Active Chilled Beam System Design & Layout

Size: px
Start display at page:

Download "Active Chilled Beam System Design & Layout"

Transcription

1 Active Chilled Beam System Design & Layout Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

2 Contents Active Chilled Beam Basics Design Considerations Air System Design & Humidity Control Water System Design Heating with Active Beams Controls Beam Selection & Layout

3 Fan Energy Use in Buildings 4.5 Chiller/Compressor 7 Design Load KW/SF Supply & Return Fans Chilled Water Pump Condenser Water Pump Cooling Tower Fan Condenser Fan Energy Use KWh/SF Central VAV Central CAV Packaged CAV 0 Central VAV Central CAV Packaged CAV Energy Consumption Characteristics of Commercial Building HVAC Systems publication prepared for U.S. Department of Energy

4 Water = Efficient Transport 10 1 Ton of Cooling requires 550 CFM of air or ¾ diameter water pipe 4 GPM of water

5 Active Chilled Beams Chilled Ceilings Passive Chilled Beams Active Chilled Beams Higher space loads Higher occupant densities Combined ventilation/cooling preferred Integration into fiber tile ceilings required

6 Active Chilled Beam 0 Operation Principle Primary air nozzles Primary air plenum 1 Part Primary Air Suspended ceiling Heat exchanger 4 Parts Room Air

7 Heat Removal Ratio Airflow requirement reduced by 70% 70% of sensible heat removed by chilled beam water coil

8 Active Chilled Beam 0 Airflow Pattern

9 Active Chilled Beams 0 System Highlights Very high cooling capacity Up to 100 BTUH/FT 2 floor space Up to 1500 BTUH per LF Integrated cooling, ventilation and heating All services in the ceiling cavity Suitable for integration into all ceiling types Reduces ceiling costs compared to Passive Beams

10 Active Chilled Beams 0 System Highlights Significant space savings Smaller ductwork saves space in shafts, plant rooms and ceiling Can be installed tight up against the slab Reduced floor to floor heights Reduced construction costs on new buildings Low noise levels Low maintenance No moving or consumable parts

11 Energy Savings 0 Compared to VAV Source Technology Application % Saving* US Dept. of Energy Report (4/2001) Beams/Radiant Ceilings General 25A30 ASHRAE 2010 Technology Awards Passive Chilled Beams Call Center 41 ACEE Emerging Technologies Report (2009) Active Chilled Beams General 20 ASHRAE Journal 2007 Active Chilled Beams Laboratory 57 SmithGroup Active Chilled Beams Offices 24 *Compared to VAV Energy Consumption Characteristics of Commercial Building HVAC Systems publication prepared for U.S. Department of Energy

12 Active Chilled Beams 0 Typical Installation

13 Active Chilled Beams 0 Typical Installation

14 Space Savings 12 A0 9 A10

15 Space Savings

16 Space Savings 9 A10 8 A0

17 Space Savings All Air HVAC System 5 Floors Exposed Chilled Beams 6 Floors

18 ACTIVE CHILLED BEAM DESIGN CONSIDERATIONS

19 Building Suitability Building Characteristics that favor Active Chilled Beams Zones with moderateahigh sensible load densities Where primary airflows would be significantly higher than needed for ventilation Sensible Heat Ratio s (SHR) of 0.8 and above Buildings most affected by space constraints Hi rises, existing buildings with induction systems Zones where the acoustical environment is a key design criterion Laboratories where sensible loads are driving airflows as opposed to air change rates Buildings seeking LEED or Green Globes certification

20 Building Suitability Characteristics that less favor Active Chilled Beams Buildings with operable windows or leaky construction Beams with drain pans could be considered Building pressurization control should be used Zones with relatively low sensible load densities Zones with relatively low sensible heat ratios and low ventilation air requirements Zones with high filtration requirements for the rea circulated room air Zone with high latent loads

21 SHR s for Typical Spaces SHR Range Auditoriums, Theaters Apartments Banks, Court Houses, Municipal Buildings Churches Dining Halls Computer Rooms Cocktail Lounges, Bars, Taverns, Clubhouses, Nightclubs Jails Hospital Patient Rooms, Nursing Home, Patient Rooms Kitchens Libraries, Museums Malls, Shopping Centers Medical/Dental Centers, Clinics and Offices Motel and Hotel Public Areas Motel and Hotel Guest Rooms Police Stations, Fire Stations, Post Offices Precision Manufacturing Restaurants Residences Retail, Department Stores Other Shops School Classrooms Supermarkets

