1 Description: In this worksheet you are going to determine: wire sizing, over current sizing, and disconnect sizing for multiple questions on the sample data below. Additionally, you will be using actual manufacturer specs to size all of the above LEGEND RLA Rated Load Amps FLA Full Load Amps LRA Lock Rotor Amps MCA Minimum Circuit Amps OFM Outside Fan Motor MOCP Max.*Overcurrent IDF - Indoor Fan Motor COMP - Compressor Note: For ampacity calculations of a multi-motor assembly, 25% is added only to the largest motor. So if the compressor has a RLA of 10 (almost always the largest load is the compressor) then you multiply the RLA by 1.25 to get the total amperage for the compressor. You then add that number to the remaining loads to determine the total amp rating of the unit. Sample Electrical Data: Finding total amperage: Comp Amps: 10(RLA) IDF Amps: 2.0 (FLA) ODF Amps 1.5 (FLA) Compressor is the largest load so: 10 amps X 1.25 = 12.5 amps then you just add that to all the remaining loads: 12.5 amps (compressor) amps (IDF) amps (ODF) = 16 amps total Finding Conductor Size: From your wire size chart, you round up to the amperage shown in chart. Look for the corresponding wire size.through using this chart you will soon memorize the most common sizes

2 Wire Amps Size / / /0 225 Using the wire sizing chart: 1. With the given amps you round up to get the correct wire size. As an example, if you have a load that requires 17 amps, you would install #12 wire, because #14 wire only goes to 15 amps, 2 amps shy of the required. 2. If you know the wire size you have, then you are able to determine maximum allowable amperage Things to keep in mind: 1. This is the amp ratings for THHN / THWN insulated wire. If the ambient temperature goes up, the allowable amp rating goes down. Almost all of the wire that we use is the dual rated THHN / THWN. 2. Another consideration is how many wires you are installing into one piece of conduit, known as the conduit fill. By code you can only install a fixed number of wires into a conduit.

3 1. Sample Electrical Data: Comp Amps: 11.2 (RLA) IDF Amps: 2.4 (FLA) ODF Amps 1.8 (FLA) 2. Sample Electrical Data: Comp Amps: 21 (RLA) IDF Amps: 3.4 (FLA) ODF Amps 2.8 (FLA) 3. Sample Electrical Data: Comp Amps: 35 (RLA) IDF Amps: 8 (FLA) ODF Amps 3.5 (FLA) 4. Sample Electrical Data: Comp Amps: 4.5 (RLA) IDF Amps: 1.1(FLA) ODF Amps 0.8 (FLA)

4 Mod 2

5 A. Model 38GK... 5 TON C. Model 50YX... 2 TON B. Model 38TDB... 4 TON D. Model 38CE...

Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA

Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA presented by: Keith Calais 1 What is it? Ampacity is the current, in Amperes, that a conductor can carry continuously under the conditions

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner

More information

Electric Motor Brake Horsepower Calculations

Electric Motor Brake Horsepower Calculations Electric Motor Brake Horsepower Calculations By Norm Christopherson These motor calculations are contained here as they apply to the changing conditions of the blower motor when pulley adjustments are

More information

Motor Circuit Protection Tables

Motor Circuit Protection Tables NEC Article 40 and Tables Explanation Columns & 2 Motor horsepower ratings are listed in Column. Full load amps from Tables 40.247 through 40.250 are provided in Column 2. Column Various fuse types are

More information

Installation Instructions

Installation Instructions 05,06 Single Package, Displacement Ventilation or Single Zone Variable Airflow Rooftop Units Electric Cooling with PURONr (R---410A) Refrigerant and COMFORTLinkt Controls Installation Instructions IMPORTANT:

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

CHAPTER 2 EXAMPLES AND TABLES

CHAPTER 2 EXAMPLES AND TABLES CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060 4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE

More information

2 MODEL AND APPLICATION INFORMATION

2 MODEL AND APPLICATION INFORMATION A LOOK AT SERVICE SAFETY 2 MODEL AND APPLICATION INFORMATION I. Compressor Model Number Codes..... 10 II. Condensing Unit Model Number Codes.. 11 III. Serial Label Information.............. 12 IV. Basic

More information

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to: PREFACE Because of changes in installation codes, the increasing complexity of the equipment involved, and other factors, more and more markings are being used on electrical heating and cooling equipment.

