1 SECTION TRANSIENT VOLTAGE SURGE SUPPRESSION PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the materials and installation requirements for Surge Protective Devices (SPDs) and includes all service entrance, distribution and branch panel type surge protective devices suitable for use as Type 1 or Type 2 devices per UL rd Edition, applied to the line or load side of the utility feed inside the facility. B. This section also includes materials and installation of Transient Voltage Surge Suppressors (TVSS) for the protection of electronic circuits and equipment. 1.2 RELATED WORK A. Section 16010, "General Electrical Requirements" B. Section 16123, "Wire and Cable" C. Section 16130, "Raceway and Boxes" D. Section 16060, "Secondary Grounding" E. Section 16421, "Motor Control" 1.3 REFERENCES A. UL rd Edition (2009 Revision effective 9/29/2009). B. UL C. ANSI/IEEE C62.41, Recommended Practice for Surge Voltages in Low-Voltage AC Power Circuits. D. ANSI/IEEE C62.45, Guide for Surge Testing for equipment connected to Low-Voltage AC Power Circuits. E. IEEE 1100 Emerald Book. F. NEMA LS-1, 1992-(R2000) Low-Voltage Surge Protection Devices. G. National Fire Protection Association (NFPA 70: National Electrical Code). 1.4 SUBMITTALS A. Submit shop drawings, product data and manufacturer's installation instructions. B. The surge suppression submittals shall also include: 1. Copies of Manufacturer s catalog data, technical information and specifications on equipment proposed for use. 2. Copies of documentation stating that the Surge Protection Device is listed from a

2 1.5 WARRANTY Nationally Recognized Testing Laboratory (NRTL) (UL, ETL, etc.) and are tested and multi-listed to UL 1449 and UL Copies of actual let through voltage data in the form of oscillograph results for both ANSI/IEEE C62.41 Category 3 (combination wave) and B3 (Ring wave) tested in accordance with ANSI/IEEE C Copies of Noise Rejection testing as outlined in NEMA LS (R2000) Section Noise rejection is to be measured between 50kHZ and 100MHz verifying the devices noise attenuation. Must show multiple attenuation levels over a range of frequencies. 5. Copies of Surge Fuse Testing. Each unit shall be surge tested with fusing in series to verify that a transient of maximum surge current capacity/magnitude is fully suppressed without fuse failure, operation or degradation per NEMA LS (R2000) Section Copies of test reports from a recognized independent testing laboratory, capable of producing 200kA surge current waveforms, verifying the suppressor components can survive published surge current rating on both a per mode and per phase basis using the ANSI/IEEE C62.41 impulse waveform C3 (8 x 20 microsecond, 20kV/10kA). Test data on an individual module is not acceptable. 7. Copy of warranty statement clearly establishing the terms and conditions to the building/facility owner/operator. A. All TVSS units shall be guaranteed to be free of defects in materials and workmanship for a period of five years from the date of installation. B. Any suppressor which fails or operates improperly, even as a result of a direct lightning strike, will be replaced by the manufacturer at no expense to the owner. 1.6 QUALITY ASSURANCE A. All suppressors shall be manufactured in the United States by a company normally engaged in the design, development, and manufacture of such devices for electrical and electronics systems equipment for a minimum period of five years. B. All manufacturers will provide products which do not interrupt power to the protected system in the event of a suppressor failure, for life safety applications, i.e., fire alarm. Written certification of this parameter shall be provided by the suppressor manufacturer. C. The suppressors listed in this specification shall not impair the performance of the protected systems, including, but not limited to, the following parameters: degradation of signal quality or levels, attenuation, and distortion. The suppressors shall not initiate conditions which jeopardize the life safety features of fire alarms, communications, energy management, and other code related protection. PART 2 - PRODUCTS VOLT AND 480 VOLT SUB PANEL SUPPRESSORS A. Suppressors shall be listed in accordance with UL 1449, "Standard for Safety, Transient Voltage Surge Suppressors", and UL 1283, "Electromagnetic Interference Filters". B. Declared Maximum Continuous Operating Voltage (MCOV) shall be greater than 115 percent of the nominal system operating voltage and in compliance with test and evaluation procedures outlined in the nominal discharge surge current test of UL rd

