Power factor correction and harmonic filtering. Catalogue. Propivar capacitors and MV banks

Size: px
Start display at page:

Download "Power factor correction and harmonic filtering. Catalogue. Propivar capacitors and MV banks"

Transcription

1 and harmonic filtering Catalogue 2007 Propivar capacitors and MV banks

2 Contents Overview 2 MV capacitor bank selection guide 2 Propivar capacitors 4 Insulation level 7.2 kv (20/60)50/60 Hz 6 Insulation level 12 kv (28/75)50/60 Hz 8 Insulation level 17.5 kv (38/95)50/60 Hz 9 Insulation level 24 kv (50/125)50/60 Hz 10 Insulation level 36 kv (70/170)50/60 Hz 11 MV capacitor banks 12 Fixed compensation 12 CP214 fixed capacitor bank 13 Insulation level 7.2 kv (20/60) - 50/60 Hz 13 Standard type (slightly polluted network) 13 Insulation level 12 kv (28/75) - 50/60 Hz 14 Standard type (slightly polluted network) 14 CP214 SAH fixed capacitor bank 15 Insulation level 7.2 kv (20/60) - 50/60 Hz 15 SAH type (highly polluted network) 15 Insulation level 12 kv (28/75) - 50/60 Hz 16 SAH type (highly polluted network) 16 CP227 fixed capacitor bank 17 Insulation level 7.2 kv (20/60) - 50/60 Hz 17 Standard type (slightly polluted network) 17 Insulation level 12 kv (28/75) - 50/60 Hz 18 Standard type (slightly polluted network) 18 Insulation level 17.5 kv (38/95) - 50/60 Hz 19 Standard type (slightly polluted network) 19 Insulation level 24 kv (50/125) - 50/60 Hz 20 Standard type (slightly polluted network) 20 Insulation level 36 kv (70/170) - 50/60 Hz 21 Standard type (slightly polluted network) 21 MV capacitor banks 22 Automatic compensation 22 CP253 automatic capacitor bank 23 Insulation level 7.2 kv (20/60) - 50/60 Hz 23 Standard type (slightly polluted network) 23 Insulation level 12 kv (28/75) - 50/60 Hz 25 Standard type (slightly polluted network) 25 CP253SAH automatic capacitor bank 26 Insulation level 7.2 kv (20/60) - 50/60 Hz 26 SAH type (highly polluted network) 26 Insulation level 12 kv (28/75) - 50/60 Hz 28 SAH type (highly polluted network) 28 CP254 automatic capacitor bank 29 Insulation level 17.5 kv (38/95) - 50/60 Hz 29 Standard type (slightly polluted network) 29 Insulation level 24 kv (50/125) - 50/60 Hz 30 Standard type (slightly polluted network) 30 Insulation level 36 kv (70/170) - 50/60 Hz 31 Standard type (slightly polluted network) 31

3 Overview 0 MV capacitor bank selection guide Step 1: basic data collection How to choose the right power factor correction capacitor bank? The recommended method consists of five successive steps Network characteristics: b voltage U (V) b network frequency f (50 or 60 Hz). Characteristics of the installation: b insulation voltage U insulation b rated power of the transformer Sn (kva) b transformer short circuit voltage Usc (%) b existing capacitor bank (Qc (kvar), type of capacitor bank, ). Operating conditions: b energy bills b measurements of power: P (kw) cos phi. Step 2: calculation of the reactive power Qc (kvar) DB The reactive power is determined either: b from the electricity bills, depending on the method of recording the consumption of kvar applied by the energy supplier b from the electrical data of the installation. The aim is: b not to pay for the consumption of reactive energy and to ensure optimum use of the transformers, cables and control and protection switchgear b to satisfy the standards currently in force: compliance with a minimum cos phi, energy quality standards. Step 3: choice of type of capacitor bank according to the harmonics The presence of non-linear loads (variable speed drives, UPS, etc.) creates harmonic currents and voltages. The compensation equipment is chosen according to the value of these harmonics. b either the installation has no harmonics and there is no risk of resonance b either the installation has harmonics and/or there is a risk of resonance b in the absence of information about the installation and as a precautionary measure V Select a capacitor bank for a slightly polluted network (see selection table in step 5) V Select a capacitor bank for a highly polluted network (see selection table in step 5) V Select a capacitor bank for a highly polluted network (see selection table in step 5) Harmonic filtering To improve the quality of electrical power, Merlin Gerin provides a range of compensation and filtering solutions. The HV or MV filters that absorb the harmonic currents in the electrical installation consist mainly of capacitors associated with filtering reactors. They are used to: b bring the percentage of distortion back to the acceptable values recommended by the energy distributors b and also compensate for the reactive power. Schneider Electric can undertake compensation and filtering analyses.