More information

BRANCH CIRCUIT AND FEEDER REQUIREMENTS

BRANCH CIRCUIT AND FEEDER REQUIREMENTS CHAPTER 36 BRANCH CIRCUIT AND FEEDER REQUIREMENTS SECTION E3601 GENERAL E3601.1 Scope. This chapter covers branch circuits and feeders and specifies the minimum required branch circuits, the allowable

More information

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODEL: WA121 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual : 2100-234 E Supersedes: 2100-234

More information

Basic Nameplate Information

Basic Nameplate Information Basic Nameplate Information General Information: Most equipment nameplates will have some common items of information. Many of these are self explanatory, and include: Manufacturer Manufacturerʼs address

More information

Air Conditioning Sign-Off Sheet

Air Conditioning Sign-Off Sheet Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate

More information

Customized Assessment Blueprint

Customized Assessment Blueprint Customized Assessment Blueprint HVAC Installer Basic - Test Codes: 7906 and 7796 Measuring What Matters Competencies and Skills Tested in this Assessment: HVAC Theory Heat Theory and Refrigeration HVAC

More information

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................

More information

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace) UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system

More information

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact: 7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: sales@centrair.ca Website: www.centrair.ca

More information

Air-Cooled Condensers

Air-Cooled Condensers Air-Cooled Condensers 20 to 120 Tons April 2001 Introduction Air-Cooled Condensers Built for Every Need Trane has the right condenser...if you are designing a new system or replacing an existing air-cooled

More information

DATA CENTER SOLUTIONS. For More Information: (866) 787-3271 Sales@PTSdcs.com. Technical Data

DATA CENTER SOLUTIONS. For More Information: (866) 787-3271 Sales@PTSdcs.com. Technical Data DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com Technical Data Contents Overview................................................ 1 Scalable Solution for Critical Environments...................

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

THE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features

THE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features THE WALL-MOUNT ONE TON AIR CONDITIONER W2A,800 Btuh 9.00 EER Right Side Control Panel 60Hz GREEN REFRIGERANT R-A The Bard Wall-Mount One Ton Air Conditioner is a self contained energy efficient heating

More information

Generator DoCKInG StatIonS

Generator DoCKInG StatIonS Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed

More information

Product Data INDUSTRY LEADING FEATURES / BENEFITS. 40GRQ / 38GRQ High- Wall Ductless Split System Sizes 09 to 18

Product Data INDUSTRY LEADING FEATURES / BENEFITS. 40GRQ / 38GRQ High- Wall Ductless Split System Sizes 09 to 18 40GRQ / 38GRQ High- Wall Ductless plit ystem izes 09 to 18 Product Data INDUTRY LEADING FEATURE / BENEFIT A PERFECT BALANCE BETWEEN BUDGET LIMIT, ENERGY AVING AND COMFORT. The 38/40GRQ series ductless

More information

Department of Labor and Industry Electrical Licensing

Department of Labor and Industry Electrical Licensing Department of Labor and Industry Electrical Licensing License Examination Guide The information in this guide is provided by the Licensing Unit of the Department of Labor and Industry to ensure that applicants

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2 SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-

More information

50ZP024-060 Packaged Air Conditioners Installation, Start-Up and Service Instructions

50ZP024-060 Packaged Air Conditioners Installation, Start-Up and Service Instructions Visit www.carrier.com 50ZP024-060 Packaged Air Conditioners Installation, Start-Up and Service Instructions NOTE: Read the entire instruction manual before starting the installation. Index Page SAFETY

More information

catalog Single Package Vertical Air Conditioners and Heat Pumps

catalog Single Package Vertical Air Conditioners and Heat Pumps catalog Single Package Vertical Air Conditioners and Heat Pumps Catalog: SK145.00-EG1 (1008) TABLE OF CONTENTS Single Package Vertical Units Introduction...............................................................................

