MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS
|
|
|
- Mavis McDonald
- 9 years ago
- Views:
Transcription
1 MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS Gary P. Guagliardi Director Sales & Marketing HindlePower, Inc. Easton, PA Introduction This paper explores the use of mobile DC power systems for three specific applications. Recovery from catastrophic battery and/or equipment failure. Performance and diagnostic tool for site battery/system maintenance and testing. DC System Redundancy for Site Loads Mobile DC Power System Description Overview Mobile DC Power Systems are typically engineered and equipped with battery chargers, batteries, AC/DC meters and controls including ancillary safety equipment in accordance with applicable IEEE Design and Installation Practices for Stationary Batteries and DC Systems as described in IEEE Std. 946 and IEEE Std Engineering mobile power system components with mechanical and electrical isolation capability allows the user to suspend system operation for safety and maintenance purposes. Depending on DC load requirements, provisions are made to offer systems in single or multiple DC output voltage configurations. For example, nominal 48VDC and 120VDC mobile power systems offer versatility to service substations operating on one or both dc voltages. The 48VDC supply may be accomplished via a dedicated 48V battery and charger or by means of a 120V to 48V DC to DC Converter. Please refer to Figure 1 depicting a typical mobile DC power system. Mobile power systems are often equipped with ac power generators to provide a dedicated input power source where commercial utility power may not be available. Generators provide input power for the entire system including battery chargers and other ac powered equipment used during black start, commissioning or in the event of a total ac station power failure. 18-1
2 Figure 1. Utility Substation 18-2
3 Primary Mobile DC Power System Component Description and Function Batteries: Acting as the heart of the entire system, batteries play a critical role as a back-up power source for lost or interrupted station power. They assume the function of the existing station battery for both transient (i.e. breaker trip and oil pump function in substations) as well as assuming constant equipment loads (i.e. switchgear and communications) in the event of an ac power outage leading to battery charger failure. Careful consideration should be given to the battery selection to ensure not only electrical performance but also to the mechanical/structural design to allow optimal handling and provide desired design life. Batteries used in these applications may be subjected to a degree of shock and vibration as well as temperature excursions, well beyond what is typically encountered in stationary applications, while the trailer system is in use. There are a multitude of battery chemistries and configurations available. However, two specific battery types, Valve- Regulated Lead Acid (VRLA) and Nickel-Cadmium (NiCad), offer several unique advantages. VRLA Batteries are well suited for mobile power system applications. They are typically more space efficient, easier to install, require less maintenance and are relatively lower in cost compared to most other battery types. Their internal construction consisting of a micro-porous fiber plate wrap offers a higher level of shock and vibration protection (versus standard VLA type batteries) while the trailer is in transit. However, VRLA battery design offers a few disadvantages. Their performance and life are more dramatically affected by changes in temperature than their wet-cell counterparts. Higher operating temperatures lead to potential adverse conditions such as cell dry-out where non-compensated charging results in excessive hydrogen evolution and loss of water. In addition, typical VRLA multi-cell mono-bloc type batteries, commonly found in these applications, may not offer desired cycle life leading to more frequent battery replacement. NiCad Batteries offer a rugged mechanical design where periods of shock and vibration are common during trailer transportation to and from the intended site. Also, NiCad Batteries experience minimal performance degradation in environments with potentially large differentials in ambient and/or operational temperatures often associated with these applications. This is particularly true where climatically controlled devices are inoperative or not available. Finally, NiCad Batteries are able to electrically recover back to their nameplate capacity and operational cell voltages after deep discharge or from depleted capacity due to extended periods on open circuit. The type of battery used in mobile applications should be carefully considered based on a number of criteria such as station duty profile, expected operating temperature conditions and desired design life. Wet vented lead-acid (VLA) batteries are not recommended for mobile applications. Although they offer many performance advantages versus VRLA design, they contain free liquid electrolyte that may spill or leak during times of transporting trailers to/from a site. Electrolyte contact could result in equipment and/or environmental damage. Both DOT and EPA