1 Installation instruction CTS 602 by Nilan VPL 28 Version: 10.00, Software-version: 2.30

2 Table of contents Table of contents... 2 Figure table... 2 Introduction... 3 Power supply... 4 Assembly of VPL... 5 Condensation drain / water seal... 6 Ducting... 7 Heating surface, water... 8 Electrical heating element (retrofitting) Starting and set up of the CTS 602 control Activating the service menu Heating surface Air quality Air exchange Defrost Temp. control Inlet control Room control Restart Preset Manual Modbus Datalog Assambling System dimension Accessories / spare parts Figure table Figure 1: CTS 602 control... 4 Figure 2: Mounting the VPL-Unit... 5 Figure 3: Condensation drain / water seal... 6 Figure 4: Insulation of ducting... 7 Figure 5: Connecting the heating surface, suggestion... 8 Figure 6: Headlines in the servicemenu Figure 7: The "Heating surface" menu Figure 8: The "Air quality" Menu Figure 9: The "Air exchange" menu Figure 10: The "Defrost" menu Figure 11: The "Temp. control" menu Figure 12: The "Inlet control" menu Figure 13: The "Room control" menu Figure 14: The "Restart" menu Figure 15: The "Preset" menu Figure 16: The "Manual" menu Figure 17: The "Modbus" Menu Figure 18: The "Datalog" Menu Figure 19: System dimension... 25

3 Introduction Please control that the following documents have been delivered together with the unit: - Directions for assembly & use (this document) - CTS 602 directions - Electrical chart Should you have any questions on how to operate the system, contact your nearest Nilan dealer, who you can find at The unit can be equipped with different accessories e.g. hygrostat and filter box with pollen filter. Operating the unit is done with the CTS 602 control. The control has many functions such as menu based attendance, week programme, time controlled filter guard and adjustment of the velocity of the ventilator. (Directions for the CTS 602 control is described in another document delivered with the unit.) This document may be subject to change Side 3 of 26

4 Power supply Power supply including safety switch must be installed by an authorized electrician. The unit must be connected according to the attached electrical chart. The unit is delivered with 1m test cable for the CTS 602 panel. The panel should be connected to the CTS 602 control in the unit with cable type 2x2x0.25mm 2 twisted in pairs. (Maximum length 50m). The CTS 602 panel must be placed dry and frost-proof. The panels integrated feeler prevents further cooling of the building if the primary heat-supply stops by stopping the ventilation if the panel feeler gets below a specific value. (Factory setting is 10 C; the value can be set from 1 C to 20 C.) Figure 1: CTS 602 control If a water post-heating element is installed, the control valve and circulation pump must be electronically connected as described in the provided wiring diagrams. This document may be subject to change Side 4 of 26

5 Assembly of VPL When mounting the VPL-unit future service and maintenance should be considered. There is required a minimum of open space in front and behind the unit of 600mm. The system s connection pieces and the pipes are connected with a flexible transition (flex pipes/sound flex pipes or the like). The system must be level due to the condense outlet. The condense outlet requires a clearance height of minimum mm under the outlet connection piece. It is not necessary to re-insulate the system as it is delivered with a 20mm standard insulation. The system is low-noise and low-vibration. However, potential vibrations spreading from the system to the individual building parts must be taken into account. We recommend a minimum distance of 30 mm from building parts and other fixtures. To detach the system from the floor, we recommend that the system is placed on vibration absorbers as illustrated in figure 2 (See Accessories) Inlet Fresh air Exhaust Outlet : Vibration absorbers. 2: 22mm plywood/ chip board 3: Firm insulating batts 4: Wooden beam Figure 2: Mounting the VPL-Unit This document may be subject to change Side 5 of 26

6 Condensation drain / water seal The VPL unit is delivered with a 20mm condensation drain. (PVC, GF-fittings). The drain is placed under the discharge. The condensation drain should be carried with an even inclination of at least 1 cm per meter, frost-proof to the nearest outlet. The overflow from the safety valve should also be carried to the nearest outlet. To avoid frost problems it can be necessary to supply the condensation drain with a heating cable. It is the plumbers responsibility to secure the drain. When the system is running, there can be a vacuum of up to 500Pa (corresponding to 50mm water column) in the outlet. For this reason, the difference in height in the water seal must be minimum 50mm. This means that the first bend of the water seal must be at least twice as long in order for the system to be able to dispose of the condense water (see figure 3). The condensation drain must be airproof from the unit to the water seal in order for the condensation water to be let away from the unit. If the condensation drain is not airproof false air will be sucked in to the unit and the water will stay inside the unit. The water seal can dry out and avoid the water from running out of the unit. Therefore the water seal should be tested regularly and refilled with water if necessary. An elevated height of the water seal will reduce the need for refilling with water. Ø20 mm drain min. 50 mm. VPL min. 50 mm. min. 112,5 mm Figure 3: Condensation drain / water seal The water seal should be tested as described below. (the unit must be connected to the ducting and the front door should be closed): The condensation tray is filled with water and the unit is started at the highest ventilation step. The unit should run for a couple of minutes. Check that the condensation tray is empty when the test is finished. This document may be subject to change Side 6 of 26

