Installation instructions. Lightning protection/earthing. HVI power HVI power long.

Size: px
Start display at page:

Download "Installation instructions. Lightning protection/earthing. HVI power HVI power long."

Transcription

1 Lightning protection/earthing Installation instructions HVI power HVI power long GB Publication No / Update Mat. No Copyright 2016 DEHN + SÖHNE

2 CONTENTS 1. Application of HVI power Conductors Safety notes Specification of HVI power Conductors Design of HVI power Conductors Technical data Chemical properties Different types Pre-assembled HVI power Conductors Pre-assembled HVI power Conductors for installation inside the supporting tube Pre-assembled HVI power Conductors for installation outside the supporting tube HVI power long - on a reel Required accessories, tools and mounting parts HVI power Conductors for installation inside / outside the supporting tube Assembly of HVI power Conductors Cutting HVI power Conductors to length / stripping HVI power Conductors Mounting the head piece / connection element Wrapping a heat shrinkable sleeve around the head piece / connection element Installation Installing HVI power Conductors in the supporting tube Installing HVI power Conductors outside the supporting tube Sealing end Sealing end range at the supporting tube based on the example of an antenna Variable sealing end Sealing end at a building s structure

3 6.4 Installing HVI powerconductors Installation with regard to the wind zone / wind speed Checklist for installing HVI Conductors

4 1. Application of HVI power Conductors To avoid dangerous flashover between parts of the external lightning protection system and internal installations such as conductive parts (electrical installation, pipework, etc.), the separation distance s must be observed when installing lightning protection systems. High impulse voltages cause flashover on the surface of insulating material if no additional measures are taken. This effect is also referred to as creeping flashover. If the creeping discharge inception voltage is exceeded, a surface discharge is initiated which can easily flash over a distance of several metres. To prevent creeping discharges, HVI power Conductors feature a special outer sheath which allows high lightning impulse voltages to be discharged to a reference potential. For functional reasons, a connection is established in the sealing end range between the semiconductive outer sheath and the building s equipotential bonding system (no lightning voltage). This connection to the functional equipotential bonding system can be made e.g. at earthed metal roof-mounted structures located in the protected zone of the lightning protection system, earthed parts of the building s structure that do not carry lightning voltage or the protective conductor of the low-voltage system. No conductive or earthed parts may be located in the sensitive sealing end range within the separation distance s. 2. Safety notes ÂÂ IEC : Installation, electrotechnical expertise ÂÂHVI power Conductors may only be installed under the conditions shown and referred to in these installation instructions. ÂÂOnly qualified and trained personnel (lightning protection specialists) may install HVI power Conductors. We recommend to visit a special training course on HVI products held by DEHN + SÖHNE ( ÂÂFor safety reasons, installation work must be stopped as soon as a thunderstorm approaches / is noticed. The components of the HVI power system have been tested as a complete system. Mixing components of the HVI power system with components from other manufacturers is not permitted. 4

5 ÂÂPrior to installation, HVI power Conductors must be examined for good order and condition. If damage or any other defect is found, HVI power Conductors must not be installed. The black sheath of HVI power Conductors must not be damaged by compressive deformation or cuts. ÂÂWhen using HVI power Conductors fire and explosion protection measures must be taken. ÂÂIf HVI power Conductors are installed on thatched roofs (e.g. reed, straw), special installation conditions must be observed for these flammable locations. The special installation conditions for HVI Conductors are described in our Lightning Protection / Earthing main catalogue (HVI Lightning Protection for Thatched Roofs). These conditions also apply to HVI power Conductors. ÂÂIf the supporting tube is led through a roof, the roof must be properly sealed. Warm roofs must be properly sealed and insulated. ÂÂHVI power Conductors are suitable for outdoor use and can be installed downstream of the sealing end e.g. on roofs, in walls, in concrete (mechanically protected, if required) or on facades / facade constructions. However, the conductors are not suitable for permanent exposure to moisture. HVI power Conductors must not be installed in the soil. ÂÂSoiled HVI power Conductors can be cleaned with a cloth soaked with a special cleaning agent (Part No ). To be able to comply with dangerous goods regulations, this product is only transported within Germany and Austria. ISOPROPYL ALCOHOL (99.1 to 99.9 %) (CSA No ) can be used as an alternative! ÂÂHVI power Conductors must not be painted due to the special design of the outer sheath. ÂÂThe function of HVI power Conductors is to maintain the separation distance. They do not have a magnetic shielding effect due to their design. Therefore, induction effects in secondary conductors / loops must be observed. If required, surge protection measures must be taken. ÂÂFor application-specific questions, please contact the relevant sales team or the DEHN representative in your country. Â Â It has not yet been checked whether HVI power Conductors are suitable for use in hazardous areas. Therefore, it is not allowed to use HVI power Conductors in these areas. 5

6 3. Specification of HVI power Conductors 3.1 Design of HVI power Conductors HVI power Conductors are high-voltage-resistant, insulated down conductors with a semiconductive outer sheath (see Fig. 1). They are typically used as insulated down conductors for lightning protection systems to maintain the separation distance in accordance with IEC At first, the separation distance s must be calculated as described in 6.3 of the IEC standard using a material factor km = 1 in air, or km = 0.5 for solid material. It must be checked whether this calculated separation distance can be implemented by means of the equivalent separation distance of the HVI power Conductor (see technical data, Table 1, page 7): calculated separation distance equivalent separation distance. If this is not the case, the measures described in 6.3, page 22 must be taken. The length which is required for calculating the separation distance s is measured from the head piece to the next lightning equipotential bonding level, e.g. the earth-termination system. In case of a down conductor with k c = 1, the following maximum conductor lengths are permitted depending on the class of LPS: LPS I max m LPS II max m LPS III max m semiconductive outer sheath (outer semiconductor, black) insulating layer smoothing layer stranded copper conductor (25 mm²) Figure 1 Design of HVI power Conductors 6

7 3.2 Technical data Outer sheath black, RAL 9011 Equivalent separation distance of the HVI power Conductor Outer diameter Minimum bending radius Air Solid material Permanent temperature range (fixed installation) 0.9 m 1.8 m 27 mm 270 mm -30 to +70 C Ambient temperature and conductor temperature during installation and processing Maximum tensile load Stranded inner conductor (copper) Table 1 Technical data of HVI power Conductors -5 to +40 C 1,200 N 25 mm² 3.3 Chemical properties Halogen-free Reaction to fire Weather-proof (UV-stabilised) Fire load Diluents yes not self-extinguishing yes 6.4 kwh/m none Table 2 Chemical properties of HVI power Conductors 7

8 4. Different types The component range of the HVI power Conductor system consists of a HVI power Conductor and a range of connection and fixing elements matched to this conductor. Special know-how is required to design and install HVI power Conductors. HVI power Conductors are available as pre-assembled conductors or on a 100 m reel (HVI power long). More detailed information about the component range of the HVI power Conductor system can be found in our brochures DS210/E and DS212/E, our Lightning Protection / Earthing main catalogue or at As a basic principle, all HVI power Conductors can be shortened, but not extended! 4.1 Pre-assembled HVI power Conductors In general, one conductor end of the pre-assembled HVI power Conductor is fitted with the relevant connection element as (Table 3, page 9 and Table 4, page 10). Thus, the head piece is firmly mounted and a heat shrinkable sleeve is wrapped around it. If required, the second conductor end can be shortened to exactly match the loose connection element to the design of the installation. When ordering HVI power Conductors, the conductor / minimum length must be observed / indicated. This information is binding. Conductors cannot be returned since they are tailored to customer needs (pre-assembled conductor lengths). Pre-assembled HVI power Conductors are available with a standard / minimum length of 6 m. Customised conductors can be ordered in 0.5 m steps. The standard / minimum length of 6 m must be used in combination with a 3.5 m long supporting tube. A minimum conductor length of 8 m is recommended for a 5 m long supporting tube. A connection element, heat shrinkable sleeve and hexagon socket wrench are loosely delivered (see also Table 3). Special tools (HVI cutter and HVI strip 27) should be used to cut HVI power Conductors to length / shorten HVI power Conductors and the connection element / heat shrinkable sleeve should be attached by means of the relevant connection element (see 5., page 16 ff.). 8

