1 SECTION CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 SUMMARY A. Provide complete, fully operational fans where indicated on Drawings. B. Section Includes: 1. Hooded propeller roof fans 2. Upblast centrifugal roof fans 3. Downblast centrifugal roof fans 4. Upblast centrifugal roof fans Grease exhaust 5. Centrifugal filtered supply fans 6. Inline Fans 7. Ceiling Mounted High Volume, Low Speed Fans C. Related Sections: 1.2 SUBMITTALS 1. Section HVAC Duct and Casings - Ducts: Product requirements for hangers for placement by this section. 2. Section Air Duct Accessories: Product requirements for duct accessories for placement by this section. 3. Coordinate work in this Section with Division 7. A. Provide line-by-line specification review annotated to certify compliance or deviation. B. Shop Drawings: Indicate size and configuration of fan assembly, mountings, weights, ductwork and accessory connections. C. Product Data: Submit data on each type of fan and include accessories, fan curves with specified operating point plotted, power, RPM, sound power levels for both fan inlet and outlet at rated capacity, electrical characteristics and connection requirements. D. Manufacturer's Installation Instructions: Submit fan manufacturer s instructions. E. Manufacturer's Certificate: Certify products meet or exceed specified requirements. 1.3 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: Submit instructions for lubrication, motor and drive replacement, spare parts list, and wiring diagrams. 1.4 QUALITY ASSURANCE A. Performance Ratings: Conform to AMCA 210 and bear AMCA Certified Rating Seal
2 B. Sound Ratings: AMCA 301, tested to AMCA 300, and bear AMCA Certified Sound Rating Seal. C. UL Compliance: UL listed and labeled, designed, manufactured, and tested in accordance with UL 705 and UL 762 for kitchen exhaust. D. Balance Quality: Conform to AMCA 204. E. Energy Recovery Unit Wheel Energy Transfer Rating: Meet ARI WARRANTY A. Furnish one (1) year manufacturer s warranty for fans. Warranty shall begin from date of Certificate of Substantial Completion. Warranty start date from shipment or start up will not be acceptable. B. The mechanical sub contractor is responsible for all interim warranty timelines from date of delivery to substantial completion. 1.6 EXTRA MATERIALS A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. Spare materials shall be provided by equipment manufacturer and not by the installing mechanical contractor. PART 2 - PRODUCTS 1. Fan Belts: Two (2) sets for each belt-driven fan. 2.1 HOODED PROPELLER ROOF FANS B. Unit shall be a low profile, hooded, roof mounted, belt driven or direct drive, propeller supply ventilator. Coordinate drive with fan schedule on drawings. C. Fan shall be constructed in accordance with UL 705. Fan shall bear the AMCA certified ratings seal for air performance. D. Construction: The fan shall be of bolted and welded construction utilizing corrosion resistant fasteners. The motor, bearings and drives shall be mounted on a welded tubular steel power assembly. The power assembly shall be rigidly secured to the fan housing. The powder coated steel fan housing shall include a minimum 14 gauge base with integral spun venturi and continuously welded or application of butyl tape to inside of the curb cap for maximum leak protection. The fan shall be enclosed with a minimum 18 gauge galvanized steel hood bolted to the fan housing. The hood shall have a removable
3 top cap to allow unobstructed access to the motor and power assembly without removing entire hood. The fan outlet shall be protected from entry of foreign material by ½" x ½" galvanized steel screen. Unit shall bear an engraved aluminum nameplate and shall be shipped in ISTA certified transit tested packaging. E. Coating: All ungalvanized steel fan components shall be treated with an electrostatically applied, baked polyester powder coating. Each component shall be subject to a five stage environmentally friendly wash system, followed by a minimum 2 mil thick baked powder finish. Paint must exceed 1,000 hour salt spray under ASTM B117 test method. F. Propeller: Propeller shall be a high-efficiency fabricated steel design with blades securely fastened to a minimum 7 gauge steel hub. The hub shall be keyed and locked to the fan shaft utilizing two setscrews. Propeller shall be balanced in accordance with AMCA Standard , Balance Quality and Vibration Levels for Fans. G. Motor: Motor shall be heavy duty type with permanently lubricated sealed ball bearings and furnished at the specified voltage, phase and enclosure. H. Bearings: Bearings shall be designed and tested specifically for use in air handling applications. Construction shall be heavy duty regreasable ball type in a cast iron housing selected for a minimum L50 life in excess of 200,000 hours at maximum cataloged operating speed. I. Belts and Drives: Belts shall be oil and heat resistant, non-static type. Drives shall be precision machined cast iron type, keyed and securely attached to the wheel and motor shafts. Drives shall be sized for 150% of the installed motor horsepower. The variable pitch motor drive must be factory set to the specified fan RPM. J. Roof Curb:12 inch high of 18 gauge galvanized steel construction with continuously welded seams, built-in cant strips, 1-1/2 inch insulation, damper tray, hinged curb adapter for access to dampers, and factory installed nailer strip. Coordinate installation with Division 7. K. Accessories: 1. Motorized damper in damper tray of roof curb. Actuator shall be same voltage as motor in fan. Damper shall energize fan through integral end switch. 2. Disconnect Switch: Coordinate with Division 26. Provide factory wired disconnect switch on 120v motor only. Factory provided disconnect switches shall be rated for outdoor use. Three phase combination disconnect/starter shall be provided by Division Direct drive units shall be provided with motor speed control option. 2.2 UPBLAST CENTRIFUGAL ROOF FANS
