Speaker. Steve Leyton Protection Design & Consulting
|
|
- Felicia Kelley Gilbert
- 7 years ago
- Views:
Transcription
1
2 Speaker Steve Leyton Protection Design & Consulting Steve Leyton is President of Protection Design & Consulting in San Diego, CA and a member of the Fire Smarts Faculty. He began his career in 1981 on the design/build side of fire sprinkler industry and founded PD&C in Since then, the firm s work has been focused on Architectural as well as Contractor clients. Professional affiliations include membership in NFPA, International Code Council (ICC), American Fire Sprinkler Association (AFSA), National Fire Sprinkler Association (NFSA), California Fire Prevention Officers Northern and Southern Sections, and the San Diego Fire Protection Association. In code development, he is a member of the NFPA14, NFPA 13D/13R and NFPA 5000 Technical Committees. He served as Chair of the installation committee for the California State Fire Marshal s Residential Sprinkler Code Adoption Task Group and Co-Chair of the ICC Ad-Hoc Committee on Residential Fire Sprinklers. Over the course of his career, Steve has worked on all manner of residential, commercial/ industrial, institutional and high-rise projects in the United States, Mexico and Asia. 2
3 NFPA s preferred definition of automatic sprinkler: A fire suppression or control device that operates automatically when its heat-activated element is heated to its thermal rating or above, allowing water to discharge over a specified area.
4 Sprinklers are categorized based on the following: Orientation (upright, pendent, sidewall) Area of coverage Specific characteristics of its ability to control or suppress a fire Thermal response Discharge (spray pattern) characteristics - standard, extended, etc. Limitations by use or occupancy residential, storage, standard Key characteristics of sprinklers: Temperature rating Thermal sensitivity which is a measurement of how quickly a sprinkler activates once it is exposed to its temperature rating Orifice size which is the diameter of the opening through which water flows
5 Sprinklers must discharge a minimum flow rate Based on area of coverage Based on whether ceiling is sloped Pressure affected by orifice size or K-factor Available pressure impacted by pipe size, fittings and overall friction loss.
6 Sprinklers must discharge a minimum flow rate Based on area of coverage Whether ceiling is sloped and to what rise Pressure driven by orifice size and K-factor Available pressure impacted by pipe size, fittings and overall friction loss.
7 Residential sprinklers available in two pendent styles with different trim and cover plates: Recessed (aka semi-recessed) Concealed (dome type) Concealed (flat plate) Costs and listings vary it is critical to assure that a certain sprinkler is listed for the application!!
8
9
10
11 Each manufacturer offers a variety of factory finishes for both sprinklers and escutcheons. Custom finishes available by special order; typically referenced by paint card number. No field painting of sprinklers or cover plates; only factory-applied coatings are allowed.
12
13 Some sprinklers have limited areas of coverage Can vary by manufacturer and K-factor Some not listed for slopes; some listed for slopes up to 4:12; some listed for slopes up to 8:12. Manufacturers are aggressively testing new sprinklers for exposed beams and slopes.
14
15
16
17
18
19 Operational Sensitivity For Horizontal Ceilings (maximum 2 inch rise for 12 inch run), the sprinklers are to be installed with a deflector to ceiling distance of 1-3/8 to 4 inches or in the recessed position using only the Style 20 Recessed Escutcheon as shown in Figure 2. Notes The Beam Ceiling Design Criteria section starting on Page 4 permits deflector to ceiling distances up to 15-3/4 inches. So as to help avoid obstructions to water distribution, a maximum 12 inch deflector-to-ceiling distance is permitted for NFPA 13DandNFPA 13R applications where the sprinklers are located in closets. (Tyco Technical Bulletin TFP400)
20 Meter Rating Safe flow rate and rated flow rate not related Two basic meter types, turbine and disk New push for listed meters. Unscientific tests show that meters will perform at double their rated flow and beyond. Backflow requirements vary by purveyor.