regulations must be considered whenever batteries are employed as part of a DC system. See Battery Safety Equipment regarding the importance of battery spill containment. As mentioned earlier, the trailer may be exposed to a degree of shock and vibration while in transit. Therefore, a properly designed mechanical restraint system should prevent both horizontal and vertical battery movement. Flexible inter-cell cable connectors are recommended to minimize potential battery post connection stress and reduce the risk of post or seal damage. Battery Chargers: The battery charger functions as the primary DC power source for maintaining battery float voltage and providing current to continuous dc station loads. For trailer applications where VRLA batteries are used, it is highly recommended that chargers are equipped with an option allowing a temperature compensated charging algorithm. This feature allows the charger to automatically adjust its output voltage based on actual battery temperature. Temperature compensation helps ensure proper charge voltage and promotes intended battery life. Electrical Connections and Safety: Several factors should be considered regarding physical connections to the mobile system, as referenced in IEEE Std Essentially, this is an outdoor application. To ensure the integrity of both the AC and DC power connections, in accordance with applicable NEMA Standards, water-tight, twist-lock type connections are ideal to guard against short circuits and potential shock hazard due to ingress of moisture or wind-driven rain and snow. Both AC input and output DC circuit breakers protect the mobile system from electrical faults and provide a means of turning the system on or off. 18-3
4 AC Power Generator: Offer a dedicated AC power source, particularly in applications where input utility power is not available. Generators provide input power to a circuit breaker panel where it s distributed to the battery chargers and receptacles used for powering other ancillary equipment (i.e. battery monitoring devices, hydrogen sensors, interior lighting and/or HVAC), as required. Meters/Control/Annunciator Panels: It is crucial for the operator to be able to properly monitor the mobile DC system on both the ac and dc side of the application. Annunciator panels provide power diagnostics related to I/O voltage and current as well as alarms to identify any potential system faults. Pinpointing system faults allow corrective action to be taken quickly to eliminate potential harm to both the mobile power system or station equipment connected to it. The Annunciator panel design includes the use of weather-proof, twist-lock receptacles for making AC and DC power cable connections. These connectors help ensure proper contact and guard against moisture and wind-driven elements from interfering with electrical connections that could lead to system faults. As a further measure of electrical protection, input and output circuit breakers minimize the threat of potential short circuit or high in-rush currents originating from station equipment that could lead to equipment damage. Hydrogen Detection/Alarms and Mitigation: As with any power system, using stationary batteries as part of the circuit, good industry practices recommend the use of hydrogen detection equipment. These devices are designed to alert the operator of unacceptable levels of hydrogen evolution. Detectors equipped with alarm relay contacts provide a means of reducing hydrogen levels by initiating exhaust fans, forcing excess hydrogen from the point of origin. In conjunction with initiating fan operation relay contacts wired to the battery charger may be programmed to shut the charger down once a hydrogen threshold has been reached. Further assisting forced air ventilation, passive type roof vents provide a further degree of hydrogen mitigation. Electrical-Mechanical DC Protection: U.L. Listed DC Disconnect Switches offer a degree of flexibility by providing a variety of uses in mobile power systems. Primarily, DC Disconnects isolate the battery to conduct recommended maintenance, conduct battery testing procedures and cell replacement. These devices also provide a degree of protection from short circuit current interruption. Battery Safety Equipment: Maintaining a safe work environment, in accordance with applicable OSHA requirements, is just as critical in a mobile DC power system as it is in a control building or battery room where batteries are used and personnel are present. Easy access to industry accepted eye-wash stations and spill containment are important for applications where batteries contain free electrolyte. These systems include neutralization and proper disposal in accordance with local, state and federal DOT Regulations as well as applicable OSHA Standards and Practices for Stationary Batteries. Battery Monitoring and Load Testing: Understanding the health of the applied battery is essential to ensure it will perform as intended. Mobile power systems equipped with load bank and monitoring equipment allow operators to test the existing battery and assist in identifying potential performance and/or capacity issues. Mobile DC Power Connection to the Substation There are several methods for making