4 B. Fan shall be a spun aluminum, roof mounted, belt driven or direct drive, upblast centrifugal ventilator. Coordinate drive with fan schedule on drawings. C. Fan shall be constructed in accordance with UL 705. Fan shall bear the AMCA certified ratings seal for air performance. D. Construction: The fan shall be of bolted and welded construction utilizing corrosion resistant fasteners. The spun aluminum structural components shall be constructed of minimum 16 gauge marine alloy aluminum, bolted to a rigid aluminum support structure. The aluminum base shall have sealed curb cap corners by continuous weld or application of butyl tape to inside of the curb cap for maximum leak protection. The windband shall have a rolled bead for added strength. A two piece top cap shall have stainless steel quick release latches to provide access into the motor compartment without the use of tools. An integral conduit chase shall be provided into the motor compartment to facilitate wiring connections. The motor, bearings and drives shall be mounted on a minimum 14 gauge steel power assembly, isolated from the unit structure with rubber vibration isolators. These components shall be enclosed in a weather-tight compartment, separated from the exhaust airstream. Lifting lugs shall be provided to help prevent damage from improper lifting. Unit shall bear an engraved aluminum nameplate and shall be shipped in ISTA certified transit tested packaging. E. Wheel: Wheel shall be centrifugal backward inclined, constructed of 100 percent aluminum, including a precision machined cast aluminum hub. Wheel inlet shall overlap an aerodynamic aluminum inlet cone to provide maximum performance and efficiency. Wheel shall be balanced in accordance with AMCA Standard , Balance Quality and Vibration Levels for Fans. F. Motor: Motor shall be heavy duty type with permanently lubricated sealed ball bearings and furnished at the specified voltage, phase and enclosure. G. Bearings: Bearings shall be designed and individually tested specifically for use in air handling applications. Construction shall be heavy duty regreasable ball type in a cast iron pillow block housing selected for a minimum L50 life in excess of 200,000 hours at maximum cataloged operating speed. H. Belts & Drives: Belts shall be oil and heat resistant, non-static type. Drives shall be precision machined cast iron type, keyed and securely attached to the wheel and motor shafts. Drives shall be sized for 150 percent of the installed motor horsepower. The variable pitch motor drive must be factory set to the specified fan RPM. I. Roof Curb: 12 inch high of 18 gauge galvanized steel construction with continuously welded seams, built-in cant strips, 1-1/2 inch insulation, damper tray, hinged curb adapter for access to dampers, and factory installed nailer strip. Coordinate installation with Division 7. J. Accessories: 1. Motorized damper in damper tray of roof curb. Actuator shall be same voltage as motor in fan. Damper shall energize fan through integral end switch. 2. Disconnect Switch: Coordinate with Division 26. Provide factory wired disconnect switch on 120v motor only. Factory provided disconnect switches shall be rated for outdoor use. Three phase combination disconnect/starter shall be provided by Division
5 3. Direct drive units shall be provided with motor speed control option. 2.3 DOWNBLAST CENTRIFUGAL ROOF FANS B. Fan shall be a spun aluminum, roof mounted, belt driven, downblast centrifugal ventilator. C. Fan shall be constructed in accordance with UL 705. Fan shall bear the AMCA certified ratings seal for air performance. D. Construction: The fan shall be of bolted and welded construction utilizing corrosion resistant fasteners. The spun aluminum structural components shall be constructed of minimum 16 gauge marine alloy aluminum, bolted to a rigid aluminum support structure. The aluminum base shall have sealed curb cap corners by continuous weld or application of butyl tape to inside of the curb cap for maximum leak protection. The windband shall have a rolled bead for added strength. A two piece top cap shall have stainless steel quick release latches to provide access into the motor compartment without the use of tools. An integral conduit chase shall be provided into the motor compartment to facilitate wiring connections. The motor, bearings and drives shall be mounted on a minimum 14 gauge steel power assembly, isolated from the unit structure with rubber vibration isolators. These components shall be enclosed in a weather-tight compartment, separated from the exhaust airstream. Lifting lugs shall be provided to help prevent damage from improper lifting. Unit shall bear an engraved aluminum nameplate and shall be shipped in ISTA certified transit tested packaging. E. Wheel: Wheel shall be centrifugal backward inclined, constructed of 100 percent aluminum, including a precision machined cast aluminum hub. Wheel inlet shall overlap an aerodynamic aluminum inlet cone to provide maximum performance and efficiency. Wheel shall be balanced in accordance with AMCA Standard , Balance Quality and Vibration Levels for Fans. F. Motor: Motor shall be heavy duty type with permanently lubricated sealed ball bearings and furnished at the specified voltage, phase and enclosure. G. Bearings: Bearings shall be designed and individually tested specifically for use in air handling applications. Construction shall be heavy duty regreasable ball type in a cast iron pillow block housing selected for a minimum L50 life in excess of 200,000 hours at maximum cataloged operating speed. H. Belts & Drives: Belts shall be oil and heat resistant, non-static type. Drives shall be precision machined cast iron type, keyed and securely attached to the wheel and motor shafts. Drives shall be sized for 150 percent of the installed motor horsepower. The variable pitch motor drive must be factory set to the specified fan RPM