21 Restrictions may force Design To Available Meter Both NFPA 13D and P2904 require concurrent domestic allowance be hydraulically accounted for in MP systems. This is also a commonly enforced amendment nationwide. AHJ can decide whether or not to count domestic allowance against meter rating.
22 Viking 4.3K Recessed
23 Viking 4.9K Recessed
24
25 Sprinklers available in a range of appearances and coverage areas Offer efficiencies of piping runs Of particular benefit when piping from low ceilinged area into higher volume compartments
26
27
28
29
30
31
32
33
34 Application and installation must be in accordance with manufacturer s listings and guide Not always a listed sprinkler for the application Beams, obstructions and slopes must be factored Use your resources! Manufacturers offer application guides and technical support.
35 Stand-Alone Tree Simplest design, dead-end mains & lines Stand-Alone Loop Can be single or multi-story Compounded with vertical supply risers Multi-purpose Looped, Passive Purge Multi-purpose - Network
36 .
37 .
38
39 Pipe or tube used in sprinkler systems shall be of the materials specified in Table or shall be in accordance with The chemical properties, physical properties, and dimensions of pipe materials shall be at least equivalent to the standards cited in Table
40 Table Pipe or Tube Materials and Dimensions Materials and Dimensions Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for Fire Protection Use Standard ASTM A 795 Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless ASTM A 53 Welded and Seamless Wrought Steel Pipe ANSI B 36.10M Electric-Resistance-Welded Steel Pipe ASTM A 135 Seamless Copper Tube [Copper Tube (Drawn, Seamless)] ASTM B 75 Seamless Copper Water Tube ASTM B 88 Wrought Seamless Copper and Copper-Alloy Tube ASTM B 251 Liquid and Paste Fluxes for Soldering Applications of Copper and Copper- Alloy Tube Filler Metals for Brazing and Braze Welding (BCuP, copper- phosphorus, or copper-phosphorus-silver brazing filler metal) Solder Metal [alloy grades containing less than 0.2 percent lead as identified in ASTM B 32, Table 5, Section 1, and having a solidus temperature that exceeds 400 F (204 C)] ASTM B 813 AWS A5.8 ASTM B 32
41 Pipe used in sprinkler systems other than those addressed in shall be designed to withstand a working pressure of not less than 175 psi (12.1 bar) Nonmetallic pipe used in multipurpose piping systems not equipped with a fire department connection shall be designed to withstand a working pressure of not less than 130 psi (8.9 bar) at 120 F (49 C). Types of pipe other than those specified in Table shall be permitted to be used where listed for sprinkler system use.
42 7.4 Piping Support Listed pipe shall be supported in accordance with any listing limitations Pipe that is not listed, and listed pipe with listing limitations that do not include piping support requirements, shall be supported from structural members using support methods comparable to those required by applicable local plumbing codes.
43 P Sprinkler piping system. Sprinkler piping shall be supported in accordance with the requirements for cold water distribution piping. Sprinkler piping shall comply with the material requirements for cold water distribution piping. For multipurpose piping systems, the sprinkler piping shall connect to and be a part of the cold water distribution piping system. P Nonmetallic pipe and tubing. Nonmetallic pipe and tubing, such as CPVC and PEX, shall be listed for use in residential fire sprinkler systems.