More information

Wire types and sizes

Wire types and sizes Wire types and sizes This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

forair optimal air environments ResidentialPresentation

forair optimal air environments ResidentialPresentation forair optimal air environments ResidentialPresentation Quick Fact Countless neighborhood residents never recognize their home air conditioning system works roughly 3,000+ hours each year. In order to

More information

THE STABILOY BRAND ADVANTAGE UNLOCKING THE SECRETS OF ALUMINUM A LOOK AT THE ADVANTAGES OF ALUMINUM ALLOY OVER COPPER

THE STABILOY BRAND ADVANTAGE UNLOCKING THE SECRETS OF ALUMINUM A LOOK AT THE ADVANTAGES OF ALUMINUM ALLOY OVER COPPER THE STABILOY BRAND ADVANTAGE UNLOCKING THE SECRETS OF ALUMINUM A LOOK AT THE ADVANTAGES OF ALUMINUM ALLOY OVER COPPER Ever Wonder Why There s No Copper in the Air? Since the early 1900s, aluminum and aluminum

More information

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING There are several ways to wire multiple batteries to achieve the correct battery voltage or capacity for a particular DC

More information

E2 Series Electric Furnaces

E2 Series Electric Furnaces E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

NIPSCO AIR CONDITIONER (AC) CYCLING PROGRAM. Frequently Asked Questions. 1. Can I really make a difference by participating?

NIPSCO AIR CONDITIONER (AC) CYCLING PROGRAM. Frequently Asked Questions. 1. Can I really make a difference by participating? NIPSCO AIR CONDITIONER (AC) CYCLING PROGRAM Frequently Asked Questions 1. Can I really make a difference by participating? Yes. By participating, you and thousands of others help NIPSCO manage demand and

More information

MODEL 5060 USER S GUIDE ELECTRICALC PRO. Set. Stor. Rcl. Off. On/C #THHN #THW VD% Length. DEFuse. ParSz. kilo. WireSz. Grnd. HPth. Watts. Volts.

MODEL 5060 USER S GUIDE ELECTRICALC PRO. Set. Stor. Rcl. Off. On/C #THHN #THW VD% Length. DEFuse. ParSz. kilo. WireSz. Grnd. HPth. Watts. Volts. USER S GUIDE ELECTRICALC PRO MODEL 5060 3O 60 Cu VD WIRE SIZE 125% CONSTRUCTION MASTER ELECTRICALC PRO Cond Type Off On/C CondSz #THW #XHHW #THHN VD% Starter SEFuse InsTrip M Type Wire Res HPmotor DEFuse

More information

ice 3 FLUID TO FLUID HEAT PUMP

ice 3 FLUID TO FLUID HEAT PUMP ice 3 FLUID TO FLUID HEAT PUMP SUBMITTAL DATA (888) 530-7713 P O Box 5, Wentworth, H 03282 Rev.3 (5-30-14) ice 3, IC-2040 Fluid-to-Fluid R-410a Heat Pump Engineering Guide Specifications General otes:

More information

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

50GS, 50GX Single Package Electric Cooling Units Installation, Start-Up, and Operating Instructions 50GS Sizes 018-060, 50GX Sizes 024-060

50GS, 50GX Single Package Electric Cooling Units Installation, Start-Up, and Operating Instructions 50GS Sizes 018-060, 50GX Sizes 024-060 Visit www.carrier.com 50GS, 50GX Single Package Electric Cooling Units Installation, StartUp, and Operating Instructions 50GS Sizes 018060, 50GX Sizes 024060 NOTE: Read the entire instruction manual before