6 I. Roof Curb: 12 inch high of 18 gauge galvanized steel construction with continuously welded seams, built-in cant strips, 1-1/2 inch insulation, damper tray, hinged curb adapter for access to dampers, and factory installed nailer strip. Coordinate installation with Division 7. J. Accessories: 1. Motorized damper in damper tray of roof curb. Actuator shall be same voltage as motor in fan. Damper shall energize fan through integral end switch. 2. Disconnect Switch: Coordinate with Division 26. Provide factory wired disconnect switch on 120v motor only. Factory provided disconnect switches shall be rated for outdoor use. Three phase combination disconnect/starter shall be provided by Division Direct drive units shall be provided with motor speed control option. 2.4 UPBLAST CENTRIFUGAL ROOF FANS - GREASE EXHAUST B. Unit shall be a low profile, hooded, roof mounted, belt driven or direct drive, propeller supply ventilator. Coordinate drive with fan schedule on drawings. C. Unit shall be constructed in accordance with UL 762. Fan shall bear the AMCA certified ratings seal for sound and air performance. D. Construction: The fan shall be of bolted and welded construction utilizing corrosion resistant fasteners. The aluminum base shall have sealed curb cap corners by continuous weld or application of butyl tape to inside of the curb cap for maximum leak protection. The windband shall have a rolled bead for added strength. A two piece top cap shall have stainless steel quick release latches to provide access into the motor compartment without the use of tools. An external wiring compartment to facilitate wiring connections. The motor, bearings and drives shall be mounted on a 14 gauge steel power assembly. These components shall be enclosed in a weather-tight compartment, separated from the exhaust airstream. A one (1) inch thick, three pound density foil back heat shield shall be utilized to protect the motor and drive components from excessive heat. Lifting lugs shall be provided to help prevent damage from improper lifting. Unit shall bear an engraved aluminum nameplate and shall be shipped in ISTA certified transit tested packaging. E. Wheel: Wheel shall be centrifugal backward inclined, constructed of 100 percent aluminum, including a precision machined cast aluminum hub. Wheel inlet shall overlap an aerodynamic aluminum inlet cone to provide maximum performance and efficiency. F. Motor: Motor shall be heavy duty type with permanently lubricated sealed ball bearings and furnished at the specified voltage, phase and enclosure
7 G. Bearings: Heavy duty regreasable ball type in a cast iron pillow block housing selected for a minimum L50 life in excess of 200,000 hours. H. Belts and Dives: Belts shall be oil and heat resistant, non-static type. Drives shall be precision machined cast iron type, keyed and securely attached to the wheel and motor shafts. Drives shall be sized for 150 percent of the installed motor horsepower. The variable pitch drive must be factory set to the specified fan RPM. I. Roof Curb: 12 inch high of 18 gauge galvanized steel construction with continuously welded seams, built-in cant strips, 1-1/2 inch insulation, damper tray, hinged curb adapter for access to dampers, and factory installed nailer strip. Coordinate installation with Division 7. J. Accessories: 1. Disconnect Switch: Coordinate with Division Direct drive units shall be provided with motor speed control option. 3. Gravity actuated back-draft damper with adjustable counter weight. 4. Provide minimum 10 tall vented curb extension. 5. Provide grease trap with drain connection. 6. Provide heat baffle. 7. Provide Clean-Out Port. 2.5 CENTRIFUGAL FILTERED SUPPLY FAN - KITCHEN HOOD B. Unit shall be a low profile, hooded, roof mounted, belt driven or direct drive, propeller supply ventilator. Coordinate drive with fan schedule on drawings. C. Description: Fan shall be a side intake, roof mounted, belt driven, centrifugal filtered supply fan. D. Fan shall be constructed in accordance with UL 705. Fan shall bear the AMCA certified ratings seal for air performance. E. Construction: The fan shall be of bolted construction utilizing corrosion resistant fasteners. Housing shall be minimum 18 gauge galvanized steel, bolted to a minimum 16 gauge steel fan base with pre-punched mounting holes. Unit shall be provided with an insulated top cover and 1" washable permanent aluminum filter. Internal blower and motor assembly shall be mounted on rubber vibration isolators. Unit shall bear an engraved aluminum nameplate and shall be shipped in ISTA certified transit tested packaging. F. Wheel: Wheel shall be DWDI centrifugal forward curved type, constructed of painted steel. Wheel shall be balanced in accordance with AMCA Standard , Balance Quality and Vibration Levels for Fans