9 4.2 Pre-assembled HVI power Conductors for installation inside the supporting tube Pre-assembled HVI power Conductor for installation inside the supporting tube are used to directly connect the air-termination system of the external lightning protection system to the earth-termination system, e.g. isolated air-termination system of a mobile phone antenna with HVI power Conductor installed inside the supporting tube. Pre-assembled HVI power Conductors for installation inside the supporting tube Installation inside the supporting tube Part No. Standard / minimum length m + x m (max m in case of kc = 1) Delivery includes 1 fixed head piece with heat shrinkable sleeve 1 connection element, 1 heat shrinkable sleeve and 1 hexagon socket wrench (loose) Fixed head piece installation inside the supporting tube Head piece and HVI power Conductor with heat shrinkable sleeve HVI power Conductor with special sheath Loosely delivered: - Connection element - Heat shrinkable sleeve - Hexagon socket wrench Table 3 Table 3 Pre-assembled HVI power-leitung for installation inside the supporting tube 9

10 4.3 Pre-assembled HVI power Conductors for installation outside the supporting tube Pre-assembled HVI power Conductors for installation outside the supporting tube are used to directly connect the air-termination system of the external lightning protection system to the earth-termination system, e.g. isolated air-termination system of a mobile phone antenna with HVI power Conductors installed inside the supporting tube. HVI power Conductors may only be installed outside the supporting tube if GRP/Al HVI-power supporting tubes are used. Pre-assembled HVI power Conductor for installation outside the supporting tube Installation outside the supporting tube Part No. Standard-/ minimum length m + x m (max m, in case of k c = 1) Delivery includes 1 fixed head piece with heat shrinkable sleeve 1 fixing ring, 1 contact pin, 1 connection element, 2 threaded pins, 1 heat shrinkable sleeve, 2 hexagon socket wrenches, 2 lock nuts (loosely delivered) installation outside the supporting tube Fixed head piece HVI power Conductor with special sheath Head piece and HVI power Conductor with heat shrinkable sleeve Loosely delivered: -Fixing ring -Contact pin -Connection element -2 threaded pins -Heat shrinkable sleeve -2 hexagon socket wrenches -2 lock nuts Table 4 Pre-assembled HVI power Conductor for installation outside the supporting tube 10

11 4.4 HVI power long - on a reel HVI power long Conductors are delivered on a disposable reel or are cut to length. It must be observed that the connection set required for installation is not included in delivery. Consequently, the connection set and the required EB connection element(s) must be ordered separately depending on the requirements, type and configuration of the installation (see Table 5). General accessories and tools are listed in Table 6, page 12/13. HVI power long Part No. Length Delivery includes Field of application m Disposable reel with an outer diameter of approximately 900 mm Width: about 474 mm 1 Allen key and installation instructions m HVI power, pre-assembled For on-site assembly Installation outside the supporting tube Connection set: 1 head piece 1 connection element 2 heat shrinkable sleeves Connection set, HVI power long Head piece and connection element for connection to both ends of the HVI power Conductor for installation inside the supporting tube Installation outside the supporting tube EB connection element EB connection element (Ø 27 mm) for controlling the electrical field in the sealing end range. Required for the second sealing end Variable tripod with EB element for the sealing end, variable height from 610 to 1095 mm (top edge of the concrete base) Table 5 HVI power long - Reel and required accessories 11

12 4.5 Required accessories, tools and mounting parts HVI power Conductors can be installed using the following mounting parts and tools: Part No. Delivery includes Description Metal conductor holder HVI power Conductor Stainless steel conductor holder (Ø 27 to 30 mm), M8 thread Metal conductor holder HVI power Conductor Stainless steel conductor holder (Ø 27 to 30 mm), M8 thread with plastic base Metal conductor holder HVI power Concdutor Stainless steel conductor holder (Ø 27 to 30 mm), M6 thread Metal conductor holder HVI power Conductor Stainless steel conductor holder (Ø 27 to 30 mm), with slot (Ø 5.5 x 10 mm) HVI strip 27 Stripping tool for stranded conductors (Ø 27 mm) consisting of a handle and a stripping insert HVI head 27 Stripping insert (Ø 27 mm) for HVI strip 27 stripping tool HVI cutter Cable pliers for stripping HVI power Conductors Holder for flat roofs (SET) For installing conductors on flat roofs, weight: 8.5 kg 12

13 Part No. Delivery includes Description Holder for flat roofs (SET) For installing conductors on flat roofs, weight: 4.6 kg Holder for gable roofs Brace with perforated bending points for installing HVI power Conductors on gable roofs Disconnecting clamp Rd/Rd Rd/Fl UNI disconnecting clamp Rd Stainless steel disconnecting clamp (8 to 10 / 8 to 10 mm) with intermediate plate for two round conductors or 8 to 10 / 30 mm for round and flat conductors (200 ka for LPS I) Stainless steel UNI disconnecting clamp 8 to 10 / 16 mm for connecting an air-termination rod or earth entry rod to a round conductor (200 ka for LPS I) KS connector Rd Stainless steel KS connector (10 mm) for connecting round conductors to flat profiles (200 ka for LPS I) MV clamp Rd/Rd Stainless steel MV clamp for round conductors (8-10 mm) for universal use as cross, T and parallel clamp (200 ka for LPS I) MV clamp Rd/Rd Stainless steel MV clamp for round conductors (8-10 mm / 16 mm) for universal use as cross, T and parallel clamp (200 ka for LPS I) Variable tripod with EB element For establishing the variable sealing end Wall mounting bracket for supporting tubes Wall mounting bracket, adjustment range from 150 to 200 mm Fixing clamp with tensioning strap Clamping range: 50 to 300 mm Table 6 Accessories and tools 13

14 4.6 HVI power Conductors for installation inside / outside the supporting tube The supporting tubes in which the HVI power Conductors are integrated house an EB element in the form of a spring element. The head of the supporting tube is mechanically sealed and thus water-proof. For static reasons, spanning cables over several supporting tubes to split the current is not possible in every situation! Please contact us for more detailed information. Different types of supporting tubes are available for installing HVI power Conductors inside / outside the supporting tube (see Table 7., page 14 and Table 8., page 15): HVI power Conductors may only be installed outside the supporting tube if GRP/Al HVI-power supporting tubes are used. Types of stainless steel supporting tubes for installation inside the supporting tube Part No. Consisting of: Component length Total length Minimum length of the HVI power Conductors Supporting tube 3.5 m 4.5 m 6 m + x m Supporting tube with side outlet Air-termination tip (Ø 10 mm) 1.0 m Supporting tube 3.5 m 6.0 m 6 m + x m Supporting tube with side outlet Air-termination tip Ø 22/16/10 mm 2.5 m optionally available with side outlet optionally available with side outlet Supporting tube 5.0 m 6.0 m 6 m + x m Supporting tube with side outlet Air-termination tip (Ø 10 mm) Supporting tube Supporting tube with side outlet Air-termination tip Ø 22/16/10 mm 1.0 m (recommended minimum length: 8 m) 5.0 m 7.5 m 6 m + x m (recommended minimum length: 8 m) 2.5 m Table 7 Types of stainless steel supporting tubes 14

15 Types of aluminium supporting tubes for installation inside / outside the supporting tube Part No. Consisting of: Component length Supporting tube with side outlet Total length Minimum length of the HVI power Conductors 3.5 m 3.5 m 6 m + x m Supporting tube with side outlet and air-termination tip (Ø 10 mm) Supporting tube with side outlet and air-termination rod Ø 22/16/10 mm 3.5 m 1.0 m 3.5 m 2.5 m 4.5 m 6 m + x m 6.0 m 6 m + x m side outlet Supporting tube with side outlet Supporting tube with side outlet and air-termination tip (Ø 10 mm Supporting tube with side outlet and air-termination rod Ø 22/16/10 mm 5.0 m 5.0 m 6 m + x m (recommended minimum length: 8 m) 5.0 m 1.0 m 5.0 m 2.5 m 6.0 m 6 m + x m (recommended minimum length: 8 m) 7.5 m 6 m + x m (recommended minimum length: 8 m) Supporting tube 3.5 m 3.5 m 6 m + x m Supporting tube with air-termination tip Ø 10 mm Supporting tube with air-termination rod Ø 22/16/10 mm 3.5 m 1.0 m 3.5 m 2.5 m 4.5 m 6 m + x m 6.0 m 6 m + x m (recommended minimum length: 8m) Supporting tube 5.0 m 5.0 m 6 m + x m (recommended minimum length: 8m) Supporting tube with air-termination tip Ø 10 mm Supporting tube with air-termination rod Ø 22/16/10 mm 5.0 m 1.0 m 5.0 m 2.5 m 6.0 m 6 m + x m (recommended minimum length: 8m) 7.5 m 6 m + x m (recommended minimum length: 8m) Table 8 Types of aluminium supporting tubes 15