22 Role of the Primary Air Ventilate the occupants according to ASHRAE 62A 2004 Handle all of the latent load in the space Primary air is only source of latent heat removal Create induction through chilled beam Pressurize the building

23 Primary Air Design Central AHU sized to handle: sensible and latent cooling/heating of the ventilation air portion of the sensible internal cooling/heating loads AND all of the internal and infiltration latent loads Primary air delivered continuously to the chilled beams VAV primary air can be considered for the perimeter if the sensible loads are high Chilled beam water coils provide additional sensible cooling/heating to control zones

24 Primary Air Temperature 0 Cooling 55 F or Lower 65 F or Higher Reduces lengths/quantities of beams Good for office buildings with high perimeter loads Reduces or eliminates reheat Ideal for labs or hospitals with code required minimum air changes Often used with VAV in applications with high sensible loads More or longer beams required in some applications Air must be suitably dehumidified whatever the dry bulb temp is!

25 Room Neutral Air Sensible recovery device (downstream of coil) Desiccant dehumidification units Passive dehumidification wheels

26 Reducing Primary Air Temperature Active Chilled Beams Primary Air Pressure Primary Air Flow Rate Supply Air Flow Rate Supply Air Temp Out (Cooling) Primary Air Sensible Cooling Secondary Air Sensible Cooling Nett Unit Sensible Cooling Chilled Water Flow Rate Qty Unit TAG Zone Name Unit Model 2 or 4 Pipe Coil Nominal Length (feet) P PA (Inch w.c.) Q PA (CFM) Q SA (CFM) t SAout ( F) q PAs (Btuh) q SCAs (Btuh) q s (Btuh) Q SCHW (GPM) 2 ACBA1 1 DADANCO ACB Room Design Primary Air Secondary Chilled Water Secondary Hot Water Elevation % Propylene Feet Glycol Cooling 75 F 50% RH 55 F 80% RH 58 F 110 F 0 0 Heating 70 F 50% RH 55 F 83% RH Active Chilled Beams Primary Air Pressure Primary Air Flow Rate Supply Air Flow Rate Supply Air Temp Out (Cooling) Primary Air Sensible Cooling Secondary Air Sensible Cooling Nett Unit Sensible Cooling Chilled Water Flow Rate Water Pressure Drop Qty Unit TAG Zone Name Unit Model 2 or 4 Pipe Coil Nominal Length (feet) P PA(Inch w.c.) Q PA(CFM) Q SA(CFM) t SAout( F) q PAs(Btuh) q SCAs(Btuh) q s(btuh) Q SCHW (GPM) SCHW pressure drop (Feet w.c.) 3 ACBA1 1 DADANCO ACB Room Design Primary Air Secondary Chilled Water Secondary Hot Water Elevation Feet% Propylene Glycol Cooling 75 F 53% RH 65 F 70% RH 58 F 70 F Heating 70 F 50% RH 107 F 83% RH Typically 25% + more chilled beams required when using 65 F primary air % Ethylene Gylcol

27 Latent Load Calculation The amount of cooling required to remove the moisture from the air Q L = 0.68 x q x w gr or QL = 4,840 x q x w lb Where A Q L = latent heat (Btuh) q = air volume flow (cfm) w gr = humidity ratio difference (grains water/lb dry air) w lb = humidity ratio difference (lbwater/lb dry air)

28 Dehumidification Air for 1 Person 0 200BTUH Primary air flow (CFM) % less air Primary air dew point ( F) Room Design Condition 55% RH 52% RH 50% RH

29 Supply Water Temperature Safety Margin Passive Chilled Beams + 1 F Do not design below room dew point! Active Chilled Beams A 2.9 F Climatic Ceilings by Energie

30 Condensation Radiant Panel Test Condensation after 8.5 hours on a chilled surface intentionally held 7.8 F colder than the space DPT. Not one droplet fell under these conditions Chilled Ceilings in Parallel with Dedicated Outdoor Air Systems: Addressing the Concerns of Condensation, Capacity, and Cost Stanley A. Mumma, Ph.D., P.E.