7 Ducting We recommend that there are used ducts and fittings with rubber packing that meet sealing class B and that the connections between the unit and the ducting are made with 1 metre sound absorbing flexible transitions as regards sound reduction. The ducts should be shortened with a hacksaw or an angle grinder and laid out according to the working drawing. The ducts are typically laid out on the main beam of the truss frame and are secured with hole belts or they are being hanged in assembly belts. Please avoid any unnecessary area reductions and breaks of the ducting. The ducts should be insulated in some cases with the ordinary attic-insulation. All ducts should be insulated with 100mm mineral wool to avoid heat loss and condensation. This also applies for flexible transitions. It is recommended that the insulation is carried out with 2 layers of 50mm. If the ducts are laid out in an unheated room it will cause condensation problems if the unit are turned off for a longer period of time as the hot air from the heated room will rise to the ducts and cause condensation which can cause damp problems. Loft insulationmaterial Duct Granulate Figure 4: Insulation of ducting The discharge duct is leading the exhaust air away either above the roof or through the outer wall. It is important that the roof cowl has at least the same open space as the duct leading to the roof cowl. A reduction at this place will cause an unnecessary pressure drop which can lead to a reduced ventilation output. The holes for the inlet- and exhaust valves should be cut according to the mounting-frame for the prescribed valve. The frame for the valve must be secured with screws before placing the valve in the frame. The valves are placed in accordance with the size, construction and use of the room. As an example we would not recommend placing an inlet valve just above people with sedentary work because the inlet air in some cases would be experienced as a draught. This document may be subject to change Side 7 of 26

8 Heating surface, water Connecting the heating surface must be done by an authorized plumber. If the unit is placed outside or in a cold location the installation must frost secured. Supplementary heating surface should be installed in supply air duct after the VPL. The heating unit is delivered as accessory and consists of: Heating surface with temperature sensor T9 and frost-protection B3, actuator and regulating valve. An options print has to be mounted. The heating surface is to be installed in the inlet ducting just after the VPL unit. The heating surface must also be activated in the CTS 602 control as described on page 12. The mixing loop can be constructed as suggested below. The heating surface should be connected, scavenged and checked for any leakages before starting the unit. The dirt-catcher should be checked and cleaned after a thoroughly flushing of the system. 3 1 M 2 Heating surface Flow Air flow T9 Return B3 Note that the temperature sensor T9 and frost-protection B3 is placed at the heated side of the heating surface close to the return connection. See electrical chart. 1: Actuator and regulating valve: Danfoss AME 140/24V 0-10V signal, 2-way valve VZ2 Kv 0,4, (Nilan delivery) Kvs-value must be checked in accordance with supply. Differential pressure: 0,1 0,6bar There is calculated with a cooling of 20 C over the heating surface at a flow of 60 C. 2: Scavenging (not Nilan delivery) 3: Dirt-catcher (not Nilan delivery) Figure 5: Connecting the heating surface, suggestion This document may be subject to change Side 8 of 26

9 IMPORTANT regarding Danfoss Actuator type AME 140: Re-installing the actuator must be done as described below: 1. Disconnect the power supply and remove the cover of the actuator. 2. Liberate the gear by pressing down the button as the spindle is turned up (counter clockwise) 3. Re-install the actuator and turn on power. 4. DIP-switch nr. 1 should be moved to ON and then to. 5. The actuator is automatically calibrating for up to 6 minutes. (The LED is flashing when calibrating and is lit constantly when finished). 6. Re-install the cover of the actuator. Permissible ambient temperature for Danfoss Actuator type AME 140/24 V is 0 C to 55 C. Actuators are IP42 and therefore not suitable for mounting in the open. See electrical chart. This document may be subject to change Side 9 of 26

10 Electrical heating element (retrofitting) Electrical heating surface should be installed in the ducting (Ø160/Ø200). When retrofitting an electrical heating surface it should be activated in the CTS 602 control panel. ( HEATING SURFACT) Power supply of the Electrical heating element must be installed by an authorized electrician. Heating surface, electrical (retrofitting) The heating surface should be installed in the injection duct. There should be a safety distance of minimum 150mm from the heating surface to any flammable materials. The heating surface must be insulated with a fire resistant material. However the electrical box may not be insulated. (Important: instructions from the manufacturer of the heating surface must be followed). Signal overheating Unit 230 V T7 Supply L 0,5 m The heating surface has a temperature regulator and a safety thermostat installed. Clamps 3 & 4 in CN6 should be short-circuited. When installing other types of heating surfaces be aware of security. The heating surface must equipped with a temperature regulator and a safety thermostat The heating surface must be activated in the CTS 602 control panel. T2 is annulled when the heating surface is activated in the CTS 602 control. See installation instructions for heating element and temperature control. HEATING ELEMENT must be enabled to work with the unit. TEMP. allows you to choose the controlling temperature sensor for the unit. After the option of an electrical heating element T7 is the air supply sensor. This document may be subject to change Side 10 of 26

