New North Pointe K-4 Campus Tomball Independent School District SECTION HVAC FANS

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "New North Pointe K-4 Campus Tomball Independent School District SECTION HVAC FANS"

Transcription

1 SECTION CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 SUMMARY A. Provide complete, fully operational fans where indicated on Drawings. B. Section Includes: 1. Hooded propeller roof fans 2. Upblast centrifugal roof fans 3. Downblast centrifugal roof fans 4. Upblast centrifugal roof fans Grease exhaust 5. Centrifugal filtered supply fans 6. Inline Fans 7. Ceiling Mounted High Volume, Low Speed Fans C. Related Sections: 1.2 SUBMITTALS 1. Section HVAC Duct and Casings - Ducts: Product requirements for hangers for placement by this section. 2. Section Air Duct Accessories: Product requirements for duct accessories for placement by this section. 3. Coordinate work in this Section with Division 7. A. Provide line-by-line specification review annotated to certify compliance or deviation. B. Shop Drawings: Indicate size and configuration of fan assembly, mountings, weights, ductwork and accessory connections. C. Product Data: Submit data on each type of fan and include accessories, fan curves with specified operating point plotted, power, RPM, sound power levels for both fan inlet and outlet at rated capacity, electrical characteristics and connection requirements. D. Manufacturer's Installation Instructions: Submit fan manufacturer s instructions. E. Manufacturer's Certificate: Certify products meet or exceed specified requirements. 1.3 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: Submit instructions for lubrication, motor and drive replacement, spare parts list, and wiring diagrams. 1.4 QUALITY ASSURANCE A. Performance Ratings: Conform to AMCA 210 and bear AMCA Certified Rating Seal

2 B. Sound Ratings: AMCA 301, tested to AMCA 300, and bear AMCA Certified Sound Rating Seal. C. UL Compliance: UL listed and labeled, designed, manufactured, and tested in accordance with UL 705 and UL 762 for kitchen exhaust. D. Balance Quality: Conform to AMCA 204. E. Energy Recovery Unit Wheel Energy Transfer Rating: Meet ARI WARRANTY A. Furnish one (1) year manufacturer s warranty for fans. Warranty shall begin from date of Certificate of Substantial Completion. Warranty start date from shipment or start up will not be acceptable. B. The mechanical sub contractor is responsible for all interim warranty timelines from date of delivery to substantial completion. 1.6 EXTRA MATERIALS A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. Spare materials shall be provided by equipment manufacturer and not by the installing mechanical contractor. PART 2 - PRODUCTS 1. Fan Belts: Two (2) sets for each belt-driven fan. 2.1 HOODED PROPELLER ROOF FANS B. Unit shall be a low profile, hooded, roof mounted, belt driven or direct drive, propeller supply ventilator. Coordinate drive with fan schedule on drawings. C. Fan shall be constructed in accordance with UL 705. Fan shall bear the AMCA certified ratings seal for air performance. D. Construction: The fan shall be of bolted and welded construction utilizing corrosion resistant fasteners. The motor, bearings and drives shall be mounted on a welded tubular steel power assembly. The power assembly shall be rigidly secured to the fan housing. The powder coated steel fan housing shall include a minimum 14 gauge base with integral spun venturi and continuously welded or application of butyl tape to inside of the curb cap for maximum leak protection. The fan shall be enclosed with a minimum 18 gauge galvanized steel hood bolted to the fan housing. The hood shall have a removable

3 top cap to allow unobstructed access to the motor and power assembly without removing entire hood. The fan outlet shall be protected from entry of foreign material by ½" x ½" galvanized steel screen. Unit shall bear an engraved aluminum nameplate and shall be shipped in ISTA certified transit tested packaging. E. Coating: All ungalvanized steel fan components shall be treated with an electrostatically applied, baked polyester powder coating. Each component shall be subject to a five stage environmentally friendly wash system, followed by a minimum 2 mil thick baked powder finish. Paint must exceed 1,000 hour salt spray under ASTM B117 test method. F. Propeller: Propeller shall be a high-efficiency fabricated steel design with blades securely fastened to a minimum 7 gauge steel hub. The hub shall be keyed and locked to the fan shaft utilizing two setscrews. Propeller shall be balanced in accordance with AMCA Standard , Balance Quality and Vibration Levels for Fans. G. Motor: Motor shall be heavy duty type with permanently lubricated sealed ball bearings and furnished at the specified voltage, phase and enclosure. H. Bearings: Bearings shall be designed and tested specifically for use in air handling applications. Construction shall be heavy duty regreasable ball type in a cast iron housing selected for a minimum L50 life in excess of 200,000 hours at maximum cataloged operating speed. I. Belts and Drives: Belts shall be oil and heat resistant, non-static type. Drives shall be precision machined cast iron type, keyed and securely attached to the wheel and motor shafts. Drives shall be sized for 150% of the installed motor horsepower. The variable pitch motor drive must be factory set to the specified fan RPM. J. Roof Curb:12 inch high of 18 gauge galvanized steel construction with continuously welded seams, built-in cant strips, 1-1/2 inch insulation, damper tray, hinged curb adapter for access to dampers, and factory installed nailer strip. Coordinate installation with Division 7. K. Accessories: 1. Motorized damper in damper tray of roof curb. Actuator shall be same voltage as motor in fan. Damper shall energize fan through integral end switch. 2. Disconnect Switch: Coordinate with Division 26. Provide factory wired disconnect switch on 120v motor only. Factory provided disconnect switches shall be rated for outdoor use. Three phase combination disconnect/starter shall be provided by Division Direct drive units shall be provided with motor speed control option. 2.2 UPBLAST CENTRIFUGAL ROOF FANS