16 5. Assembly of HVI power Conductors 5.1 Cutting HVI power Conductors to length / stripping HVI power Conductors The HVI cutter (cable pliers, Part No ) can be used to cut HVI power Conductors to the required length. Ensure right-angled cut! The stripping tool (Part No ) allows the outer semiconductive sheath and the PE insulation of the HVI power Conductor to be easily and reliably stripped without damaging the copper conductor underneath it. The HVI strip 27 tool consists of a handle and an exchangeable stripping insert. This HVI strip 27 stripping insert (Part No ) can be reordered individually. The stripping insert is plugged into the handle without tools via a bayonet coupling. The stripping length can be adjusted in steps of 0.2 mm by means of the knob housed in the handle. The chosen stripping length is visible on the scale of the handle. The effective stripping length corresponds to the set length with a tolerance of ± 2 mm (see Fig. 2). The HVI strip 27 tool is handled as follows: ÂÂSet the stripping length (35 mm) on the tool or check whether the set length is correct. ÂÂAttach the stripping insert of the tool to the cut conductor end. ÂÂThe sheath is cut / stripped by turning the handle clockwise and applying light pressure by means of the tool.! Safety note: Do NOT place your finder in the stripping insert. Risk of injury! HVI head 27 stripping insert HVI strip 27 handle knob for adjusting the stripping length HVI power Conductor bayonet coupling scale Figure 2 HVI head 27 tool 16

17 5.2 Mounting the head piece / connection element To mount the head piece / connection element, the insulation of HVI power Conductors must be removed by 35 mm. After removing the insulation, the head piece / connection element is mounted on the conductor ends of the HVI power Conductor. The following steps must be observed (see also Fig. 3): ÂÂPosition the head piece / connection element above the HVI power Conductors and turn it clockwise onto the relevant conductor end as far as it will go. To this end, an open-end wrench (wrench size 19) can be used at the wrench contact surface of the head piece / connection element. ÂÂTighten the two threaded pins using a tightening torque of 5 Nm. Thus, the copper conductor of the HVI power Conductors is safely electrically connected (capable of carrying lightning currents). HVI power Conductor stranded copper conductor 35 mm threaded pins (coated), tightening torque of 5 Nm wrench contact surface wrench size 19 head piece wrench contact surface wrench size 19 connection element Ø 10 mm wrench contact surface wrench size 19 connection element Figure 3 Mounting the head piece / connection element 17

18 5.3 Wrapping a heat shrinkable sleeve around the head piece / connection element Applying heat shrinkable sleeves After mounting the head piece / connection element to the HVI power Conductor, a heat shrinkable sleeve must be wrapped around the relevant mounting areas to protect them from mechanical, environmental or chemical influences. The connection set includes two heat shrinkable sleeves. The following must be observed when wrapping a heat shrinkable sleeve around the head piece / connection element: ÂÂThe indicated shrinking area between the head piece / connection element and the HVI power Conductor must be observed (Fig. 4). ÂÂThe heat shrinkable sleeve is applied between the front shrinking area of the relevant head piece / connection element and the HVI power Conductor. The heat shrinkable sleeves must flush with the shrinking area. If required, they must be repositioned during the shrinking on process. ÂÂThe specified shrinking temperature of max. 150 C must be observed! ÂÂThe shrinking temperatures in the shrinking area of the HVI power Conductor must not be too high. In case of excessive shrinking temperatures, the semiconductive sheath of the HVI power Conductor can be damaged or destroyed and the function of the HVI power Conductor may not be ensured any more. ÂÂThe heat shrinkable sleeve must not trap air or form bubbles! Shrinking area of the head piece Shrinking area of the connection element Shrinking area of the connection element Correct shrinking Incorrect shrinking Figure 4 Wrapping around a heat shrinkable sleeve around the head piece / connection element 18

19 6. Installation 6.1 Installing HVI power Conductors in the supporting tube Before installing the supporting tube, insert and fix the head piece of the pre-assembled HVI power Conductor into the supporting tube and fix it (see also page Figure 5., page 20). The following steps must be observed: ÂÂUnscrew the locking screw of the head piece (M8 x 25 mm) at the head of the supporting tube. ÂÂInsert the HVI power Conductor from below into the supporting tube. To this end, the compressive strength of the integrated EB spring element must be overcome. The conductor can be inserted and removed several times. To contact the head piece, insert the HVI power Conductor into the supporting tube as far as it will go and hold it there. ÂÂFirmly tighten the locking screw (M8 x 25 mm) again using a tightening torque of 15 Nm. This ensures that the head piece is fixed in the supporting tube and that is electrically connected (capable of carrying lightning currents). Make sure that there is a sufficient distance (about 7 mm) between the screw head and the supporting tube after tightening the locking screw. The adhesive coating of the screw only hardens after about 5 minutes so that the screw can be correctly positioned and tightened during this period. After hardening of the adhesive coating, the screw must be replaced by a new one when the screw is removed. ÂÂCheck whether the HVI power Conductor is properly fixed in the supporting tube (see Fig. 5). Proper installation can be verified by slightly pulling the conductor at the point where it leaves the supporting tube. ÂÂThe relevant air-termination tip or rod must be installed before or after the supporting tube has been installed depending on the configuration of the installation. Â Â Insert the air-termination tip or rod from above into the head of the supporting tube and tighten the two locking screws (M8 x 16 mm / M8 x 10 mm) using a tightening torque of 15 Nm. 19

20 As-delivered condition air-termination rod ø = 22/16/10 mm air-termination tip ø 10 mm locking screws tightening torque of 15 Nm -air-termination tip 2x M8x16 mm -air-termination rod 2x M8x10 mm Assembled condition Correct assembly head of the supporting tube water-proof locking screw head piece, hexagon screw M8 x 25 mm, tightening torque of 15 Nm approx. 7 mm locking screw head piece (hexagon screw M8x25 mm, tightening torque of 15 Nm) GRP / StSt supporting tube Incorrect assembly approx. 13 mm approx. 0 mm optionally available with side outlet HVI power Conductor (as-delivered condition) Figure 5 Installation of the head piece in the supporting tube 20

21 6.2 Installing HVI power Conductors outside the supporting tube Attach the fixing ring Remove the Allen screws Tighten the threaded pins M8 x 50 (tightening torque of 15 Nm) Place the contact plate on the threaded pins Install the HVI power Conductor Mount the self-locking nuts with serrated bearing using a tightening torque of 15 Nm to fix the connection part Fix the conductor at the fixing ring Nm 1. sectional view 7. Figure 6 Installing the HVI power Conductor outside the supporting tube 21

22 6.3 Sealing end The calculated separation distance s" from conductive / earthed parts must be maintained in the sealing end range. No conductive or earthed parts such as metal conductor holders, structural parts, reinforcement, etc., may be installed in the sealing end range, for example: ÂÂAt the supporting tube between the head piece and EB connection element (see 6.3.1, page 22) ÂÂVariable sealing end at the ring conductor / capping of the roof parapet (see 6.3.2, page 26) ÂÂSealing end at the building s structure between the EB connection element and the earth connection element Sealing end range at the supporting tube based on the example of an antenna The sealing end range ranges from the connection of the head piece to the EB spring element integrated in the supporting tube (see Fig. 7, detail A and B) and can be assumed to run along the entire route of the GRP tube. Due to the mechanical spring contact, acting as an EB element, the HVI power Conductor (semiconductive special sheath) is connected to the supporting tube. To this end, the supporting tube must be conductively connected to the next equipotential bonding system of the installation connection of the head piece Detail A EB element Detail B antenna mast Detail A: connection of the head piece sealing end range connection with the equipotential bonding system of the installation connection to the earth-termination system α α s pipe clamp supporting tube HVI power Conductor Detail B: EB spring element mechanical spring contact The conductive connection between the supporting tube and the earthed metal antenna mast is established by means of e.g. a pipe clamp (Part No ) (mechanical and electrical connection). Figure 7 Sealing end range in the supporting tube 22

