINTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012
INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably
More informationGeneration Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055
Generation Interconnection Feasibility Study Report-Web Version For PJM Generation Interconnection Request Queue Position Z1-055 South Bend Generation Project March 2014 PJM Interconnection 2014. All rights
More informationAn Overview of Wind Plant Design Standards and Common Nomenclature and Available Resources to the Power Engineer
An Overview of Wind Plant Design Standards and Common Nomenclature and Available Resources to the Power Engineer IEEE PES Wind Plant Collector System Design Working Group Session: Wind Plant Collector
More information100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
More informationCHAPTER 1 INTRODUCTION
CHAPTER 1 INTRODUCTION Power systems form the largest man made complex system. It basically consists of generating sources, transmission network and distribution centers. Secure and economic operation
More informationoperating under normal conditions supplying - isolated loads - an infinite bus - a fin1 te bus load.
Electrical Equipment - Course 230.2 GENERATORS: PART 8 LOADING 1. INTRODUCTION On completion of this lesson the trainee will be able to: 1. Explain how a small.generator or generators behave when they
More informationPI/PSLF Based Model Validation Application. Eric Bakie and Milorad Papic WECC JSIS Meeting Tempe, AZ January 21-23, 2014
PI/PSLF Based Model Validation Application Eric Bakie and Milorad Papic WECC JSIS Meeting Tempe, AZ January 21-23, 2014 1 OUTLINE 1. Background Information 2. What is PI/PSLF Based PPMV Application? 3.
More informationKeywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting, excitation system
SYNCHRONOUS MACHINES Tze-Fun Chan Hong Kong Polytechnic University, Hong Kong, China Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting,
More informationIntegration of Renewable Resources
Integration of Renewable Resources David Hawkins and Clyde Loutan PSERC Presentation October 2, 2007 Renewable Portfolio Standards Goals 2 Source: Kevin Porter; Exeter Associates, Inc Current Level of
More informationReactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION
Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?
More informationFRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003
F R C C FRCC Standards Handbook FRCC Automatic Underfrequency Load Shedding Program Revision Date: July 2003 FRCC Underfrequency Load Shedding Program Modification and Approval Process Requests to modify
More information2012 San Francisco Colloquium
2012 San Francisco Colloquium http : //www.cigre.org Advances in voltage source converter (VSC) technologies B4-6 500 kv VSC Transmission System for lines and cables B. JACOBSON, B. WESTMAN, M. P. BAHRMAN*
More informationCOMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran A_lashkarara@hotmail.com Seyed Ali NABAVI NIAKI University of Mazandaran
More informationTopics. HVDC Fundamentals
Topics HVDC Fundamentals Conventional Converters Capacitor Commutated Converters Voltage Source Converters Reactive Power Requirements System Configurations Tapping Control basics High Power Transmission
More informationGuidelines for Large Photovoltaic System Integration
1 Guidelines for Large Photovoltaic System Integration Silviu Darie, PhD(EE), PE(EE) Abstract- The paper summarizes the result of a research project funded by the Department of Energy (DOE) in collaboration
More informationSimple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
More informationSPECIFICATION COG-2007
Cleco Power LLC SPECIFICATION COG-2007 FOR PARALLEL OPPERATION OF CUSTOMER-OWNED GENERATION ON CLECO S ELECTRICAL SYSTEM Revised: March 7, 2014 CONTENTS ITEM NO. TITLE PAGE NO. 1.0 Scope 3 2.0 Policy On
More informationAdvance Electronic Load Controller for Micro Hydro Power Plant
Journal of Energy and Power Engineering 8 (2014) 1802-1810 D DAVID PUBLISHING Advance Electronic Load Controller for Micro Hydro Power Plant Dipesh Shrestha, Ankit Babu Rajbanshi, Kushal Shrestha and Indraman
More informationSmart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems
Smart Grid and Renewable Energy Grid Integration Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems 1 How Smart Can We Make This Grid? 2 Smart Grid Drivers Need to Use
More informationVariable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
More informationPerformance Analysis of Grid connected Wind Energy Conversion System with a DFIG during Fault Condition
Performance Analysis of Grid connected Wind Energy Conversion System with a DFIG during Fault Condition Sasi.C Assistant Professor Department of Electrical Engineering Annamalai University Chidambaram,
More informationSystem Protection Schemes in Eastern Denmark
System Protection Schemes in Eastern Denmark Joana Rasmussen COWI A/S, Energy Department System Protection Schemes in Eastern Denmark 1.Advanced system protection schemes are investigated and perspectives
More informationMonitoring the Operation of Wind Turbines Alex Robertson, Vestas Northern Europe
Monitoring the Operation of Wind Turbines Alex Robertson, Vestas Northern Europe Renewable Efficient Energy II Conference, 21.03.2012, Vaasa, Finland Modern wind power plant produce more data than ever
More informationAppendix N: GENERATOR DATA SHEET FOR SYNCHRONOUS GENERATORS CONNECTED TO PG&E ELECTRIC SYSTEM
Appendix N: GENERATOR DATA SHEET FOR SYNCHRONOUS GENERATORS CONNECTED TO PG&E ELECTRIC SYSTEM TECHNICAL DATA SHEET FOR SYNCHRONOUS MACHINES IN THE PG&E SYSTEM FOR POWER FLOW, TRANSIENT STABILITY, AND FAULT
More informationModern Power Systems for Smart Energy Society
Modern Power Systems for Smart Energy Society Zhe CHEN Professor, PhD Email: zch@et.aau.dk Website: http://homes.et.aau.dk/zch http://www.et.aau.dk 1 Contents Energy background in Denmark Challenges to
More informationProject description. Power Electronics for Reliable and Energy efficient Renewable Energy Systems
Project description Title: Power Electronics for Reliable and Energy efficient Renewable Energy Systems OBJECTIVES Principal objective Provide competence and decision basis for enabling reliable and energy
More informationVOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
More informationBill is the author of 15 papers and lectures on transmission lines and other power system topics.
