1 SECTION CHLORINATION SYSTEM PART 1 - GENERAL 1.1. SCOPE OF WORK A. Under this item the Contractor shall furnish and install a sodium hypochlorite solution metering system complete with all accessories and ready to operate as shown on the drawings and/or as directed by the Engineer. As well, the Contractor shall furnish one (1) complete standby metering pump to be turned over to the owner and be kept in inventory for backup purposes. Solution tank and metering pump shall be installed on a spill containment pallet SUBMITTALS A. Furnish shop drawings for each component of the complete installation in accordance with Section OPERATING CONDITIONS A. The design operating requirement shall have capability to disinfect potable water flowing at 1,000 gallons per minute with 1 mg per liter chlorine using 12.5% sodium hypochlorite. PART 2 - PRODUCT 2.1. METERING PUMPS: The pumps shall be programmable electronic metering pumps with microprocessor control, clear liquid crystal display and four key tactile keypad. A. Housing: Corrosion resistant NEMA 4X of glass fiber reinforced polypropylene, o-ring sealed. B. Operational Modes Stroke Frequency: 1. Manual mode can be selected and will allow a manual stroke rate adjustment from 1 stroke per hour to 100 strokes per minute. 2. External mode allows for operation on pulse divide, pulse multiply (batch accumulate) or a 4-20 madc input. C. Manual Stroke Length Adjustment: Stroke length may be manually adjusted between 20 and 100 percent. D. Pump shall accept a shut-down contact for metering pump stop when an external dry contact (flow meter low flow contact) opens. E. Characteristics: 3.8 liters per hour maximum feed rate, 150 psi injection pressure, 120 VAC power, with liquid end suitable for 12.5% sodium hypochlorite. F. Model: LMI AA951490HI. G. Accessories: 1. Four function valve plus auto prime, Part No , 50 feet 1/4 OD PE tubing gallon polyethylene solution tank and cover, Model Corporation stop and injection nozzle ¾ NPT bronze corporation stop, CPVC nozzle Model Four pin cable, Part Number for control panel low flow contact to stop metering pump. 5. Two conductor cables with eight pin connector, Part Number 33807, for 4-20ma signal from control panel to pump SPILL CONTAINMENT PALLET A. Pallet shall be polyethylene, 66-gallon containment measuring 51 x x with grating cover and ¾ drain plug. Eagle Model EM1620, or equal. CHLORINATION SYSTEM

2 PART 3 - EXECUTION 3.1. INSTALLATION A. The chlorination system shall be installed in accordance with the manufacturer's instructions and as shown on the drawings. B. Chlorine solution tubing, piping, fittings and equipment, including injection point fittings and pipe, in contact with chlorine solution shall be of materials rated to be resistant to corrosion from chlorine solutions. C. Provide the services of a factory trained representative to certify the installation is installed and operating according to design and instruct the operator in proper operation of the system. Calibrate pump to provide 100 strokes per minute at 1,000 gallon per minute outflow. Low flow contact to stop pump when flow is into tank and when outflow is less than 20 gallons per minute. END OF SECTION CHLORINATION SYSTEM

3 SECTION TELEMETRY PANEL AND SCADA UPGRADES PART 1 - GENERAL 1.1. SUMMARY OF WORK A. New Remote Telemetry Unit (RTU) for the new water storage tank located on country route 36. B. Upgrades to the existing Wonderware SCADA system screens EXISTING SYSTEM OVERVIEW A. Water is pumped from the existing Louisville Water Treatment Plant into the distribution system which currently consist of two water storage tanks, Kingsley Road and Wilson Hill. Pump on/off operation is determined by operator adjustable tank level setpoints. The operator can also determine which tank to use for on/off operation. Water level from the remote tanks are received at the water plant utilizing spread spectrum radio communications between the sites NEW SYSTEM OVERVIEW A. A new water storage tank on County Route 36 is being constructed and added to the water distribution system. The new tank shall communicate with the existing telemetry system as specified herein SUBMITTALS/ACCEPTABLE MANUFACTURERS A. The system integrator shall, for review, provide to the contractor, for submission to the engineer, five (5) sets of the following documentation: 1. Written Sequence of Control System Operation 2. Electrical and Mechanical Schematic Drawings 3. Bill of Materials 4. Vendor Data Sheets 5. Control System Warranty (see below) B. The system integrator shall be General Controls Systems, Green Island, NY 12183, No other supplier shall be excepted OPERATIONS AND MAINTENANCE DOCUMENTATION A. The system integrator shall provide to the contractor, Four (4) sets of the following Operations and Maintenance documentation; all documentation shall be neatly bound in 3-ring binders. 1. Final Written Sequence of Control System Operation. 2. As-Installed Electrical and Mechanical Schematic Drawings. 3. Bill of Materials. 4. Vendor Operation, Maintenance and troubleshooting documentation. 5. PLC and OIU program printouts. 6. Back-up Copies of As-installed PLC and OIU programs on CD WARRANTY A. The system Integrator shall provide with the above submittals, a written parts and labor warranty against system failure for twelve (12) months from system startup, not to exceed eighteen (18) months from date of shipment from their factory. This warranty period will, with the exception of human negligence or acts of nature such as lightning, floods, wind etc., provide for repair of any and all defects of workmanship, as well as repair or replacement of any defective or failed components, at the project site, and at no cost to others. TELEMETRY PANEL AND SCADA UPGRADES