physical AC and DC power connections from the mobile power system to the substation. AC power cables are sized in accordance with NEC practices and are calculated based on ampacity and distance to the substation connection point. Connection to the mobile power system is made via NEMA standard weather-proof, twist-lock, shore power type connectors. The station end of the cable is typically connected to the substation via one of three common user-specified connector styles including: Non-terminated connection where cable is bugged into the ac feed. Screw-type lug connectors Mueller Clamp connectors Color coded positive and negative polarity DC power cables are sized in accordance with user specifications. Connection to the mobile power system is made via weather proof, twist lock type connectors. DC cables should be rated for the maximum 18-4
5 station load, taking voltage drops into account. As with the AC power cables, the station end of the DC power cables connect via one of the three type user-specified connections styles listed above. Substation Power Docking Station: To facilitate a standard connection point to a number of sites, docking stations allow operators to connect in a consistent fashion and eliminate the need to provide a variety of connectors. The docking station is typically an externally mounted NEMA 3R rated enclosure with AC and DC power termination points pre-wired to the substation. Docking stations equipped with transfer switches or steering diode assemblies permit switching and isolation between substation power and mobile power for maintenance or black start applications. Communication to the docking station via SCADA alarm connection provides system diagnostic alarms and alerts users of potential system faults or performance issues. Application #1: Catastrophic/Disaster Recovery/Black Start During a catastrophic battery and/or equipment failure, mobile power systems should be engineered and designed for swift deployment to quickly restore site power and resume normal operation while site issue(s) are diagnosed and repaired. Disaster recovery time is greatly reduced by providing a system on demand. Application #2: Battery and DC System Maintenance As a maintenance tool, mobile power systems act as a temporary power source for conducting site maintenance and testing. As industry demands for greater reliability increase, mobile power systems offer a means to carry out critical procedures and verify the system potential performance in accordance with NERC standards and the operator s reliability plan. Mobile power systems equipped with load banks offer the ability to test substation battery performance and capacity. These tests may be performed off-line while maintaining power to the site. Measuring and recording battery performance through the use of battery monitoring equipment identifies potential battery issues that require immediate attention. Application #3: Redundancy Mobile DC power systems offer a level of redundancy required where interruption of critical loads and system operation cannot be compromised. Connecting these systems into the station circuit using a steering diode assembly allows the existing loads to select the DC power source with the highest potential in applications involving parallel battery plants. This application ensures site loads remain operational, minimizes risk and greatly increases system reliability. Summary Mobile DC Power Systems offer user flexibility as either a back-up or redundant power source. They also serve as invaluable tools to facilitate proper DC power station maintenance. However, for these mobile systems to work safely and effectively, sound engineering practices must be followed in their design and operation. In addition, proper maintenance and testing of the mobile dc power system should be conducted per IEEE Std. 450 and NERC PRC-005 requirements to assure design performance and reliability. References IEEE Std IEEE Recommended Practice for the Design of DC Auxiliary Power Systems for Generating Systems. IEEE Std IEEE Recommended Practice for Emergency and Standby Power Systems for Industrial and Commercial Applications. IEEE Std Guide for the Protection of Stationary Battery Systems. IEEE Std IEEE Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-Acid Batteries for Stationary Applications. NEMA Standards Publication PE 5. Utility Type Battery Chargers. 18-5
6 OSHA Standard NERC Standard PRC-005 (latest draft) 18-6
7 Figure 2. Typical Mobile DC Power System Internal Component Layout Drawing 18-7
8 Figure 3. Typical Mobile DC Power System Outline Drawing 18-8
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
WHOLESALE DIRECT INC. 5620 WEST 65TH STREET
Auto Pump V 200 100 0 100 Max Rating Vehicle mount compressor ensures truck air brake system is properly pressurized for immediate dispatch from station Pressure switch regulated operation automatically
Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation
Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation BATTERY CHARGING GUIDELINES FOR GLOBAL/DAVIDSON TUBULAR PLATE BATTERIES Introduction Your Global/Davidson
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively
THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.)
THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.) J. Allen Byrne Engineering, Training and Tech Support Manager Interstate PowerCare, a Division
Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options
Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options By Stephen McCluer White Paper #30 Revision 11 Executive Summary The lead-acid battery is the predominant choice for Uninterruptible
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
Paralleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
Mobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
Recommended Practice for Installation of Transit Vehicle Fire Protection Systems
Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Approved October 25, 2007 APTA Fire Safety Working Group Approved May 3, 2008 APTA Bus Safety Committee Approved October
DRAFT REGULATORY GUIDE DG-1154 (Proposed Revision 2 of Regulatory Guide 1.128, dated October 1978)
U.S. NUCLEAR REGULATORY COMMISSION October 2006 OFFICE OF NUCLEAR REGULATORY RESEARCH Division 1 DRAFT REGULATORY GUIDE Contact: W.S. Raughley (301) 415-7577 DRAFT REGULATORY GUIDE DG-1154 (Proposed Revision
Substation Battery & Charger Maintenance
Document title AUTHORIZED COPY Substation Battery & Charger Maintenance Document number MNT-TRMX-00015 Applies to: Keywords: Transmission Operations & Planning Department Carolinas and Florida maintenance;
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
Thyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
Auxiliary DC Control Power System Design for Substations
Auxiliary DC Control Power System Design for Substations Michael J. Thompson Schweitzer Engineering Laboratories, Inc. David Wilson McLaren, Inc. Presented at the 61st Annual Georgia Tech Protective Relaying
Charging what can be more simple? SAE J1772
Charging what can be more simple? SAE J1772 Charging What Can Be More Simple? We charge our electronic devices everyday Laptops Cell phones PDAs Bluetooth devices Power tools MP3 players Toys Other Why
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES
BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES Introduction Your 6-volt deep cycle battery set has been specially formulated for long cycle life and has particular voltage and specific gravity
Ammonia Detection System Codes and Design Specifications
Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
EKOS Cart. Instructions for Use
EKOS Cart Instructions for Use EKOS Corporation 11911 North Creek Parkway South Bothell, WA 98011 USA (425) 415-3100 (tel) (425) 415-3102 (fax) [email protected] (e-mail) - 1-4913-002 REV E Intended Use
RAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
Battery Technology for Data Centers and Network Rooms: Fire Safety Codes USA
Battery Technology for Data Centers and Network Rooms: Fire Safety Codes USA By Stephen McCluer White Paper #31 Revision 6 Executive Summary Fire safety regulations and their application to UPS battery
UPS Applications and VRLA Battery Sizing
TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the
Mixing Sodium and Lead Battery Technologies in Telecom Applications
Mixing Sodium and Lead Battery Technologies in Telecom Applications Paul Smith Shanon Kolasienski Technical Marketing Manager Application Engineer GE Critical Power GE Energy Storage Plano, TX 75074 Schenectady,
Executive Summary. Technical Description
Executive Summary The Cellwatch system is built using modules. The majority of the system is constructed with Data Collection Modules (DCMs). The DCMs are optically linked to Control Units (CUs) that in
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the
THERMAL MANAGEMENT SOLUTIONS
t2000 Series Electronic heat-tracing controller Product Overview /COMMUNICATIONS INTERACE CARRIER REQ TO SEND The DigiTrace heat trace controller is designed to provide the benefits associated with single
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only
Charge Regulator SCR 12 Marine
Charge Regulator SCR 12 Marine Manual Many thanks for purchasing a superwind product. The SCR 12 Marine is a charge regulator of highest quality and will perfectly and reliably charge your batteries for
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
INSTALLATION & SERVICE MANUAL. Display Panel
INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed
Utility Distribution Systems
Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date
INSPECTION AND TESTING OF EMERGENCY GENERATORS
INSPECTION AND TESTING OF EMERGENCY GENERATORS Certification requirements NFPA 101(00), Sec. 7.9.2.3 requires that emergency generators be installed, tested and maintained in accordance with NFPA 110,
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
LEAD ACID BATTERY working LIFETIME STUDY
LEAD ACID BATTERY working LIFETIME STUDY Valve Regulated Lead Acid (VRLA) Batteries Overview The most common type of battery used on UPS systems and for backup of telecommunications systems. VRLA batteries
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
Single Phase UPS Management, Maintenance, and Lifecycle
Single Phase UPS Management, Maintenance, and Lifecycle White Paper 210 Revision 0 by Justin Solis Executive summary How long will my battery last? and what is the best practice for maintaining my UPS?