3 Edition, section MCOV values claimed based on the component s value or on the 30-minute 115% operational voltage test, section 38 in UL1449 will not be accepted. C. Unit shall have not more than 10% deterioration or degradation of the UL1449 3rd Edition Voltage Protective Rating (VPR) due to repeated surges. Unit shall have a monitoring option available to be able to test and determine the percentage of protective available at all times. D. Suppressors shall be independently tested with the category C3 high exposure waveform (20 kv, 10kA, 8/20 micro-second waveform) clamp voltage test results. E. Suppressors shall incorporate copper bus bars for the surge current path. Small round wiring or plug-in connections shall not be used in the path for surge current diversion. Surge current diversion modules shall use bolted connections to the bus bars for reliable low impedance connections. F. The unit shall include an engineered solid-state high performance suppression filter system, utilizing metal oxide varistors, and polypropylene capacitors. G. The unit shall contain 200,000 AIC fuses on each phase. H. The status of each phase shall be monitored on the front of the suppressor's enclosure. I. For three phase, four wire plus ground configurations, the unit shall provide protection in all modes, Line to Neutral, Line to Ground, and Neutral to Ground. J. Suppressors shall be equipped with an audible alarm which shall activate upon device failure. An alarm on/off switch shall be provided to silence the alarm and an alarm pushto-test switch shall be provided to test the alarm. The switches and alarm shall be located on the front cover of the suppressor's enclosure. K. Suppressor shall meet or exceed the following criteria: 1. Tested maximum single impulse surge current rating per mode shall be; Line to Line 80,000A Line to Neutral 80,000A Line to Ground 80,000A Neutral to Ground 80,000A 2. Pulse life test: Capable of protecting against and surviving 2500 ANSI/IEEE C62.41 Category C3(20kV, 10 ka) transients without failure or degradation of UL 1449 suppression rating by more than 10%. 3. Protection Modes: SVR(6kV, 500A) and UL rd Edition VPR(6kV, 3kA) for grounded WYE/delta and High Leg Delta circuits with voltages of (480Y/277), (208Y/120), (600Y/347) 3-Phase/4 wire and (120/240) Split phase/3 wire circuits shall be as follows and comply with test procedures outlined in UL rd Edition section Ratings shall not exceed the following: System Mode MCOV UL 1449 UL 1449 Voltage 2 nd Ed. SVR 3 rd Ed. VPR 120/208 L-N / /700 L-G / /700 N-G /400

4 900/900 L-L / / /480 L-N / /1000 L-G / /1200 N-G / /1200 L-L / / The suppressor shall have a response time no greater than five nanoseconds for any of the individual protection modes. L. The unit shall include a high-frequency extended range tracking filter and shall be UL 1283 listed as an electromagnetic interference filter. The filter shall reduce fast rise-time, high frequency, error producing transients. The filter shall provide minimum noise attenuation as follows: Attenuation Frequency 100KHz 1 MHz 10MHz 100MHz Atttenuation db M. The unit shall incorporate solid state, long life, externally mounted LED visual status indicators that indicate the on line status of each phase of the unit. N. The unit shall incorporate an integral test point allowing easy off line diagnostic testing which verifies the operational integrity of the unit's suppression filter system. O. The unit shall include mechanical lugs for each phase, neutral and ground. The lugs shall accommodate up to #4 AWG copper conductor with integral fused disconnect switch, and up to 1/0 AWG copper conductor without an integral fused disconnect switch. P. Suppressor manufacturer shall provide certified test data confirming a "fail-short" failure mode. Q. Acceptable manufacturers: Current Technology Eaton Innovative Technology Square D Surge Logic 2.2 TERMINAL STRIP HARD-WIRED (120 VAC) SUPPRESSORS A. Suppressors shall be listed in accordance with UL 1449, "Standard for Safety, Transient Voltage" "Surge Suppressors". B. Suppressors shall consist of a three stage hybrid design: first stage - MOV, second stage - inductor, third stage - silicon avalanche diode or MOV. C. Suppressors shall be internally fused in such a manner that power to protected equipment is not interrupted in the event of a suppressor failure. D. Suppressors shall provide three suppression paths: line to neutral, line to ground, and neutral to ground. E. Suppressors shall provide a maximum single impulse current rating of 25 ka (8/20 micro-

