SERVICE MANUAL MXZ-2A20NA MXZ-2A20NA - MXZ-3A30NA MXZ-3A30NA - MXZ-4A36NA OUTDOOR UNIT. No. OB444. Models HFC. Inverter-controlled multi system type

Size: px
Start display at page:

Download "SERVICE MANUAL MXZ-2A20NA MXZ-2A20NA - MXZ-3A30NA MXZ-3A30NA - MXZ-4A36NA OUTDOOR UNIT. No. OB444. Models HFC. Inverter-controlled multi system type"

Transcription

1 Revision C: MXZ-4A36NA have been added. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Please void OB444 REVISED EDITION-B. OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A No. OB444 REVISED EDITION-C Inverter-controlled multi system type Models MXZ-A0NA MXZ-A0NA - MXZ-3A30NA MXZ-3A30NA - MXZ-4A36NA Indoor unit service manual MSZ-A NA Series (OB450) CONTENTS MXZ-A0NA MXZ-A0NA -. TECHNICAL CHANES. PART NAMES AND FUNCTIONS 6 3. INDOOR UNIT OPERATIONAL CHARACTERISTICS 7 4. SPECIFICATION 8 5. OUTLINES AND DIMENSIONS 6. WIRIN DIARAM 5 7. REFRIERANT SYSTEM DIARAM DATA ACTUATOR CONTROL 5 0. SERVICE FUNCTIONS 5. TROUBLESHOOTIN 54. DISASSEMBLY INSTRUCTIONS 7 3. PARTS LIST RoHS PARTS LIST OPTIONAL PARTS 00 NOTE: This service manual describes technical data of the outdoor units. RoHS compliant products have <> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List The Slim Line. From Mitsubishi Electric. TM

2 Revision A: RoHS PARTS LIST has been added. Revision B: MXZ-A0NA - and MXZ-3A30NA - have been added. Revision C: MXZ-4A36NA has been added. MXZ-A0NA New model TECHNICAL CHANES MXZ-30TN MXZ-3A30NA. Combinations of connectable indoor units have been increased.. Capacity class of connectable indoor units have been made larger. 3. Compressor has been changed. (THV47FBA TNB0FMCH) 4. Outdoor fan motor has been changed. (RA6N60-AA RC0J60-AB) 5. Refrigerant has been changed. (R R40A) 6. Refrigerant system diagram has been changed. of high pressure switch has been removed. Accumulator has been removed. Receiver has been added. 7. Communication system has been changed. 8. Power supply way has been changed(change to supply to outdoor unit). 9. Evaporation temperature thermistor has been added. 0. Ambient temperature thermistor has been added. MXZ-A0NA MXZ-A0NA -. Compressor has been changed. (SNB30FPDH SNB30FQBH). as pipe temperature thermistor has been removed. 3. Pre-heat control has been added. 4. Electronic control P.C. board has been changed. 5. Power board has been changed. MXZ-3A30NA MXZ-3A30NA -. Ball valve has been changed to stop valve.. as pipe temperature thermistor has been removed. 3. Pre-heat control has been added. 4. Auto line correcting function has been added. 5. Noise filter P.C. board has been changed. 6. Electronic control P.C. board has been changed. 7. Weight has been changed. (58lb. 48lb.) MXZ-4A36NA New model

3 INFORMATION FOR THE AIR CONDITIONER WITH R40A REFRIERANT This room air conditioner adopts HFC refrigerant (R40A) which never destroys the ozone layer. Pay particular attention to the following points, though the basic installation procedure is same as that for R air conditioners. As R40A has working pressure approximate.6 times as high as that of R, some special tools and piping parts/ materials are required. Refer to the table below. Take sufficient care not to allow water and other contaminations to enter the R40A refrigerant during storage and installation, since it is more susceptible to contaminations than R. 3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R40A. (Refer to. Refrigerant piping.) 4 Composition change may occur in R40A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent composition change. New refrigerant Refrigerant R40A Composition (Ratio) HFC-3: HFC-5 (50%:50%) Refrigerant handling Pseudo-azeotropic refrigerant Chlorine Not included Safety group (ASHRAE) A/A Molecular weight 7.6 Boiling point (-F) Steam pressure [77-F](PSI) 5.8 Saturated steam density [77-F](lb/ft 3 ) Combustibility Non combustible ODP w 0 WP w 730 Refrigerant charge method From liquid phase in cylinder Additional charge on leakage Possible Kind Incompatible oil Color Non Smell Non w :Ozone Depletion Potential : based on CFC- w :lobal Warming Potential : based on CO Refrigeration Refrigerant oil Previous refrigerant R R (00%) Single refrigerant Included A Non combustible as phase Possible Compatible oil Light yellow Non 3

4 Compressor New Specification Current Specification The incompatible refrigeration oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the Since refrigerant and refrigeration oil are compatible, refrigeration oil goes back to the compressor through the lower position oil back hole. refrigeration oil of the upper layer to flow back to the compressor. Suction muffler Suction muffler Compressor Oil back hole Refrigeration oil Compressor Oil back hole Refrigerant Refrigeration oil /Refrigerant Conversion chart of refrigerant temperature and pressure (PSI) 580 Saturated liquid pressure R40A R.Tools dedicated for the air conditioner with R40A refrigerant The following tools are required for R40A refrigerant. Some R tools can be substituted for R40A tools. R40A tools auge manifold Charge hose as leak detector Torque wrench Flare tool Flare gauge Vacuum pump adapter Electronic scale for refrigerant charging No : Not Substitutable for R40A Can R tools be used? No No No Yes No Yes New New New (-F) Description R40A has high pressures beyond the measurement range of existing gauges. Hose material has been changed to improve the pressure resistance. Dedicated for HFC refrigerant. /4in. and 3/8in. /in. and 5/8in. Clamp bar hole has been enlarged to reinforce the spring strength in the tool. Provided for flaring work (to be used with R flare tool). Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps. It is difficult to measure R40A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization. Yes : Substitutable for R40A 4

5 .Refrigerant piping Specifications Use the copper or copper-alloy seamless pipes for refrigerant that meet the following specifications. Outside diameter (inch) /4 3/8 / 5/8 Wall thickness (inch) Insulation material Heat resisting foam plastic Specific gravity Thickness 0.35 inch Flaring work and flare nut Flaring work for R40A pipe differs from that for R pipe. For details of flaring work, refer to installation manual FLARIN WORK. Pipe diameter (inch) /4 3/8 / 5/8 Dimension of flare nut (mm) [inch] R40A R 7 [/6] 7 [/6] [7/8] [7/8] 6 [-/3] 4 [5/6] 9 [-5/3] 7 [-/6] 3.Refrigeration oil Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces. 4.Air purge Do not discharge the refrigerant into the atmosphere. Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant circuit. Use the vacuum pump for air purging for the purpose of environmental protection. 5.Additional charge For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigeration cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly. Indoor unit Refrigerant gas cylinder operating valve Union Liquid pipe as pipe Service port Stop valve Outdoor unit auge manifold valve (for R40A) Charge hose (for R40A) Refrigerant gas cylinder for R40A with siphon Refrigerant (liquid) Electronic scale for refrigerant charging 5

6 Air inlet (Back and side) Air outlet Drain outlet MXZ-3A30NA Air inlet (Back and side) Air outlet MXZ-3A30NA - Drain outlet MXZ-4A36NA Air inlet (Back and side) Air outlet Drain outlet 6

7 3 INDOOR UNIT OPERATIONAL CHARACTERISTICS The following charts show indoor unit performance when operating individually or in combination. For authorized system configurations of the indoor units, please refer to the Mr. Slim brochure. MXZ-A0NA MXZ-A0NA - Indoor units Cooling capacity (BTU/h) combination Unit A Unit B Total 09 (5,400 ~ ),000,000 (5,400 ~,000) 5, ,000 (5,400 ~ 5,000) 8, ,500 7,500 0,000,500,500 0,000 (7,800 ~ 8,000) 0,000 (7,800 ~ 0,000) 0,000 (7,800 ~ 0,000) 0,000 (7,800 ~ 0,000) Power consumption (W) 730 (490 ~ 730) 990 ( 490 ~ 990),540 (490 ~,540),740 (630 ~,740),50 (630 ~,50),50 (630 ~,50),50 (630 ~,50) Current (A) 08V 30V Power factor (%) Indoor units combination Unit A 0,900 3,600 8,000 0,900 9,500 8,50,000 Heating capacity (BTU/h) Unit B Total 0,900 (5,00 ~ 5,400) 3,600 (5,00 ~ 6,400) 8,000 (5,00 ~,00),800 0,900 (8,500 ~,800),000,500 (8,500 ~,000),000 3,750 (8,500 ~,000),000,000 (8,500 ~,000) Power consumption (W) 940 (480 ~,430),80 (480 ~,460),70 (480 ~,00),80 (50 ~,80),780 (50 ~,780),780 (50 ~,780),780 (50 ~,780) Current (A) 08V 30V Power factor (%)