44 Raw pellets manufactured by two firms BlazeMaster, manufactured by Lubrizol Raw materials only Numerous brands of Blazemaster Products Viking, Tyco, Harvel, Nibco, IPEX FlameGuard, manufactured by Spears Raw materials and finished products Directly distributed Products are cross-listed and universally compatible
45 Pipe and fittings specifically designed and for fire protection systems UL 1821 FM 1635 Same working pressure rating as metallic piping 175 PSI at 120 F Can be installed exposed in basements; flame resistance lends well to garage installations Special listing requires use of listed hangers and supports at specified on-center spacing
46
47
48
49 Pipe and fittings specifically designed and for fire protection systems UL 1821 NSF Lower working pressure rating 130 PSI at 120 F Must be concealed low flame resistance rating Applications currently limited to MP systems by NFPA 13D
50
51
52 Both CPVC and PEX require restraint to prevent sprinklers from up CPVC utilizes additional supports near sprinklers PEX utilizes self-anchoring fittings
53
54
55 Questions and Answers Phone:
C I T Y O F S E L M A F I R E D E P A R T M E N T
C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
More informationSeries TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description
Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall s Quick and Standard Response (Light Hazard) General Description TYCO Series TY-FRB 5.6 and
More informationWe look forward to working with you. Worldwide Headquarters 1400 Pennbrook Parkway Lansdale, PA 19446. www.tyco-rapidresponse.com
TYCO IS HERE TO HELP Tyco will work closely with you to make the installation of Rapid Response Residential Fire Sprinkler Systems a quick and easy addition to your new home construction. We can develop
More informationModel SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description
Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary s, Standard are
More informationSprinkler Identification Numbers
Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 K-factor Horizontal Quick Response, Standard Coverage General Description described in this data sheet are quick response -standard coverage, decorative
More informationSprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts. www.tyco-fire.com
Worldwide Contacts www.tyco-fire.com Model EC-HS 80 K-factor, Quick Response Extended Coverage Horizontal Sidewall Sprinklers Installations per VdS CEA 400, Annex E, LH/OH General Description The Model
More informationQuick response concealed horizontal sidewall sprinkler
January 1, 2011 Sprinkler 63a 1. DESCRIPTION Viking Quick Response Concealed Horizontal Sidewall Sprinkler VK408 is a small solder link and lever spray sprinkler designed for installation on concealed
More informationRESIDENTIAL SPRINKLER INSTALLATION GUIDE
RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,
More informationSeries TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description
Worldwide Contacts www.tyco-fire.com Series 2.8,.2,.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description The TYCO Series, 2.8,.2,.6, 8.0 K-factor,
More informationTECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013
Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge
More informationViking Residential Sprinkler Installation Guide
Viking Residential Sprinkler Installation Guide January, 2009 Trusted Above AllT M www.flowbusiness.cl Sprinkler RES1 January 9, 2009 1. DESCRIPTION Viking residential automatic sprinklers are equipped
More informationModel/Sprinkler Identification Numbers
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-L 5.6 and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description
More informationTEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs
TITLE 22 PART 17 CHAPTER 363 RULE 363.11 EXAMINING BOARDS TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs (a) General requirements for Course Providers
More informationModel KFR56 Series Quick Response Standard Spray
Bulletin 036 Model KFR56 Series Quick Response Standard Spray Bulletin 036 Model KFR56 Sprinkler Types Standard Upright Standard Pendent Horizontal Sidewall Model KFR56 Sprinkler Types Pendent F1/F2/FP
More informationAntifreeze Solutions in Residential Fire Sprinkler Systems
Antifreeze Solutions in Residential Fire Sprinkler Systems The 2013 edition of NFPA 13D, as amended by TIA 13 1, discourages the use of antifreeze solutions within residential fire sprinkler systems unless
More informationESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA
December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas
More informationBUILD FOR QUALITY BUILD FOR VALUE BUILD FOR LIFE
BUILD FOR QUALITY BUILD FOR VALUE BUILD FOR LIFE AUTOMATIC FIRE SPRINKLER PROTECTION Residential fire sprinkler system installations are increasing every day thanks to growing buyer demand, lower costs,
More informationModel F1FR Series Quick Response Glass Bulb Sprinklers
Model F1FR56 Sprinkler Types Standard Spray Standard Spray Conventional / Vertical Sidewall Model F1FR56 Recessed Sprinkler Types Standard Spray Model F1FR56 Concealed Sprinkler Types Standard Spray Model
More informationModel WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description
Worldwide Contacts www.tyco-fire.com Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description The TYCO Model WS Specific Application Window
More informationSeries TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-FRL 5.6 and 8.0 K-factor Extended Horizontal Sidewall s Quick & Standard (Light Hazard) General Description The Series TY-FRL, 5.6,
More informationClark County Fire Prevention
Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF
More informationesfr pendent sprinkler vk510 (k25.2)
January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition
More informationINTERNATIONAL RESIDENTIAL CODE PLUMBING
INTERNATIONAL RESIDENTIAL CODE PLUMBING RP1-07/08 P2503.5.1 Proposed Change as Submitted: Proponent: Michael Cudahy, representing Plastic Pipe and Fittings Association Revise as follows: P2503.5.1 Rough
More informationAutomatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
More informationType EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description
Worldwide Contacts www.tyco-fire.com Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description The TYCO Type EA-1 PROTECTO- SPRAY Directional Spray Nozzles are automatic
More informationHow To Install A Fire Sprinkler
Fire Sprinklers: Coming to a Home Near You With a smoking record for saving lives and protecting houses, it s no surprise sprinklers were adopted into the International Residential Code BY CHRIS ERMIDES
More informationExtended Coverage Sprinklers
Extended Coverage Sprinklers Welcome ASPE Wally Barker Sprinkler Systems 101 MATERIALS OF CONSTRUCTION The components that make up a sprinkler head are: Frame or casting Deflector Fusible element or frangible
More informationYour Instructor. Two Biggest Obstacles to Residential Sprinklers. Two Biggest Obstacles to Residential Sprinklers
Residential Sprinklers ----- Issues and Answers Your Instructor Jeffrey M. Shapiro, PE Executive Director IRC Fire Sprinkler Coalition 1 2 The IRC Fire Sprinkler Coalition Not-for-profit association representing
More informationSeries ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description IMPORTANT Always refer
More informationType D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description
Worldwide Contacts www.tyco-fire.com Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description The TYCO Type D3 PROTECTO- SPRAY Nozzles are open (non-automatic) directional
More informationSteel Fire Sprinkler Pipe
Steel Fire Sprinkler Pipe Wheatland Tube Fire Sprinkler Products Wheatland Tube began producing steel fire sprinkler pipe in 1931, and today offers the most complete line of products in the industry. Engineers
More informationIDENTIFICATION BROCHURE FOR Central RESIDENTIAL WET SPRINKLERS
IDENTIFICATION BROCHURE FOR Central RESIDENTIAL WET SPRINKLERS 1 INTRODUCTION TO THE VOLUNTARY REPLACEMENT PROGRAM This brochure provides information that will assist you in identifying whether the sprinklers
More informationViking Residential Sprinkler Installation Guide
Viking Residential Sprinkler Installation Guide Trusted bove ll TM www.vikinggroupinc.com Sprinkler RES1 1. DESCRIPTION Viking residential automatic s are equipped with a fast response heat-sensitive operating
More informationSeries DS-1 Dry-Type Sprinklers 5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description
Worldwide Contacts www.tyco-fire.com Series DS-1 Dry-Type Sprinklers 5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description TYCO Series DS-1 Dry-Type Sprinklers, 5.6
More informationRoland Garcia Pearland Fire Department
Roland Garcia Pearland Fire Department NFPA13D Texas Legislation Conflicting Views - Fire Service and Home Builders Incentives offered in the ICC Detect and control residential fires Prevent injury and
More informationModel F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description
Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed
More informationWhat to Expect From the Examination. How to Study the Plumbing Codes
Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.
More informationSPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST
SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following
More informationH O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S
H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S HomeFireSprinkler.org F I R E T H E L A R G E ST S I N G L E C AU S E O F
More informationEngineering Specifications
PUREFLOW PEX PRODUCTS PART 1 GENERAL 1.1 SUMMARY 1.1.1 This specification covers Branch & Main, Parallel Water Distribution Systems (MANABLOC), Cross-linked Polyethylene tubing and fittings using PEX Press
More informationSprinkler Guards Model C Model D
Bulletin 208 Rev. M Sprinkler Guards Model C Model D Bulletin 208 Rev. M Model C Sprinkler Guards Model C Series sprinkler guards are designed to be assembled onto installed sprinklers. They are constructed
More informationDESIGN GUIDE FOR INSTALLING PARTIAL SPRINKLER PROTECTION IN UNFINISHED BASEMENT AREAS
UP DESIGN GUIDE FOR INSTALLING PARTIAL SPRINKLER PROTECTION IN UNFINISHED BASEMENT AREAS March 2014 This document is not intended to advocate nor discourage the installation of residential sprinkler systems
More informationASME/ANSI B16.1-1998 - Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B16.3-1998 - Malleable Iron Threaded Fittings ASME/ANSI B16.
ASME/ANSI B16.1-1998 - Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B16.3-1998 - Malleable Iron Threaded Fittings ASME/ANSI B16.4-1998 - Cast Iron Threaded Fittings ASME/ANSI B16.5-1996 - Pipe
More informationSprinkler Identification Numbers (SINs) Technical Data
Worldwide Contacts www.tyco-fire.com Series DS-1 5.6 K-factor, Dry-type Sprinklers Pendent, Upright, and Horizontal Sidewall Standard Response, Standard Coverage General Description TYCO Series DS-1 5.6K
More informationTechnical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities
Technical Article for High Bay and Automated Storage in Warehouse-Type Storage Facilities Scott Martorano, CFPS Senior Manager Technical Services February, 2010 Worldwide Fire Protection www.vikinggroupinc.com
More information2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
More informationSuccess In Scottsdale
HELP THEM PROTET THEIR WORL. esthetical l y Pl easing. ffordably Priced. Rapid Response Home Fire Sprinklers come in a wide range of styles and colors that will complement any décor or home design. nd,
More informationIDENTIFICATION BROCHURE FOR Central COMMERCIAL WET SPRINKLERS
IDENTIFICATION BROCHURE FOR Central COMMERCIAL WET SPRINKLERS 1 INTRODUCTION TO THE VOLUNTARY REPLACEMENT PROGRAM This brochure provides information that will assist you in identifying whether the sprinklers
More informationFACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING 21 11 00
211100_flexheadin_01_MS_0409 5/22/09 PTC 56 Lowland Street Holliston, MA 01746 Phone: (800) 829-6975 Phone: (508) 893-9596 Fax: (508) 893-6020 E-mail: sales1@flexhead.com www.flexhead.com This MANU-SPEC
More informationINSTALLATION INSTRUCTIONS & TECHNICAL MANUAL
INSTALLATION INSTRUCTIONS & TECHNICAL MANUAL TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale, Pennsylvania 19446 www.tyco-fire.com TECHNICAL SERVICES TEL: (800) 381-9312 FAX: (800) 791-5500 E-MAIL:
More informationRefrigeration Installation 101
Refrigeration Installation 101 Hundreds of Installations Refrigerated Cases 2 Compressor Racks 3 Condensing Units 4 Walk-in Boxes 5 Some were done very well 6 Some had some issues... 7 8 Some seemingly
More informationChapter 7 Plumbing Connections
Chapter 7 Plumbing Connections 7-1 General All plumbing equipment and installations must be designed, constructed, and installed in accordance with this code and where not specific, to the applicable provisions
More informationThis document was scanned from hard copy to portable document format (PDF) and edited to 99.5% accuracy. Some formatting errors not detected during
FA-155 / May 1995 This document was scanned from hard copy to portable document format (PDF) and edited to 99.5% accuracy. Some formatting errors not detected during the optical character recognition process
More informationSTANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2
STANDARD for Plumbing, Heating, Hot Water, Cold Water & Electrical work undertaken by owners within the building known as Sussex Lodge London W2 & 16 Stanhope Terrace London W2 BPME Consulting Engineers
More informationWHAT YOU NEED TO KNOW ABOUT INSURING A HOME WITH FIRE SPRINKLERS