5 second waveform) per mode. F. Pulse life rating: Capable of protecting against and surviving 500 Category B3 transients (6 kv - 1.2/50 micro-second, 3 ka - 8/20 micro-second waveform). G. Suppressors' maximum clamping voltage when subjected to Category B3 transients shall not exceed 350 V peak. H. Visible indication of proper suppressor connection and operation shall be provided. I. The suppressor shall have a two year warranty. J. Acceptable manufacturers: Advanced Protection Technologies, Inc., Model TE/AC03UL, or approved equal. PART 3 - EXECUTION 3.1 GENERAL A. Install TVSS equipment according to manufacturer's recommendations. B. Contractor shall properly match TVSS equipment to equipment being protected, including wire sizes, operating voltages and currents. C. Contractor shall coordinate with providers of all equipment being protected and provide TVSS equipment which meets these specifications. D. Provide required NEMA 1 (indoor) or NEMA 3R (outdoor) enclosures for suppressors adjacent to each electronic system cabinet, or coordinate with each electronic system supplier to provide oversized cabinets to incorporate suppressors into electronic systems cabinet. E. Electronic system equipment shall be protected by treating groups of related devices as a "cluster" and protecting all hard wire circuits which enter and leave the cluster. All equipment chassis within a protected cluster shall be bonded to a ground bar at the "window" location for the cluster, the window being the common point where all hard wire circuits enter or leave the cluster VOLT AND 480 VOLT SUB PANELS A. Install one secondary suppressor at each sub panel location, according to manufacturer's recommendations. B. Conductors between suppressor and point of attachment shall be kept short and straight. C. Neutral and ground shall not be bonded together at secondary panelboard locations. D. Provide suitable three pole breaker in all panels as recommended by suppression manufacturer to connect unit. 3.3 GROUND INSTALLATION A. Ground Bus Connections 1. Provide local ground bus in each terminal cabinet housing surge protection

6 equipment (with other materials as required). 2. Bond local ground bus to terminal cabinet with minimum #6 copper wire. 3. Connect terminal cabinet local ground bus to systems ground bus with minimum #6 copper insulated wire (unless otherwise noted) in conduit. 4. Note that the systems ground bar is also to be used for power transformation ground (480 V to 208 V) where applicable. B. Surge Suppression Equipment Grounding 1. Connect each suppressor to local ground bus in terminal cabinet with wire sized as recommended by manufacturer. Where M block type terminations/suppressors are used, bond ground rail to local ground bar with wire as recommended by manufacturer. 2. Ensure that 120 VAC power source/supply suppressor is also grounded to same local ground bus as suppressors provided in this section for same system (i.e., fire alarm, intercom, television, etc.). C. Grounding Conductors 1. Conductors shall be a minimum size of #12 THWN (in conduit, insulated) unless otherwise noted or otherwise recommended by the manufacturer. 2. Conductors shall be as short as possible. 3. No bend radius shall be less than 6 inches or more than 90 degrees. 4. Conductors shall be secured at 12 inch intervals with an approved copper clamp. 5. Grounding conductors shall be properly connected to the building service ground by approved clamps. 6. Do not bundle unprotected conductors with protected conductors. D. Grounding Connectors 1. Connectors, splicers, and other fittings used to interconnect grounding conductors, or bond to equipment or grounding bars, shall be approved by UL or NEC for the purpose. 2. All connectors and fittings shall be of the one time crimp or compression setscrew type solderless connection. 3. Special treatment to fittings, lugs, or other connectors of dissimilar material shall be applied to prevent electrogalvanic action. END OF SECTION

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1 Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