23 An antenna pipe clamp (Part No ), for example, can be used to connect the antenna mast to the equipotential bonding system (functional equipotential bonding system). HVI power Conductor installed inside the supporting tube with pipe clamp on a mobile phone antenna protective angle acc. to IEC , Table 2 e.g. air-termination tip StSt, (Ø 10 mm, L = 1000 mm), Part No α α s sealing end range 1800 mm e.g. antenna GRP / StSt supporting tube, e.g. Part No , supporting tube L = 3500 mm e.g. stainless steel pipe clamp, Part No clamping range supporting tube Ø = 50 to 300 mm Note: Observe antenna earthing as per DIN VDE 0855! HVI power Conductor earth connection element connection to the building`s equipontential bonding system earth-termination system Figure 8 Isolated air-termination system with a HVI power Conductor installed on a mobile phone antenna Pipe clamp 23

24 HVI power Conductor integrated in the supporting tube with wall fixing bracket protective angle acc. to IEC , Table 2 α α e.g. air-termination rod (Ø 22/16/10 mm, L = 2500 mm), Part No s sealing end range 1800 mm supporting tube with air-termination rod, GRP / StSt, e.g. Part No , supporting tube L = 3500 mm + air-termination rod L = 2500 mm e.g. wall fixing bracket, StSt, clamping range supporting tube Ø = 40 to 50 mm, with double cleat, Part No double cleat for connecting 2x Rd 8 to 10 mm to the equipotential bonding system HVI power Conductor earth-termination system earth connection element connection to the building s equipotential bonding system Figure 9 Isolated air-termination system with HVI power Conductor and wall fixing bracket 24

25 HVI power long Conductor installed inside the supporting tube with side outlet / installation in a tripod or four-legged stand Example of: tripods / four-legged stands (height of 1750 mm) insert supporting tube supporting tube unscrewed clamp tighten supporting tube supporting tube HVI power Conductor HVI power Conductor stand pipe stand pipe Figure 10 Tripod / four-legged stand (e.g. Part Nos / / / ) Note: For more detailed information on the installation of tripods and four-legged stands, please refer to installation instructions No which can be downloaded at in the Download section or enter the relevant Part No. in the Product search on our homepage. 25

26 6.3.2 Variable sealing end If the HVI power Conductor is not connected to the earth-termination system, but to parts carrying lightning voltage (e.g. capping of the roof parapet, ring conductor), Table 9 is decisive for the effective length of the sealing end (see also Fig. 11, page 27 and Fig. 12, page 28). No special installation conditions must be observed in the area below the separation distance s of 17.5 cm (in air) on the earth connection element (direct connection). Due to the routing of the HVI power Conductor and the resulting reduced separation distance, it is not common to establish a second sealing end if the separation distance s is 75 cm (in air). Length of the variable sealing end (cm) maximum HVI power Conductor maximum variable sealing end HVI power Conductor Part No common variable sealing end of the HVI power Conductor Equivalent separation distance s (in air) 75 Table 9 Variable sealing end The length of the variable sealing end is determined by multiplying the separation distance s air by the factor 2. Length L of the sealing end = separation distance S air x 2 26

27 Variable sealing end at isolated ring conductors / cappings of the roof parapet If several parts of an installation are to be protected, it is not advisable to lead the HVI power Conductor from each air-termination system to the earth-termination system. The HVI power Conductor from the air-termination system can be connected to e.g. an isolated ring conductor or to the capping of the roof parapet. From this isolated ring conductor (capping of the roof parapet), several down conductors can routed to the earth-termination system. In this case, the partitioning coefficient k c is reduced downstream of the isolated ring conductor. As a result, the separation distance s is also reduced. Pre-assembled HVI power Conductor or HVI power long Conductor can be used for this purpose (see Fig. 11 and 12, page 28). The isolated ring conductor must be installed on spacers and concrete bases e.g. on the roof level while maintaining the calculated separation distance s. variable sealing end L=S air x 2 connection element 350 mm - max mm (standard) isolated ring conductor s air spacer HVI power Conductor min. length, L = S air conductor holder e.g. Part No variable tripod stand with EB element Part No connection with the building s equipotential bonding system Figure 11 Variable sealing end on an isolated ring conductor with HVI power Conductor 27

28 variable sealing end L=S air x mm - max mm (standard) connection element capping of the roof parapet s air HVI power Conductor min. length, L = S air conductor holder e.g. Part No variable tripod stand with EB element Part No connection to the building s equipotential bonding system Figure 12 Variable sealing end on the capping of the roof parapet 28

29 6.3.3 Sealing end at a building s structure If HVI power Conductor are installed on a building s structure, the calculated separation distance s in the sealing end range must be maintained from the metal parts in the building s structure. The sealing end range ranges from the EB connection element to the connection of the earth connection element (see Fig. 13). The mechanical contact with the EB element (semiconductive sheath) allows to discharge lightning impulse voltages to a reference potential. To this end, a conductive connection to the next equipotential bonding system (equipotential bonding level) of the installation is required. A UNI disconnecting clamp (Part No , 200 ka) is used to connect the earth connection element of the HVI power Conductor to the earth-termination system. Detail A: EB element EB connection element Detail A (Part No ) holder, e.g. Part No connection to the building s equipotential bonding system EB Detail B: connection of the earth connection element HVI power Conductor building s structure sealing end range 35 cm mm earth connection element Detail B s s down conductor connection to the earth-termination system disconnecting clamp, Part No Figure 13 Sealing end range on a building s structure 29

30 The following must be observed: ÂÂVThe black surface of the HVI power Conductor must be cleaned before installing the EB connection element (Part No ). ÂÂThe surface must be smooth and free of grease. ÂÂPossible grease must be removed using a cloth soaked with a special cleaning agent (Part No ). ÂÂThe EB connection element must not be soiled.. ÂÂThe EB connection element must firmly enclose the HVI power Conductor. 6.4 Installing HVI powerconductors The entire HVI power Conductor must be installed in the protected zone of the air-termination system of the external lightning protection system and must not contact parts of the air-termination system, down conductor or structural parts that carry lightning voltage. An exception can be made if the separation distance s at the point where the HVI power Conductor crosses the part carrying lightning voltage (air-termination system, capping of the roof parapet, down conductor) is 35 cm (in air) or 70 cm (in case of solid material). In this case, the sheath of the HVI power Conductor can be connected to the part carrying lightning voltage. If installed downstream of the sealing end range, the HVI power Conductor must be fixed at intervals of 1 m. The fixing screws of the metal conductor holders must be tightened with a tightening torque of max. 5 Nm. If the HVI power Conductor is installed in a structure, protection measures, e.g. fire barriers, must be taken. 6.5 Installation with regard to the wind zone / wind speed When installing / dimensioning air-termination systems, the wind load or wind power according to Eurocode must be observed. The relevant product is dimensioned for the maximum bending stress and the relevant tilting moment. The wind power is determined based on locational and environmental parameters such as the base wind speed, terrain category and height of the location and object. The combination of the different factors results in the gust wind speed which must be used as a basis for dimensioning and installing air-termination systems and installations. Consequently, the determination of the gust wind speed depends on the relevant object. More detailed information on this topic can be found in the relevant product catalogue. 30