8 MXZ-3A30NA MXZ-3A30NA - Indoor units Cooling capacity (BTU/h) combination Unit A Unit B Unit C Total 09 (7,00 ~ ), ,000 5,000 6,00,000 7,600,000,500 0,800 3,000,00 3,000 8,500 7,750 7,300,000 5,000 6,00 0,400,000 4,500 5,00 3,000 3,800 3,000 8,500 7,750 7,300,400,900 3,800 (7,00 ~,000) 5,000 (7,00 ~ 5,000) 6,00 (7,00 ~ 6,00),000 (7,00 ~,000) 8,000 (,000 ~ 8,000),000 (,000 ~,000) 4,000 (,000 ~ 4,000) 5,00 (,000 ~ 5,00) 8,000 (,000 ~ 8,000) 4,000 (,000 ~ 4,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 7,000 (,600 ~ 7,000) 8,400 (,600 ~ 8,400) 8,400 (,600 ~ 8,400) 8,400 (,600 ~ 8,400) Power consumption (W) 800 (650 ~ 800),000 (650 ~,000),30 (650 ~,30),480 (650 ~,480),0 (650 ~,00),800 (90 ~,800),000 (90 ~,000),500 (90 ~,500),700 (90 ~,700) 3,00 (90 ~ 3,00),500 (90 ~,500),800 (90 ~,800),800 (90 ~,800),800 (90 ~,800),800 (90 ~,800),800 (90 ~,800),860 (,000 ~,850) 3,50 (,000 ~ 3,50) 3,50 (,000 ~ 3,50) 3,50 (,000 ~ 3,50) Current (A) 08V 30V Power factor (%)

9 Indoor units Heating capacity (BTU/h) combination Unit A Unit B Unit C Total ,900 3,600 8,000 0,00 3,00 0,900 0,900 0,00 9,300 7,300 3,500,000,00 3,500,700 3,500 9,500 8,600 7,800 7,350 0,900 3,600 6,900 7,700 9,700 3,500 5,000 5,800 3,500 4,300 3,500 9,500 8,600 7,800 7,350 9,500,400 3,000 3,900 0,900 (8,600 ~ 5,400) 3,600 (8,600 ~ 6,400) 8,000 (8,600 ~,00) 0,00 (8,600 ~,500) 3,00 (8,600 ~ 7,800),800 (,000 ~ 3,000) 4,500 (,000 ~ 33,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 8,500 (,400 ~ 36,000) 8,600 (,400 ~ 36,000) 8,600 (,400 ~ 36,000) 8,600 (,400 ~ 36,000) Power consumption (W),00 (780 ~,50),380 (780 ~,600),940 (780 ~,80),40 (780 ~,300),50 (780 ~ 3,000),700 (740 ~,560),980 (740 ~,800),00 (740 ~,90),00 (740 ~,90),980 (740 ~,740),00 (740 ~,90),60 (740 ~,860),40 (740 ~,860),0 (740 ~,800),0 (740 ~,800),00 (740 ~,800),80 (740 ~,880),80 (740 ~,880),80 (740 ~,880),80 (740 ~,880) Current (A) 08V 30V Power factor (%)

10 MXZ-4A36NA 08V Indoor units Cooling capacity (BTU/h) combination Unit A Unit B Unit C Unit D Total 09 (7,00 ~ ),000,000 (7,00 ~,000) 5, ,000 (7,00 ~ 5,000) 6,00 7 6,00 (7,00 ~ 6,00), ,000 7,600,000,500 0,800 3,000,00 3,000 8,800 8,00 6,900 8,700,000 5,000 6,00 0,400,000 4,500 5,00 3,000 3,800 3,000 8,800 8,00 6,900,700,000 4,500 5,700 8,300,700 (7,00 ~,000) 8,000 (,000 ~ 8,000),000 (,000 ~,000) 4,000 (,000 ~ 4,000) 5,00 (,000 ~ 5,00) 8,000 (,000 ~ 8,000) 4,000 (,000 ~ 4,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 7,000 (,600 ~ 7,000) 30,000 (,600 ~ 30,000) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) Power consumption (W) 800 (650 ~ 800),000 (650 ~,000),30 (650 ~,30),480 (650 ~,480),00 (650 ~,00),800 (90 ~,800),000 (90 ~,000),500 (90 ~,500),700 (90 ~,700) 3,00 (90 ~ 3,00),500 (90 ~,500),800 (90 ~,800),800 (90 ~,800),800 (90 ~,800),800 (90 ~,800),800 (90 ~,800),860 (,000 ~,850) 3,70 (,000 ~ 3,70) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) Current (A) 08V Power factor (%)

11 Indoor units Cooling capacity (BTU/h) combination Unit A Unit B Unit C Unit D Total 3, ,000 0,700 3,400 (,600 ~ 3,00) 3, ,600 0,00 4,400 (,600 ~ 3,00) 3, ,500,300,300 (,600 ~ 3,00) 3, ,00,700 3,300 (,600 ~ 3,00) 3, ,700 0,700 9,900 9,400 9,00 8,300 7,700 7,700,700 0,700 9,900 9,400,500 8,300 7,700 7,700,700 0,700,300 3,300,500 8,300 7,700 0,300,00,900 0,300 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 36,000 (,600 ~ 36,400) 36,000 (,600 ~ 36,400) 36,000 (,600 ~ 36,400) 36,000 (,600 ~ 36,400) Power consumption (W) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,80 (,000 ~ 3,900) 3,80 (,000 ~ 3,900) 3,80 (,000 ~ 3,900) 3,80 (,000 ~ 3,900) Current (A) 08V Power factor (%)

12 Indoor units Heating capacity (BTU/h) combination Unit A Unit B Unit C Unit D Total ,900 3,600 8,000 0,00 3,00 0,900 0,900 0,00 9,300 7,300 3,500,000,00 3,500,700 3,500 0,800 0,000 8,900 8,400 7,800 9,400 8,300 0,900 3,600 6,900 7,700 9,700 3,500 5,000 5,800 3,500 4,300 3,500 0,800 0,000 8,900 8,400 7,800,500 0,400 0,800,400 4,600 5,600 6,800,500 3,700 0,900 (8,600 ~ 5,400) 3,600 (8,600 ~ 6,400) 8,000 (8,600 ~,00) 0,00 (8,600 ~,500) 3,00 (8,600 ~ 7,800),800 (,000 ~ 3,000) 4,500 (,000 ~ 33,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) Power consumption (W),00 (780 ~,50),380 (780 ~,600),940 (780 ~,80),40 (780 ~,300),50 (780 ~ 3,000),700 (740 ~,560),980 (740 ~,800),00 (740 ~,90),00 (740 ~,90),980 (740 ~,740),00 (740 ~,90),60 (740 ~,860),40 (740 ~,860),0 (740 ~,800),0 (740 ~,800),00 (740 ~,800),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880) Current (A) 08V Power factor (%)

13 Indoor units Heating capacity (BTU/h) combination Unit A Unit B Unit C Unit D Total ,900 7,600 7,00 7,000 0,800 9,700 9,300 8,300 7,700 7,700 9,900,400,900,700 0,800 9,700 9,300,700 8,300 7,700 7,700 4,600,400 3,300,700 0,800 3,000 3,800,700 8,300 7,700 0,300,00,900 0,300 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 36,000 (,400 ~ 4,00) 36,000 (,400 ~ 4,00) 36,000 (,400 ~ 4,00) 36,000 (,400 ~ 4,00) Power consumption (W),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880) 3,00 (740 ~ 4,000) 3,00 (740 ~ 4,000) 3,00 (740 ~ 4,000) 3,00 (740 ~ 4,000) Current (A) 08V Power factor (%)