4 Overview 0 MV capacitor bank selection guide (cont.) Step 4: choice of type of compensation Global compensation The type of compensation should be chosen by taking into account the calculated reactive power Qc (kvar) and the apparent power Sn (MVA) of the upstream transformer. Qc/Sn < 15% the reactive power of the capacitor banks is constant and they are started up or shut down when a predetermined kvar value is reached. It is an on/off type of operation. V Fixed compensation Qc/Sn > 15% the customer specifies automatic startup or shutdown for the capacitor bank (controlled by Varlogic varmetric relay). The reactive power of the capacitor banks is split into steps with the possibility of starting or stopping more or fewer steps. The reactive power corresponds to the change in load requirements V Automatic compensation Motor compensation b if there is no risk of self-excitation V The capacitor bank will be connected in parallel with the motor b if there is a risk of self-excitation. V But it is only possible to connect to the motor terminals, the capacitor bank will be connected to the busbar independently of the motor. Step 5: selection table The recommended choice is based on the network insulation voltage, network harmonic pollution level and on the type of compensation. b if the power of the capacitor bank to be installed is less than 600 kvar b if the power of the capacitor bank to be installed u 600 kvar. V A low voltage solution is recommended V See the following table. Insulation level 7.2 kv 12 kv 17.5 kv 24 kv 36 kv Slightly polluted network Fixed CP214 CP214 CP227 CP227 CP227 CP227 CP227 Auto CP253 CP253 CP254 CP254 CP254 Highly polluted network Fixed CP214 SAH CP214 SAH Auto CP253 SAH CP253 SAH CP227 SAH and CP254 SAH as a specific order.

5 Propivar capacitors E The Propivar capacitors are used to compensate reactive power on medium and high voltage networks. Single-phase Propivar capacitor. Presentation A Propivar medium voltage capacitor is a steel case or tank provided with resin insulators. The tank comprises an assembly of capacitor elements having a maximum permissible rated voltage of 2250 V. When connected in series-parallel groups, they provide high power units for elevated system voltages. There are two types of capacitors: b with internal fuses (single-phase capacitor) b without internal fuses (three-phase or single-phase capacitor). Each capacitor is normally provided with discharge resistors to bring the residual voltage down to 75 V 10 minutes after the capacitor has been switched off. If requested, the capacitors can be supplied without discharge resistors. Construction The Propivar capacitors are composed of elements which include: b aluminium foil electrodes b a dielectric liquid with no PCB or chlorine and a polypropylene film. Compliance with standards The Propivar capacitor complies with standard NF C and with the following standards: b IEC 60871, 1 and 2 b BS 1650 b VDE 0560 b C22-2 N 190-M1985 b NEMA CP1. Capacitors with internal fuses comply with the following standards: NF C , IEC Protection by internal fuse Propivar capacitors can be supplied with internal protection: each element or unit capacitor is equipped with a fuse. In the event of a breakdown of an element, the element is disconnected and isolated. Breakdown of a unit capacity may occur: b when capacitor voltage is close to its maximum amplitude. In this case, it is the power stored in the capacitances of the parallel elements which guarantees a current sufficient to rupture the internal fuse (fig. 1) b when capacitor voltage is close to zero. This current ensures breaking of the internal fuse (fig. 2). Advantages of this protection type: b instantaneous disconnection of the short-circuiting element b lifetime of the capacitor b reduction in material costs and maintenance b continuity of service is ensured b possiblity of programming site maintenance. E14445B E14445A Propivar capacitor with internal fuses, composed of 4 groups connected in series, each group comprising 12 elements connected in parallel. Fig. 1 Fig. 2 Main characteristics The exceptional life of Propivar capacitors is due to their temperature withstand, small temperature rise, chemical stability and overvoltage and overcurrent withstand. Temperature withstand These capacitors can be put into service at low temperatures without any special precautions being taken. At higher ambient temperatures, the temperature rise is very low, so they can be operated without any risk of modifying the insulation characteristics of the dielectric. Chemical stability Transient overvoltages in circuits and partial discharge levels in tanks cause accelerated ageing of capacitors. The exceptional life of Propivar capacitors is closely connected with the intrinsic properties of the dielectric liquid: b very high chemical stability b high absorption capacity for gases generated during partial discharges b very high dielectric strength. Overvoltage and overcurrent withstand The capacitors can accept: b an overvoltage of 1.10 Un for 12 hours a day b a power frequency overvoltage of 1.15 Un for 30 minutes a day b a permanent overcurrent of 1.3 In. The withstand of capacitors is verified by: v cycles at an overvoltage level of 2.25 Un (cycle duration 1 s) v ageing tests at 1.4 Un. 4

6 Propivar capacitors0 Insulating voltage of the Propivar capacitors in accordance with IEC and 2 standard in the majority of european and several other countries: Highest voltage for equipment Um kv Insulation level Rms kv, 50 Hz-1 mn Basic impulse level (BIL) kv, 1.2/50 µs In accordance with NEMA CP1 standard based on current practice in some countries of North America and others: Highest voltage for equipment Um kv Insulation level Rms kv, 50 Hz-1 mn Basic impulse level (BIL) kv, 1.2/50 µs Environmental protection / biodegradability Propivar capacitor contains a dielectric liquid with no PCB or chlorine. Other characteristics Service frequency 50 Hz - (available in 60 Hz, please consult us) Temperature range -25 to +45 C Average loss factor at 20 C after stabilisation Maximum rated single phase capacitors reactive power (1) 600 kvar three phase capacitors 450 kvar 0.16 W/kvar with internal fuses 0.12 W/kvar without internal fuses Capacitance value tolerance -5, +15 % Capacitance variation DC/C / C Connection to resin insulators for cables with a section y 50 mm 2 Tank welded steel Thickness 1.5 mm Colour Grey RAL 7038 Anticorrosion treatment Fixing system 2 perforated brackets for M10 screw (1) Other reactive powers, on request. 5