4 B. Fan shall be a spun aluminum, roof mounted, belt driven or direct drive, upblast centrifugal ventilator. Coordinate drive with fan schedule on drawings. C. Fan shall be constructed in accordance with UL 705. Fan shall bear the AMCA certified ratings seal for air performance. D. Construction: The fan shall be of bolted and welded construction utilizing corrosion resistant fasteners. The spun aluminum structural components shall be constructed of minimum 16 gauge marine alloy aluminum, bolted to a rigid aluminum support structure. The aluminum base shall have sealed curb cap corners by continuous weld or application of butyl tape to inside of the curb cap for maximum leak protection. The windband shall have a rolled bead for added strength. A two piece top cap shall have stainless steel quick release latches to provide access into the motor compartment without the use of tools. An integral conduit chase shall be provided into the motor compartment to facilitate wiring connections. The motor, bearings and drives shall be mounted on a minimum 14 gauge steel power assembly, isolated from the unit structure with rubber vibration isolators. These components shall be enclosed in a weather-tight compartment, separated from the exhaust airstream. Lifting lugs shall be provided to help prevent damage from improper lifting. Unit shall bear an engraved aluminum nameplate and shall be shipped in ISTA certified transit tested packaging. E. Wheel: Wheel shall be centrifugal backward inclined, constructed of 100 percent aluminum, including a precision machined cast aluminum hub. Wheel inlet shall overlap an aerodynamic aluminum inlet cone to provide maximum performance and efficiency. Wheel shall be balanced in accordance with AMCA Standard , Balance Quality and Vibration Levels for Fans. F. Motor: Motor shall be heavy duty type with permanently lubricated sealed ball bearings and furnished at the specified voltage, phase and enclosure. G. Bearings: Bearings shall be designed and individually tested specifically for use in air handling applications. Construction shall be heavy duty regreasable ball type in a cast iron pillow block housing selected for a minimum L50 life in excess of 200,000 hours at maximum cataloged operating speed. H. Belts & Drives: Belts shall be oil and heat resistant, non-static type. Drives shall be precision machined cast iron type, keyed and securely attached to the wheel and motor shafts. Drives shall be sized for 150 percent of the installed motor horsepower. The variable pitch motor drive must be factory set to the specified fan RPM. I. Roof Curb: 12 inch high of 18 gauge galvanized steel construction with continuously welded seams, built-in cant strips, 1-1/2 inch insulation, damper tray, hinged curb adapter for access to dampers, and factory installed nailer strip. Coordinate installation with Division 7. J. Accessories: 1. Motorized damper in damper tray of roof curb. Actuator shall be same voltage as motor in fan. Damper shall energize fan through integral end switch. 2. Disconnect Switch: Coordinate with Division 26. Provide factory wired disconnect switch on 120v motor only. Factory provided disconnect switches shall be rated for outdoor use. Three phase combination disconnect/starter shall be provided by Division

5 3. Direct drive units shall be provided with motor speed control option. 2.3 DOWNBLAST CENTRIFUGAL ROOF FANS B. Fan shall be a spun aluminum, roof mounted, belt driven, downblast centrifugal ventilator. C. Fan shall be constructed in accordance with UL 705. Fan shall bear the AMCA certified ratings seal for air performance. D. Construction: The fan shall be of bolted and welded construction utilizing corrosion resistant fasteners. The spun aluminum structural components shall be constructed of minimum 16 gauge marine alloy aluminum, bolted to a rigid aluminum support structure. The aluminum base shall have sealed curb cap corners by continuous weld or application of butyl tape to inside of the curb cap for maximum leak protection. The windband shall have a rolled bead for added strength. A two piece top cap shall have stainless steel quick release latches to provide access into the motor compartment without the use of tools. An integral conduit chase shall be provided into the motor compartment to facilitate wiring connections. The motor, bearings and drives shall be mounted on a minimum 14 gauge steel power assembly, isolated from the unit structure with rubber vibration isolators. These components shall be enclosed in a weather-tight compartment, separated from the exhaust airstream. Lifting lugs shall be provided to help prevent damage from improper lifting. Unit shall bear an engraved aluminum nameplate and shall be shipped in ISTA certified transit tested packaging. E. Wheel: Wheel shall be centrifugal backward inclined, constructed of 100 percent aluminum, including a precision machined cast aluminum hub. Wheel inlet shall overlap an aerodynamic aluminum inlet cone to provide maximum performance and efficiency. Wheel shall be balanced in accordance with AMCA Standard , Balance Quality and Vibration Levels for Fans. F. Motor: Motor shall be heavy duty type with permanently lubricated sealed ball bearings and furnished at the specified voltage, phase and enclosure. G. Bearings: Bearings shall be designed and individually tested specifically for use in air handling applications. Construction shall be heavy duty regreasable ball type in a cast iron pillow block housing selected for a minimum L50 life in excess of 200,000 hours at maximum cataloged operating speed. H. Belts & Drives: Belts shall be oil and heat resistant, non-static type. Drives shall be precision machined cast iron type, keyed and securely attached to the wheel and motor shafts. Drives shall be sized for 150 percent of the installed motor horsepower. The variable pitch motor drive must be factory set to the specified fan RPM

6 I. Roof Curb: 12 inch high of 18 gauge galvanized steel construction with continuously welded seams, built-in cant strips, 1-1/2 inch insulation, damper tray, hinged curb adapter for access to dampers, and factory installed nailer strip. Coordinate installation with Division 7. J. Accessories: 1. Motorized damper in damper tray of roof curb. Actuator shall be same voltage as motor in fan. Damper shall energize fan through integral end switch. 2. Disconnect Switch: Coordinate with Division 26. Provide factory wired disconnect switch on 120v motor only. Factory provided disconnect switches shall be rated for outdoor use. Three phase combination disconnect/starter shall be provided by Division Direct drive units shall be provided with motor speed control option. 2.4 UPBLAST CENTRIFUGAL ROOF FANS - GREASE EXHAUST B. Unit shall be a low profile, hooded, roof mounted, belt driven or direct drive, propeller supply ventilator. Coordinate drive with fan schedule on drawings. C. Unit shall be constructed in accordance with UL 762. Fan shall bear the AMCA certified ratings seal for sound and air performance. D. Construction: The fan shall be of bolted and welded construction utilizing corrosion resistant fasteners. The aluminum base shall have sealed curb cap corners by continuous weld or application of butyl tape to inside of the curb cap for maximum leak protection. The windband shall have a rolled bead for added strength. A two piece top cap shall have stainless steel quick release latches to provide access into the motor compartment without the use of tools. An external wiring compartment to facilitate wiring connections. The motor, bearings and drives shall be mounted on a 14 gauge steel power assembly. These components shall be enclosed in a weather-tight compartment, separated from the exhaust airstream. A one (1) inch thick, three pound density foil back heat shield shall be utilized to protect the motor and drive components from excessive heat. Lifting lugs shall be provided to help prevent damage from improper lifting. Unit shall bear an engraved aluminum nameplate and shall be shipped in ISTA certified transit tested packaging. E. Wheel: Wheel shall be centrifugal backward inclined, constructed of 100 percent aluminum, including a precision machined cast aluminum hub. Wheel inlet shall overlap an aerodynamic aluminum inlet cone to provide maximum performance and efficiency. F. Motor: Motor shall be heavy duty type with permanently lubricated sealed ball bearings and furnished at the specified voltage, phase and enclosure