31 Design Cooling Loads 0 Beware of Overrating! Building was designed for 80 BTUH/ft 2 perimeter load Actual load in building use was 40 BTUH/ft 2 Parameter Proposed in design Actual observed load Area(Sq.ft) Sensible Load(Btuh) 16,000 8,000 Latent Load(Btuh) Minimum Outside Air(CFM) Quantity of ACB s 2 2

32 Design Cooling Loads 0 Beware of Overrating! Chilled beams selected for double actual required primary air to achieve overestimated load Primary air providing 65% of the total sensible cooling of the actual load 2 x beams at 115 CFM

33 Design Cooling Loads 0 Beware of Overrating! Therefore if load drops to 65% no waterside cooling will occur If load drops below 65% space will overcool unless reheat is used

34 Causes of Overrating Loads Assumptions on building materials performance Equipment loads that never eventuate Use of generic performance data Use of safety factors Lack of familiarity with load calculation software

35 Design Cooling Loads 0 Rules of Thumb Location Sensible Zone Load North East South West Interior 25A30 Btuh/Sq.ft 35A45 Btuh/Sq.ft 30A40 Btuh/Sq.ft 40A50 Btuh/Sq.ft 15A20 Btuh/Sq.ft Exclude loads:a Outside air load Plenum gain Fan motor gain Duct losses If loads exceed these values review closely

36 WATER SYSTEM DESIGN

37 CHW System Design Options Secondary loop Tap into district CHW loop Heat exchanger into return no GPM demand Can increase main plant efficiency Dedicated chiller & DX Dehumidification by DX AHU Significantly increased COP A 11+ Twin chillers One for AHU s 6 COP One for chilled beam circuit 11+ COP

38 Mixing Valve Supply temperature monitor Secondary chilled water supply to beams Primary chilled water supply S 58 F T 45 F SCHW Pump T Primary chilled water return Primary chilled water return 64 F Secondary chilled water return

39 Secondary Loop Supply temperature monitor Secondary chilled water supply to beams Primary chilled water supply 45 F S 58 F SCHW Pump T T 54 F Primary chilled water return Heat Exchanger 64 F Secondary chilled water return

40 Dedicated Chiller To chilled beam zones Bypass Valve T Chilled water pump 64 F Cooling Tower Dedicated Geothermal chiller Heat 11+ Pump COP 58 F Geothermal Loop

41 District Chilled Water Loops Tap into return pipe with heat exchanger and secondary loop No demand in district loop GPM Increases main chiller plant COP

42 Reverse Return Pipe Design S T

43 15 Minute Break

44 HEATING WITH ACTIVE CHILLED BEAMS

45 Advantages of 20Pipe Beams Versus 40Pipe Higher coil performance 4 pipe performance is compromised 75% Cooling (12 pipes) 25% Heating (4 pipes) Fewer or shorter beams Lower hot water temperatures 90 F for 2 pipe 130 F for 4 pipe

46 Boiler Efficiency 0 Lower Hot Water Temp Hot water typically 90A130 F Reduce boiler energy consumption by maximizing efficiency of a condensing boiler through very low return water temperatures Use of water to water heat pumps (KN boiler efficiency chart courtesy of Hydrotherm)

47 20Pipe Beams and Terminal Heating Chilled Water Supply Terminal Heating Coil Hot Water Supply 2APipe Active Chilled Beams Hot Water Return S T Chilled Water Return S

48 Heating Using 60Way Valves

49 60Way Valve

50 CONTROL CONSIDERATIONS

51 Airside Control Constant volume air Reduces cost Maintains constant control of humidity Guarantees minimum fresh air delivery Monitor room dew point Use small quantity of high quality sensors Do not use RH sensors Locate sensors in room not in ceiling Reduce primary moisture content to control room RH Avoid turning off or rescheduling SCHW temp

52 Waterside Control Variable water flow Pressure independent control Two position valves or modulating valves 6Away valves can be used on 4 pipe into 2 pipe chilled beams Reschedule or shut off SCHW only if primary moisture content cannot reduced

53 Waterside Control Sequence 76 Room Temperature ( F) SCHW ON Dead Zone SCHW OFF SCHW ON SCHW OFF Dead Zone 71 Time HW ON

54 Typical Start Up Control Sequence Dry out cycle before engaging SCHW pumps Setback primary air humidity ratio ONLY initiate pumps when room dew point is within design limits

55 Condensation and Dew Point Sensors Dew point sensor Condensation sensor Drip sensor

56 ACTIVE BEAM SYSTEM DESIGN COST CONTROL

57 First Cost Control Many projects still designed with far to many beams Caused by confusing selection software or low performance beams 4Apipe system designs are costly 2Apipe system with terminal heating or 6Away valves reduce cost Mechanical contractors unfamiliar with system Install a mockup to show contractors