14 MXZ-4A36NA 30V Indoor units Cooling capacity (BTU/h) combination Unit A Unit B Unit C Unit D Total 09 (7,00 ~ ),000,000 (7,00 ~,000) 5, ,000 (7,00 ~ 5,000) 6,00 7 6,00 (7,00 ~ 6,00), ,000 7,600,000,500 0,800 3,000,00 3,000 8,800 8,00 6,900 8,700,000 5,000 6,00 0,400,000 4,500 5,00 3,000 3,800 3,000 8,800 8,00 6,900,700,000 4,500 5,700 8,300,700 (7,00 ~,000) 8,000 (,000 ~ 8,000),000 (,000 ~,000) 4,000 (,000 ~ 4,000) 5,00 (,000 ~ 5,00) 8,000 (,000 ~ 8,000) 4,000 (,000 ~ 4,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 6,000 (,000 ~ 6,000) 7,000 (,600 ~ 7,000) 30,000 (,600 ~ 30,000) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) Power consumption (W) 800 (650 ~ 800),000 (650 ~,000),30 (650 ~,30),480 (650 ~,480),00 (650 ~,00),800 (90 ~,800),000 (90 ~,000),500 (90 ~,500),700 (90 ~,700) 3,00 (90 ~ 3,00),500 (90 ~,500),800 (90 ~,800),800 (90 ~,800),800 (90 ~,800),800 (90 ~,800),800 (90 ~,800),860 (,000 ~,850) 3,70 (,000 ~ 3,70) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) Current (A) 30V Power factor (%)

15 Indoor units Cooling capacity (BTU/h) combination Unit A Unit B Unit C Unit D Total 3, ,000 0,700 3,400 (,600 ~ 3,00) 3, ,600 0,00 4,400 (,600 ~ 3,00) 3, ,500,300,300 (,600 ~ 3,00) 3, ,00,700 3,300 (,600 ~ 3,00) 3, ,700 0,700 9,900 9,400 9,00 8,300 7,700 7,700,700 0,700 9,900 9,400,500 8,300 7,700 7,700,700 0,700,300 3,300,500 8,300 7,700 0,300,00,900 0,300 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 3,00 (,600 ~ 3,00) 36,000 (,600 ~ 36,400) 36,000 (,600 ~ 36,400) 36,000 (,600 ~ 36,400) 36,000 (,600 ~ 36,400) Power consumption (W) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,500 (,000 ~ 3,500) 3,80 (,000 ~ 3,900) 3,80 (,000 ~ 3,900) 3,80 (,000 ~ 3,900) 3,80 (,000 ~ 3,900) Current (A) 30V Power factor (%)

16 Indoor units Heating capacity (BTU/h) combination Unit A Unit B Unit C Unit D Total ,900 3,600 8,000 0,00 3,00 0,900 0,900 0,00 9,300 7,300 3,500,000,00 3,500,700 3,500 0,800 0,000 8,900 8,400 7,800 9,400 8,300 0,900 3,600 6,900 7,700 9,700 3,500 5,000 5,800 3,500 4,300 3,500 0,800 0,000 8,900 8,400 7,800,500 0,400 0,800,400 4,600 5,600 6,800,500 3,700 0,900 (8,600 ~ 5,400) 3,600 (8,600 ~ 6,400) 8,000 (8,600 ~,00) 0,00 (8,600 ~,500) 3,00 (8,600 ~ 7,800),800 (,000 ~ 3,000) 4,500 (,000 ~ 33,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 7,000 (,000 ~ 35,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) Power consumption (W),00 (780 ~,50),380 (780 ~,600),940 (780 ~,80),40 (780 ~,300),50 (780 ~ 3,000),700 (740 ~,560),980 (740 ~,800),00 (740 ~,90),00 (740 ~,90),980 (740 ~,740),00 (740 ~,90),60 (740 ~,860),40 (740 ~,860),0 (740 ~,800),0 (740 ~,800),00 (740 ~,800),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880) Current (A) 30V Power factor (%)

17 Indoor units Heating capacity (BTU/h) combination Unit A Unit B Unit C Unit D Total ,900 7,600 7,00 7,000 0,800 9,700 9,300 8,300 7,700 7,700 9,900,400,900,700 0,800 9,700 9,300,700 8,300 7,700 7,700 4,600,400 3,300,700 0,800 3,000 3,800,700 8,300 7,700 0,300,00,900 0,300 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 3,400 (,400 ~ 36,000) 36,000 (,400 ~ 43,000) 36,000 (,400 ~ 43,000) 36,000 (,400 ~ 43,000) 36,000 (,400 ~ 43,000) Power consumption (W),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880),700 (740 ~,880) 3,00 (740 ~ 4,350) 3,00 (740 ~ 4,350) 3,00 (740 ~ 4,350) 3,00 (740 ~ 4,350) Current (A) 30V Power factor (%)

18 4 SPECIFICATION Item Capacity Power consumption EER [SEER] 3 HSPF IV (V) COP External finish Power supply Max. fuse size (time delay) Min. circuit ampacity Fan motor Compressor Refrigerant control Sound level Defrost method Dimensions Cooling Heating 47 Heating 7 Cooling Heating 47 Heating 7 Cooling Heating Heating Model Weight Remote controller Control voltage (by built-in transformer) Refrigerant piping Model Btu/h Btu/h Btu/h W W W Winding resistance (at 68 F) " W D H Liquid Valve size as Indoor Connection method Outdoor Refrigerant charge (R40A) Refrigeration oil (Model) V, phase, Hz A A F.L.A R.L.A L.R.A db(a) in. in. in. lb. in. in. lb. oz. MXZ-A0NA MXZ-A0NA - MXZ-A0NA MXZ-A0NA - MXZ-A0NA MXZ-A0NA - NOTE : Test conditions are based on ARI 0/40. : Rating conditions (cooling) Indoor : 80 FDB, 67 FWB, Outdoor : 95 FDB, (75 FWB) (heating) Indoor : 70 FDB, 60 FWB, Outdoor : 47 FDB, 43 FWB : (heating) Indoor : 70 FDB, 60 FWB, Outdoor : 7 FDB, 5 FWB 3 : (cooling) Indoor : 80 FDB, 67 FWB, Outdoor : 8 FDB, 65 FWB 8 MXZ-A0NA MXZ-A0NA - 0,000/ (7,800 ~ 0,000),000/ (8,500 ~,000) 4,500,50/ (630 ~,50),780/ (50 ~,780),500 (,500) 9.3 [5] 9.0 (7.0) 3.63 Munsell 5Y 8/ 08/30,, SNB30FPDH SNB30FQBH U-V 0.45 V-W 0.45 W-U 0.45 U-V 0.98 V-W 0.98 W-U LEV 49/5 Reverse cycle 33-/ /6 30 Wireless type -4V DC Not supplied (optional parts) /4 A,B:3/8 Flared Flared 5lb. 5oz. 0.3 (NEO) 3.7 (NEO) Unit: F Mode Test Indoor air condition Outdoor air condition Dry bulb Wet bulb Dry bulb Wet bulb Cooling Heating : "A" Cooling steady state at rated compressor speed 3: "B-" Cooling steady state at rated compressor speed "B-" Cooling steady state at minimum compressor speed Low ambient cooling steady state at minimum compressor speed Intermediate cooling steady state at intermediate compressor speed w : Standard rating-heating at rated compressor speed : Low temperature heating at rated compressor speed Max. temperature heating at minimum compressor speed High temperature heating at minimum compressor speed Frost accumulation at rated compressor speed Frost accumulation at intermediate compressor speed w (75) (65) (65) (53.5) (69) w At intermediate compressor speed =("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".