4 1.7. QUALITY ASSURANCE A. The Equipment, controls and accessories covered in this specification section constitute a completely integrated system, designed, constructed and tested by one Systems Integrator, accountable for it's operation and performance. The Systems Integrator named herein has been selected based their ability to engineer, design and manufacture systems of the type herein specified. In addition, they posses a New York State based, factory trained, service staff experienced in routine and emergency service of equipment of the type herein specified. B. Control panels shall be fabricated with the following features as a minimum: 1. All sub panel wiring shall be run in plastic wire duct sized with 50% spare space, AC and DC wiring shall be run in separate wire ducts. 2. All power supplies shall be sized for an additional 50% spare ampacity over expected load. Each power supply shall include an AC input fuse and independent output fuses for each device requiring DC power. 3. All field terminations shall be made on compression type terminal blocks labeled according to wire number, separate terminal strips shall be provided for AC and DC signals. A minimum of 20% spare terminals shall be provided. 4. Wiring to door mounted components shall be neatly bundled wiring harnesses protected by plastic spiral wire wrap when crossing door hinge. Wiring harnesses shall have adequate stress loops and be fastened at both sides of hinge crossing. 5. All wiring shall be wire numbered at both ends with plastic Brady type labels. 6. All nameplates shall be engraved on lamacoid material providing black lettering on a white background. Lettering shall be no smaller than 3/32 of an inch in height. 7. Twenty percent spare mounting space is required for future modifications. C. The System Integrator shall be U.L. approved for manufacturing systems in compliance with UL 508. Each assembly and subassembly of the system shall be listed and labeled as U.L. approved. D. The Systems Integrator shall be General Controls Systems, Green Island, NY 12183, PART 2 - PRODUCTS 2.1. COUNTY ROUTE 36 WATER STORAGE TANK A. The county route 36 water storage tank panel shall receive a 4-20madc signal proportional to tank water level. B. The level shall be transmitted to the water treatment plant utilizing spread spectrum radio communication. C. Upgrades, as required, to the existing Phoenix Contact radio equipment shall be performed under this contract. D. All accessories shall be provided for a complete installation, such as, antenna, mounting hardware, coaxial cable, surge protectors and other related equipment. E. A Transient Voltage Surge Suppressor (TVSS) shall be provided for the incoming 120VAC/1Ph/60Hz supply. The TVSS shall provide line-to-line, line to neutral and line to ground protection. F. Lightning protection shall be provided on all instrumentation remotely wired to the control panels. G. Coaxial cable shall be of sufficient length to be routed from chlorination building to the top of the new tank. TELEMETRY PANEL AND SCADA UPGRADES

5 2.2. SCADA SYSTEM AND DATA ACQUISITION UPGRADES A. The systems integrator shall be responsible for updating the existing Wonderware SCADA system. B. Screen Development the systems integrator shall develop the following screens 1. County Route 36 Level and set points 2. Alarms and historical data. C. Animations full animations of the following shall be provided on each screen: 1. Tank Levels D. Trending provide historical data collection and trending displays for the following: 1. Country Route 36Tank level E. Screen development shall be accomplished based on final approval of submitted shop drawings indicating each screen and associated sub-screens. Integrator shall work directly with the engineer and water plant operators when developing the Wonderware screens PARTS A. All telemetry panel components and devices shall be consistent with the components originally supplied by General controls under previous contracts. B. One pressure transmitter for the County Route 36 site shall be provided by the system integrator. The pressure transmitter shall be consistent with the existing ABB, 600T series transmitter. PART 3 - EXECUTION 3.1. INSTALLATION A. The contractor shall install equipment at locations indicated on the drawings. B. The contractor shall provide all necessary cable, conduits, and fittings as required. All wiring shall be in conduit or sealtite START-UP SERVICE A. The system integrator shall provide the services of a qualified service technician/engineer to perform the following service duties. The technician/engineer shall be a direct employee of the Systems Integrator. B. Provide startup services to inspect the equipment installation and provide final calibration and programming of the system. If additional time is required to facilitate start-up, it shall be at no additional cost to the Owner. C. Provide instruction to facility personnel, in the operation, proper maintenance, trouble shooting and repair of the equipment. D. Following completion of the above service, the Systems Integrator shall provide an affidavit to the facility, certifying that the system is installed and operating in accordance with the contract documents. END OF SECTION TELEMETRY PANEL AND SCADA UPGRADES