8 G. Motor: Motor shall be heavy duty type with permanently lubricated sealed ball bearings and furnished at the specified voltage, phase and enclosure. H. Bearings: Bearings shall be permanently lubricated, sealed ball type selected for a minimum L50 life in excess of 200,000 hours at maximum cataloged operating speed. I. Belts and Drives: Belts shall be oil and heat resistant, non-static type. Drives shall be precision machined cast iron type, keyed and securely attached to the wheel and motor shafts. Drives shall be sized for 150% of the installed motor horsepower. The variable pitch motor drive must be factory set to the specified fan RPM. J. Roof Curb: 12 inch high of 18 gauge galvanized steel construction with continuously welded seams, built-in cant strips, 1-1/2 inch insulation, damper tray, hinged curb adapter for access to dampers, and factory installed nailer strip. Coordinate installation with Division 7. K. Accessories: 2.6 INLINE FANS 1. Motorized damper in damper tray of roof curb. Actuator shall be same voltage as motor in fan. Damper shall energize fan through integral end switch. 2. Disconnect Switch: Coordinate with Division 26. Provide factory wired disconnect switch on 120v motor only. Factory provided disconnect switches shall be rated for outdoor use. Three phase combination disconnect/starter shall be provided by Division Direct drive units shall be provided with motor speed control option. B. Fan shall be a duct mounted, centrifugal, belt driven or direct drive, inline type supply or exhaust ventilator. C. All fans shall bear the AMCA Certified Ratings Seal for both sound and air performance. D. Construction: The fan housing shall be of the square design constructed of heavy gauge galvanized steel and shall include square duct mounting collars. Fan construction shall include two removable access panels located perpendicular to the motor mounting panel. The access panels must be of sufficient size to permit easy access to all interior components. Each fan shall bear a permanently affixed manufacturer s nameplate containing the model number and individual serial number for future identification. E. Coating: For fans serving Natatoriums or corrosive environments provide epoxy coating on all inside and outside surfaces including fan wheel and pulley. F. Wheel: The fan wheels shall be centrifugal backward inclined, constructed o f aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced
9 G. Motor: Motors shall be heavy duty ball bearing type, carefully matched to the fan load and furnished at the specified voltage, phase, and enclosure. Motor Pulleys shall be adjustable for system balancing. H. Bearings: Precision ground and polished shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum catalogued operating speed. I. Belts & Drives: Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to the wheel and motor shafts. J. Accessories: 1. Disconnect Switch: Coordinate with Division 26. Provide factory wired disconnect switch on 120v motor only. Three phase combination disconnect/starter shall be provided by Division Gravity actuated back-draft damper with adjustable counter weight. 3. Direct drive units shall be provided with motor speed control option. 4. Companion Flanges: For inlet and outlet duct connections. 5. Fan Guards: 1/2 by 1-inch mesh of galvanized steel in removable frame. Provide guard for inlet or outlet for units not connected to ductwork. 6. Motor and Drive Cover (Belt Guard): Epoxy-coated steel. 2.7 CEILING MOUNTED HIGH VOLUME, LOW SPEED FANS 1. Big Ass Fans B. Construction: Fan shall be ETL certified and built pursuant to construction guidelines set forth by UL standards 507, 746C, 1004, 1917 and CSA standards 22.2 No. 4, 22.2 No. 17, 22.2 No. 113, 22.2 No. 100, 22.2 No The fan shall be designed to move an effective amount of air for cooling and destratification in commercial applications. The fan shall incorporate a direct drive system designed specifically for high volume, low speed fans to ensure silent operation. The sound levels from the fan operating at maximum speed shall not exceed 40 dba (measured 20 or below the blades and 20 or horizontally from the center of the fan). C. Air Foils: The fan shall be equipped with ten (10) high volume, low speed airfoils or precision extruded aluminum alloy. Each airfoil shall be of the high performance TEC design. The airfoils shall be connected by means of two (2) locking bolts per airfoil. The airfoils shall be connected to the hub and interlocked with stainless steel retainers. D. Winglets: The fan shall be equipped with ten (10) TEC winglets designed to redirect outward airflow into downward airflow, thereby enhancing the efficiency and effectiveness of the fan. The winglets shall be die cast aluminum. Winglets shall be attached at the tip of each airfoil. The standard color of the winglets shall be super durable black. E. Trim: The fan shall be equipped with trim inserts that nest between the hub and the inner edge of the foil. The trim inserts (10 each) shall provide a cleaner fit between the airfoils and the hub to help reduce the drag, turbulence and the noise. Trim inserts shall be black
10 F. Motor: The fan motor shall be a permanent magnet brushless motor rated for continuous operation at maximum speed with the capability of modulating the fan speed from 0-100% without the use of a gearbox or other mechanical means of control. The motor shall operate from any voltage ranging from VAC, 1 PH, 60 HZ, without requiring adapters or customer selection. The motor shall be non-ventilated, heat sink design with the capability of continuous operation in -40 to 131 F ambient conditions. G. Hub: The fan hub shall be a single precision permanent mold casting of aluminum alloy for high strength and light weight. The hub shall be precision machined to achieve a well balanced and solid rotating assembly. The hub shall incorporate ten (10) safety pins made from aluminum that will secure the hub/airfoil assembly in case of shaft failure. The pins shall be attached to the body of the hub using the bolts. H. Mounting System: The fan mounting system shall be designed for quick and secure installation from a structural support beam. All components in the mounting system shall be of welded construction using steel no less than 3/16 thick and be powder coated for appearance and resistance to corrosion. All mounting bolts shall be SAE Grade 8 or equivalent. As an option, mounting components may be colored; confirm with architect/owner. I. Safety Cables: The fan shall be equipped with upper and lower safety cables. The upper safety cable shall provide an additional means of securing the fan assembly to the building structure. The lower safety cable shall provide an additional means of securing the motor unit to the mounting system. All safety cables shall be 3/16 diameter and fabricated out of 7x19 stranded galvanized steel. The loops must be secured with swaged Nicopress fittings, pre-loaded and tested to 3,000 lb f. Field construction of safety cables in not permitted. J. Controller: The controller shall be incorporated into the fan assembly. The controller shall be factory programmed to minimize starting and breaking torques. The controller shall be housed in an enclosure to prevent accidental contact with the enclosed equipment and to prevent entry of unwanted substances. K. Wall Control: The fan shall be equipped with a remote wall control. The wall control shall be capable of mounting to a standard receptacle by means of a mounting plate (which shall be included with the wall mounted device). The wall controller shall be equipped with a 1.8 TFT-LCD screen and user interface for controlling the fans direction, operation and speed. Communication with the fan drive and controller shall be by a standard, commercially available CAT-5 (or higher) Ethernet cable that is field installed and provided by the installer. A 5 patch cable shall be provided to test and verify communication signals locally prior to connecting the remote connection cable. L. Warranty: The manufacturer shall replace any products or components defective in material or workmanship, free of charge to the customer (including all transportation charges). M. Accessories: 1. Provide clear lockable enclosure for wall controller with two sets of keys
11 PART EXAMINATION A. Verify roof curbs are installed and dimensions are as shown on shop drawings. 3.2 INSTALLATION A. Secure roof fans with cadmium plated steel lag screws to roof curb structure. B. Install power ventilators level and plumb. C. Install dampers in roof curb damper tray. D. Provide hinged curb adapter to permit access to dampers and duct connection. E. Install safety screen where inlet or outlet is exposed. F. Provide sheaves required for final air balance. G. Install units with clearances for service and maintenance. H. Label units according to requirements specified in Section "Identification for HVAC Piping and Equipment." 3.3 MANUFACTURER'S FIELD SERVICES A. Furnish services of factory trained representative for minimum of one (1) day to start-up, calibrate controls, and instruct Owner on operation and maintenance. 3.4 CLEANING A. Vacuum clean inside of fan cabinet. 3.5 DEMONSTRATION A. Demonstrate fan operation and maintenance procedures. 3.6 PROTECTION OF FINISHED WORK A. Do not operate fans until ductwork is clean, bearings are lubricated, and fan has been test run under observation. END OF SECTION
SECTION 23 34 13. A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer.
PART 1 GENERAL SECTION 23 34 13 HVAC FANS 1.01 SUMMARY A. Section Includes: 1. Exhaust fans. 2. Transfer fans. B. Related Documents: 1. Drawings and general provisions of the Contract, including General
More informationRecirculating Roof Fans Models ESRMD, ESRMDF and ERD
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Four-Way Fan Exhaust Supply Mix Recirculate BUILDING VALUE IN AIR. October 2005 Recirculating Roof Fans Exhaust/Supply/Recirculation/Mix Model ESRMD
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationUPBLAST & HOODED PROPELLER ROOF VENTILATORS
The Industrial Choice. Model D53 / B53 Model HD53 / HB53 UPBLAST & HOODED ELLER ROOF VENTILATORS Direct Drive & Belt Driven Model D53 / B53 Upblast Exhaust Fans Model HD53 / HB53 Hooded Supply & Exhaust
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationUNIVERSITY OF ROCHESTER DESIGN STANDARDS OCTOBER 18, 2013
SECTION 233416 - CENTRIFUGAL HVAC FANS PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. Fans shall be dynamically balanced and factory-tested and certified in accordance with applicable AMCA test codes. All
More informationTube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller
Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller Belt Drive Low and High Pressure October 009 Features Page Header Tube Axial Roof Upblast Fans Greenheck belt drive tube axial upblast
More informationROOF TOP MOUNTED Air Handler Specification
ROOF TOP MOUNTED Air Handler Specification PART 1: GENERAL (Model RT) Mechanical Specification 1.01 WORK INCLUDED A. Provide complete air handling unit(s) suitable for outdoor installation. Contractor
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationSECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
More informationCooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
More informationCE6500 Energy Recovery Ventilator
ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge
More informationSECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
More informationRoof Curbs, Extensions and Equipment Supports
Roof s, Extensions and Equipment Supports December 2012 Roof Page s, Header Extensions and Equipment Supports Table of Contents Model GPI Standard and Optional Construction Features... 3 Model Number Code....
More informationCommercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
More informationInstallation. Centrifugal Roof and Wall Exhausters
This publication contains the installation, operation and maintenance instructions for standard units of the AC- Centrifugal Roof and Wall Exhausters. ACE-D / ACE-B ACW-D / ACW-B / ACW-HP / ACW-XP ACRU-D
More informationSECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
More informationMechanical Rooftop Custom Capabilities
Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition
More informationSECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationInstallation Manual CLIFC Fan & Coil Variable Speed
Installation Manual CLIFC Fan & Coil Variable Speed General Description GENERAL DESCRIPTION FANS EQUIPMENT Totally Factory assembled within the unit all piping, wiring, and required controls for operation
More informationPump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationDESIGN CLARIFICATION (DC)
DESIGN CLARIFICATION (DC) Owner: Victor Valley Wastewater Reclamation Authority Date: 03/03/2015 Contractor: W M Lyles Carollo Project No.: 8299A.20 Project Name: Subregional WRPs DC No.: 001 DC Title:
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationSPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION 238221 - BLOWER COIL UNITS
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
More informationAir-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
More informationA. Section includes air conditioning units, controls and control panels.
SECTION 23 81 23 - COMPUTER-ROOM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes air conditioning units, controls and control panels. 1.2 REFERENCES A. Air-Conditioning, Heating, and
More informationCEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
More informationVXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6
- B 1 Product Detail Engineering Data... B2 Structural Support... B6 Engineering Specifications... B9 - B 2 Engineering Data REMARK: Do not use for construction. Refer to factory certified dimensions &
More informationSPECIFICATIONS FOR BOON EDAM TOMSED MODEL TUT-65TMB
SPECIFICATIONS FOR BOON EDAM TOMSED MODEL TUT-65TMB PRODUCT DESCRIPTION: BOON EDAM TOMSED MODEL TUT-65TMB STAINLESS STEEL BARCODE SCANNING ELECTRONIC REGISTERING TURNSTILE SCOPE OF OPERATION: A. The TUT-65TMB
More informationTOP RUNNING SINGLE GIRDER BRIDGE CRANE
SECTION 14630 TOP RUNNING SINGLE GIRDER BRIDGE CRANE 1.01 SUMMARY PART 1- GENERAL A. The work required under this section shall include the designing, manufacturing, shipping, installing and field testing
More informationRPV - RP - RA air handling units
APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP
More informationBC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
More informationINSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional
More informationUtility Distribution Systems
Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date
More informationTube Type Oil Skimmer Comparison
Process Overview- Tube Type Oil Skimmers Oil flows down the face of the skimmer and into a sludge pan that is plumbed to a barrel. Model BG01 & BG34 or 6V Oil Skimmer 1.0 or 3/4 Diameter Collector Tube
More informationA. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.
SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel
More informationBUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
More informationP.A.L. S SPECIFICATIONS
PART 1- GENERAL 1.1 SCOPE To furnish all labor, materials and equipment necessary or required to complete the installation of the lift as indicated on the Drawings and Specifications. This specification
More informationVentilation Solutions Kitchens. fantech
Ventilation Solutions Kitchens 2 Kitchens Today s kitchens have become much more than a place for cooking and food preparation. The kitchen is the heart of the home. It s the center of activity for the
More informationDirect Gas Fired [Make-Up Air / Displacement Ventilation / Space Heating] System
Section 15622 AA-Series (rev. 04/16/15) Direct Gas Fired [Make-Up Air / Displacement Ventilation / Space Heating] System Note: Optional items and/or items requiring a choice, are shown between brackets
More information2003 ACCORD - Automatic Transmission Removal
2003 ACCORD - Automatic Transmission Removal Special Tools Required Engine support hanger, A and Reds AAR-T-12566 Engine hanger balancer bar VSB02C000019 Front subframe adapter VSB02C000016 These special
More informationSECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions
More informationMechanical Installation
Page -1-1. INTRODUCTION AND PURPOSE 1.1. This specification covers the installation, testing and precommissioning of mechanical equipment. Work is to be performed in conjunction with the manufacturer s
More informationSECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
More informationRoof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
More informationUFGS-23 34 23 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-23 34 23.00 40 (May 2014) ------------------------------ Preparing Activity: NASA Superseding UFGS-23 34 23 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
More informationD Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00
SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air
More informationPump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationBERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
More informationWe will discuss common industrial applications with guides for the proper use of electric motors on these.