58 PEX Piping Significantly Reduces Costs 70% reduced pipe material cost $0.60 v s $1.95 per linear foot Reduced labor, much faster installation No torches or soldering, no glue Longevity 50 year life expectancy No corrosion Dampens water rushing noise and water hammer noise Does not require insulation Plenum rated systems available With 25 year warranty

59 Active Chilled Beam Selection & Layout

60 Room Load Data

61 ACB Selection & Layout Tips Select beams for minimum possible primary air w.c. typical airside beam P Be aware of airside/waterside cooling ratio Maximize waterside cooling Chilled beams throw more air than VAV diffusers Be wary of air velocities Use ASHRAE standard 55 guidelines for thermal comfort

62 ACB Selection & Layout Tips Careful positioning near walls & columns Can interfere with beam if too close Chilled beams positioned closer than 6 centers may not cool correctly Minimum 2 x tile spacing rule of thumb Use manufacturers selection software Best software allows selection of the entire building

63 Tips to Minimize Primary Air Flow Be wary of overrating cooling loads Use low temperature primary air F is possible but beam must be internally insulated Locate beams along perimeter to increase output Use a higher on coil temperature when beams are positioned along perimeter This additional capacity is often overlooked Use booster fans

64 DOAS with Booster Fans DEDICATED OUTDOOR AIR UNIT Outdoor Air + A A A FAN BOOSTERS Return Air Return Air ACTIVE CHILLED BEAM ZONES ACTIVE CHILLED BEAM ZONES

65 LAYOUT OFFICE

66 Building With Exterior Cellular Offices Office 3 Office 4 Office 5 Office 6 50 BTUH/ft 2 30 BTUH/ft 2 30 BTUH/ft 2 Occupants: 1 Area: 144 ft 2 Ventilation: 15 CFM Cooling: 7200 BTUH Latent load: 288 BTUH Heating Load: 3000 BTUH Occupants: 1 Area: 144 ft 2 Ventilation: 15 CFM Cooling: 4320 BTUH Latent load: 288 BTUH Heating Load: 2100 BTUH Occupants: 1 Area: 144 ft 2 Ventilation: 15 CFM Cooling: 4320 BTUH Latent load: 288 BTUH Heating Load: 2100 BTUH 30 BTUH/ft 2 Occupants: 1 Area: 144 ft 2 Ventilation: 15 CFM Cooling: 4320 BTUH Latent load: 288 BTUH Heating Load: 2100 BTUH Office 7 30 BTUH/ft 2 Occupants: 1 Area: 144 ft 2 Ventilation: 15 CFM Cooling: 4320 BTUH Latent load: 288 BTUH Heating Load: 2100 BTUH Office 2 35 BTUH/ft 2 Occupants: 1 Area: 144 ft 2 Ventilation: 15 CFM Cooling: 5040 BTUH Latent load: 288 BTUH Heating Load: 2500 BTUH Office 1 35 BTUH/ft 2 Occupants: 1 Area: 144 ft 2 Ventilation: 15 CFM Cooling: 5040 BTUH Latent load: 288 BTUH Heating Load: 2500 BTUH 12 Office 8 20 BTUH/ft 2 Occupants: 15 Area: 1,512 ft 2 Ventilation: 170 CFM Cooling: 30,240 BTUH Latent load: 3024 BTUH Heating Load: 0 BTUH TOTAL AREA 2,520 FT 2 12

67 ACB Design Parameters Room Conditions: 75 F db/53% RH 70 F db winter Primary Air Conditions: 55 F db/51.6 wb(48.7 DP) Summer & Winter Chilled Water 57 F versus a 56.5 F room dewpoint(53% RH) Warm Water 110 F