O C M III. Open Channel Flow Monitor

O C M III. Open Channel Flow Monitor O C M III Open Channel Flow Monitor Part 1. General 1.1 Scope A. This section describes the requirements for an ultrasonic flow transmitter with sensor and temperature compensation probe. B. Under this

More information

SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS)

SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS) SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS) PART 1: GENERAL 1.01 SCOPE OF WORK A. Under this section of the specifications, the contractor shall furnish and install a shop-fabricated 4X4 Dispersal

More information

CalMod Design-Build Electrification Services

CalMod Design-Build Electrification Services SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor

More information

SECTION 13421 PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL. 1.01 Summary. A. Section Includes:

SECTION 13421 PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL. 1.01 Summary. A. Section Includes: SECTION 13421 PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL 1.01 Summary A. Section Includes: 1. The ISS shall furnish all labor, materials, equipment, services and incidentals

More information

SECTION 22 LIGHTNING PROTECTION SYSTEM

SECTION 22 LIGHTNING PROTECTION SYSTEM SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

BLUE RIBBON CORP. BC001 Birdcage Installation Manual

BLUE RIBBON CORP. BC001 Birdcage Installation Manual Product Overview: This manual is applicable for the BC001 Birdcage Submersible Level Transmitters. If the product you have has a different prefix part number than listed above please contact the factory

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information

MBA-MM-1040/10/13/1665 MULTI MEDIA FILTERS

MBA-MM-1040/10/13/1665 MULTI MEDIA FILTERS MASTER Water Conditioning Corp. www.masterwater.com Installation and Operation Manual MBA-MM-1040/10/13/1665 MULTI MEDIA FILTERS with the 263/742 Logix Control Valve June 2010 Table of Contents Page No.

More information

OPL BASIC. Dosing System for Professional Laundry machines. Contents

OPL BASIC. Dosing System for Professional Laundry machines. Contents OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page

More information

How To Size A Stenner Pump

How To Size A Stenner Pump Metering Pumps Manufactured Since 1957 PCM Series Pump Control Module INSTALLATION AND MAINTENANCE MANUAL Table of Contents WarrantyandServicePolicy...3 Safety Information...............................................

More information

H.V.A.C. Design Plumbing Design

H.V.A.C. Design Plumbing Design H.V.A.C. Design H.V.A.C. Design Mira Costa College Arts Complex CP Upgrade 1. PART 1 GENERAL 1.1. DESCRIPTION SECTION 23 09 00 HVAC INSTRUMENTATION AND CONTROL 2. PART 2 - PRODUCTS 2.1. Materials

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1 Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,

More information

Electric Panel Pump Control System. Operation, Maintenance and Installation Manual

Electric Panel Pump Control System. Operation, Maintenance and Installation Manual Manual No. 5EP-OM1-1 Electric Panel Pump Control System Operation, Maintenance and Installation Manual INTRODUCTION... 1 RECEIVING AND STORAGE... 1 DESCRIPTION OF OPERATION... 1 INSTALLATION... 2 SEQUENCE

More information

WIRELESS REMOTE MONITORING OF CATHODIC PROTECTION SYSTEMS. John Hawkyard MICorr Deputy General Manager Rawabi Corrosion Technology Co Ltd Al-Khobar

WIRELESS REMOTE MONITORING OF CATHODIC PROTECTION SYSTEMS. John Hawkyard MICorr Deputy General Manager Rawabi Corrosion Technology Co Ltd Al-Khobar WIRELESS REMOTE MONITORING OF CATHODIC PROTECTION SYSTEMS John Hawkyard MICorr Deputy General Manager Rawabi Corrosion Technology Co Ltd Al-Khobar INTRODUCTION Cathodic Protection is an electrochemical

More information

Introduction To SCADA and Telemetry

Introduction To SCADA and Telemetry Introduction To SCADA and Telemetry Joe Mullaney Senior I&C Engineer MSE Technology Applications, Inc. Tetragenics Division joe.mullaney@mse-ta.com Overview Definitions What is SCADA? What is Telemetry?