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION Chromalox Installation, Operation RENEWAL PARTS IDENTIFICATION Portable Industrial Unit Blower Air Type DRA and DIVISION SALES REFERENCE DATE SECTION (Supersedes P-) PF-) NOVEMBER, 00 DRA PF- -0-00 Specifications

More information

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR 3 Phase Air Conditioner Component R2A3**GHR DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER

More information

Voltage Drop. Voltage Drop 1

Voltage Drop. Voltage Drop 1 Voltage Drop The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences. Qualified person is defi ned in Article 100 of

More information

Installation Manual. 24 VDC Rooftop Air Conditioner

Installation Manual. 24 VDC Rooftop Air Conditioner SeaMach 24 VDC Rooftop Air Conditioner Installation Manual 24 VDC Rooftop Air Conditioner Chapter 1: Safety Considerations... 2 Chapter 2: General Information... 3 Chapter 3: Air Conditioning Sizing...

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

Motor Protection Voltage Unbalance and Single-Phasing

Motor Protection Voltage Unbalance and Single-Phasing Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the

More information

Split Systems Cooling Condensers

Split Systems Cooling Condensers Installation Operation Maintenance Split Systems Cooling Condensers 7½ - 20 Tons Model Numbers: TTA090A***F (60 Hz) TTA075AD**F (50 Hz) TTA155BD**F (50 Hz) TTA120A***F (60 Hz) TTA085AD**F (50 Hz) TTA155CD**G

More information

Building Cables and Wires

Building Cables and Wires Building Cables and Wires 4 Introduction alfanar is equipped with state-of-the-art manufacturing facilities such as latest machineries, instrumentation, quality control and testing laboratory, etc., for

More information

FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE

FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE Form 2B, Page 1 FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE COURSE NUMBER: ACR 0100 COURSE TITLE: PREREQUISITE(S): COREQUISITE(S): Basic Electricity and Schematics None None

More information

Air Conditioners (Outdoor)

Air Conditioners (Outdoor) 14/06/13 A1 Air Conditioners (Outdoor) Outdoor Condenser Units - R-410A Refrigerant Split System Air Conditioners, 208/230 Volt, Single Phase Designed using galvanized steel Composite base pan absorbs

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

SERVICE MANUAL MU-A09WA MU-A12WA MU-A12WA- 1 OUTDOOR UNIT. No. OB449. Wireless type Models HFC. Revision : A SPLIT-TYPE AIR CONDITIONERS

SERVICE MANUAL MU-A09WA MU-A12WA MU-A12WA- 1 OUTDOOR UNIT. No. OB449. Wireless type Models HFC. Revision : A SPLIT-TYPE AIR CONDITIONERS SPLIT-TYPE AIR CONDITIONERS Revision : A MU-AWA- Please void OB449. has been added. OUTDOOR UNIT SERVICE MANUAL Wireless type Models MU-AWA MU-AWA- HFC utilized R40A No. OB449 REVISED EDITION-A Indoor

More information

Cable Tray Selection-

Cable Tray Selection- Cable Selection- For allowable cable types see the Appendix page A-9. The following guidelines are based on the 2002 National Electrical Code, Article 392. I) Number of Multiconductor Cables rated 2000

More information

PANASONIC TROUBLE SHOOTING GUIDE

PANASONIC TROUBLE SHOOTING GUIDE A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling

More information

10.1 Indoor Unit Error Display

10.1 Indoor Unit Error Display 10.1 Indoor Unit Error Display Display E0 E1 E2 E3 E5 E6 P0 P1 P2 P4 LED STATUS EEPROM parameter error Indoor / outdoor units communication protection Zero-crossing signal error Fan speed out of control

More information

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008 Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be