31 Note: Wind load calculations based on Eurocode differ due to country-specific definitions. The values given were determined based on the national Annexes for Germany (see lightning protection/earthing catalogue as of ). Country-specific differences must be observed. Version I supporting tube with air-termination tip, Part No / , StSt, ø 10 mm, L = 1000 mm Version II supporting tube with air-termination rod, Part No / , StSt, ø 22/16/10 mm, L = 2500 mm α α 1000 mm 2500 mm α α GFK/NIRO supporting tube 2.5 m 2,5 m antenna 0.5 m 0,5 m antenna mast connection to the building s equipotential bonding system earth-termination system Figure 14 Wind speed Version I and II for installation on the supporting tube 31

32 7. Checklist for installing HVI Conductors If all questions in the below checklist are answered with "yes", it can be assumend that the HVI power Conductor is installed correctly. The checklist can be downloaded from the Download section of our homepage. Checklist for HVI Installation Address of the test object: Name: Contact partner: Street: Postcode, Place: Phone: Item Question 1 Is the whole system positioned in the protected area? 2 Has the separation distance been calculated? (down conductor to the earth termination system, isolated system with connection to existing external lightning protection system or lightning equipotential bonding on roof level) 3 Is the maximum equivalent separation distance specified by DEHN + SÖHNE for the application of the HVI Conductor kept? HVI light Conductor / DEHNcon H s 0.45 m in air s 0.9 m solid material HVI Conductor s 0.75 m in air s 1.5 m solid material HVI power Conductor s 0.9 m in air s 1.8 m solid material 4 Is the calculated separation distance kept in the range of the sealing end? 5 Is the supporting tube and, if required, the equipotential bonding element of the sealing end correct, i.e. only connected with the equipotential bonding / the lightning equipotential bonding of the system? 6 Is the minimum distance of 0.2 m kept between HVI Conductors routed in parallel and has the connection to opposite down conductors been considered? 7 Has the minimum bending radius been kept? HVI light Conductor (dark grey outer coating) 200 mm HVI Conductor (black outer coating) 200 mm HVI Conductor (grey outer coating) 230 mm HVI power Conductor (black outer coating) 270 mm 8 Is the equipotential bonding element of the sealing end in contact with the semiconductive layer (not grey coating)? 9 Has the supplementary information in DEHN installation instructions No. 1501/No.1892 been considered for installation of the HVI /HVI power Conductor in hazardous areas? 10 Did you exclusively use (tested) components of the manufacturer DEHN + SÖHNE? Rating YES NO Company Place Date Signature of tester DEHN Form No. 2848/E/0815 Figure 15 Check list 32

33 33

34 34

35 35

36 Surge Protection DEHN + SÖHNE Hans-Dehn-Str. 1 Tel Lightning Protection GmbH + Co.KG. Postfach 1640 Fax Safety Equipment Neumarkt sales@dehn.de DEHN protects. Germany

DEHN + SÖHNE. DEHNconductor System No Problems with Proximities

DEHN + SÖHNE. DEHNconductor System No Problems with Proximities DEHN + SÖHNE DEHNconductor System No Problems with Proximities DEHNconductor System - New Possibilities for controling Proximities. For preventing dangerous flashovers among parts of external lightning

More information

Reliable System Solutions for Isolated Air-Termination Systems.

Reliable System Solutions for Isolated Air-Termination Systems. Lightning Protection Surge Protection Safety Equipment DEHN + SÖHNE GmbH + Co.KG. Hans-Dehn-Str. 1 Postfach 1640 92306 Neumarkt Germany Reliable System Solutions for Isolated Air-Termination Systems. Tel.

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 62305-3 Edition 2.0 2010-12 colour inside Protection against lightning Part 3: Physical damage to structures and life hazard INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE

More information

DEHNconcept Planning of lightning protection systems. www.dehn-international.com

DEHNconcept Planning of lightning protection systems. www.dehn-international.com DEHNconcept Planning of lightning protection systems www.dehn-international.com A successful project starts with professional planning 2 fotolia.com Our engineering knowhow for your projects In addition

More information

Operating Instructions

Operating Instructions Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4

More information

Installation instruction CASAFLEX - Connecting piece DN 100

Installation instruction CASAFLEX - Connecting piece DN 100 1 CASAFLEX - 11 10 114,3 x 4,5 3 5 2 4 1 7 6 8 12 9 Do not begin work until you have read the installation instruction carefully. 1 internal backing sleeve 2 graphite packing 3 connecting piece 4 thrust

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

1 FOSC cover 1 piece Protecting fiber cable splices in whole 2 FOSC bottom 1 piece Fixing reinforced core, fiber cable

1 FOSC cover 1 piece Protecting fiber cable splices in whole 2 FOSC bottom 1 piece Fixing reinforced core, fiber cable TS-GPJ02VM 1. Scope of application This Installation Manual suits for the Fiber Optic Splice Closure (Hereafter abbreviated as FOSC), as the guidance of proper installation. The scope of application is:

More information

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE

More information

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001 > As wall, ceiling and pendant light fitting or side entry lamp > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp is opened

More information

ASSEMBLY INSTRUCTIONS Residential Roof solutions

ASSEMBLY INSTRUCTIONS Residential Roof solutions ASSEMBLY INSTRUCTIONS Residential Roof solutions CROSSRAIL System USA Table of contents TABLE OF CONTENTS THE COMPANY SAFETY REGULATIONS MATERIALS REQUIRED TOOLS REQUIRED ASSEMBLY TERMS AND CONDITIONS

More information

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions

More information

5800 Temperature Sensor Cable Assembly

5800 Temperature Sensor Cable Assembly 5800 Temperature Sensor Cable Assembly Removal and Replacement Instruction Sheet #60-4702-070 Revision D, January 14, 2013 Overview The 5800 has two refrigeration temperature sensors, one attached to the

More information

Guide rail bracket (for adjustable heads)

Guide rail bracket (for adjustable heads) (for adjustable heads) Part. 209 40 ø,5 ø10,5 2 2,5 115 15 42 5 11 37 72 4 70 Code 209 / 0754 MATERIALS: Bracket made out of reinforced polyamide black colour. FEATURES: To be used with heads Part.221,

More information

Terminal Boxes Series 8146

Terminal Boxes Series 8146 Series > Enclosures in shock-resistant glass fibre reinforced polyester resin > basic enclosure sizes various heights > Fitted according to the customer's requirements > For terminals up to max. 00 mm

More information

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-...

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-... Installation guide for the SafeLine type anchorage device Tested in compliance with EN 795: 1996 No.: SE-... Version: 09.10.2008 SE 67 Subject to technical alterations! Contents 1. General information

More information

Front axle components, overview

Front axle components, overview just a test. Front axle components, overview 40-1 General Information Load bearing components and parts of the suspension must not be welded or straightened. Vehicles without drive axle must not be moved,

More information

00MK-MA0190-EN00. Mounting System ASSEMBLY INSTRUCTIONS. Universal Light system with locking brackets, for sloped roof

00MK-MA0190-EN00. Mounting System ASSEMBLY INSTRUCTIONS. Universal Light system with locking brackets, for sloped roof 00MK-MA0190-EN00 Mounting System ASSEMBLY INSTRUCTIONS Universal Light system with locking brackets, for sloped roof Rev.02 November 2014 Table of contents General instructions 2 General safety instructions

More information

EH-20 20m antenna. By VE3RGW

EH-20 20m antenna. By VE3RGW EH-20 20m antenna By VE3RGW Equivalent circuit of EH-20 (prototype 2A) antenna system. Upper cylinder Lower cylinder Ground Counter pose Phasing coil Impedance transformer and tune circuit Tune coil Feed

More information

Installation Instructions 4508 4508S

Installation Instructions 4508 4508S SYMPHONY Spread Lavatory Faucet with Speed Connect Drain Congratulations on purchasing your American Standard faucet with Speed Connect drain, a feature found only on American Standard faucets. Speed Connect

More information

Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U 02. 01. Technical characteristics types D and E... 02.

Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U 02. 01. Technical characteristics types D and E... 02. Directory chapter 02 - () Types D, E, F, FM, 2F, F9, interface connectors I/U Page Technical characteristics types D and E.............................. 02.10 Type D connectors.................... 02.11

More information

RayClic Connection System Installation Instructions

RayClic Connection System Installation Instructions F M -W RayClic Connection System Installation Instructions RayClic WARNING: Shock Hazard 718K Pipe Heating Cable with HWAT, IceStop, also Listed De-icing and and XL-Trace heating Snow Melting Equipment

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

Consultants Handbook

Consultants Handbook Consultants Handbook CONSULTANTS HANDBOOK Welcome to our Wallis Designers Lightning Protection Handbook. This handbook offers a guide for any designers of the structural Lightning protection system to

More information

LK Wallbox UNI Push. Assembly. Only intended for LK PE-X Universal Pipe X.

LK Wallbox UNI Push. Assembly. Only intended for LK PE-X Universal Pipe X. LK Wallbox UNI Push Only intended for LK PE-X Universal Pipe X. LK Wallbox UNI Push 16 Single Article no. 188 06 38 LK Wallbox UNI Push 20 Single Article no. 188 06 39 LK Distance template LK Wallbox UNI

More information

RAUFOSS EXPLOSIVE COMPRESSION FITTINGS

RAUFOSS EXPLOSIVE COMPRESSION FITTINGS INSTRUCTION MANUAL FOR RAUFOSS EXPLOSIVE COMPRESSION FITTINGS Box 7 2831 Raufoss Norway Tlf.: +47 61 15 17 87 Fax: +47 61 15 25 56 25 January 2013, rev 2 Available on www.vpmetall.no Page 1 CONTENTS GENERAL

More information

Machine devices, jig devices

Machine devices, jig devices Machine devices, jig devices 853 K0697 Rolled thread studs DIN 6379 Material: Tempered steel. KIPP Rolled thread studs DIN 6379 Order No. D L B1 B2 Approx. weight g Surface finish: Thread rolled. Class

More information

Permanent Stainless Steel Anchorage Point for Concrete, Solid Masonry and Steel Constructions

Permanent Stainless Steel Anchorage Point for Concrete, Solid Masonry and Steel Constructions ABS-Lock X / X - SR Permanent Stainless Steel Anchorage Point for Concrete, Solid Masonry and Steel Constructions The ABS-Lock X system was developed to provide both a secure single anchorage point for

More information

Remote Head REMO ONE. Code 5750. Manual

Remote Head REMO ONE. Code 5750. Manual Remote Head REMO ONE Code 5750 Manual by sachtler. All rights reserved Version: 1.2/09/05 Issue date: September 2005 Order no.: srh20t010a We want you to receive Sachtler products that are always state

More information

DIAMOND Retractable Rodding Robot Model SPRAYROD-R

DIAMOND Retractable Rodding Robot Model SPRAYROD-R 2004-12-21 2 1 (23) DIAMOND Retractable Rodding Robot Model SPRAYROD-R 2004-12-21 2 2 (23) Table of contents 1 TECHNICAL DESCRIPTION...4 1.1 MAIN DETAILS...5 1.2 COMPONENTS DESCRIPTION...5 1.2.1 Pneumatic

More information

39HQ Airovision Air Handling Units

39HQ Airovision Air Handling Units 39HQ Airovision Air Handling Units Mounting instructions CONTENTS 1 - TRANSPORT AND LIFTING INSTRUCTIONS... 3 1.1 - General... 3 1.2 - Transport and storage... 3 1.3 - Roof edge protection during transport

More information

RayClic Connection System Installation Instructions

RayClic Connection System Installation Instructions RayClic Connection System Installation Instructions Description RayClic-S Splice Kit RayClic-T Tee and End Seal Kit RayClic-X Cross and End Seal Kit These kits are for use with Raychem IceStop, XL-Trace

More information

Ecoflex Wall Penetration Systems: An efficient, sustainable solution for penetrating concrete or block walls

Ecoflex Wall Penetration Systems: An efficient, sustainable solution for penetrating concrete or block walls Pre- insulated pipe systems ecoflex Wall Penetration installation guide Ecoflex Wall Penetration Systems: An efficient, sustainable solution for penetrating concrete or block walls Pre-insulated Pipe Systems

More information

Elektromotoren und Gerätebau Barleben GmbH

Elektromotoren und Gerätebau Barleben GmbH Elektromotoren und Gerätebau Barleben GmbH OPERATING INSTRUCTIONS Transformer Protection Relay NM Series (Buchholz principle) Elektromotoren und Gerätebau Barleben GmbH Table of contents Page 1. Safety

More information

Assembly Instruction CAI- Connector with universal Endbell

Assembly Instruction CAI- Connector with universal Endbell CANNON STANDARD Seite 1 von 17 CAI- Connector with universal Endbell Shell size 10 to 36 with APK contact / Trident T2P - contact Illustration and assembly exemplary of CAI Layout 20-0306 with APK / Trident

More information

Depending on which elastic support you have you can secure the V2 power unit to the following seat bracket tubes: EXTERNAL DIAMETER 27.

Depending on which elastic support you have you can secure the V2 power unit to the following seat bracket tubes: EXTERNAL DIAMETER 27. ASSEMBLY 1 - EPS V2 POWER UNIT (SOLUTION 5) 1.1 - POSITIONING INSIDE THE SEAT TUBE WITH ELASTIC SUPPORT IN THE SEAT BRACKET TUBE Depending on which elastic support you have you can secure the V2 power

More information

BILLET HEADLAMP WITH SHORT/TALL MOUNTS

BILLET HEADLAMP WITH SHORT/TALL MOUNTS -J099 REV. 00-0- BILLET HEADLAMP WITH SHORT/TALL MOUNTS GENERAL Kit Number 9-0, 9-0 Models Kit 9-0 is a -/ inch headlamp and kit 9-0 is a -/ inch headlamp. Both kits will fit the models listed in Table.

More information

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases

More information

Speed-Mat Rectangle Cutter

Speed-Mat Rectangle Cutter Speed-Mat Rectangle Cutter 1 Honeycomb baseboard. 2 Left hold down. 14 3 Bottom hold down. 4 4 Left / right rule. 8 5 8 5 Left / right rule pointer. 1 6 Top / bottom rule. 7 Top / bottom rule pointer.

More information

Series 30000 Hose Reels

Series 30000 Hose Reels Operating Instructions and Parts List for Series 30000 Hose Reels - MANUAL DRIVEN - - POWER DRIVEN - SAFETY PRECAUTIONS Personal injury and/or equipment damage may result if proper safety precautions are

More information

EMC Engineering Guidelines For Automation Systems PS 4 PS 416 04/97 AWB 27-1287-GB

EMC Engineering Guidelines For Automation Systems PS 4 PS 416 04/97 AWB 27-1287-GB EMC Engineering Guidelines For Automation Systems PS 4 PS 416 1st edition 04/97 Moeller GmbH, Bonn Author: Werner Albrecht Editors: Klaus Krüger, Thomas Kracht Translator: Chris Baker, Terence Osborn Contents

More information

INSTALLATION INSTRUCTIONS: Viewline 52 mm

INSTALLATION INSTRUCTIONS: Viewline 52 mm -5 Safety information The product was developed, manufactured and inspected according to the basic safety requirements of EC Guidelines and state-of-the-art technology. The instrument is designed for use

More information

C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S

C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S January 2009 Issue 6 Valu Guide Brackets The Ultimate in Adjustability and Cost Savings Valu Guide brackets are part of a family

More information

Pipe Clamps and Accessories

Pipe Clamps and Accessories Products 4.0 Products 4.1 Connection options to pipe clamps with Triple-Thread Connector NT 3G (M16, M10, M8) 4.2 Connection options to pipe clamps with Triple-Thread Connector NT 3G (3/8", M12, M10) 4.3

More information

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered Electrical Temperature Measurement DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered WIKA Data Sheet TE 60.75 Applications Machinery, plant and tank construction

More information

Navico-Northstar 2kW JRC Radar Package, Scanner Cable Removal and Replacement

Navico-Northstar 2kW JRC Radar Package, Scanner Cable Removal and Replacement Navico-Northstar 2kW JRC Radar Package, Scanner Cable Removal and Replacement This work instruction describes the methods and means for which to remove and reinstall optional scanner cable configurations

More information

Original Assembly Guide

Original Assembly Guide TCT Multipurpose Single Bevel Sliding Compound Mitre Saw Original Assembly Guide Read instructions before assembling this tool. Table of Contents GB Assembly Guide Read instructions before assembling this

More information

Linear Luminaire with LED Series EXLUX 6402/2

Linear Luminaire with LED Series EXLUX 6402/2 > Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the

More information

Drive shaft, servicing

Drive shaft, servicing Volkswagen Passat B6 - Drive shaft, servicing Стр. 1 из 41 40-7 Drive shaft, servicing Drive shafts, overview I - Assembly overview: Drive axle with CV joint VL100 40-7, Drive axle with CV joint VL100,

More information

Volkswagen Jetta, Golf, GTI 1999, 2000 Brake System 47 Brakes - Hydraulic Components (Page GR-47)

Volkswagen Jetta, Golf, GTI 1999, 2000 Brake System 47 Brakes - Hydraulic Components (Page GR-47) 47 Brakes - Hydraulic Components (Page GR-47) FS III front brake calipers, servicing Front brake caliper piston, removing and installing FN 3 front brake calipers, servicing Front caliper piston, removing

More information

CAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED.

CAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED. CAST IRON THE BASICS 1. DO NOT LIFT ON YOUR OWN. 2. ONLY LIFT THE RADIATOR VERTICALLY. 3. DO NOT LIFT MORE THAN 8/10 SECTIONS AT ANY ONE TIME. 4. POSITION THE RADIATOR BEFORE FINAL ASSEMBLY. 5. THIS PRODUCT

More information

White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection

White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection White paper SACE Tmax XT Circuit-Breaker Terminals and Connection Circuit-Breaker Terminals and Connections Index Introduction... 2 1. Components used for wiring... 3 1.1. Electrical...3 1.2. Flexibility

More information

INFRARED QUARTZ WALL HEATER

INFRARED QUARTZ WALL HEATER INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this

More information

IMPORTANT DOCUMENTATION DO NOT DISCARD!

IMPORTANT DOCUMENTATION DO NOT DISCARD! PART NO.: 6441-263C SERIES GRT 3 JAW PARALLEL GRIPPERS INFORMATION SHEET IMPORTANT DOCUMENTATION DO NOT DISCARD! Use this information sheet to assist with gripper installation and setup. File with maintenance

More information

Phoenix Solar AG. Phoenix TectoSun 3 Installation instructions

Phoenix Solar AG. Phoenix TectoSun 3 Installation instructions AG Phoenix TectoSun 3 Installation instructions 2 THE TECTOSUN 3 MOUNTING SYSTEM FROM PHOENIX SOLAR THE ADVANTAGES AT A GLANCE Tested by TÜV, RAL seal of uality for all components Quick and easy installation

More information

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132

More information

KIRÁLY TRADING KFT H-1151 Budapest Mogyoród útja 12-14 tel: 061307-3801 Email_pzoli@kiralytrading.hu. Clamps Clamping devices

KIRÁLY TRADING KFT H-1151 Budapest Mogyoród útja 12-14 tel: 061307-3801 Email_pzoli@kiralytrading.hu. Clamps Clamping devices 04000 Clamps Clamping devices 23000 22000 21000 20000 09000 08000 07000 06000 05000 04000 03000 02000 01000 297 04010 Adjustable straps Tempered steel 1.1191 Black oxide finish nlm 04010-101 Suitable thrust

More information

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks Securitron Magnalock Corp. www.securitron.com ASSA ABLOY, the global leader Tel 800.624.5625 techsupport@securitron.com in door opening solutions INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Front brakes (FN- 3), servicing

Front brakes (FN- 3), servicing j a t Front brakes (FN- 3), servicing 46-1 Front brakes, servicing Note: Install complete repair kit. After replacing brake pads and before moving vehicle, depress brake pedal several times firmly to properly

More information

Mounting Instructions. Torque Transducer. A0329 3.2 en

Mounting Instructions. Torque Transducer. A0329 3.2 en Mounting Instructions Torque Transducer T5 T5 Contents 3 Page Safety instructions.............................................. 4 1 Measuring characteristics..................................... 7 2 Mounting.....................................................

More information

DYNA RIDER FOOTBOARD KIT

DYNA RIDER FOOTBOARD KIT -J0 REV. 0-0-0 DYNA RIDER FOOTBOARD KIT GENERAL Kit Number 000 Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com (English

More information

Guidelines for Earthquake Bracing of Residential Water Heaters

Guidelines for Earthquake Bracing of Residential Water Heaters Guidelines for Earthquake Bracing of Residential Water Heaters Department of General Services Division of the State Architect 1102 Q Street, Suite 5100 Sacramento, CA 95814 Phone: (916) 324-7099 Fax: (916)

More information

Volkswagen Jetta, Golf, GTI 1999, 2000 Brake System 46 Brakes - Mechanical Components (Page GR-46)

Volkswagen Jetta, Golf, GTI 1999, 2000 Brake System 46 Brakes - Mechanical Components (Page GR-46) 46 Brakes - Mechanical Components (Page GR-46) Front brakes Brake pads, removing and installing Brake pads, removing and installing FN 3 brake caliper, servicing FS III brake caliper, servicing Rear wheel

More information

SIGRAFLEX EMAIL. Properties. Applications

SIGRAFLEX EMAIL. Properties. Applications Multilayer sealing sheet, adhesive-free made from flexible graphite foil reinforced with stainless steel foils especially for use in PTFE envelope gaskets SIGRAFLEX EMAIL has been developed specially for

More information

building applications copper - redefined

building applications copper - redefined building applications copper - redefined copper - redefined The task The development of an innovative tube for the future: economical, environmentally friendly, ecological, completely safe and easy to

More information

S OUNTING INSTRUCTION M M o u n t i n g k i t 2 &

S OUNTING INSTRUCTION M M o u n t i n g k i t 2 & M O U N T I N G I N S T R U C T I O N S instructions This document is protected by copyright. The SICK AG company retains this right. Reproducing this document in whole or part is only permissible within

More information

Linkeo 19" freestanding cabinets

Linkeo 19 freestanding cabinets 87045 LIMOGES Cedex France Telephone: (+33) 05 55 06 87 87 - Fax: (+33) 05 55 06 88 88 Linkeo 19" freestanding cabinets Page 1. General characteristics....1 2. Range....2 3. Technical characteristics...3

More information

6720616592.00-1.SD. Flat roof. Rack Mounting. Installation instructions 6 720 647 036 (2010/11) AU

6720616592.00-1.SD. Flat roof. Rack Mounting. Installation instructions 6 720 647 036 (2010/11) AU 6720616592.00-1.SD Flat roof Rack Mounting AU Installation instructions 2 Contents AU Contents 1 Key to symbols and safety instructions....... 3 1.1 Explanation of symbols................ 3 1.2 Safety

More information

B 246 Assembly instructions

B 246 Assembly instructions B 246 Assembly instructions VOSS quick connect system 246 for diesel fuel systems in automotive engineering These assembly instructions are intended for qualified fitters of fuel systems in automotive

More information

Precision Miniature Load Cell. Models 8431, 8432 with Overload Protection

Precision Miniature Load Cell. Models 8431, 8432 with Overload Protection w Technical Product Information Precision Miniature Load Cell with Overload Protection 1. Introduction The load cells in the model 8431 and 8432 series are primarily designed for the measurement of force

More information

Series 8146/5-V37 and Series 8150/5-V37

Series 8146/5-V37 and Series 8150/5-V37 www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection

More information

Puddle Flange. FRANK Puddle Flange

Puddle Flange. FRANK Puddle Flange Puddle Flange FRANK Puddle Flange The problem Problems keep on occurring when connecting pipes during construction work. Pipes laid in the ground must be introduced into concrete walls or shafts. In many

More information

RELAZZO DECKING THE TERRACE. INSTALLATION GUIDE. Construction Automotive Industry. REHAU R20680 EN 05.2015 www.rehau.com/relazzo

RELAZZO DECKING THE TERRACE. INSTALLATION GUIDE. Construction Automotive Industry. REHAU R20680 EN 05.2015 www.rehau.com/relazzo Construction Automotive Industry RELAZZO DECKING THE TERRACE. INSTALLATION GUIDE REHAU R20680 EN 05.2015 www.rehau.com/relazzo Scan the QR code and learn more: RELAZZO DECKING THE TERRACE. Installation