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY SECTION 28 13 00 SECURITY AND ACCESS CONTROL SYSTEM

DIVISION 28 ELECTRONIC SAFETY AND SECURITY SECTION 28 13 00 SECURITY AND ACCESS CONTROL SYSTEM DIVISION 28 ELECTRONIC SAFETY AND SECURITY PART 1 GENERAL 1.01 DESCRIPTION A. Division 28 Contractor shall extend a complete Matrix Systems Access Control System as shown on the Drawings and as specified

More information

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The

More information

i ChatterBox! Motorcycle Security

i ChatterBox! Motorcycle Security i Before you Start the Installation * Please read this manual to become familiar with the requirements necessary to complete the installation. * Use a high quality multi-meter to test all wires before

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

HEAVY WATER LEAK DETECTOR

HEAVY WATER LEAK DETECTOR HEAVY WATER LEAK DETECTOR WEB www.overhoff.com MODEL 1925 HEAVY WATER LEAK DETECTOR (HWLD) LOW LEVEL REAL TIME TRITIUM-IN-WATER MONITOR This monitor has been designed for real time low-level detection

More information

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply

More information

SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532.

SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532. SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES PART 1 GENERAL 1.01 RELATED WORK SPECIFIED ELSEWHERE A. Interior Raceways, Fittings, and Accessories: Section 260532. B. Wiring, General - 600 Volts

More information

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface

More information

MASTER. Water Conditioning Corp. MBA-10/13 FILTERS with the 253/742 Logix Control Valve. Installation and Operation Manual. www.masterwater.

MASTER. Water Conditioning Corp. MBA-10/13 FILTERS with the 253/742 Logix Control Valve. Installation and Operation Manual. www.masterwater. MASTER Water Conditioning Corp. www.masterwater.com Installation and Operation Manual MBA-10/13 FILTERS with the 253/742 Logix Control Valve June 2010 Table of Contents Page No. Topic Description 1 Model

More information

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing) CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.

More information

ATS Overhead Table Shelf System INSTRUCTION MANUAL

ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

Excellence through Versatility

Excellence through Versatility Metering Pumps Excellence through Versatility Liquid Metronics Incorporated has been providing quality products and service to the water treatment industry worldwide for over 25 years. Leading the way

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

SECTION 23 90 13 NOx, CO AND NATURAL GAS DETECTION, MONITORING AND ALARM CONTROL SYSTEMS

SECTION 23 90 13 NOx, CO AND NATURAL GAS DETECTION, MONITORING AND ALARM CONTROL SYSTEMS SECTION 23 90 13 NOx, CO AND NATURAL GAS DETECTION, MONITORING AND ALARM CONTROL SYSTEMS PART 1 - GENERAL 1.01 Section Includes A. Requirements for provision of the Natural Gas (CH4), Carbon Monoxide (CO)

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly

DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly DREXELBROOK A Leader In Level Measurement Solutions USonic-R Series Ultrasonic Level Measurement System User Friendly Set the measurement range directly in inches, feet, millimeters, centimeters, or meters

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

Mobile Data Power Model: MDP-25

Mobile Data Power Model: MDP-25 Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

MASTER. Installation and Operation Manual. Water Conditioning Corp. MCA Time Clock Series Residential Softeners. February 2011 Version

MASTER. Installation and Operation Manual. Water Conditioning Corp. MCA Time Clock Series Residential Softeners. February 2011 Version MASTER Water Conditioning Corp. Installation and Operation Manual MCA Time Clock Series Residential Softeners February 2011 Version Table of Contents Page No. Topic Description 1 Model # and Packaging

More information

Design & Construction Standards, Revised January 2013 5.21.30-1

Design & Construction Standards, Revised January 2013 5.21.30-1 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.