More information

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for

More information

AIR CONDITIONING SYSTEM

AIR CONDITIONING SYSTEM AC-1 AIR CONDITIONING SYSTEM REFER TO FOLLOWING REPAIR MANUALS: Manual Name Land Cruiser (Hardtop and Canvas Top) Chassis and Body Repair Manual Land Cruiser (Station Wagon) Chassis and Body Repair Manual

More information

Voltage Drop (Single-Phase)

Voltage Drop (Single-Phase) Voltage Drop (Single-Phase) To Find: To Find Voltage Drop Formula: 2 x K x L x I V.D. = ------------------- C.M. Variables: C.M. = Circular Mill Area (Chapter 9, Table 8) To Find Voltage Drop Percentage

More information

TC-9102 Series Surface Mount Temperature Controllers

TC-9102 Series Surface Mount Temperature Controllers TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may

More information

Conductor Sizing and the National Electrical Code

Conductor Sizing and the National Electrical Code Conductor Sizing and the National Electrical Code The National Electrical Code requirements for conductor sizing and overcurrent protection have always been confusing and complex. Factors that must be

More information

WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS. Models: WA182, WA242. Bard Manufacturing Company, Inc.

WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS. Models: WA182, WA242. Bard Manufacturing Company, Inc. INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGED AIR CONDITIONER Models: WA82, WA242 Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 94...Moving ahead just as planned Manual No.: 200-369E Supersedes:

More information

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0 Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view

More information

BASIC NEC CODE RULES AND DESIGN PRACTICE

BASIC NEC CODE RULES AND DESIGN PRACTICE BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,

More information

Chemical resistance Accidental

Chemical resistance Accidental Industrial flexible cable, insulation and outer sheath in elastomer Description Application TITANEX flexible cable is intended for installations with moving equipment, electric appliances and for building

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp SERVICE ENTRANCE - UNDERGROUND 07-01-15 PAGE 1 OF 6 USE: Arrangement of service equipment to supply electric energy to an underground, outdoor self contained meter installation. LATEST REVISION: PREVIOUS

More information

FACT-FINDING STUDY ON POWERING OVER DATA CABLES. Anthony Tassone Principal Engineer Wire & Cable, Commercial & Industrial

FACT-FINDING STUDY ON POWERING OVER DATA CABLES. Anthony Tassone Principal Engineer Wire & Cable, Commercial & Industrial FACT-FINDING STUDY ON POWERING OVER DATA CABLES Anthony Tassone Principal Engineer Wire & Cable, Commercial & Industrial With the increased use of remotely powered devices and increasing levels of power

More information

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor

More information

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS WA WL W24A W24L WA WL W3A W3L W42A W42L W4A W4L WA WL Bard Manufacturing Company, Inc. Bryan, Ohio 40 Since 94...Moving ahead just

More information

WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS. Models: WA301, WA361. Bard Manufacturing Company Bryan, Ohio 43506

WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS. Models: WA301, WA361. Bard Manufacturing Company Bryan, Ohio 43506 INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGED AIR CONDITIONER Models: WA30, WA36 MIS-656 Bard Manufacturing Company Bryan, Ohio 43506 Since 94...Moving ahead just as planned. Manual No.: 20-92M Supersedes:

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

Build A Simple Electric Motor (example #1)

Build A Simple Electric Motor (example #1) PHY115 Experiment 11 Build A Simple Electric Motor (example #1) MATERIAL This is the necessary equipment. Present any list of material in your written lab report. 1.5 V battery in series 1 ceramic magnet

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

Statement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

Statement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary Installation Service Statement of Work - 1 - Cooling Start-up Service Cooling Start-up Service Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details

More information

Engineering Specifications

Engineering Specifications Engineering Specifications NORDIC W-85-H-B-*S-PD Water to Water Heat Pump Single-Stage R134a Nominal 7.5 Ton With Double Wall Condenser for Domestic Hot Water Production Maritime Geothermal Ltd. P.O. Box

More information

History and Overview. Manual Motor Protectors & Combination Motor Controllers

History and Overview. Manual Motor Protectors & Combination Motor Controllers Manual Motor Protectors & Application te May 2005 Supersedes, April 2004 Applications: Manual Motor Starter Manual Motor Disconnect IEC Circuit Breaker (European Market) NEC Group Installation Motor Starter

More information

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.