7 Propivar capacitors Insulation level 7.2 kv (20/60) 50/60 Hz Three phase capacitors DB Network voltage (V) Capacitor voltage (V) (H x L x D / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 300 x 347 x 190 / 135 / R 300 x 347 x 190 / 135 / R 400 x 347 x 190 / 135 / R 500 x 347 x 190 / 135 / R 500 x 347 x 190 / 135 / R 600 x 347 x 190 / 135 / R 700 x 347 x 190 / 135 / R D Three phase capacitors Three-phase Propivar capacitor. Network voltage (V) Capacitor voltage (V) (H x L x D / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 300 x 347 x 190 / 135 / R 300 x 347 x 190 / 135 / R 400 x 347 x 190 / 135 / R 500 x 347 x 190 / 135 / R 810 x 347 x 165 / 135 / R 700 x 347 x 190 / 135 / R 700 x 347 x 190 / 135 / R 810 x 347 x 190 / 135 / R 810 x 347 x 190 / 135 / R Options Set of 3 clamps for delta connexion Set of 3 clamps for star connexion R R

8 Propivar capacitors Insulation level 7.2 kv (20/60) 50/60 Hz Single phase capacitors with internal fuses DB Network voltage (V) Capacitor voltage (V) (H x L x D / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 400 x 347 x 165 / 233 / R 400 x 347 x 190 / 233 / R 500 x 347 x 190 / 233 / R 500 x 347 x 190 / 233 / R 600 x 347 x 190 / 233 / R 700 x 347 x 190 / 233 / R D Single-phase Propivar capacitor. Single phase capacitors without internal fuses Network voltage (V) Capacitor voltage (V) (H x L x D / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 300 x 347 x 190 / 233 / R 300 x 347 x 190 / 233 / R 400 x 347 x 190 / 233 / R 400 x 347 x 190 / 233 / R 500 x 347 x 190 / 233 / R 600 x 347 x 190 / 233 / R Options Set of 2 clamps for delta connexion Set of 2 clamps for star connexion R R 7

9 Propivar capacitors Insulation level 12 kv (28/75) 50/60 Hz Three phase capacitors DB Network voltage (V) Capacitor voltage (V) (H x L x D / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 300 x 347 x 190 / 233 / R 400 x 347 x 190 / 233 / R 500 x 347 x 190 / 233 / R 600 x 347 x 190 / 233 / R 600 x 347 x 190 / 233 / R 700 x 347 x 190 / 233 / R 810 x 347 x 190 / 233 / R D Three-phase Propivar capacitor. Options Set of 3 clamps for delta connexion Set of 3 clamps for star connexion R R Single phase capacitors with internal fuses DB Network voltage (V) Capacitor voltage (V) (H x L x P / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 400 x 347 x 165 / 233 / R 500 x 347 x 180 / 233 / R 600 x 347 x 180 / 233 / R 700 x 347 x 190 / 233 / R 810 x 347 x 190 / 233 / R 1000 x 347 x 190 / 233 / R D Single-phase Propivar capacitor. Single phase capacitors without internal fuses Network voltage (V) Capacitor voltage (V) (H x L x P / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 300 x 347 x 190 / 233 / R 300 x 347 x 190 / 233 / R 400 x 347 x 190 / 233 / R 500 x 347 x 190 / 233 / R 600 x 347 x 190 / 233 / R 700 x 347 x 190 / 233 / R 900 x 347 x 190 / 233 / R Options Set of 2 clamps for delta connexion Set of 2 clamps for star connexion R R

10 Propivar capacitors Insulation level 17.5 kv (38/95) 50/60 Hz Single phase capacitors with internal fuses DB Network voltage (V) Capacitor voltage (V) (H x L x D / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 400 x 347 x 165 / 282 / R 500 x 347 x 190 / 282 / R 600 x 347 x 190 / 282 / R 700 x 347 x 190 / 282 / R 900 x 347 x 190 / 282 / R 1000 x 347 x 190 / 282 / R D Single-phase Propivar capacitor. Single phase capacitors without internal fuses Network voltage (V) Capacitor voltage (V) (H x L x D / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 300 x 347 x 190 / 282 / R 300 x 347 x 190 / 282 / R 400 x 347 x 190 / 282 / R 400 x 347 x 190 / 282 / R 500 x 347 x 190 / 282 / R 600 x 347 x 190 / 282 / R 810 x 347 x 190 / 282 / R 900 x 347 x 190 / 282 / R Options Set of 2 clamps for delta connexion Set of 2 clamps for star connexion R R

11 Propivar capacitors Insulation level 24 kv (50/125) 50/60 Hz Single phase capacitors with internal fuses DB Network voltage (V) Capacitor voltage (V) (H x L x D / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 810 x 347 x 165 / 282 / R 810 x 347 x 165 / 282 / R 810 x 347 x 190 / 282 / R 1000 x 347 x 190 / 282 / R D Single-phase Propivar capacitor. Single phase capacitors without internal fuses Network voltage (V) Capacitor voltage (V) (H x L x D / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 300 x 347 x 190 / 282 / R 400 x 347 x 190 / 282 / R 400 x 347 x 190 / 282 / R 500 x 347 x 190 / 282 / R 600 x 347 x 190 / 282 / R 700 x 347 x 190 / 282 / R 900 x 347 x 190 / 282 / R Options Set of 2 clamps for delta connexion Set of 2 clamps for star connexion R R 10

12 Propivar capacitors Insulation level 36 kv (70/170) 50/60 Hz Single phase capacitors with internal fuses DB Network voltage (V) Ref Capacitor voltage (V) (H x L x D / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 600 x 347 x 190 / 377 / R 700 x 347 x 190 / 377 / R 810 x 347 x 190 / 377 / R 1000 x 347 x 190 / 377 / R D Single-phase Propivar capacitor. Single phase capacitors without internal fuses Network voltage (V) Capacitor voltage (V) (H x L x D / b / H2) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 300 x 347 x 190 / 377 / R 400 x 347 x 190 / 377 / R 500 x 347 x 190 / 377 / R 500 x 347 x 190 / 377 / R 600 x 347 x 190 / 377 / R 810 x 347 x 190 / 377 / R 1000 x 347 x 190 / 377 / R Options Set of 2 clamps for delta connexion Set of 2 clamps for star connexion R R 11