68 Selection Software

69 ACB Layout ACBA3 PRIM. AIR Min. 15 CFM Max. 45 CFM Office 3 50 BTU sahr/ft 2 PRIM. AIR Min. 15 CFM Max. 25 CFM Office 4 ACBA4 ACBA5 ACBA6 ACBA7 30 BTU sa HR/FT 2 PRIM. AIR Min. 15 CFM Max. 25 CFM 30 BTU sa PRIM. AIR Min. 15 CFM Max. 25 CFM Office 5 HR/FT 2 Office 6 30 BTU sa HR/FT 2 Office 7 PRIM. AIR Min. 15 CFM Max. 25 CFM 30 BTU sa HR/FT 2 Min. O/A 275 CFM Max. O/A 485 CFM DOAS ACBA1 ACBA2 PRIM. AIR Min. 15 CFM Max. 35 CFM Office 2 35 BTU sahr/ft 2 PRIM. AIR Min. 15 CFM Max. 35 CFM Office 1 35 BTU sahr/ft 2 12 ACBA8b ACBA8a PRIM. AIR 270 CFM ACBA8d ACBA8c ACBA8f ACBA8e VAV Min. 105 CFM Max. 215 CFM Min. 170 CFM Max. 270 CFM Internal Offices 20 BTU sahr/ft 2 VAV S/A 12 TOTAL AREA 2,520 FT 2 R/A

70 Beam Layout Notes 1Away beam in the perimeter offices Captures solar load, increases beam output Higher onacoil temperature Free s up ceiling space for lighting Works well for heating Interior office 2Away throw beams Check velocity between colliding airstreams Minimum of 1 beam per 300 ft 2

71 10Way Perimeter Beam Increased on coil temp Increased cooling output Less primary air required

72 10Way Beams at Perimeter CFD Cooling

73 10Way Beams at Perimeter CFD Heating

74 10Way Beams at Perimeter CFD Heating

75 VAV Reheat Design Parameters Room Conditions: 75 F db/50% RH 70 F db winter Primary Air Conditions: 55 F db/55 wb Summer & Winter Chilled Water 45 F Hot Water 150 F

76 VAV Layout MAX 332 CFM MIN 63 CFM MAX 199 CFM MIN 50 CFM MAX 199 CFM MIN 50 CFM MAX 199 CFM Office 3 30 BTU sa 30 BTU sa Office 4 HR/FT Office 5 Office 6 50 BTU sahr/ft 2 2 HR/FT 2 MIN 50 CFM 30 BTU sa HR/FT 2 MAX 199 CFM Office 7 MIN 50 CFM 30 BTU sa HR/FT 2 O/A 275 CFM E/A 275 CFM VAV 4 VAV 5 VAV 6 VAV 7 S/A AHU MAX 232 CFM MIN 63 CFM VAV 2 Min. 693 CFM Max CFM Office 2 35 BTU sahr/ft 2 VAV IO MAX 1,394 CFM MAX 232 CFM MIN 63 CFM Office 1 35 BTU sahr/ft 2 VAV 1 12 MIN 304 CFM Internal Offices 20 BTU sahr/ft 2 R/A 12 TOTAL AREA 2,520 FT 2

77 Summary Comparison VAV Total Air System Size 2986 CFM Max Turndown 693 CFM Max. Airflow 1.18 CFM/FT 2 Min. Average Airflow 0.27 CFM CFM/FT 2 60% Load 0.71 CFM FT 2 ACB+DOAS Total Air System Size 565 CFM Max Turndown 275 CFM Max. Airflow 0.22 CFM/FT 2 Min. Average Airflow 0.11 CFM CFM/FT 2 60% Load 0.11 CFM FT 2 84% airflow reduction at 60% load!

78 CFD Modeling Critical Applications

79 QUESTIONS?

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

HVAC Simplified Approach Option

HVAC Simplified Approach Option HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is

More information

Active & Passive Beams

Active & Passive Beams Active & Passive Beams Active & Passive Beams Introduction Beam systems are an alternative to traditional all-air conditioning systems. Beams use water to move energy through a building and service the

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

Preliminary Final Proposal

Preliminary Final Proposal 1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air

More information

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce

More information

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Moisture Control. It s The Dew Point. Stupid! Its not the humidity. Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR

More information

How To Design A Building In New Delhi

How To Design A Building In New Delhi ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption

More information

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1 Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager

More information

Tom Brooke, PE, MBA, CEM tabrooke@embarqmail.com

Tom Brooke, PE, MBA, CEM tabrooke@embarqmail.com Tom Brooke, PE, MBA, CEM tabrooke@embarqmail.com Framework, perspective or example in a particular discipline at a given time These four new models are: New and additional, or Updated Today's Paradigm

More information

Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland

Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC

More information

Mechanical Systems Proposal revised

Mechanical Systems Proposal revised Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option

More information

Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment

Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment AT-01-7-3 Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment Kurt M. Shank Student Member ASHRAE Stanley A.