11 Starting and set up of the CTS 602 control In this passage we will go through the service menu of the CTS 602 control. For daily use of the CTS 602 control please see the CTS 602 directions. (delivered together with the VPL). Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on Activating the service menu Press q and at the same time for 10 seconds. The service menu is now available. Press q multiple times until the panel shows SERVICE. Press to enter the service menu. It is now possible to move around in the menu by using pq. The headlines of the service menu are shown below: SERVICE HEATING SURFACE QUALITY EXCHANGE TEMP. RESET MODBUS ADR 30 DATALOG INTV 10 Figure 6: Headlines in the servicemenu This document may be subject to change Side 11 of 26

12 Heating surface The unit can be equipped with a heating surface. It is possible to retrofit a heating surface. The surface must be activated in the CTS 602 control in order to function together with the unit and for the frost-protection to be active. Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE SELECT WATERSUP SELECT WATERSUP Should be chosen when installing a heating surface for water Controlled via 0-10 V signal Delay between start of ventilators and heating surface (0 60 minutes) QUALITY EXCHANGE TEMP. KONTROL DELAY 2 MIN SELECT 0 10 V SELECT EB SUP SELECT EL SUP SELECT VALG 0/5/10 V VALG 0 10 V SELECT PERIOD Should be chosen when installing an electrical heating surface, binary controlled Should be chosen when installing an electrical heating surface, controlled via 0-10 V signal The setting is chosen for systems without heating element RESET MANUEL MODBUS ADR 30 DATALOG INTV 10 Figure 7: The "Heating surface" menu This document may be subject to change Side 12 of 26

13 Air quality In the Air quality menu it is possible to choose between 3 types of regulation: Humidity, Humidity + CO 2 or. On the CTS602 control panel, press: - ESC to return to the previous menu - qp to scroll upwards or downwards through the menus or to adjust the setting of an activated menu option - to activate a menu option - to confirm a menu option setting - switch off the controls - ON to switch on the controls FUNCTION HUM +CO 2 SERVICE HEATING SURFACE FUNCTION HUMIDITY QUALITY FUNCTION FUNCTION EXCHANGE TEMP. KONTROL RESET MANUEL MODBUS ADR 30 DATALOG INTV 10 Figure 8: The "Air quality" Menu This document may be subject to change Side 13 of 26

14 Air exchange In the Air exchange menu it is possible to adjust 4 steps of ventilation speed (air volume). Inlet and exhaust is to be adjusted individually at each level. The inlet speed can be adjusted to a minimum and the exhaust can be adjusted to both a maximum and a minimum. It is possible to delay the starting of the fan in order to give time to the register to open. Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE QUALITY EXCHANGE MIN 0 The value indicates the lowest permissible ventilation step of the inlet ventilator (0 2) The value indicates the lowest permissible ventilation step of the exhaust ventilator (1 2). TEMP. EXHAUST MIN 1 EXHAUST MAX 4 The value indicates the highest permissible ventilation step of the exhaust ventilation (3 4) >1< 35% >2< 50% >3< 75% >4< 100% Here it is possible to adjust each ventilation step in % of maximum ventilator output. EXHAUST >1< 35% MODBUS ADR 30 EXHAUST >2< 50% DATALOG INTV 10 EXHAUST >3< 75% EXHAUST >4< 100% DELAY 2 MIN Figure 9: The "Air exchange" menu This document may be subject to change Side 14 of 26

15 Defrost In the Defrost menu it is possible to chose how the unit should perform during defrosting of the evaporator in the exhaust. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE EXHANGE Low-level injection during defrosting EXHANGE. Custom injection during defrosting. EXCH. LOW EXCH. USER EXCH. USER TEMP. COMP MAX 10 MIN EXCH. Discontinued injection during defrosting MODBUS ADR 30 DATALOG INTV 10 Figure 10: The "Defrost" menu This document may be subject to change Side 15 of 26

16 Temp. control In the Temp. control menu it is possible to chose a room temperature where the unit stops in order to avoid further cooling of the building if the primary heating shuts down. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE QUALITY EXCHANGE Indicates which sensor that needs to be the controlling one. PANEL T15 (Panel Sensor) EXT: T10 (Duct sensor) EXHAUST: T3 (Exhaust) SENSOR EXHAUST SENSOR EXTERNAL TEMP. SENSOR PANEL SENSOR PANEL PRIORITY HP + EXT LOW 10 C PRIORITY HP + EXT PRIORITY HF HP+EXT:ventilation with heatpump and heating surface activ MODBUS ADR 30 PRIORITY The unit stops at this room temperature (1-20 C) - - means that the function is unactive. - - should be chosen if the panel is placed in a cold environment. : ventilation without heating surface HP: ventilation only with heatrecovery DATALOG INTV 10 Figure 11: The "Temp. control" menu This document may be subject to change Side 16 of 26