7 G. Bearings: Heavy duty regreasable ball type in a cast iron pillow block housing selected for a minimum L50 life in excess of 200,000 hours. H. Belts and Dives: Belts shall be oil and heat resistant, non-static type. Drives shall be precision machined cast iron type, keyed and securely attached to the wheel and motor shafts. Drives shall be sized for 150 percent of the installed motor horsepower. The variable pitch drive must be factory set to the specified fan RPM. I. Roof Curb: 12 inch high of 18 gauge galvanized steel construction with continuously welded seams, built-in cant strips, 1-1/2 inch insulation, damper tray, hinged curb adapter for access to dampers, and factory installed nailer strip. Coordinate installation with Division 7. J. Accessories: 1. Disconnect Switch: Coordinate with Division Direct drive units shall be provided with motor speed control option. 3. Gravity actuated back-draft damper with adjustable counter weight. 4. Provide minimum 10 tall vented curb extension. 5. Provide grease trap with drain connection. 6. Provide heat baffle. 7. Provide Clean-Out Port. 2.5 CENTRIFUGAL FILTERED SUPPLY FAN - KITCHEN HOOD B. Unit shall be a low profile, hooded, roof mounted, belt driven or direct drive, propeller supply ventilator. Coordinate drive with fan schedule on drawings. C. Description: Fan shall be a side intake, roof mounted, belt driven, centrifugal filtered supply fan. D. Fan shall be constructed in accordance with UL 705. Fan shall bear the AMCA certified ratings seal for air performance. E. Construction: The fan shall be of bolted construction utilizing corrosion resistant fasteners. Housing shall be minimum 18 gauge galvanized steel, bolted to a minimum 16 gauge steel fan base with pre-punched mounting holes. Unit shall be provided with an insulated top cover and 1" washable permanent aluminum filter. Internal blower and motor assembly shall be mounted on rubber vibration isolators. Unit shall bear an engraved aluminum nameplate and shall be shipped in ISTA certified transit tested packaging. F. Wheel: Wheel shall be DWDI centrifugal forward curved type, constructed of painted steel. Wheel shall be balanced in accordance with AMCA Standard , Balance Quality and Vibration Levels for Fans

8 G. Motor: Motor shall be heavy duty type with permanently lubricated sealed ball bearings and furnished at the specified voltage, phase and enclosure. H. Bearings: Bearings shall be permanently lubricated, sealed ball type selected for a minimum L50 life in excess of 200,000 hours at maximum cataloged operating speed. I. Belts and Drives: Belts shall be oil and heat resistant, non-static type. Drives shall be precision machined cast iron type, keyed and securely attached to the wheel and motor shafts. Drives shall be sized for 150% of the installed motor horsepower. The variable pitch motor drive must be factory set to the specified fan RPM. J. Roof Curb: 12 inch high of 18 gauge galvanized steel construction with continuously welded seams, built-in cant strips, 1-1/2 inch insulation, damper tray, hinged curb adapter for access to dampers, and factory installed nailer strip. Coordinate installation with Division 7. K. Accessories: 2.6 INLINE FANS 1. Motorized damper in damper tray of roof curb. Actuator shall be same voltage as motor in fan. Damper shall energize fan through integral end switch. 2. Disconnect Switch: Coordinate with Division 26. Provide factory wired disconnect switch on 120v motor only. Factory provided disconnect switches shall be rated for outdoor use. Three phase combination disconnect/starter shall be provided by Division Direct drive units shall be provided with motor speed control option. B. Fan shall be a duct mounted, centrifugal, belt driven or direct drive, inline type supply or exhaust ventilator. C. All fans shall bear the AMCA Certified Ratings Seal for both sound and air performance. D. Construction: The fan housing shall be of the square design constructed of heavy gauge galvanized steel and shall include square duct mounting collars. Fan construction shall include two removable access panels located perpendicular to the motor mounting panel. The access panels must be of sufficient size to permit easy access to all interior components. Each fan shall bear a permanently affixed manufacturer s nameplate containing the model number and individual serial number for future identification. E. Coating: For fans serving Natatoriums or corrosive environments provide epoxy coating on all inside and outside surfaces including fan wheel and pulley. F. Wheel: The fan wheels shall be centrifugal backward inclined, constructed o f aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced

9 G. Motor: Motors shall be heavy duty ball bearing type, carefully matched to the fan load and furnished at the specified voltage, phase, and enclosure. Motor Pulleys shall be adjustable for system balancing. H. Bearings: Precision ground and polished shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum catalogued operating speed. I. Belts & Drives: Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to the wheel and motor shafts. J. Accessories: 1. Disconnect Switch: Coordinate with Division 26. Provide factory wired disconnect switch on 120v motor only. Three phase combination disconnect/starter shall be provided by Division Gravity actuated back-draft damper with adjustable counter weight. 3. Direct drive units shall be provided with motor speed control option. 4. Companion Flanges: For inlet and outlet duct connections. 5. Fan Guards: 1/2 by 1-inch mesh of galvanized steel in removable frame. Provide guard for inlet or outlet for units not connected to ductwork. 6. Motor and Drive Cover (Belt Guard): Epoxy-coated steel. 2.7 CEILING MOUNTED HIGH VOLUME, LOW SPEED FANS 1. Big Ass Fans B. Construction: Fan shall be ETL certified and built pursuant to construction guidelines set forth by UL standards 507, 746C, 1004, 1917 and CSA standards 22.2 No. 4, 22.2 No. 17, 22.2 No. 113, 22.2 No. 100, 22.2 No The fan shall be designed to move an effective amount of air for cooling and destratification in commercial applications. The fan shall incorporate a direct drive system designed specifically for high volume, low speed fans to ensure silent operation. The sound levels from the fan operating at maximum speed shall not exceed 40 dba (measured 20 or below the blades and 20 or horizontally from the center of the fan). C. Air Foils: The fan shall be equipped with ten (10) high volume, low speed airfoils or precision extruded aluminum alloy. Each airfoil shall be of the high performance TEC design. The airfoils shall be connected by means of two (2) locking bolts per airfoil. The airfoils shall be connected to the hub and interlocked with stainless steel retainers. D. Winglets: The fan shall be equipped with ten (10) TEC winglets designed to redirect outward airflow into downward airflow, thereby enhancing the efficiency and effectiveness of the fan. The winglets shall be die cast aluminum. Winglets shall be attached at the tip of each airfoil. The standard color of the winglets shall be super durable black. E. Trim: The fan shall be equipped with trim inserts that nest between the hub and the inner edge of the foil. The trim inserts (10 each) shall provide a cleaner fit between the airfoils and the hub to help reduce the drag, turbulence and the noise. Trim inserts shall be black