More information

Centro-Matic Automatic Lubrication Systems System Controls

Centro-Matic Automatic Lubrication Systems System Controls Selecting the right controls for your automated lubrication system is one of the last steps in the design process. Several different models may be chosen to control power-operated pumps, depending on the

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

PagePac PAGEPAL V-5335700

PagePac PAGEPAL V-5335700 PagePac Issue 3 by PAGEPAL V-5335700 INTRODUCTION The PagePal unit interfaces most telephone systems (PBX, KTS, Centrex) to virtually any public address audio system. In addition, PagePal furnishes inputs

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS

PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS 2 Table of Contents Safety... 4 Introduction... 5 Features and Benefits... 6 Control Overview... 7

More information

Technical Update TAA.TU.11093 Rev. 1

Technical Update TAA.TU.11093 Rev. 1 http://www.gambro.com/en/usa_tech/ 800-525-2623 303-222-6500 Technical Update TAA.TU.11093 Rev. 1 Effective: 05 APR 2013 CO# 13084 Product: Subject: From: Phoenix Dialysis System Required Electrical Safety

More information

Fire Pump Controllers Remote Alarm Panels

Fire Pump Controllers Remote Alarm Panels Fire Pump Controllers Remote Alarm Panels Remote Alarm Panels 1.8 Remote Alarm Panels FDAP-M Electric... DFDAP-M Diesel... Product Specifications... 2 6 9 Features 1-1 DFDAP-M / FDAP-M Remote Alarm Panel

More information

MASTER. Water Conditioning Corp. MP-MBA-15T-30T using the 255/762 Logix Control Valve. Installation and Operation Manual. www.masterwater.

MASTER. Water Conditioning Corp. MP-MBA-15T-30T using the 255/762 Logix Control Valve. Installation and Operation Manual. www.masterwater. MASTER Water Conditioning Corp. www.masterwater.com Installation and Operation Manual MP-MBA-15T-30T using the 255/762 Logix Control Valve July 2006 Table of Contents Page No. Topic Description 1 Model

More information

SPECIAL SPECIFICATION 6819 Wireless Ethernet Microwave Radio

SPECIAL SPECIFICATION 6819 Wireless Ethernet Microwave Radio 2004 Specifications CSJ 2266-02-127 SPECIAL SPECIFICATION 6819 Wireless Ethernet Microwave Radio 1. Description. Furnish and install Wireless Ethernet Microwave Radio (WEMR) as shown on the plans, as detailed

More information

The Pennsylvania State University ------------- Physical Security Office. Intrusion Alarm. Performance Specification

The Pennsylvania State University ------------- Physical Security Office. Intrusion Alarm. Performance Specification The Pennsylvania State University ------------- Physical Security Office Intrusion Alarm Performance Specification By PHYSICAL SECURITY OFFICE Group (Access Controls & Electronic Security Programs) and

More information

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical

More information

Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual

Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual Operation and Maintenance Manual Introduction Read all instructions thoroughly. Installation of the OilTector must comply with all Federal, State and Local Codes, Regulations and Practices. The OilTector

More information

Mono-Block II Installation & Operation Manual

Mono-Block II Installation & Operation Manual Mono-Block II Installation & Operation Manual Enraf Fluid Technology UK, Ltd. Enraf Fluid Technology USA, Inc. 6 Pennant Park, Standard Way 2000 Northfield Court Fareham, Hampshire, England PO16 8XU Roswell,

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

SingleNet Single Cable Control System

SingleNet Single Cable Control System Single Cable Control System Economical, Reliable and Expandable Two-Wire Single Cable System DRIP/MICRO IRRIGATION PRODUCTS Single Cable Control System System Manager or Irrigation Controller Controls

More information

ViZion Installation Guide

ViZion Installation Guide ViZion Installation Guide v2.0 1 ViZion Installation Guide Table of Contents Inventory Hardware Setup Understanding Synchronization Cable Begin by taking an inventory of the required equipment DR Unit

More information

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION: Revision Level: 01 Revision Date: 07/07/2011 Please read all instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Air Purifier. Failure to do

More information

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature

More information

ADDENDUM #1(BID PACKAGE # 3)

ADDENDUM #1(BID PACKAGE # 3) H2Engineering, Inc. 114 East Fifth Avenue Tallahassee, FL 32303 Phone 850.224.7922 Fax 850.224.5876 ADDENDUM #1(BID PACKAGE # 3) To: Jeff Williams From: Peter Lindstrom Co: Leon County Date: October 04,

More information

SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES

SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES 611-1 Description. This Section sets forth Contract acceptance procedures for installations of traffic control signals and devices

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply) transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

Water Leak Detection System

Water Leak Detection System Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright

More information

BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS

BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS INTRODUCTION Rupture discs are often used as primary pressure relief devices and to isolate pressure relief valves. When used as a primary pressure relief