17 Inlet control In the Inlet control menu it is possible to adjust the period of time before restart of the compressor. The Inlet control menu should only be adjusted by persons with knowledge of control engineering. (To restore factory settings, see page 19) indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE QUALITY EXCHANGE TEMP. GAIN 7.0%/ INTEGRAL 120 s N-ZONE 2.0 C TMP-RAMP 0.10 /s PERIODE VERYFAST CAP-RAMP 0.5%/s PERIODE TAST MODBUS ADR 30 COND MAX 55 PERIODE NORMAL DATALOG INTV 10 PERIOD AUTO PERIODE AUTO Max. capacitor temperature can be adapted to the ventilation system: Cooling operation: If the high pressure switch falls out, the "Max 55 C" is lowered to for example 50 C. At reduced cooling performance due to the hot gas bypass the "Max 55 C " is raised to C. By high pressure failure the temperature is reduced. HEATPUMP RST 6m Min. time (in minutes) where the compressor must be stopped before restarting. Figure 12: The "Inlet control" menu This document may be subject to change Side 17 of 26

18 Room control In the Room control menu it is possible to adjust the regulator for controlling the room temperature. The Room control menu should only be adjusted by persons with knowledge of control engineering. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE QUALITY EXCHANGE The RESPONSE menu is only accessible when the CTS 600 control is set up to heating surface TEMP. RESPONSE USER RESPONSE USER RESPONSE FAST GAIN 6.0 / RESPONSE NORMAL RESPONSE NORMAL INTERGRAL 6m N-ZONE 0.5 C RESPONSE SLOW N-ZONE 0.5 C MODBUS ADR 30 DATALOG INTV 10 Rum control parametres: Response Gain Integral Slow Normal Fast User Figure 13: The "Room control" menu This document may be subject to change Side 18 of 26

19 Restart The Restart menu enables you to set the unit to automatically restart in connection with highpressure/low-pressure alarms. Fire alarms can be acknowledged automatically in connection with fire drills/testing. A condition for acknowledgement is that the fire thermostat input has returned to normal state. indicates that the menu point flashes and can be set to another value The setting HP/LP in the Restart menu may not be used under normal conditions. Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE QUALITY. EXCHANGE FIRE: Auto restart when fire input is back to normal TEMP. FIRE CONTIN. Continuous operation after another Critical Alarm HP/LP This setting must never be used during normal operation. Indicates that the system is to be restarted automatically in connection with high or low pressure alarms. MODBUS ADR 30 DATALOG INTV 10 Figure 14: The "Restart" menu This document may be subject to change Side 19 of 26

20 Preset indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING QUALITY EXCHANGE TEMP. The backup is restored. Subsequently, the system must be restarted. RESTORE The backup will be saved. BACKUP STANDARD When standard is chosen all factory settings are reset. An eventual supplementary heating surface must be re-activated. A heating surface is NOT frost-protected until it is correctly installed and activated in the service menu. MODBUS ADR 30 DATALOG INTV 10 Figure 15: The "Preset" menu This document may be subject to change Side 20 of 26

21 Manual In the Manual menu it is possible to test the functions of the unit manually. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE QUALITY EXCHANGE VENT+HEAT Manual test of ventilation & heat. TEMP. VENT+CPR Manual test of ventilation and compressor EXHAUST Manual test of exhaust Manual test of inlet FLAPS Manual test of flaps Manual test of the defrost function. Manual test de-activated normal working) MODBUS ADR 30 DATALOG INTV 10 Figure 16: The "Manual" menu This document may be subject to change Side 21 of 26

22 Modbus Options that flash are indicated by On the CTS602 control panel, press: - ESC to return to the previous menu - qp to scroll upwards or downwards through the menus or to adjust the setting of an activated menu option - to activate a menu option - to confirm a menu option setting - switch off the controls - ON to switch on the controls SERVICE HEATING SURFACE QUALITY EXCHANGE TEMP. MANUEL MODBUS ADD 30 Modbus Communication [1..247] DATALOG INTV 10 Figure 17: The "Modbus" Menu This document may be subject to change Side 22 of 26

23 Datalog The datalog interval is set via the menu SERVICE - DATALOG INTV at between 1 and 120 minutes. If 0 / is selected, logging is not periodical, but only on events and alarms. Temperatures are logged in Celsius, in whole degrees, in order to minimise the log file size. The status of digital inputs and outputs is combined in two shared log variables: Din and Dout. SERVICE HEATING QUALITY EXCHANGE TEMP. KONTROL MODBUS ADR 30 DATALOG INTV 10 Data increment [1..120] minutes Figure 18: The "Datalog" Menu This document may be subject to change Side 23 of 26