More information

Installation Instructions Hustler 6-BTV Trap Vertical

Installation Instructions Hustler 6-BTV Trap Vertical Installation Instructions Hustler 6-BTV Trap Vertical ASSEMBLY 1. Check the package contents against the parts list on page 2. 2. WARNING. Installation of this product near power lines is dangerous. For

More information

Weatherproof Tournament Table Tennis Table

Weatherproof Tournament Table Tennis Table Weatherproof Tournament Table Tennis Table Owner s Manual Model Number 7035-590 Absolutely Weatherproof Printed on 100% recycled paper.! Made in Germany Thank you for purchasing our high quality KETTLER

More information

EZ-Steer Assisted Steering System

EZ-Steer Assisted Steering System EZ-Steer Assisted Steering System Installation Instructions Platform Kit P/N 53059-54 Case IH CVX 1135 CVX 1145 CVX 1155 CVX 1170 CVX 1190 CVX 1195 CVX 135 CVX 145 CVX 155 CVX 175 CVX 195 New Holland TVT

More information

Catalog May 2015. Cable Accessories < 1 kv

Catalog May 2015. Cable Accessories < 1 kv Catalog May 2015 Cable Accessories < 1 kv Table of content Cable Accessories 1 Cable Accessories 1 kv Product range 2 Universal cleats 3 List of content 4 Notes 5 We reserve the right to make technical

More information

Enphase Engage Cable and Accessories

Enphase Engage Cable and Accessories INSTALLATION MANUAL Enphase Engage Cable and Accessories 141-00016, Rev 03 Corporate Headquarters Contact Information Enphase Energy Inc. 1420 N. McDowell Blvd. Petaluma, CA 94954 USA Phone: +1 707-763-4784

More information

Volkswagen B3 Passat Manual Transmission 02A 34 Manual Transmission - Controls, Assembly (Page GR-34) 02A 5-speed. Gearshift cable/lever installing

Volkswagen B3 Passat Manual Transmission 02A 34 Manual Transmission - Controls, Assembly (Page GR-34) 02A 5-speed. Gearshift cable/lever installing 34 Manual Transmission - Controls, Assembly (Page GR-34) 02A 5-speed Gearshift cable/lever installing Gearshift housing repairing Gearshift lever repairing lever/relay lever, installing Gearshift mechanism

More information

Installation information. METTLER TOLEDO MultiRange Floor scales / Pit scales

Installation information. METTLER TOLEDO MultiRange Floor scales / Pit scales Installation information METTLER TOLEDO MultiRange Floor scales / Pit scales KC300/KCS300 KC600/KCS600 KD600/KD1500 KE1500/KE3000 KES1500/KES3000 KG3000/KG6000 KN1500 Floor scales / Pit scales Contents

More information

Feed-through terminal block - SSK 110 KER-EX - 0502058

Feed-through terminal block - SSK 110 KER-EX - 0502058 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid

More information

Installation Instructions 6028.801

Installation Instructions 6028.801 DAZZLE Installation Instructions 08.80 Spread Lavatory Faucet with Speed Connect Drain* Congratulations on purchasing your American Standard faucet with Speed Connect drain, a feature found only on American

More information

Weatherproofing Kit for Connectors and Antennas

Weatherproofing Kit for Connectors and Antennas Weatherproofing Kit for Connectors and Antennas Butyl rubber tape The kit can be used for one or more connections depending on the configuration and cable type as follows: / (9-mm) plastic tape (-mm) plastic

More information

AMPSEAL* Automotive Plug Connector and Header Assembly

AMPSEAL* Automotive Plug Connector and Header Assembly AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2

More information

Saferand easierinstallation

Saferand easierinstallation EN 85-07 Saferand easierinstallation IföSigninstallationsystem andifösignbuilt-incistern www.ifosanitar.com/sign Aneffectivesolution withmanyadvantages. Ifö Sign installation system makes life a little

More information

Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors

Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors Installation Manual Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors SW602206 Rev B Table of Contents Chapter 1: Safety Warning... 3 Chapter 2: Kit Contents... 4 Included in Kit...

More information

Inductive sensor NI10-M18-Y1X-H1141

Inductive sensor NI10-M18-Y1X-H1141 ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Threaded barrel, M18 x 1 Chrome-plated brass DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6 (NA- MUR) M12

More information

HDA -----------------------------------------------------------

HDA ----------------------------------------------------------- ----------------------------------------------------------- Lightstrips ---------------------------------------------------------------------- Ceiling system for heating and cooling LIGHTSTRIPS LIGHTSTRIPS

More information

INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS

INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS FOR YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS GENERAL DESCRIPTION:

More information

Elektromotoren und Gerätebau Barleben GmbH

Elektromotoren und Gerätebau Barleben GmbH Elektromotoren und Gerätebau Barleben GmbH OPERATING INSTRUCTIONS Transformer Protection Relay (Buchholz principle) Elektromotoren und Gerätebau Barleben GmbH Table of contents Page 1 Safety instructions

More information

CAM-03, Camshaft Assembly Oil Seal Replacement

CAM-03, Camshaft Assembly Oil Seal Replacement CAM-03, Camshaft Assembly Oil Seal Replacement Tools Jack stands Floor Jack Metric Socket set Metric Wrench set Porsche Timing Belt Tension tool (P9201) Flywheel Lock (P9206) Balance Shaft Pin Spanner

More information

HT-0095 Mini PV Receptacles 22-32 AWG Crimping Hand Tool. Tool P/N HT-0095

HT-0095 Mini PV Receptacles 22-32 AWG Crimping Hand Tool. Tool P/N HT-0095 HT-0095 Mini PV Receptacles 22-32 AWG Crimping Hand Tool Tool P/N HT-0095 FCI MANUAL P/N 415988-001 Issued: Date (03/12/99) Page 1 of 18 HT-0095 Issued: Date (03/12/99) Page 2 of 18 Introduction Table

More information

Powermate Range Pitch 7.62

Powermate Range Pitch 7.62 owermate Range itch 7.62 in headers Socket connectors CB connection Solder connection SV 7.62/90 500 V / 43 A SV 7.62/180 500 V / 41 A.2.4 Cable connection Clamping yoke connection Tension clamp connection

More information

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions Printing 3 March 2008 CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions This instruction is intended for CP2 cable pedestal installations and replacements. The following tools will be

More information

CUSTOM AUXILIARY FORWARD LIGHTING KIT

CUSTOM AUXILIARY FORWARD LIGHTING KIT -J0 REV. 0--0 CUSTOM AUXILIARY FORWARD LIGHTING KIT GENERAL Kit Number -0, 0000 Models This Custom Auxiliary Lighting Kit adds lamps and turn signals to 00 and later FLHX model motorcycles. Additional

More information

Threaded Resistance Thermometers Model TR10-D, Miniature Design

Threaded Resistance Thermometers Model TR10-D, Miniature Design Electrical Temperature Measurement Threaded Resistance Thermometers Model TR10-D, Miniature Design WIKA Data Sheet TE 60.04 Applications Machine building, plant and tank construction Power transmission

More information

Achat 115MA full-range speaker. user manual

Achat 115MA full-range speaker. user manual Achat 115MA full-range speaker user manual Musikhaus Thomann Thomann GmbH Hans-Thomann-Straße 1 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: info@thomann.de Internet: www.thomann.de

More information

14 PHOENIX CONTACT Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108. info@powermation.com - 800-843-9859 - www.powermation.

14 PHOENIX CONTACT Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108. info@powermation.com - 800-843-9859 - www.powermation. 14 PHOENIX CONTACT PLUSCON circular is a circular connector for use in industrial automation. The range of design sizes available is varied, starting with the design sizes M5 to M8 and M1, for sensor/actuator

More information

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17)

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17) 17 Engine-Lubrication system (Page GR-17) Lubrication system components, removing and installing Oil pan, removing and installing Oil pressure and oil pressure switch, checking Dynamic oil pressure warning

More information