10 F. Motor: The fan motor shall be a permanent magnet brushless motor rated for continuous operation at maximum speed with the capability of modulating the fan speed from 0-100% without the use of a gearbox or other mechanical means of control. The motor shall operate from any voltage ranging from VAC, 1 PH, 60 HZ, without requiring adapters or customer selection. The motor shall be non-ventilated, heat sink design with the capability of continuous operation in -40 to 131 F ambient conditions. G. Hub: The fan hub shall be a single precision permanent mold casting of aluminum alloy for high strength and light weight. The hub shall be precision machined to achieve a well balanced and solid rotating assembly. The hub shall incorporate ten (10) safety pins made from aluminum that will secure the hub/airfoil assembly in case of shaft failure. The pins shall be attached to the body of the hub using the bolts. H. Mounting System: The fan mounting system shall be designed for quick and secure installation from a structural support beam. All components in the mounting system shall be of welded construction using steel no less than 3/16 thick and be powder coated for appearance and resistance to corrosion. All mounting bolts shall be SAE Grade 8 or equivalent. As an option, mounting components may be colored; confirm with architect/owner. I. Safety Cables: The fan shall be equipped with upper and lower safety cables. The upper safety cable shall provide an additional means of securing the fan assembly to the building structure. The lower safety cable shall provide an additional means of securing the motor unit to the mounting system. All safety cables shall be 3/16 diameter and fabricated out of 7x19 stranded galvanized steel. The loops must be secured with swaged Nicopress fittings, pre-loaded and tested to 3,000 lb f. Field construction of safety cables in not permitted. J. Controller: The controller shall be incorporated into the fan assembly. The controller shall be factory programmed to minimize starting and breaking torques. The controller shall be housed in an enclosure to prevent accidental contact with the enclosed equipment and to prevent entry of unwanted substances. K. Wall Control: The fan shall be equipped with a remote wall control. The wall control shall be capable of mounting to a standard receptacle by means of a mounting plate (which shall be included with the wall mounted device). The wall controller shall be equipped with a 1.8 TFT-LCD screen and user interface for controlling the fans direction, operation and speed. Communication with the fan drive and controller shall be by a standard, commercially available CAT-5 (or higher) Ethernet cable that is field installed and provided by the installer. A 5 patch cable shall be provided to test and verify communication signals locally prior to connecting the remote connection cable. L. Warranty: The manufacturer shall replace any products or components defective in material or workmanship, free of charge to the customer (including all transportation charges). M. Accessories: 1. Provide clear lockable enclosure for wall controller with two sets of keys

11 PART EXAMINATION A. Verify roof curbs are installed and dimensions are as shown on shop drawings. 3.2 INSTALLATION A. Secure roof fans with cadmium plated steel lag screws to roof curb structure. B. Install power ventilators level and plumb. C. Install dampers in roof curb damper tray. D. Provide hinged curb adapter to permit access to dampers and duct connection. E. Install safety screen where inlet or outlet is exposed. F. Provide sheaves required for final air balance. G. Install units with clearances for service and maintenance. H. Label units according to requirements specified in Section "Identification for HVAC Piping and Equipment." 3.3 MANUFACTURER'S FIELD SERVICES A. Furnish services of factory trained representative for minimum of one (1) day to start-up, calibrate controls, and instruct Owner on operation and maintenance. 3.4 CLEANING A. Vacuum clean inside of fan cabinet. 3.5 DEMONSTRATION A. Demonstrate fan operation and maintenance procedures. 3.6 PROTECTION OF FINISHED WORK A. Do not operate fans until ductwork is clean, bearings are lubricated, and fan has been test run under observation. END OF SECTION

Steel and Aluminum Utility Vent Sets

Steel and Aluminum Utility Vent Sets CP Steel and Aluminum Utility Vent Sets Page Introduction........................................ Standard Construction Features........................ 3 Specifications & Dimensions Belt Drives Backward

More information

Guide Specification SECTION HVAC FANS PART 1 - GENERAL 1.1 SUMMARY

Guide Specification SECTION HVAC FANS PART 1 - GENERAL 1.1 SUMMARY SECTION 23 34 00 - HVAC FANS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Centrifugal fans. 2. Propeller fans. 3. Downblast centrifugal roof fans. 4. Upblast centrifugal roof fans. 5. Ceiling fans.

More information

SECTION HVAC FANS

SECTION HVAC FANS SECTION 23 34 00 HVAC FANS PART 1 - GENERAL 1.1 DESCRIPTION A. Fans for heating, ventilating, and air conditioning. B. Product Definitions: AMCA Publication 99, Standard l-66. 1.2 RELATED WORK A. Section

More information

PROJ. NO SECTION HVAC FANS

PROJ. NO SECTION HVAC FANS SECTION 23 34 00 HVAC FANS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

A. Project Altitude: Base air ratings on actual site elevations.

A. Project Altitude: Base air ratings on actual site elevations. SECTION 233416 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION 23 34 13. A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer.

SECTION 23 34 13. A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer. PART 1 GENERAL SECTION 23 34 13 HVAC FANS 1.01 SUMMARY A. Section Includes: 1. Exhaust fans. 2. Transfer fans. B. Related Documents: 1. Drawings and general provisions of the Contract, including General

More information

2.3 Adequate space and access shall be provided for all fan locations for maintenance and operations.

2.3 Adequate space and access shall be provided for all fan locations for maintenance and operations. HVAC FANS GENERAL INFORMATION 1.1 This section applies to centrifugal and axial fans. DESIGN REQUIREMENTS 2.1 The Consultant shall include such considerations as duct leakage (expect 5 percent), temperature

More information

Division 26: Electrical characteristics and wiring connections. Section Commissioning Requirements

Division 26: Electrical characteristics and wiring connections. Section Commissioning Requirements PAGE 1 OF 7 SECTION 23 40 00 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Dust collector. B. Roof mounted exhaust fans. C. Cabinet fans. D. In-line centrifugal fans E. Motors, drives and accessories. 1.02

More information

A. Codes and Standards that are Standard at the University: 2. AMCA 204: Balance Quality and Vibration Levels for Fans

A. Codes and Standards that are Standard at the University: 2. AMCA 204: Balance Quality and Vibration Levels for Fans PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

A. Shop Drawings: Indicate size and configuration of fan assembly, mountings, weights, ductwork and accessory connections.