More information

Installation Instructions

Installation Instructions H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

CAB LCAB HACAB RMP/AMP CC CY/YY RVP CUSTOM CU

CAB LCAB HACAB RMP/AMP CC CY/YY RVP CUSTOM CU GENERAL PURPOSE (ORDINARY) LOCATION Custom Controls provides the petro-chemical and offshore industries with HVAC equipment of the highest quality and reliability on the market at an economical price.

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting

More information

Line Loss WSDOT Winter 2008 BZA

Line Loss WSDOT Winter 2008 BZA Electrical Design Training Class Line Loss WSDOT Winter 2008 BZA Presented by: Keith Calais 1 OHM S LAW P = Watts (Power) I = CURRENT (AMPERES) R = RESISTANCE (OHMS) E = ELECTROMOTIVE FORCE (VOLTS) P =

More information

City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines

City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines Western Riverside County Code Uniformity Program City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines PHONE (951) 826-5697 3900 Main Street, Riverside, CA 92522

More information

T7079A,B Solid State Remote Temperature Controllers

T7079A,B Solid State Remote Temperature Controllers T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature

More information

MU09TW MU12TN MU15TN MU17TN

MU09TW MU12TN MU15TN MU17TN SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL Wireless type Models (W) MSTN (W) MS5TN (W) MS7TN (W) MU09TW MUTN MU5TN MU7TN No. OB74 CONTENTS MSTN MS5TN MS7TN INDOOR UNIT MU5TN MU7TN OUTDOOR UNIT Remote controller.

More information

Stand Alone PV System Sizing Worksheet (example)

Stand Alone PV System Sizing Worksheet (example) Stand Alone PV System Sizing Worksheet (example) Application: Stand alone camp system 7 miles off grid Location: Baton Rouge, La Latitude: 31.53 N A. Loads A1 Inverter efficiency 85 A2 Battery Bus voltage

More information

1. BEFORE INSTALLATION

1. BEFORE INSTALLATION ENGLISH SPLIT-TYPE AIR CONDITIONERS INSTALLATION MANUAL JG79A191H03 MSZ-GE06/09/12/15/18NA MSY-GE09/12/15/18NA When installing multi units, refer to the installation manual of the multi unit for outdoor

More information

PTAC Selection Guide. Optimize your spend with the right PTAC equipment!

PTAC Selection Guide. Optimize your spend with the right PTAC equipment! PTAC Selection Guide Optimize your spend with the right PTAC equipment! The Direct Supply Difference Direct Supply Equipment & Furnishings understands the challenges of securing equipment for your communities.

More information

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored

More information

Voltage Loss Formula s

Voltage Loss Formula s www.litz-wire.com HM Wire International Inc. Phone: 330-244-8501 Fax: 330-244-8561 Voltage Loss Formula s www.hmwire.com Voltage loss in a wire is synonymous to pressure loss in a pipe. Electric current

More information

Refrigerated Design Texas

Refrigerated Design Texas Refrigerated Design Texas Refrigerated Design Texas 1808 FM 66 / P.O. Box 622 Waxahachie, TX 75167 / 75168 Toll Free (800) 736-9518 Ph. (972) 937-3215 Fax (972) 937-0970 www.rdtonline.com Table of Contents

More information

Owners Manual. Refrigerated Air Dryer. HX75 thru HX2400

Owners Manual. Refrigerated Air Dryer. HX75 thru HX2400 Owners Manual Refrigerated Air Dryer HX75 thru HX2400 IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS INFORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILIAR WITH THE PROPER INSTALLATION

More information