19 Item Capacity Power consumption EER [SEER] 3 HSPF IV (V) COP External finish Power supply Max. fuse size (time delay) Min. circuit ampacity Fan motor Compressor Refrigerant control Sound level Defrost method Dimensions Cooling Heating 47 Heating 7 Cooling Heating 47 Heating 7 Cooling Heating Heating W D H Weight Remote controller Control voltage (by built-in transformer) Refrigerant piping Liquid Valve size as Indoor Connection method Outdoor Refrigerant charge (R40A) Refrigeration oil (Model) Model Btu/h Btu/h Btu/h W W W V, phase, Hz A A F.L.A Model Winding resistance (at 68 F) " R.L.A L.R.A db(a) in. in. in. lb. in. in. lb. oz. MXZ-3A30NA MXZ-3A30NA - MXZ-3A30NA MXZ-3A30NA - 8,400/ (,600 ~ 8,400) 8,600/ (,400 ~ 36,000) 8,800 3,50/ (,000 ~ 3,50),80/ (740 ~,880),0 8.7 [6.0] 0.0 (7.5) 3.84 Munsell 3.0Y 7.8/. 08/30,, TNB0FMCH U-V 0.6 V-W 0.6 W-U LEV 49/49 Reverse cycle 35-7/6-9/3 35-7/ Wireless type -4V DC Not supplied (optional parts) /4 A:/ B,C:3/8 Flared Flared 7lb. oz. 9.4 (NEO) NOTE : Test conditions are based on ARI 0/40. : Rating conditions (cooling) Indoor : 80 FDB, 67 FWB, Outdoor : 95 FDB, (75 FWB) (heating) Indoor : 70 FDB, 60 FWB, Outdoor : 47 FDB, 43 FWB : (heating) Indoor : 70 FDB, 60 FWB, Outdoor : 7 FDB, 5 FWB 3 : (cooling) Indoor : 80 FDB, 67 FWB, Outdoor : 8 FDB, 65 FWB Unit: F Mode Test Indoor air condition Outdoor air condition Dry bulb Wet bulb Dry bulb Wet bulb Cooling Heating : "A" Cooling steady state at rated compressor speed 3: "B-" Cooling steady state at rated compressor speed "B-" Cooling steady state at minimum compressor speed Low ambient cooling steady state at minimum compressor speed Intermediate cooling steady state at intermediate compressor speed w : Standard rating-heating at rated compressor speed : Low temperature heating at rated compressor speed Max. temperature heating at minimum compressor speed High temperature heating at minimum compressor speed Frost accumulation at rated compressor speed Frost accumulation at intermediate compressor speed w (75) (65) (65) (53.5) (69) w At intermediate compressor speed =("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed". 9

20 Item Capacity Power consumption EER [SEER] 3 HSPF IV (V) COP External finish Power supply Max. fuse size (time delay) Min. circuit ampacity Fan motor Compressor Refrigerant control Sound level Defrost method Dimensions Weight Remote controller Control voltage (by built-in transformer) Refrigerant piping Valve size Connection method W D H Refrigerant charge (R40A) Refrigeration oil (Model) Cooling Heating 47 Heating 7 Cooling Heating 47 Heating 7 Cooling Heating Heating Liquid as Indoor Outdoor Model Btu/h Btu/h Btu/h W W W V, phase, Hz A A F.L.A Model Winding resistance (at 68 F) " R.L.A L.R.A db(a) in. in. in. lb. in. in. lb. oz. 08V 08V MXZ-4A36NA 36,000/ (,600 ~ 36,400) 36,000/ (,400 ~ 4,00) 30V 36,000/ (,400 ~ 43,000) 4,600 3,80/ (,000 ~ 3,900) 3,00/ (740 ~ 4,000) 30V 3,00/ (740 ~ 4,350) 3, [6.0] 9.5 (7.0) 3.40 Munsell 3.0Y 7.8/. 08/30,, TNB0FMCH U-V 0.6 V-W 0.6 W-U LEV 54/57 Reverse cycle 35-7/6-9/3 35-7/6 50 Wireless type -4V DC Not supplied (optional parts) /4 A:/ B,C,D:3/8 Flared Flared 8lb. 3oz. 9.4 (NEO) NOTE : Test conditions are based on ARI 0/40. : Rating conditions (cooling) Indoor : 80 FDB, 67 FWB, Outdoor : 95 FDB, (75 FWB) (heating) Indoor : 70 FDB, 60 FWB, Outdoor : 47 FDB, 43 FWB : (heating) Indoor : 70 FDB, 60 FWB, Outdoor : 7 FDB, 5 FWB 3 : (cooling) Indoor : 80 FDB, 67 FWB, Outdoor : 8 FDB, 65 FWB Unit: F Mode Test Indoor air condition Outdoor air condition Dry bulb Wet bulb Dry bulb Wet bulb Cooling Heating : "A" Cooling steady state at rated compressor speed 3: "B-" Cooling steady state at rated compressor speed "B-" Cooling steady state at minimum compressor speed Low ambient cooling steady state at minimum compressor speed Intermediate cooling steady state at intermediate compressor speed w : Standard rating-heating at rated compressor speed : Low temperature heating at rated compressor speed Max. temperature heating at minimum compressor speed High temperature heating at minimum compressor speed Frost accumulation at rated compressor speed Frost accumulation at intermediate compressor speed w (75) (65) (65) (53.5) (69) w At intermediate compressor speed =("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed". 0

21 5 OUTLINES AND DIMENSIONS MXZ-A0NA MXZ-A0NA - Unit: inch REQUIRED SPACE 6-9/6" 9-/6" 6-/3" Open as a rule More than 9.69 in. if the front and both sides are open 9-3/6" -/3" -/" Air in /3" -7/3" Air in Air out Drain hole 3-[-5/6" -/" -7/3" /6" 4-3/6" /6" 5-9/3" 4-3/3" 3/6" Oval hole (Base bolt M0) More than 3.94 in. Open as a rule More than 9.69 in. if the back, both sides and top are open More than 3.78 in. More than 3.94 in. More than 7.87 in. if there are obstacles to both sides 33-/6" -3/6" Indoor and outdoor connect wiring 3-[7/8" hole -3/6" 3" /" 4-3/6" 5/6" -5/3" -3/6" 8-5/8" -3/6" -3/4" 7-5/6" " as pipe [3/8"flared (both A&B unit) B unit connection A unit connection -3/4" 9/3" -5/8" 5-5/6" Liquid pipe [/4"flared (both A&B unit) rounding terminal Conduit cover Lock nut Connector

22 MXZ-3A30NA Unit: inch REQUIRED SPACE Open as a rule More than 9.69 in. if the front and both sides are open 7-7/8" 9-/6" (7-7/8") -3/8" -U-shape notched holes (Base bolt M0) -3/8" 9-7/3" 0-5/8" Air in (-/6") (5/8") More than 3.94 in. More than 3.94 in. More than 7.87 in. if there are obstacles to both sides Air in 8-/8" -9/3" Air out Drain hole 3-[-5/6" 35-7/6" -9/6" -3/3" 9-7/3" 3-3/3" (5/8") 5" 5-/4" -5/3" -3/3" Oval hole (Base bolt M0) 35-7/6" -3/6" -5/6" Open as a rule More than 9.69 in. if the back, both sides and top are open -9/3" 3/3" -/6" -/4" 3-5/3" Indoor and outdoor connect wiring 4-[7/8" hole 9-9/6" C unit connection B unit connection A unit connection More than 3.78 in. as pipe [3/8" flared (B,C unit) [/" flared (A unit) -/" 9/3" Liquid pipe [/4" flared 3-5/3" 9/3" Lock nut Conduit cover Connector

23 ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;; ;;;;;;;;;; ;;;;;;;;;; ;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;; MXZ-3A30NA - Unit: inch 7-7/8" 9-/6" 7-7/8" 9-7/3" 0-5/8" -9/3" -3/8" -3/8" Air in Drain hole 3-[-5/6" Handle Air in Air out 3-[7/8"Punched hole (Connect wiring hole) 35-7/6" -/6" -9/6" 5/8" 5/6" 7/6" 5/8" -U Shaped notched hole (Base bolt M0) 4" (Bolt pitch) 5-/4" -(5/3"o-3/3") Oval hole (Base bolt M0) -[7/8"Knockout (Connect wiring hole) -3/6" -9/3" 3/3" Handle 8-/8" -3/6" 8-7/3" 4-3/4" 9-/8" 35-7/6" C B A 3-5/3" as pipe [3/8 (B,C unit) [/ (A unit) C unit connection B unit connection A unit connection -/" 9/3" -5/3" 5-3/6" Liquid pipe [/4 flared.installation space Note : Leave front and both sides clearance fully. More than 9-/6" More than 3-5/6" Note : Leave front and overhead clearance fully. More than 7-7/8" Lock nut Connector Conduit cover Note : Leave front, overhead and both sides clearance fully. More than 3-5/6" More than 9-/6" More than3-5/3".service space More than 3-5/6" More than 3-5/3" More than 3-5/6" More than 9-/6" SERVICE SPACE More than 3-5/3" 3

24 MXZ-4A36NA Unit: inch 7-7/8" 9-/6" 7-7/8" 9-7/3" 0-5/8" -9/3" -3/8" -3/8" Air in Drain hole 3-[-5/6" Handle Air in Air out 3-[7/8"Punched hole (Connect wiring hole) 35-7/6" -/6" -9/6" 5/8" 5/6" 7/6" 5/8" -U Shaped notched hole (Base bolt M0) 4" (Bolt pitch) 5-/4" -(5/3"o-3/3") Oval hole (Base bolt M0) -[7/8"Knockout (Connect wiring hole) -3/6" -9/3" 3/3" Handle 8-/8" -3/6" -3/3" 4-3/4" 9-/8" 35-7/6" D C B A as pipe [3/8 (B,C,D unit) 3-5/3" [/ (A unit) D unit connection C unit connection B unit connection A unit connection -/" 9/3" -5/3" 5-3/6" Liquid pipe [/4 flared.installation space Note : Leave front and both sides clearance fully. More than 9-/6" More than 3-5/6" Note : Leave front and overhead clearance fully. More than 7-7/8" Lock nut Conduit cover Connector Note : Leave front, overhead and both sides clearance fully. More than 3-5/6" More than 9-/6" More than3-5/3".service space More than 3-5/6" More than 3-5/3" More than 3-5/6" More than 9-/6" SERVICE SPACE More than 3-5/3" 4