A. Shop Drawings: Indicate size and configuration of fan assembly, mountings, weights, ductwork and accessory connections. SECTION 233400 HVAC FANS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Roof ventilators. 2. Ceiling Fans 3. Kitchen Hood B. Related Sections: 1. Section 230529 - Roof curb flashing. 2. Section 230548

More information

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS COMMERCIAL KITCHEN APPLICATIONS Belt Driven Model VRBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company

More information

SECTION HVAC FANS

SECTION HVAC FANS PART 1 GENERAL 1.1 DESCRIPTION SECTION 23 34 00 A. Fans for heating, ventilating and air conditioning. B. Product Definitions: AMCA Publication 99, Standard 1-66. 1.2 RELATED WORK A. Section 01 00 00,

More information

TURNING AIR INTO SOLUTIONS. SQUARE INLINE CENTRIFUGAL FANS DSI BSI

TURNING AIR INTO SOLUTIONS. SQUARE INLINE CENTRIFUGAL FANS DSI BSI TURNING AIR INTO SOLUTIONS. SQUARE INLINE CENTRIFUGAL FANS DSI BSI CATALOG 40 March 06 SQUARE INLINE CENTRIFUGAL FANS Models DSI BSI Twin City Fan s DSI direct drive and type BSI belt driven square inline

More information

SECTION HVAC Fans

SECTION HVAC Fans SECTION 23 34 00 PART 1 GENERAL 1.1 SUMMARY A. Section Includes 1. The ceiling-mounted circulation fan is the model scheduled with the capacities indicated. The fan shall be furnished with standard mounting

More information

Holzheimer Bolek + Meehan Architects RMF Engineering

Holzheimer Bolek + Meehan Architects RMF Engineering PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

Industry best 5 year fan housing warranty, 1 year motor warranty

Industry best 5 year fan housing warranty, 1 year motor warranty MODEL RED MODEL FEATURES Exhaust air up to 3,000 CFM in high static pressure applications up to 1 w.g. Attractive spun aluminum exterior Direct drive units have low sound levels and quiet operation Non-overloading

More information

SECTION AXIAL HVAC FANS PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION AXIAL HVAC FANS PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 233413 - AXIAL HVAC FANS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Recirculating Roof Fans Models ESRMD, ESRMDF and ERD

Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Four-Way Fan Exhaust Supply Mix Recirculate BUILDING VALUE IN AIR. October 2005 Recirculating Roof Fans Exhaust/Supply/Recirculation/Mix Model ESRMD

More information

SMOKE AND HEAT REMOVAL ROOF VENTILATOR

SMOKE AND HEAT REMOVAL ROOF VENTILATOR BULLETIN 653 February 2004 SMOKE AND HEAT REMOVAL ROOF VENTILATOR Model SV40 Smoke and Heat Removal Roof Ventilator The Model SV40 combines year-round powered ventilation with smoke and heat removal capabilities.

More information

Division 23 - HVAC Section Switzerland Beallsville K-12 CENTRIFUGAL HVAC FANS

Division 23 - HVAC Section Switzerland Beallsville K-12 CENTRIFUGAL HVAC FANS SECTION 23 34 16 - CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233416-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

UPBLAST & HOODED PROPELLER ROOF VENTILATORS

UPBLAST & HOODED PROPELLER ROOF VENTILATORS The Industrial Choice. Model D53 / B53 Model HD53 / HB53 UPBLAST & HOODED ELLER ROOF VENTILATORS Direct Drive & Belt Driven Model D53 / B53 Upblast Exhaust Fans Model HD53 / HB53 Hooded Supply & Exhaust

More information

SECTION HVAC FANS

SECTION HVAC FANS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 34 00 HVAC FANS SPEC WRITER NOTES: 1. Delete between //-- // if not applicable to project. Also delete any other item or paragraph not applicable in the section

More information

San Jose City College PE Building &Wellness Center San Jose, CA

San Jose City College PE Building &Wellness Center San Jose, CA SECTION 23 34 00 HVAC FANS PART 1 GENERAL 1.1 SUMMARY A. Work Included: 1. Roof Exhaust Fans 2. Cabinet Fans 3. Ceiling Exhaust Fans 4. In-Line Centrifugal Fans 5. Destratification Fans for thermal equalization

More information

fixed pitch propeller fans

fixed pitch propeller fans Air Moving Solutions. fixed pitch propeller fans MODEL TCWP CATALOG AX500 December 2012 PropellerFans Model TCWP Fixed Pitch Heavy-Duty Construction Twin City Fan & Blower fixed pitch propeller fans, model

More information

The Industrial Choice. Model SV40 SMOKE & HEAT REMOVAL ROOF VENTILATOR. Model SV40

The Industrial Choice. Model SV40 SMOKE & HEAT REMOVAL ROOF VENTILATOR. Model SV40 The Industrial Choice. Model SV40 SMOKE & HEAT REMOVAL ROOF VENTILATOR Model SV40 CATALOG 653 February 2013 Smoke and Heat Removal Model SV40 Roof Ventilator Model SV40 Welded Steel Propeller Assembly

More information

CORE & SHELL SECTION HVAC FANS

CORE & SHELL SECTION HVAC FANS SECTION 233400 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Centrifugal roof ventilators. 2. Forward-curved centrifugal fans. B. Related Sections include the following: 1.

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Air Moving Solutions. ADJUSTABLE PITCH PROPELLER fans. Model TCWPX

Air Moving Solutions. ADJUSTABLE PITCH PROPELLER fans. Model TCWPX Air Moving Solutions. ADJUSTABLE PITCH PROPELLER fans Model TCWPX CATALOG AX510 March 2012 AdjustablePitch Model TCWPX Sizes 24'' - 48'' Heavy-Duty Construction Twin City Fan & Blower adjustable pitch

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS OCTOBER 18, 2013

UNIVERSITY OF ROCHESTER DESIGN STANDARDS OCTOBER 18, 2013 SECTION 233416 - CENTRIFUGAL HVAC FANS PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. Fans shall be dynamically balanced and factory-tested and certified in accordance with applicable AMCA test codes. All

More information

Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller

Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller Belt Drive Low and High Pressure October 009 Features Page Header Tube Axial Roof Upblast Fans Greenheck belt drive tube axial upblast

More information

SECTION HVAC FANS

SECTION HVAC FANS PART 1 - GENERAL 1.1 DESCRIPTION CLIN0002 (INCLUDES 2A & 2B) SECTION 23 34 00 HVAC FANS A. Fans for heating, ventilating and air conditioning. B. Product Definitions: AMCA Publication 99, Standard l-66.