INTRODUCTION: Baldor Electric Company has prepared this Specifiers Guide to help you cover all the bases when you are specifying electric motors. It will cover in a generic way most of the subjects which
More informationOperation and Installation Manual. Max Series
Operation and Installation Manual Max Series Models 95MAX 155MAX 155ECM 155MAXRX 200MAX 200MAXRX MAXTOP 195DCS 300DCS 200ERV 200ERVD New Auto Dehumidistat Function prevents unwanted use of the dehumidistat
More informationSECTION 6. Glass Storefront Doors:
SECTION 6 Glass Storefront Doors: Table of Contents 3070 Storefront Door System Description & Dimensions 6070 Storefront Door System Description & Dimensions Door Leaf Detail Optional 10 Bottom Rail Detail
More informationDisplay hidden notes to specifier. (Don't know how? Click Here) A. Advanced Upcoiling Security Grilles, power operated.
SECTION 08333 ADVANCED UPCOILING SECURITY GRILLE MODEL 600 ADV Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Advanced Upcoiling Security Grilles,
More informationPOWERS Controls No. 4 Pneumatic Damper Actuator
POWERS Controls No. 4 Pneumatic Damper Actuator Technical Instructions Document No. 155-032P25 AP 331-2 Actuator Assembly 331-2929 Typical Actuator Assembly 331-2904 Typical Actuator Assembly 331-3000
More informationAir Conditioner Duct Construction & Repair
PROPER ROOF AIR CONDITIONER MOUNTING At Newmar, there are two different models of air conditioners available on all towable and motorized units. The different models are the Dometic Brisk and Penguin models,
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 23 62 13 - AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",
More informationSECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
More informationAIR CONDITIONING PRODUCTS COMPANY
Quality Products Fixed Louvers AIR CONDITIONING PRODUCTS COMPANY all Shutter Backdraft Damper Ceiling Shutter Motorized Damper Fixed Louver Ga le Shutter Drainable Louver Supply Damper Fiberglass Shutter
More informationEvaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
More informationExplosion-Proof Electric Unit Heaters
Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,
More informationLight Duty Commercial Electric Water Heater
Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and
More informationWE-350 Series ¼ Turn Electric Actuator
WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information
More informationMAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationSECTION 15410 GROUND WATER STORAGE TANKS
SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design
More informationCFM @.0 SP H/M/L AFLR-12 12 3.033 1565/1464/1309 60 1836/1469/1175 24/22/20 115 AFLR-20 20 3 1/8 1468/1209/1063 60 7562/6050/4840 34/31/28 115
Air Circulators High Velocity Floor Fans Circulate Large Volumes of Air Product Specifications Size Spd HP HZ CFM/WATT @.0 SP AFLR-12 12 3.033 1565/1464/1309 60 1836/1469/1175 24/22/20 115 AFLR-20 20 3
More informationCity of San Diego, CWP Guidelines
PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,
More informationAABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
More informationOwner s Manual EFX. Explosion-Proof Exhaust Fan. This manual covers installations, maintenance, repair and replacement parts. WARNING!
Heaters for the Harshest Environments Owner s Manual ISO 9001 EFX Explosion-Proof Exhaust Fan This manual covers installations, maintenance, repair and replacement parts. WARNING! READ ALL IMPORTANT NOTICES
More informationSECTION 233000 HVAC AIR DISTRIBUTION
1320 / Talent Community Center 233000-1 HVAC AIR DISTRIBUTION SECTION 233000 HVAC AIR DISTRIBUTION PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Ductwork. 2. Ductwork accessories. 3. Fans. 4. Air
More informationLow Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
More informationINSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check
More informationJames M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
More informationUB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table
More informationLOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete.