CPS 100 480Y S K CPS 100 480Y S C

CPS 100 480Y S K CPS 100 480Y S C Ref. No. 1299 Visor Series Ordering Guidelines Table.1-4. Retrofit Surge Protection Products TVSS General Description Clipper Power System Visor Series CPS 100 480Y S K.1-9 Surge Ratings 100 = /phase 120

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B SURGE PROTECTIVE DEVICES (SPDs) EXTERNAL SIDEMOUNT UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

Applications. Remote Display Mounting Kits

Applications. Remote Display Mounting Kits June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge

More information

Power surges can also be generated by equipment in your facility such as:

Power surges can also be generated by equipment in your facility such as: Power Quality Surge Suppressors What is Surge Protection A surge suppressor can be the first and best defense against the instant or gradual destruction of electrical equipment. Compared to the replacement

More information

TSn SERIES Surge Protective Device

TSn SERIES Surge Protective Device Page: 1 of 8 TSn SERIES Surge Protective Installation & Operation Manual 3621 Saunders Avenue www.systems.us Ph 804.355.1100 Richmond, VA 23227 4354 Sales@Systems.us Fax 804.355.8900 Page: 2 of 8 Quick

More information

SURGELOGIC TVSS Surge Protective Devices Enhance System Protection and Reduce Equipment Damage

SURGELOGIC TVSS Surge Protective Devices Enhance System Protection and Reduce Equipment Damage TVSS Surge Protective Devices Enhance System Protection and Reduce Equipment Damage Internal and External Mounted TVSS Retrofit or New Construction Low Let-through Levels High Surge Capacities Internal

More information

Surgelogic Surge Protective Device (SPD)

Surgelogic Surge Protective Device (SPD) Surgelogic Surge Protective Device () EB, EM, and HW Series atalog 1310T0202R05/09 2009 lass 1310 OTETS Description............................................. Page Product Description...........................................2

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

Surgelogic Surge Protection Device EMA, EBA, and HWA Series

Surgelogic Surge Protection Device EMA, EBA, and HWA Series Surgelogic Surge Protection Device EM, EB, and HW Series atalog 1310T0202R5/07 2007 lass 1310 OTETS Description..............................................Page Product Descriptions..........................................

More information

Power Quality for Information Technology System

Power Quality for Information Technology System Power Quality for Information Technology System ITS OBVIOUS THE TOLERANCE IS DIFFRENT But What isn t Tobvious? HOW MANY OF YOU HAVE : A COMPUTER AT HOME? = Computers are not screens and Keyboards COMPUTERS

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers 9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

Continuous Power... Continuous Protection

Continuous Power... Continuous Protection Series 165 We Keep Your Power On Continuous Power... Continuous Protection An Automatic Transfer Switch helps prevent... Your business or home from losing power during bad weather or utility power equipment

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

Power Management Module 2. Installation

Power Management Module 2. Installation Power Management Module 2 30 300 kva Installation Table of Contents Safety... 1 Safety Instructions... 1 Certification Standards Three Phase... 1 Product Safety... 2 Special Precautions... 2 System Description...

More information

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5 White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

surge protection solutions

surge protection solutions Surge protection devices Innovative Technology Innovative and reliable surge protection solutions Eaton Innovative Technology SPD products Innovative Technology products are a part of Eaton s electrical

More information

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the

More information

ASCO SERIES 185 Power Transfer Switches

ASCO SERIES 185 Power Transfer Switches ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

Canopy Surge. User Manual

Canopy Surge. User Manual Canopy Surge Suppressor User Manual SS00-UM-en Issue 2 May 2003 2003 Motorola, Inc. All rights reserved. Printed in the U.S.A Notices Safety Precautions: Before beginning your installation, please read

More information

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,

More information

Protect your home and family with Advanced Technology from Cutler-Hammer

Protect your home and family with Advanced Technology from Cutler-Hammer Protect your home and family with Advanced Technology from Cutler-Hammer Residential Home Fire Statistics Annually - over 415,000 Residential Fires Annually - over 40,000 electrical fires over 350 deaths

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

ENGINEERING REPORT. XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613

ENGINEERING REPORT. XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613 ENGINEERING REPORT XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613 PERFORMED BY: MIDWEST ELECTRICAL CONSULTANTS, INC 18055 UPLAND DRIVE TINLEY PARK, ILLINOIS 60487 (708) 444-0001 fax: 444-0003