More information

SERIES I HIGH PRESSURE BLOWERS. 7697 Snider Road, Mason, OH 45040-9135 Telephone: 513-573-0600. Cat. No. HP-I-107

SERIES I HIGH PRESSURE BLOWERS. 7697 Snider Road, Mason, OH 45040-9135 Telephone: 513-573-0600. Cat. No. HP-I-107 OEM and Industrial Air Handling Specialist HP SERIES I HIGH PRESSURE BLOWERS 7697 Snider Road, Mason, OH 4040-913 Telephone: 13-73-0600 Visit us at www.cincinnatifan.com for more information. Cat. No.

More information

TURNING AIR INTO SOLUTIONS. PROPELLER WALL FANS (DIRECT & BELT DRIVEN) WPD WPB

TURNING AIR INTO SOLUTIONS. PROPELLER WALL FANS (DIRECT & BELT DRIVEN) WPD WPB TURNING AIR INTO SOLUTIONS. PROPLLR WALL S (DIRCT & BLT DRIVN) WPD WPB CATALOG 48 September PROPLLR WALL S Overview WPB WPD Twin City Fan & Blower WPD Medium Duty and WPB Light and Medium Duty Propeller

More information

1.02 MATERIAL: A. Metal: Prime furniture steel, free of scales, buckles, or other defects; ASTM A366.

1.02 MATERIAL: A. Metal: Prime furniture steel, free of scales, buckles, or other defects; ASTM A366. 1.01 GENERAL: A. Fume hoods shall be of a "picture frame" airfoil design and construction. Each fume hood superstructure shall provide for safe efficient removal of all fumes, both heavy and light, with

More information

ROOF TOP MOUNTED Air Handler Specification

ROOF TOP MOUNTED Air Handler Specification ROOF TOP MOUNTED Air Handler Specification PART 1: GENERAL (Model RT) Mechanical Specification 1.01 WORK INCLUDED A. Provide complete air handling unit(s) suitable for outdoor installation. Contractor

More information

CE8000 Energy Recovery Ventilator

CE8000 Energy Recovery Ventilator ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 7000-8500 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel 18-gauge

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS SECTION 23 22 23 PART 1 GENERAL 1.1 DESCRIPTION A. Steam condensate pumps for Heating, Ventilating and Air Conditioning. B. Definitions: 1. Capacity: Liters per second (L/s) (Gallons per minute GPM) of

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

SECTION ROOFTOP HEATING AND COOLING UNITS

SECTION ROOFTOP HEATING AND COOLING UNITS SECTION 15782 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work

More information

Carnes Energy Recovery Ventilators

Carnes Energy Recovery Ventilators Carnes Energy s Model WE Energy s (300 to 8,000 CFM) Model WE Energy s provide affordable outside ventilation by combining an exhaust fan, make-up air handler and Carnes Energy Recovery Wheel into a compact

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, HVAR, ADD, ADDR, DDS, DDP

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, HVAR, ADD, ADDR, DDS, DDP INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, HVAR, ADD, ADDR, DDS, DDP The purpose of this manual is to aid in the proper installation and operation

More information

CE6500 Energy Recovery Ventilator

CE6500 Energy Recovery Ventilator ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

Cooktop Low-Profile Ventilation Hoods

Cooktop Low-Profile Ventilation Hoods INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............

More information

Custom-made Air Handling Units

Custom-made Air Handling Units CUTTING-EDGE INDUSTRIAL AIR HANDLING Custom-made Air Handling Units AHU Steam AHU Air conditioning AHU Recovery Options INDUSTRIAL AIR Bousquet technologies specializes in manufacturing industrial air

More information

Stock Fan Coils & Unit Heaters

Stock Fan Coils & Unit Heaters Complete solutions for fan coil applications Stock Fan Coils & Unit Heaters Engineered for flexibility and performance High Quality Fan Coils For Every Application McQuay fan coil units have earned a reputation

More information

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

TUBE AXIAL DUCT FANS. g A d n. ir H. d M Snider Road, Mason, OH Telephone: Cat. No. TA-310 Supersedes TA-1106

TUBE AXIAL DUCT FANS. g A d n. ir H. d M Snider Road, Mason, OH Telephone: Cat. No. TA-310 Supersedes TA-1106 d an M E O ial r t s u Ind g A lin d n a ir H t lis a i c e Sp TUBE AXIAL DUCT S 7697 Snider Road, Mason, OH 45040-9135 Telephone: 513-573-0600 Visit us at www.cincinnatifan.com for more information. Cat.

More information

KAP Series -Air Purification Unit

KAP Series -Air Purification Unit KAP Series -Air Purification Unit Installation, Operation and Maintenance Manual CONTENTS DESCRIPTION... 3 Common Installation Formats... 4 INSTALLATION... 4 Preparation... 4 Duct Work & Minimum Sizes...

More information

HRV / ERV. HEALTHY CLIMATE Heat / Energy Recovery Ventilator I N D O O R A I R Q U A L I T Y E N G I N E E R I N G D A T A MODEL NUMBER IDENTIFICATION

HRV / ERV. HEALTHY CLIMATE Heat / Energy Recovery Ventilator I N D O O R A I R Q U A L I T Y E N G I N E E R I N G D A T A MODEL NUMBER IDENTIFICATION I N D O O R A I R Q U A L I T Y HRV / ERV HEALTHY CLIMATE Heat / Energy Recovery Ventilator E N G I N E E R I N G D A T A Bulletin No. 210323 June 2006 Supersedes August 2004 MODEL NUMBER IDENTIFICATION

More information

Bulletin IDF11 MAKE-UP AIR. Model: IDF High Capacity, Indirect-Fired, Make-Up Air Units

Bulletin IDF11 MAKE-UP AIR. Model: IDF High Capacity, Indirect-Fired, Make-Up Air Units Bulletin 11 MAKE-UP AIR Model: High Capacity, Indirect-Fired, Units Introduction TM Title 2 TM Table of Contents Series Model: 75-1,200 MBH Capacity 600-14,800 CFM Capacity Introduction...4 Features &

More information

Roof Curbs, Extensions and Equipment Supports

Roof Curbs, Extensions and Equipment Supports Roof s, Extensions and Equipment Supports December 2012 Roof Page s, Header Extensions and Equipment Supports Table of Contents Model GPI Standard and Optional Construction Features... 3 Model Number Code....