25 6 WIRIN DIARAM MXZ-A0NA 5

26 MXZ-A0NA - 6

27 MXZ-3A30NA 7

28 MXZ-3A30NA - 8

29 MXZ-4A36NA RT64 POWER BOARD NOISE FILTER P.C.BOARD L X64 CT U R CT PFC BLK RED CT6 ROUND CB CB CB3 F64 S YLW 3 4 WHT TAB4 NOTES:.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing..use copper conductors only (For field wiring). 3.Symbols below indicate. :Terminal block :connector R64B R64A TB L IPM N/F BLK WHT RED YLW BLU ORN PNK RY L BLK POWER SUPPLY 08/30V phase 60Hz CN903 NR64 N BLK F65 3 N/F BLK CN90 CN6 BLU BLK RS3 RS U BLK V WHT RED SSR6 W BLK BLK HC930 V MC W CN3 CN5 4 3 CN 5 6 S3 S S TB5-4V RS4 RS 7 TO INDOOR UNIT No.D CONNECTIN CN CN93 CN93 MF TAB BLK BLU TAB CN9 LD9 BLK 3 BRN LD LD CN4 LDE LDE 08/30V PH. 60Hz BLU BLU BLK BLK 3 CN63 BLU BLK BLK BLK BLK BLK -4V WHT RED BLK BLK BLK BLK BLK BLK S4 RY TB4 S3 S S TO INDOOR UNIT No.C CONNECTIN 3 CN6 08/30V PH. 60Hz 3 CN80 CN CN CN78 ORN F93 F80-4V T80 TO INDOOR UNIT No.B CONNECTIN P.C.BOARD CONTROL ELECTRONIC TB3 RED BLU BLK BLU BLU BLK BLK S3 S S R930A 08/30V PH. 60Hz R930B (RN) CN60 CN6-4V CN663 CN68 TO INDOOR UNIT No.A CONNECTIN CN CN CN (WHT) (RED) (BLU) CN79 CN79 CN TB S3 S S 08/30V PH. 60Hz WHT YLW ORN BLU BRN RED RY RY RY RY BLK BLK RY RY RED RED WHT YLW ORN BLU BRN RED RED BRN BLU ORN YLW WHT WHT YLW ORN BLU BRN RED WHT YLW ORN BLU BRN RED NAME TRANSFORMER TERMINAL BLOCK SYMBOL T80 TB~5 HPS RT6 RT68 RT65 LEV A LEV B LEV C LEV D RT6 LEV F RELAY REVERSIN VALVE SOLENOID COIL X64 S4 SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME CB~3 SMOOTHIN CAPACITOR HC930 INTELLIENT POWER MODULE MF FAN MOTOR RT6 DEFROST THERMISTOR CT, CURRENT TRANSFORMER HPS HIH PRESSURE SWITCH NR64 VARISTOR RT6 DISCHARE TEMP.THERMISTOR CT6 CURRENT TRANSFORMER IPM INTELLIENT POWER MODULE N/F NOISE FILTER RT64 FIN TEMP.THERMISTOR F64 FUSE(TAL50V) L REACTOR PFC POWER FACTOR CONTROLLER RT65 AMBIENT TEMP.THERMISTOR F65 FUSE(T6.3AL50V) LEV A~D EXPANSION VALVE R64A,B RESISTOR OUTDOOR HEAT EXCHANER RT68 F80 FUSE(T3.5AL50V) LEV F EXPANSION VALVE R930A,B RESISTOR TEMPERATURE THERMISTOR F93 FUSE(T3.5AL50V) MC COMPRESSOR RS~4 RESISTOR SSR6 SOLENOID COIL RELAY 9

30 7 REFRIERANT SYSTEM DIARAM MXZ-A0NA MXZ-A0NA - Unit:mm R.V. coil OFF ON Refrigerant flow in cooling Refrigerant flow in heating Service port Compressor Service Discharge temperature port thermistor RT6 Oil separator Indoor unit B Unit B gas pipe temperature thermistor W Ball valve with service port Capillary tube O.D.0.98 I.D way valve Indoor unit A Unit A gas pipe temperature thermistor W Muffler Outdoor heat exchanger temperature thermistor RT68 FAN-OUT HEX-OUT Ambient temperature thermistor RT65 Indoor unit A Capillary tube O.D.0.6 I.D Strainer #00 LEV A Ball valve Strainer #00 Power receiver LEV E Strainer #00 Distributor Defrost thermistor RT6 Capillary tube O.D.0.4 I.D Indoor unit B Capillary tube O.D.0.6 I.D Strainer #00 LEV B W Except MXZ-A0NA -. 30

31 Operating Range MXZ-A0NA MXZ-A0NA - Cooling Heating Maximum Minimum Maximum Minimum Indoor intake air temperature 95 FDB, 7 FWB 67 FDB, 57 FWB 80 FDB, 67 FWB 70 FDB, 60 FWB Outdoor intake air temperature 5 FDB 4 FDB 75 FDB, 65 FWB 4 FDB, FWB MAX. REFRIERANT PIPIN LENTH & PIPE SIZE SELECTION MXZ-A0NA MXZ-A0NA - Piping length each indoor unit (a, b) Total piping length (a+b) Bending point for each unit Total bending point 8ft. MAX. 64ft. MAX. 5 MAX. 60 MAX. It does not matter which unit is higher. Indoor units a Outdoor unit 49ft. 49ft. b 33ft. Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below. When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe. For further information on Different-diameter pipe, see 5-. Unit : inch Indoor unit Outdoor unit union diameter Extension pipe diameter class Pipe diameter For Liquid /4 Liquid /4 Liquid /4 09 Indoor unit A as 3/8 as 3/8 as 3/8 Liquid /4 Liquid /4 Liquid /4 Indoor unit B as 3/8 as 3/8 as 3/8 5 Liquid /4 Liquid /4 as 3/8 as 3/8 3

32 MXZ-3A30NA R.V. coil OFF ON Indoor unit C Indoor unit B Indoor unit A Unit C gas pipe temperature thermistor Unit B gas pipe temperature thermistor Unit A gas pipe temperature thermistor Indoor unit A Indoor unit B Indoor unit C Refrigerant flow in cooling Refrigerant flow in heating Strainer #00 Strainer #00 Strainer #00 LEV A LEV B LEV C High-pressure switch Ball valve with service port Capillary tube O.D.0.6 I.D Service port Service Compressor port Discharge temperature thermistor RT6 Oil separator Muffler Ball valve Strainer #00 Distributor Capillary tube O.D.0.0 I.D way valve Power receiver LEV E Strainer #00 Outdoor heat exchanger Outdoor heat exchanger temperature thermistor RT68 Defrost thermistor RT6 Unit:mm Ambient temperature thermistor RT65 Capillary tube O.D.0.6 I.D Distributor MXZ-3A30NA - R.V. coil OFF ON Indoor unit C Indoor unit B Indoor unit A Refrigerant flow in cooling Refrigerant flow in heating Compressor Service port High-pressure switch Oil separator Stop valve (with service port) Muffler Service port Discharge temperature thermistor RT6 Capillary tube O.D.0.0 I.D way valve Unit:mm Indoor unit A Indoor unit B Indoor unit C Strainer #00 Strainer #00 Strainer #00 Capillary tube O.D.0.6 I.D LEV A LEV B LEV C Capillary tube Stop valve Strainer Strainer O.D.0. I.D #00 LEV F #00 Distributor Power receiver 3 Outdoor heat exchanger Outdoor heat exchanger temperature thermistor RT68 Defrost thermistor RT6 Ambient temperature thermistor RT65