24 Assambling By assembling the T10/RH must be moved FU Unit T10/RH CV T10/RH Air Exhaust Important! When montaging the VPL28 with the FU28 the T10/RH has to be moved as it is shown on the sketch. It is important that the T10 and the RH is moved to the front of a potential Heat Pipe for the measurements to be correct, because the T10 is a primary sensor. This document may be subject to change Side 24 of 26

25 System dimension Figure 19: System dimension 1: Udeluft, Fresh Air, Aussenluft, Air neuf 2: Tilluft, Air Inlet, Zuluft, Air pulse 3: Fraluft, Air Exhaust, Abluft, Air repris 4: Afkastluft, Air Discharge, Fortluft, Air extrait 11: Kondensafløb, Evacuation condersats, Kondensatmuffe, Vacuation des condensats This document may be subject to change Side 25 of 26

26 Accessories / spare parts VPL 28 Filter types Designation Qty. Nilan item no. Duct filter Ø250mm Heating surface, water Unit Qty. Nilan item no. VPL Z Heating surface, electrical Unit Qty. Nilan item no. VPL Filter FU Unit Filterclass Designation Qty. Nilan item no. FU28H G4 Pladefilter (1 sæt) Heating Cable for condensate drain (frost protection) Unit Designation Nilan item no. VPL 28 Heating Cable (specify length when ordering) 2172 Vibration Unit Designation Qty. Nilan item no. VPL 28 Sylomer (Green) FU28H Sylomer (Green) This document may be subject to change Side 26 of 26

Installation and maintenance instructions. Danfoss Vent

Installation and maintenance instructions. Danfoss Vent Installation and maintenance instructions Danfoss Vent 1 Unit design... 2 2 Project planning and installation instructions... 3 2.1 Ventilation...3 2.2 Piping installation....3 2.3 Condensation line...4

More information

User manual. 086U6297 Rev. 9 EN

User manual. 086U6297 Rev. 9 EN User manual Atria Atria Duo Atria Duo Optimum Atria Optimum Comfort Diplomat Diplomat Duo Diplomat Duo Optimum Diplomat Duo Optimum G2 Diplomat Optimum Diplomat Optimum G2 086U6297 Rev. 9 EN Thermia Värme

More information

PORTABLE AIR CONDITIONER

PORTABLE AIR CONDITIONER PORTABLE AIR CONDITIONER MAC 7500 Owner s Manual Air Conditioner Dehumidifier Oscillating Fan Please read this owner s manual carefully before operating the unit. POWERED BY 66126113.p65 17 INTRODUCTION

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

Technical data. Danfoss DHP-A

Technical data. Danfoss DHP-A Technical data Danfoss DHP-A An air heat pump which produces both heat and hot water Can operate efficiently down to -0 C Danfoss TWS tank gives plenty of hot water quickly and with low operating costs

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

User's Guide. CTS6000 WebControl

User's Guide. CTS6000 WebControl User's Guide CTS6000 WebControl Version 1.01, 29.06.2010 Contents Contents... 2 List of figures... 3 Introduction... 4 Introduction to CTS6000... 4 Reading instructions... 4 Quick startup... 5 Daily operation...

More information

ALL IN ONE. Heat Pump Water Heater

ALL IN ONE. Heat Pump Water Heater ALL IN ONE Heat Pump Water Heater INSTALLATION AND OPERATION INSTRUCTIONS Please read this user s manual carefully before operate the unit. www.airtradecentre.com CONTENTS A. IMPORTANT REMARKS ------------------------------------------------------------------------------------------------

More information

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/ CW-5000/ 5200 Contents Cautions ---------------------------------------------------------------- 3 Parts introduction --------------------------------------------------- 4 Installation ------------------------------------------------------------

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Laddomat 21-60 Charging unit

Laddomat 21-60 Charging unit Laddomat 21-60 Charging unit User and installation instructions NOTE! Diagrams in this brochure only describe connection principles. Each installation must be measured and carried out according to the

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

MP-4000 Alarm List (Software version 2.4.3 or later)

MP-4000 Alarm List (Software version 2.4.3 or later) Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.