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

GIVENS SPRAY TEC DOWNDRAFT PAINT SPRAY BOOTH

GIVENS SPRAY TEC DOWNDRAFT PAINT SPRAY BOOTH GIVENS SPRAY TEC DOWNDRAFT PAINT SPRAY BOOTH Givens Downdraft Paint Spray Booths are designed to give many years of trouble-free service. Since this booth is pitted, the air flow coming from the ceiling

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

RXIC-A01A Whole House/Light Commercial HEPA Filtration System

RXIC-A01A Whole House/Light Commercial HEPA Filtration System RXIC-A01A Whole House/Light Commercial HEPA Filtration System FEATURES PRODUCT DATA/OWNER S GUIDE HEPA media captures at least 99.97 percent of 0.3 micron particles that pass through it. Application for

More information

Installation. Centrifugal Roof and Wall Exhausters

Installation. Centrifugal Roof and Wall Exhausters This publication contains the installation, operation and maintenance instructions for standard units of the AC- Centrifugal Roof and Wall Exhausters. ACE-D / ACE-B ACW-D / ACW-B / ACW-HP / ACW-XP ACRU-D

More information

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2

More information

Mechanical Rooftop Custom Capabilities

Mechanical Rooftop Custom Capabilities Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition

More information

Mechanical Rooftop Custom Capabilities

Mechanical Rooftop Custom Capabilities Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition

More information

1. ABMA 9 - Load Ratings and Fatigue Life for Ball Bearings. 2. ABMA 11 - Load Ratings and Fatigue Life for Roller Bearings.

1. ABMA 9 - Load Ratings and Fatigue Life for Ball Bearings. 2. ABMA 11 - Load Ratings and Fatigue Life for Roller Bearings. SECTION 23 74 13 - CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes modular factory fabricated air-handling units and accessories for indoor and outdoor installation.

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

SECTION 15732 AIR CONDITIONING UNIT

SECTION 15732 AIR CONDITIONING UNIT SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration

More information

Installation Manual CLIFC Fan & Coil Variable Speed

Installation Manual CLIFC Fan & Coil Variable Speed Installation Manual CLIFC Fan & Coil Variable Speed General Description GENERAL DESCRIPTION FANS EQUIPMENT Totally Factory assembled within the unit all piping, wiring, and required controls for operation

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

Central Station Air Handlers SeasonMaster and SeasonVent

Central Station Air Handlers SeasonMaster and SeasonVent Replacement Parts List No. 055222600 Revision F 11/11 Central Station Air Handlers SeasonMaster and SeasonVent LHD, LYF, LSL, LML & LWL Sizes 103 thru 228 Vintage C LML, LSB Sizes 106 thru 111 Vintage

More information

The. Advantage ,000 cfm Supplemental Heating & Cooling

The. Advantage ,000 cfm Supplemental Heating & Cooling R GO GREEN GO RUSKIN The Advantage 600 12,000 cfm Supplemental Heating & Cooling Regardless of building type or rating system, today s building must be as energy efficient as possible. The design of the

More information

CEILING FANS THE PREMIUM QUALITY LINE FROM COMMERCIAL/INDUSTRIAL & SPECIAL APPLICATION. World Leader in Ceiling Fan Systems

CEILING FANS THE PREMIUM QUALITY LINE FROM COMMERCIAL/INDUSTRIAL & SPECIAL APPLICATION. World Leader in Ceiling Fan Systems THE PREMIUM QUALITY LINE FROM COMMERCIAL/INDUSTRIAL & SPECIAL APPLICATION CEILING FANS EXCLUSIVE LOW CEILING S The only metal blade fans U.L. listed for mounting 7 blade height to floor. U.S. PATENT NUMBER

More information

Turning Air Into Solutions. FIBERGLASS VENTILATORS MODEL FA/FAB MODEL WA/WAB MODEL SA MODEL HA/HAB MODEL MA

Turning Air Into Solutions. FIBERGLASS VENTILATORS MODEL FA/FAB MODEL WA/WAB MODEL SA MODEL HA/HAB MODEL MA Turning Air Into Solutions. FIBERGLASS VENTILATORS FA/FAB WA/WAB SA HA/HAB MA CATALOG 3000 August 2015 FiberglassRoofVentilators Fiber-Aire FA/FAB I WA/WAB I SA I HA/HAB I MA Application The Fiber-Aire

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

DIRECT DRIVE PLENUM FAN (DDP)

DIRECT DRIVE PLENUM FAN (DDP) Our Expertise, Your Air-Moving Solution DIRECT DRIVE PLENUM FAN (DDP) PART# 0601720001_rev_A INSTALLATION, OPERATION & MAINTENANCE MANUAL Please read and save these instructions for future reference. Read

More information

C. ANSI C Electrical Analog Indicating Instruments. E. ANSI C Guide for Transformer through Fault Duration.

C. ANSI C Electrical Analog Indicating Instruments. E. ANSI C Guide for Transformer through Fault Duration. SECTION 264260 - DISTRIBUTION SWITCHBOARDS PART 1 GENERAL 1.01 SECTION INCLUDES A. Main switchboard. 1.03 RELATED SECTIONS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION & MAINTENANCE MANUAL Model KBH & KBV KBV KBH INSTALLATION, OPERATION & MAINTENANCE MANUAL For Horizontal & Vertical Belt Drive Blower Coil Units TABLE OF CONTENTS General Safety Guidelines & Safety Symbols Safety Considerations

More information

Volt Products

Volt Products 220-240 Volt Products Exhaust Fans & Fan/Lights 676EX 671EX 688EX 679EX Utility Fans 509EX 512MEX Multi-Port Ventilators MP100EX MP140EX MP200EX Broan-NuTone LLC, 926 W. State Street, Hartford, WI 53027

More information

3. Listed [grease] [dishwasher] [grease and dishwasher] ducts.

3. Listed [grease] [dishwasher] [grease and dishwasher] ducts. SECTION 23 51 00 BREECHINGS, CHIMNEYS, AND STACKS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Power Roof Ventilator Installation, Operation, and Maintenance Manual. Down-blast Centrifugal Fan

Power Roof Ventilator Installation, Operation, and Maintenance Manual. Down-blast Centrifugal Fan Power Roof Ventilator Installation, Operation, and Maintenance Manual Up-blast Centrifugal Utility Fan Up-blast Centrifugal Fan Down-blast Centrifugal Fan Axial Fan RECEIVING AND INSPECTION Upon receiving