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

Intersection Preassembled 19-inch Rack

Intersection Preassembled 19-inch Rack Intersection Preassembled 19-inch Rack The intersection preassembled 19-inch rack comes fully assembled, wired and ready to be installed in a server rack. The rack provides communications, power conversion

More information

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power App Notes ~ Outdoor Power System Design and Cost Considerations 1 Authors Peter Nystrom President TSi Power Corp. Coordination of Telecommunications Surge Protective Devices in Countries with Unstable

More information

City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION

City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

QuickSpecs. Overview. HP Power Distribution Rack. HP Power Distribution Rack. DA - 12859 North America Version 5 August 22, 2008 Page 1

QuickSpecs. Overview. HP Power Distribution Rack. HP Power Distribution Rack. DA - 12859 North America Version 5 August 22, 2008 Page 1 Overview It's getting harder to manage a data center efficiently, with rising utility bills and ever-increasing demands due to processor power and server density increases. Growing user requests mean heavier

More information

AC Module Installation Guide Content

AC Module Installation Guide Content AC Module Installation Guide Content for ET-P660250AC May 9, 2012 2011-2012 ET Solar Group All Rights Reserved. No part of this publication may be reused in any manner nor in any form or format without

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

SANS 10142-1 : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation

SANS 10142-1 : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation SANS 10142-1 : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation 4 Compliance Proof of Compliance (Sub clause 4.1.1) The SABS safety mark The SABS approved performance mark

More information

AN96-07. Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x

AN96-07. Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x On January 1, 1996, exports into Europe began facing some tough transient immunity standards. The International Electrotechnical Commission (IEC), a worldwide

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

SECTION 22 LIGHTNING PROTECTION SYSTEM

SECTION 22 LIGHTNING PROTECTION SYSTEM SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE Karl M. Hink, Executive Vice President Originally presented at the Power Quality 99 Conference ABSTRACT Motor protection

More information

Corner-Grounded Delta (Grounded B Phase) Systems

Corner-Grounded Delta (Grounded B Phase) Systems Data Bulletin 2700DB0202R03/12 09/2012 Replaces 2700DB0202R2/09 dated 02/2009 Corner-Grounded Delta (Grounded B Phase) Systems Class 2700 Retain for future use. Introduction Corner-grounded delta systems

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:

More information

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Surge Protection Solutions for PTC 2 Coaxial Cable Entry Panels, Coax

More information

RC NETWORKS SALES GUIDE

RC NETWORKS SALES GUIDE SALES GUIDE INTRODUCTION TO Recent developments in electronic equipment have shown the following trends: Increasing demands for numerical control machines, robotics and technically advanced appliances

More information

CalMod Design-Build Electrification Services

CalMod Design-Build Electrification Services SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor

More information

E-Version SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT

E-Version SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL 1.1. SCOPE OF WORK A. Under this item the Contractor shall furnish and install a sodium hypochlorite solution metering system complete with all accessories

More information

Installation Guide Content for P250xV-240 microinverters

Installation Guide Content for P250xV-240 microinverters A C M o d u l e Installation Guide Content for P250xV-240 microinverters May 15, 2012 2011-2012 SolarBridge Technologies, Inc. All Rights Reserved. No part of this publication may be reused in any manner

More information

Generic - Hearing Loop - (AFILS) U.S. System Specification

Generic - Hearing Loop - (AFILS) U.S. System Specification This document is a generic specification for any Hearing Loop (Audio Frequency Induction Loop System). For the remainder of the document, we will refer to using the term Hearing Loop rather than Audio

More information

Telecommunication Line Protectors

Telecommunication Line Protectors TN CR 0025 Telecommunication Line s 1.1 The nature of telecom surges The telecom services considered in this report are transported on twisted pair. Each service has two wires, or lines, sometimes called

More information

AND8229/D. An Introduction to Transient Voltage Suppression Devices APPLICATION NOTE