More information

CE6500 Energy Recovery Ventilator

CE6500 Energy Recovery Ventilator ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge

More information

CADB and CADT-D / DI / DC Series

CADB and CADT-D / DI / DC Series HEAT RECOVERY UNITS CADB and CADT-D / DI / DC Series NEW The CADB, CADT heat recovery range consists of: - Self-supporting casing with extruded aluminium profile structure and beige plastic coated galvanised

More information

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents

More information

Instruction manual for Firstline FCS12000CH

Instruction manual for Firstline FCS12000CH Instruction manual for Firstline FCS12000CH Contents Introduction... 2 Safety Awareness... 3 Safety Awareness... 4 Name of Parts... 5 Name of Parts... 6 Remote Controller Preparation... 7 Operation of

More information

AZB 800. Vertical Flue Gas Ducting Ø60/100mm 7 719 001 884

AZB 800. Vertical Flue Gas Ducting Ø60/100mm 7 719 001 884 AZB 800 Vertical Flue Gas Ducting Ø60/100mm 7 719 001 884 Ø120 1310 Ø125 50 125 6 720 610 703-00.1O for Gas Condensing Boilers: OSW Contents Contents Safety instructions 2 Symbols 2 1 Use 3 1.1 General

More information

Description of functions

Description of functions Description of functions Laddomat 21 is designed to......allow the boiler to reach a high working temperature soon after firing....to preheat the cold tank water in the bottom of the boiler so that the

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6 TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL

More information

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 Technical Specifications Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 For chiller storage of all sorts of items Chiller storage temperature: 2-5 C Provides excellent thermal efficiency

More information

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS Céliera Corporation. All rights reserved. Unauthorized duplication, reproduction prohibited. CONTENTS SAFETY PRECAUTIONS...

More information

SWIMMING POOL HEAT PUMP Owners Manual

SWIMMING POOL HEAT PUMP Owners Manual SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information

User manual. Atec. 086L0130 Rev. 1 EN

User manual. Atec. 086L0130 Rev. 1 EN User manual Atec 086L0130 Rev. 1 EN Thermia Värme AB reserves the right to make changes to components and specifications without prior notice. 2010 Thermia Värme AB. The Swedish language is used for the

More information

Cooking at the Speed of light!

Cooking at the Speed of light! Cooking at the Infrared Cooking & Colouring Infrabaker is a modular infrared continuous cooking system developed by Infrabaker International. The machine is designed to cook and/or put colour on a wide

More information

Domestic heat pumps. DHP-A Opti DHP-C Opti DHP-C Opti W/W DHP-H DHP-H Opti DHP-H Opti Pro/Opti Pro + DHP-L DHP-L Opti DHP-L Opti Pro/Opti Pro +

Domestic heat pumps. DHP-A Opti DHP-C Opti DHP-C Opti W/W DHP-H DHP-H Opti DHP-H Opti Pro/Opti Pro + DHP-L DHP-L Opti DHP-L Opti Pro/Opti Pro + MAKING MODERN LIVING POSSIBLE User Guide DHP-A Opti DHP-C Opti DHP-C Opti W/W DHP-H DHP-H Opti DHP-H Opti Pro/Opti Pro + DHP-L DHP-L Opti DHP-L Opti Pro/Opti Pro + www.heating.danfoss.com The English language

More information

Heat Pump Water Heater IOM Manual

Heat Pump Water Heater IOM Manual Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump

More information

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 THANK YOU FOR CHOOSING YOUR NEW DEHUMIDIFIER. BEFORE USING THE UNIT READ THESE INSTRUCTIONS FULLY AND RETAIN THEM FOR FUTURE REFERENCE

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS 2 This water heater must be installed (water and electrical installation), commissioned and serviced

More information

ACW200C / ACW200CH. Innovative AutoDrain Technology. Owner s Manual Portable Air Conditioner with Heat

ACW200C / ACW200CH. Innovative AutoDrain Technology. Owner s Manual Portable Air Conditioner with Heat Owner s Manual Portable Air Conditioner with Heat ACW200C / ACW200CH It is important that you read these instructions before using your new purchase and we strongly recommend that you keep them in a safe

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

PORTABLE AIR CONDITIONER

PORTABLE AIR CONDITIONER VERY IMPORTANT! MODEL: GDC-AC9RW / GDC-AC9RCS GDC-AC9RCW / GDC-AC12RW GDC-AC12RB / GDC-AC12RCB GDC-AC12RCW INSTRUCTIONS FOR USE PORTABLE AIR CONDITIONER Do not install and use your portable air conditioner

More information

Vertical Display and Storage B1350-2. SKOPE Gen2: Three Door Chiller

Vertical Display and Storage B1350-2. SKOPE Gen2: Three Door Chiller Vertical Display and Storage User Manual MAN1227 Rev. 3.0 March 2008 edition CONTACT ADDRESSES Designed and Manufactured by New Zealand SKOPE INDUSTRIES LIMITED PO Box 1091, Christchurch New Zealand Freephone:

More information

1 DESCRIPTION OF THE APPLIANCE

1 DESCRIPTION OF THE APPLIANCE 1 DESCRIPTION OF THE APPLIANCE 1.1 INTRODUCTION The cast iron SF boilers are a valid solution for the present energetic problems, since they can run with solid fuels: wood and coal. These series of boilers