Transmission Lines Electricity s Highway This talk starts with an explanation of Surge Impedance Loading and demonstrates how it is used for transmission line work. The St. Clair Curve widely used in transmission
More informationCost Benefit Methodology for Optimal Design of Offshore Transmission Systems
Centre for Sustainable Electricity and Distributed Generation Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems Predrag Djapic and Goran Strbac July 2008 FUNDED BY BERR URN 08/1144
More informationFACT SHEET. BSES, Delhi - Distribution Network. Power Systems Consultancy from ABB
BSES, Delhi - Distribution Network improve power quality System design for optimal techno-economic distribution network based on current and future load forecast Analysis of existing sub-transmission and
More informationPower Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E
SIEMENS Siemens Energy, Inc. Power Technology Issue 104 Modeling of TwoWinding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos GrandeMoran, Ph.D. Principal Consultant
More informationDistributed Generation and the Impact on a Distribution System. Brian Lassiter Technical Sales Engineer
Distributed Generation and the Impact on a Distribution System Brian Lassiter Technical Sales Engineer Company Overview Founded in 1989 in Abilene, TX Industry leader in Engineering and Operations Utility
More informationEnergy Systems Integration
Energy Systems Integration Dr. Martha Symko-Davies Director of Partnerships, ESI March 2015 NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy,
More informationDistribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014
1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly
More informationCircuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49
Circuits with inductors and alternating currents Chapter 20 #45, 46, 47, 49 RL circuits Ch. 20 (last section) Symbol for inductor looks like a spring. An inductor is a circuit element that has a large
More informationRenewable Energy Applications: Photovoltaic and Wind Energy Conversion Systems (WECS)
Renewable Energy Applications: Photovoltaic and Wind Energy Conversion Systems (WECS) Josep Pou Antoni Arias Page 1 Outline 1. Renewable Energy Perspectives 2. Solar Photovoltaic (PV) 3. Wind Generation
More informationPreliminary Feasibility Assessment For. The Rio Tinto Alcan to BCH Transfer Limit of 460 MW. With 50% Series Compensation on Both KMO KIT lines
Preliminary Feasibility Assessment For The Rio Tinto Alcan to BCH Transfer Limit of 460 MW With 50% Series Compensation on Both KMO KIT lines Report : ASP2010-T001 July 2010 Asset Strategy & Planning,
More informationDynamic Security Assessment in the Future Grid. Vijay Vittal Ira A. Fulton Chair Professor Arizona State University
1 Dynamic Security Assessment in the Future Grid Vijay Vittal Ira A. Fulton Chair Professor Arizona State University 2 Key requirements for DSA Need to perform DSA as close to real time as possible Need
More informationElectrical Power System Fundamentals for Non-Electrical Engineers
Electrical Power System Fundamentals for Non-Electrical Engineers by Steve Mackay EIT Micro-Course Series Every two weeks we present a 35 to 45 minute interactive course Practical, useful with Q & A throughout
More informationToward standards for dynamics in future electric energy systems The basis for plug and play industry paradigm
Toward standards for dynamics in future electric energy systems The basis for plug and play industry paradigm Marija Ilić milic@ece.cmu.edu Electric Energy Systems Group (EESG) http://www.eesg.ece.cmu.edu/,
More informationRequirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH
Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT
More informationSHE Transmission. 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015
SHE Transmission 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015 Summary This paper presents SHE Transmission s views and approach on the impact of transmission losses on the transmission
More informationMechanical and electrical rebuilding of a turbine generator for phase-shift operation
www.siemens.com/energy Mechanical and electrical rebuilding of a turbine generator for phase-shift operation POWER-GEN Europe 2013 Vienna, Austria June 04-06, 2013 Authors: Detlef Frerichs Anastassios
More informationIntegration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering
Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward
More informationMINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION
MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION REPORT ON NETWORK RELIABILITY ASPECTS OF THE CHOICE LINE VERSUS CABLE FOR
More informationTransmission Planning Standards for the Baltimore Gas & Electric Company Transmission System
Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System Prepared By: Transmission Planning Unit Baltimore Gas & Electric Company Table of Contents 1. INTRODUCTION
More informationTransient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink
Transient analysis of integrated solar/diesel hybrid power system using ATLAB Simulink Takyin Taky Chan School of Electrical Engineering Victoria University PO Box 14428 C, elbourne 81, Australia. Taky.Chan@vu.edu.au
More informationVOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES
VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES C. Schwaegerl*, M.H.J. Bollen, K. Karoui #, A. Yagmur + *Siemens AG, # Tractebel STRI AB
More informationOPTIMAL DISPATCH OF POWER GENERATION SOFTWARE PACKAGE USING MATLAB
OPTIMAL DISPATCH OF POWER GENERATION SOFTWARE PACKAGE USING MATLAB MUHAMAD FIRDAUS BIN RAMLI UNIVERSITI MALAYSIA PAHANG v ABSTRACT In the reality practical power system, power plants are not at the same
More informationRecord Specification and File Format for Specifying Contingency Definitions and Remedial Actions Schemes
Record Specification and File Format for Specifying Contingency Definitions and Remedial Actions Schemes Date : October 22, 2013 December 6, 2013 January 21, 2015 August 28, 2015 November 6, 2015, November
More informationSession 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile
Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile Michael Coddington National Renewable Energy Laboratory Golden, Colorado,
More informationAC Power. by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department
by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department EE 209 Fundamentals of Electrical and Electronics Engineering, Prof. Dr. O. SEVAİOĞLU, Page 1 Voltage Waveform Consider the
More informationImpact of Distributed Generation on Voltage Profile in Deregulated Distribution System
Impact of Distributed Generation on Voltage Profile in Deregulated Distribution System W. EL-KHATTAM M. M. A. SALAMA Electrical & Computer Engineering, Waterloo University, Ontario, Canada Abstract: Due
More informationRule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
More informationPowerWorld Simulator
PowerWorld Simulator Quick Start Guide 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com Purpose This quick start guide is intended to
More informationIntroduction to PowerWorld Simulator: Interface and Common Tools
Introduction to PowerWorld Simulator: Interface and Common Tools 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com Fault Analysis Analysis
More informationFrequency Response: Basics
GE Energy Impact of Frequency Responsive Wind Plant Controls on Grid Performance Nicholas Miller Kara Clark Miaolei Shao December 20, 2010 Frequency Response: Basics Grid must maintain balance between
More informationDC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters
More informationPSS SINCAL - Overview -
PSS SINCAL - Overview - PTI Day Buenos Aires, October 19/20, 2010 Dr. Michael Schwan,, Siemens PTI (Germany) www.siemens.com/energy/power-technologies PSS SINCAL Overview Page 3 Network Calculation Software
More informationTHE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.
THE PER-UNIT SYSTEM An interconnected power system typically consists of many different voltage levels given a system containing several transformers and/or rotating machines. The per-unit system simplifies
More informationReactive Power Generation by DFIG Based Wind Farms with AC Grid
Reactive Power Generation by DFIG Based Wind Farms with AC Grid Connection I. Erlich, M. Wilch and C. Feltes UNIVERSITY DUISBURG-ESSEN Bismarckstr. 81 D-47057 Duisburg Tel.: +49 / (203) 379 3437 Fax: +49
More informationDistributed Flexible AC Transmission System (D FACTS) Jamie Weber. weber@powerworld.com, 217 384 6330 ext. 13
Distributed Flexible AC Transmission System (D FACTS) Jamie Weber weber@powerworld.com, 217 384 6330 ext. 13 Slide Preparation: Kate Rogers Davis kate@powerworld.com, 217 384 6330, Ext 14 2001 South First
More informationMICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS
MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS C.P. ION 1 C. MARINESCU 1 Abstract: This paper presents a new method to supply single-phase loads using a three-phase induction
More informationQ140 Cluster Addendum
Cluster Addendum 1. INTRODUCTION This Interconnection Customer (IC), submitted a Small Generator Interconnection Request (IR) to Arizona Public Service Company (APS) for their proposed project, located
More informationOperating Security Standards
Version 1.1 Prishtina December 2009 TABLE OF CONTENTS 1 Introduction... 1 2 Definitions... 1 2.1 General...1 2.1.2 Kosovo Transmission System...1 2.1.3 Circuit...2 2.1.4 The N-1 Criterion...2 2.1.5 Normal
More information2012 San Francisco Colloquium
2012 San Francisco Colloquium http : //www.cigre.org HVDC and Power Electronic Systems for Overhead Line and Insulated Cable Applications B4-8 Trans Bay Cable A Breakthrough of VSC Multilevel Converters
More informationPOWER TRANSMISSION FROM OFFSHORE WIND FARMS
POWER TRNSMISSION FROM OFFSHORE WIND FRMS Thorsten Völker University of pplied Sciences Bremerhaven Germany BSTRCT The future for wind power generation in Germany is offshore wind energy. The preferred
More informationWind Turbine Operation in Power Systems and Grid Connection Requirements
Wind Turbine Operation in Power Systems and Grid Connection Requirements A. Sudrià 1, M. Chindris 2, A. Sumper 1, G. Gross 1 and F. Ferrer 1 1 Centre for Technological Innovation in Static Converters and
More information