LOADING DOCK EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Loading dock equipment of the following types: 1. Dock lifts. 2. Control stations. 1.2 RELATED SECTIONS A. Section 03100 - Concrete Forms and
More informationInstallation, operation and maintenance manual TX 35A
Installation, operation and maintenance manual TX 35A Rev.10 may 2012 Page 1 of 18 1.0.0 Table of contents INSTALLATION, OPERATION AND MAINTENANCE MANUAL...1 1.0.0 TABLE OF CONTENTS...2 2.0.0 ILLUSTRATIONS...2
More informationFOXAIR 60/50 ALL MODELS
FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,
More informationConsortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales
Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR LAUNDRY EQUIPMENT MAINTENANCE Maintenance Module 32 March 2011 issue This document has been compiled by the Engineering
More informationOWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
More informationCLEAR-DIVISIONS CENTERFOLD
CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in
More informationTransformer oil cooler ALFA A02
A02 Transformer oil cooler ALFA Transformer oil cooler ALFA The transformer oil cooler ALFA is used to cool power transformers by means of forced air and oil flow. The oil in the cooler is circulated using
More informationSECTION 10680 MediaStation Model 125 Electric Lateral Files (ELF)
SECTION 10680 MediaStation Model 125 Electric Lateral Files (ELF) PART 1-GENERAL 1.01 RELATED WORK SPECIFIED IN OTHER SECTIONS A. Electrical connections see electrical specifications. 1.02 SUBMITTALS A.
More informationMODEL IX -WAC/HP AIR CONDITIONERS & HEAT PUMPS FOR HIGHLY CORROSIVE & HAZARDOUS AREAS
1.5, 2, 2.5, 3, 3.5, 4, 5 & 6 Ton Industrial Grade Wall Mounted Air Conditioners & Heat Pumps Unit Application Bebco Model IX-WAC/HP Industrial Grade Air Conditioners & Heat Pumps are designed as a total
More informationAC Electric Motors best practice
If you want to learn more about best practice machinery maintenance, or world class mechanical equipment maintenance and installation practices, follow the link to our Online Store and see the Training
More information-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX
-1-002085 CONE SETTER PLATFORM ATTACHMENT INDEX I. GENERAL EQUIPMENT : A. Intent Statement B. Cone Setter Platform II. III. 1. Understructure Frame 2. Mounting Components 3. Paint 4. Basket 5. Labels 6.
More informationMagnum Mobile Generator MMG55 Specifications
Empowering Real People Magnum Mobile Generator MMG55 Specifications ENGINE John Deere PE5030TF270 - turbocharged, diesel engine o Prime - 72 hp @ 1800 rpm o Standby - 80 hp @ 1800 rpm o 4 cylinder o 3.0
More informationCORROSION RESISTANT FRP FANS & BLOWERS
CORPORATION CORROSION RESISTANT FRP FANS & BLOWERS Superior Quality High Efficiency Low Noise Level Competitive Pricing Fans in Stock Dedicated to detail, precision and quality control Welcome to M.K.
More informationEurovacuum EV Series. Single Stage Oil Sealed Rotary Vane Pump
Eurovacuum EV Series Single Stage Oil Sealed Rotary Vane Pump Eurovacuum EV Series Single Stage Oil Sealed Rotary Vane Pumps Eurovacuum Company is offering its various products to meet industrial vacuum
More informationVision Engravers and Routers PRE-Installation Guide. 2015 Vision Engraving & Routing Systems
Vision Engravers and Routers PRE-Installation Guide Revised: 8/19/2015 Vision Engravers and Routers PRE-Installation Guide All rights reserved. No parts of this work may be reproduced in any form or by
More informationRFQ # PR5006805 Replace Kitchen Equipment in the CGR
RFQ # PR5006805 Replace Kitchen Equipment in the CGR GENERAL The Consulate General of the United States of America has a requirement to furnish and install new kitchen equipment at the Consul General s
More informationSUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
More informationJohnson Air-Rotation Systems
AR Series TM Johnson Air-Rotation Systems Solution TM D Series TM FF Series TM 80/20 PR Series TM Johnson Air-Rotation systems announces a major addition to its product line, completing its line of high
More informationMRI RF SHIELDING DESIGN
MRI RF SHIELDING DESIGN Nelco s MRI RF Shielding is specifically designed for the MRI industry. Our engineers have developed a shielded enclosure made entirely of nonmagnetic materials that is unsurpassed
More informationB. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationSpecifications. Preformed Metal Wall and Roof Panels. Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023
Specifications Preformed Metal Wall and Roof Panels Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023 Section 07410 Preformed Metal Wall and Roof Panels Structural
More informationCRN5-5 A-FGJ-G-E-HQQE 3x230/400 50HZ
GRUNDFOS DATA BOOKLET CRN5-5 A-FGJ-G-E-HQQE 3x23/4 5HZ Grundfos Pump 96517184 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crn5/96517184/crn-5-5-a-fgj-g-e-hqqe.html
More informationHorizontal Jet Pumps 1/3-1-1/2 HP
Horizontal Jet s 1/3-1-1/2 FW01 0909 Supersedes 0409 The CPJ, CPH and EK models feature the famous Flint and Walling Service Plus motor, available in either NEMA J or Uni-frame flange construction. The
More informationCHILLED WATER DATA ROOM UNITS
Critical Infrastructure for the World s Leading Data Centers CHILLED WATER DATA ROOM UNITS Downflow Net Sensible Cooling 79 220kW Upflow Net Sensible Cooling 66 206kW A Nortek Company DATA CENTER COOLING
More information