More information

Dedicated Outdoor Air Systems (D.O.A.S.)

Dedicated Outdoor Air Systems (D.O.A.S.) Commercial and Industrial Climate Control Systems Dedicated Outdoor Air Systems (D.O.A.S.) AMDOAS-1 What is it? Why use one? What are my options? Selection considerations Design steps What is it? A separate

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

STULZ Water-Side Economizer Solutions

STULZ Water-Side Economizer Solutions STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014

More information

Topics for Today. Order of Magnitude Mechanical Estimating. Order of Magnitude Estimate Goal. Project Delivery Methods. Questions for Client

Topics for Today. Order of Magnitude Mechanical Estimating. Order of Magnitude Estimate Goal. Project Delivery Methods. Questions for Client Order of Magnitude Mechanical Estimating Justin Apprill, P.E. Topics for Today Estimate Goals A Concept for Accurate Conceptual Estimating HVAC Systems Common System Types and Rules of Thumb Pricing Example

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc. LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air Trevor Wende Vice President, Marketing Advantix Systems, Inc. 0 Humidity: The Hidden Cost Driver Conventional A/C process Start

More information

Enclosed Football Stadium Design History and Lessons Learned

Enclosed Football Stadium Design History and Lessons Learned Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP btowell@cxegroup.com CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention

More information

SAM HOUSTON STATE UNIVERSITY

SAM HOUSTON STATE UNIVERSITY PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0. Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Integrated Solar Radiant Systems

Integrated Solar Radiant Systems Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

Design Options for HVAC Distribution Systems

Design Options for HVAC Distribution Systems Design Options for HVAC Distribution Systems Course No: M06-017 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877)

More information

HVAC Characteristics. Test Space HVAC Characteristics

HVAC Characteristics. Test Space HVAC Characteristics HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations,

More information

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

Flexibility, Efficiency In San Antonio Arena

Flexibility, Efficiency In San Antonio Arena 2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not

More information

Radiant Panels and Chilled Sails. www.price-hvac.com

Radiant Panels and Chilled Sails. www.price-hvac.com Radiant Panels and Chilled Sails www.price-hvac.com Radiant Panels and Chilled Sails Introduction Radiant panels use thermal radiation to modify surface temperatures in order to provide sensible cooling

More information

Hospital Application Guide. Cost-effective climate control for hospitals

Hospital Application Guide. Cost-effective climate control for hospitals Hospital Application Guide Cost-effective climate control for hospitals Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing

More information

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems

More information

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com

More information

Why Do I Need Precision Air Conditioning?

Why Do I Need Precision Air Conditioning? Why Do I Need Precision Air Conditioning? Executive Summary Today's technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

HVAC Basic Science - System Capacity

HVAC Basic Science - System Capacity HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414

More information

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM Page 1 UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM Each of the 38 points of requested information is discussed, and references to the supporting manual are given to substantiate the requirement.

More information

EnergyPro Building Energy Analysis. Assisted Living Building

EnergyPro Building Energy Analysis. Assisted Living Building EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the

More information

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects Makeup Air For Exhaust Systems In Tight Houses Tony Jellen Engineering Projects PA Housing & Land Development Conference February 23, 2012 Effects of Kitchen Ventilation on Residential Dwellings Anthony

More information

ASHRAE Student System Selection Competition New Office Building - Nashville, Tennessee Spring 2009

ASHRAE Student System Selection Competition New Office Building - Nashville, Tennessee Spring 2009 ASHRAE Student System Selection Competition New Office Building - Nashville, Tennessee Spring 2009 Kansas State University Department of Architectural Engineering and Construction Science 240 Seaton Hall

More information

Dehumidification Design

Dehumidification Design Dehumidification Design Using Data-Center Heat Utilizing free heat from a server room was the concept behind an air-handling system in a college-campus building Considerable energy savings are possible

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Design Options For HVAC Distribution System

Design Options For HVAC Distribution System PDHonline Course M147 (4 PDH) Design Options For HVAC Distribution System Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088

More information

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building. MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating

More information

TODAY S PARADIGM FOR AIR TO AIR HEAT RECOVERY

TODAY S PARADIGM FOR AIR TO AIR HEAT RECOVERY Tom Brooke, April 11, 2012 TODAY S PARADIGM FOR AIR TO AIR HEAT RECOVERY INTRODUCTION Technology advances! Just as commercial and industrial HVAC controls, chillers, and unitary equipment are constantly