WHAT YOU NEED TO KNOW ABOUT INSURING A HOME WITH FIRE SPRINKLERS A GUIDE FOR PROPERTY & CASUALTY INSURANCE PROFESSIONALS HomeFireSprinkler.org FIRE THE LARGEST SINGLE CAUSE OF PROPERTY LOSS Fire is the
More informationSECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES
SECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationTECHNICAL DATA. 30a. September 18, 2009 1-1/4-8 (DN32 - DN200)
September 18, 2009 30a 1. DESCRIPTION Viking EasyPac Commercial Riser Manifold Assemblies are available in sizes 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 6 and 8 for commercial systems. They are available with an
More informationMERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS
MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth
More informationTechnical Data. Installation
Technical Services: Tel: (800) 81-91 / Fax: (800) 791-5500 Model 51 (1) Riser Manifold 1-1/ thru 6 Inch (DN40 thru DN150) For NFPA 1 Sprinkler Systems General Description The Figure 51 (1) Riser Manifolds
More informationTyco Fire & Building Products is a leading manufacturer and distributor of water-based fire suppression systems and components, offering one of the
Tyco Fire & Building Products is a leading manufacturer and distributor of water-based fire suppression systems and components, offering one of the broadest lines of fire protection system equipment worldwide.
More informationHome Fire Sprinkler Cost Assessment - 2013
Home Fire Sprinkler Cost Assessment - 2013 Final Report Prepared by: Newport Partners The Fire Protection Research Foundation One Batterymarch Park Quincy, MA, USA 02169-7471 Email: foundation@nfpa.org
More informationSECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
More informationOntario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
More informationSECTION 1 GENERAL REQUIREMENTS
Page 1 of 6 SECTION 1 GENERAL REQUIREMENTS 1. SCOPE OF WORK: The work to be performed under the provisions of these documents and the contract based thereon includes furnishing all labor, equipment, materials,
More informationAre you finding difficulty with the Code? Do you need consultations?
Are you finding difficulty with the Code? Do you need consultations? Come and visit us at the consultant booth between 11-13 November 2013 at the Qatar National Convention Center (QNCC) and get free consultation
More informationA. The shade structure contractor shall be responsible for the design, engineering, fabrication, and supply of the work specified herein.
13310 FABRIC SHADE STRUCTURES FOR PLAYGROUND AREAS ************************************************************************************************************************ SPECIFIER: CSI Master Format
More informationModel F156 Sprinkler Types. Model F156 Recessed Sprinkler Types. Model F142, F1XLH & F128 Sprinkler Types
Bulletin 013 Rev. M Models F1 Series Standard Response s Bulletin 013 Rev. M Model F156 Types Standard Upright Standard Pendent Conventional Vertical Sidewall Model F156 Recessed Types Pendent/F1/F2/FP
More informationPIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant
More informationOntario Association of Fire Chiefs Position Paper Residential Fire Sprinklers
Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers The Ontario Association of Fire Chiefs (OAFC) supports changes to the Ontario Building Code to require that all new residential
More informationNFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,
More informationASME Packaged Indirect Fired Water Heater
Utilizes Or HTHW To Heat Domestic Water, Semi-Instantaneous or Storage Type Model BW Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone cement lining
More informationCost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator
Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator Andy L. Kaempfer Business Development Manager Potter Electric Signal Company, LLC 1609 Park 370 Place St. Louis,
More informationwww.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 10 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES
More information(a) Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems.
12.33 - CROSS-CONNECTION CONTROL. (a) Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems. (b) Definitions. The following definitions shall apply
More informationEFSN Training i Module 1. 90 Minutes
Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler
More informationSECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 230529 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Steel pipe hangers and supports. 2. Metal framing systems. 3. Thermal-hanger shield inserts. 4. Fastener systems.
More informationRESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
More informationCost Estimation for Materials and Installation of Hot Water Piping Insulation
Cost Estimation for Materials and Installation of Hot Water Piping Insulation Prepared for Pacific Northwest National Laboratory Under Contract Number: 18O9O2 By Gary Klein, Managing Partner Affiliated
More informationFraternity and Sorority House Fire Safety
Fraternity and Sorority House Fire Safety Buddy Dewar Director of Regional Operations National Fire Sprinkler Association 850-222-2070 How To Manage Greek Housing Fire Sprinkler Retrofit Brief Overview.
More informationBased on SG GSA Fire & Security Products Contract GS-07F-0396M, Mod PO-0099 January 30, 2013
SimplexGrinnell TXMAS ecommerce Ferguson Fire and Fabrication Sprinkler Price List Based on SG GSA Fire & Security Products Contract GS-07F-0396M, Mod PO-0099 January 30, 2013 Product ID Description TXMAS
More informationSaves time. Saves money. Up to 2 size for commercial gas piping.
Flexible Gas Piping by OmegaFlex Saves time. Saves money. Up to 2 size for commercial gas piping. Cost-effective, safe and completely reliable, TracPipe/CounterStrike is the ideal pipe for new construction,
More informationCopper and Copper Alloy Tube, Pipe and Fittings
Copper and Copper Alloy Tube, Pipe and Fittings COPPER and COPPER ALLOY TUBE and PIPE Seamless Copper Pipe: Copper pipe is almost pure copper manufactured to the requirements of ASTM B 42 - Standard Specification
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationRAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID
More informationSECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS
1 SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and
More informationSpecifications for Lightning Protection. ASAE Engineering Practice
Chapter 8: Lightning Specifications for Lightning Protection ASAE safety standards are not laws. They are recommended voluntary standards used by designers, engineers, manufacturers and users of the equipment,
More informationMINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY. State Fire Marshal
MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY Policy #: Subject of Policy: INS-04 (2007) Escape Windows Revised and Approved By: Title: Jerry Rosendahl State Fire
More informationAll work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
More informationSECTION 260536 - CABLE TRAYS. A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system.
SECTION 260536 - CABLE TRAYS PART 1 - GENERAL SECTION INCLUDES: A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system. B. Cable tray systems are defined to include, but
More informationTECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2.
May 3, 2013 Foam 138a 1. DESCRIPTION Chemguard Water Powered Oscillating Monitors are designed to automatically discharge over a specific design area upon system activation. These are suitable for use
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationSIZING OF WATER PIPING SYSTEM
SIZING OF WATER PIPING SYSTEM SECTION E101 GENERAL E101.1 Scope. E101.1.1 This appendix outlines two procedures for sizing a water piping system (see Sections E103.3 and E201.1). The design procedures
More informationSapa: SECTION 05520 ARCHITECTURAL ALUMINUM HANDRAILS AND RAILINGS
PART 1 GENERAL Sapa: SECTION 05520 ARCHITECTURAL ALUMINUM HANDRAILS AND RAILINGS 1.1 SECTION INCLUDES A. Aluminum and Glass Handrails B. Aluminum Railings 1.2 RELATED SECTIONS A. Section 05700 - Ornamental
More informationSeries MJC Multiple Jet Controls DN20, DN25, DN40, and DN50, 12 bar BSPT Inlet & Outlets Threads General Description.
Worldwide Contacts www.tyco-fire.com Series Multiple Jet Controls DN20, DN25, DN40, and DN50, 2 bar BSPT Inlet & Outlets Threads General Description The TYCO Series Multiple Jet Controls are control valves
More informationWATER SUPPLY AND DISTRIBUTION
CHAPTER 29 WATER SUPPLY AND DISTRIBUTION SECTION P2901 GENERAL P2901.1 Potable water required. Dwelling units shall be supplied with potable water in the amounts and pressures specified in this chapter.
More information