33 Operating Range MXZ-3A30NA MXZ-3A30NA - Cooling Heating Maximum Minimum Maximum Minimum Indoor intake air temperature 95 FDB, 7 FWB 67 FDB, 57 FWB 80 FDB, 67 FWB 70 FDB, 60 FWB Outdoor intake air temperature 5 FDB 4 FDB 75 FDB, 65 FWB 4 FDB, FWB MAX. REFRIERANT PIPIN LENTH & PIPE SIZE SELECTION MXZ-3A30NA MXZ-3A30NA - Piping length each indoor unit (a, b, c) Total piping length (a+b+c) Bending point for each unit Total bending point It does not matter which unit is higher. 8ft. MAX. 30ft. MAX. 5 MAX. 70 MAX. Indoor units a b Outdoor unit 33ft. (MXZ-3A30NA) 49ft. (MXZ-3A30NA - ) 33ft. (MXZ-3A30NA) 49ft. (MXZ-3A30NA - ) c 33ft. Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below. When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe. For further information on Different-diameter pipe, see 5-. Unit : inch Indoor unit Outdoor unit union diameter Extension pipe diameter class Pipe diameter For Liquid /4 Liquid /4 Liquid /4 09 Indoor unit A as 3/8 as 3/8 as / Liquid /4 Liquid /4 Liquid /4 Indoor unit B as 3/8 as 3/8 as 3/8 Liquid /4 Liquid /4 Liquid /4 5 Indoor unit C as 3/8 as 3/8 as 3/8 Liquid /4 Liquid /4 7 as / as / Liquid /4 Liquid /4 4 as 5/8 as 5/8 33

34 MXZ-4A36NA Service port Unit:mm R.V. coil OFF ON Indoor unit D Indoor unit C Indoor unit B Indoor unit A Indoor unit A Indoor unit B Indoor unit C Indoor unit D Refrigerant flow in cooling Refrigerant flow in heating Strainer #00 Strainer #00 Strainer #00 Strainer #00 LEV A LEV B LEV C Compressor Service port High-pressure switch Oil separator Stop valve (with service port) Muffler Capillary tube O.D.0.6 I.D LEV D Discharge temperature thermistor RT6 Capillary tube O.D.0.0 I.D way valve Outdoor heat exchanger Outdoor heat exchanger temperature thermistor RT68 Defrost thermistor RT6 Ambient temperature thermistor RT65 Capillary tube Stop valve Strainer Strainer O.D.0. I.D #00 LEV F #00 Distributor Power receiver 34

35 Operating Range MXZ-4A36NA Cooling Heating Maximum Minimum Maximum Minimum Indoor intake air temperature 95 FDB, 7 FWB 67 FDB, 57 FWB 80 FDB, 67 FWB 70 FDB, 60 FWB Outdoor intake air temperature 5 FDB 4 FDB 75 FDB, 65 FWB 4 FDB, FWB MAX. REFRIERANT PIPIN LENTH & PIPE SIZE SELECTION MXZ-4A36NA Piping length each indoor unit (a, b, c, d) Total piping length (a+b+c+d) Bending point for each unit Total bending point It does not matter which unit is higher. 8ft. MAX. 30ft. MAX. 5 MAX. 70 MAX. Indoor units a b Outdoor unit 49ft. c 49ft. d 33ft. Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below. When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe. For further information on Different-diameter pipe, see 5-. Unit : inch Indoor unit Outdoor unit union diameter Extension pipe diameter class Pipe diameter For Liquid /4 Liquid /4 Liquid /4 09 Indoor unit A as 3/8 as 3/8 as / Liquid /4 Liquid /4 Liquid /4 Indoor unit B as 3/8 as 3/8 as 3/8 Liquid /4 Liquid /4 Liquid /4 5 Indoor unit C as 3/8 as 3/8 as 3/8 Liquid /4 Liquid /4 Liquid /4 7 Indoor unit D as / as / as 3/8 Liquid /4 Liquid /4 4 as 5/8 as 5/8 35

36 8 DATA Model MXZ-A0NA MXZ-A0NA - Item Unit Cooling Heating Capacity Btu / h 0,000,000 Total SHF Input kw.5.78 Outdoor unit MXZ-A0NA MXZ-A0NA - Electrical circuit Power supply (V, phase, Hz) Input kw.3 08/30,, Comp. current (08/30V) A 0.08/9. 8.4/7.45 Fan motor current (08/30V) A 0.43/ /0.39 Condensing pressure PSI Suction pressure PSI 8 0 Discharge temperature F Refrigerant circuit Condensing temperature Suction temperature F F Comp. shell bottom temp. Ref. pipe length [Total pipe length for multi-system] F ft [50] 44 Refrigerant charge (R40A) 5lb.5oz. Outdoor unit Intake air temperature Fan speed DB WB F F rpm Airflow CFM,485,640 36

37 Model MXZ-3A30NA MXZ-3A30NA - Item Unit Cooling Heating Capacity Btu / h 8,400 8,600 Total SHF Input kw Outdoor unit MXZ-3A30NA MXZ-3A30NA - Electrical circuit Power supply (V, phase, Hz) Input kw 3. 08/30,, 60.7 Comp. current (08/30V) A 5.45/3. 0.5/9.8 Fan motor current (08/30V) A 0.43/ /0.39 Condensing pressure PSI Suction pressure PSI Discharge temperature F Refrigerant circuit Condensing temperature Suction temperature F F Comp. shell bottom temp. Ref. pipe length [Total pipe length for multi-system] F ft [75] 5 Refrigerant charge (R40A) 7lb.oz. Outdoor unit Intake air temperature Fan speed DB WB F F rpm Airflow CFM,365,605 37

38 Model MXZ-4A36NA Item Unit Cooling Heating Capacity Btu / h 36,000 36,000 Total SHF Input kw Outdoor unit MXZ-4A36NA Electrical circuit Power supply (V, phase, Hz) Input kw /30,, Comp. current (08/30V) A 7.85 / /.98 Fan motor current (08/30V) A 0.43 / / 0.39 Condensing pressure PSI Suction pressure PSI Discharge temperature F Refrigerant circuit Condensing temperature Suction temperature F F Comp. shell bottom temp. Ref. pipe length [Total pipe length for multi-system] F ft [00] 40 Refrigerant charge (R40A) 8lb.3oz. Outdoor unit Intake air temperature Fan speed DB WB F F rpm Airflow CFM,068,068 38

39 8-. OPERATIN RANE () POWER SUPPLY Model Rating uaranteed Voltage Outdoor unit MXZ-A0NA MXZ-A0NA - MXZ-3A30NA MXZ-3A30NA - MXZ-4A36NA 08/30V 60Hz [ Min. 98V 08V 30V Max. 53V () OPERATION Function Cooling Heating Condition Intake air temperature "A" Cooling steady state at rated compressor speed "B-" Cooling steady state at rated compressor speed "B-" Cooling steady state at minimum compressor speed Low ambient cooling steady state at minimum compressor speed Intermediate cooling steady state at intermediate compressor speedw Standard rating-heating at rated compressor speed Low temperature heating at rated compressor speed Max. temperature heating at minimum compressor speed High temperature heating at minimum compressor speed Frost accumulation at rated compressor speed Frost accumulation at intermediate compressor speedw DB ( F) w At intermediate compressor speed =("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed" Indoor WB ( F) DB ( F) Outdoor WB ( F) (75) (65) (65) (53.5) (69)

40 MXZ-A0NA MXZ-A0NA - MXZ-3A30NA MXZ-3A30NA - MXZ-4A36NA The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve. () UARANTEED VOLTAE 98 ~ 53V 60Hz () AIR FLOW Air flow should be set at MAX. (3) MAIN READINS () Indoor intake air wet-bulb temperature : FWB } () Indoor outlet air wet-bulb temperature : FWB Cooling (3) Outdoor intake air dry-bulb temperature : FDB (4) Total input: W (5) Indoor intake air dry-bulb temperature : FDB (6) Outdoor intake air wet-bulb temperature : FWB Heating } (7) Total input : W Indoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service. How to measure the indoor air wet-bulb/dry-bulb temperature difference. Attach at least sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.. Attach at least sets of wet-and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun. 3. Check that the air filter is cleaned. 4. Open windows and doors of room. 5. Press the EMERENCY OPERATION switch once(twice) to start the EMERENCY COOL(HEAT) MODE. 6. Compressor starts running at 33Hz (COOL) or 45Hz (HEAT). The frequency at each operation mode is fixed. 7. When system stabilizes after more than 5 minutes, measure temperature and take an average temperature minutes later, measure temperature again and check that the temperature does not change. INDOOR UNIT OUTDOOR UNIT Wet-and dry-bulb thermometers Wet-and dry-bulb thermometers 40