AND8229/D. An Introduction to Transient Voltage Suppression Devices APPLICATION NOTE An Introduction to Transient Voltage Suppression Devices Prepared by: Jim Lepkowski ON Semiconductor APPLICATION NOTE INTRODUCTION Transient Voltage Suppression (TVS) protection devices such as shielded

More information

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch

More information

VLT Series 300 Watt True Sine Wave Inverter

VLT Series 300 Watt True Sine Wave Inverter VLT Series 300 Watt True Sine Wave Inverter PURE SINE WAVE INVERTER I ON 0 OFF REMOTE CONTROL AC OUTPUT POWER STATUS Vout Vin Models VLT12-300 VLT24-300 300 Watt VLT Series Inverter - 1 - TABLE OF CONTENTS

More information

Chapter 9. Bonding and Grounding

Chapter 9. Bonding and Grounding Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and

More information

East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

Transient and Lightning Protection for the Water Industries

Transient and Lightning Protection for the Water Industries Transient and Lightning Protection for the Water Industries Mike Nager Phoenix Contact mnager@phoenixcon.com 5 th ISA Water/Wastewater Automatic Controls Division Symposium (WWAC) August 3-5, Orlando,

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

wietap wietap Overvoltage Protection Tensions running high

wietap wietap Overvoltage Protection Tensions running high wietap wietap Overvoltage Protection Tensions running high 2 wietap wietap Overvoltage protection Important information on overvoltage The necessity of overvoltage protection on machines and systems as

More information

Design of Bidirectional Coupling Circuit for Broadband Power-Line Communications

Design of Bidirectional Coupling Circuit for Broadband Power-Line Communications Journal of Electromagnetic Analysis and Applications, 2012, 4, 162-166 http://dx.doi.org/10.4236/jemaa.2012.44021 Published Online April 2012 (http://www.scirp.org/journal/jemaa) Design of Bidirectional

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

Current Probes. User Manual

Current Probes. User Manual Current Probes User Manual ETS-Lindgren L.P. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall

More information

AC Module Installation Guide Content

AC Module Installation Guide Content AC Module Installation Guide Content for ET-P660250AC May 9, 2012 2011-2012 ET Solar Group All Rights Reserved. No part of this publication may be reused in any manner nor in any form or format without

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

Uninterruptible Power Supply

Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features

More information

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

Power Quality Issues, Impacts, and Mitigation for Industrial Customers Power Quality Issues, Impacts, and Mitigation for Industrial Customers By Kevin Olikara, Power and Energy Management Products Rockwell Automation, Inc. Now, more than ever, electronic equipment and computing

More information

White Paper: Electrical Ground Rules

White Paper: Electrical Ground Rules Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been

More information

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Guidelines on the Short Circuit Current Rating for Industrial Control Panels usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A

More information

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the

More information

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Cable Solutions for Servo and Variable Frequency Drives (VFD) Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect

More information

Harmonics in your electrical system

Harmonics in your electrical system Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

Single Phase Soft Starter

Single Phase Soft Starter Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

AC and DC Drive System Installation Information

AC and DC Drive System Installation Information Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS

More information

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase

More information

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Learning Module 13: Panelboards and Switchboards. 101 Basic Series Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and

More information

Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc.

Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc. Grounding Practice at Data and Communications Centers David Brender, P.E., CPQ National Program Manager Copper Development Association Inc. Overview of This Presentation Elements of building wiring and

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

National Craft Assessment and Certification Program S P E C I F I C A T I O N S National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems A. General This Net Metering Standard for Customer-Owned Grid Connected Electric Generating Systems sets forth the

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

Special Specification 6111 LED Neighborhood Friendly High Mast (NFHM) Illumination Assemblies

Special Specification 6111 LED Neighborhood Friendly High Mast (NFHM) Illumination Assemblies Special Specification LED Neighborhood Friendly High Mast (NFHM) Illumination Assemblies 1. DESCRIPTION 2. MATERIALS Furnish and install light emitting diode (LED) neighborhood friendly high mast illumination

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

Battery Power Inverters

Battery Power Inverters Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.1 Important Safety Instructions Please save these instructions.

More information