13 MV capacitor banks Fixed compensation Schneider Electric can supply all types of capacitor banks, whatever the: b complexity of the network in the presence or absence of harmonics b demand for reactive power b nominal insulation voltages. To make it easier to choose the right capacitor banks, they are supplied: b CP214 fixed capacitor banks b CP227 fixed capacitor banks. CP214 and CP227 fixed capacitor banks Fixed capacitor banks CP214 CP227 Rated voltage y 12 kv y 36 kv Reactive power range y 960 kvar y 5760 kvar Example of application Individual motor compensation Global installation compensation Composition Protection HBC fuse CT and relay unbalance Switching current limitation by: 3 reactors 3 reactors Connection Delta Double star Type of capacitor bank CP214 fixed capacitor bank DB CP227 fixed capacitor bank DB Insulation voltage: Technical data The capacitor banks have the following common characteristics: b environmentally compatible Propivar capacitors with no PCB or chlorine dielectric liquid b service frequency: 50 Hz (available in 60 Hz, please consult us) b maximum temperature: 45 C b average temperature over 24 hours: 35 C b installation altitude y 1000 m b IP23 cubicle mounted b incoming cables from below with power cables connected to the copper pads b optional: outdoor type, fuse blow indicator, fast discharge reactors, lockable door. 12

14 CP214 fixed capacitor bank Insulation level 7.2 kv (20/60) - 50/60 Hz Standard type (slightly polluted network) DB CP214. Network voltage (V) Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (L x D x H) 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R DB Network voltage (V) Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (L x D x H) 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R CP214 options Melted fuse indication device Quick discharge coils: kv (set of 2) Door with lock for indoor type enclosure Outdoor type Door with lock for outdoor type enclosure Double roof for outdoor type enclosure R R R R R R 13

15 CP214 fixed capacitor bank Insulation level 12 kv (28/75) - 50/60 Hz Standard type (slightly polluted network) DB DB CP214. D Network voltage (V) Dimensions 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (mm) (L x D x H) 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R 1180 x 905 x R CP214 options Melted fuse indication device Quick discharge coils: kv (set of 2) Door with lock for indoor type enclosure Outdoor type Door with lock for outdoor type enclosure Double roof for outdoor type enclosure R R R R R R 14

16 CP214 SAH fixed capacitor bank Insulation level 7.2 kv (20/60) - 50/60 Hz SAH type (highly polluted network) DB DB CP214 SAH. Network voltage (V) Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (L x D x H) 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R Network voltage (V) Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (L x D x H) 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R CP214 SAH options Melted fuse indication device Quick discharge coils: kv (set of 2) Door with lock for indoor type enclosure Outdoor type Door with lock for outdoor type enclosure Double roof for outdoor type enclosure R R R R R R 15

17 CP214 SAH fixed capacitor bank Insulation level 12 kv (28/75) - 50/60 Hz SAH type (highly polluted network) DB DB CP214 SAH. Network voltage (V) Réf. 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (L x D x H) 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R 2000 x 1100 x R CP214 SAH options Melted fuse indication device Quick discharge coils: kv (set of 2) Door with lock for indoor type enclosure Outdoor type Door with lock for outdoor type enclosure Double roof for outdoor type enclosure Réf R R R R R R 16

18 CP227 fixed capacitor bank Insulation level 7.2 kv (20/60) - 50/60 Hz Standard type (slightly polluted network) DB Network voltage (V) Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (L x D x H) 1400 x 1400 x R 1400 x 1400 x R 1400 x 1400 x R CP227. CP227 options Unbalance protection relay (separately delivered) Quick discharge coils: kv (set of 2) Door with lock for indoor type enclosure Outdoor type Door with lock for outdoor type enclosure R R R R R DB

19 CP227 fixed capacitor bank Insulation level 12 kv (28/75) - 50/60 Hz Standard type (slightly polluted network) DB Network voltage (V) Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (L x D x H) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1900 x 1400 x 2000 (2) R (2) 1900 x 1400 x 2000 (2) R (2) 1900 x 1400 x 2000 (2) R (2) (1) 6C: 6 capacitors. (2) 12C: 12 capacitors. DB CP227. CP227 options Unbalance protection relay (separately delivered) Quick discharge coils: kv (set of 2) Door with lock for indoor type enclosure Outdoor type CP227-6C Outdoor type CP227-12C Door with lock for outdoor type enclosure R R R R R R 18

20 CP227 fixed capacitor bank Insulation level 17.5 kv (38/95) - 50/60 Hz Standard type (slightly polluted network) DB CP227. Network voltage (V) (L x D x H) 50 Hz 60 Hz 50 Hz 60 Hz 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1900 x 1400 x 2000 (2) R (2) 1900 x 1400 x 2000 (2) R (2) 1900 x 1400 x 2000 (2) R (2) 1900 x 1400 x 2000 (2) R (2) 1900 x 1400 x 2000 (2) R (2) (1) 6C: 6 capacitors. (2) 12C: 12 capacitors. DB CP227 options Unbalance protection relay (separately delivered) Quick discharge coils: kv (set of 2) Door with lock for indoor type enclosure Outdoor type CP227-6C Outdoor type CP227-12C Door with lock for outdoor type enclosure R R R R R R 19