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

Dehumidifier D 850E. - Instruction manual version 02

Dehumidifier D 850E. - Instruction manual version 02 Dehumidifier D 850E - Instruction manual version 02 Content 1. Description of dehumidifier 1.1. General data 1.2. Technical data 2. Operation and usage 2.1. Usage 2.2. Location and installation 2.3. Preparing

More information

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description Description Compact air/water heat pump for outside installation. With suction gas cooled rotary compressor. With extensive aluminium/cu lamellar tube evaporator and PVC Titanium condenser. Axial fan Refrigerant

More information

SWIMMING POOL HEAT PUMP

SWIMMING POOL HEAT PUMP SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical

More information

ECL Comfort 110 Application 130. Weather compensated flow temperature control of heating and boiler systems. Instructions

ECL Comfort 110 Application 130. Weather compensated flow temperature control of heating and boiler systems. Instructions Instructions *087R9781* *VIKTG202* Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

HEATER, AIR CONDITIONING AND VENTILATION

HEATER, AIR CONDITIONING AND VENTILATION 55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-9 DUCT

More information

ELECTRIC CENTRAL HEATING FLOW BOILER

ELECTRIC CENTRAL HEATING FLOW BOILER ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment

More information

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850

More information

COMPRESSED AIR DRYER

COMPRESSED AIR DRYER COMPRESSED AIR DRYER Model 40211 ASSEMBLY and OPERATING INSTRUCTIONS 3491 Mission Oaks Blvd., Camarillo, CA 93011 Visit our Web site at http://www.harborfreight.com Copyright 2002 by Harbor Freight Tools.

More information

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................

More information

Stove Guard Kit User Manual

Stove Guard Kit User Manual Stove Guard Kit User Manual Innohome improves the Safety of your Home. inno home www.innohome.com Stove Guard Kit User Manual Stove Guard Kit User Manual Congratulations! You now own one of the most intelligent

More information

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

For installation guide see reverse of book

For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL

DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL Service Information If service or parts are required, contact the nearest Norcold Service Center. To find an authorized Norcold Service Center

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries

More information

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

POLICY BULLETIN Tecumseh Compressor Company Compressor Group to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging

More information

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0 Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view

More information

Thermostatic valve Type AVTA

Thermostatic valve Type AVTA MAKING MODERN LIVING POSSIBLE Data sheet Thermostatic valve Type AVTA Thermostatic valves are used for proportional regulation of flow quantity, depending on the setting and the sensor temperature. The

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support

More information

01-3 0000-00 6810-20 AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS 2004.09

01-3 0000-00 6810-20 AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS 2004.09 0000-00 01-3 6810-20 1. FFH SPECIFICATION 01-4 0000-00 2. SYSTEM LAYOUT AND COMPONENTS 0000-00 01-5 01-6 0000-00 3. FFH GENERAL INFORMATION The system is to increase the coolant temperature quickly by

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

CHAPTER 11 HEATING, VENTILATION AND AIR CONDITIONING. Section Title Page

CHAPTER 11 HEATING, VENTILATION AND AIR CONDITIONING. Section Title Page CHAPTER 11 HEATING, VENTILATION AND AIR CONDITIONING Section Title Page 11.000 Heating and Ventilation............................... 11.1 11.001 Introduction................................... 11.1 11.002

More information

AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T

AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T Product Instruction Manual Accona AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T Panel heater v16.5/5 Version 3.2 Jan 2015 Contents 1. Important safety points 2. Installation 2.1. Wall mounting

More information

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3

More information

Installation Instructions

Installation Instructions GB-DAS Installation Instructions devireg 850 ground or roof systems (1-4 sensors) 1 Contents: 1. Installation instructions - ground systems................... 1.a. Placing the ground sensor(s)...........................

More information

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table

More information

Overheating limit control

Overheating limit control Pahlén electric heater Maxi Heat with digital control is a compact and effective heater for swimming pools. It consists of a glassfibre reinforced polypropylene tank containing resistance-type heating

More information

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES

More information

Air conditioning unit Saphir vario. 2. Product information for the new Truma air conditioning unit. Comfort on the move

Air conditioning unit Saphir vario. 2. Product information for the new Truma air conditioning unit. Comfort on the move Air conditioning unit 2. Product information for the new Truma air conditioning unit October 2006 Edition Comfort on the move Air conditioning systems Manoeuvring systems Energy systems Heating systems

More information

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module 1. General Description 1 2. General Warnings 1 3. Interface 2 4. Temp Alarms Setting 3 5. Programming 3 6. Light Management 4 7. Installation and

More information

MAKING MODERN LIVING POSSIBLE. Thermostatic valve AVTA. Technical brochure

MAKING MODERN LIVING POSSIBLE. Thermostatic valve AVTA. Technical brochure MAKING MODERN LIVING POSSIBLE Thermostatic valve AVTA Technical brochure 2 IC.PD.500.A3.02-520B3728 Danfoss A/S 07-2009/ RA-MC/mr Contents Page Features............................................................................................4