41 8-. CAPACITY AND THE INPUT CURVES MXZ-A0NA MXZ-A0NA - Indoor air WB temperature difference (degree) Indoor unit class (Inverter output frequency) 09 class (36Hz) class (50Hz) 5 class (77Hz) Indoor air DB temperature difference (degree) Indoor unit class (Inverter output frequency) class (45Hz) class (56Hz) 5 class (75Hz) Indoor intake air Dry-bulb temperature (-F) Indoor intake air Dry-bulb temperature (-F) Outdoor intake air Wet-bulb temperature (-F) Outdoor intake air Wet-bulb temperature (-F) NOTE:The above broken lines are for the heating operation without any frost and defrost operation. MXZ-3A30NA MXZ-3A30NA - MXZ-4A36NA Indoor air WB temperature difference (degree) Indoor unit class (Inverter output frequency) 09 class (0Hz) class (7Hz) 5 class (36Hz) 7 class (40Hz) 4 class (56Hz) Indoor air DB temperature difference (degree) Indoor unit class (Inverter output frequency) class (34Hz) class (4Hz) class (56Hz) class (60Hz) class (7Hz) Indoor intake air Dry-bulb temperature (-F) Indoor intake air Dry-bulb temperature (-F) Outdoor intake air Wet-bulb temperature (-F) Outdoor intake air Wet-bulb temperature (-F) NOTE:The above broken lines are for the heating operation without any frost and defrost operation. 4

42 8-3. Capacity and input correction by means of inverter output frequency (OUTDOOR UNIT : MXZ-A0NA MXZ-A0NA - ). 09-class unit in single operation.0 <COOL>Capacity.0 <COOL>Total input.0 <HEAT>Capacity.0 <HEAT>Total input Hz Hz Frequency Frequency. -class unit in single operation <COOL>Capacity <COOL>Total input Hz Frequency <HEAT>Capacity Hz Frequency <HEAT>Total input Hz Hz Frequency Frequency 3. 5-class unit in single operation <COOL>Capacity <COOL>Total input Hz Frequency <HEAT>Capacity Hz Frequency <HEAT>Total input Hz Frequency Hz Frequency Hz Frequency Hz Frequency 4

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2 SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-

More information

SERVICE MANUAL MU-A09WA MU-A12WA MU-A12WA- 1 OUTDOOR UNIT. No. OB449. Wireless type Models HFC. Revision : A SPLIT-TYPE AIR CONDITIONERS

SERVICE MANUAL MU-A09WA MU-A12WA MU-A12WA- 1 OUTDOOR UNIT. No. OB449. Wireless type Models HFC. Revision : A SPLIT-TYPE AIR CONDITIONERS SPLIT-TYPE AIR CONDITIONERS Revision : A MU-AWA- Please void OB449. has been added. OUTDOOR UNIT SERVICE MANUAL Wireless type Models MU-AWA MU-AWA- HFC utilized R40A No. OB449 REVISED EDITION-A Indoor

More information

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED

More information

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1 SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH

More information

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

MU09TW MU12TN MU15TN MU17TN

MU09TW MU12TN MU15TN MU17TN SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL Wireless type Models (W) MSTN (W) MS5TN (W) MS7TN (W) MU09TW MUTN MU5TN MU7TN No. OB74 CONTENTS MSTN MS5TN MS7TN INDOOR UNIT MU5TN MU7TN OUTDOOR UNIT Remote controller.

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : AEMI0AH AEMIAHB AEMIAH AEMI0AH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.k.k.0k Outdoor Model No. AEMI0AH AEMIAHB AEMIAH

More information

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV TABLE OF CONTENTS RX-JV/GV 1 Features.............................................................

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKE1NB41 & CZ18BT1U + CUKE1NK1 CSKE18NB4UW & CZ18BT1U + CUKE18NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) CSKE1NB41 (CZ18BT1U) CSKE18NB4UW (CZ18BT1U)

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000

More information

SERVICE MANUAL MUZ-HJ25VA MUZ-HJ35VA OUTDOOR UNIT. No. OBH648. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MUZ-HJ25VA MUZ-HJ35VA OUTDOOR UNIT. No. OBH648. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-HJ25VA MUZ-HJ35VA - E1 - E1 Indoor unit service manual MSZ-HJ VA Series (OBH647) MUZ-HJ25VA MUZ-HJ35VA CONTENTS 1.

More information

SERVICE MANUAL MUZ-GC25VA - MUZ-GC25VAH - MUZ-GC35VA - MUZ-GC35VAH - E1 OUTDOOR UNIT. No. OBH469. Wireless type Models HFC

SERVICE MANUAL MUZ-GC25VA - MUZ-GC25VAH - MUZ-GC35VA - MUZ-GC35VAH - E1 OUTDOOR UNIT. No. OBH469. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL Wireless type Models E1 - E1 H - E1 - - E1 HFC utilized R410A. OBH469 Indoor unit service manual MSZ-GC VA Series (OBH468) H CONTENTS

More information

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions

More information

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

New Deluxe Wall Mounted Heat Pump Series EXTERIOS New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History

More information

SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET

SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET (PART NO. 97474700) For authorized service personnel only. This installation instruction sheet describes how to install the outdoor unit only.

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM97 CM7 CM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CM97

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6. TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM

More information

PANASONIC TROUBLE SHOOTING GUIDE

PANASONIC TROUBLE SHOOTING GUIDE A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6 TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL

More information

SERVICE MANUAL MSZ-A18YV - E1 MSZ-A24YV - MSZ-A24YV - E1 INDOOR UNIT. No. OB345 REVISED EDITION-A. Models. Revision A : SPLIT-TYPE AIR CONDITIONERS

SERVICE MANUAL MSZ-A18YV - E1 MSZ-A24YV - MSZ-A24YV - E1 INDOOR UNIT. No. OB345 REVISED EDITION-A. Models. Revision A : SPLIT-TYPE AIR CONDITIONERS SPLIT-TYPE AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL Models E MSZ-A8YV - E MSZ-AYV - MSZ-A6YV - E Revision A : Parts numbers of indoor fan motor and motor band have been changed. Another type of the

More information

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKS12NB41 & CZ18BT1U + CUKS12NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)

More information

Appendix - Controllers 179

Appendix - Controllers 179 Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO.

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO. TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA

More information

evo+ Installation, Service & Troubleshooting DUCTLESS SYSTEM

evo+ Installation, Service & Troubleshooting DUCTLESS SYSTEM evo+ DUCTLESS SYSTEM Installation, Service & Troubleshooting Models: GWH09AB-A3DNA2B GWH12AB-A3DNA2B GWH09AB-D3DNA2D GWH12AB-D3DNA2D GWH18AB-D3DNA2D GWH24AB-D3DNA2D Table of Contents Safety Precautions

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description Description Compact air/water heat pump for outside installation. With suction gas cooled rotary compressor. With extensive aluminium/cu lamellar tube evaporator and PVC Titanium condenser. Axial fan Refrigerant

More information

DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS

DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS AN EXCELLENT CHOICE IN COOLING, COMFORT AND CONVENIENCE Why choose a Mini-Split system? Installing

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0 Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view

More information

PARTS CATALOG MUZ-HJ25VA - E1, ER1, ET1 MUZ-HJ35VA - E1, ER1, ET1 MUZ-HJ50VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBB648 REVISED EDITION-C.