21 CP227 fixed capacitor bank Insulation level 24 kv (50/125) - 50/60 Hz Standard type (slightly polluted network) DB DB CP227. Network voltage (V) (L x D x H) 50 Hz 60 Hz 50 Hz 60 Hz 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1400 x 1400 x 2000 (1) R (1) 1900 x 1400 x 2000 (2) R (2) 1900 x 1400 x 2000 (2) R (2) 1900 x 1400 x 2000 (2) R (2) 1900 x 1400 x 2000 (2) R (2) 1900 x 1400 x 2000 (2) R (2) 1900 x 1400 x 2000 (2) R (2) (1) 6C: 6 capacitors. (2) 12C: 12 capacitors. CP227 options Unbalance protection relay (separately delivered) Quick discharge coils: kv (set of 2) Door with lock for indoor type enclosure Outdoor type CP227-6C Outdoor type CP227-12C Door with lock for outdoor type enclosure R R R R R R 20

22 CP227 fixed capacitor bank Insulation level 36 kv (70/170) - 50/60 Hz Standard type (slightly polluted network) DB Network voltage (V) (L x D x H) 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 2500 x 2100 x R 2500 x 2100 x R 2500 x 2100 x R 2500 x 2100 x R 2500 x 2100 x R 2500 x 2100 x R 2500 x 2100 x R 2500 x 2100 x R DB CP227. CP227 options Unbalance protection relay (separately delivered) Door with lock for indoor type enclosure Outdoor type Door with lock for outdoor type enclosure R R R R 21

23 MV capacitor banks Automatic compensation Schneider Electric can supply all types of capacitor banks, whatever the: b complexity of the network in the presence or absence of harmonics b demand for reactive power b nominal insulation voltages. To make it easier to choose the right capacitor banks, they are supplied: b CP253 automatic capacitor banks b CP254 automatic capacitor banks. CP253 and CP254 automatic capacitor banks Type of capacitor bank CP253 CP254 Rated voltage y 12 kv y 36 kv Reactive power range y 4500 kvar y 5760 kvar Example of application Global installation compensation Energy distribution substation compensation Composition Protection HBC fuse Unbalance CT and relay Switching device Rollarc contactor SF1 circuit breaker Switching current limitation via: 3 reactors 3 reactors Regulation Varlogic varmetric controller Varlogic varmetric controller Connection Delta Double star Type of capacitor bank CP253 automatic capacitor bank CP254 automatic capacitor bank DB DB Insulation voltage: Technical data The capacitor banks have the following common characteristics: b environmentally compatible Propivar capacitors with no PCB or chlorine dielectric liquid b service frequency: 50 Hz (available in 60 Hz, please consult us) b maximum temperature: 40 C b average temperature over 24 hours: 35 C b installation altitude y 1000 m b IP23 cubicle mounted b incoming cables from below with power cables connected to the copper pads b optional: outdoor type, fuse blow indicator, fast discharge reactors, lockable door. 22

24 CP253 automatic capacitor bank Insulation level 7.2 kv (20/60) - 50/60 Hz Standard type (slightly polluted network) DB DB CP253. L Network voltage (V) Dimensions 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (mm) (L x D x H) 1 stage 1500 x 1600 x R 1500 x 1600 x R 1500 x 1600 x R 1500 x 1600 x R 1500 x 1600 x R 1500 x 1600 x R 1500 x 1600 x R 2 stages 2600 x 1600 x R 2600 x 1600 x R 2600 x 1600 x R 2600 x 1600 x R 2600 x 1600 x R 2600 x 1600 x R 2600 x 1600 x R 2600 x 1600 x R 2600 x 1600 x R 2600 x 1600 x R 2600 x 1600 x R 3 stages 3700 x 1600 x R 3700 x 1600 x R 3700 x 1600 x R 3700 x 1600 x R 3700 x 1600 x R 3700 x 1600 x R 3700 x 1600 x R 3700 x 1600 x R 3700 x 1600 x R 3700 x 1600 x R 3700 x 1600 x R 3700 x 1600 x R 4 stages 4800 x 1600 x R 4800 x 1600 x R 4800 x 1600 x R 4800 x 1600 x R 4800 x 1600 x R 4800 x 1600 x R 4800 x 1600 x R 5 stages 5900 x 1600 x R 5900 x 1600 x R CP253 options Quick discharge coils: kv (set of 2) n x R Door with lock for indoor type enclosure n x R Outdoor type n x R Door with lock for outdoor type enclosure n x R Control and protection box, for one (1) stage R Local manual control switch, for one (1) stage R Control and protection box, for two (2) stages R Local manual control switch, for two (2) stages R Control and protection box, for three (3) stages R Local manual control switch, for three (3) stages R Control and protection box, for four (4) stages R Local manual control switch, for four (4) stages R Control and protection box, for five (5) stages R Local manual control switch, for five (5) stages R n is the quantity of steps required. 23