More information

FOXAIR 60/50 ALL MODELS

FOXAIR 60/50 ALL MODELS FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,

More information

Hot Water. Heat pump water heaters. Residential and Commercial R410a

Hot Water. Heat pump water heaters. Residential and Commercial R410a Hot Water Heat pump water heaters Residential and Commercial R410a Heat pump technology Heat Pump Water Heating is a new idea using existing technology and is viewed as the latest generation of water heating

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS

CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS D E F Y I N G C O N V E N T I O N Congratulations on your new Corner Fridge Your new corner fridge may have different functions

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer

More information

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA USER S MANUAL FH052EAV1 FH070EAV1 E HNIKA PORTUGUÊS ENGLISH ESPAÑOL ITALIANO DEUTSCH FRANÇAIS System Air Conditioner (Cooling and Heating) E S F I P D G DB98-29263A(1) Safety Precautions Register your

More information

Data sheet ECC 12 and 22

Data sheet ECC 12 and 22 Application ECC is an electronic room temperature controller for water-based systems. ECC can control - fan-coil units - inductions units - air conditioning systems - small ventilating systems - 2-pipe

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6. TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM

More information

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions. B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary

More information

Baxi Combi 80e & 105e

Baxi Combi 80e & 105e Baxi Combi 8e & 15e Please keep these instructions safe. Should you move house, please hand them over to the next occupier. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Natural

More information

RS Stock No. 724-4207 Instruction Manual RS-1340 Hot Wire Anemometer

RS Stock No. 724-4207 Instruction Manual RS-1340 Hot Wire Anemometer RS Stock No. 724-4207 Instruction Manual RS-1340 Hot Wire Anemometer EN FR IT DE ES CONTENTS / EN Title CONTENTS Page 1. SAFETY INFORMATION...1 2. INTRODUCTION...2 3. SPECIFICATIONS...3 4. PARTS & CONTROLS...4

More information

Energy Efficiency HOSPITALITY. www.energia.ie

Energy Efficiency HOSPITALITY. www.energia.ie Energy Efficiency HOSPITALITY www.energia.ie Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could make a real

More information

Condensing unit type EPSILON-ECHOS LE Technical information manual

Condensing unit type EPSILON-ECHOS LE Technical information manual Condensing unit type EPSILON-ECHOS LE Technical information manual 2 > EPSILON ECHOS Water chiller > EPSILON ECHOS /HP Reversible heat pump > EPSILON ECHOS /ST Water chiller with storage tank and pumps

More information

USER S MANUAL. Duct Type Series. Free Joint Multi Air Conditioner (Cooling and Heating) FUEA Series E S F I P D G DB98-29565A(1) ENGLISH ESPAÑOL

USER S MANUAL. Duct Type Series. Free Joint Multi Air Conditioner (Cooling and Heating) FUEA Series E S F I P D G DB98-29565A(1) ENGLISH ESPAÑOL USER S MANUAL Duct Type Series MH MH FEEA Series FUEA Series ENGLISH ESPAÑOL PORTUGUÊS E HNIKA DEUTSCH ITALIANO FRANÇAIS Free Joint Multi Air Conditioner (Cooling and Heating) E S F I P D G DB98-29565A(1)

More information

PANASONIC TROUBLE SHOOTING GUIDE

PANASONIC TROUBLE SHOOTING GUIDE A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459 SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work

More information

Baxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler

Baxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Baxi Combi Instant 8e & 15e Gas Fired Wall Mounted Combination Boiler Please keep these instructions safe. Should you move house, please hand them over to the next occupier.

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477

More information

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE

More information

ESTIMATING PLUMBING, HEATING, VENTILATING, AND AIR CONDITIONING (HVAC), AND ELECTRICAL WORK

ESTIMATING PLUMBING, HEATING, VENTILATING, AND AIR CONDITIONING (HVAC), AND ELECTRICAL WORK C H A P T E R 7 ESTIMATING PLUMBING, HEATING, VENTILATING, AND AIR CONDITIONING (HVAC), AND ELECTRICAL WORK OBJECTIVES After reading this chapter and completing the review questions, you should be able

More information

HDA -----------------------------------------------------------

HDA ----------------------------------------------------------- ----------------------------------------------------------- Lightstrips ---------------------------------------------------------------------- Ceiling system for heating and cooling LIGHTSTRIPS LIGHTSTRIPS

More information

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series SWIMMING POOL AIR-HANDLING UNITS KU-DB Series ME20 proklima 2 SWIMMING POOL AIR-HANDLING UNITS - KU-DB Series proklima 3 TABLE OF CONTENTS 1 Introduction page 3 2 Features page 4 SWIMMING POOL AREA t =

More information

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section

More information