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
3000W Power Inverter
3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE
If you accidentally get battery acid on your skin, flush it with lots of water
RV Battery Savvy To properly maintain and extend the life of your RV batteries you need to have a basic understanding of what a battery is and how it works. Batteries used in RVs are lead acid batteries.
Understanding Emergency Power Off (EPO)
Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
CITY OF LOS ANGELES CALIFORNIA
BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI
MANUAL D250S DUAL. Solar panel + Vehicle ground/solar panel
MANUAL CONGRATULATIONS on the purchase of your new CTEK professional battery management unit. This unit is part of a range of professional battery chargers from CTEK SWEDEN AB. It represents the latest
ABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where
PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where the power generated by the solar panel (panels) runs an
Re-defining the utility-scale inverter
Re-defining the utility-scale inverter We believe in green energy in the ability to meet and contribute to growing power demands while supporting a smart grid that serves a smart society. Solution at a
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS
Manual No. BLWR043 Rev. 4 September 2012 OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS CVF-8AC CVF-8AC50 CVF-6ACAN CVF-15ACAN CVF-25ACAN CVF-8A15KIT CVF-8A25KIT MODELS: CVF-8DC CVF-6DCAN CVF-15DCAN CVF-25DCAN
DTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
Air-cooled Generator Battery Charger Installation Guidelines
Air-cooled Generator Battery Charger Installation Guidelines Table of Contents Table of Contents...Inside Front Cover Section 1 General Information... IFC 1.1 Introduction...IFC 1.2 Battery Charger Compatibility...
875 Dearborn Drive Columbus, Ohio 43085 Tel: (614) 846-7500 Fax: (614) 885-3990
Selection and Sizing of Batteries for UPS Backup 875 Dearborn Drive Columbus, Ohio 43085 Tel: (614) 846-7500 Fax: (614) 885-3990 Selection and Sizing of Batteries for UPS Backup Abstract Introduction Battery
ST Series POWER SUPPLIES USER INSTRUCTIONS
Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional
Generator DoCKInG StatIonS
Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
Battery Discharge Testing: Implementing NERC Standards and Field Experiences
Battery Discharge Testing: Implementing NERC Standards and Field Experiences Dinesh Chhajer Applications Engineer Megger Dallas, TX 75237 Robert Foster Applications Engineer Abstract Periodic testing and
TROUBLESHOOTING GUIDE
TROUBLESHOOTING GUIDE LESTRONIC II BATTERY CHARGER FOR MOTIVE POWER BATTERIES PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS For correct operation of the equipment, it is important to read
SOLAR PV SYSTEM MAINTENANCE GUIDE
SOLAR PV SYSTEM MAINTENANCE GUIDE GUYANA HINTERLANDS STAND-ALONE SOLAR PV INSTALLATIONS IMPROVING HEALTH FACILITY INFRASTRUCTURE (IHFI) GUYANA CONTRACT NO. EPP-I-00-03-00008-00, TASK ORDER 07 APRIL 2013
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
POWER TO GET THE JOB DONE
52720 1.5 AMP SLOW 12 VOLT BATTERY CHARGER OWNER S MANUAL KEEPS BATTERIES FULLY CHARGED IN STORAGE Automatic over-charging protection Short circuit protection Reverse hook-up protection Overheat protection
High Efficiency Battery Charger using Power Components [1]
application note TPB:101 High Efficiency Battery Charger using Power Components [1] Marco Panizza Senior Applications Engineer July 2006 Contents Page Introduction 1 A Unique Converter 1 Control Scheme
SELECTION, APPLICATION AND MAINTENANCE
DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine
SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE
Series Circuit Breaker Monitors CONSOLIDATED Electronics, Inc. MONITORING THE FUTURE Why SF Gas Density Monitors? 6 Cut Maintenance Costs Your capital investment may be recovered with the elimination of
Magnum Mobile Generator MMG55 Specifications