25 CP253 automatic capacitor bank Insulation level 7.2 kv (20/60) - 50/60 Hz Standard type (slightly polluted network) DB DB CP253. L Network voltage (V) Dimensions 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (mm) (L x D x H) 1 stage 1350 x 1350 x R 1350 x 1350 x R 1350 x 1350 x R 1350 x 1350 x R 1350 x 1350 x R 1350 x 1350 x R 1350 x 1350 x R 2 stages 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 3 stages 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 4 stages 3650 x 1350 x R 3650 x 1350 x R 3650 x 1350 x R 3650 x 1350 x R 3650 x 1350 x R 3650 x 1350 x R 3650 x 1350 x R 5 stages 4600 x 1350 x R 4600 x 1350 x R CP253 options Quick discharge coils: kv (set of 2) n x R Door with lock for indoor type enclosure n x R Outdoor type n x R Door with lock for outdoor type enclosure n x R Control and protection box, for one (1) stage R Local manual control switch, for one (1) stage R Control and protection box, for two (2) stages R Local manual control switch, for two (2) stages R Control and protection box, for three (3) stages R Local manual control switch, for three (3) stages R Control and protection box, for four (4) stages R Local manual control switch, for four (4) stages R Control and protection box, for five (5) stages R Local manual control switch, for five (5) stages R n is the quantity of steps required. 24

26 CP253 automatic capacitor bank Insulation level 12 kv (28/75) - 50/60 Hz Standard type (slightly polluted network) DB DB CP253. L Network voltage (V) Dimensions 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (mm) (L x D x H) 1 stage 1350 x 1350 x R 1350 x 1350 x R 1350 x 1350 x R 1350 x 1350 x R 1350 x 1350 x R 1350 x 1350 x R 2 stages 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 2050 x 1350 x R 3 stages 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 2950 x 1350 x R 4 stages 3650 x 1350 x R 3650 x 1350 x R 3650 x 1350 x R 3650 x 1350 x R 3650 x 1350 x R 3650 x 1350 x R 3650 x 1350 x R 5 stages 4600 x 1350 x R 4600 x 1350 x R 4600 x 1350 x R 4600 x 1350 x R 4600 x 1350 x R CP253 options Quick discharge coils: kv (set of 2) n x R Door with lock for indoor type enclosure n x R Outdoor type n x R Door with lock for outdoor type enclosure n x R Control and protection box, for one (1) stage R Local manual control switch, for one (1) stage R Control and protection box, for two (2) stages R Local manual control switch, for two (2) stages R Control and protection box, for three (3) stages R Local manual control switch, for three (3) stages R Control and protection box, for four (4) stages R Local manual control switch, for four (4) stages R Control and protection box, for five (5) stages R Local manual control switch, for five (5) stages R n is the quantity of steps required. 25

27 CP253SAH automatic capacitor bank Insulation level 7.2 kv (20/60) - 50/60 Hz SAH type (highly polluted network) DB DB CP253 SAH. L Network voltage (V) Dimensions 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz (mm) (L x D x H) 1 stage 1500 x 2400 x R 1500 x 2400 x R 1500 x 2400 x R 1500 x 2400 x R 1500 x 2400 x R 1500 x 2400 x R 1500 x 2400 x R 2 stages 2600 x 2400 x R 2600 x 2400 x R 2600 x 2400 x R 2600 x 2400 x R 2600 x 2400 x R 2600 x 2400 x R 2600 x 2400 x R 2600 x 2400 x R 2600 x 2400 x R 2600 x 2400 x R 2600 x 2400 x R 3 stages 3700 x 2400 x R 3700 x 2400 x R 3700 x 2400 x R 3700 x 2400 x R 3700 x 2400 x R 3700 x 2400 x R 3700 x 2400 x R 3700 x 2400 x R 3700 x 2400 x R 3700 x 2400 x R 3700 x 2400 x R 3700 x 2400 x R 4 stages 4800 x 2400 x R 4800 x 2400 x R 4800 x 2400 x R 4800 x 2400 x R 4800 x 2400 x R 4800 x 2400 x R 4800 x 2400 x R 5 stages 5900 x 2400 x R 5900 x 2400 x R CP253 SAH options Quick discharge coils: kv (set of 2) n x R Door with lock for indoor type enclosure n x R Outdoor type n x R Door with lock for outdoor type enclosure n x R Control and protection box, for one (1) stage R Local manual control switch, for one (1) stage R Control and protection box, for two (2) stages R Local manual control switch, for two (2) stages R Control and protection box, for three (3) stages R Local manual control switch, for three (3) stages R Control and protection box, for four (4) stages R Local manual control switch, for four (4) stages R Control and protection box, for five (5) stages R Local manual control switch, for five (5) stages R n is the quantity of steps required. 26

Power factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World

Power factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World Catalogue 2002 Automatic capacitor banks Building a New Electric World 0Contents Power factor correction 2 Power factor equipment selection guide 3 General technical data 4 Capacitors and banks 50 z 6

More information

How To Build A Low Voltage Capacitor Lvcp

How To Build A Low Voltage Capacitor Lvcp Low Voltage Capacitor LVCP The new choice for Power Factor Correction LVCP : the new choice for Power Factor Correction The LVCP is a compact and powerful capacitor. It offers high modularity, unmatched

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

7. Reactive energy compensation

7. Reactive energy compensation 593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical

More information

MV POWER CAPACITORS AND BANKS. All film dielectric MV Power Capacitors QUALITY MADE IN ITALY

MV POWER CAPACITORS AND BANKS. All film dielectric MV Power Capacitors QUALITY MADE IN ITALY 2014 MV POWER CAPACITORS AND BANKS BIORIPHASO TF All film dielectric MV Power Capacitors QUALITY MADE IN ITALY Index Icar: Products and solutions 1 ICAR Quality System 3 Medium and High Voltage Solutions

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

DYNACOMP The top-class dynamic response compensator

DYNACOMP The top-class dynamic response compensator DYNACOMP The top-class dynamic response compensator Reactive power and Power Quality Reactive power Excessive reactive power drawn by linear- and non-linear loads deteriorates the Power Quality of the