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent

More information

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010 White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence

More information

Principals of Condensing Boiler System Design

Principals of Condensing Boiler System Design Principals of Condensing Boiler System Design Dennis Jones, P.E. Member ASHRAE ABSTRACT Condensing boilers can provide significant energy savings due to operating efficiencies as high as 98% as compared

More information

Mechanical Insulation. Hospitals and Schools

Mechanical Insulation. Hospitals and Schools Study on Mechanical Insulation in Hospitals and Schools March 1, 2011 Study Mechanical Insulation in Hospitals and Schools G. Christopher P. Crall, P.E. Ronald L. King Executive Summary Mechanical insulation

More information

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of

More information

ASHRAE Rocky Mountain Chapter. RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc.

ASHRAE Rocky Mountain Chapter. RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc. ASHRAE Rocky Mountain Chapter Evaporative Cooling RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc. April 19, 2013 1 Fundamentals Dry Bulb Temperature Wet Bulb Temperature

More information

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools Heat Recovery Dehumidification (HRD) system Designed for municipal swimming pools A dehumidification and ventilation system with dynamic heat pump heat recovery to swimming pool water and air ENVIRONMENTAL

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic Introduction to HVAC Systems One of the Systems Series February 2012 TRG-TRC018-EN Introduction to HVAC Systems One of the Systems Series A publication of Trane Preface Introduction

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

MECHANICAL SYSTEMS DESIGN. Team 2010 2

MECHANICAL SYSTEMS DESIGN. Team 2010 2 MECHANICAL SYSTEMS DESIGN Andrew Bridges, Ben Hollon, Sean Kolich, Weston Arbogast, Kaitlin Page Andrew Bridges, Ben Hollon, Sean Kolich, Weston Arbogast, Kaitlin Page Team 2010 2 PRESENTATION OVERVIEW

More information

VAV Laboratory Room Airflow The Lowdown on Turndown

VAV Laboratory Room Airflow The Lowdown on Turndown Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally

More information

Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013

Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013 The Fundamentals of HVAC: What Shapes the Storage Environment Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013 Introduction Presenter Jeremy Linden, Preservation

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL Brittany Hanam, MASc, EIT RDH Building Engineering Ltd. Vancouver, BC John Straube, PhD, P.Eng. Building Engineering Group, Civil

More information

Role of Economizers in Dedicated Outdoor Air Systems

Role of Economizers in Dedicated Outdoor Air Systems Introduction: Role of Economizers in Dedicated Outdoor Air Systems A question that frequently arises when a dedicated outdoor air system (DOAS) (Mumma, 2001) is discussed, particularly when the parallel

More information

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA.

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA. 1. There is verbiage in the hazardous material report referring to a state licensed abatement contractor. Within the recommendations part of the report (page 64 of 111 of the specification pdf) is the

More information

Fan Applications & System Guide

Fan Applications & System Guide Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation

More information

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment

More information

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with

More information

Dedicated Outdoor Air-Dual Wheel System Control Requirements

Dedicated Outdoor Air-Dual Wheel System Control Requirements 4428 Dedicated Outdoor Air-Dual Wheel System Control Requirements Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE ABSTRACT The central thrust of this paper is to develop a clear understanding of the performance

More information

Energy Efficient HVAC-system and Building Design

Energy Efficient HVAC-system and Building Design Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: maija.virta@halton.com SUMMARY This paper

More information

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants HIGH PERFORMANCE CHILLED WATER SYSTEMS EarthWise HVAC Simon Ho e: Simon.Ho@irco.com 2012 EarthWise HVAC High Performance CHW Plants Low Flow Low Temperature Systems Variable Flow Systems Variable CHW Variable

More information

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons

HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined

More information

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water 2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation

More information

RADIANT COOLING SYSTEMS PRINCIPLES OF RADIANT COOLING SYSTEMS INSTALLATION, DESIGN, CONTROLS, CAPACITIES

RADIANT COOLING SYSTEMS PRINCIPLES OF RADIANT COOLING SYSTEMS INSTALLATION, DESIGN, CONTROLS, CAPACITIES RADIANT COOLING SYSTEMS PRINCIPLES OF RADIANT COOLING SYSTEMS INSTALLATION, DESIGN, CONTROLS, CAPACITIES www.rehau.com Construction Automotive Industry INTRODUCTIONS PRESENTER Lance MacNevin - Manager,

More information

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015 Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information