More information

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05 RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,

More information

10/20 COMBINATION UNIT

10/20 COMBINATION UNIT MASTER Water Conditioning Corp. www.masterwater.com Installation and Operation Manual 10/20 COMBINATION UNIT with the 255/742 Logix Control Valve With Vortech October 2006 Table of Contents Page No. Topic

More information

2.24. Pump Controller 704. Data Sheet

2.24. Pump Controller 704. Data Sheet Pump Controller 704 2.24 There are several reasons to choose an MJK pump controller. Pump controller 704, as described in this data sheet, was introduced in 1989. It has been updated several times with

More information

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING PART 1-GENERAL 1.01 DESCRIPTION A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width modulated (PWM) inverter designed for use on a standard NEMA

More information

BLADDER SURGE CONTROL SYSTEM

BLADDER SURGE CONTROL SYSTEM PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures

More information

Invitation to Bid FIRE ALARM & DETECTION SYSTEM

Invitation to Bid FIRE ALARM & DETECTION SYSTEM Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066

More information

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage

More information

DeltaSpan Submersible Pressure Level Transmitter Manual LD31 Series 22 AUG 08 Rev A

DeltaSpan Submersible Pressure Level Transmitter Manual LD31 Series 22 AUG 08 Rev A DeltaSpan Submersible Pressure Level Transmitter Manual LD31 Series 22 AUG 08 Flowline, Inc. 10500 Humbolt Street Los Alamitos, CA 90720 Tel: (562) 598-3015 Fax: (562) 431-8507 www.flowline.com 22 AUG

More information

The Control of ph and Oxidation Reduction Potential (ORP) in Cooling Tower Applications By Charles T. Johnson, Walchem Corporation

The Control of ph and Oxidation Reduction Potential (ORP) in Cooling Tower Applications By Charles T. Johnson, Walchem Corporation The Control of ph and Oxidation Reduction Potential (ORP) in Cooling Tower Applications By Charles T. Johnson, Walchem Corporation Introduction The importance of keeping cooling tower water in proper chemical

More information

Bi-Directional Amplifier Systems

Bi-Directional Amplifier Systems Bi-Directional Amplifier Systems Installation and Operation Manual Model Series 850622 EMR CORPORATION 17431 N. 25th Ave. Phoenix, AZ 85023 Emails: sales@emrcorp.com Phone: (623) 581-2875 Toll-Free: (800)

More information

FAQ s on Siemens Magmeters

FAQ s on Siemens Magmeters FAQ s on Siemens Magmeters 1. The cables for the coils and electrodes for the magmeters look the same. Does it matter which cable is used for coils and which one is used for the electrodes? Both cables

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless

More information

Streaming Potential System (SPT1000, SPD1000)

Streaming Potential System (SPT1000, SPD1000) Streaming Potential System (SPT1000, SPD1000) User's Manual Sentrol Systems, Inc. 3949 Cotswold Dr. SW, Lilburn, GA 30047-2371 Tel: 770-564-1541, Fax: 770-564-8605 www.sentrolsystems.com Since the streaming

More information

LDG DTS-4/4R Desktop Coaxial Switch / Remote

LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 ldg@ldgelectronics.com www.ldgelectronics.com

More information

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030)

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) PART 1 - GENERAL SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) 1.01 SUMMARY This section describes the operation and control of a drip irrigation system. The major components

More information

Installation & Operation Manual for EC-8 Phone Line Consolidator

Installation & Operation Manual for EC-8 Phone Line Consolidator Installation & Operation Manual for EC-8 Phone Line Consolidator For Use With Talk-A-Phone Hands-Free Emergency Phones Section Page Getting Started 2 Hardware Installation 3 Software Programming 5 Operation

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

Ceiling Mount Air Handler Manual

Ceiling Mount Air Handler Manual www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty

More information

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence

More information

Chemical Feed System Operation and Design Considerations

Chemical Feed System Operation and Design Considerations PNWS AWWA MAY 7, 2014 EUGENE, OREGON Chemical Feed System Operation and Design Considerations Kevin Batridge Lake Oswego Tigard Water Partnership Austin Peters MWH Global Chemical Delivery and Storage

More information

ASCO SERIES 185 Power Transfer Switches

ASCO SERIES 185 Power Transfer Switches ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder

OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder P R O D U C T G R O U P OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder Manual # 600-0901 November 30, 1999 Rev. D - 99068 DESCRIPTION The ST-888 Mobilecall Display Decoder is a desktop

More information