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

Solutions for Power factor Correction at Medium Voltage

Solutions for Power factor Correction at Medium Voltage Solutions for Power factor Correction at Medium Voltage Energy efficiency technology CIRCUTOR, SA Headquarters in Viladecavalls. Leaders by experience CIRCUTOR has over 40 years experience and 6 production

More information

Power Capacitor Units for improved power quality

Power Capacitor Units for improved power quality Power Capacitor Units for improved power quality Applications for capacitors Reactive power compensation Most of the apparatus and loads connected to the electrical power system consume both active and

More information

Reactive Power Compensation. ABB High Voltage Products June 19, 2013 Slide 1

Reactive Power Compensation. ABB High Voltage Products June 19, 2013 Slide 1 José Matias High Voltage Components ABB AB Santiago - Chile, 05-June-2013 Reactive Power Compensation June 19, 2013 Slide 1 Reactive Power Compensation Main Topics Topics Introduction The need for capacitors

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

GUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT

GUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT GUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT GENERAL: 1. The selection of switchgear for switching the capacitors should be done carefully. The circuit breaker

More information

Shunt Capacitor Bank Fundamentals and Protection

Shunt Capacitor Bank Fundamentals and Protection 2003 Conference for Protective Relay Engineers - Texas A&M University April 8-10, 2003, College Station (TX) Shunt Capacitor Bank Fundamentals and Protection Gustavo Brunello, M.Eng, P.Eng Dr. Bogdan Kasztenny

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

Guide for the Design and Production of LV Power Factor Correction Cubicles

Guide for the Design and Production of LV Power Factor Correction Cubicles Power Factor Correction Guide for the Design and Production of LV Power Factor Correction Cubicles Panel Builder Guide 2011 Panel Builder Guide 2011 Contents CHAPTER 1: General design rules 3-11 Applicable

More information

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

How To Understand The Electrical Power Supply Of A Power Supply System

How To Understand The Electrical Power Supply Of A Power Supply System 17 Circuit diagram symbols E 18 CIRCUIT DIAGRAM SYMBOLS electrical network elements three-phase line or cable single-phase line or cable short circuit earth electrode outgoing feeder supply incoming feeder

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

Current transformer selection guide

Current transformer selection guide The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for. The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

POWER FACTOR CORRECTION

POWER FACTOR CORRECTION [CATALOGUE PFC-SFC] POWER FACTOR CORRECTION INDUSTRIAL SWITCHGEAR & AUTOMATION SPECIALISTS A component of nhp s green star solution... www.nhp.com.au Power Factor - What does it mean? Where open electricity

More information

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125 Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated

More information

13. Electrical network design methodology and application example

13. Electrical network design methodology and application example 873 13. Electrical network design methodology and application example 874 13. ELECTRICAL NETWORK DESIGN METHODOLOGY AND APPLICATION EXAMPLE The profitability of an industrial installation is directly linked

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

CLASS 5830 REACTIVAR Power Factor Capacitors AV4000/AV5000 STANDARD AUTOMATIC BANKS

CLASS 5830 REACTIVAR Power Factor Capacitors AV4000/AV5000 STANDARD AUTOMATIC BANKS CLASS 5830 REACTIVAR Power Factor Capacitors AV4000/AV5000 STANDARD AUTOMATIC BANKS The new Square D REACTIVAR AV4000 & AV5000 standard Automatic Power Factor Correction banks offer unsurpassed safety,

More information

Cahier technique no. 196

Cahier technique no. 196 Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for

More information

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw ,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS

More information

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed

More information

Presentation of the France Transfo factories

Presentation of the France Transfo factories Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H. POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,

More information

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will

More information

The standards mentioned in this document

The standards mentioned in this document The standards mentioned in this document Where can you order IEC publications? Central Offices of the International Electrotechnical Commission 1, rue de Varembé Geneva - Switzerland. The documentation

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1

ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1 ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1 Design and Planning Specification for New Low Voltage Installations for Housing Developments 1. SCOPE This appendix to ENA

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

max 6f / computer max

max 6f / computer max POWER FACTOR REGULATORS computer max max 6f / computer max max 12f Instructions Manual ( M98234601-03-10A ) - 1 - Index 1 INTRODUCTION AND SAFETY RECOMMENDATIONS... 3 1.1 DELIVERY SPOT CHECK... 3 1.2 STARTING

More information

Low Voltage Products. Low Voltage Capacitors Power Factor Correction Solutions

Low Voltage Products. Low Voltage Capacitors Power Factor Correction Solutions Low Voltage Products Low Voltage Capacitors Power Factor Correction Solutions Low Voltage Capacitors Reliability for Power Factor Correction Dry type design The ABB Low Voltage Capacitors, called CLMD,

More information

ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw

ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw Solar inverters ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw PV energy, combined with energy storage systems, can help increase self-consumption and energy selfsufficiency*. One of the biggest challenges

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

High-Voltage GIS yesterday - today - tomorrow

High-Voltage GIS yesterday - today - tomorrow High-Voltage GIS yesterday - today - tomorrow Peter Glaubitz, Siemens AG, Principal Expert GIS-Technology siemens.at/future-of-energy Table of content GIS yesterday beginning and establishment of Gas-

More information

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS by John Houdek, President, Allied Industrial Marketing, Inc., and Cesar Chavez, Engineering Manager, ARTECHE / Inelap Abstract: The addition of power factor improvement capacitors to individual motors

More information

SECTION 16461 DRY-TYPE TRANSFORMERS

SECTION 16461 DRY-TYPE TRANSFORMERS SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any

More information

SIVACON The Versatile Low-Voltage Switchboard

SIVACON The Versatile Low-Voltage Switchboard s SIVACON The Versatile Low-Voltage Switchboard Type-Tested Power Distribution Board 8PT The Obvious Solution for Global Challenges SIVACON Type testing in low-voltage switchgear is increasingly becoming

More information

Thermistor motor protection

Thermistor motor protection Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES High pulse loading capability Small size. APPLICATIONS Where high resistance, high stability and high reliability at high voltage are required High humidity environment White goods Power supplies.