More information

SPECIFICATIONS FOR BOON EDAM TOMSED MODEL TUT-65TMB

SPECIFICATIONS FOR BOON EDAM TOMSED MODEL TUT-65TMB SPECIFICATIONS FOR BOON EDAM TOMSED MODEL TUT-65TMB PRODUCT DESCRIPTION: BOON EDAM TOMSED MODEL TUT-65TMB STAINLESS STEEL BARCODE SCANNING ELECTRONIC REGISTERING TURNSTILE SCOPE OF OPERATION: A. The TUT-65TMB

More information

CEILING CASSETTE FAN COIL UNIT

CEILING CASSETTE FAN COIL UNIT CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and

More information

TURNING AIR INTO SOLUTIONS. CEILING & INLINE/CABINET VENTILATORS. T TL (T-Series)

TURNING AIR INTO SOLUTIONS. CEILING & INLINE/CABINET VENTILATORS. T TL (T-Series) TURNING AIR INTO SOLUTIONS. CEILING & INLINE/CABINET VENTILATORS T TL (T-Series) CATALOG 4600 June 2016 CEILING & INLINE VENTILATORS Overview T I TL T-Series Ventilators Twin City Fan & Blower s T Series

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Ventilating Fan FV-20VQ3 FV-30VQ3 FV-0VQ3 Panasonic READ AND SAVE THESE INSTRUCTIONS. Please read these instructions carefully before attempting to install, operate or service

More information

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION 238221 - BLOWER COIL UNITS

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION 238221 - BLOWER COIL UNITS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

SECTION 16425 SWITCHBOARDS. 1. Requirements for main and distribution switchboards.

SECTION 16425 SWITCHBOARDS. 1. Requirements for main and distribution switchboards. SECTION 16425 SWITCHBOARDS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Requirements for main and distribution switchboards. B. Related Sections: 1. Section 16420 - Service Entrance 2. Section 16430

More information

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE

More information

Fan & Blowers. Motorized Impellers and Centrifugal Blowers. Backward & Forward Curved 2 & 4 Pole Motors Single & Dual Inlet. FB 01.

Fan & Blowers. Motorized Impellers and Centrifugal Blowers. Backward & Forward Curved 2 & 4 Pole Motors Single & Dual Inlet. FB 01. Fan & Blowers Motorized Impellers and Centrifugal Blowers Backward & Forward Curved 2 & 4 Pole Motors Single & Dual Inlet FB 1.12 January 212 1 HVAC Air Movers Designed for Hard Work and Long Service Motor

More information

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6 - B 1 Product Detail Engineering Data... B2 Structural Support... B6 Engineering Specifications... B9 - B 2 Engineering Data REMARK: Do not use for construction. Refer to factory certified dimensions &

More information

POWERS Controls. Technical Instructions Document No P25 AP March 5, No. 6 Pneumatic Damper Actuator.

POWERS Controls. Technical Instructions Document No P25 AP March 5, No. 6 Pneumatic Damper Actuator. POWERS Controls No. 6 Pneumatic Damper Actuator Technical Instructions AP 331-3 Description 331-2793 Actuator 331-2857 Actuator 331-3012 Extended Shaft and Frame with Clevis and Pin Mounting The POWERS

More information

Utility Distribution Systems

Utility Distribution Systems Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date

More information

Fractional Horsepower Motors a n d Specialty Blowers. Bulletin 7000 ONE SOURCE MANY P O W E R F U L S O L U T I O N S.

Fractional Horsepower Motors a n d Specialty Blowers. Bulletin 7000 ONE SOURCE MANY P O W E R F U L S O L U T I O N S. Fractional Horsepower Motors a n d Specialty Blowers Bulletin 7 ONE SOURCE MANY P O W E R F U L S O L U T I O N S. C-Frame Motors & Blowers 2 C-Frame Motors Compact, reliable C-Frame subfractional HP motors

More information

Scraper Flight Distribution Conveyor

Scraper Flight Distribution Conveyor SERPENTIX CONVEYOR CORP. 9085 Marshall Ct. Westminster, CO 80031-2920 Phone: 303.430.8427 Fax: 303.430.7337 www.serpentixconveyor.com rob@serpentix.com Scraper Flight Distribution Conveyor SERPENTIX CONVEYOR

More information

CAGED ALUMINUM ACCESS LADDERS

CAGED ALUMINUM ACCESS LADDERS SECTION 05512 CAGED ALUMINUM ACCESS LADDERS ***** UPNO VR, Inc. manufactures several types of aluminum access ladders. This guide specification section can be used to specify fixed, wall mounted, vertical

More information

Parallel Fan Powered Variable Air Volume (VAV) Terminal Boxes

Parallel Fan Powered Variable Air Volume (VAV) Terminal Boxes Installation Manual IM 1102 Group: Controls Part Number: IM 1102 Date: October 2010 Supersedes: New Parallel Fan Powered Variable Air Volume (VAV) Terminal Boxes Model(s): MQFVI5 2010 McQuay International

More information

RPV - RP - RA air handling units

RPV - RP - RA air handling units APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP

More information

Hurricane and High Wind Fans Models: G, GB, CUE, CUBE, S-CUBE, USGF, R, RB, FGI, FGR, LBP, LDP, RSF, RSFP SWB, SFB and SFD

Hurricane and High Wind Fans Models: G, GB, CUE, CUBE, S-CUBE, USGF, R, RB, FGI, FGR, LBP, LDP, RSF, RSFP SWB, SFB and SFD Hurricane and High Wind Fans Models: G, GB, CUE, CUBE, S-CUBE, USGF, R, RB, FGI, FGR, LBP, LDP, RSF, RSFP SWB, SFB and SFD March 2010 Overview Third-party Certified High Wind and Hurricane Fans As the

More information

Industrial Process Fans Radial Material Handling Wheels Models IPO, IPW, IPA

Industrial Process Fans Radial Material Handling Wheels Models IPO, IPW, IPA Industrial Process Fans Radial Material Handling Wheels Models IPO, IPW, IPA September 202 Industrial Duty Centrifugal Fans Greenheck s radial wheel industrial process centrifugal fans are designed to

More information

SECTION CENTRIFUGAL HVAC FANS

SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS are a part of this Section.

A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS are a part of this Section. SECTION 15240 - VIBRATION ISOLATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS are a part of this Section. 1.02 SUMMARY A.

More information

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION

More information