Empowering Real People Magnum Mobile Generator MMG55 Specifications ENGINE John Deere PE5030TF270 - turbocharged, diesel engine o Prime - 72 hp @ 1800 rpm o Standby - 80 hp @ 1800 rpm o 4 cylinder o 3.0
10000HXL31/15000HXL31/20000HXL31
Table of Contents www.eaton.com/dxups USER MANUAL ON LINE UPS 10000HXL31/15000HXL31/20000HXL31 Uninterruptible Power Supply Table of Contents 1. Brief introduction 1.1 System and model description---------------------------------------------------------------------1
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
SD Series. SD Series Rectifiers. EPC Energy & Power Conversion
Rectifiers Microprocessor controlled rectifier technology Fully adjustable float, boost and equalizing charge modes with V/I characteristic Advanced technology for phase control Verylowvoltage ripple and
LESTRONIC DV AUTOMATIC 12 OR 24 VOLT DUAL OUTPUT DUAL MODE BATTERY CHARGER MODEL 16350 TYPE 12/24EL40-10ET
LESTRONIC DV AUTOMATIC 12 OR 2 VOLT DUAL OUTPUT DUAL MODE BATTERY CHARGER MODEL 16350 TYPE 12/2EL0-10ET PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS For correct operation of the equipment,
The following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
OWNER S MANUAL. Model AE150/AE300/AE500 1.5AMP MULTI-USE SMART BATTERY CHARGER READ ENTIRE MANUAL BEFORE USING THIS PRODUCT
Model AE150/AE300/AE500 MULTI-USE SMART BATTERY CHARGER Certified by Californiia BCS Regulations AE300E AE500E 5AMP MULTI-USE AUTOMOTIVE BATTERY CHARGER 3AMP MULTI-USE SMART BATTERY CHARGER AE500E 5AMP
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
2. Add the following definitions to 3.3 General Definitions and renumber 3.3 as required:
NFPA 72-2013 National Fire Alarm and Signaling Code TIA Log No. 1188 Reference: Various Sections on Battery Comment Closing Date: June 19, 2015 Submitter: Herbert Hurst, Savannah River Nuclear Solutions,
www.ringautomotive.co.uk Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A
SmartChargePro7 RSCPR7-12v, 7A SmartChargePro10 RSCPR10-12v, 10A SmartChargePro15 RSCPR15-12v, 15A SmartChargePro25 RSCPR25-12v, 2 / 6 / 12 / 25A SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A SmartChargePro50
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems A. General This Net Metering Standard for Customer-Owned Grid Connected Electric Generating Systems sets forth the
PHOTOVOLTAIC SYSTEM CONTROLLERS SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V
PHOTOVOLTAIC SYSTEM CONTROLLERS OPERATOR S MANUAL SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V 6A / 12V 10A / 12V 10A / 24V 20A / 12V 20A
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Switch Mode, Automatic, Lead Acid Battery Charger 3 Stage (IUoU)
AUTOMATIC BATTERY CHARGER Switch Mode, Automatic, Lead Acid Battery Charger 3 Stage (IUoU) Model No. SEC - 1260A SEC - 1280A SEC - 2440A Item No. 08021 08061 08077 OWNER S MANUAL Please read this manual
8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
Remote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
Screen 3.5" Color Touch 4.3" Color Touch Keypad or Function Keys Programming Com Port, Built-in
Samba PLC+HMI SM35-J-RA22 SM43-J-RA22 Installation Guide 12 Digital Inputs, including 1 HSC/Shaft-encoder Inputs, 2 Analog Inputs, 2 PT100/TC inputs 8 Relay Outputs 2 Analog Outputs General Description
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Specification Requirements DBL 700MX and 1000MX Series UPS
Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
Battery Handbook. By: RON SMITH
Battery Handbook By: RON SMITH Information compiled from the Battery Charger Handbook and the Battery Handbook written by Alvin G. Graham, Chief Engineer, Ratelco Electronics Inc. Introduction The purpose
Using Industrial Ethernet Switches to Assure Maximum Uptime White Paper
Six Best Practices for Effective Wind Farm Operation Using Industrial Ethernet Switches to Assure Maximum Uptime White Paper Six Best Practices for Effective Wind Farm Operation Using Industrial Ethernet
DC400 Dispensing Cutoff System
DC400 Dispensing Cutoff System DC404 and DC406 Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com