PARTS CATALOG MUZ-HJ25VA - E1, ER1, ET1 MUZ-HJ35VA - E1, ER1, ET1 MUZ-HJ50VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBB648 REVISED EDITION-C. SPLIT-TYPE AIR CONDITIONERS Revision C: MUZ-HJ25VA-, MUZ-HJ35VA- and MUZ-HJ50VA- have been added. The defrost heater for MUZ-HJ25VA and MUZ- HJ35VA has been added to the optional parts. Please void OBB648

More information

AIR CONDITIONER INSTALLATION MANUAL

AIR CONDITIONER INSTALLATION MANUAL INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by

More information

HVAC SYSTEM (HEATER, VENTILATOR, AND A/C)

HVAC SYSTEM (HEATER, VENTILATOR, AND A/C) HVAC SYSTEM (HEATER, VENTILATOR, AND A/C) HEATER SYSTEM 1. Heater System A: GENERAL A semi-center type integrated air conditioning unit is used, where a high performance heater core and an evaporator core

More information

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into

More information

Refrigeration Basics 101. By: Eric Nelson

Refrigeration Basics 101. By: Eric Nelson Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE7NKU CS-MKE9NKU CS-MKE12NKU CS-MKE18NKU CS-MKE24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU

More information

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories

More information

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

Operating Instructions Split System Air Conditioner

Operating Instructions Split System Air Conditioner Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KS30NKU + CU-KS30NKUA CS-KS36NKU + CU-KS36NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KS30NKU CS-KS36NKU Product Code No. 852 360 86

More information

SERVICE MANUAL MUZ-GA25VA - MUZ-GA35VA - MUZ-GA25VAH - MUZ-GA25VAH - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL MUZ-GA25VA - MUZ-GA35VA - MUZ-GA25VAH - MUZ-GA25VAH - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MUZ-GA5VA - E MUZ-GA35VA - E MUZ-GA5VAH - MUZ-GA35VAH - E HFC utilized R40A. OB379 Indication of model name MUZ-GA5VA - E MUZ-GA35VA

More information

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4. AquaFREE System Technical Catalogue Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.5/6)H(1/3) Specifications in this manual are subject to change without notice

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating

More information

SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING

SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

innovative comfort solutions

innovative comfort solutions engineering and specifications Guide duct-free air conditioning systems Art cool inverter flex multi-split floor standing ceiling cassette PTAC PTHP through-the-wall innovative comfort solutions 1 AT LG,

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

SWIMMING POOL HEAT PUMP Owners Manual

SWIMMING POOL HEAT PUMP Owners Manual SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

AIR-CONDITIONER SPLIT TYPE

AIR-CONDITIONER SPLIT TYPE FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,

More information

FAN SPEED AIR SWING SET CANCEL FAN AIR SWING SET CANCEL WARNING

FAN SPEED AIR SWING SET CANCEL FAN AIR SWING SET CANCEL WARNING AUT O HE AT COOL DRY AUT O HE AT COOL DRY FAN SP E ED FAN SPEED AC AC AIR SWING SE T CHE CK CLOCK RE SE T AIR SWING SE T CHE CK CLOCK RE SE T FAN SPEED AIR SWING RC RC Order No: PAPAMY32039CE (YE9/2QKE)

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

ARMSTRONG AIR HEAT PUMPS www.armstrongair.com

ARMSTRONG AIR HEAT PUMPS www.armstrongair.com INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7

More information

PARTS CATALOG OUTDOOR UNIT. No. OBB516. Models

PARTS CATALOG OUTDOOR UNIT. No. OBB516. Models SPLIT-TYPE AIR CONDITIONERS Revision D: The fan guards for MUZ-GE50VA(H) - E, MUZ -GE60VA - E and MUZ-GE7VA - E have been changed. Please void OBB56 REVISED EDITION-C. OUTDOOR UNIT PARTS CATALOG No. OBB56

More information

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: "How to check miswiring and serial signal error" for MUZ type has been added. The description about "Low standby power control" has been added to "TECHNICAL CHANGES".

More information

SERVICE MANUAL INDOOR UNIT. No. OB450. Models. Revision D: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-D

SERVICE MANUAL INDOOR UNIT. No. OB450. Models. Revision D: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-D Revision D: MSZ-GA NA and MSY-GA NA have been added. SPLIT-TYPE AIR CONDITIONERS Please void OB450 REVISED EDITION-C. INDOOR UNIT SERVICE MANUAL. OB450 REVISED EDITION-D Models MSZ-A09NA, - 1 MSZ-A12NA,

More information

HEATER, AIR CONDITIONING AND VENTILATION

HEATER, AIR CONDITIONING AND VENTILATION 55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-9 DUCT

More information

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

More information

SiUS041111. Service Manual. Inverter Pair Wall Mounted Type K-Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump

SiUS041111. Service Manual. Inverter Pair Wall Mounted Type K-Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump Service Manual Inverter Pair Wall Mounted Type K-Series [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump Inverter Pair Wall Mounted Type K-Series Cooling Only Indoor Unit FTXN09KEVJU

More information

DESIGN STANDARDS SECTION 23 60 00

DESIGN STANDARDS SECTION 23 60 00 PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.

More information

CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE

CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE Order No. MAC0512111C8 Air Conditioner CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE TABLE OF CONTENTS PAGE 1 Safety Precautions----------------------------------------------- 3 2 Specifications -----------------------------------------------------

More information

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

How To Measure Temperature On A Thermostat

How To Measure Temperature On A Thermostat Кондиционеры Mitsubishi Heavy Техническое руководство Кондиционеры настенного типа SRK20HD-S, SRK28HD-S, SRK40HD-S, SRK20CD-S, SRK28CD-S, SRK40CD-S CTENTS 1. GENERAL INFORMATI... 1 1.1 Specific features...

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER ( Split system, air to air heat pump type )

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER ( Split system, air to air heat pump type ) Manual No. 06. SRK-T. 050 updated September 29, 2009 INVERTER WALL MOUNTED TYPE ROOM AIR-CDITIER ( Split system, air to air heat pump type ) SRK20ZD-S1, SRK25ZD-S1, SRK35ZD-S1, SRK50ZD-S1 SRK63ZE-S1, SRK71ZE-S1

More information

FTQ. Daikin Inverter Ducted Heat Pump

FTQ. Daikin Inverter Ducted Heat Pump FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative

More information

HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL

HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL Models: CROWN09HP230V1A CROWN12HP230V1A CROWN18HP230V1A Thank you for choosing a Crown High-Wall Unit for your customer. Please

More information

Submitted to Reference Approval Construction Unit Designation Schedule #

Submitted to Reference Approval Construction Unit Designation Schedule # SUBMITTAL AQV09JA High Wall 9,000 Btu/h Heat Pump Nom Cooling Capacity (Btu/h) 9,000 SEER 20.0 Cool Capacity Range (Btu/h) 3,100 to 11,900 Nom Heating Capacity (Btu/h) 11,950 HSPF 10.0 Heating COP 3.7

More information

SWIMMING POOL HEAT PUMP

SWIMMING POOL HEAT PUMP SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical

More information

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Air Conditioner Water Heater - A Product of HotSpot Energy LLC Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

SiUS091133. Service Manual. Inverter Pair FTXS-L Series FDXS-L Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump

SiUS091133. Service Manual. Inverter Pair FTXS-L Series FDXS-L Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump Service Manual Inverter Pair FTXS-L Series FDXS-L Series [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump Inverter Pair FTXS-L Series FDXS-L Series Cooling Only Indoor Unit FTXS30LVJU

More information

SERVICE MANUAL MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA INDOOR UNIT. No. OBH647. Models. Revision A: MSZ-HJ50VA- E1 has been added.

SERVICE MANUAL MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA INDOOR UNIT. No. OBH647. Models. Revision A: MSZ-HJ50VA- E1 has been added. SPLIT-TYPE AIR CONDITIONERS Revision A: MSZ-HJ50VA- E1 has been added. Please void OBH647. INDOOR UNIT SERVICE MANUAL. OBH647 REVISED EDITION-A Models MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA - E1 - E1 - E1 CONTENTS

More information

AquaFREE system. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE

AquaFREE system. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE AquaFREE system Technical Catalogue Outdoor units: RAS(3~5)HVRNE RAS(4/5)HRNE Indoor units: RWM(3~5)FSN1E RWM(3~5)FSN1E(4.5/6)H(1/3) RWM(3~5)FSN1ES1 RWM(3~5)FSN1E(4.5/6)SH(1/3) Specifications in this

More information

Rusty Walker, Corporate Trainer Hill PHOENIX

Rusty Walker, Corporate Trainer Hill PHOENIX Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat

More information

FULL DC INVERTER SYSTEMS

FULL DC INVERTER SYSTEMS FULL DC INVERTER SYSTEMS INDIDUAL AND MODULAR DESIGN & FLEXIBLE COMBINATION commercial air conditioners SDV4 2011/2012 AIR CONDITIONING 1 WELCOME TO THE WORLD of SINCLAIR AIR CONDITIONERS Company operation

More information

CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS

CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS Please read this instruction sheet completely before installing the product. When the power cord is damaged, replacement work should be

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL

More information

Customized Assessment Blueprint

Customized Assessment Blueprint Customized Assessment Blueprint HVAC Installer Basic - Test Codes: 7906 and 7796 Measuring What Matters Competencies and Skills Tested in this Assessment: HVAC Theory Heat Theory and Refrigeration HVAC

More information

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision E: MSZ-GE22VAD- A1 has been added. Please void OBH531 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OBH531 REVISED EDITION-E Models MSZ-GE22VA - A1 MSZ-GE50VA - A1

More information

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle

More information

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODEL: WA121 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual : 2100-234 E Supersedes: 2100-234

More information