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

The design and performance of Static Var Compensators for particle accelerators

The design and performance of Static Var Compensators for particle accelerators CERN-ACC-2015-0104 Karsten.Kahle@cern.ch The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,

More information

Current distribution Comb busbars for Declic and SFT residential devices

Current distribution Comb busbars for Declic and SFT residential devices Current distribution Comb busbars for Declic and SFT residential devices Comb busbar, for connecting 26 x 9 mm modules, consisting of two insulated bars to supply 1P + N devices (Declic, SFT, etc.). Due

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

Medium voltage circuit breaker

Medium voltage circuit breaker Medium voltage circuit breaker IEC 60 056 and ANSI C37-06 define on one hand the operating conditions, the rated characteristics, the design and the manufacture; and on the other hand the testing, the

More information

DS1 Diode-based transient-free capacitor switch

DS1 Diode-based transient-free capacitor switch Medium voltage products DS1 Diode-based transient-free capacitor switch Power and productivity for a better world TM Compensation of reactive power DS1 the future of switches Compensation of reactive power

More information

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet PI044E - Winding 311 Technical Data Sheet PI044E SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES E Bompard*, E Carpaneto*, R Napoli*, P Ribaldone**, C Vercellino** * Dipartimento di Ingegneria Elettrica Industriale,

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information

Merlin Gerin technical guide Medium Voltage. MV design guide. We do more with electricity.

Merlin Gerin technical guide Medium Voltage. MV design guide. We do more with electricity. Merlin Gerin technical guide Medium Voltage MV design guide We do more with electricity. Design Guide This guide is a catalogue of technical know-how intended for medium voltage equipment designers. Goal

More information

CERN Accelerator School. Electrical Network and Power Converters. Hans Ulrich Boksberger Paul Scherrer Institute 5232 Villigen PSI Switzerland

CERN Accelerator School. Electrical Network and Power Converters. Hans Ulrich Boksberger Paul Scherrer Institute 5232 Villigen PSI Switzerland CERN Accelerator School Electrical Network and Power Converters Hans Ulrich Boksberger Paul Scherrer Institute 5232 Villigen PSI Switzerland 1/ 21 / 17.5.2004 / HU Boksberger Outline Utility Standards

More information

Plug-in relays Mini ISO relays

Plug-in relays Mini ISO relays Powertrain Systems Chassis Systems Safety Security Body Driver Information Convenience Description Features Limiting continuous current 70 A Dimensional characteristics and the functional allocation of

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY

More information

CAS 36 Ring Main Unit

CAS 36 Ring Main Unit Power distribution networks Ring Main Unit Catalogue 2008 A new path for achieving your electrical installations A comprehensive offer The range is part of a comprehensive offer of products that are perfectly

More information

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61

CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61 FUSES Catalogue CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61 INTRODUCTION The main function of current limiting fuses is to protect electrical apparatus, such as distribution transformers, motors

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING

More information

Low Voltage Products. Low Voltage Capacitor Banks Power Factor Correction Solutions

Low Voltage Products. Low Voltage Capacitor Banks Power Factor Correction Solutions Low Voltage Products Low Voltage Capacitor Banks Power Factor Correction Solutions ABB LV Capacitor Banks The Most Comprehensive Solution for Automatic Power Factor Correction 2 ABB LV Capacitor Banks

More information

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

3) What is the difference between Insulating, Isolating, and Shielded Winding transformers? Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer

More information

Low and High Voltage Power Supplies

Low and High Voltage Power Supplies Low and High Voltage Power Supplies We work according to ISO 9001: 2008 Since 1994 Fug works according to the quality assurance system ISO 9001. All shipped units are checked and documented in our testing

More information

FACTS. Solutions to optimise network performance GRID

FACTS. Solutions to optimise network performance GRID Solutions to optimise network performance GRID Solutions to optimise your network Our worldwide presence: Better solutions for your network all around the world Tampere Philadelphia Stafford Konstanz Beijing

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

IRON-CORE REACTORS FOR DETUNING POWER CAPACITORS IN MEDIUM AND LOW VOLTAGE NETWORKS

IRON-CORE REACTORS FOR DETUNING POWER CAPACITORS IN MEDIUM AND LOW VOLTAGE NETWORKS IRON-CORE REACTORS FOR DETUNING POWER CAPACITORS IN MEDIUM AND LOW VOLTAGE NETWORKS ED DTR 06.11 Made in Germany H A N S V O N M A N G O L D T A A C H E N Harmonic network distortion and its effects (

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Here is our comprehensive product range dedicated to MV distribution and earthfault compensation.

Here is our comprehensive product range dedicated to MV distribution and earthfault compensation. Here is our comprehensive product range dedicated to MV distribution and earthfault compensation. Self-protected TPC transformers (with and without built-in inductance), are commonly used to revamp existing

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary

More information

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS PI144K - Winding 311 Technical Data Sheet PI144K SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section

More information